Monitoring Manual
Product Documentation
English, code: 10012918 rev. 2021.11.26
INDEX
1. SCOPE 4
2. MONITORING PROTOCOLS 4
3. CONNECTIONS 4
ETHERNET CONNECTION ON ICOM3 CONTROL 4
4. MODBUS TCP/IP 5
INPUT STATUS 5
HOLDING AND INPUT REGISTERS 7
5. BACNET 11
BACNET IMPLEMENTATION 11
BINARY VALUES 12
ANALOG VALUES 14
MULTI STATE VALUES 15
INTEGER VALUES 16
6. FAQS 18
GENERAL FAQS 18
MODBUS RELATED FAQS 18
BACNET RELATED FAQS 18
2. Monitoring Protocols
The Modbus protocols is provided over IP through a dedicated Ethernet port, that is physically disconnected from the
rest of the other controller interfaces and communicating via serial RS485 protocol with the micro processor.
The web site is available at that address. At the first access the user is guided by a “First Boot Access” wizard that
forces the creation of the web user accounts.
The following standard monitoring protocols are made available:
Modbus TCP/IP
- Port 502
- default address: 1
BACnet IP v1.14
- UDP Port 47808
- default address: 1
- default device name: NHES1
The last column on every datapoints table reports the SW version from which the specific datapoint is made available.
3. Connections
ETHERNET CONNECTION ON ICOM3 CONTROL
Monitoring Port
The Monitoring Port features the following BACnet implementation on protocol rev. 1.14:
BACnet Standardized Device Profile: BACnet Application Specific Controller (B-ASC)
Segmentation Capability:
Able to transmit segmented messages Window Size: 16
Able to receive segmented messages Window Size: 16
Network Security Options: Non-secure Device - is capable of operating without BACnet Network Security
INTEGER VALUES
GENERAL FAQS
Question / Issue Solution
1) Are the three monitoring protocols available - Yes they are
simultaneously?