KEAS-VFD Data Sheet REV C2

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

LS25-1 GAS FIELD DEVELOPMENT PROJECT

MEG FLASH SEPERATOR RECYCLE PUMPS TRAIN A&B


LS25-1气田开发项目MEG 闪蒸分离器循环泵系列 A&B

Document Title : KEAS -VFD DATA SHEET -75kW/110kW MOTOR


MEG FLASH SEPARATOR RECYCLE PUMPS A&B

COMPANY Doc No. : CCL2022HNHW0273-EL-DDS-2601

Contractor Doc No. : 210505-E-DS-2601

C2 11-July -23 APPROVED FOR CONSTRUCTION ILAYA VI EAE


C1 15-May-23 ISSUED FOR APPROVAL ILAYA VI EAE
B1 30-Mar-23 ISSUED FOR APPROVAL ILAYA VI EAE
A1 30-Mar-23 ISSUED FOR APPROVAL ILAYA VI EAE
R1 30-Mar-23 ISSUED FOR APPROVAL ILAYA VI EAE
REV. DATE DESCRIPTION PREPARED CHECKED APPROVED

PROJECT DOCUMENTS ARE CONTROLLED DOCUMENTS.


REVISION CHANGES ARE DENOTED AS IN RIGHT HAND MARGIN

COMPANY: CONTRACT NUMBER:


CNOOC CHINA LTD. _HAINAN
210505-E-DS-2601

CONTRACTOR: PURCHASE ORDER:


VME PROCESS ASIA PACIFIC PTE LTD
210505

SUPPLIER: TOTAL PAGES:


30
KEAS CONTROL SYSTEM INDIA PVT,LTD.
TITLE DOCUMENT NO
KEAS -VFD DATA SHEET -75kW/110kW MOTOR MEG FLASH SEPERATOR RECYCLE PUMPS TRAIN A&B CCL2022HNHW0273-EL-DDS-2601
PROJECT DESCRIPTION PURCHASE ORDER NUMBER SHEET REV
LS25-1 GAS FIELD DEVELOPMENT PROJECT
MEG FLASH SEPERATOR RECYCLE PUMPS TRAIN A&B - 2 OF 30 C2
LS25-1气田开 发项 MEG 闪蒸分离器循环泵系列 A&B
COMPANY REQUISITION No. SPECIFICATION No.
CNOOC CHINA LTD. _HAINAN - -
CONTRACTOR REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
VME PROCESS ASIA PACIFIC PTE LTD R1 AM 30-Mar-23 VI 30-Mar-23 EAE ISSUED FOR REVIEW
CONTRACTOR A1 AM 30-Mar-23 VI 30-Mar-23 EAE ISSUED FOR APPROVAL
KEAS CONTROL SYSTEM INDIA PVT,LTD. B1 AM 30-Mar-23 VI 30-Mar-23 EAE ISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE C1 AM 30-Mar-23 VI 15 -May-23 EAE ISSUED FOR APPROVAL
SCHNEIDER /KEAS 30-Mar-23 C2 AM 11-July -23 VI 19-June-23 EAE APPROVED FOR CONSTRUCTION

INDEX SHEET
SHEET NO. TITLE R1 A1 B1 C1 C2
1 COVER SHEET 30-Mar-23 30-Mar-23 30-Mar-23 3-Apr-23 11-Jul -23

2 INDEX SHEET 30-Mar-23 30-Mar-23 30-Mar-23 3-Apr-23 11-Jul -23

3 REVISION RECORD 30-Mar-23 30-Mar-23 30-Mar-23 3-Apr-23 11-Jul -23

4 VFD DATA SHEET 30-Mar-23 30-Mar-23 30-Mar-23 3-Apr-23 11-Jul -23


TITLE DOCUMENT NO
KEAS -VFD DATA SHEET -75kW/110kW MOTOR MEG FLASH SEPARATOR RECYCLE PUMPS CCL2022HNHW0273-EL-DDS-2601
PROJECT DESCRIPTION PURCHASE ORDER NUMBER SHEET REV
LS25-1 GAS FIELD DEVELOPMENT PROJECT
MEG REGENERATION AND RECLAMATION PACKAGE - 3 OF 30 B2
LS25-1气田开发项目 MEG 再生和回收包
COMPANY REQUISITION No. SPECIFICATION No.
CNOOC CHINA LTD. _HAINAN - -
CONTRACTOR REV No. BY DATE CKD DATE APP. DATE DESCRIPTION
VME PROCESS ASIA PACIFIC PTE LTD R1 AM 30-Mar-23 VI 30-Mar-23 EAE ISSUED FOR APPROVAL
CONTRACTOR A1 AM 30-Mar-23 VI 30-Mar-23 EAE ISSUED FOR APPROVAL
KEAS CONTROL SYSTEM INDIA PVT,LTD. B1 AM 30-Mar-23 VI 30-Mar-23 EAE ISSUED FOR APPROVAL
ORIGINATOR ORIG. DATE B2 AM 15-May-23 VI 15-May-23 EAE ISSUED FOR APPROVAL
SCHNEIDER /KEAS 30-Mar-23

REVISION RECORD SHEET


REV. NO. PURPOSE LIST OF PAGES OF UPDATED / MODIFIED SECTIONS, IF ANY
R1 ISSUED FOR APPROVAL FIRST ISSUE
A1 ISSUED FOR APPROVAL FIRST ISSUE
B1 ISSUED FOR APPROVAL FIRST ISSUE
B2 ISSUED FOR APPROVAL FIRST ISSUE
C1 ISSUED FOR APPROVAL FIRST ISSUE
C2 APPROVED FOR CONSTRUCTION FIRST ISSUE
DRIVEN EQUIPMENT DATA
Motor type Squirrel Cage Induction Motor Ex Protection type of motor Ex 'de' Insulation Class F Temperature rise limited to Class B
Motor Description MEG Flash Separator Recycle Pump Motor for Train A Motor Tag Number PAP-4801-A1/A2
Motor rated kW / rpm / voltage 75 / TBC / 380 (For other parameters refer Motor Data Sheet)
GENERAL INFORMATION
Name of VFD Manufacturer Schneider Electric Country of Manufacture VTA
Service Centre (at delivery location) VTA VFD Tag Number To Be Provided
SERVICE CONDITIONS POWER SYSTEM CONDITIONS
380V AC, ±6% (steady State);
Location Offshore System Voltage
±20% (Transient Conditions)
Installation Indoor , Safe area (E-House System Frequency 50 Hz (+/-) 5%

Altitude above MSL Not more than 50 meters above Mean Sea Level System Earthing IT Earthing

Ambient Temperature (Min . / Max.) 11.5 °C / 38.2 °C Three Phase Fault Current Client to Confirm
Relative Humidity 100% Space Heater Power Supply 220VAC,1 Phase, 50 Hz
Hazardous area Classification Unclassified, safe area
RATING AND DESIGN DATA
Maximum Design temperature 45 °C Minimum Design temperature -15°C (w/o derating)
KW output at design ambient 75 kW @ 45 o
C VFD control (speed/torque/power) speed and torque conrol
Rated Operating Voltage & variation 380...480 V - 15...10 % Control Method-Induction Motor Yes
Frequency & variation 50 50...60 Hz - 5...5 % Pulse system (6/12/...) (at input) 6 pulse rectifier

Combined voltage & frequency variation (+/-) 5% Pulse system (6/12/..) (at output) 6 pulse rectifier

System Earthing IT (Un Earthed) Harmonics in power supply side <48 % from 80...100 % of load
Supply system fault level (MVA/kA) Client to Confirm On loss of reference signal: No change in operating condition
VFD operational speed range n/a to n/a RPM Communication with DCS (ICSS) Yes
No. of Phases Communication with PMS Yes
Input / Output 3 / 3 Design Life 20 Years
Applicable Design Standard IEC / UL
CONSTRUCTION DATA
Type of VFD Schneider Make, Model No : ATV630D75N4 Mounting Type Wall mounted
Type/Make of semiconductors (input) SCR Dynamic Braking Pump Application doen't required Dynamic Braking
Type/Make of semiconductors (output) IGBT RFI Internal Filter Yes
VFD encl. ingress (IP) Protection IP23 External Filter Not required
Cooling system of VFD air cooled with louvers Link Inductor Yes
Externally mounted Reactor? Yes No Safety STOP Yes
External Harmonic Filter? Yes No Operation interface (HMI) Yes, with Local LCD display
Space heater in VFD panel Yes No HMI IP rating IP 56
Heater supply voltage 220V AC external supply Dimension Details:
Anti condensation Heater Watts Other WxDxH in mm 290x322x922
Indication lamps (LED) Required Weight in Kg 55
Earth bar inside panel Required , PE &IE Panel Paint Colour RAL 7035
Heat Dissipation of Panel 1897 W Panel Paint Colour RAL 7035
PERFORMANCE DATA
Rated input current 131 A@380 V A Reacceleration facility available Yes No
Rated output current 145 A@2.5 kHz A Availability of VFD VTA 100%
Output Voltage Range <= power supply voltage MTBF of VFD > 47 Years yrs

MTTR is decided by maintenance


schedule and device maintenance
Output Frequency Range 0.1 Hz to 599 Hz MTTR of VFD hours
cycle, its different with different
customer.

Speed 10% rpm 50% rpm 90% rpm 100% rpm 1.543 kW at 100% load
Dissipated Heat Power
Efficiency at full load 83.8 % 96.5 % 97.7 % 97.8 % 1.157 kW at 75% load
Efficiency at 50% load 81.6 % 95,8 % 97,2 % 97,4 % Early opening signal from N.A. Yes No
1st & 2nd critical speed VTA rpm VTA rpm upstream breaker required?
Run-up time of VFD to full speed 1 - 6000 s Standard Switching Frequecy 2.5 kHz
Overload Current at 60s 159.5 A during 60 s Selectable Switching Frequency 2 - 8 kHz
Input Power Factor 0,919 @ 380V 50Hz (ND) Control output frequency 500 Hz
Displacement Factor 0,994 @ 380V 50Hz (ND) Frequency resolution 0.1 Hz

Speed Regulation (V/f, VVW, sensorless


Max. noise/ sound pressure level 62.4 dB 0 - 100 % (0.1 - 500Hz)
Vector control, Vector w/ encoder )

Speed Variation (V/f, VVW, sensorless


Analog / Digital Input&oupt provision Yes 0 - 100 % (0.1 - 500Hz)
Vector control, Vector w/ encoder)

TRANSFORMER DATA
Name of manufacturer VTA No. of secondary windings VTA
Country of Manufacture VTA % impedance(s) of transformer VTA
Transformer type VTA Connection symbol VTA
Transformer voltage ratio (s) VTA Transformer efficiency VTA
kVA rating VTA Transformer primary cable VTA
CABLE AND CONNCETION DETAILS
Any special cable type requirement VTA Max. length of cable between VFD & Motor 250 meters (Client to confirm)
Incomer cable type 0.6 / 1 kV EPR/LSHF/SWA/LSHF Max. length of cable between Swgr & VFD 50 meters (Client to confirm)
Incomer Cable Size, nos. TBC Incoming & Outgoing cable entry Size TBC
Outgoing cable type 0.6 / 1 kV EPR/LSHF/SWA/LSHF Cable Entry Bottom
Outgoing Cable Size, nos. TBC Gland Plate Removable type, pre-drilled
INSPECTION AND TESTS
Type Test Unwitnessed type test for Identical item
Routine Test Yes, Un witnessed
DNV Class Complaince Yes , required
NOTES:
VTA - Vendor to advise , TBC - To Be Confirmed,
1 VFD panel shall be designed and manufactured in accordance with applicable IEC standards.
2 VFD Manufacturer shall duly fill this data sheet and also attach manufacturer standard datasheet along with this document.
3 All threaded cable entries shall be tapped ISO metric standard threads. Spare entries shall be provided with stopping plugs.
4 Signal from VFD to on-site control panel: VFD operation status(Normally open dry contact), VFD ready signal(normally open dry contact),
VFD failure(normally closed dry contact), signal from VFD to on site control panel is 4-20mA.
5 Power of space heater in motors is supplied by VFD cabinet.
6 Equipment tag plates(including equipment tag number and name, equipment name in both Chinese and English). Tag plate is made of SS316L and fixed with SS316L rivets.
7 Data storage unit of VFD shall be a permanent storage unit which will not cause data loss due to equipment power failure.
8 Harmonic calculation of VFD drive to fullfill the requirement of IEEE519 or GB/T-14549 and provide third-party(ABS, BV,CCS,DNV) ship inpection certification.
9 VFD panel size shall be limited to 1220mm(L)X620mm(D)X2300mm(H)
10 VFD control the frequency of the supply Speed Range Depend upon Motor

Anvira - Filled_VFD Datasheet_Rexel_R2 (1) # Internal


Page 1 of 1
DRIVEN EQUIPMENT DATA
Motor type Squirrel Cage Induction Motor Ex Protection type of motor Ex 'de' Insulation Class F Temperature rise limited to Class B
Motor Description MEG Flash Separator Recycle Pump Motor for Train B Motor Tag Number PAP-P-4801-B1/B2
Motor rated kW / rpm / voltage 110 / TBC / 380 (For other parameters refer Motor Data Sheet)
GENERAL INFORMATION
Name of VFD Manufacturer Schneider Electric Country of Manufacture It can be identify by serial number of the product
Service Centre (at delivery location) VTA VFD Tag Number To Be Provided
SERVICE CONDITIONS POWER SYSTEM CONDITIONS
380V AC, ±6% (steady State);
Location Offshore System Voltage
±20% (Transient Conditions)
Installation Indoor , Safe area (E-House System Frequency 50 Hz (+/-) 5%

Altitude above MSL Not more than 50 meters above Mean Sea Level System Earthing IT Earthing

Ambient Temperature (Min . / Max.) 11.5 °C / 38.2 °C Three Phase Fault Current Client to Confirm
Relative Humidity 100% Space Heater Power Supply 220VAC,1 Phase, 50 Hz
Hazardous area Classification Unclassified, safe area
RATING AND DESIGN DATA
Maximum Design temperature 45 °C Minimum Design temperature -15 °C (w/o derating)
KW output at design ambient 110 kW @ 45 o
C VFD control (speed/torque/power) Speed and Torque conrol
Rated Operating Voltage & variation 380...480 V - 15...10 % Control Method-Induction Motor Yes
Frequency & variation 50 50...60 Hz - 5...5 % Pulse system (6/12/...) (at input) 6 pulse rectifier

Combined voltage & frequency variation (+/-) 5% Pulse system (6/12/..) (at output) 6 pulse rectifier

System Earthing IT (Un Earthed) Harmonics in power supply side 44.9% THDi @100% load.
Supply system fault level (MVA/kA) Client to Confirm On loss of reference signal: No change in operating condition
VFD operational speed range n/a to n/a RPM Communication with DCS (ICSS) Yes
No. of Phases Communication with PMS Yes
Input / Output 3 / 3 Design Life 20 Years
Applicable Design Standard IEC / UL
CONSTRUCTION DATA
Type of VFD IGBT ,Schneider Make, Model No : ATV630C11N4 Mounting Type Wall mounted
Type/Make of semiconductors (input) SCR Dynamic Braking Pump Application doen't required Dynamic Braking
Type/Make of semiconductors (output) IGBT RFI Internal Filter Yes
VFD encl. ingress (IP) Protection IP23 External Filter Not required
Cooling system of VFD air cooled with louvers Link Inductor Yes
Externally mounted Reactor? Yes No Safety STOP Yes
External Harmonic Filter? Yes No Operation interface (HMI) Yes, with Local LCD display
Space heater in VFD panel Yes No HMI IP rating IP 56
Heater supply voltage 220V AC external supply Dimension Details:
Anti condensation Heater Watts Other WxDxH in mm 320x390x852
Indication lamps (LED) Required Weight in Kg 125
Earth bar inside panel Required , PE &IE Panel Paint Colour RAL 7035
Heat Dissipation of Panel 2750 W Panel Paint Colour RAL 7035
PERFORMANCE DATA
Rated input current 201 A@380 V A Reacceleration facility available Yes No
Rated output current 211 A@2.5 kHz A Availability of VFD VTA %
Output Voltage Range <= power supply voltage MTBF of VFD > 47 Years yrs

MTTR is decided by maintenance


schedule and device
Output Frequency Range 0.1 Hz to 599 Hz MTTR of VFD
maintenance cycle, its different
with different customer.

Speed 10% rpm 50% rpm 90% rpm 100% rpm 2.82 kW at 100% load
Dissipated Heat Power
Efficiency at full load 82,5 % 96,3 % 97,6 % 97,8 % 2.115 kW at 75% load
Efficiency at 50% load 80,0 % 95,5 % 97,1 % 97,3 % Early opening signal from N.A. Yes No
st
1 &2 nd
critical speed VTA rpm VTA rpm upstream breaker required?
Run-up time of VFD to full speed 1 - 6000 s Standard Switching Frequecy 2.5 kHz
Overload Current at 60s & 3s 232.1 A during 60 s Selectable Switching Frequency 2 - 8 kHz
Input Power Factor 0,899 @ 380V 50Hz (ND) Control output frequency 500 Hz
Displacement Factor 0,991 @ 380V 50Hz (ND) Frequency resolution 0.1 Hz
Speed Regulation (V/f, VVW,
Max. noise/ sound pressure level 69.9 dB sensorless Vector control, Vector w/ Yes
encoder )

Speed Variation (V/f, VVW, sensorless


Analog / Digital Input&oupt provision Yes Yes
Vector control, Vector w/ encoder)

TRANSFORMER DATA
Name of manufacturer VTA No. of secondary windings VTA
Country of Manufacture VTA % impedance(s) of transformer VTA
Transformer type VTA Connection symbol VTA
Transformer voltage ratio (s) VTA Transformer efficiency VTA
kVA rating VTA Transformer primary cable VTA
CABLE AND CONNCETION DETAILS
Any special cable type requirement VTA Max. length of cable between VFD & Motor 250 meters (Client to confirm)
Incomer cable type 0.6 / 1 kV EPR/LSHF/SWA/LSHF Max. length of cable between Swgr & VFD 50 meters (Client to confirm)
Incomer Cable Size, nos. TBC Incoming & Outgoing cable entry Size TBC
Outgoing cable type 0.6 / 1 kV EPR/LSHF/SWA/LSHF Cable Entry Bottom
Outgoing Cable Size, nos. TBC Gland Plate Removable type, pre-drilled
INSPECTION AND TESTS
Type Test Unwitnessed type test for Identical item
Routine Test Yes, Un witnessed
DNV Class Complaince Yes , required
NOTES:
VTA - Vendor to advise , TBC - To Be Confirmed,
1 VFD panel shall be designed and manufactured in accordance with applicable IEC standards.
2 VFD Manufacturer shall duly fill this data sheet and also attach manufacturer standard datasheet along with this document.
3 All threaded cable entries shall be tapped ISO metric standard threads. Spare entries shall be provided with stopping plugs.
4 Signal from VFD to on-site control panel: VFD operation status(Normally open dry contact), VFD ready signal(normally open dry contact),
VFD failure(normally closed dry contact), signal from VFD to on site control panel is 4-20mA.
5 Power of space heater in motors is supplied by VFD cabinet.
6 Equipment tag plates(including equipment tag number and name, equipment name in both Chinese and English). Tag plate is made of SS316L and fixed with SS316L rivets.
7 Data storage unit of VFD shall be a permanent storage unit which will not cause data loss due to equipment power failure.
8 Harmonic calculation of VFD drive to fullfill the requirement of IEEE519 or GB/T-14549 and provide third-party(ABS, BV,CCS,DNV) ship inpection certification.
9 VFD panel size shall be limited to 1220mm(L)X620mm(D)X2300mm(H)
10 VFD control the frequency of the supply Speed Range Depend upon Motor
Jan 13, 2021
Characteristics
Product data sheet

380...480V, IP00
ATV630C11N4
variable speed drive ATV630, 110kW/150HP,

1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Range of product Altivar Process ATV600
Product or component Variable speed drive
type
Product specific Process and utilities
application
Device short name ATV630
Variant Standard version
Product destination Asynchronous motors
Synchronous motors
EMC filter Integrated 492.13 ft (150 m) EN/IEC 61800-3
category C3
IP degree of protection IP00 conforming to IEC 61800-5-1
IP00 conforming to IEC 60529
IP21 with kit VW3A9704)IEC 61800-5-1
IP21 with kit VW3A9704)IEC 60529
Type of cooling Forced convection
Supply frequency 50...60 Hz - 5...5 %
[Us] rated supply 380...480 V - 15...10 %
voltage
Motor power kW 110 KW (normal duty)
90 kW (heavy duty)
Maximum Horse Power 150 Hp normal duty
Rating 125 hp heavy duty
Line current 201 A 380 V normal duty)
165 A 480 V normal duty)
170 A 380 V heavy duty)
143 A 480 V heavy duty)
Prospective line Isc 50 kA
Apparent power 121.8 KVA 480 V normal duty)
102.6 kVA 480 V heavy duty)
Continuous output 211 A at 2.5 kHz for normal duty
current 173 A at 2.5 kHz for heavy duty
Maximum transient 232.1 A during 60 s (normal duty)
current 259.5 A during 60 s (heavy duty)
Asynchronous motor Constant torque standard
control profile Optimized torque mode
Variable torque standard
Synchronous motor Permanent magnet motor
control profile Synchronous reluctance motor
Output frequency 0.0001…0.5 kHz
Speed drive output 0.1…599 Hz
frequency
Nominal switching 2.5 kHz
frequency
Switching frequency 2.5...8 kHz with derating factor
2...8 kHz adjustable
Safety function STO (safe torque off) SIL 3
Discrete input logic 16 preset speeds

2
Communication port Modbus TCP
protocol Ethernet
Modbus serial
Option card Slot A: communication module, Profibus DP V1
Slot A: communication module, Profinet
Slot A: communication module, DeviceNet
Slot A: communication module, Modbus TCP/
EtherNet/IP
Slot A: communication module, CANopen daisy
chain RJ45
Slot A: communication module, CANopen SUB-D 9
Slot A: communication module, CANopen screw
terminals
Slot A/slot B: digital and analog I/O extension
module
Slot A/slot B: output relay extension module
Slot A: communication module, Ethernet IP/Modbus
TCP/MD-Link
Communication module, BACnet MS/TP
Communication module, Ethernet Powerlink

Complementary
Mounting mode Wall mount
Output voltage <= power supply voltage
Permissible temporary current boost 1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)
Motor slip compensation Can be suppressed
Not available in permanent magnet motor law
Automatic whatever the load
Adjustable
Acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 s
Braking to standstill By DC injection
Protection type Thermal protection motor
Safe torque off motor
Motor phase break motor
Thermal protection drive
Safe torque off drive
Overheating drive
Overcurrent between output phases and earth drive
Overload of output voltage drive
Short-circuit protection drive
Motor phase break drive
Overvoltages on the DC bus drive
Line supply overvoltage drive
Line supply undervoltage drive
Line supply phase loss drive
Overspeed drive
Break on the control circuit drive
Frequency resolution Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
Electrical connection Control: removable screw terminals0.5...1.5 mm²/AWG 20...AWG 16
Line side screw terminal 2 x 50...3 x 120 mm² 2 x AWG 1/0...2 x 300 kcmil
Motor screw terminal 2 x 50...3 x 120 mm² 2 x AWG 1/0...2 x 300 kcmil
Connector type RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses 1…247 for Modbus serial
Method of access Slave Modbus TCP
Supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type:
overload and short-circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %,
<10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA,
protection type: overload and short-circuit protection
Local signalling 3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Maximum Width 12.60 in (320 mm)
Height 33.54 in (852 mm)
Depth 15.35 in (390 mm)

3
Net Weight 180.78 lb(US) (82 kg)
Analogue input number 3
Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm,
resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0...20 mA/4...20 mA, impedance: 250
Ohm, resolution 12 bits
Discrete input number 8
Discrete input type DI1...DI6 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm
DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
Input compatibility DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
Discrete input logic Positive logic (source) (DI1...DI6), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1...DI6), > 16 V (state 0), < 10 V (state 1)
Positive logic (source) (DI5, DI6), < 0.6 V (state 0), > 2.5 V (state 1)
Positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1)
Analogue output number 2
Analogue output type Software-configurable voltage AO1, AO2: 0...10 V DC impedance 470 Ohm,
resolution 10 bits
Software-configurable current AO1, AO2: 0...20 mA, resolution 10 bits
Sampling duration 2 Ms +/- 0.5 ms (DI1...DI4) - discrete input
5 Ms +/- 1 ms (DI5, DI6) - discrete input
5 Ms +/- 0.1 ms (AI1, AI2, AI3) - analog input
10 ms +/- 1 ms (AO1) - analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input
AO1, AO2: +/- 0.2 % for analog output
Relay output number 3
Relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability
100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
Minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC
Maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at
250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at
30 V DC
Isolation Between power and control terminals
Variable speed drive application selection Compressor centrifugal Building - HVAC
Other application Food and beverage processing
Fan Mining mineral and metal
Pump Mining mineral and metal
Fan Oil and gas
Other application Water and waste water
Screw compressor Building - HVAC
Pump Food and beverage processing
Fan Food and beverage processing
Atomization Food and beverage processing
Electro submersible pump (ESP) Oil and gas
Water injection pump Oil and gas
Jet fuel pump Oil and gas
Compressor for refinery Oil and gas
Centrifuge pump Water and waste water
Positive displacement pump Water and waste water
Electro submersible pump (ESP) Water and waste water
Screw pump Water and waste water
Lobe compressor Water and waste water
Screw compressor Water and waste water
Compressor centrifugal Water and waste water
Fan Water and waste water
Conveyor Water and waste water
Mixer Water and waste water
Motor power range AC-3 110…220 KW 380…440 V 3 phase
110…220 kW 480…500 V 3 phase

4
Environment
Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
Noise level 69.9 dB 86/188/EEC
Power dissipation in W Forced convection 2026 W 380 V 2.5 kHz
Volume of cooling air 158506.07 Gal/hr(US) (600 m3/h)
Operating position Vertical +/- 10 degree
Maximum THDI <48 % full load conforming to IEC 61000-3-12
Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming
to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution degree 2 conforming to EN/IEC 61800-5-1
Vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn 11 ms IEC 60068-2-27
Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3
Ambient air temperature for operation 5…122 °F (-15…50 °C) without derating)
122…140 °F (50…60 °C) with derating factor)
Ambient air temperature for storage -40…158 °F (-40…70 °C)
Operating altitude <= 1000 m without derating
1000...4800 m with current derating 1 % per 100 m
Standards UL 508C
EN/IEC 61800-3
Environment 1 category C2 EN/IEC 61800-3
Environment 2 category C3 EN/IEC 61800-3
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Product certifications ATEX zone 2/22
ATEX INERIS
TÜV
CSA
UL
DNV-GL
Marking CE

Ordering and shipping details


Category 22207 - ATV630 FRAMES 5 & 6
Discount Schedule CP4E
GTIN 00785901638148
Nbr. of units in pkg. 1
Package weight(Lbs) 220 lb(US) (99.79 kg)
Returnability Yes
Country of origin IN

Packing Units
Unit Type of Package 1 PCE
Package 1 Height 18.90 in (48 cm)
Package 1 width 25.98 in (66 cm)
Package 1 Length 40.55 in (103 cm)
Unit Type of Package 2 CAR
Number of Units in Package 2 1
Package 2 Weight 275.58 lb(US) (125 kg)
Package 2 Height 25.59 in (65 cm)
Package 2 width 18.50 in (47 cm)
Package 2 Length 40.55 in (103 cm)

5
Offer Sustainability
Sustainable offer status Green Premium product
California proposition 65 WARNING: This product can expose you to chemicals including: Lead and
lead compounds, which is known to the State of California to cause cancer
and birth defects or other reproductive harm. For more information go to
www.P65Warnings.ca.gov
REACh Regulation
REACh Declaration
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS
Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS Declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End Of Life Information
WEEE The product must be disposed on European Union markets following specific
waste collection and never end up in rubbish bins.
Upgradeability
Upgraded Components Available

6
Product data sheet ATV630C11N4
Dimensions Drawings

Dimensions

Drives with IP21 Top Cover


Right and Front Views

Drives Without IP21 Top Cover


Right and Front Views

7
Drives with Lower Conduit Box Sold Separately
Rear, Front and Left Views

8
Product data sheet ATV630C11N4
Mounting and Clearance

Clearances

X1 X2 X3

≥ 250 mm (10 in.) ≥ 250 mm (10 in.) ≥ 100 mm (3.94 in.)

Mounting Types

Mounting Type A: Individual IP21

a ≥ = 110 mm (4.33 in.)

9
Mounting Type B: Side by Side IP20 , Only possible at ambient temperature lower than 40 °C (104 °F)

Mounting Type C: Individual IP20

a ≥ = 110 mm (4.33 in.)

10
Product data sheet ATV630C11N4
Connections and Schema

Three-Phase Power Supply with Upstream Breaking via Line Contactor

Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance
with standard IEC/EN 60204-1

(1) Line choke if used


(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 :Line Contactor
Q2, Circuit breakers
Q3 :
S1, Pushbuttons
S2 :
T1 : Transformer for control part

Three-Phase Power Supply with Downstream Breaking via Contactor

Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance
with standard IEC/EN 60204-1

(1) Line choke if used


(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 :Contactor

11
Control Block Wiring Diagram

(1) Safe Torque Off


(2) Analog Output
(3) Digital Input
(4) Reference potentiometer
(5) Analog Input
R1A, Fault relay
R1B,
R1C :
R2A, Sequence relay
R2C :
R3A, Sequence relay
R3C :

Sensor Connection
It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.

Sink / Source Switch Configuration

The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
● Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
● Set the switch to Ext if using PLC outputs with NPN transistors.

12
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs

Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs

Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs

Switch Set to EXT Position Using an External Power Supply for the DIs

13
Product data sheet ATV630C11N4
Performance Curves

Derating Curves

40 °C (104 °F) - Mounting type A, B and C


50 °C (122 °F) - Mounting type A and C
60 °C (140 °F) - Mounting type C
In : Nominal Drive Current
SF : Switching Frequency

14
Product datasheet ATV630D75N4
Characteristics variable speed drive ATV630 - 75kW/100HP -
380...480V - IP21/UL type 1

Main
Range of product Altivar Process ATV600
Product or component type Variable speed drive
Product specific application Process and utilities
Device short name ATV630
Variant Standard version
Product destination Asynchronous motors
Synchronous motors
Mounting mode Wall mount
EMC filter Integrated EN/IEC 61800-3 category C3 150 m
IP degree of protection IP21 IEC 61800-5-1

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
IP21 IEC 60529
Degree of protection UL type 1 UL 508C
Type of cooling Forced convection
Supply frequency 50...60 Hz - 5...5 %
Network number of phases 3 phases
[Us] rated supply voltage 380...480 V - 15...10 %
Motor power kW 75 kW normal duty

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
55 kW heavy duty

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Motor power hp 100 hp normal duty
75 hp heavy duty
Line current 131.3 A 380 V normal duty
112.7 A 480 V normal duty
98.9 A 380 V heavy duty
86.9 A 480 V heavy duty
Prospective line Isc 50 kA
Apparent power 93.7 kVA 480 V normal duty
72.2 kVA 480 V heavy duty
Continuous output current 145 A 2.5 kHz normal duty
106 A 2.5 kHz heavy duty
Maximum transient current 159.5 A 60 s normal duty
159 A 60 s heavy duty
Asynchronous motor control Constant torque standard
profile Variable torque standard
Optimized torque mode
Synchronous motor control profilePermanent magnet motor
Output frequency 0.0001...0.5 kHz
Nominal switching frequency 2.5 kHz
Switching frequency 2...8 kHz adjustable
2.5...8 kHz with derating factor
Safety function STO (safe torque off) SIL 3
Discrete input logic 16 preset speeds
Communication port protocol Ethernet
Modbus serial
Modbus TCP
Option card Communication module Profibus DP V1 slot A
Communication module Profinet slot A
Communication module DeviceNet slot A
Communication module Modbus TCP/EtherNet/IP
slot A
Communication module CANopen daisy chain
RJ45 slot A
Communication module CANopen SUB-D 9 slot A
Communication module CANopen screw

1 / 11
terminals slot A
Digital and analog I/O extension module slot A/slot
B
Output relay extension module slot A/slot B
Communication module Ethernet IP/Modbus
TCP/MD-Link slot A

Complementary
Output voltage <= power supply voltage
Permissible temporary current boost 1.1 x In 60 s normal duty
1.5 x In 60 s heavy duty
Motor slip compensation Adjustable
Automatic whatever the load
Can be suppressed
Not available in permanent magnet motor law
Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s
S, U or customized
Braking to standstill By DC injection
Protection type Line supply overvoltage drive
Line supply phase loss drive
Line supply undervoltage drive
Overcurrent between output phases and earth drive
Thermal protection motor
Thermal protection drive
Safe torque off motor
Motor phase break motor
Safe torque off drive
Overheating drive
Short-circuit protection drive
Motor phase break drive
Overspeed drive
Break on the control circuit drive
Overvoltages on the DC bus drive
Overload of output voltage drive
Frequency resolution Display unit
Analog input
Electrical connection Removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 control
Screw terminal 95...120 mm² AWG 3/0...250 kcmil motor
Screw terminal 95...120 mm² AWG 3/0...250 kcmil line side
Connector type RJ45 Ethernet/Modbus TCP on the remote graphic terminal
RJ45 Modbus serial on the remote graphic terminal
Physical interface 2-wire RS 485 Modbus serial
Transmission frame RTU Modbus serial
Transmission rate 10/100 Mbit/s Ethernet IP/Modbus TCP
4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Data format 8 bits, configurable odd, even or no parity Modbus serial
Type of polarization No impedance Modbus serial
Number of addresses 1...247 Modbus serial
Method of access Slave Modbus TCP
Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10
mA overload and short-circuit protection
External supply for digital inputs 24 V DC 19...30 V <= 1.25 mA overload and short-
circuit protection
Internal supply for digital inputs and STO 24 V DC 21...27 V <= 200 mA overload and
short-circuit protection
Local signalling 3 LEDs local diagnostic
3 LEDs dual colour embedded communication status
4 LEDs dual colour communication module status
1 LED red presence of voltage
Width 290 mm
Height 922 mm
Depth 323 mm
Product weight 58 kg
Analogue input number 3
Analogue input type Software-configurable voltage AI1, AI2, AI3 0...10 V DC 30 kOhm 12 bits
Software-configurable current AI1, AI2, AI3 0...20 mA/4...20 mA 250 Ohm 12 bits

2 / 11
Discrete input number 8
Discrete input type Programmable DI1...DI6 24 V DC 3.5 kOhm
Programmable as pulse input DI5, DI6 0...30 kHz 24 V DC
Safe torque off STOA, STOB 24 V DC > 2.2 kOhm
Input compatibility Level 1 PLC EN/IEC 61131-2 DI1...DI6 discrete input
Level 1 PLC IEC 65A-68 DI5, DI6 discrete input
Level 1 PLC EN/IEC 61131-2 STOA, STOB discrete input
Discrete input logic Positive logic (source) DI1...DI6 < 5 V > 11 V
Negative logic (sink) DI1...DI6 > 16 V < 10 V
Positive logic (source) DI5, DI6 < 0.6 V > 2.5 V
Positive logic (source) STOA, STOB < 5 V > 11 V
Analogue output number 2
Analogue output type Software-configurable voltage AO1, AO2 0...10 V DC 470 Ohm 10 bits
Software-configurable current AO1, AO2 0...20 mA 10 bits
Sampling duration 2 ms +/- 0.5 ms DI1...DI4 discrete input
5 ms +/- 1 ms DI5, DI6 discrete input
5 ms +/- 0.1 ms AI1, AI2, AI3 analog input
10 ms +/- 1 ms AO1 analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error +/- 0.15 % of maximum value analog input AI1, AI2, AI3
+/- 0.2 % analog output AO1, AO2
Relay output number 3
Relay output type Configurable relay logic R1 fault relay NO/NC 100000 cycles
Configurable relay logic R2 sequence relay NO 100000 cycles
Configurable relay logic R3 sequence relay NO 100000 cycles
Refresh time 5 ms +/- 0.5 ms R1, R2, R3 relay output
Minimum switching current 5 mA 24 V DC R1, R2, R3 relay output
Maximum switching current 3 A 250 V AC resistive 1 R1, R2, R3 relay output
3 A 30 V DC resistive 1 R1, R2, R3 relay output
2 A 250 V AC inductive 0.4 7 ms R1, R2, R3 relay output
2 A 30 V DC inductive 0.4 7 ms R1, R2, R3 relay output
Isolation Between power and control terminals
Functionality Full
Specific application Utility
IP degree of protection IP21
Discrete and process manufacturing Building - HVAC compressor centrifugal
Building - HVAC compressor centrifugal
Food and beverage processing other application
Mining mineral and metal fan
Mining mineral and metal pump
Oil and gas fan
Water and waste water other application
Building - HVAC screw compressor
Food and beverage processing pump
Food and beverage processing fan
Food and beverage processing atomization
Oil and gas electro submersible pump (ESP)
Oil and gas water injection pump
Oil and gas jet fuel pump
Oil and gas compressor for refinery
Water and waste water centrifuge pump
Water and waste water positive displacement pump
Water and waste water electro submersible pump (ESP)
Water and waste water screw pump
Water and waste water lobe compressor
Water and waste water screw compressor
Water and waste water compressor centrifugal
Water and waste water fan
Water and waste water conveyor
Water and waste water mixer
Power range 55...100 kW 380...440 V 3 phases
55...100 kW 480...500 V 3 phases
Motor starter type Variable speed drive

Environment
insulation resistance > 1 mOhm 500 V DC for 1 minute to earth
noise level 62.4 dB 86/188/EEC

3 / 11
power dissipation in W 174 W natural convection 380 V 2.5 kHz
1369 W forced convection 380 V 2.5 kHz
volume of cooling air 295 m3/h
operating position Vertical +/- 10 degree
THDI <= 48 % from 80...100 % of load IEC 61000-3-12
electromagnetic compatibility 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
Electrostatic discharge immunity test level 3 IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
pollution degree 2 EN/IEC 61800-5-1
vibration resistance 1.5 mm peak to peak 2...13 Hz IEC 60068-2-6
1 gn 13...200 Hz IEC 60068-2-6
shock resistance 15 gn 11 ms IEC 60068-2-27
relative humidity 5...95 % without condensation IEC 60068-2-3
ambient air temperature for operation 50...60 °C with derating factor
-15...50 °C without derating
ambient air temperature for storage -40...70 °C
operating altitude <= 1000 m without derating
1000...4800 m with current derating 1 % per 100 m
environmental characteristic Chemical pollution resistance class 3C3 EN/IEC 60721-3-3
Dust pollution resistance class 3S3 EN/IEC 60721-3-3
standards EN/IEC 61800-3
EN/IEC 61800-3 environment 1 category C2
EN/IEC 61800-3 environment 2 category C3
UL 508C
EN/IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
product certifications ATEX INERIS
ATEX zone 2/22
CSA
TÜV
UL
REACH
DNV-GL
marking CE

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1426 - Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available

Dimensions

Views: Front - Left

4 / 11
Drives Without IP21 Top Cover

Views: Left - Rear

5 / 11
Clearances

X1 X2 X3

≥ 100 mm (3.94 in.) ≥ 100 mm (3.94 in.) ≥ 10 mm (0.39 in.)

Mounting Types

6 / 11
Mounting Type A: Individual IP21

a ≥ 110 mm (4.33 in.)


=
Mounting Type B: Side by Side IP20 (Possible, 2 Drives Only)

Mounting Type C: Individual IP20

a ≥ 110 mm (4.33 in.)


=

Single or Three-Phase Power Supply with Upstream Breaking via Line Contactor

Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in
accordance with standard IEC/EN 60204-1

7 / 11
(1) Use digital output R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 :Line Contactor
Q2, Circuit breakers
Q3 :
S1, Pushbuttons
S2 :
T1 : Transformer for control part

Single or Three-Phase Power Supply with Downstream Breaking via Switch Disconnector

Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in
accordance with standard IEC/EN 60204-1

(1) Use digital output R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
Q1 : Switch disconnector

Control Block Wiring Diagram

8 / 11
(1) Safe Torque Off
(2) Analog Output
(3) Digital Input
(4) Reference potentiometer
(5) Analog Input
A1 : ATV6.. Drive
R1A, Fault relay
R1B,
R1C :
R2A, Sequence relay
R2C :
R3A, Sequence relay
R3C :
Sensor Connection

It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.

Sink / Source Switch Configuration

The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
Š Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
Š Set the switch to Ext if using PLC outputs with NPN transistors.
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs

Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs

9 / 11
Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs

Switch Set to EXT Position Using an External Power Supply for the DIs

Derating Curves

40 °C (104 °F) - Mounting type A, B and C


50 °C (122 °F) - Mounting type A, B and C
60 °C (140 °F) - Mounting type B and C
In : Nominal Drive Current
SF : Switching Frequency

Our Proposal: Circuit Breaker + Contactor + Drive for Motor Power 75 kW and 380 or 440 VAC

Motor Power Icu Breaker Contactor (*) Motor Starter


(kW) (kA)

75 kW for 380 V 36

LV430830 LC1D115P7 ATV630D75N4

10 /
11
75 kW for 440 V 35

LV430830 LC1D115P7 ATV630D75N4


Non contractual pictures.
(*) You can select the contactor proposed or variants. Please consider examples hereafter or follow the link to the complete offer.

Motor Power Coil voltage 24 48 110 115 220 230 400 Other
kW VAC - 50/60 Hz

75 LC1D115 .. B7 E7 F7 FE7 M7 P7 V7 Complete Offer

Motor Power Coil voltage 24 48 Other


kW VDC - U 0.75…1.25 Uc

75 LC1D115 .. BD ED Complete Offer


(**) You can select the breaker proposed or variants. Please consider examples hereafter or follow the link to the complete offer.

Motor Power Icu Breaker with Icu Breaker with Icu Breaker with Other
kW (kA) capacity level (kA) capacity level (kA) capacity level
F F H H N N

75 kW for 380 V 36 LV430830 70 LV430834 50 LV430832 Complete Offer

75 kW for 440 V 35 LV430830 65 LV430834 50 LV430832 Complete Offer

11 /
11