Manual Book Mp5w-Y-S

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DRW160458AD

PULSE METER Specifications Connections


Series MP5S MP5Y MP5W ※Terminal connections differ by power supply and output type of each series and model.
MP5S Series
MP5S/Y/W SERIES
Display method 7-segment LED (zero blanking method) ※Use teminals of size specified below.
Character size W4×H8mm W7×H14mm a b
Display range -19999 to 99999
INSTRUCTION MANUAL Power AC voltage 100-240VAC 50/60Hz a b Min. Max.

Brown
supply

Black

Black
AC/DC voltage 24VAC 50/60Hz, 24-48VDC 3.5mm 7.0mm

Blue
Max. 7.5VA Max. 9VA Max. 15VA <Forked>
※1
Power AC voltage INA INB +12V 0V HOLD/RESET
(100-240VAC 50/60Hz) (100-240VAC 50/60Hz) (100-240VAC 50/60Hz)
consum- MP5Y Series
ption Max. 6VA (24VAC 50/60Hz), Max. 7VA (24VAC 50/60Hz), Max. 11VA (24VAC 50/60Hz), 6 7 8 9 10
AC/DC voltage
Max. 4.5W (24-48VDC ) Max. 6.2W (24-48VDC ) Max. 7W (24-48VDC ) Power/Input Terminal (common) ※MP5Y- N (indicator) only has 'Power/Input terminals'.
Permissible voltage range 90 to 110% of rated voltage ※1: Operation mode F1 to F12
External power supply Max. 12VDC ±10% 80mA : Display value HOLD
Operation mode F13 to F16 ※1: Operation mode F1 to F12
Sub power supply - Max. 24VDC 30mA : Display value RESET : Display value HOLD 11 12
·Solid state input 1: Max. 50kHz (pulse width: min. 10㎲) ※2: Model Operation mode F13 to F16
Source
Input frequency ·Solid state input 2: Max. 5kHz (pulse width: min. 100㎲) : Display value RESET
※For F7, F8, F9, F10 operation mode, max. 1kHz (pulse width: min. 500㎲) Black Black Blue Brown
MP5Y-2
24-48VDC
※2: Model
·Contact input: Max. 45Hz (pulse width: min. 11ms) 24VAC 50/60Hz Source
MP5S MP5Y MP5W 1 2 3 4 5 6 7 1 2 3 4 5
[Voltage input] High: 4.5-24VDC , Low: 0-1VDC, Input impedance: 3.9kΩ MP5Y-4
100-240VAC 24-48VDC
MP5S-2N
Thank you for choosing our Autonics product. Input method [No-voltage input] Short-circuit impedance: Max. 80Ω, Residual voltage: Max. 1VDC,
Open-circuit impedance: Min. 100kΩ
INA INB 0V +12V 50/60Hz 24VAC 50/60Hz
HOLD/RESET
※1
100-240VAC
Please read the following safety considerations before use. ·Operation mode F1, F2, F7, F8, F9, F10 : 0.0005Hz to 50kHz - +
※2
MP5S-4N
50/60Hz - + ※2
·Operation mode F3, F4, F5, F6 : 0.01 to max. of each time range SOURCE SOURCE
Measurement range
Safety Considerations ·Operation mode F11, F12, F13, F16 : 0 to 99999
※Hirose connector socket is not included.
·Operation mode F14, F15 : -19999 to 99999 O
 utput Connector (MP5Y- 1 to 5) Contact a hirose connector dealer regarding sockets MP5W Series
※Please observe all safety considerations for safe and proper product operation to avoid hazards. Measurement accuracy ·Operation mode F1, F2, F7, F8, F9, F10 : F.S.±0.05%rdg±1-digit ※Hirose connector: HIF3BA-10PA-2.54DS and cables.
(23℃±5℃) ·Operation mode F3, F4, F5, F6 : F.S.±0.01%rdg±1-digit Power/Input Terminal (Common)
※Safety considerations are categorized as follows. ※Hirose connector socket: HIF3BA-10D-2.54R (sold separately)
Display cycle OFF (for F2, F16 operation mode), 0.05, 0.5, 1, 2, 4, 8 sec (same as update output cycle)
Warning Failure to follow these instructions may result in serious injury or death. ⊙ MP5Y- 1 (NPN open collector output) ⊙ MP5Y- 2 (PNP open collector output) ※MP5W- N (indicator) only has 'Power/Input terminals'.
Frequency/Revolutions/Speed (F1), Passing speed (F2), Cycle (F3),
Caution Failure to follow these instructions may result in personal injury or product damage. Passing time (F4), Time interval (F5), Time differential (F6), Absolute ratio (F7), MAIN OUT (NPN OPEN COLLECTOR) MAIN OUT (PNP OPEN COLLECTOR)
Operation mode Error ratio (F8), Density (F9), Error (F10), Length measurement 1 (F11), 30VDC 30mA 30VDC 30mA
※The symbols used on the product and instruction manual represent the following Interval (F12), Accumulation (F13), Addition/Subtraction-individual input (F14),
symbol represents caution due to special circumstances in which hazards may occur. Addition/Subtraction-phase difference input (F15), Length measurement 2 (F16) HH GO LL HH GO LL
Prescale function Direct input method (0.0001×10-9 to 9.9999×109)
Warning Hysteresis 0 to 9999
※1
2 4 6 8 10 2 4 6 8 10
Relay triple 250VAC 3A resistive load
1. Fail-safe device must be installed when using the unit with machinery that may cause - 250VAC 3A resistive load
1 3 5 7 9 1 3 5 7 9
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, Main Relay quintuple Black Black Blue Brown
NPN/PNP open

Output
Max. 30VDC 30mA COM H L COM H L
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster collector quintuple - ※1: Operation mode F1 to F12 1 2 3 4 5 6 7 8 9
prevention devices, etc.) BCD dynamic Max. 30VDC 30mA : Display value HOLD
⊙ MP5Y- 3 (BCD dynamic output) ⊙ MP5Y- 4 (PV transmission output) Operation mode F13 to F16 INA INB 0V 0V +12V
Failure to follow this instruction may result in fire, personal injury, or economic loss. Sub PV transmission DC4-20mA/DC0-20mA max. load 500Ω
BCD OUT(NPN OPEN COLLECTOR) : Display value RESET
2. Install on a device panel to use. Communication RS485 communication output (Modbus RTU method) 30VDC 30mA DC4-20mA/DC0-20mA ※2: Model
※1
Source HOLD/RESET - +
Failure to follow this instruction may result in electric shock or fire Memory retention Non-volatile memory (number of inputs: 100,000 operations) Load 500Ω Max. (+) SOURCE
※2

3. Do not connect, repair, or inspect the unit while connected to a power source. Insulation resistance Over 100MΩ (at 500VDC megger) A C D0 D2 D4 24-48VDC BANK
MP5W-2
24VAC 50/60Hz
Failure to follow this instruction may result in electric shock or fire. Dielectric strength 2,000VAC 60Hz for 1 min
4. Check 'Connections' before wiring. Noise immunity ±2kV the square wave noise (pulse width: 1㎲) by the noise simulator 2 4 6 8 10 2 4 6 8 10 MP5W-4
100-240VAC
50/60Hz
Failure to follow this instruction may result in fire. Mechanical 0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 1 hour 1 3 5 7 9 1 3 5 7 9
5. Do not disassemble or modify the unit. Vibration
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 10 min
Failure to follow this instruction may result in electric shock or fire. Mechanical 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times COM B D D1 D3 Output Terminal (MP5W- A/1)
Shock (-)
⊙ MP5W- A (Relay quintuple output) ⊙ MP5W- 1 (Relay triple output)
Caution Malfunction 100m/s² (approx. 30G) in each X, Y, Z direction for 3 times ※Autonics display unit (DS/DA Series) is recommended

1. When connecting the power/measurement input and relay output, use AWG 24(0.20mm2) to Relay Mechanical - Min. 10,000,000 operations for stable minus (-) sign display. Output Terminal (MP5Y- 6) CONTACT OUT:
life cycle Electrical - Min. 100,000 operations (250VAC 3A resistive load) 250VAC 3A RESISTIVE LOAD CONTACT OUT:
AWG 15(1.65mm2) cable and tighten the terminal screw with a tightening torque of 0.98 to 1.18N.m. ⊙ MP5Y- 5 (RS485 communication output) ⊙ MP5Y- 6 (Relay triple output) 250VAC 3A RESISTIVE LOAD
Use proper cables for the rated load current. Environ- Ambient temp. -10 to 50℃, storage: -20 to 60℃ RS485 B(-)
H GO L
Failure to follow this instruction may result in fire or malfunction due to contact failure.
ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH 8 9 10 11 12 13 14 15
2. Use the unit within the rated specifications. Approval Иᜧ 2 4 6 8 10
※2
Failure to follow this instruction may result in fire or product damage. Weight Approx. 191g (approx. 132g) Approx. 230g (approx. 140g) Approx. 334g (approx. 210g)
3. Use dry cloth to clean the unit, and do not use water or organic solvent. ※1: Setting range will vary depending on the decimal point. 1 3 5 7 9 H GO L 10 11 12 13 14 15 10 11 12 13 14 15
CONTACT OUT:
Failure to follow this instruction may result in electric shock or fire. ※2:The weight includes packaging. The weight in parenthesis is for unit only.
RS485 A(+) 250VAC 3A RESISTIVE LOAD
4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct ※Environment resistance is rated at no freezing or condensation. HH H GO L LL COM
sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in fire or explosion.
Dimensions ※Side dimensions of MP5Y/W differ by output type.
(unit: mm) B
 racket (unit: mm) Output Connector (MP5W- 2/4/5/8/9)
5. Keep metal chip, dust, and wire residue from flowing into the unit. MP5S ⊙ For MP5S ※Hirose connector socket is not included.
48 10 90 ※Hirose connector: HIF3BA-20PA-2.54DS
Failure to follow this instruction may result in fire or product damage. Contact a hirose connector dealer
41 ※Hirose connector socket: HIF3BA-20D-2.54R (sold separately) regarding sockets and cables.
※1: Sub power supply
Ordering Information 4.2

3.9
※2: POL signal turns ON when the display value is a minus (-) value.
⊙ MP5W- 2 (NPN open collector + BCD dynamic output)

3
MP 5 Y - 4 N MAIN OUT (NPN OPEN COLLECTOR)
※Autonics display unit (DS/DA Series) is
30VDC 30mA

45
+24VDC recommended for stable minus (-) sign display.
Main output Sub output
Output

※1
(Comparative value output) (Display value output) 30mA Max.

45.4
HH GO DOT COM2

50
LL B D D1 D3

61
S N Indicator -
2 4 6 8 10 12 14 16 18 20
N Indicator -
1 NPN open collector quintuple output - MP5Y ⊙ MP5Y- 1/2/3/4/5 ⊙ MP5Y- 6
72 6 89.5 14.5 1 3 5 7 9 11 13 15 17 19
2 PNP open collector quintuple output - 15.3
※2
3 Indicator BCD dynamic output COM H L A C D0 D2 D4 POL

4.5
Y 0V BCD OUT (NPN OPEN COLLECTOR)
PV transmission output 0.82
4 Indicator 30VDC Max. 30mA
(current output)
⊙ MP5W- 4 ⊙ MP5W- 5

30
36

5 Indicator RS485 comm. output (NPN open collector + PV transmission output) (PNP open collector + PV transmission output)

15
6 Relay triple output (H, GO, L) -
MAIN OUT (NPN OPEN COLLECTOR) MAIN OUT (PNP OPEN COLLECTOR)
N Indicator - 10.5 10.5 42.2 30VDC 30mA 30VDC 30mA
12.2 +24VDC
Relay quintuple output ※MP5Y- N (indicator) does not include the shaded part 45.4
A - 30mA Max.
※1
(+)
16.4 47.8
(HH, H, GO, L, LL) MP5W (output hirose connector or output terminal).
61.64
HH GO LL HH GO LL
1 Relay triple output (H, GO, L) - ⊙ MP5W- 2/4/5/8/9 ⊙ MP5W- A/1 48.6
96 89.5 14.5 2 4 6 8 10 12 14 16 18 20 2 4 6
2 NPN open collector quintuple output BCD dynamic output 6 10.5
W PV transmission output
4 NPN open collector quintuple output 1 3 5 7 9 11 13 15 17 19 1 3 5
(current output)
PV transmission output ⊙ For MP5Y/W COM H L COM H L
5 PNP open collector quintuple output 0V (-)
(current output)
45
48

DC4-20mA/DC0-20mA
8 NPN open collector quintuple output RS485 comm. output 73 (Load 500Ω Max.)
9 PNP open collector quintuple output RS485 comm. output 30 ⊙ MP5W- 8 ⊙ MP5W- 9
Power
supply 2 24VAC 50/60Hz, 24-48VDC (NPN open collector + RS485 comm. output) (PNP open collector + RS485 comm. output)
10.5 10.5 12±0.2

10
4 100-240VAC 50/60Hz MAIN OUT (NPN OPEN COLLECTOR) MAIN OUT (PNP OPEN COLLECTOR)

6
30VDC 30mA 30VDC 30mA
S DIN W48×H48mm P
 anel Cut-out Dimensions ※MP5W- N (indicator) does not include the shaded part +24VDC RS485
Size A (output hirose connector or output terminal). 30mA Max.
※1
B (-)
Y DIN W72×H36mm HH GO LL HH GO LL
W DIN W96×H48mm
Digits (unit: mm) 2 4 6 8 10 12 14 16 18 20 2 4 6

4
9.5

1
5 99999 (5-digit) D Size
Item A B C D
Series
MP Pulse meter 1 3 5 7 9 11 13 15 17 19 1 3 5
0.2±0.2

MP5S Min. 55 Min. 62 45.5+0.5 45.5+0.5 M3


※The above specifications are subject to change and some models may be discontinued B C
0 0

COM H L COM H L
MP5Y Min. 91 Min. 40 68+0.7
0 31.5+0.5
0
0V A (+)
without notice.
※Be sure to follow cautions written in the instruction manual and the technical descriptions MP5W Min. 116 Min. 52 92+0.8
0 45+0.6
0 RS485
(catalog, homepage).
1/4
Input/Output Specifications Unit Description ● Parameter 1 Group ● Parameter 3 Group
ON
2 sec
Input Specifications OFF 2 sec RUN mode PARa1 PARa2 PARa3
1. Input signal ON OFF Pulse width
MP5S MP5Y RUN mode PARa1 PARa2 PARa3
Standard duty ratio of input signal is 1:1. 4 3 sec
T 3 sec Flashes
(1) Solid state input 1 ※1 Flashes
Input frequency: Max. 50kHz (ON/OFF pulse width: min. 10㎲ of each) ※T: single cycle of alternately alternately
※1
●Setting range by operation mode
Operation mode
(2) Solid state input 2 input signal MODE F
ㄹ 1 ●Setting range: F1 to F16 FS-H 99999
High-limit value of PV
Operation mode Setting range
transmission output
Input frequency: Max. 5kHz (ON/OFF pulse width: min. 100㎲ of each) 1 1 F1, F2, F7, F9, F11,
0 to 99999
※For F7, F8, F9, F10 operation mode, max. 1kHz (ON/OFF pulse width: min. 500㎲ of each) ●Setting range F12, F13, F16
(3) Contact input Parameter Input sensor type F3, F4, F5, F6 0 to set time range
① Input frequency: Max. 45Hz (when each ON/OFF pulse width is over 11ms) IN-A NPnhF Sensor type of input A NPnhF NPN solid state input 1 Low-limit value of PV F8, F10, F14, F15 `9999 to 99999
② Contact specifications: 12VDC, stable switching of load current as small as 5mA NPnmF NPN solid state input 2 FS-L 00000 transmission output (the setting range varies depending
2. Input type [IN-A, IN-B] NPnlF NPN contact input on the decimal point setting.)
PNphF PNP solid state input 1 ※Only appears in PV transmission
MP5 allows selection between NPN input (solid state/contact) or PNP input (solid state/contact).
IN-B output models.
(1) NPN input type (2) PNP input type NPnhF Sensor type of input B PNpmF PNP solid state input 2 Current output
②NPN voltage ③NPN open collector ②PNP voltage ③PNP open collector PNplF PNP contact input MA 4-20 specifications
①Contact
output type sensor output type sensor MP5
①Contact
output type sensor output type sensor MP5
2 3 2 3 Output mode ●Setting range: 4-20, 0-20
+12V +12V ●Setting range
Communication address
OUT-T
Sensor circuit

Sensor circuit

Sensor circuit

Sensor circuit

Sensor circuit

Sensor circuit
3.9kΩ
MP5W 4
STARD Parameter Output mode Parameter Output mode ADDR 01 ●Setting range: 01 to 99
IN STARD S (Standard) OUT-B B (Block)
IN OUT-H H (High) OUT-I I (One-shot)
0V Communication speed
(COM) 0V
(COM)
3.9kΩ OUT-L L (Low) OUT-F F (Deflection) B
ㅠ ㅜ PS 9600 ●Setting range: 9600, 19200,
※Does not 38400, 2400, 4800 (bps)
Output hysteresis
1 HYS 0001 ●Setting range: 0000 to 9999 appear in
Output Specifications (the setting range varies depending indicator Communication parity bit
1. Relay output 2. Transistor output on the decimal point setting.) models. P
ㅜ RTY NONE ●Setting range: NONE (none),
※Only appears
① Output: C omparative or alarm output ① Output: C omparative output or alarm output EVEN (even), ODD (odd)
in RS485
(refer to " Output mode") (refer to " Output mode") fDEFY LL, L comparative output limit function
② Output type: Relay
GUARD Communication stop bit
comm. output
② Output type: NPN/PNP open collector models.
③ Contact capacity: 250VAC 3A resistive load ③ Rated load voltage: 30VDC STP 2 ●Setting range: 1, 2
④ Life cycle: [Mechanical] min. 10,000,000 operations ④ Max. load current: 30mA STArT 9(9 Communication response wait time
(switching frequency 180 operations/min) Start compensation timer function & ●Setting range by communication speed
[Electrical] min. 100,000 operations compensation time
(3A 250VAC, 30VDC resistive load) 2 3 RSwT 20 Communication speed Setting range
●Setting range: )0 to 9(9 (sec) (unit: bps) (unit: ms)
(switching frequency 20 operations/min) 1: Display component 2400 16 to 99
3. BCD dynamic output(negative logic) Displays current value in RUN mode. AUToA 999(9 Auto-zero time for input A
4800 8 to 99
① Output: present value Alternately displays setting parameters and corresponding value in SETTING mode. ●Setting range: 9600, 19200, 38400 5 to 99
② Output signal: BCD data (A, B, C, D, DOT) ← A: lowest bit, DOT: highest bit 2:  key )1 to 999(9 (sec) Communication write
Digit data (D0, D1, D2, D3, D4) ← D0: lowest digit, D4: highest digit In RUN mode, press the key once to check max./min. value. COmW D
ㅇ ISA ●Setting range: ENA (enable), DISA (disable)
③ Output type: NPN open collector In RUN mode, hold the key for over 2 sec to enter parameter groups. AUToB 999(9 Auto-zero time for input B
Lock Parameter Function
④ Rated load voltage: 30VDC 3:  , , key ●Setting range: OFF Unlock
⑤ Max. load current: 30mA
⑥ Dynamic COM cycle (T) = 40ms
Select parameter groups, and select or setting values in the corresponding parameters.
Memory retention
LOC OFF LOc0 Lock all
LOc1 Parameter 1/2/3 lock
E.g.) To display value = 125.89 by BCD dynamic output 4: Output status indicator MEMO OFF ●Setting range: ㅒㅜON, OFF LOc2 Parameter 2/3 lock
4 0
10 digit 10 digit
LOc3 Parameter 3 lock
PV Display value 1 2 5. 8 9 Parameter Groups ( : parameter display,
A ● Parameter 2 Group Operation Mode By Parameter Groups X: no parameter display)
Parameter 0 group 2 sec Operation
BCD
B
(Max./Min. monitoring value)
RUN HOLD/RESET
※ RUN mode PARa1 PARa2 PARa3 Parameter
mode F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 F12 F13 F14 F15 F16
Data C mode 3 sec PStHH
※1

※2
D
※Operation mode F1 to F12: Flashes PSt H
Data bank Appears in all operation modes (F1 to F16).
display value HOLD ※2

0 group
※1
alternately PSt L
Operation mode F13 to F16: ●Setting range: 1, 2
DOT pBANK 1 ※Only appears in MP5W. PSt LL
※1

2 sec 3 sec display value RESET


hPEK
D0
0.1ms
Parameter 1/2/3 group lPEK
Decimal point location of display value
D1 DOT 00000 ●Setting range: 00000, 000)0, 00)00, 0)000, )0000 MODE
※Press the , , Appears in all operation mode (F1 to F16).
Digit D2 keys to select or set the desired value. IN-A
※Press the key once after changing the setting value, to save the setting value and move to the ●Setting range ※3
D3 IN-B
next parameter. tSEC (sec) tMIN (min) ※2 ※4
※Hold the key for 1.5 sec at any parameters to return to the select parameter group mode. tUNT tSEC 99(99 99(99 999.99s 99(99 999.99m
OUT-T

1 group
D4 ※2
5ms 8ms ※Hold the key for 3 sec to save the setting value and return to RUN mode after changing the HYS
40ms 999(9 9999.9s 999(9 9999.9m
※2
setting value. tMIN 99(99 9(5(9 99m 59.9s 9(5(9 99h 59.9m GVARD
4. PV transmission output ※If there is no key input for 60 sec while setting the parameters, the new settings are ignored, and the (5(59 9h 59m 59s 99(59 999h 59m
Time unit and range AVToA
①Application: transmit measured value unit will return to RUN mode with previous settings. 99999 99999s 99999 99999m
②Function: transmit measured value within setting range of high-limit output [FS-H] to low-limit ※The dotted line parameters may not appear depending on output specifications or other parameter
AVToB
output [FS-L] after conversion into DC4-20mA or DC0-20mA current. settings. Please refer to ' Operation mode by parameter group'. MEMO
③Output range of high/low-limit ※1: Each parameter and corresponding setting value will flash alternately every 0.5 sec. PStHH 99999 HH comparative value pBANK ※Only appears in MP5W. Appears in all operation modes (F1 to F16).
·High-limit [FS-H] range: From min. value to max. value within measurement range ※Does not appear ※The parameters are identical to
in F output mode
DOT
·Low-limit [FS-L] range: From min. value to max. value within measurement range ([FS-H]≥[FS-L]+1) ● Parameter 0 Group [PStHH], [PSt H], [PSt L], [PStLL]
of parameter 0 group and the tUNT
(1) DC4-20mA transmission output ※1
①Transmit measured value within setting range of high- RUN mode PSt H 99999 H comparative value
setting values will be linked. PStHH
※2
limit output [FS-H] to low-limit output [FS-L] after Display ●Setting range by operation mode PSt H
value Operation mode Setting range ※2 Appears in all operation modes (F1 to F16).
conversion into DC4-20mA current. FS-H PStLL

2 group
F1, F2, F7, F9, F11,
②Resistive load: Max. 500Ω F12, F13, F16
0 to 99999 PSt L
※1

③Resolution: 8000 divisions FS-L ※The parameters are identical


PSt L 00000 L comparative value
F3, F4, F5, F6 0 to set time range PScaH
Set [FS-L] and [FS-H] and HH comparative value
the output is DC4-20mA.
PStHH 99999 ※Does not appear
to [PStHH], [PSt H], [PSt L], F8, F10, F14, F15 `9999 to 99999
PScaY
Flashes [PStLL] of parameter 2 group LL comparative value (the setting range varies depending
20mA alternately
※1 in F output mode and the setting values will be on the decimal point setting.) PScbH
※Does not appear
If the setting width between [FS-L] and linked. PStLL 00000 in F output mode ※Only appears in comparative PScbY
value setting models. ※5
[FS-H] is lower than 8000 divisions, the 4mA DISpT
●Setting range by operation mode
resolution is also reduced. PSt H H comparative value
(2) DC0-20mA transmission output
99999 Operation mode Setting range Prescale mantissa (X) of input A
COUnB
①Transmit measured value within setting range of high-limit
Display F1, F2, F7, F9, F11,
0 to 99999 PScaH ^0000 ●Setting range: )0001 to (9999 FS-H
※Only appears in PV transmission output models.
value F12, F13, F16
output [FS-H] to low-limit output [FS-L] after conversion FS-H FS-L Appears in operation modes (F1 to F16).
0 to setting time
F3, F4, F5, F6 ㅡMA
into DC0-20mA current. range
FS-L Prescale exponent (y) of input A
②Resistive load: Max. 500Ω PSt L 00000 L comparative value F8, F10, F14, F15 `9999 to 99999 ADDR
③Resolution: 10,000 divisions Set [FS-L] and [FS-H] and (the setting range varies depending
PScaY 10 01 ●Setting range: 10 - 9 (10-9) to 10 09 (109)

3 group
the output is DC0-20mA. on the decimal point setting.)
BPS
20mA ※Only appears in comparative PRTY ※Only appears in RS485 comm. output models.
If the setting width between [FS-L] and value setting models. Prescale mantissa (X) of input B STP Appears in all operation modes (F1 to F16).
[FS-H] is lower than 10,000 divisions, LL comparative value PScbH ^0000 ●Setting range: )0001 to (9999 REwT
0mA PStLL 00000
the resolution is also reduced. ※Does not appear
COmW
5. RS485 communication output in F output mode,
Prescale exponent (y) of input B LOC
Comm. protocol Modbus RTU
Comm. speed
2400, 4800, 9600 (default), PScbY 10 01 ●Setting range: 10 - 9 (10-9) to 10 09 (109) ※1: Only appears in only for quintuple output models.
Connection method RS485 19200, 38400 bps ※2: Only appears in triple, quintuple output models.
Max. monitoring
Application standard Compliance with EIA RS485 Comm. response time 5 to 99ms (default: 20ms) hPEK 99999 value Display cycle of measured value
※3: The settings for IN-B and IN-A are applied.
※4: ( ) F output mode[OUT-F] cannot be set.
Max. connections 31 units (address: 1 to 99) Start bit 1-bit (fixed) ●Setting range: )05, )5, 1, 2, 4, 8 (sec)
※Resetting monitoring value DISpT )05 ※Setting range in operation mode F2, F16
※5: ( ) setting range: OFF, )05, )5, 1, 2, 4, 8
Synchronization method Asynchronous Data bit 8-bit (fixed) : Hold the key for over 2 sec.
: OFF, )05, )5, 1, 2, 4, 8 (sec) Monitoring delay function by output mode
Comm. method Two-wire half duplex Parity bit None (default), Even, Odd (reset current value) Output mode S mode H mode L mode B mode I mode F mode
Comm. distance Max. 800m Stop bit 1-bit, 2-bit (default) Min. monitoring
lPEK `9999 value COUnB 99999
Setting value of input B Parameter STARD OVT-; OVT-L OVT-B OVT-I OVT-F
※For more information about RS485 communication output specifications, refer to ' RS485 ●Setting range: 1 to 99999 Comparative output limit
communication output'. Start compensation timer
2/4
Operation Modes [MODE] F6 Mode: Time Differential MP5
F12 Mode: Interval L (Low) Output Mode [OUT-L]
HH
B (Block) Output Mode [OUT-B]
HH

Comparative

Comparative
Displays measured time from Input A ON to Input B ON. Measures and displays the number of input A pulses from input B ON to the next ON. MP5
Select operation mode from operation mode[MODE] of parameter 1 group. H H

value

value
Time difference(T) = t(ta to tb) Interval = P × α ※P: number of input A pulses, α: prescale value L L
MP5 has 16 operation modes. LL LL
※t(ta to tb): measured time from input A ON to input B ON[sec]
Display value and display unit HH ※1
HH
※1

F1 Mode: Frequency/Revolutions/Speed Display value and display unit([tUNT] of parameter 2) Sensor B H ※1 H


※1
Display
Display Display unit L ※1
Output GO
Measures the frequency of input A and displays the calculated frequency, revolutions, and speed.
value
Display unit Timing chart Sensor A
value Timing chart Photoelectric
Output
※1 L ※1
※L: travel distance of conveyor belt of 1 cycle[m] LL
1) Frequency(Hz) = f × α (α= 1[sec]) Quantity Input A sensor LL ※1
α: prescale value SEC MIN Input A GO
(default) 1 2 3 4 5 1 2 3 4 1 2 3 HH output : Display value ≤ Comparative setting value HH HH output : Display value ≥ Comparative setting value HH
2) Revolutions(rpm) = f × α (α= 60[sec])

Time differential
60L 999.99s Input B Input B
For multiple objects, α = 999.99m mm H output : Display value ≤ Comparative setting value H H output : Comparative setting value HH > Display value ≥
3) Speed(m/min) = f × α (α= 60L[sec]) N (default) ta Interval ta Comparative setting value H
Hold L output : Display value ≤ Comparative setting value L
Hold cm
9999.9s 9999.9m LL output : Display value ≤ Comparative setting value LL L output : Comparative setting value LL < Display value ≤
Display value and display unit input input
Comparative setting value L
99m 59.9s 99h 59.9m t1 t2 t3 t4 t5 t6 t7 m ※GO output ON when there are no HH, H, L, LL outputs
Display α Display 5×α 4×α LL output : Display value ≤ Comparative setting value LL
Display unit MP5 9h 59m 59s 999h 59m Display t1 t2 t3 t4 t6 t7 I (One-shot) Output Mode [OUT-I]
value (prescale value) ※GO output ON when there are no HH, H, L, LL outputs
※ta: return time(over 20ms) HH
99999s 99999m

Comparative
Hz 1 ※ta: return time(over 20ms) F13 Mode: Accumulation H HH output : Display value ≥ Comparative setting value HH
Frequency

value
kHz 0.001 Encoder F7 Mode: Absolute Ratio L H output : Comparative setting value HH > Display value ≥
MP5 Measures and displays the counted value of input A pulses. LL 0.3s Comparative setting value H
rps 1 Timing chart Measures and displays relative speed, amount, speed, etc. of input B against input A in percentage(%).
Accumulation = P × α Display value and display unit L output : Comparative setting value H > Display value ≥
Revolutions HH
rpm(default) 60 Input A Absolute ratio = (Input B / Input A) × 100%
※P: number of input A pulses, Display value Display unit MP5 0.3s Comparative setting value L
H LL output : Comparative setting value L > Display value ≥
mm/sec 1,000L t1 t2 t3 t4 t5 t6 Frequency of input B[Hz] × Bα α: prescale value
Absolute ratio = × 100[%] Accumulation Quantity Output GO Comparative setting value LL
Hold Frequency of input A[Hz] × Aα 0.3s
cm/sec 100L Operation L
※No GO output ※One-shot output time is fixed at 0.3 sec.
Speed m/sec 1L Input ※Aα: prescale value of input A, Bα: prescale value of input B ①Counts the number of input A pulses 0.3s ※No hysteresis
Flow meter A Flow meter B
Timing chart LL
m/min 60L Display 1 1 1 1 1 ②Input B is an enable input signal.
Display value and display unit Input A F (Deflection) Output Mode [OVT-F]
km/hour 3.6L t1 α t2 α t3 α t5 α t6 α During ON, the quantity and display 1 2 3 4 5 6 1 2 3 4
Display
Display unit Timing chart value of input A will be held, and Input B Transmits outputs when the saved setting value exceeds H deviation or L deviation.
value MP5 Saving setting value: press the + keys to save as setting value.
Input A Liquid during OFF input A will be re- RESET
F2 Mode: Passing Speed Absolute counted. Checking setting value: press the key to check the setting value.
MP5 % fA Setting deviation: Sets H deviation [PSt H], and L deviation[PSt L] of parameter group 0,2 with the
ratio ③When RESET input is ON, the Display 0 1 2 3 4 5 6 0 1 2 3 4
Displays the passing speed between input A ON and input B ON. Input B setting value as reference. (The set deviation value is saved during Power OFF until it is re-set.)
integrated counted value will be
Passing speed(V) = f × α(α= L[m]) fB reset to "0" ※α = 1 display value Deviation setting range: 0.0001 to 99999(the setting range varies depending on the decimal point [DOT] setting.)
※f : r eciprocal of time [sec] between input A(sensor) ON and Frequency of input B[Hz] × Bα Saving setting value( + key) E.g.) Decimal point[DOT]: 0000.0,
Display = × 100[%] F14 Mode: Addition/Subtraction-Individual Input (high-limit)
input B(sensor) ON. Frequency of input A[Hz] × Aα MP5 Setting range: 0.1 to 9999.9
H deviation
L: distance between input A(sensor) and input B(sensor) [m] ※Hold: When the hold signal turns ON, the display value is maintained until the display cycle turns to Displays the counted value from added input A pulses
Sensor B Setting value ※2: When selecting initial comparative output
α: prescale value hold OFF. and subtracted input B pulses. When there are two inputs
Timing chart Sensor A simultaneously, it will not count.
(low-limit)
L deviation
limit function, it does not transmit outputs.
Display value and display unit F8 Mode: Error Ratio Photoelectric Input B ※3: The graph is assuming that there is a
Input A Addition/Subtraction(individual input) = Input A × α - Input B × β sensor ON
Display Display α Measures and displays the relative rate of input B against the reference value of input A Input A (subtraction) Power OFF saved setting value prior to the setting
Input B in percentage(%). ※α : prescale value of input A, β: prescale value of input B Saving ON value save point. The actual output
value unit (prescale value) (addition) setting value OFF
Hold ta Input B-Input A Conveyor A Display value and display unit Operation and timing chart ※2 position may be different.
mm/sec 1,000L Error ratio = × 100[%] L deviation ON
input Display value Display unit Pulse of input A is added and pulse of input B is subtracted. ※There are no HH, GO, LL outputs.
Passing speed

Input A Conveyor B output OFF


cm/sec 100L t1 t2 t3 t4 t5 t6 t7 ※3 ※The deviation can be set to "0" but the
(Frequency of input B[Hz] × Bα)- Addition/ H H deviation ON
m/sec 1 1 1 1 1 1 Input A L output OFF actual operation will be the same as "1".
1L Subtraction
(default) Display t1 α t2 α t3 α t4 α t6 α
t7 α Error ratio = (Frequency of input A[Hz] × Aα) × 100[%] Quantity
H
Frequency of input A[Hz] × Aα (individual input) Input B
m/min 60L
※ta: return time(over 20ms) ※Aα: prescale value of input A, Bα: prescale value of input B MP5
L Functions Comparative setting value
km/hour 3.6L RESET H Hysteresis [HYS] H, HH
Display value and display unit Timing chart L
Near the comparative setting value, the output Comparative setting value
Display Input A L, LL A
Display unit Display 0 1 2 32 0 1 2 3 2 1 may turn ON/OFF frequently and unstably. A
F3 Mode: Cycle value To prevent this, hysteresis value is set based
fA ※α, β=1 display value Output H, HH
Displays the measured time from input A ON to the next ON. Error ratio % on the comparative setting value.
Output L, LL
Cycle(T) = t ※t: measurement time[sec] Input B F15 Mode: Addition/Subtraction-Phase Difference Input ※A: hysteresis value
fB When input A is Low, counting is added to the low of input B. Input A ※The hysteresis value can be set to "0" but the actual operation value is "1"
Display value and display unit([tUNT] of parameter 2)
※Hold: When the hold signal turns ON, the display value is maintained until the display cycle turns to When input A is Low, counting is subtracted from the high of input B. Delay Monitoring [GUArD]
Display
MP5
Input B
Display unit Photoelectric hold OFF. Addition/Subtraction(phase difference) After supplying power, the starting current of motors and other inputs are changeable. This function
value Timing chart sensor = Detects position and speed using A and B phases of MP5 allows stable control by limiting all outputs for a certain period of time, until the target measurement
SEC MIN F9 Mode: Density encoder outputs as input. unit stabilizes. It may also control L,LL outputs until a specific output is reached.
Input A
999.99s Measures and displays the density ratio (%) of input B against the total sum of input A and input B. Comparative output limiting function [fDEFY]: Applicable in S(Standard), B(Block), F(Deflection)
999.99m t1 t2 t3 t4 t5 t6 Display value and display unit Timing chart
(default) Input B output modes only. : limits L, LL outputs before H or HH outputs.
Hold H
Cycle

9999.9s 9999.9m Density = × 100[%] Display value Display unit ※Initial L, LL ouptuts does not operate, so GO output operates.
input Input A + Input B Input A L
99m 59.9s 99h 59.9m Addition/ H
Display t1 t2 t3 t5 t6 Frequency of input B[Hz] × Bα Input B 1) During S (Standard) output mode 2) During B (Block) output mode
9h 59m 59s 999h 59m Density = × 100[%] Subtraction L
(Frequency of input A[Hz] × Aα) + (Frequency of input B[Hz] × Bα) Quantity HH HH

Comparative

Comparative
(phase difference
RESET H
99999s 99999m H H

value

value
※Aα: prescale value of input A, Bα: prescale value of input B input) L L L
LL LL
F4 Mode: Passing Time Display value and display unit Display 0 1 2 3 2 1 0 1 2 0
HH HH
Measure the time from input A ON to the next ON, and displays the passing time of the arbitrary Display Timing chart F16 Mode: Length Measurement 2
Display unit H H
distance. value Input A Flow meter A Flow meter B Measures and displays the number of pulses from input A until the value of input B reaches the setting value. Output GO Output GO
Passing time[sec]= t × α Density % fA Length measurement 2 = P × α (until the setting value of input B) L L
L[m] Input B ※P: number of input A pulses, α: prescale value LL LL
(α= ) Liquid Comparative output limit Comparative output limit
Distance advanced in 1 pulse cycle[m] fB Display value and display unit Timing chart (e.g.) setting value of input B=4
[m] MP5 function removal function removal
※t: measured time[sec], L: arbitrary distance[m] ta nce ※Hold: When the hold signal turns ON, the display value is maintained until the display cycle turns to Display value Display unit H ※After supplying power, there is no initial L, LL comparative outputs ( ).
L : Dis Input A L ※Each setting value of HH, H, LL, L is not related to their relative sizes. Hence, HH value may be lower or equal to LL value.
α: prescale value hold OFF. Length
MP5 Quantity H 1 2 1 2 3 4 1 2 3 3) During F (Deflection) output mode
Display value and display unit([tUNT] of parameter 2) F10 Mode: Error measurement 2 Input B L ※After supplying power, there is no comparative output ( ) of
Comparative output limit
Measures and displays the error of input B against reference value of input A. ※If input A and input B are ON during L deviation.

Comparative
Display H function removal
Display unit H deviation ※In F output mode, the comparative output limiting function is
Error = Input B - Input A initial power supply, it will not count RESET L

value
value Timing chart Setting value removed at the set value (standard setting)
Error = (Frequency of input B[Hz] × Bα) - (Frequency of input A[Hz] × Aα) and only count the number of rising L deviation ※H and L deviation are not related to their relative sizes.
SEC MIN Display 0 1 2 3 4 0 1 2 3 4 5 6 7 0 1 2 3 4 5
edge. (H deviation setting value > L deviation setting value,
999.99s Input A ※Aα: prescale value of input A, Bα: prescale value of input B Conveyor A ※1
0 7 H
※Display value is renewed depending Display H deviation setting value < L deviation setting value)
Passing time

999.99m Conveyor B Output


(default) t1 t2 t3 t4 t5 t6 Display value and display unit on the display cycle[DISpT]
Hold L Monitoring delay time
9999.9s 9999.9m
input Display Timing chart setting.
Display unit ※1: When the display cycle[DISpT] setting is OFF, it will maintain the quantity of input A until the Start compensation timer function[STArT]
99m 59.9s 99h 59.9m value Input A L, LL
Display t1 α t2 α t3 α t5 α t6 α value of input B reaches the setting value of input B [COUnB].
Set monitoring delay time so that there is no
comparative
9h 59m59s 999h 59m Error END User setting output during the delay time. setting value
fA
99999s 99999m
Input B MP5 Output Modes [OUT-T] No output
MP5 Series supports 6 output modes. (There is no output mode in indicator models).
Auto-zero Time Setting [AUToA, AUToB] Output
fB When there is no input signal during auto-zero setting time, the display value is automatically set to
※Hold: When the hold signal turns ON, the display value is maintained until the display cycle turns to Requirement for setting comparative value: (B output mode) LL<L<H<HH, (F output mode) L<H,
(other output modes) individual output operation 0(zero). Please set the auto-zero setting time so that it is longer than the interval of the slowest input
F5 Mode: Time Interval MP5 hold OFF. signal. If the setting time is too long and there is no input signal, the rate at which the display value
※1: hysteresis regardless of size or order of set comparative values.
Displays measured time of input A ON. F11 Mode: Length Measurement 1 falls to 0(zero) decrease, and output response rate may slow down.
Motor S (Standard) Output Mode [STARD] H (High) Output Mode [OVT-H] Data bank [pBANK] (only for MP5W)
Time interval(T) = t ※t: measured time of input A ON [sec] Measure and display the number of input A pulses during input B ON.
Stamp HH
Comparative

Comparative
Input A HH Comparative setting value and prescale value are saved as two types(data bank 1, 2) and can be
Display value and display unit([tUNT] of parameter 2) Length measurement = P × α Input B H H
selected for use by opening or shorting of terminals.
value

value
L L
Display Timing chart ※P: number of input A pulses, α: prescale value Photoelectric LL LL Terminal 3, 5 open: use value of data bank 1 Terminal 3, 5 short: use value of data bank 2
Display unit
value
Input A Display value and display unit sensor HH ※1
HH
※1 Prescale [PSc .H, PSc .Y]
SEC MIN MP5 ※1 Displays values in required units or specific multiples by counting the number of input pulses, then
Display Timing chart H
※1 H
999.99s t1 ta t2 ta t3 Display unit Output GO Output L ※1 multiplying the number of pulses or the length of pulses by variables(X×10y).
999.99m Hold value Input A
Time interval

(default) 1 2 3 4 5 6 1 2 1 2 3 4 L ※1 LL ※1 Number of = f×α ※f: The number of input pulses


input Quantity ※1 GO revolutions(rpm) = f×60×(1 / N)
Input B LL per second[Hz],
measurement

9999.9s 9999.9m (default) = f×60×(1 / 4)


Display t1 t2 t3 tb HH output : Display value ≥ Comparative setting value HH HH output : Display value ≥ Comparative setting value HH α: Prescale value
Length

99m 59.9s 99h 59.9m mm ta = f×60×0.25 N: The number of pulses


Hold H output : Display value ≥ Comparative setting value H H output : Display value ≥ Comparative setting value H MP5
9h 59m 59s 999h 59m ※ta: return time(over 20ms) input L output : Display value ≤ Comparative setting value L L output : Display value ≥ Comparative setting value L = f×15 per revolution
cm Setting prescale value(α=15)
99999s 99999m LL output : Display value ≤ Comparative setting value LL LL output : Display value ≥ Comparative setting value LL
Display 6 α 2 α 4 α Set mantissa(X) as 1.5000, and exponent(Y) as 1 for prescale value(α)=15.
m ※GO output ON when there are no HH, H, L, LL outputs ※GO output ON when there are no HH, H, L, LL outputs
※ta, tb: return time(over 20ms) The same display value can be obtained with α value set as X=0.1500, and Y=2. 3/4
RS485 Communication Output 5-5. Preset Multiple Registers (Func 10 H)
1) Query (Master)
6-4. R
 ead Holding Registers(Func 03) / Preset Single Register(Func 06)/
Preset Multiple Registers(Func 16)
Applicable for models with RS485 communication output through sub output (MP5Y- 5, MP5W- Error Check 6-4-1. Comparative value settings and peak value check group 6-4-4. Parameter 3 Group
8/9). Please refer to ' Ordering information'. Slave Function Starting Address No. of Register Byte Data Data
(CRC 16) Factory Factory
Address (command) Count No.(Address) Func R/W Parameter Description Setting range No.(Address) Func R/W Parameter Description Setting range
1. Communication Specifications High Low High Low High Low High Low Low High default default
Comm. protocol Modbus RTU 2400, 4800, 9600 (default), 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 400001(0000) HH comparative High-limit value of
Comm. speed 03/16 R/W PStHH Preset HH 0 to 99999 99999 400151(0096) Full scale
Connection method RS485 19200, 38400 bps CRC16 400002(0001) value 03/16 R/W FS-H PV transmission 99999
400152(0096) High output Setting range varies by
Application standard Compliance with EIA RS485 Comm. response time 5 to 99ms (default: 20ms) 2) Response (Slave) 400003(0002) H comparative
03/16 R/W PSt H Preset H 0 to 99999 99999 model and operation
Max. connections 31 units (address: 1 to 99) Start bit 1-bit (fixed) Function Starting Address No. of Register Error Check(CRC 16) 400004(0003) value 400153(0096) Low-limit value of mode
※1
Slave Address Full scale
(command) High Low High Low Low High 400005(0004) 03/16 R/W FS-L PV transmission 0
Synchronization method Asynchronous Data bit 8-bit (fixed) L comparative ※1
400154(0096) Low
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 03/16 R/W PSt L Preset L 0 to 99999 00000 output
Comm. method Two-wire half duplex Parity bit None (default), Even, Odd 400006(0005) value
Transmission 0: 4-20(mA)
Comm. distance Max. 800m Stop bit 1-bit, 2-bit (default) CRC16 400007(0006) LL comparative ※1 400155(0096) 03/06/16 R/W MA mA 0
03/16 R/W PStLL Preset LL 0 to 99999 00000 output spec. 1: 0-20(mA)
5-6. Exception Response-Error Code(exception processing) 400008(0007) value
2. System Configuration Communication
Terminating resistance Function Error Check(CRC 16) 400009(0008) High peak value ※2 400156(0096) 03/06/16 R/W ADDR Unit address 1 to 99 1
RS232C/ 03/16 R/W hPEK High peak 99999 - address
USB/Wi-Fi RS485 (100 to 120Ω) Slave Address (command) Exception code 400010(0009) of measured value
RS485 +80H Low High 0: 2400
400011(000A) Low peak value ※2
1: 4800
DEVICE 1Byte 1Byte 1Byte 1Byte 1Byte 03/16 R/W lPEK Low peak -19999 - Communication
#31 400012(000B) of measured value 400157(0096) 03/06/16 R/W BPS Bits per sec 2: 9600 2
400013 to Speed
Comm. converter CRC16
03/06/16 R/W Reserved
3: 19200
A (+) B (-) A (+) B (-) A (+) B (-)  hen a communication error occurs, the highest bit from the received command (function) is set (1),
W 400050 4: 38400
B (-)
Computer a response command is sent, and the corresponding exception code is transmitted. ※1: In operation modes F8, F10, F14, F15,the setting range is -19999 to 99999 0: NONE
RS485 RS485 RS485
(1) ILLEGAL FUNCTION(Exception Code: 01 H) ※2: Max./Min. measurement value Communication
ON OFF DEVICE DEVICE DEVICE 400158(0096) 03/06/16 R/W PRTY Parity bit 1: EVEN 0
#1 #2 #30 : Unsupported command 6-4-2. Parameter 1 Group parity bit
2: ODD
A (+) (2) ILLEGAL DATA ADDRESS(Exception Code: 02 H) Factory
: The requested start address does not not match the transmission address of the device. No.(Address) Func R/W Parameter Description Setting range Communication 0: 1
default 400159(0096) 03/06/16 R/W STP Stop bit 1
※It is recommended to use Autonics communication converter; SCM-WF48 (Wi-Fi to RS485·USB (3) ILLEGAL DATA VALUE(Exception Code: 03 H) stop bit 1: 2
wireless communication converter, sold separately), SCM-US48I (USB to RS485 converter, sold 0: F1 to Communication
: The number of requested data does not match the transmission number of the device. Input operation Response
separately), SCM-38I (RS232C to RS485 converter, sold separately). 400051(0032) 03/06/16 R/W MODE Mode 1: F2 14: F15 0 400160(0096) 03/06/16 R/W RSwT response 5 to 99(ms) 20
(4) SLAVE DEVICE FAILURE(Exception Code: 04 H) mode waiting time
Please use twisted pair wire, which is suitable for RS485 communication, for SCM-WF48, 2: F3 15: F16 waiting time
: The requested command cannot be processed properly.(CRC)
SCM-US48I and SCM-38I. 0: NPnhF Communication
3. Communication Control Sequence 6. Address Mapping Table 400052(0033) 03/06/16 R/W IN-A Input A 1: NPnmF Communication 0: DISA
400161(0096) 03/06/16 R/W COmW write 0
1. Communication equence follows Modbus RTU protocol. 2: NPnlF write 1: ENA
6-1. Read Coil Status(Func 01) / Force Single Coil(Func 05) Sensor type 0 enable/disable
2. Communication with the host system can be established after 1 sec (1,000ms) of supplying power. 3: PNphF
3. The initial transmission authority is held by the host device (PC). When the host device transmits a No.(Address) Func R/W Parameter Description Setting range Note 0: OFF
400053(0034) 03/06/16 R/W IN-B Input B 4: PNpmF
request, the MP5W/Y Series sends a response. 000001(0000) 01 R/W HH HH comparative output 0: OFF / 1: ON 1: LOc0
5: PNplF
000002(0001) 01 R/W H H comparative output 0: OFF / 1: ON 400162(0096) 03/06/16 R/W LOC Lock Lock 2: LOc1 0
Comparative 0: STARD
Read command

Read command

000003(0002) 01 R/W GO 0: OFF / 1: ON 3: LOc2


No. of data

No. of data

GO comparative output
output LED 1: OUT-H
Address

Address

Address

Address
CRC16

CRC16

000004(0003) 01 R/W L L comparative output 0: OFF / 1: ON 4: LOc3


OutpQut 2: OUT-L
Host 000005(0004) 01 R/W LL LL comparative output 0: OFF / 1: ON 400054(0035) 03/06/16 R/W OUT-T Output mode 0 400163 to
type 3: OUT-B 03/06/16 R/W Reserved
system 000006(0005) 01 R/W 0: OFF / 1: ON 400200
4: OUT-I
000007(0006) 01 R/W 0: OFF / 1: ON
5: OUT-F
※A: a
 fter 1 sec of supplying 000008 to 000050 01 R/W 0: OFF / 1: ON
Response command

※1: High-limit/low-limit setting value of PV transmission output.


No. of data

400055(0036) 03/06/16 R/W HYS Hysteresis Hysteresis value 1 to 9999 1


Address

power
CRC16

6-2. Read Input Status(Func 02) (varies by model and operation mode)
B: 3
 8400bps: approx. 1.75ms Output limit 0: fDEFY
MP5W/Y 400056(0037) 03/06/16 R/W GUArD Output limit 0
19200bps: approx. 2ms No.(Address) Func R/W Parameter Description Setting range Note function 1: STArT Series Operation mode Setting range
Series
A 9600bps: approx. 4ms 100001(0000) 02 R RESET(HOLD) External input RESET input status Start limit Start compensation
B C 400057(0038) 03/06/16 R/W STArT 0.0 to 99.9 0.0 F1, F2, F7, F9, F11, F12, F13, F16 0 to 99999
4800bps: approx. 8ms 100002(0001) 02 R BANK variables BANK input status value timer value
100003(0002) 02 R 0: OFF / 1: ON MP5Y
※The longer of the communication response wait time[RSwT] of 2400bps: approx.16ms 400058(0039) 03/16 R/W Auto-zero F3, F4, F5, F6 0 to set time range
100004(0003) 02 R 0: OFF / 1: ON AUToA MP5W
parameter group 3 and response time of B is applied. C: over 20ms 400059(003A) 03/16 R/W A Auto-zero
100005(0004) 02 R 0: OFF / 1: ON 0.1 to 9999.9 9999.9 F8, F10, F14, F15 -1999 to 99999
4. Cautions For Communication 400060(003B) 03/16 R/W Auto-zero time
100006(0005) 02 R 0: OFF / 1: ON AUToB
1. Twisted pair wire (AWG24) is recommended for RS485 communication. When not using twisted pair 400061(003C) 03/16 R/W B
100007(0008) 02 R 0: OFF / 1: ON
wires, please make sure that A (+) and B (-) cable lengths are equal. 0: OFF
2. After connecting the communication cable, terminating resisters (100 to 120Ω) must be attached at
100008(0007)
100009(0008)
02
02
R
R
0: OFF / 1: ON
0: OFF / 1: ON
400062(003D) 03/06/16 R/W MEMO Memory Memory retention
1: ON
0 Comprehensive Device Management Program [DAQMaster]
both ends. 100010(0009) 02 R 0: OFF / 1: ON 400063 to
03/06/16 R/W Reserved DAQMaster is a comprehensive device management software for setting parameters and monitoring
5. Communication Command And Block Definition 100011(000A) 02 R 0: OFF / 1: ON 400100 processes. DAQMaster can be downloaded from our website at www.autonics.com.
5-1. Read Coil Status (Func 01 H), Read Input Status (Func 02 H) 100012 to 100050 02 R 0: OFF / 1: ON 6-4-3. Parameter 2 Group
1) Query (Master) Item Minimum specifications
6-3. Read Input Registers(Func 04) Factory
Function Starting Address No. of Points(no. of data) Error Check(CRC 16) No.(Address) Func R/W Parameter Description Setting range
Slave Address No.(Address) Func R/W Parameter Description Factory default Note default System IBM PC compatible computer with Pentium Ⅲ or above
(command) High Low High Low Low High
300001 to 300100 04 R Reserved 0: 1 Operations Windows 98/NT/XP/Vista/7/8/10
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 400101(0064) 03/06/16 R/W pBANK Data bank Data bank 0
300101(0064) 04 R Product number H 0 Dedicated 1: 2
model 0: 00000 Memory 256MB+
CRC16 300102(0065) 04 R Product number L 0 number
2) Response (Slave) 1: 000)0 Hard disk 1GB+ of available hard disk space
300103(0066) 04 R Hardware version 1 Decimal
Error Check(CRC 16) 400102(0065) 03/06/16 R/W DOT Dot 2: 00)00 0 VGA Resolution: 1024×768 or higher
Slave Address
Function Byte Count
Data(low) Data Data(high) 300104(0067) 04 R Software version 1 point
(command) (no. of data byte) Low High
3: 0)000
300105(0068) 04 R Model 1 "MP" Others RS232C serial port (9-pin), USB port
4: )0000
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 300106(0069) 04 R Model 2 "5 "
300107(006A) 04 R Model 3 "- " 0: tSEC
MP5Y- 5, 400103(0066) 03/06/16 R/W tUNT Time unit Time unit 0
CRC16 1: tMIN
5-2. Read Holding Registers(Func 03 H), Read Input Registers (Func 04 H)
300108(006B)
300109(006C)
04
04
R
R
Model 4
Model 5
" "
" "
MP5W- 8
(※MP5W- 0: 99(99 999.99s Cautions during Use
1) Query (Master) 9 displayed 1: 999(9 9999.9s
300110(006D) 04 R Model 6 " " 1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
Function Starting Address No. of Points(no. of data) Error Check(CRC 16) 300111(006E) 04 R Model 7 " " as MP5W- 2: 9(5(9 99m 59.9s 2. 24VAC, 24-48VDC power supply should be insulated and limited voltage/current or Class 2, SELV
Slave Address
(command) High Low High Low Low High 300112(006F) 04 R Model 8 " " 8) 3: (5(59 9h 59m 59s power supply device.
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 300113(0070) 04 R Model 9 " " 4: 99999 99999s 3. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting
400104(0067) 03/06/16 R/W tSEC Time sec Time range 0
300114(0071) 04 R Model 10 " " 5: 99(99 999.99m the power.
CRC16 6: 999(9 9999.9m
300115(0072) 04 R Reserved 4. Keep away from high voltage lines or power lines to prevent inductive noise.
2) Response (Slave) 7: 9(5(9 99h 59.9m
300116(0073) 04 R Reserved In case installing power line and input signal line closely, use line filter or varistor at power line and
Function Byte Count Data Data Data Error Check(CRC 16) 300117(0074) 04 R Reserved 8: 99(59 999h 59m shielded wire at input signal line.
Slave Address
(command) (no. of data byte) High Low High Low High Low Low High 300118(0075) 04 R Coil status start address 0000 9: 99999 99999m Do not use near the equipment which generates strong magnetic force or high frequency noise.
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 300119(0076) 04 R Coil status quantity 0 400105(0068) 03/16 R/W HH comparative 5. This unit may be used in the following environments.
PStHH Preset HH 0 to 99999 99999
300120(0077) 04 R Input status start address 0000 400106(0069) 03/16 R/W value ①Indoors (in the environment condition rated in 'Specifications')
CRC16
300121(0078) 04 R Input status quantity 0 400107(006A) 03/16 R/W H comparative ②Altitude max. 2,000m
5-3. Force Single Coil (Func 05 H) PSt H Preset H 0 to 99999 99999
300122(0079) 04 R Holding register start address 0000
400108(006B) 03/16 R/W value ③Pollution degree 2
1) Query (Master) 300123(007A) 04 R Holding register quantity 0 ④Installation category II
Function Coil Address Force Data Error Check(CRC 16) 300124(007B) 04 R Input register start address 0000
400109(006C) 03/16 R/W L comparative ※1
Slave Address PSt L Preset L 0 to 99999 0
(command) High Low High Low Low High 400110(006D) 03/16 R/W value
300125(007C) 04 R Input register quantity 0
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 300126 to 300200 04 R Reserved 400111(006E) 03/16 R/W
PStLL Preset LL
LL comparative
0 to 99999
※1
0
Major Products
Factory 400112(006F) 03/16 R/W value
CRC16 No.(Address) Func R/W Parameter Description Setting range Photoelectric Sensors Temperature Controllers
default 400113(0070) 03/16 R/W Prescale A Prescale A
2) Response (Slave) PScaH 0.0000 to 9.9999 6.0000 Fiber Optic Sensors Temperature/Humidity Transducers
HH HH LED Display 0: OFF 1: ON 0-bit Mantissa mantissa
Front Display

Coil Address Force Data Error Check(CRC 16) 400114(0071) 03/16 R/W Door Sensors SSRs/Power Controllers
Slave Address Function H H LED Display 0: OFF 1: ON 1-bit
(address) (command) High Low High Low Low High 301001(03E8) 04 R GO GO LED Display 0: OFF 1: ON 2-bit Prescale A Prescale A 00 to 09: +(0 to 9) Door Side Sensors Counters
400115(0072) 03/06/16 R/W PScaY 01
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte L L LED Display 0: OFF 1: ON 3-bit Exponent exponent 10 to 19: -(0 to 9) Area Sensors Timers
LED

LL LL LED Display 0: OFF 1: ON 4-bit 400116(0073) 03/16 R/W Prescale B Prescale Proximity Sensors Panel Meters
CRC16 301002(03E9) PScbH 0.0000 to 9.9999 6.0000
04 R PV Measurement value -19999 to 99999 400117(0074) 03/16 R/W Mantissa B mantissa Pressure Sensors Tachometer/Pulse (Rate) Meters
5-4. Preset Single Register (Func 06 H) 301003(03EA) Prescale B Prescale 00 to 09: +(0 to 9) Rotary Encoders Display Units
1) Query (Master) 0: 00000 3: 0)000 400118(0075) 03/06/16 R/W PScbY 01
Exponent B exponent 10 to 19: -(0 to 9) Connectors/Sockets Sensor Controllers
Function Register Address Preset Data Error Check(CRC 16) 301004(03EB) 04 R DOT 1: 000)0 4: )0000 Switching Mode Power Supplies http://www.autonics.com
Slave Address 2: 00)00 0: OFF 4: 2
(command) High Low High Low Low High Control Switches/Lamps/Buzzers
0: 999.99s 5: 999.99m Display Display 1: )05 5: 4 HEADQUARTERS:
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 400119(0076) 03/06/16 R/W DISpT 1 I/O Terminal Blocks & Cables
1: 9999.9s 6: 9999.9m time cycle 2: )5 6: 8 18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
CRC16 301005(03EC) 04 R UNIT 2: 99m 59.9s 7: 99h 59.9m 3: 1 Stepper Motors/Drivers/Motion Controllers South Korea, 48002
3: 9h 59m 59s 8: 999h 59m Graphic/Logic Panels TEL: 82-51-519-3232
2) Response (Slave) 400120(0077) 03/16 R/W INB Operation
4: 99999s 9: 99999m COUnB Setting mode 1 to 99999 99999 Field Network Devices E-mail: sales@autonics.com
Function Register Address Preset Data Error Check(CRC 16)
Slave Address 0: F1 to 400121(0078) 03/16 R/W value F16 INB Laser Marking System (Fiber, Co₂, Nd: YAG)
(command) High Low High Low Low High 301006(03ED) 04 R MODE Operation mode 1: F2 14: F15 Laser Welding/Cutting System DRW160458AD
2: F3 15: F16 400122 to
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 03/06/16 R/W Reserved
301007(03EE) 04 R 400150
CRC16 ※1: In operation modes F8, F10, F14, F15, the setting range is -19999 to 99999 4/4