FREETOX N2XOH 0,6/1 kV FB Single- Contact

core; UV Resist. Local Sales


ventas.peru@nexans.com

Special application in places with poor ventilation and places public attendance high.

DESCRIPTION

Application:

In low voltage power distribution networks. Special application in places with poor
ventilation, direct application in places with public attendance high. It can be installed
in ducts in dry and wet places.

Construction:

1. Conductor: Flexible soft copper, class 5.

2. Insulation: Cross linked polyethylene XLPE. STANDARDS


3. Outer sheath: HFFR- UV halogen free thermoplastic compound. International IEC 60228;
IEC 60332-1-2;
IEC 60332-3-24 Cat.C;
Main characteristics:
IEC 60502-1; IEC 60684-2;
The cable has excellent electric properties. The cross-linked polyethylene insulation IEC 60754-1; IEC 60754-2;
allows a higher power capacity current under any operation conditions, lower dielectric IEC 61034-2
losses, high insulation resistance. The outer sheath have the following characteristics:
National ICEA S-95-658; NTP-
Fire retardant, low emission dense smoke and halogen free. Adequate resistance to
IEC 60228; NTP-IEC 60502-1;
oils. Resistance to sunlight.
UL 2556
Cross section:

From 2,5 mm2 up to 500 mm2.

Marking:

INDECO S.A FREETOX N2XOH 0,6/1 kV - Section - FB - Year - Sequential length.

Packing:

Non returnable wooden reels.

Colour:

Insulation: Natural.

Outer sheath: Black-UV, Green-UV, Red-UV or White-UV.

National standards

NTP-IEC 60228: Conductors of insulated cables.

Halogen free Conductor flexibility Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant
IEC 60754-1 Class 5 IEC 60228 ICEA S-95-658 Low toxicity to IEC Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 IEC 60332-3-24
60684-2 Corrosivity IEC Cat.C
60754-2

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 2.3 Generated 11/24/21 www.nexans.pe Page 1 / 6
FREETOX N2XOH 0,6/1 kV FB Single- Contact
core; UV Resist. Local Sales
ventas.peru@nexans.com

NTP-IEC 60502-1: Power cables with extruded insulation and their accessories for
rated voltages from 1 kV and 3 kV.

International standards

IEC 60228: Conductors of insulated cables.

IEC 60502-1: Power cables with extruded insulation and their accessories for rated
voltages from 1 kV and 3 kV.

IEC 60332-1-2: Test for vertical flame propagation for a single insulated wire or cable -
Procedure for 1 kW pre-mixed flame.

UL 2556: Wire and Cable Test Methods. Section 9.3: FT1 (Vertical-Specimen) Flame
Test.

IEC 60332-3-24: Test for vertical flame spread of vertically-mounted bunched wires or
cables - Category C.

IEC 60684-2: Flexible insulating sleeving - Part 2: Methods of test.

IEC 60754-1: Test on gases evolved during combustion of materials from cables. Part
1: Determination of the halogen acid gas content.

IEC 60754-2: Test on gases evolved during combustion of materials from cables. Part
2: Determination of acidity (by pH measurement) and conductivity.

IEC 61034-2: Measurement of smoke density of cables burning under defined


conditions.

ICEA S-95-658: Power cables rated 2000 volts or less for the distribution of electrical
energy. Section 6.4.2: Oil: Oil Immersion Test.

UL 2556:Wire and Cable Test Methods. Section 4.2.8.5: Carbon-Arc and Xenon-Arc
Tests- Sunlight resistance.

CHARACTERISTICS
Construction characteristics
Conductor material Soft copper
Insulating material XLPE
Outer sheath Halogen free thermoplastic compound - UV
Resist.
Halogen free IEC 60754-1
Conductor flexibility Class 5 IEC 60228

Halogen free Conductor flexibility Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant
IEC 60754-1 Class 5 IEC 60228 ICEA S-95-658 Low toxicity to IEC Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 IEC 60332-3-24
60684-2 Corrosivity IEC Cat.C
60754-2

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 2.3 Generated 11/24/21 www.nexans.pe Page 2 / 6
FREETOX N2XOH 0,6/1 kV FB Single- Contact
core; UV Resist. Local Sales
ventas.peru@nexans.com

Electrical characteristics
Dielectric strength 3.5 kV
Time of application Dielectric strength core to screen AC 5 min.
Usage characteristics
Oil resistance ICEA S-95-658
Gases toxicity Low toxicity to IEC 60684-2
Gases corrosivity Low pH Corrosivity IEC 60754-2
Smoke density Low IEC 61034-2
Flame retardant IEC 60332-1-2; FT1
Fire retardant IEC 60332-3-24 Cat.C
U.V resistance UL 2556 - Sunlight Resistance
Maximum operating temperature 90 °C
Overload maximum core temperature 130 °C
Short-circuit max. conductor temperature 250 °C

DIMENSIONAL DATA
Cross Conductor Min. insulation Min. outer sheath Diam. over Approx.
section diam. thick. thick. sheath weight
[mm²] [mm] [mm] [mm] [mm] [kg/km]
2.5 1.9 0.7 0.9 5.3 47
4 2.4 0.7 0.9 5.8 63
6 3.0 0.7 0.9 6.4 83
10 4.1 0.7 0.9 7.5 129
16 5.3 0.7 0.9 8.6 187
25 6.6 0.9 0.9 10.4 280
35 7.8 0.9 0.9 11.6 374
50 9.3 1.0 0.9 13.3 522
70 11.3 1.1 1.0 15.7 723
95 12.8 1.1 1.0 17.2 922
120 14.5 1.2 1.1 19.3 1182
150 16.2 1.4 1.2 21.6 1429
185 18.0 1.6 1.2 23.9 1739
240 20.7 1.7 1.2 26.8 2272
300 23.2 1.8 1.3 29.7 2824
400 26.5 2.0 1.5 33.8 3700
500 30.3 2.2 1.6 38.3 4793

Halogen free Conductor flexibility Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant
IEC 60754-1 Class 5 IEC 60228 ICEA S-95-658 Low toxicity to IEC Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 IEC 60332-3-24
60684-2 Corrosivity IEC Cat.C
60754-2

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 2.3 Generated 11/24/21 www.nexans.pe Page 3 / 6
FREETOX N2XOH 0,6/1 kV FB Single- Contact
core; UV Resist. Local Sales
ventas.peru@nexans.com

ELECTRICAL DATA
Cross Max. DC Resist. Perm. Current Perm. current rating in air current rating in Nominal
section Cond. 20°C buried 20°C 30°C - flat formation air 30°C - trefoil capacitance
[mm²] [Ohm/km] [A] [A] [A] [pF/m]
2.5 7.98 30 30 29 239.0
4 4.95 39 42 40 286.0
6 3.3 49 55 53 343.0
10 1.91 65 77 74 445.0
16 1.21 84 105 101 593.0
25 0.78 107 141 135 549.0
35 0.554 129 176 169 637.0
50 0.386 153 216 207 682.0
70 0.272 188 279 268 750.0
95 0.206 226 342 328 840.0
120 0.161 257 400 383 873.0
150 0.129 287 464 444 843.0
185 0.106 324 533 510 803.0
240 0.0801 375 634 607 866.0
300 0.0641 419 736 703 916.0
400 0.0486 491 868 823 944.0
500 0.0384 556 998 946 983.0

PRODUCT LIST
Nexans Ref. Country Ref. Name Sheath colour Approximate weight
[kg/km]
P00029364-4 - FREETOX N2XOH 0,6/1 kV 35 mm2 FB Black - UV 374
P00005925-7 - FREETOX N2XOH 0,6/1 kV 50 mm2 FB Black - UV 522
P00005926-5 - FREETOX N2XOH 0,6/1 kV 70 mm2 FB Black - UV 723
P00008486-4 - FREETOX N2XOH 0,6/1 kV 120 mm2 FB Green - UV 1182
P00005929-8 - FREETOX N2XOH 0,6/1 kV 150 mm2 FB Black - UV 1429
P00018617-8 - FREETOX N2XOH 0,6/1 kV 185 mm2 FB Black - UV 1739
P00008265-6 - FREETOX N2XOH 0,6/1 kV 240 mm2 FB Green - UV 2272
P00014785-9 - FREETOX N2XOH 0,6/1 kV 300 mm2 FB Black - UV 2824
P00004556-6 - FREETOX N2XOH 0,6/1 kV 400 mm2 FB Black - UV 3700
P00014320-8 - FREETOX N2XOH 0,6/1 kV 10 mm2 FB Black - UV 129
= Make to order, = In stock,

Halogen free Conductor flexibility Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant
IEC 60754-1 Class 5 IEC 60228 ICEA S-95-658 Low toxicity to IEC Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 IEC 60332-3-24
60684-2 Corrosivity IEC Cat.C
60754-2

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 2.3 Generated 11/24/21 www.nexans.pe Page 4 / 6
FREETOX N2XOH 0,6/1 kV FB Single- Contact
core; UV Resist. Local Sales
ventas.peru@nexans.com

Nexans Ref. Country Ref. Name Sheath colour Approximate weight


[kg/km]
P00021346-6 - FREETOX N2XOH 0,6/1 kV 16 mm2 FB Black - UV 187
P00029503-3 - FREETOX N2XOH 0,6/1 kV 25 mm2 FB Black - UV 280
P00030616-1 - FREETOX N2XOH 0,6/1 kV 500 mm2 FB Black - UV 4793
P00018613-6 - FREETOX N2XOH 0,6/1 kV 95 mm2 FB Black - UV 922
P00031912-0 - FREETOX N2XOH 0,6/1 kV 16 mm2 FB Green - UV 187
P00031911-0 - FREETOX N2XOH 0,6/1 kV 10 mm2 FB Green - UV 129
P00031910-0 - FREETOX N2XOH 0,6/1 kV 6 mm2 FB Green - UV 83
P00021359-4 - FREETOX N2XOH 0,6/1 kV 2,5 mm2 FB Black - UV 47
P00005563-6 - FREETOX N2XOH 0,6/1 kV 4 mm2 FB Black - UV 63
P00006463-6 - FREETOX N2XOH 0,6/1 kV 6 mm2 FB Black - UV 83
P00002265-14 - FREETOX N2XOH 0,6/1 kV 120 mm2 FB Black - UV 1182
P00015037-9 - FREETOX N2XOH 0,6/1 kV 240 mm2 FB Black - UV 2272
P00034437-0 - FREETOX N2XOH 0,6/1 kV 300 mm2 FB White - UV 2824
P00034438-0 - FREETOX N2XOH 0,6/1 kV 300 mm2 FB Red - UV 2824
= Make to order, = In stock,

BENDING RADIUS WHEN INSTALLED IN L.V.

R=Dxf
R: Bending radius when installed (mm)

D: Diameter over sheath or over insulation (when it has not sheath) (mm)

f: Multiplicative factor; given the following table:

BENDING RADIUS FACTOR LV

Halogen free Conductor flexibility Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant
IEC 60754-1 Class 5 IEC 60228 ICEA S-95-658 Low toxicity to IEC Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 IEC 60332-3-24
60684-2 Corrosivity IEC Cat.C
60754-2

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 2.3 Generated 11/24/21 www.nexans.pe Page 5 / 6
FREETOX N2XOH 0,6/1 kV FB Single- Contact
core; UV Resist. Local Sales
ventas.peru@nexans.com

CALCULATION OF CURRENT CONDITION: COPPER CONDUCTOR SINGLE-CORE


L.V.; 90°C

CURRENT CAPACITY VALUES AND CURRENT CALCULATION CONDITIONS BASED ON IEC 60364-5-52:2009 :

TABLE B.52.5 (METHOD D2: Buried in tringular formation).


TABLE B.52.12 (METHOD F: Air in flat formation and in contact).
TABLE B.52.12 (METHOD F: Air in tringular formation).

Maximum conductor temperature : 90°C.


Ambient air temperature : 30°C.
Ground temperature : 20°C.
Depth of laying up to: 0,8 m.
Thermal resistivity of soil : 2,5 K.m/W.

Halogen free Conductor flexibility Oil resistance Gases toxicity Gases corrosivity Smoke density Flame retardant Fire retardant
IEC 60754-1 Class 5 IEC 60228 ICEA S-95-658 Low toxicity to IEC Low pH Low IEC 61034-2 IEC 60332-1-2; FT1 IEC 60332-3-24
60684-2 Corrosivity IEC Cat.C
60754-2

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 2.3 Generated 11/24/21 www.nexans.pe Page 6 / 6

You might also like