Liebert AHU Thermal Wall V1T Application

Monitoring Manual

Product Documentation
English, code: 10012918 rev. 2021.11.26
INDEX

1. SCOPE 4
2. MONITORING PROTOCOLS 4
3. CONNECTIONS 4
ETHERNET CONNECTION ON ICOM3 CONTROL 4

4. MODBUS TCP/IP 5
INPUT STATUS 5
HOLDING AND INPUT REGISTERS 7

5. BACNET 11
BACNET IMPLEMENTATION 11
BINARY VALUES 12
ANALOG VALUES 14
MULTI STATE VALUES 15
INTEGER VALUES 16

6. FAQS 18
GENERAL FAQS 18
MODBUS RELATED FAQS 18
BACNET RELATED FAQS 18

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 3/18


1. Scope
This document provides the monitoring data point lists for Vertiv AHU Thermal Wall Units running the V1T SW
application. The Vertiv Units that are covered by this monitoring manual are:
 TW200 - TW400 Hyperscale Configuration
 TW240 Retail Configuration

2. Monitoring Protocols
The Modbus protocols is provided over IP through a dedicated Ethernet port, that is physically disconnected from the
rest of the other controller interfaces and communicating via serial RS485 protocol with the micro processor.

 Default IP Adress of the Monitoring Port: 192.168.254.200

The web site is available at that address. At the first access the user is guided by a “First Boot Access” wizard that
forces the creation of the web user accounts.
The following standard monitoring protocols are made available:

 Modbus TCP/IP
- Port 502
- default address: 1

 BACnet IP v1.14
- UDP Port 47808
- default address: 1
- default device name: NHES1

The last column on every datapoints table reports the SW version from which the specific datapoint is made available.

3. Connections
ETHERNET CONNECTION ON ICOM3 CONTROL

Monitoring Port

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 4/18


4. Modbus TCP/IP
INPUT STATUS

The following Boolean read-only datapoints are available on:


- Input Status Command 02

IS Description Type Delay Unit Config. SW Version


1 Supply Temp. Probe Fail (Bottom-Left) Alarm 30 sec All 1.0.0
2 Supply Temp. Probe Fail (Bottom-Middle) Alarm 30 sec All 1.0.0
3 Supply Temp. Probe Fail (Bottom-Right) Alarm 30 sec All 1.0.0
4 Supply Temp. Probe Fail (Top-Left) Alarm 30 sec All 1.0.0
5 Supply Temp. Probe Fail (Top-Middle) Alarm 30 sec TW200/400 1.0.0
6 Supply Temp. Probe Fail (Top-Right) Alarm 30 sec All 1.0.0
7 DP Probe Fail (Right) Alarm 30 sec All 1.0.0
8 DP Probe Fail (Left) Alarm 30 sec All 1.0.0
9 T/H Sensor 1 Communication Error (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
10 T/H Sensor 2 Communication Error (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
11 T/H Sensor 1 Communication Error (Right White Space) Alarm 30 sec TW200/400 1.0.0
12 T/H Sensor 2 Communication Error (Right White Space) Alarm 30 sec TW200/400 1.0.0
13 T/H Sensor 1 Communication Error (Left White Space) Alarm 30 sec TW200/400 1.0.0
14 T/H Sensor 2 Communication Error (Left White Space) Alarm 30 sec TW200/400 1.0.0
15 T/H Sensor 1 Failure (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
16 T/H Sensor 2 Failure (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
17 T/H Sensor 1 Failure (Right White Space) Alarm 30 sec TW200/400 1.0.0
18 T/H Sensor 2 Failure (Right White Space) Alarm 30 sec TW200/400 1.0.0
19 T/H Sensor 1 Failure (Left White Space) Alarm 30 sec TW200/400 1.0.0
20 T/H Sensor 2 Failure (Left White Space) Alarm 30 sec TW200/400 1.0.0
21 Fans Failure Alarm 1 min All 1.0.0
22 Fans Communication Failure Alarm 1 min All 1.0.0
23 CW Valve Motor Error (Bottom-Left) Alarm 1 min All 1.0.0
24 CW Valve Motor Error (Bottom-Middle) Alarm 1 min All 1.0.0
25 CW Valve Motor Error (Bottom-Right) Alarm 1 min All 1.0.0
26 CW Valve Motor Error (Top-Left) Alarm 1 min All 1.0.0
27 CW Valve Motor Error (Top-Middle) Alarm 1 min TW200/400 1.0.0
28 CW Valve Motor Error (Top-Right) Alarm 1 min All 1.0.0
29 CW Valves Communication Failure Alarm 1 min All 1.0.0
30 CW Valve Feedback Fail (Bottom-Left) Warning 3 min All 1.0.0
31 CW Valve Feedback Fail (Bottom-Middle) Warning 3 min All 1.0.0
32 CW Valve Feedback Fail (Bottom-Right) Warning 3 min All 1.0.0
33 CW Valve Feedback Fail (Top-Left) Warning 3 min All 1.0.0
34 CW Valve Feedback Fail (Top-Middle) Warning 3 min TW200/400 1.0.0
35 CW Valve Feedback Fail (Top-Right) Warning 3 min All 1.0.0
36 High Supply Temperature (Bottom-Left) Alarm 1 min All 1.0.0
37 High Supply Temperature (Bottom-Middle) Alarm 1 min All 1.0.0
38 High Supply Temperature (Bottom-Right) Alarm 1 min All 1.0.0
39 High Supply Temperature (Top-Left) Alarm 1 min All 1.0.0
40 High Supply Temperature (Top-Middle) Alarm 1 min TW200/400 1.0.0
41 High Supply Temperature (Top-Right) Alarm 1 min All 1.0.0
42 Fans Working Hours Limit (Bottom Left) Warning 0 sec TW200/400 1.0.0
43 Fans Working Hours Limit (Top Left) Warning 0 sec TW200/400 1.0.0
44 Fans Working Hours Limit (Bottom Right) Warning 0 sec TW200/400 1.0.0

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 5/18


IS Description Type Delay Unit Config. SW Version
45 Fans Working Hours Limit (Top Right) Warning 0 sec TW200/400 1.0.0
46 CW Valve Working Hours Limit (Bottom-Left) Warning 0 sec All 1.0.0
47 CW Valve Working Hours Limit (Bottom-Middle) Warning 0 sec All 1.0.0
48 CW Valve Working Hours Limit (Bottom-Right) Warning 0 sec All 1.0.0
49 CW Valve Working Hours Limit (Top-Left) Warning 0 sec All 1.0.0
50 CW Valve Working Hours Limit (Top-Middle) Warning 0 sec TW200/400 1.0.0
51 CW Valve Working Hours Limit (Top-Right) Warning 0 sec All 1.0.0
52 Missing Unit Configuration Files Alarm 0 sec All 1.0.0
53 Fans DP Control Enable (Left) Warning 0 sec TW200/400 1.0.0
54 Fans DP Control Enable (Right) Warning 0 sec TW200/400 1.0.0
55 Fire Alarm Alarm 2 sec All 1.0.0
56 ATS 1 Communication Error Warning 30 sec All 1.1.1
57 ATS 2 Communication Error Warning 30 sec All 1.1.1
58 ATS 3 Communication Error Warning 30 sec All 1.1.1
59 ATS 4 Communication Error Warning 30 sec All 1.1.1
60 T/H Sensor 1 Failure (Cold Aisle) Alarm 30 sec TW240 1.1.1
61 T/H Sensor 2 Failure (Cold Aisle) Alarm 30 sec TW240 1.1.1
62 Return Temp. Probe Fail (Bottom-Left) Alarm 30 sec TW240 1.1.1
63 Return Temp. Probe Fail (Bottom-Middle) Alarm 30 sec TW240 1.1.1
64 Return Temp. Probe Fail (Bottom-Right) Alarm 30 sec TW240 1.1.1
65 Return Temp. Probe Fail (Top-Left) Alarm 30 sec TW240 1.1.1
66 Return Temp. Probe Fail (Top-Right) Alarm 30 sec TW240 1.1.1
67 T/H Sensor 1 Communication Error (Cold Aisle) Alarm 30 sec TW240 1.1.1
68 T/H Sensor 2 Communication Error (Cold Aisle) Alarm 30 sec TW240 1.1.1
69 Fans DP Control Enable (Upper) Warning 0 sec TW240 1.1.1
70 Fans Working Hours Limit (Upper) Warning 0 sec TW240 1.1.1
71 Fans Rotation Error Alarm 0 sec All 1.1.1
72 Expansion I/O Board Communication Error Alarm 30 sec All 1.1.1
73 Network Communication Failure Warning 15 sec All 2.0.0
74 Master Unit Changed Messsage 5 sec TW240 2.0.0
75 Master Unit Not Available Warning 1 min TW240 2.0.0
76 System DT Not Valid Alarm 10 sec TW240 2.0.0
77 System DP Not Valid Alarm 10 sec TW240 2.0.0
78 ATS 5 Communication Error Warning 30 sec All 2.0.1
79 ATS 6 Communication Error Warning 30 sec All 2.0.1
80 Multiple High Supply Temperatures Alarm 0 sec TW200/400 2.0.1
81 Low Fans Speed Protection Enabled Warning 0 sec TW200/400 2.0.1
90 Local On Messsage 0 sec All 1.0.0
91 BMS On Messsage 0 sec All 1.0.0
92 Local Off Messsage 0 sec All 1.0.0
93 BMS Off Messsage 0 sec All 1.0.0
94 Remote Off Messsage 0 sec All 1.0.0
95 Service Control Mode Enabled Messsage 0 sec All 1.0.0
96 Maintenance Mode Enabled Messsage 0 sec All 1.0.0

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 6/18


HOLDING AND INPUT REGISTERS
The following Analog and Integer datapoints are available on:
- Holding Registers Command 03
- Input Registers Command 04
Note: Holding Registers marked as “R” in Access column cannot be written.

HR/IR Description Range Scale Access Unit Config. Version


0001 Remote Differential Temperature 0.0 – 50.0 °C; 1/10 °C x10 R TW200/400 1.0.0
(Right Fans Speed Control Input)
0002 Remote Differential Pressure 0.0 – 500.0 Pa; 1/10 Pa x10 R TW200/400 1.0.0
(Right Fans Speed Control Input)
0003 Remote Differential Temperature 0.0 – 50.0 °C; 1/10°C x10 R TW200/400 1.0.0
(Left Fans Speed Control Input)
0004 Remote Differential Pressure 0.0 – 500.0 Pa; 1/10 Pa x10 R TW200/400 1.0.0
(Left Fans Speed Control Input)
0005 Bottom-Left Coil Supply Temperature 0.0 – 50.0 °C; 1/10 °C x10 R All 1.0.0
0006 Bottom-Middle Coil Supply 0.0 – 50.0 °C; 1/10 °C x10 R All 1.0.0
Temperature
0007 Bottom-Right Coil Supply 0.0 – 50.0 °C; 1/10 °C x10 R All 1.0.0
Temperature
0008 Top-Left Coil Supply Temperature 0.1 0.0 – 50.0 °C; 1/10 °C x10 R All 1.0.0
0009 Top-Middle Coil Supply Temperature 0.0 – 50.0 °C; 1/10 °C x10 R TW200/400 1.0.0
0010 Top-Right Coil Supply Temperature 0.0 – 50.0 °C; 1/10 °C x10 R All 1.0.0
0011 Hot Aisle Temperature 1 -40.0 - +80.0 °C; 1/10 °C x10 R All 1.0.0
0012 Hot Aisle Temperature 2 -40.0 - +80.0 °C; 1/10 °C x10 R All 1.0.0
0013 Right White Space Temperature 1 -40.0 - +80.0 °C; 1/10 °C x10 R TW200/400 1.0.0
0014 Right White Space Temperature 2 -40.0 - +80.0 °C; 1/10 °C x10 R TW200/400 1.0.0
0015 Left White Space Temperature 1 -40.0 - +80.0 °C; 1/10 °C x10 R TW200/400 1.0.0
0016 Left White Space Temperature 2 -40.0 - +80.0 °C; 1/10 °C x10 R TW200/400 1.0.0
0017 Right Differential Pressure 0.0 – 500.0 Pa; 1/10 Pa x10 R TW200/400 1.0.0
0018 Left Differential Pressure 0.0 – 500.0 Pa; 1/10 Pa x10 R TW200/400 1.0.0
Remote Differential Temperature x10 R TW240 1.1.0
0019 0.0 – 50.0 °C; 1/10 °C
(Upper Fans Speed Control Input)
Remote Differential Pressure x10 R TW240 1.1.0
0020 0.0 – 500.0 Pa; 1/10 Pa
(Upper Fans Speed Control Input)
0021 Bottom-Left Coil Return Temperature 0.0 – 50.0 °C; 1/10 °C x10 R TW240 1.1.0
Bottom-Middle Coil Return x10 R TW240 1.1.0
0022 0.0 – 50.0 °C; 1/10 °C
Temperature
Bottom-Right Coil Return x10 R TW240 1.1.0
0023 0.0 – 50.0 °C; 1/10 °C
Temperature
0024 Top-Left Coil Return Temperature 0.0 – 50.0 °C; 1/10 °C x10 R TW240 1.1.0
0025 Top-Right Coil Return Temperature 0.0 – 50.0 °C; 1/10 °C x10 R TW240 1.1.0
0026 Remote Cold Aisle Temperature 1 0.0 – 50.0 °C; 1/10 °C x10 R TW240 1.1.0
0027 Remote Cold Aisle Temperature 2 0.0 – 50.0 °C; 1/10 °C x10 R TW240 1.1.0
1001 Supply Temperature Setpoint 5.0 – 35.0 °C; 1/10 °C x10 R/W All 1.0.0
1002 Remote DT Setpoint 0.0 – 30.0 °C; 1/10 °C x10 R/W All 1.0.0
1003 Remote DP Setpoint 0.0 – 15.0 Pa; 1/10 Pa x10 R/W All 1.0.0
5002 Unit Status 0=Local Off, 1=Remote Off; x1 R All 1.0.0
2=Not Used; 3= Bms Off;
4=Not used; 5=Alarm Off;
6-9=Not used;
10=Maintenance;
11=Local On; 12=Warning On;

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 7/18


HR/IR Description Range Scale Access Unit Config. Version
13=Alarm On; 14-15: Not
used; 16=Service Mode
5005 Right Fan 1 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm, 4=Comm. Failure
5006 Right Fan 2 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm, 4=Comm. Failure
5007 Right Fan 3 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm, 4=Comm. Failure
5008 Right Fan 4 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm, 4=Comm. Failure
5009 Right Fan 5 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5010 Right Fan 6 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5011 Left Fan 1 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5012 Left Fan 2 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5013 Left Fan 3 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5014 Left Fan 4 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5015 Left Fan 5 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5016 Left Fan 6 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5017 Bottom-Right Section Fans Speed 0 – 100 % x1 R TW200/400 1.0.0
(feedback value provided by the fan)
5018 Top-Right Fans Speed 0 – 100 % x1 R TW200/400 1.0.0
(feedback value provided by the fan)
5019 Bottom-Left Section Fans Speed 0 – 100 % x1 R TW200/400 1.0.0
(feedback value provided by the fan)
5020 Top-Left Section Fans Speed 0 – 100 % x1 R TW200/400 1.0.0
(feedback value provided by the fan)
5021 Right Fans Speed Control Mode 0=Off, 1=Emergency Mode, x1 R TW200/400 1.0.0
2=Diff. Temperature Control,
3-4=Diff. Pressure Control,
5= Maintenance Mode,
6= Service Mode,
7=Fire Alarm Mode
5022 Left Fans Speed Control Mode 0=Off, 1=Emergency Mode, x1 R TW200/400 1.0.0
2=Diff. Temperature Control,
3-4=Diff. Pressure Control,
5= Maintenance Mode,
6= Service Mode,
7=Fire Alarm Mode
5023 Bottom-Left CW Valve Status 0=Not Available, 1=Ok, x1 R All 1.0.0
3=Alarm, 4=Comm.Failure
5024 Bottom-Middle CW Valve Status 0=Not Available, 1=Ok, x1 R All 1.0.0
3=Alarm, 4=Comm.Failure
5025 Bottom-Right CW Valve Status 0=Not Available, 1=Ok, x1 R All 1.0.0
3=Alarm, 4=Comm.Failure
5026 Top-Left CW Valve Status 0=Not Available, 1=Ok, x1 R All 1.0.0
3=Alarm, 4=Comm.Failure

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 8/18


HR/IR Description Range Scale Access Unit Config. Version
5027 Top-Middle CW Valve Status 0=Not Available, 1=Ok, x1 R TW200/400 1.0.0
3=Alarm, 4=Comm.Failure
5028 Top-Right CW Valve Status 0=Not Available, 1=Ok, x1 R All 1.0.0
3=Alarm, 4=Comm.Failure
5029 Bottom-Left CW Valve Position 0 – 100 % x1 R All 1.0.0
5030 Bottom-Middle CW Valve Position 0 – 100 % x1 R All 1.0.0
5031 Bottom-Right CW Valve Position 0 – 100 % x1 R All 1.0.0
5032 Top-Left CW Valve Position 0 – 100 % x1 R All 1.0.0
5033 Top-Middle CW Valve Position 0 – 100 % x1 R TW200/400 1.0.0
5034 Top-Right CW Valve Position 0 – 100 % x1 R All 1.0.0
5035 Working Hours Bottom-Right Fans 0-32000 h x1 R TW200/400 1.0.0
5036 Working Hours Top-Right Fans 0-32000 h x1 R TW200/400 1.0.0
5037 Working Hours Bottom-Left Fans 0-32000 h x1 R TW200/400 1.0.0
5038 Working Hours Top-Left Fans 0-32000 h x1 R TW200/400 1.0.0
5039 Working Hours Bottom-Left Valve 0-32000 h x1 R All 1.0.0
5040 Working Hours Bottom-Middle Valve 0-32000 h x1 R All 1.0.0
5041 Working Hours Bottom-Right Valve 0-32000 h x1 R All 1.0.0
5042 Working Hours Top-Left Valve 0-32000 h x1 R All 1.0.0
5043 Working Hours Top-Middle Valve 0-32000 h x1 R TW200/400 1.0.0
5044 Working Hours Top-Right Valve 0-32000 h x1 R All 1.0.0
5045 Upper Fan 1 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW240 1.1.0
3=Alarm,4=Comm. Failure
5046 Upper Fan 2 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW240 1.1.0
3=Alarm,4=Comm. Failure
5047 Upper Fan 3 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW240 1.1.0
3=Alarm,4=Comm. Failure
5048 Upper Fan 4 Status 0=Not Installed, 1=ON, 2=OFF, x1 R TW240 1.1.0
3=Alarm,4=Comm. Failure
5049 Upper Fans Speed Control Mode 0=Off, 1=Emergency Mode, x1 R TW240 1.1.0
2=DT Control, 3-4=DP Control,
5= Maintenance Mode,
6= Service Mode,
7=Fire Alarm Mode
5050 Working Hours Upper Fans 0 – 32000 h x1 R TW240 1.1.0
5051 ATS1 Power Supply 0: POS-0,1: POS-1,2: POS-2 x1 R All 1.1.0
-1: ATS Not Installed,
-2: ATS Communication Error
5052 ATS1 Power Supply1 Status 0-OK, 1-Not OK x1 R All 1.1.0
5053 ATS1 Power Supply2 Status 0-OK, 1-Not OK x1 R All 1.1.0
5054 ATS2 Active Power Supply 0: POS-0,1: POS-1,2: POS-2 x1 R All 1.1.0
-1: ATS Not Installed,
-2: ATS Communication Error
5055 ATS2 Power Supply1 Status 0-OK, 1-Not OK x1 R All 1.1.0
5056 ATS2 Power Supply2 Status 0-OK, 1-Not OK x1 R All 1.1.0
5057 ATS3 Active Power Supply 0: POS-0,1: POS-1,2: POS-2 x1 R All 1.1.0
-1: ATS Not Installed,
-2: ATS Communication Error
5058 ATS3 Power Supply1 Status 0-OK, 1-Not OK x1 R All 1.1.0
5059 ATS3 Power Supply2 Status 0-OK, 1-Not OK x1 R All 1.1.0
5060 ATS4 Active Power Supply 0: POS-0,1: POS-1,2: POS-2 x1 R All 1.1.0
-1: ATS Not Installed,
-2: ATS Communication Error

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 9/18


HR/IR Description Range Scale Access Unit Config. Version
5061 ATS4 Power Supply1 Status 0: POS-0,1: POS-1,2: POS-2 x1 R All 1.1.0
-1: ATS Not Installed,
-2: ATS Communication Error
5062 ATS4 Power Supply2 Status 0-OK, 1-Not OK x1 R All 1.1.0
5063 Upper Fans Speed 0 – 100 % x1 R TW240 1.1.0
(feedback value provided by the fan)
5064 ATS5 Active Power Supply 0: POS-0,1: POS-1,2: POS-2 x1 R All 2.0.1
-1: ATS Not Installed,
-2: ATS Communication Error
5065 ATS5 Power Supply1 Status 0-OK, 1-Not OK x1 R All 2.0.1
5066 ATS5 Power Supply2 Status 0-OK, 1-Not OK x1 R All 2.0.1
5067 ATS6 Active Power Supply 0: POS-0,1: POS-1,2: POS-2 x1 R All 2.0.1
-1: ATS Not Installed,
-2: ATS Communication Error
5068 ATS6 Power Supply1 Status 0-OK, 1-Not OK x1 R All 2.0.1
5069 ATS6 Power Supply2 Status 0-OK, 1-Not OK x1 R All 2.0.1
5070 Communication Watchdog Counter 0-65535 x1 R All 2.1.0
6001 Unit On-Off Toggle Button 0= Current status not changed x1 R/W All 1.0.0
1= Change current status from
OnOff or OffOn
6002 Fans Minimum Speed 0 – 100 % x1 R/W All 1.0.0
6003 Fans Maximum Speed 0 – 100 % x1 R/W All 1.0.0
6004 Fans Emergency Speed 0 – 100 % x1 R/W All 1.0.0
6005 Enable Maintenance Mode 0=No, 1=Yes x1 R/W All 1.0.0
6006 Fans Maintenance Speed 0 – 100 % x1 R/W All 1.0.0
6007 Valves Maintenance Position 0 – 100 % x1 R/W All 1.0.0
6008 Enable of Multiple Coil Failure 0-No, 1-Yes x1 R/W TW200/400 2.0.1
Protection function
6009 Fans Speed forced by Multiple Coil 0-100% x1 R/W TW200/400 2.0.1
Failure Protection

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 10/18


5. BACNET
BACNET IMPLEMENTATION

The Monitoring Port features the following BACnet implementation on protocol rev. 1.14:
BACnet Standardized Device Profile: BACnet Application Specific Controller (B-ASC)

Building Blocks Supported:


DS-COV-B DS-RP-A DS-RP-B DS-WP-A DS-WP-B DS-RPM-A DS-RPM-B
DS-WPM-A DS-WPM-B DM-DDB-A DM-DDB-B DM-DOB-B DM-DCC-B

Segmentation Capability:
Able to transmit segmented messages Window Size: 16
Able to receive segmented messages Window Size: 16

Standard Object Types Supported:


Device Analog Input (AI)
Analog Output (AO) Analog Value (AV)
Binary Input (BI) Binary Output (BO)
Binary Value (BV) MultiState Input (MSI)
MultiState Output (MSO) MultiState Value (MSV)
Positive Integer Value (PIV) Integer Value (IV)

Data Link Layer Options:


BACnet IP
BACnet IP, Foreign Device

Character Sets Supported: ISO 10646 (UTF-8)

Network Security Options: Non-secure Device - is capable of operating without BACnet Network Security

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 11/18


BINARY VALUES

BV Variable Description Type Delay Unit Config. Version


1 AL001_SupplyPbFailBL.Active Supply Temp. Probe Fail (Bottom-Left) Alarm 30 sec All 1.0.0
2 AL002_SupplyPbFailBM.Active Supply Temp. Probe Fail (Bottom-Middle) Alarm 30 sec All 1.0.0
3 AL003_SupplyPbFailBR.Active Supply Temp. Probe Fail (Bottom-Right) Alarm 30 sec All 1.0.0
4 AL004_SupplyPbFailTL.Active Supply Temp. Probe Fail (Top-Left) Alarm 30 sec All 1.0.0
5 AL005_SupplyPbFailTM.Active Supply Temp. Probe Fail (Top-Middle) Alarm 30 sec TW200/400 1.0.0
6 AL006_SupplyPbFailTR.Active Supply Temp. Probe Fail (Top-Right) Alarm 30 sec All 1.0.0
7 AL007_DP1PbFail.Active DP Probe Fail (Right) Alarm 30 sec All 1.0.0
8 AL008_DP2PbFail.Active DP Probe Fail (Left) Alarm 30 sec All 1.0.0
9 AL009_THpb1CommErr.Active T/H Sensor 1 Comm. Error (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
10 AL010_THpb2CommErr.Active T/H Sensor 2 Comm. Error (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
11 AL011_THpb3CommErr.Active T/H Sensor 1 Comm. Error (Right White Space) Alarm 30 sec TW200/400 1.0.0
12 AL012_THpb4CommErr.Active T/H Sensor 2 Comm. Error (Right White Space) Alarm 30 sec TW200/400 1.0.0
13 AL013_THpb5CommErr.Active T/H Sensor 1 Comm. Error (Left White Space) Alarm 30 sec TW200/400 1.0.0
14 AL014_THpb6CommErr.Active T/H Sensor 2 Comm. Error (Left White Space) Alarm 30 sec TW200/400 1.0.0
15 AL015_THpb1Fail.Active T/H Sensor 1 Failure (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
16 AL016_THpb2Fail.Active T/H Sensor 2 Failure (Hot Aisle) Alarm 30 sec TW200/400 1.0.0
17 AL017_THpb3Fail.Active T/H Sensor 1 Failure (Right White Space) Alarm 30 sec TW200/400 1.0.0
18 AL018_THpb4Fail.Active T/H Sensor 2 Failure (Right White Space) Alarm 30 sec TW200/400 1.0.0
19 AL019_THpb5Fail.Active T/H Sensor 1 Failure (Left White Space) Alarm 30 sec TW200/400 1.0.0
20 AL020_THpb6Fail.Active T/H Sensor 2 Failure (Left White Space) Alarm 30 sec TW200/400 1.0.0
21 AL021_FansFailure.Active Fans Failure Alarm 1 min All 1.0.0
22 AL022_FansCommFail.Active Fans Communication Failure Alarm 1 min All 1.0.0
23 AL023_VlvMotorErrBL.Active CW Valve Motor Error (Bottom-Left) Alarm 1 min All 1.0.0
24 AL024_VlvMotorErrBM.Active CW Valve Motor Error (Bottom-Middle) Alarm 1 min All 1.0.0
25 AL025_VlvMotorErrBR.Active CW Valve Motor Error (Bottom-Right) Alarm 1 min All 1.0.0
26 AL026_VlvMotorErrTL.Active CW Valve Motor Error (Top-Left) Alarm 1 min All 1.0.0
27 AL027_VlvMotorErrTM.Active CW Valve Motor Error (Top-Middle) Alarm 1 min TW200/400 1.0.0
28 AL028_VlvMotorErrTR.Active CW Valve Motor Error (Top-Right) Alarm 1 min All 1.0.0
29 AL029_VlvsCommFail.Active CW Valves Communication Failure Alarm 1 min All 1.0.0
30 WN030_VlvFbkFailBL.Active CW Valve Feedback Fail (Bottom-Left) Warning 3 min All 1.0.0
31 WN031_VlvFbkFailBM.Active CW Valve Feedback Fail (Bottom-Middle) Warning 3 min All 1.0.0
32 WN032_VlvFbkFailBR.Active CW Valve Feedback Fail (Bottom-Right) Warning 3 min All 1.0.0
33 WN033_VlvFbkFailTL.Active CW Valve Feedback Fail (Top-Left) Warning 3 min All 1.0.0
34 WN034_VlvFbkFailTM.Active CW Valve Feedback Fail (Top-Middle) Warning 3 min TW200/400 1.0.0
35 WN035_VlvFbkFailTR.Active CW Valve Feedback Fail (Top-Right) Warning 3 min All 1.0.0
36 AL036_HighSupTempBL.Active High Supply Temperature (Bottom-Left) Alarm 1 min All 1.0.0
37 AL037_HighSupTempBM.Active High Supply Temperature (Bottom-Middle) Alarm 1 min All 1.0.0
38 AL038_HighSupTempBR.Active High Supply Temperature (Bottom-Right) Alarm 1 min All 1.0.0
39 AL039_HighSupTempTL.Active High Supply Temperature (Top-Left) Alarm 1 min All 1.0.0
40 AL040_HighSupTempTM.Active High Supply Temperature (Top-Middle) Alarm 1 min TW200/400 1.0.0
41 AL041_HighSupTempTR.Active High Supply Temperature (Top-Right) Alarm 1 min All 1.0.0
42 WN042_FansLimitBL.Active Fans Working Hours Limit (Bottom Left) Warning 0 sec TW200/400 1.0.0
43 WN043_FansLimitTL.Active Fans Working Hours Limit (Top Left) Warning 0 sec TW200/400 1.0.0
44 WN044_FansLimitBR.Active Fans Working Hours Limit (Bottom Right) Warning 0 sec TW200/400 1.0.0
45 WN045_FansLimitTR.Active Fans Working Hours Limit (Top Right) Warning 0 sec TW200/400 1.0.0
46 WN046_CwVlvLimitBL.Active CW Valve Working Hours Limit (Bottom-Left) Warning 0 sec All 1.0.0
47 WN047_CwVlvLimitBM.Active CW Valve Working Hours Limit (Bottom- Warning 0 sec All 1.0.0
Middle)
48 WN048_CwVlvLimitBR.Active CW Valve Working Hours Limit (Bottom-Right) Warning 0 sec All 1.0.0

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 12/18


BV Variable Description Type Delay Unit Config. Version
49 WN049_CwVlvLimitTL.Active CW Valve Working Hours Limit (Top-Left) Warning 0 sec All 1.0.0
50 WN050_CwVlvLimitTM.Active CW Valve Working Hours Limit (Top-Middle) Warning 0 sec TW200/400 1.0.0
51 WN051_CwVlvLimitTR.Active CW Valve Working Hours Limit (Top-Right) Warning 0 sec All 1.0.0
52 AL052_MissingUnitConf.Active Missing Unit Configuration Files Alarm 0 sec All 1.0.0
53 WN053_DPLeftFansEn.Active Fans DP Control Enable (Left) Warning 0 sec TW200/400 1.0.0
54 WN054_DPRightFansEn.Active Fans DP Control Enable (Right) Warning 0 sec TW200/400 1.0.0
55 AL055_FireAlarm.Active Fire Alarm Alarm 2 sec All 1.0.0
56 WN047_CwVlvLimitBM.Active ATS 1 Communication Error Alarm 30 sec All 1.1.0
57 WN048_CwVlvLimitBR.Active ATS 2 Communication Error Alarm 30 sec All 1.1.0
58 WN049_CwVlvLimitTL.Active ATS 3 Communication Error Alarm 30 sec All 1.1.0
59 WN050_CwVlvLimitTM.Active ATS 4 Communication Error Alarm 30 sec All 1.1.0
60 WN051_CwVlvLimitTR.Active T/H Sensor 1 Failure (Cold Aisle) Alarm 30 sec TW240 1.1.0
61 AL052_MissingUnitConf.Active T/H Sensor 2 Failure (Cold Aisle) Alarm 30 sec TW240 1.1.0
62 WN053_DPLeftFansEn.Active Return Temp. Probe Fail (Bottom-Left) Alarm 30 sec TW240 1.1.0
63 WN054_DPRightFansEn.Active Return Temp. Probe Fail (Bottom-Middle) Alarm 30 sec TW240 1.1.0
64 AL055_FireAlarm.Active Return Temp. Probe Fail (Bottom-Right) Alarm 30 sec TW240 1.1.0
65 WN047_CwVlvLimitBM.Active Return Temp. Probe Fail (Top-Left) Alarm 30 sec TW240 1.1.0
66 WN048_CwVlvLimitBR.Active Return Temp. Probe Fail (Top-Right) Alarm 30 sec TW240 1.1.0
67 WN049_CwVlvLimitTL.Active T/H Sensor 1 Communication Error (Cold Aisle) Alarm 30 sec TW240 1.1.0
68 WN050_CwVlvLimitTM.Active T/H Sensor 2 Communication Error (Cold Aisle) Alarm 30 sec TW240 1.1.0
69 WN051_CwVlvLimitTR.Active Fans DP Control Enable (Upper) Warning 0 sec TW240 1.1.0
70 AL052_MissingUnitConf.Active Fans Working Hours Limit (Upper) Warning 0 sec TW240 1.1.0
71 WN053_DPLeftFansEn.Active Fans Rotation Error Alarm 0 sec All 1.1.0
72 AL072_Exp1CommErr.Active Expansion I/O Board Communication Error Alarm 30 sec All 1.1.0
73 WN073_NetFail Network Communication Failure Warning 15 sec All 2.0.0
74 MG074_MasterChange Master Unit Changed Messsage 5 sec TW240 2.0.0
75 WN075_MasterNotAvail Master Unit Not Available Warning 1 min TW240 2.0.0
76 AL076_SysDTPrbFail System DT Not Valid Alarm 10 sec TW240 2.0.0
77 AL077_SysDPPrbFail System DP Not Valid Alarm 10 sec TW240 2.0.0
78 WN078_ATS5CommErr.Active ATS 5 Communication Error Warning 30 sec All 2.0.1
79 WN079_ATS6CommErr.Active ATS 6 Communication Error Warning 30 sec All 2.0.1
80 AL080_MultiHiSupTemp.Active Multiple High Supply Temperatures Alarm 0 sec TW200/400 2.0.1
WN081_LowFansSpeedProt.Act Low Fans Speed Protection Enabled Warning 0 sec TW200/400 2.0.1
81 ive
90 MG090_LocalOn.Active Local On Messsage 0 sec All 1.0.0
91 MG091_BmsOn.Active BMS On Messsage 0 sec All 1.0.0
92 MG092_LocalOff.Active Local Off Messsage 0 sec All 1.0.0
93 MG093_BmsOff.Active BMS Off Messsage 0 sec All 1.0.0
94 MG094_RemoteOff.Active Remote Off Messsage 0 sec All 1.0.0
95 MG095_ServiceMode.Active Service Control Mode Enabled Messsage 0 sec All 1.0.0
96 MG096_Maintenance.Active Maintenance Mode Enabled Messsage 0 sec All 1.0.0

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 13/18


ANALOG VALUES

AV Variable Description Range Access Unit Config. Version


1 RightFans_DeltaT.Val Remote Differential Temperature 0.0 – 50.0 °C R TW200/400 1.0.0
(Right Fans Speed Control Input)
2 RightFans_DeltaP.Val Remote Differential Pressure 0.0 – 500.0 Pa R TW200/400 1.0.0
(Right Fans Speed Control Input)
3 LeftFans_DeltaT.Val Remote Differential Temperature 0.0 – 50.0 °C R TW200/400 1.0.0
(Left Fans Speed Control Input)
4 LeftFans_DeltaP.Val Remote Differential Pressure 0.0 – 500.0 Pa R TW200/400 1.0.0
(Left Fans Speed Control Input)
5 SupplyTemp[1].Value Bottom-Left Coil Supply Temperature 0.0 – 50.0 °C R All 1.0.0
6 SupplyTemp[2].Value Bottom-Middle Coil Supply Temperature 0.0 – 50.0 °C R All 1.0.0
7 SupplyTemp[3].Value Bottom-Right Coil Supply Temperature 0.0 – 50.0 °C R All 1.0.0
8 SupplyTemp[4].Value Top-Left Coil Supply Temperature 0.0 – 50.0 °C R All 1.0.0
9 SupplyTemp[5].Value Top-Middle Coil Supply Temperature 0.0 – 50.0 °C R TW200/400 1.0.0
10 SupplyTemp[6].Value Top-Right Coil Supply Temperature 0.0 – 50.0 °C R All 1.0.0
11 HotAisleTemp[1] Hot Aisle Temperature 1 -40.0 – +80.0 °C R All 1.0.0
12 HotAisleTemp[2] Hot Aisle Temperature 2 -40.0 – +80.0 °C R All 1.0.0
13 WS_RightTemp[1] Right Cold Aisle Temperature 1 -40.0 – +80.0 °C R TW200/400 1.0.0
14 WS_RightTemp[2] Right Cold Aisle Temperature 2 -40.0 – +80.0 °C R TW200/400 1.0.0
15 WS_LeftTemp[1] Left Cold Aisle Temperature 1 -40.0 – +80.0 °C R TW200/400 1.0.0
16 WS_LeftTemp[2] Left Cold Aisle Temperature 2 -40.0 – +80.0 °C R TW200/400 1.0.0
17 RightDP Right Differential Pressure 0.0 – 500.0 Pa R TW200/400 1.0.0
18 LeftDP Left Differential Pressure 0.0 – 500.0 Pa R TW200/400 1.0.0
19 UpperFans_DeltaT.Val Remote Differential Temperature 0.0 – 50.0 °C R TW240 1.1.0
(Upper Fans Speed Control Input)
20 UpperFans_DeltaP.Val Remote Differential Pressure 0.0 – 500.0 Pa R TW240 1.1.0
(Upper Fans Speed Control Input)
21 ReturnTemp[1].Value Bottom-Left Coil Return Temperature 0.0 – 50.0 °C R TW240 1.1.0
22 ReturnTemp[2].Value Bottom-Middle Coil Return Temperature 0.0 – 50.0 °C R TW240 1.1.0
23 ReturnTemp[3].Value Bottom-Right Coil Return Temperature 0.0 – 50.0 °C R TW240 1.1.0
24 ReturnTemp[4].Value Top-Left Coil Return Temperature 0.0 – 50.0 °C R TW240 1.1.0
25 ReturnTemp[5].Value Top-Right Coil Return Temperature 0.0 – 50.0 °C R TW240 1.1.0
26 CA_Temp[1] Remote Cold Aisle Temperature 1 0.0 – 50.0 °C R TW240 1.1.0
27 CA_Temp[2] Remote Cold Aisle Temperature 2 0.0 – 50.0 °C R TW240 1.1.0
1001 Cfg_Vlv_SetP Supply Temperature Setpoint 5.0 – 35.0 °C R/W All 1.0.0
1002 Cfg_Fans_DTSetP Remote Differential Temperature 0.0 – 30.0 °C R/W All 1.0.0
Setpoint
1003 Cfg_Fans_DPSetP Remote Differential Pressure Setpoint 0.0 – 15.0 Pa R/W All 1.0.0

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 14/18


MULTI STATE VALUES

MV Variable Description Range Access Unit Config. Version


5002 UnitStatus Unit Status 0=Local Off, 1=Remote Off; R All 1.0.0
2=Not Used; 3= Bms Off;
4=Not used; 5=Alarm Off;
6-9=Not used;
10=Maintenance Mode;
11=Local On; 12=Warning On;
13=Alarm On; 14-15: Not
used; 16=Service Mode
5005 RightFansStat[1] Right Fan 1 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5006 RightFansStat[2] Right Fan 2 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5007 RightFansStat[3] Right Fan 3 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5008 RightFansStat[4] Right Fan 4 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5009 RightFansStat[5] Right Fan 5 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5010 RightFansStat[6] Right Fan 6 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5011 LeftFansStat[1] Left Fan 1 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5012 LeftFansStat[2] Left Fan 2 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5013 LeftFansStat[3] Left Fan 3 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5014 LeftFansStat[4] Left Fan 4 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5015 LeftFansStat[5] Left Fan 5 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5016 LeftFansStat[6] Left Fan 6 Status 0=Not Installed, 1=ON, 2=OFF, R TW200/400 1.0.0
3=Alarm,4=Comm. Failure
5021 RightFansData.CtrlMode Right Fans Speed Control 0=Off, 1=Emergency Mode, R TW200/400 1.0.0
Mode 2=DT Control, 3-4=DP Control,
5= Maintenance Mode,
6= Service Mode,
7=Fire Alarm Mode
5022 LeftFansData.CtrlMode Left Fans Speed Control 0=Off, 1=Emergency Mode, R TW200/400 1.0.0
Mode 2=DT Control, 3-4=DP Control,
5= Maintenance Mode,
6= Service Mode,
7=Fire Alarm Mode
5023 ValvesStat[1] Bottom-Left CW Valve 0=Not Available, 1=Ok, R All 1.0.0
Status 3=Alarm, 4=Comm.Failure
5024 ValvesStat[2] Bottom-Middle CW Valve 0=Not Available, 1=Ok, R All 1.0.0
Status 3=Alarm, 4=Comm.Failure
5025 ValvesStat[3] Bottom-Right CW Valve 0=Not Available, 1=Ok, R All 1.0.0
Status 3=Alarm, 4=Comm.Failure
5026 ValvesStat[4] Top-Left CW Valve Status 0=Not Available, 1=Ok, R All 1.0.0
3=Alarm, 4=Comm.Failure
5027 ValvesStat[5] Top-Middle CW Valve Status 0=Not Available, 1=Ok, R TW200/400 1.0.0
3=Alarm, 4=Comm.Failure

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 15/18


MV Variable Description Range Access Unit Config. Version
5028 ValvesStat[6] Top-Right CW Valve Status 0=Not Available, 1=Ok, R All 1.0.0
3=Alarm, 4=Comm.Failure
5045 UpperFansStat[1] Upper Fan 1 Status 0=Not Installed, 1=ON, 2=OFF, R TW240 1.1.0
3=Alarm,4=Comm. Failure
5046 UpperFansStat[2] Upper Fan 2 Status 0=Not Installed, 1=ON, 2=OFF, R TW240 1.1.0
3=Alarm,4=Comm. Failure
5047 UpperFansStat[3] Upper Fan 3 Status 0=Not Installed, 1=ON, 2=OFF, R TW240 1.1.0
3=Alarm,4=Comm. Failure
5048 UpperFansStat[4] Upper Fan 4 Status 0=Not Installed, 1=ON, 2=OFF, R TW240 1.1.0
3=Alarm,4=Comm. Failure
5049 UpperFansData.CtrlMode Upper Fans Speed Control 0=Off, 1=Emergency Mode, R TW240 1.1.0
Mode 2=Diff. Temperature Control,
3-4=Diff. Pressure Control,
5= Maintenance Mode,
6= Service Mode,
7=Fire Alarm Mode
5070 BMS_Watchdog Comm. Watchdog Counter 0-65535 R All 2.1.0

INTEGER VALUES

IV Variable Description Range Access Unit Config. Version


5017 FansBR_Fbk Bottom-Right Section Fans Speed 0 – 100 % R TW200/400 1.0.0
(feedback provided by the fan)
5018 FansTR_Fbk Top-Right Fans Speed 0 – 100 % R TW200/400 1.0.0
(feedback provided by the fan)
5019 FansBL_Fbk Bottom-Left Section Fans Speed 0 – 100 % R TW200/400 1.0.0
(feedback provided by the fan)
5020 FansTL_Fbk Top-Left Section Fans Speed 0 – 100 % R TW200/400 1.0.0
(feedback provided by the fan)
5029 ValvesData[1].Fbk Bottom-Left CW Valve Position 0 – 100 % R All 1.0.0
5030 ValvesData[2].Fbk Bottom-Middle CW Valve 0 – 100 % R All 1.0.0
Position
5031 ValvesData[3].Fbk Bottom-Right CW Valve Position 0 – 100 % R All 1.0.0
5032 ValvesData[4].Fbk Top-Left CW Valve Position 0 – 100 % R All 1.0.0
5033 ValvesData[5].Fbk Top-Middle CW Valve Position 0 – 100 % R TW200/400 1.0.0
5034 ValvesData[6].Fbk Top-Right CW Valve Position 0 – 100 % R All 1.0.0
5035 BMS_WHFansBR Working Hours Bottom-Right 0 – 32000 h R TW200/400 1.0.0
Fans
5036 BMS_WHFansTR Working Hours Top-Right Fans 0 – 32000 h R TW200/400 1.0.0
5037 BMS_WHFansBL Working Hours Bottom-Left Fans 0 – 32000 h R TW200/400 1.0.0
5038 BMS_WHFansTL Working Hours Top-Left Fans 0 – 32000 h R TW200/400 1.0.0
5039 BMS_WHValveBL Working Hours Bottom-Left Valve 0 – 32000 h R All 1.0.0
5040 BMS_WHValveBM Working Hours Bottom-Middle 0 – 32000 h R All 1.0.0
Valve
5041 BMS_WHValveBR Working Hours Bottom-Right 0 – 32000 h R All 1.0.0
Valve
5042 BMS_WHValveTL Working Hours Top-Left Valve 0 – 32000 h R All 1.0.0
5043 BMS_WHValveTM Working Hours Top-Middle Valve 0 – 32000 h R TW200/400 1.0.0
5044 BMS_WHValveTR Working Hours Top-Right Valve 0 – 32000 h R All 1.0.0
5050 BMS_WHFansUpper Working Hours Upper Fans 0 – 32000 h R TW240 1.1.0
5051 ATSData[1].Status ATS1 Active Power Supply 0: POS0, 1: POS1, 2: POS2 R All 1.0.0
-1: ATS Not Installed,

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 16/18


IV Variable Description Range Access Unit Config. Version
-2: ATS Comm. Error
5052 ATSData[1].Src1Sts ATS1 Power Supply1 Status 0-OK, 1-Not OK R All 1.0.0
5053 ATSData[1].Src2Sts ATS1 Power Supply2 Status 0-OK, 1-Not OK R All 1.0.0
5054 ATSData[2].Status ATS2 Active Power Supply 0: POS0, 1: POS1, 2: POS2 R All 1.0.0
-1: ATS Not Installed,
-2: ATS Comm. Error
5055 ATSData[2].Src1Sts ATS2 Power Supply1 Status 0-OK, 1-Not OK R All 1.0.0
5056 ATSData[2].Src2Sts ATS2 Power Supply2 Status 0-OK, 1-Not OK R All 1.0.0
5057 ATSData[3].Status ATS3 Active Power Supply 0: POS0, 1: POS1, 2: POS2 R All 1.0.0
-1: ATS Not Installed,
-2: ATS Comm. Error
5058 ATSData[3].Src1Sts ATS3 Power Supply1 Status 0-OK, 1-Not OK R All 1.0.0
5059 ATSData[3].Src2Sts ATS3 Power Supply2 Status 0-OK, 1-Not OK R All 1.0.0
5060 ATSData[4].Status ATS4 Active Power Supply 0: POS0, 1: POS1, 2: POS2 R All 1.0.0
-1: ATS Not Installed,
-2: ATS Comm. Error
5061 ATSData[4].Src1Sts ATS4 Power Supply1 Status 0-OK, 1-Not OK R All 1.0.0
5062 ATSData[4].Src2Sts ATS4 Power Supply2 Status 0-OK, 1-Not OK R All 1.0.0
5063 FansU_Fbk Upper Fans Speed 0 – 100 % R TW240 1.1.0
(feedback provided by the fan)
ATSData[5].Status ATS5 Active Power Supply 0: POS0, 1: POS1, 2: POS2 R All 2.0.1
5064 -1: ATS Not Installed,
-2: ATS Comm. Error
5065 ATSData[5].Src1Sts ATS5 Power Supply1 Status 0-OK, 1-Not OK R All 2.0.1
5066 ATSData[5].Src2Sts ATS5 Power Supply2 Status 0-OK, 1-Not OK R All 2.0.1
ATSData[6].Status ATS6 Active Power Supply 0: POS0, 1: POS1, 2: POS2 R All 2.0.1
5067 -1: ATS Not Installed,
-2: ATS Comm. Error
5068 ATSData[6].Src1Sts ATS6 Power Supply1 Status 0-OK, 1-Not OK R All 2.0.1
5069 ATSData[6].Src2Sts ATS6 Power Supply2 Status 0-OK, 1-Not OK R All 2.0.1
6001 BmsOnOffReq Unit On-Off Toggle Button 0= Maintain last status, R/W All 1.0.0
1= Change current status
from OnOff or OffOn
6002 Cfg_Fans_MinSpeed Fans Minimum Speed 0 – 100 % R/W All 1.0.0
6003 Cfg_Fans_MaxSpeed Fans Maximum Speed 0 – 100 % R/W All 1.0.0
6004 Cfg_Fans_EmgSpeed Fans Emergency Speed 0 – 100 % R/W All 1.0.0
6005 MntModeEn Enable Maintenance Mode 0 = No, 1 = Yes R/W All 1.0.0

6006 Cfg_Fans_MntSpeed Fans Maintenance Speed 0 – 100 % R/W All 1.0.0


6007 Cfg_Vlv_MntPos Valves Maintenance Position 0 – 100 % R/W All 1.0.0
6008 Cfg_Alrm_MCFProtCfg Enable of Multiple Coils Failure 0-No, 1-Yes R/W TW200/400 2.0.1
Protection function
6009 Cfg_Fans_MCFProtSpe Fans Speed forced by Multiple 0 – 100 % R/W TW200/400 2.0.1
ed Coil Failure Protection

Thermal Wall Monitoring Manual V1T Application rev. 2021.11.26 17/18


6. FAQs
The aim of this appendix is to collect a list of possible questions/issues directed primarily to Vertiv service technical
support team.

GENERAL FAQS
Question / Issue Solution
1) Are the three monitoring protocols available - Yes they are
simultaneously?

MODBUS RELATED FAQS


Question / Issue Solution
1) Is Multi-Master supported? - Yes it is
2) Is serial connection RS485 available? - Not directly, but it is possible to connect an
ETH/RS485 modbus converter like Moxa
MGate 3180 (code 276989)

BACNET RELATED FAQS


Question / Issue Solution
1) Does the Monitoring Port feature the official - Yes it is BTL certified
BACnet certification?