Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

scitation.

org/books

CHAPTER

1 DISTRIBUTION
NETWORK TYPES AND
CONFIGURATIONS

1.1 POWER SYSTEM STRUCTURE

The main components of an electric power system include generation, transmission, and distribution
networks. Distribution networks and power generation stations are connected via transmission lines.
Usually, transmission lines transmit a high amount of power through high-voltage links between main
load centers. A brief description of each system is given below (Mariam et al., 2013).

1.1.1 Large generation centers

12 June 2024 18:55:55


A high amount of electric energy is generated using bulk generation units clustered in remote areas
that are away from final consumption points.

Traditionally, various technologies have been used to generate bulk electric energy, such as nuclear,
natural gas, coal, hydro, etc. The existing power systems were owned by one company. However, due
to lower costs and the economies of scale, they were allowed to build such bulk power plants large,
and some of them are still profitable.

1.1.2 Transmission network


Transmission network includes substations, lines, and equipment to connect large power plants to load
centers where the consumption of power is mostly performed in cities and industrial areas. Transmission
lines in transmission networks operate at high-voltage levels (above 220 kV) that can cover long distances
and transport large quantities of energy; therefore, these lines operate at high-voltage levels.

1.1.3 Subtransmission network


A subtransmission network is considered as an intermediate link between distribution and transmission
networks. Subtransmission network lines cover shorter distances compared to those of the transmission
networks and that is why they operate at a lower level, i.e., 45, 66, and 132 kV.

Voltage reduction is needed because of the voltage level differences in transmission network. Bulk load
demands, such as big industries, can be directly connected to the subtransmission network.

https://doi.org/10.1063/9780735422339_001 1-1
Future Distribution Networks: Planning, Operation, and Control, Geev Mokryani
© 2022 AIP Publishing, published by AIP Publishing
Principles

1.1.4 Primary distribution network


The main part of the primary distribution network is the distribution substation that receives the
energy delivered by the transmission and subtransmission networks and performs another voltage
reduction. From medium voltage distribution lines, e.g., 11 and 25 kV, or distribution substation, the
energy will be taken one step closer to end users; thus, bulk load demands can be connected to primary
distribution networks.

1.1.5 Secondary distribution system (distribution substation)


Secondary distribution network includes medium voltage/low voltage (MV/LV) step-down
transformers and LV lines, for example, 230 and 400 V, which deliver the power generated to LV
commercial and residential consumers.

1.2 POWER SYSTEM STRUCTURE IN THE UK

12 June 2024 18:55:55


The UK’s power system structure is shown in Fig. 1.1. Centralized large-scale power plants generate
electric power that is connected to transmission networks at 400 and 275 kV in England and Wales
and at 400, 275, and 132 kV in Scotland. The generated electric power is then transmitted to a
distribution network at the grid supply point (GSP), which transforms the voltage to 132 kV from
275 and 400 kV. In England and Wales, distribution networks operate at 132 kV and in Scotland
at 33 kV and deliver the generated power to lower voltage consumers. At bulk supply points
(BSPs), voltage is transformed from 132 to 33 kV and at a primary substation from 33 kV to 11
and 6.6 kV. The generated power is then transformed through distribution substations into the LV
levels needed to supply single-phase and three-phase consumers at 230 and 400 V, respectively.
Bulk industrial and commercial users can be connected at high-voltage (HV) levels (i.e., 6.6 and
11 kV) and at extra high-voltage (EHV) levels (i.e., 132 and 33 kV) (Siemens Power Distribution
& Control, Technical, 2007–2008).

End users are connected to the substations via overhead lines and underground cables. In urban areas
with high load density, underground cables are used for feeders while in rural areas overhead lines are
used. Several switching components are required to be installed in distribution feeders to enhance the
supply security through (a) quick faults isolation, (b) the number of disconnected users’ reduction,
and (c) the reduction of interruption duration.

Switches are used to interrupt the load current and reconfigure power flow in the network. However,
the fault current can be interrupted by the breakers, and in order to detect faults and trigger breakers
to break fault current, breakers can be combined with protection relays.

1-2 Future Distribution Networks


scitation.org/books

Generation

Transmission networks 400 kV


275 kV
400/132 kV
GSP
275/132 kV

Regional distribution network Large


industrial

BSP 132/33 kV

33/11 kV
Primary substations
33/6.6 kV

Commercial
MV networks
industrial

12 June 2024 18:55:55


Distribution substations 11/0.4 kV
6.6/0.4 kV

LV networks

End users (residential, small


commercial)

FIG. 1.1
Distribution system structure in UK.

1.3 DISTRIBUTION NETWORK CONFIGURATIONS

1.3.1 Radial network structure


The most commonly used distribution network is the radial configuration as there are no closed
loops (Mehta and Mehta, 2005; Sortomme et al., 2010; and Park et al., 2013). This is the simplest
and cheapest distribution network topology; however, if a line is disconnected for any reason, all
downstream lines cannot be supplied. The radial configuration comprises generators at the starting

Distribution Network Types and Configurations 1-3


Principles

19 20 21 22

26 27 28 29 30 31 32 33

Source

1 23 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

23 24 25

FIG. 1.2
33-bus radial distribution network (Taher and Afsari, 2012).

12 June 2024 18:55:55


point connected to the load center via distribution transformer. A sample radial distribution network
is shown in Fig. 1.2 (Taher and Afsari, 2012).

This configuration has a simple circuit protection scheme in terms of design and coordination and it
is simple to find the rating requirement of the system (Bayindir et al., 2014).

Another benefit of this configuration is voltage compensation techniques, such as reactive power
compensator, that can be simply implemented.

Radial configuration is well known for its simple structure and low initial cost which is useful for low
voltage generation. This configuration is also beneficial once the substation is located near the loads,
which will make the analysis and operation of the system easy (Willis, 2004). One of the disadvantages
of this configuration is the limited flexibility in terms of planning perspective of new generators
installation and/or additional loads that will require new cables or other components installation,
thus leading to an increase in the cost. In this configuration, users rely on a single feeder or distributor
and any fault in the network will cause an interruption in power supply to all users connected to the
feeder (Isermann, 2006).

The availability of power for each load might be lower than other configurations, which is caused
due to the complexity of the maintenance of operation. In order to address this issue, an alternative
route should be implemented which has redundant circuits, i.e., at least two circuits need to operate
simultaneously from the sources to specific loads (Prakash et al., 2016).

1-4 Future Distribution Networks


scitation.org/books

1.3.2 Ring/loop/mesh configuration


Ring or loop or mesh distribution network configuration follows a ring structure starting from a
generator via several loads and back to the generator. In other words, all buses in the loop configuration
are connected in a way that they create a closed loop structure supplying one or more distribution
transformers or load and returns to the same substation (Kaipia et al., 2006). In this configuration, a
loop must meet all requirements in terms of power and voltage drop in the case when fed from only
one end, not both. A one-line diagram of a meshed distribution network is shown in Fig. 1.3 (Mehta
and Mehta, 2005).

12 June 2024 18:55:55


Solar

Load Load

Solar

Open
Close

FIG. 1.3
One-line diagram of the meshed distribution network (Islam et al., 2017).

Distribution Network Types and Configurations 1-5


Principles

Utility can supply power to the loads in any direction in this configuration; therefore, any possible
faults can be isolated with no failure in load supply (Park et al., 2013).

A ring/loop distribution network with multiple loops/rings is called a multi-ring or multi-loop


configuration.

In the multi-loop configuration, various paths for the power transfer might be available, which will bring
substantial flexibility to the network in the case of maintenance or fault in the system. However, various
or multiple paths will make the network protection complicated, where it might not be easy to determine
the fault location and take proper action for minimum customer interruption (Sortomme et al., 2010;
Saleh, 2014; and Haj-Ahmed and Illindala, 2015). Multiple decisions could be made to isolate a fault;
however, optimal decision making will depend on the operating conditions (Plesnick et al., 2000).

Ring configuration can mainly be used in residential areas as electric current can flow in several directions,
which will lead to lower power losses and improve voltage stability (Reed et al., 2012). This configuration
is recognized to form a closed loop through joining buses to each other, which will lead to the creation
of several protection zones in the network. Ring configuration has a better performance compared with
radial configuration as it will not be affected by adding extra devices to the network, and if there is a

12 June 2024 18:55:55


fault in a feeder or it is under maintenance, the ring distributor can still be energized by other feeders
(Kishorbha and Mangroliya, 2015). This proves that users’ power supply will not be interrupted when
a feeder is not in operation. One of the main disadvantages of this configuration is the reliance on the
cables that connect the components to the network. In terms of network complexity, loop configuration is
a bit more complicated than radial configuration; however, its main disadvantage is the network hosting
capacity and the high loop cost (Willis, 2004).

1.4 LV DISTRIBUTION NETWORKS

An LV distribution network is defined as a network with a maximum limit of voltage level 1 kV


based on British standards (Engineering Technical Report 140, 2017). Moreover, around the world,
the most common voltage levels of LV networks are within the range of 120–240 V single phase (i.e.,
phase to neutral), or 208–415 V three phases and four wires (3-phase 4-wire) (Schneider Electric,
2009). Based on the international standard recommendation (IEC 60038), the voltage level of a
three-phase four-wire is 230/400 V (Schneider Electric, 2009). The last stage of a power system
is the LV network, which connects directly to the end user customers and supply loads; thus, it
has a small individual capacity with a high number of buses (Li and Crossley, 2014a). Due to the
low voltage level, LV feeders’ installation and development require lower cost in comparison with
the MV and HV distribution networks (Taylor, 1990; Li and Crossley, 2014b; and Al-Jaahfreh and
Mokryani, 2019).

1-6 Future Distribution Networks


scitation.org/books

1.4.1 LV networks layouts in different regions


Around the world, the LV network has different structures; among them, the “European” and “American”
layouts are the most widely used layouts in European countries and Central and North America (Csanyi).

1.4.1.1 European layout


“European” layout of LV networks is used by most countries in Europe. For example, the LV network
in the UK is a three-phase four-wire network supplied from a three-phase MV 230/400 V distribution
transformer, where 230/400 refer to a secondary voltage level, 400 V line to line, and 230 V line to
neutral (nominal voltage or RMS) (Schneider Electric, 2009; and Engineering Technical Report 140,
2017). Figure 1.4 shows a typical European LV distribution network in the UK.

Bulk supply point 132/33/11 kV

12 June 2024 18:55:55


Secondary substation
11/0.4 kV

3-phase 3 wire
primary
3 phase-4 wire secondary network networks 11 kV
N
L1
L2
L3

Single phase 3 phase customers


customers

380/220 V
400/230 V
415/240 V
L3 L2 L1
380/220 V

FIG. 1.4
Typical European distribution network layout (Al-Jaahfreh and Mokryani, 2019).

Distribution Network Types and Configurations 1-7


Principles

Table 1.1
Catachrestic of LV feeders in the UK (Csanyi; and Al-Jaahfreh and Mokryani, 2019).

Area Urban Rural


Feeder number per transformer
Minimum 2 1
Medium 6 3
Maximum 16 6
LV feeder length (m)
Minimum 10 100
Medium 100 250
Maximum 200 600
Total line length per transformer (m)
Minimum 150 500

12 June 2024 18:55:55


Medium 450 1600
Maximum 900 3200

In this layout, each MV/LV distribution substation can supply numerous three-phase four-wire LV
feeders. Moreover, the LV feeder can carry the power efficiently up to approximately 300 m (Taylor,
1990). In other words, at a low voltage level (400 V), each substation can supply an area corresponding
to a radius of 300 m from the substation, which makes it suitable for high load density areas (Al-Jaahfreh
and Mokryani, 2019).
The LV feeders can be underground cables or overhead lines extended from the secondary distribution
substation. Most LV feeders in the UK are designed as multi-phase feeders, which consist of four wires
(three phases and neutral) (Taylor, 1990). Table 1.1 summarizes the catachrestics of LV feeders in the
UK in both urban and rural areas (Al-Jaahfreh and Mokryani, 2019).

1.4.1.2 American LV distribution networks layout


Figure 1.5 shows the American LV distribution networks layout, which is completely different from
the European layout, where the three-phase LV network is practically non-existent (Schneider Electric,
2009; and Al-Jaahfreh and Mokryani, 2019). The MV network supplies numerous single-phase
transformers that are connected through several single-phase primary laterals (Navarro-Espinosa
et al., 2014). The secondary windings of a single-phase transformer are center-tapped to produce a
single-phase three-wire supply, 120 V (line to neutral), and 240 V (line to line).

1-8 Future Distribution Networks


scitation.org/books

13.8/2.4–4.16 kV

Single phase laterals


N
L1

2.4 kV/120–240 V
1 phase-3 wire 3 phase-4 wire
transformer MV primary

N
L2

12 June 2024 18:55:55


N
L3

N L3 L2 L1

FIG. 1.5
Typical American distribution network layout (Schneider Electric, 2009; and Al-Jaahfreh and Mokryani, 2019).

As a result, the capacity rating of the single-phase MV/LV secondary transformer is much smaller
than those in the European network and the LV feeders are minimized (Al-Jaahfreh and Mokryani,
2019). The main advantage of this layout is that the load density supplied by each substation and its
installation capital cost is lower than that in the European layout. However, the LV level (120 V) at the
secondary side of the single-phase transformers is about half of the European single-phase secondary

Distribution Network Types and Configurations 1-9


Principles

voltage (240 V), which results in some technical issues. For instance, it limited the extension of the
single-phase feeder, which only has the ability to carry the power efficiently up to 60 m from the
substation (Navarro-Espinosa et al., 2014). In addition, the power losses and voltage drop in the single-
phase LV feeder are much higher than that in the three-phase LV feeders (Li and Crossley, 2014a).

Both “European” and “American” layouts are widely adopted in many countries around the world outside
Europe, Central America, and North America (Navarro-Espinosa et al., 2014). Moreover, in some
regions, the distribution network layout is a mixture of the European and American ones (Navarro-
Espinosa et al., 2014). Table 1.2 and Figs. 1.6 and 1.7 provide a summary of the voltage level of LV

Table 1.2
The voltage level in LV distribution networks in different countries.
Country Domestic (V) Commercial (V) Industrial (V)
Australia 415/240[a]* 415/240[a], 440/250[a] 415/240[a], 440/250[a]
240[b]
Austria 230[b] 380/220[a] 380/220[a]
220[b]

12 June 2024 18:55:55


China 220[b] 380/220[a] 380/220[a]
220[b] 220[b]
Denmark 400/230[a] 400/230[a] 400/230[a]
Germany 400/230[a] 400/230[a] 400/230[a]
230[b] 230[b]
India 440/250[a] 440/250[a] 440/250[a]
230[b] 230[b] 400/230[a]
Jordan 380/220[a] 380/220[a] 400/230[a]
230[b]
UK 230 and 400/230[a] 400/230[a]
220[b] 380/220[a] 380/220[a]
USA (California) 120/240[e] 120/240[d] 120/240[d]
USA (Florida) 120/240[d] 120/240[e] 408/277[a]
120/208[a] 120/208[a]
USA (New York) 120/240[e] 120/240[e] 270/280[a]
120/208[a] 120/208[a]
Saudi Arabia 220/127[a] 220/127[a] 380/220[a]
380/220[a]
Iran 220[b] 380/220[a] 380/220[a]
South Korea 220[b] 380/220[a] 380/220[a]
*The letter refers to the associated circuit that is shown in Figs. 1.6(a) and 1.6(b) as well as Figs. 1.7(a)–1.7(d).

1-10 Future Distribution Networks


scitation.org/books

a b

FIG. 1.6
Circuit diagram of LV networks around the world (associated with European layout): (a) three-phase star four-wire earthed
neutral, (b) one-phase two-wire earthed end of phase (Schneider Electric, 2009; and Al-Jaahfreh and Mokryani, 2019).

distribution networks and their associated layout in different countries around the world (Schneider
Electric, 2009). It is seen that the European layout is the most adopted layout. However, the American
layout is adopted in North America, Latin America, and a few countries in Asia and the Middle East,
such as Saudi Arabia. Moreover, some countries mixed the European and American layouts, such as

12 June 2024 18:55:55


Iran and South Korea (Schneider Electric, 2009).

a b

c d

FIG. 1.7
Circuit diagram of LV networks around the world (associated with American layout): (a) three-phase delta three-wire, (b)
three-phase delta four-wire earthed mid point of one-phase, (c) one-phase three-wire earthed neutral mid point, (d) three-
phase open delta four-wire earthed mid point of one-phase (Schneider Electric, 2009; and Al-Jaahfreh and Mokryani, 2019).

Distribution Network Types and Configurations 1-11


Principles

1.5 LV DISTRIBUTION NETWORK TOPOLOGIES

The most common LV networks are radial networks due to the simplicity of analysis and protection
system design (Taylor, 1990). However, due to the advantages of the loop or ring or mesh configuration
to mitigate some of the technical issues, such as voltage variations and reverse power flow, the use of
mesh configuration is becoming more common (Csanyi; Navarro-Espinosa et al., 2014; Aydin et al.,
2015; and Al-Jaahfreh and Mokryani, 2019). As mentioned in Sec. 1.4, most LV networks are following
the European layout. So, the three-phase 400 LV secondary circuit is designed based on the circuit
diagram as shown in Fig. 1.6(a), which is a three-phase four-wire circuit with underground cables or
overhead lines suspended from concrete, metal, or wooden poles (Lee Willis, 2004). Due to the high
load density in urban areas, the underground cables are mainly used in LV networks (Al-Jaahfreh
and Mokryani, 2019). Therefore, interconnecting the surrounding substations to each other is called
a looped or meshed or ring network arrangement as those shown in Fig. 1.8(a) (Lee Willis, 2004; and

a b
MV/LV MV/LV
substation substation MV/LV

12 June 2024 18:55:55


substation

MV/LV
MV/LV Loads
substation
substation

c MV/LV d
substation
MV/LV MV/LV
substation Substation

Normal open point

FIG. 1.8
LV network topologies: (a) loop or ring mesh arrangements, (b) radial arrangement, (c) open loop arrangements,
(d) parallel interconnected arrangements.

1-12 Future Distribution Networks


scitation.org/books

Navarro-Espinosa and Ochoa, 2016). Also, loop or ring topology has proven its ability to improve
the system hosting capacity for Distributed Generators (DGs), such as photovoltaic systems, which
helps us to mitigate the technical issues, such as voltage rise and reverse power flow (Lee Willis, 2004).
However, in rural areas, the radial arrangement could be the most economical one with a simple
protection system, as shown in Fig. 1.8(b) (Al-Jaahfreh and Mokryani, 2019). Despite the fact that the
radial topology is widely used in 400 V three-phase four-wire LV networks, it has the lowest level of
supply security and reliability, with the absence of flexibility.

In order to increase the reliability level of two adjacent radial networks, the feeders can be
interconnected via a normally open point to the supply in order to ensure the radial operation of
each feeder, where the location of the normally open point can be moved following the occurrence
of the fault to isolate the faulty section while maintaining the supply for the rest of the faulty feeder
(Taylor, 1990). Such an arrangement is also known as ring open loop topology, as shown in Fig. 1.8(c)
(Chen et al., 2004). Moreover, a parallel interconnected configuration or spot topology can be used
by interconnecting two adjacent LV radial feeders supplied from two different substations, as shown
in Fig. 1.8(d) (EEP). Such a configuration improves the system reliability and flexibility in the case
of a maintenance event, where the loads may still be supplied by the other transformer (Schneider

12 June 2024 18:55:55


Electric, 2009).

1.6 CHARACTERISTICS OF THE LV


DISTRIBUTION NETWORKS

Based on the above investigation, the main characteristic of the LV distribution network is listed as
follows:

1. Large number of buses: the LV network is to supply many domestic consumers. For example, a
part of the LV distribution network in Netherlands is shown in Fig. 1.9, which has more than 99.6%
of the whole network connections (Nijhuis, 2017).
2. The network is not monitored: a significant part of the metering system, particularly the
household meter, is still without a communication system with the network operators or smart
meters. The advanced metering infrastructure (AMI) is still in the early stage of installation,
which leads to the lack of understanding of the LV networks’ real state and, thus, a high number
of uncertainties.
3. Operated in radial or weakly meshed topology: the majority of LV network configurations is
radial, and this simplifies the power flow analysis.
4. High R/X ratios compared with HV and MV networks: especially in the case of underground
cables, which makes resistance a very important factor in determining the voltage, where the
voltage angle is approximately constant at the LV network.
5. Highly violated load pattern: the load pattern is unbalanced with a high level of uncertainty.

Distribution Network Types and Configurations 1-13


Principles

10 kV network
MV/LV substation
0.4 kV network
LV-customer

FIG. 1.9
Part of LV network in the Netherlands (Nijhuis, 2017).

12 June 2024 18:55:55


6. Untransposed feeders: the spacing between conductors is non-symmetrical and the transposition
principle does not apply compared with HV and MV networks.
7. Bi-directional power flow: the distribution generator injected the excess generated power into the
LV network, which resulted in a reverse power flow from the load side, and this raises the voltage
level in the load side.

1.7 VOLTAGE AND CURRENT IMBALANCE


IN LV DISTRIBUTION NETWORKS

For different reasons related to the operation and planning of the LV distribution networks, they are
considered as unbalanced or asymmetrical in which the voltages and current magnitudes in the three
phases are also not equal, and the phase shift angle between two adjacent phases is not exactly 120°
(Al-Jaahfreh and Mokryani, 2019).

Figure 1.10 presents a phasor diagram in order to compare the balanced three-phase network and
several unbalanced conditions, where Ua, Ub, and Uc refer to the voltage or current phasors in the
network (Beharrysingh, 2014). The main reason for voltage and current unbalance in LV distribution
networks is the uneven distribution of single-phase loads among the three phases. This might either
happen normally or due to the integration of a high amount of low carbon technologies (LCTs), such
as residential PVs or electric vehicles EVs (Li and Crossley, 2014b).

1-14 Future Distribution Networks


scitation.org/books

Ub Ub
Ub Ub

Ua
Ua
Ua Ua
Uc

Uc
Uc Uc
Balanced magnitude Unbalanced magnitude Unbalanced angles Unbalanced magnitude
and angles and angles

FIG. 1.10
Voltage and current phasor diagram for a balanced and unbalanced three-phase network (Beharrysingh, 2014).

In MV and HV distribution networks, the three-phase connected loads are balanced while most
LV networks’ loads are single-phase (Taylor, 1990). Network planners have put much effort into the

12 June 2024 18:55:55


planning stage to connect an equal number of customers to each phase to make the load level balanced
among the three phases (Al-Jaahfreh and Mokryani, 2019). However, in practice, phase load balancing
cannot be easily done. To connect the single-phase loads to the three-phase four-wire LV distribution
network, each load should be connected to two wires including phase and neutral. Figure 1.11 shows
an example of three-phase four-wire LV feeder with an uneven distribution of single-phase loads
(Beharrysingh, 2014; and Al-Jaahfreh and Mokryani, 2019).

400/230 V 3 phase, 4 wire primary LV feeder


11/0.4 kV

L1
L2
L3
N

FIG. 1.11
Uneven distribution of single load consumers (Beharrysingh, 2014; and Al-Jaahfreh and Mokryani, 2019).

Distribution Network Types and Configurations 1-15


Principles

The voltage unbalance is not significant in MV distribution networks; however, the MV network’s
unbalanced voltages are interpreted through the MV/LV distribution transformers’ windings (Taylor,
1990). Low Carbon Technologies (LCTs) are associated with any kind of technology installed in the
electricity networks and used by end user customers to reduce carbon emission (Li and Crossley,
2014a). LCTs include renewable DGs, such as PVs, EVs, heat pumps, and Combined Heat and Power
(CHP) (Chua et al., 2011). However, the integration of LCTs into LV distribution networks will increase
the current and voltage imbalance levels mainly because of the uneven distribution of single-phase
LCTs. High penetration of LCTs in a specific phase will result in a highly fluctuating demand profile.
Also, the integration of a mix LCT technologies along LV feeders may lead to an unpredicted increase
and decrease in load demand and, thus, a significant increase in the current (Mansor and Levi, 2017).

REFERENCES

Al-Jaahfreh, M. A. A. and Mokryani, G., “Planning and operation of low voltage distribution networks:
A comprehensive review,” IET Energy Syst. Integr. 1(3), 133–146 (2019).
Aydin, M. S., Navarro-Espinosa, A., and Ochoa, L. F., “Investigating the benefits of meshing real UK LV

12 June 2024 18:55:55


networks,” in Proceedings of the 23rd International Conference of Electricity Distribution (CIRED)
(Cired, 2015), pp. 1–5.
Bayindir, R., Hossain, E., Kabalci, E., and Perez, R., “A comprehensive study on distributed microgrid
technology,” Int. J. Renew. Energy Res. 4(4), 1094–1107 (2014).
Beharrysingh, S., “Phase unbalance on networks and its mitigation,” in Phase Unbalance on Low-voltage
Electricity Networks and Its Mitigation using Static Balancers (Loughborough University, 2014),
p. 299.
Chen, T. H., Huang, W. T., Gu, J. C., Pu, G. C., Hsu, Y. F., and Guo, T. Y., “Feasibility study of upgrading
primary feeders from radial and open-loop to normally closed-loop arrangement,” IEEE Trans.
Power Syst. 19(3), 1308–1316 (2004).
Chua, K. H., Wong, J., Lim, Y. S., Taylor, P., Morris, E., and Morris, S., “Mitigation of voltage unbalance
in low voltage distribution network with high level of photovoltaic system,” Energy Proc. 12(603),
495–501 (2011).
Csanyi, E., “North American versus European distribution systems,” see https://electrical-engineering-
portal.com/north-american-versus-european-distribution-systems
EEP, “4 main types of distribution feeder systems to recognize,” see https://electrical-engineering-
portal.com/4-main-types-distribution-feeder-systems#radial-distribution-system
Engineering Technical Report 140, Statutory voltage limits at customers’ terminals in the UK and
options for future application of wider limits at low voltage, July 2017.
Haj-Ahmed, M. A. and Illindala, M. S., “Investigation of protection schemes for flexible distribution of
energy and storage resources in an industrial distributed network,” IEEE Trans. Ind. Appl. 51(3),
2071–2080 (2015).

1-16 Future Distribution Networks


scitation.org/books

Isermann, R., Fault-Diagnosis Systems: An Introduction from Fault Detection to Fault Tolerance
(Springer, Heidelberg, 2006), pp. 232–245.
Islam, F. R., Prakash, K., Mamun, K. A., Lallu, A., and Pota, H. R., “Aromatic network: A novel structure
for power distribution system,” IEEE Access 5, 25236–25257 (2017).
Kaipia, T., Salonen, P., Lassila, J., and Partanen, J., “Possibilities of the low voltage DC distribution systems,”
in Nordac, Nordic Distribution and Asset Management Conference (Nordac, 2006), pp. 1–10.
Kishorbha, T. M. and Mangroliya, D. G. P., “Recent trades in distribution system,” Int. J. Adv. Eng. Res.
Dev. 2(3), 211–217 (2015).
Lee Willis, H., Power Distribution Planning Reference Book (Marcel Dekker, New York, 2004).
Li, Y. and Crossley, P. A., “Impact of electric vehicles on LV feeder voltages,” in IEEE Power and Energy
Society General Meeting (IEEE, 2014a).
Li, Y. and Crossley, P. A., “Voltage balancing in low-voltage radial feeders using Scott transformers,”
IET Gener. Transm. Distrib. 8(8), 1489–1498 (2014b).
Mansor, N. N. and Levi, V., “Integrated planning of distribution networks considering utility planning
concepts,” IEEE Trans. Power Syst. 32(6), 4656–4672 (2017).
Mariam, L., Basu, M., and Conlon, M. F., “A review of existing microgrid architectures,” J. Eng. 2013,
937614 (2013).

12 June 2024 18:55:55


Mehta, V. and Mehta, R., Principles of Power System (S. Chand, New Delhi, 2005).
Navarro-Espinosa, A. and Ochoa, L. F., “Probabilistic impact assessment of low carbon technologies
in LV distribution systems,” IEEE Trans. Power Syst. 31(3), 2192–2203 (2016).
Navarro-Espinosa, A., Ochoa, L. F., and Randles, D., “Assessing the benefits of meshed operation of
LV feeders with low carbon technologies,” in 2014 IEEE PES Innovative Smart Grid Technologies
Conference (ISGT 2014) (IEEE, 2014).
Nijhuis, M., Long-Term Planning of Low Voltage Networks (Technische Universiteit, Eindhoven, 2017).
Park, J. D., Candelaria, J., Ma, L., and Dunn, K., “DC ring-bus distributed network fault protection and
identification of fault location,” IEEE Trans. Power Deliv. 28(4), 2574–2584 (2013).
Plesnick, L., Devine, D., and Hannon, T., “An intelligent fault detection device for shipboard power
systems,” in Proceedings of the Electric Ship Symposium (SEE, France, 2000), pp. 1–6.
Prakash, K., Lallu, A., Islam, F. R., and Mamun, K. A., “Review of power system distribution network
architecture,” in 2016 3rd Asia-Pacific World Congress on Computer Science and Engineering
(APWC on CSE) (IEEE, 2016), pp. 124–130.
Reed, G. F., Grainger, B. M., Sparacino, A. R., Kerestes, R. J., and Korytowski, M. J., “Advancements
in medium voltage DC architecture development with applications for powering electric vehicle
charging stations,” IEEE Energy Tech. 1–8 (2012).
Saleh, S. A., “Signature-coordinated digital multirelay protection for distributed network systems,”
IEEE Trans. Power Electron. 29(9), 4614–4623 (2014).
Schneider Electric, Electrical Installation Guide (Schneider Electric, 2009), pp. 1–467, see https://
download. schneiderelectric. com/files

Distribution Network Types and Configurations 1-17


Principles

Siemens Power Distribution & Control, Technical: Types of Power Distribution Systems, ED-1, Vol.
18, 2007–2008, pp. 3–5.
Sortomme, E., Venkata, S. S., and Mitra, J., “Distributed network protection using communication-
assisted digital relays,” IEEE Trans. Power Deliv. 25(4), 2789–2796 (2010).
Taher, S. A. and Afsari, S. A., “Optimal location and sizing of UPQC in distribution networks using
differential evolution algorithm,” Math. Probl. Eng. 2012 (2012).
Taylor, A. V., “Electricity distribution network design,” IEE Rev. 36(4), 154 (1990).
Willis, H., Power Distribution Planning Reference Book (Marcel Dekker, New York, 2004).

12 June 2024 18:55:55

1-18 Future Distribution Networks

You might also like