Prüf-Nr./Q-Nr.

: 2768c
SIEMENS Certificate No.:

Dienststelle: DF CP R&D VC 2 / Drutschmann


Department:

Ort: Amberg Tas: 2018-07-02


Place: Date:

Anlagen: Product Description 2768c


Enclosures:

Typprtibescheinigung I T¡¡pe fes{ Certifræte


EaeusnistProduct: Solid-State Relay,Solid-StateGontactor

Iyp' 3RF20. 3RF21 .3RF22. rech.._Daten: UE / U¡ = 600 v Hersteller: SiemenS AG


tvpe: spec'tßatßn: le(Acsl) 7'5 - 88 A Manufacturer:
DF Cp
3RF23; 3RF24; 3RF29 =

Art der Prüfung I Type of test: Type Test


Prüfer/ Mr. Stadlbauer Labor / Type Test Center Siemens AG, Amberg
Tested by: Laboratory:
DAkkS accredited Testing Laboratory

Angewandte Prüfbestimmungen / Iesf specifications applied:


IEC 60947,4-3=2014-05
IEG 60947-5-l:2009-07

Durchgeführte Prüfungen I Tests cond ucted :


According to IEC 60947,4-3: Test Sequences l, ll, lll, lV, EMC Emission, EMC lmmunity
According to IEG 60947-5-l: Test Sequences ll, lll, lV

Prüfergebnis / Iesf resu/fs:


All requirements of the test specification are met.

Bemerkungen I Remarks: lSSued: 2006-05-12


lndex a, dated 2009-07-01: Standards updated; EMG test report added
lndex b, dated 2013-06-ll: Standards updated
lndex c, dated 2018-05-17: Standards updated, updated product description added
Coverc allsolid-state switching devices for resistive loads type 3RF2 and accessories type 3RF2

i.v. i.v.
DF R&D Mr. Hartinger R&D PME Mr. Meier

SIEMENS AG DigitalFactory
Dr. Jan Mrosik, GEO
Siemens Aktiengesellschafr: Chairman of the Supervisory Board: Jim Hagemann Snabe;
Managing Board: Joe Kaeser, Chairman, President and Ch¡ef Executive Officer; Roland Busch, Lisa Davis, Klaus Helmrich, Jan¡na Kugel, Cedrik Neike,
Michael Sen, Ralf P. Thomas;
Registered offices: Berlin and Munich, Germany; Commercial registries: Berlin Charlottenburg, HRB 12300, Munich, HRB 6684; WEEE-Reg.-No. DE 23691322
Formular: February 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

General

Type designation: Types 3RF2


SSR ⇓ Solid-state Relay
SSC ⇓ Solid-State Contactor

Manufacturer: Siemens AG, DF CP


92220 Amberg, Werner-von-Siemens-Str. 48, Germany

Production site: Siemens AG, DF CP


92220 Amberg, Werner-von-Siemens-Str. 48, Germany

Page 1 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Nomenclature breakdown

3RF21 20 - 1 A A 0 2
I II III IV V VI VII

I. Basic unit designation for SSR (solid-state relay), SSC (solid-state contactor)
3RF20 - SSR Solid State Relay single phase 45 mm
3RF21 - SSR Solid State Relay single phase 22,5 mm
3RF22 - SSR Solid State Relay three phase
3RF23 - SSC Solid State Contactor single phase
3RF24 - SSC Solid State Contactor three phase

II. Ratings SSR


20 - 20 A
30 - 30 A
50 - 50 A
55 - 55 A
70 - 70 A
90 - 90 A

II. Ratings SSC


10 - 10 A
20 - 20 A
30 - 30 A
40 - 40 A
50 - 50 A
70 - 70 A
90 - 90 A

III. Type of terminal


-1 - main terminal screw, aux terminal screw
-2 - main terminal cage clamp, aux terminal spring loaded
-3 - main terminal ring lug, aux terminal screw
-4 - main terminal screw, aux terminal spring loaded

IV. Switching function


A- zero point switching
B- instantaneous switch
C- low noise, zero point switching
D- zero point switching, high inrush

Page 2 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

V. Number of controlled phases


A- not use
B- two-phase controlled
C- three phase controlled

VI. Rated control supply voltage / Uc


0- DC 24 V
1- UC 24 V
2- AC 110…230 V
3- AC 110 V
4- TTL 4…30 V
5- AC 230 V
6- DC 110 V

VII. Rated voltage / Ue


2- 24…230 V
4- 48…460 V
5- 48…600 V (1200 V reverse voltage)
6- 48…600 V (1600 V reverse voltage)

Type 3RF2340-1DA04-0KN0
Special version of solid state contactor with Ie = 36A, control circuit with Ith < 10mA at the rated
control voltage

Page 3 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Nomenclature breakdown / Accessories

3RF29 00 - 0 E . 1 8
I II III IV V VI VII

I. Accessories for SSR (solid-state relay), SSC (solid-state contactor)


3RF29 - Function modules

II. Type of Accessory


00 - Analog – digital signal converter unit
04 - Load monitoring unit or power controller up to 4 A
06 - Load monitoring unit or power controller up to 6 A
16 - Load monitoring unit or power controller up to 16 A
20 - Load monitoring unit or power controller up to 20 A
32 - Load monitoring unit or power controller up to 32 A
50 - Load monitoring unit or power controller up to 50 A
90 - Load monitoring unit or power controller up to 90 A

III. Type of terminal


0- aux. terminal only

IV. Function
E- Converter
F- Load monitor function, basic
G or J - Load monitoring function, extended
H- Power controller with control function
K- Power controller with adjust function

V. Manufacturers information
.- any character, specifies manufacturers information

VI. Rated control supply voltage / Uc


0- DC 24 V
1- UC 24 V
3- AC 110 V

VII. Rated Valtage / Ue


3- 110 – 230 V
6- 400 – 600 V
8- Option modules, access to main voltage

Page 4 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Technical Data

Test item particulars.............................................. :


- form of equipment ................................................. : a.c. semiconductor controller
semiconductor controller (form 4)
semiconductor direct-on-line (DOL) contactor
hybrid controllers or contactors form H4A
hybrid controllers or contactors form H5A
hybrid controllers or contactors form H4B
hybrid controllers or contactors form H5B
- number of main poles ............................................ : main poles
1
2
3
4
main poles where operation is controlled by a
semiconductor switching element
1
2
3
4
- kind of current ....................................................... : AC

- interrupting medium............................................... : Air


(Only applicable to mechanical switching devices of Vacuum
hybrid controllers and contactors) Other: Semiconductor…………………….
- method of operation............................................... : symmetrical controlled controller
non-symmetrical controlled controller
automatic
- method of control................................................... : automatic
non-automatic
semi-automatic
……………………………………………………….
- method of connection ............................................ : load in star
load in delta
single phase
……………………………………………………….

Page 5 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Rated and limiting values, main circuit:


- rated operational voltage Ue (V)............................ : Up to 600V
- rated insulation voltage Ui (V) ............................... : Up to 600V
- rated impulse withstand voltage Uimp (kV)............ : Up to 6kV
- rated control circuit voltage Uc (V) ........................ : Up to 110V dc and up to 230V ac
- rated control supply voltage Us (V) ....................... : Up to 110V dc and up to 230V ac
- conventional free air thermal current Ith (A)........... : Up to 88A
- conventional enclosed thermal current Ithe (A)...... : N/A
- rated operational current Ie (A)............................... : Up to 88A
- rated uninterrupted current Iu (A) .......................... : N/A
- rated frequency..................................................... : 50/60Hz
- rated duty ............................................................. : eight-hour duty
uninterrupted duty
intermittent duty
temporary duty
periodic duty
- duty cycle values (F and S) ................................... : See table 1 and table 2
- overload current profile ......................................... : See table 1 and table 2
- utilization category................................................. : AC-51
AC-55a AC-55b
AC-56a AC-56b
- IP code ................................................................. : IP20
- pollution degree..................................................... : 3
- ambient air temperature (˚C) .................................. : 40°C

Short-circuit characteristic:
- rated conditional short-circuit current Iq (kA) ......... : See table 4
- kind of protective device ........................................ : See table 4

Page 6 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Rated and limiting values, auxiliary circuits:


- rated operational voltage Ue (V)……… ................. : Up to 240V
- rated insulation voltage: Ui (V) .............................. : 250V
- rated operational current: Ie (A) ............................ : Up to 3A
- kind of current ....................................................... : AC/DC
- rated frequency: (Hz) ............................................ : 50/60Hz
- number of circuits ................................................. : Up to 3
- number and kind of contact elements.................... : 1
- rated uninterrupted current: Iu (A) ......................... :
- utilization category: (AC, DC, current and voltage) : See table 3
Short-circuit characteristic :
- Rated conditional short-circuit current (kA) ............ : See table 4
- kind of protective device ....................................... : See table 4

Table 1 Duty cycles values and overload current profile (SSC-type)

3RF2310- 3RF2320- 3RF2330- 3RF2340- 3RF2350- 3RF2370- 3RF2390-


Type
.. .. .. .. .. .. ..
Ie (A) 10 20 30 40 50 70 90

X 1,4 / 1,7 1,4 / 1,7 1,4 / 1,7 1,4 / 1,6 1,4 / 1,6 1,2 1,1

Tx (s) 300 / 10 300 / 10 300 / 10 300 / 10 300 / 10 10 60

F (%) 50 50 50 50 50 50 50

S 6 / 180 6 / 180 6 / 180 6 / 180 6 / 180 180 30

3RF2340-
3RF23..- 3RF2410- 3RF2420- 3RF2430- 3RF2440- 3RF2450-
Type 1DA04-
…6. .. .. .. .. ..
0KN0
Ie (A) 36 13,2 7 15 22 30 38

X 1,2 / 1,4 1,7 1,5 / 1,9 1,5 / 1,9 1,5 / 1,9 1,5 / 1,9 1,5 / 1,9

Tx (s) 200 / 10 10 300 / 10 300 / 10 300 / 10 300 / 10 300 / 10

F (%) 50 50 50 50 50 50 50

S 9 / 180 180 6 / 180 6 / 180 6 / 180 6 / 180 6 / 180

Page 7 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Table 2 Duty cycles values and overload current profile (SSR-type)

3RF2120- 3RF2130- 3RF2150- 3RF2170- 3RF2190- 3RF2230- 3RF2255-


Type
.. .. .. .. .. .. ..
Ie (A) 20 30 50 70 90 30 55

X 1,1 1,1 1,1 1,1 1,1 1,1 1,1

Tx (s) 60 60 60 60 60 60 60

F (%) 50 50 50 50 50 50 50

S 30 30 30 30 30 30 30

Table 3 utilization category

rated operational rated operational


Contact/Type utilization category
voltage current

22A
33A
3RF21.. 24V 55A
77A
90A

30A
3RF22.. 600V
55A

7,5A
AC-51 110V 13,2A
115V 22A
230V 33A
3RF23.. 400V 36A
70A

24V 88A

7A
15A
3RF24.. 600V 22A
30A
38A

Page 8 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Table 3 utilization category

6A
12A
15A
3RF21.. AC-15 400V 20A
25A
27,5A
30A

AC-12 125V 0,5A


3RF29..
(14/11/12) DC-12 24V 0,5A

Table 4 Performance under short-circuit conditions

prospective
device type of SCPD ratings of SCPD test voltage
current

SSC-type

3NW6205-1
3RF2310-.. 16A gL/gG 50kA 440V
cylindrical fuse link
3NW6207-1
3RF2320-.. 20A gL/gG 50kA 440V
cylindrical fuse link
3NW6212-1
3RF2330-.. 32A gL/gG 50kA 440V
cylindrical fuse link
3NE1802-0
3RF2340-.. 40A gS 50kA 440V
LV HRC fuse
3NE1817-0
3RF2350-.. 50A gS 50kA 440V
LV HRC fuse
3NE1820-0
3RF2370-.. 80A gS 50kA 440V
LV HRC fuse
3NW6210-1
3RF2410-.. 25A gL/gG 50kA 550V
cylindrical fuse link
3NW6217-1
3RF2420-.. 40A gL/gG 50kA 550V
cylindrical fuse link
3NW6117-1
3RF2430-.. 40A gL/gG 50kA 550V
cylindrical fuse link
3NW6117-1
3RF2440-.. 40A gL/gG 50kA 550V
cylindrical fuse link
3NW6117-1
3RF2450-.. 40A gL/gG 50kA 550V
cylindrical fuse link

Page 9 of 10
Formular: May 2018
Product Description Prüf-Nr./Q-Nr.:
Certificate No.:
2768c

Table 4 Performance under short-circuit conditions

prospective
device type of SCPD ratings of SCPD test voltage
current
3NA6810-6
3RF2410-.. 25A gL/gG 50kA 660V
LV HRC fuse
3NA6817-6
3RF2420-.. 40A gL/gG 50kA 660V
LV HRC fuse
3NA6817-6
3RF2430-.. 40A gL/gG 50kA 660V
LV HRC fuse
3NA6817-6
3RF2440-.. 40A gL/gG 50kA 660V
LV HRC fuse
3NA6817-6
3RF2450-.. 40A gL/gG 50kA 660V
LV HRC fuse

SSR-type

3NW6207-1
3RF2020-.. 20A gL/gG 50kA 440V
cylindrical fuse link
3NW6212-1
3RF2030-.. 32A gL/gG 50kA 440V
cylindrical fuse link
3NE1817-0
3RF2050-.. 50A gS 50kA 440V
LV HRC fuse
3NW6207-1
3RF2120-.. 20A gL/gG 50kA 440V
cylindrical fuse link
3NW6212-1
3RF2130-.. 32A gL/gG 50kA 440V
cylindrical fuse link
3NE1817-0
3RF2150-.. 50A gS 50kA 440V
LV HRC fuse
3NE1820-0
3RF2170-.. 80A gS 50kA 440V
LV HRC fuse
3NW6210-1 25A gL/gG 50kA 550V
cylindrical fuse link
3RF2230-1AB45
3NA6810-6
25A gL/gG 50kA 660V
LV HRC fuse

accessory

2A rapid 1kA 110V


Diazed
3RF2990-0GA33 2A gL/gG 1kA 110V

NEOZED 2A gL/gG 1kA 110V

Page 10 of 10