Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Journal of Asian Architecture and Building Engineering

ISSN: (Print) (Online) Journal homepage: www.tandfonline.com/journals/tabe20

Study on heat storage mechanism of building wall


based on passive housing

Jizhi Zhang

To cite this article: Jizhi Zhang (2023) Study on heat storage mechanism of building wall based
on passive housing, Journal of Asian Architecture and Building Engineering, 22:2, 402-414, DOI:
10.1080/13467581.2022.2046001

To link to this article: https://doi.org/10.1080/13467581.2022.2046001

© 2022 The Author(s). Published by Informa


UK Limited, trading as Taylor & Francis
Group on behalf of the Architectural
Institute of Japan, Architectural Institute of
Korea and Architectural Society of China.

Published online: 11 Mar 2022.

Submit your article to this journal

Article views: 984

View related articles

View Crossmark data

Full Terms & Conditions of access and use can be found at


https://www.tandfonline.com/action/journalInformation?journalCode=tabe20
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING
2023, VOL. 22, NO. 2, 402–414
https://doi.org/10.1080/13467581.2022.2046001

Study on heat storage mechanism of building wall based on passive housing


Jizhi Zhang
School of Architectures & Art design, Southeast University Chengxian College, Nanjing, Jiangsu China

ABSTRACT ARTICLE HISTORY


Building energy consumption has seriously affected the economic development of various Received 1 July 2021
countries. Through in-depth analysis of the basic characteristics of passive buildings in Accepted 18 February 2022
Germany, this paper establishes a building geometric model with traditional heat collecting KEYWORDS
wall rooms. By optimizing the heat transfer model and boundary conditions of the building, the Building landscape; thermal
thermal environment of the model under steady-state and transient conditions is simulated energy storage; passive
and analyzed respectively. The heat collection characteristics of the outer surface of the heat house; thermodynamic
collection wall in winter are deeply discussed. The distribution characteristics of the tempera­ analysis
ture field and wind speed field of the vent and the room as well as the effects of the wall size
parameters and the surface structure of the heat collection wall on the heat collection
efficiency are compared. Through the test and analysis of the heat collection effect of passive
buildings, it is proved that the structural technology studied in this paper has an obvious effect
on architectural design and transformation, and has important application value. It provides
a theoretical basis for the field test of transforming the existing passive solar house.

1. Introduction
This paper investigates and analyzes the thermal envir­
China’s passive building energy-saving design concept onment, energy consumption, air tightness and resi­
is in the exploratory stage. At present, its ultra-low dents’ comfort, compares the standards of the core
energy consumption design standard mainly refers to technologies of passive buildings, and determines the
the German “passive house” design certification stan­ energy consumption and comfort control indexes of
dard. At present, three provinces in cold areas have houses in severe cold, cold, hot summer and cold
issued their own passive ultra-low energy consump­ winter areas. Make overall improvement measures
tion building design standards. Although these three from the heat transfer coefficient of enclosure struc­
design standards are different, they still take ture, avoidance of thermal bridge, air tightness
Germany’s “passive house” as design certification stan­ requirements, requirements of fresh air system and
dard. Therefore, this paper mainly analyzes the archi­ combine with the use of renewable energy to make
tectural design standard of “passive house” in overall improvement measures.
Germany (McMahon et al. 2018; Rathore and Kumar With the opening of the housing market and the
Shukla 2021; Rathore and Shukla 2021). The main char­ rapid development of real estate, China’s housing con­
acteristics of passive buildings represented by “passive struction has also developed. However, early real
houses” in Germany are low building energy consump­ estate developers and designers did not pay enough
tion and high indoor comfort. These characteristics are attention to building energy consumption and build­
easier to highlight in new buildings and better reflect ing energy conservation. In the design, they often took
the efficiency of “passive house” buildings (Rathore, the lower limit or even directly ignored the energy
Shukla, and Gupta 2020; Li et al. 2017). conservation index, resulting in the further increase of
In recent years, passive architecture has emerged in building energy consumption (McMahon et al. 2018).
China. There are few examples of passive architecture, At present, the application of building energy-
and there is a lack of experience in the theory and saving technology is mainly divided into two cate­
construction of passive architecture design. Due to gories: the first is to install various renewable energy
the shortage of resources, energy conservation cam­ collection equipment in buildings to reduce the
paigns are carried out all over the world, and China is demand for non renewable resources through the col­
no exception. Under the general requirements of lection and use of renewable energy, which is open
national building energy conservation, the importance source; the second is to reduce the energy loss of
of building energy conservation has been realized in buildings in the use process through various technical
the planning and design of new towns (Bai et al. 2018; or structural measures so as to reduce the demand of
Wang, Zhang, and Yu 2019; Hao, Ma, and Geng 2018). buildings for non renewable resources, which is

CONTACT Jizhi Zhang fudaoyi76r@163.com Southeast University Chengxian College, Nanjing, Jiangsu 210088, China
© 2022 The Author(s). Published by Informa UK Limited, trading as Taylor & Francis Group on behalf of the Architectural Institute of Japan, Architectural Institute of Korea and
Architectural Society of China.
This is an Open Access article distributed under the terms of the Creative Commons Attribution-NonCommercial License (http://creativecommons.org/licenses/by-nc/4.0/), which
permits unrestricted non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited.
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING 403

throttling. In the process of daily use and maintenance transformation of relevant technologies, successfully
of buildings, the heat loss of domestic and foreign reached the ultra-low energy consumption evaluation
maintenance structures accounts for the largest pro­ standard, and finally put into use in 2013. They also
portion of overall energy consumption. Therefore, the received good feedback in the actual use process. In
skill benefit brought by the second type of energy- terms of reducing building energy consumption and
saving method is more significant. Among them, the improving indoor comfort, the passive building energy-
passive ultra-low energy consumption buildings repre­ saving design concept is well realized (Yao 2017).
sented by German “passive house” buildings have The research project in this paper is located in the
been fully developed in Europe (Rathore and Kumar cold area of China’s architectural climate division. The
Shukla 2021). In recent years, China has also begun to total area of the project is about 3800 m2, with a total
learn from the formulation strategy of passive ultra- of 3 floors. The passive building design concept and
low energy consumption building design standards in ultra-low energy consumption design standard are
Germany. How to transform its standards into appro­ demonstrated for public buildings and residential
priate and realizable technologies, and realize passive buildings respectively. As a demonstration project,
buildings to reduce building energy consumption the completed part of the project is in good operation
while meeting people’s architectural design and in strict accordance with the design standards of pas­
energy-saving needs for indoor comfort (Rathore and sive ultra-low energy consumption residential build­
Shukla 2021) is now under great consideration. ings in cold areas and the German Phi certification
In 2006, Japan revised the law on rationalization of standards. However, as an experimental project, there
energy use issued in 1979 for the fifth time to further must be some parts that can be improved. In view of
emphasize the “Declaration obligation of energy- these problems existing in the project practice, com­
saving measures”. It emphasizes the declaration of bined with relevant data investigation, this paper stu­
building energy-saving measures and their effects for dies and analyzes the design strategy of passive
new buildings to ensure the control of building energy building exterior wall insulation system in cold areas.
consumption (Rathore, Shukla, and Gupta 2020). In
2007, EU countries also began to pay attention to
2. Related work
building energy consumption control because of
energy problems. In March of that year, they put for­ China’s passive building energy-saving design concept
ward three “20%” concepts. By 2020, they will realize is in the exploratory stage. At present, its ultra-low
building energy consumption control in three aspects: energy consumption design standard mainly refers to
greenhouse gas emission reduction, one-time energy the German “passive house” design certification stan­
consumption and the proportion of renewable energy dard. At present, three provinces in cold areas have
(Li et al. 2017). Passive building design and its ultra-low issued their own passive ultra-low energy consump­
energy consumption standards have developed tion building design standards. Although these three
rapidly in the EU. In 2008, Daniel Sheila published the design standards are different, they still take
book solar energy – passive heating and cooling, Germany’s “passive house” design certification stan­
which describes in detail the solar energy utilization dard as the main reference. Therefore, this paper
strategy of passive buildings under different regions mainly analyzes the architectural design standard of
and climatic factors (Bai et al. 2018). In 2010, the EU “passive house” in Germany.
issued the building energy efficiency directive 2010 Passive buildings use external energy solar energy
(EPBD 2010). It clearly stipulates that after to realize indoor temperature self-regulation, make full
31 December 2020, its member states must be extre­ use of solar heat energy, and meet the requirements of
mely strict with zero energy consumption buildings “warm in winter and cool in summer”. Passive build­
whether they are officially put into use or new build­ ings can keep warm by collecting and absorbing solar
ings (Wang, Zhang, and Yu 2019). By 2012, the number heat; use the reasonable layout of the building and the
of passive buildings in the world will reach more than internal space to strengthen air convection to reduce
37,000 (Hao, Ma, and Geng 2018). the indoor temperature; use energy-saving and envir­
When passive buildings enter China, their research onment-friendly materials to store solar thermal
and application areas are mainly concentrated in severe energy so as to reduce energy consumption.
cold and cold areas. In 2007, China’s Ministry of housing
and urban rural development conducted a series of
2.1. Passive landscape wall insulation structure
cooperation with the German Energy Agency, including
some passive construction projects (Chen, 2017). In The main characteristics of passive buildings repre­
2011, China’s first passive construction project, sented by “passive houses” in Germany are low build­
Qinhuangdao “on the water side” experimental residen­ ing energy consumption and high indoor comfort.
tial area, was officially launched. China and Germany These characteristics are easier to highlight in new
jointly participated in the design and localization buildings and better reflect the efficiency of “passive
404 J. ZHANG

Table 1. “Passive house” Building certification standard.


Heating Unit Approach Standard Alternative standards
Heating demand 2 � 15 -
½KWh=m a�
Cooling load ½W=m2 � � - 10
refrigeration
Dehumidification demand ½KWh=m2 a� � 15+
Cooling load ½W=m2 � � -
Air tightness
Air change times -pressure test n50 ½1=h� � 0.6
renewable energy
Demand ½KWh=m2 a� � 45 � 15kwh=m2 a
Output ½KWh=m2 a� � 60 Compensation by
changing production

housing” buildings. The relevant standards of “passive of “passive house” buildings can be seen from the
house” buildings can also be more intuitively reflected above that the heating energy consumption demand
(Chen, Wen, and Ding 2017). is less than or equal to 15kWh=m2 � a at room tempera­
As shown in Table 1, “passive house” building certi­ ture 20°C. It can be seen that the standard of “passive
fication standards are mainly divided into four items: house” in Germany is about 1/3 of the energy-saving
heating demand, that is, the total annual heating is less standard in cold areas. As shown in table 2.6, the cur­
than or equal to 15 kwh/(m2 · a) or its heating load is rent skill standard in cold areas is equivalent to the
less than or equal to 10 W/m2; refrigeration demand, energy-saving standard in Germany in 2009.(Chen 2019)
that is, the total annual refrigeration energy consump­
tion is less than or equal to 15 kwh/(m2 · a) or the
refrigeration load is less than or equal to 10 W/m2, 3. Definition and building standard of cold
while ensuring that the air dehumidification demand area
meets the standard. Air tightness, which is to ensure Climate conditions have an important impact on the
that the indoor pressure test – air change test n50 is less design and application of building energy-saving mea­
than or equal to 0.6 times per hour; the demand for sures. To study building energy-saving design, we
renewable energy and the requirements for renewable must first understand the relevant climate and geogra­
energy and renewable primary energy are newly intro­ phical characteristics of the studied area.
duced in 2015. That is to add the requirements for
renewable energy on the basis of the total consumption
of non renewable energy to further reduce the depen­ 3.1. Definition and characteristics of cold regions
dence of buildings on non renewable energy. While
meeting these standards, it is also necessary to ensure According to the requirements of building thermal per­
that the indoor temperature is 20–26 °C and the indoor formance, China classifies the climate characteristics into
relative humidity is 30% – 60% (Ma and Lu 2017). 7 regions and 20 sub regions. This paper analyzes and
studies the cold areas. China’s <General Principles for
Civil Buildings> stipulates in detail that the climate con­
2.2. Architectural comparison of China’s existing ditions in cold areas are like this: the daily average tem­
energy-saving buildings and Germany’s “passive perature in January is 0–10 °C; the daily average
housing” temperature in July is 18–28 °C; the daily average tem­
perature of 90–145 days per year is ≤ 5 °C; and the daily
According to the existing energy-saving design stan­ average temperature of less than 80 days is ≥ 25 °C (Wang
dards of residential buildings in severe cold and cold 2019).
areas in China and the current “passive housing” con­
struction standards in Germany, China adopts the heat
consumption index, while Germany adopts the heating 3.2. Design standard for exterior wall thermal
energy consumption demand. Because there are certain insulation system of passive buildings in cold
differences in calculation methods and requirements for areas
indoor temperature, the data comparison is only for
The design standard of passive ultra-low energy
reference. Cold regions with similar climate level to
consumption buildings mainly refers to the
Germany are selected as a reference. Compared with
German “passive house” architectural design certifi­
the current 65% building energy saving standard in cold
cation standard. At present, provinces in cold areas
areas, the standard stipulates that when the room tem­
have successively issued energy-saving design stan­
perature is maintained at 18 °C, the heat consumption
dards for passive ultra-low energy consumption
index of the house is less than or equal to
buildings in their own province. However, due to
41:48kWh=m2 � a (Deng 2019). The heating standard
the difference of local climate, there are certain
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING 405

Table 2. Comparison of design standards for exterior wall insulation system.


Unit: heat transfer coefficient K½W=ðm2 � KÞ�

Design standard for passive ultra low energy consumption buildings in Current building design energy saving standards in
maintenance structure cold areas cold areas
exterior wall ≤0.15 ≤0.50
Doors and windows ≤0.10 ≤2.70
roofing ≤0.15 ≤0.50
underground structure ≤0.19 ≤0.60

differences in design standards. In order to facilitate data in the design; indoor air dew point temperature is
research, we choose <Passive low energy consump­ 10.12 °C; and the inner surface temperature of the
tion buildings – residential buildings in severe cold most unfavorable thermal bridge is 17.48 °C.
and cold areas>in national building standard design Combined with the data given by the passive house
atlas 16j908-8 as standards on severe cold and cold certification software (PHPP) (Liguang and Jinyu 2019),
areas. It is compared with the cold area related as is shown in Table 3.
standards in the current domestic design standard The thickness of insulation layer of different wall
for energy efficiency of residential buildings in materials determines the heat storage and insula­
severe cold and cold areas in <Design standard for tion capacity of the wall, which affects the main
energy efficiency of residential buildings in severe performance parameter of heat transfer coefficient
cold and cold areas>(Guo 2019), as is shown in of enclosure structure.The insulation layer is pro­
Table 2. vided with fire isolation belt according to relevant
It can be seen intuitively from the above data that fire protection regulations. The material is vertical
the thermal insulation and energy-saving design stan­ silk rock wool. Compared with the conventional
dards of passive building exterior wall structure and rock wool board, the vertical silk rock wool has
structure in direct contact with the exterior wall in cold vertical fiber arrangement direction, stronger tensile
areas are significantly higher than the relevant stan­ resistance and the same class A flame retardancy.
dards of conventional building energy-saving design The thermal conductivity is slightly increased to
in cold areas. When designing the external wall insula­ 0.046 w/(m · K) (Huang, Xie, and Chen 2019). The
tion system of passive buildings in cold areas, we thermal insulation structure nodes of the outer wall
should fully consider the practice status of the existing are shown in Figure 1.
external wall insulation system of buildings in China In the external thermal insulation system of the
and the combination of foreign advanced energy- building, the thicker thermal insulation layer greatly
saving design concepts of passive buildings (Jiang weakens the impact of the thermal bridge phenom­
and Yin 2019). enon on the building. The temperature of the inner
wall corner is lower than that of the inner wall, but
higher than the dew point temperature. There will be
4. Passive building wall structure no condensation and mildew, and the service life of
the wall will be relatively increased. For cold northern
4.1. Analysis of passive wall insulation structure
areas, this method can effectively reduce building
In order to meet the design standard of ultra-low energy consumption.
energy consumption and combined with the current Figure 1 shows that the analysis of thermal insula­
situation of the project, after comparison, the external tion structure is at the opening of wall doors and
wall insulation system of graphite polystyrene board windows. Aluminum clad low-e (6 + 12A + 6 + 12A
(GEPS) thin plastering external wall with relatively + 6) double insulating glass doors and windows are
mature construction technology is selected for the selected for the external windows and doors.
external wall insulation system. The external wall ther­ The dew point of the empty glass is – 60 °C, the air
mal insulation system gives priority to the thermal tightness is grade 8, and the heat transfer coefficient
insulation performance in winter. Therefore, the indoor (calculated by the whole window after installation) is
temperature in winter is set as 18 °C and the outdoor 0.8 W/(m2 · K) (Huang, Xie, and Chen 2019). The instal­
temperature is – 5 °C according to the relevant climate lation method is shown in Figure 2.

Table 3. Parameters of insulation layer of graphite polystyrene board.


Insulation index parameter
Insulation size (length × high × thick) 600 mm×600 mm×150 mm
Single block thickness Two specifications:75 mm, 150 mm
Flame retardancy B1
thermal conductivity 0.033 W/(m·K)
406 J. ZHANG

Figure 1. Schematic diagram of wall insulation structure of the project.

Figure 2. Project exterior wall opening thermal insulation structure.


The standard heat cut-off bridge mode is adopted, in 4.2. Analysis of thermal insulation structure at
which the thermal insulation cushion block is preset on the connection of wall, roof and underground
the outside of the wall, the “L” angle steel is fixed on the structure
cushion block, and then the doors and windows are fixed
on the angle steel. According to the ultra-low energy Extruded polystyrene board (XPS) is selected for roof
consumption design standard, the waterproof and air insulation, with a thickness of 150 mm. Although it is in
isolating film is laid on the inside of the door and window the form of slope roof, the junction between the outer
frame, and the air permeable film is laid on the outside. wall and the roof is still in the form of parapet because of
The self expanding sealing tape is used to fill the gap at organized water apron. The insulation structure here
the joints to ensure the tightness. The frame and the adopts the insulation layer to cover the outer, top and
thermal insulation layer are located in the same vertical inner sides of the parapet to maintain integrity and con­
position. It helps to prevent heat loss (Huang, Wu, and nect with the roof insulation layer. At the same time, the
Zhang 2018). insulation layer on the inner side and top of the daughter
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING 407

shall be waterproof, the top of the parapet shall be trea­ collection wall and the distribution of air tempera­
ted with waterproof cover plate, and the water outlet of ture field and velocity field under two different
the parapet shall be treated. Pay attention to the water­ seasonal conditions are simulated, it is recom­
proof of the insulation layer (Zhou, Bu, and Zhu 2019). mended to model separately according to different
The insulation layer of the underground structure ventilation modes. Under the heating condition in
shall be laid below the frozen soil layer. The extruded winter, all the vents on the glass cover are closed,
polystyrene board (XPS) material with a thickness of and all the upper and lower vents on the heat
150 mm is selected as the insulation material accord­ collection wall are opened. Because the purpose of
ing to the design standard. Waterproof materials are the experiment is to discuss the influence of heat
laid inside and outside the extruded polystyrene board collection wall on indoor heating in winter, the
(XPS). Considering the small building volume, there is south wall structure can be regarded as a single-
no organized water dispersion (Wei and Zhu 2018). layer windowless composite wall. At this time, the
model can be simplified into two parts: fluid
domain Part1 and solid domain part2, and four
4.3. Application analysis of other building vents connect the indoor space and air interlayer
energy-saving measures (Yu 2018).
Since the main body of the project is the cast-in-place The positive direction of the X axis represents the
concrete frame structure supplemented by the aerated true north direction of the geographical location and
concrete block filling, it mainly relies on the inner the direction of the thickness of the trump heat collec­
plastering treatment of the outer envelope to achieve tion wall; The Z-axis direction is the height direction of
the air tightness standard. Transparent enclosure struc­ the collector wall system; the Y-axis direction is the
ture adopts aluminum-clad wood three-wave two- width direction of the experimental room, and the
cavity insulating glass doors and windows as men­ positive direction of the Y-axis is the due east direction
tioned above, and the overall heat transfer coefficient of the geographical coordinates. The model air inter­
is controlled at ≤0.8 W/(m2•K), meeting the design layer is 0.1 m thick, 2.8 m high and 3 m wide (Tang,
standard of ultra-low energy consumption. In terms Zhong, and Yang 2018).
of fresh air system, according to the standard heat
recovery fresh air system index recommended by the 5.2. Boundary conditions and parameter settings
German Passive Institute, it is selected among domes­
tic major manufacturers, and finally reaches the theo­ The calculation area is meshed with The Integrated
retical value of 79% effective “heat” recovery efficiency Computer Engineering and Manufacturing code for
in heating period and 69% effective “cold” recovery Computational Fluid Dynamics (ICEMCFD), and the
efficiency in cooling period, so as to meet the design cylindrical vent surface is divided by O-Block. Because
requirements (Zhu, Wei, and Zhang 2018). of the large velocity gradient and temperature gradi­
The heat collecting wall is also a passive building ent of the fluid here, it is locally encrypted [29]. After
energy-saving measure that can effectively reduce reading the grid, check the grid first. According to the
building energy consumption. The structure uses sun­ software operation process, various parameter settings
light to irradiate the dark heat storage wall with glass are shown in Table 4:
cover outside to heat the interlayer air between the The test temperature range is 0 ~ – 50 ° C and the
transparent cover plate and the outer surface of the outdoor design temperature of the region −20°C is
thick wall. Through the action of thermal pressure, the selected as the set value of the free surface tempera­
air flows into the room to supply indoor heat. At the ture boundary of the heat collector. According to the
same time, the wall itself directly guides indoor heat analysis of the experimental monitoring data, the tem­
through heat transfer and stores some energy, The perature of other walls except the south-oriented heat
energy stored in the wall at night is released indoors; collecting wall does not fluctuate much and remains
on the other hand, the heat collection wall loses heat stable at about 12°C in the heating cycle. Therefore,
to the outside by means of conduction, convection 285.15 K is taken as the set value for the temperature
and radiation through glass cover. boundary of other walls. The boundary conditions of
the wall are shown in Table 5.
The wall structure of the collector wall is the same
5. Experimental analysis of passive building size as the experimental room, which is a composite
wall thermal energy storage structure of 0.37 m brick wall + 0.1 m benzene board +
0.3 mm thick aluminum plate. The thickness of the air
5.1. Building CFD model
interlayer is 0.1 m, and the aluminum plate is closely
The opening and closing modes of vents are differ­ attached to the benzene plate. The solar radiation
ent in different seasons in winter and summer. If absorption coefficient on the surface of the aluminum
the heat collection characteristics of the heat plate is 0.9, the emissivity is 0.1, the glass cover is 4 mm
408 J. ZHANG

Table 4. Experimental index parameter settings.


Set up items parameter numerical value
General Gravity acceleration select Z direction −9.82 m/s2
Models RNG turbulence model at low Reynolds number All parameters remain the default values
DO Radiation model Geographic location information, time zone, date ,44.27° N, 85.94° E, Dongba District, December 23 r
Cell Zone Conditions initial temperature 283.15 K
Solution Methods COUPLED-algorithm Second order up wind
Body Force Weighted
Solution Controls Relaxation coefficient default
Monitors Plane temperature of collector wall y = 0.25 m (Plane of vent), x = −0.47 m
Solution Initialization Standard initialization, 280.15 K
initial temperature
Number of iterations 20,000

Table 5. Boundary condition setting.


Boundary surface Boundary type Set value
Inlet (lower vent) Coupled coupled wall, the boundary type is opaque Internal emissivity 0.85, not involved in solar radiation
Outlet (upper vent) Coupled coupled wall, the boundary type is opaque Internal emissivity 0.85, not involved in solar radiation
External surface of collector wall Coupled coupled wall, the boundary type is opaque Internal emissivity 0.85, not involved in solar radiation
Glass cover Mixed mixed wall; the boundary type is translucent. Outdoor temperature −25 °C, participate in solar radiation.
Other wall surface The temperature wall, the boundary type is opaque. 285.15 K, does not participate in solar radiation.

flat glass, the solar radiation transmission coefficient is that is to say, whether the insulation layer is com­
0.85, and the absorption coefficient is 0.15. The physical plete.Testo 425 anemometer is used to measure
parameters used in the simulation are shown in Table 6. the wind speed and temperature at different
Finally, the iterative calculation results are visualized locations.
and analyzed in the result. Indoor temperature field analysis:Figure 3 shows
the temperature distribution given by the infrared
thermal imaging equipment in the building. Figure 3
6. Simulation results of thermal environment
also shows the temperature field cloud map of the
under steady-state conditions in winter
section x = 1.5 m, Y = 0.25 m, and Z = 1.5 m in the
This section mainly simulates the temperature field calculated area. It can be seen that, in the steady state,
and velocity field distribution characteristics of the temperature distribution of the section presents
indoor air, vents and the surface of the collector a trend of increasing along the Z-axis and decreasing
wall when the heat exchange and air flow inside along the X-axis. The maximum temperature differ­
the air interlayer of the collector wall reach a stable ence between the upper and lower parts of the room
state. can be up to 7°C. Under partly cloudy weather condi­
tions (namely, the sun direction vector X:0.8844,
Y:0.0022,Z:-0.466 and Sunshinefactor is set as 0.75),
6.1. Temperature field analysis the simulated value of the room center point P is
The inspection or test of the building and the taken as the indoor average temperature, and the
inspection of the integrity of the external wall indoor average temperature is calculated as 12.36°C
insulation layer of the building, which is the ther­ by steady-state solution.
mal bridge inspection, can be carried out for local Analysis of the temperature field of the vent: It can be
or single-sided walls. This is mainly achieved seen from the simulation results in Figure 3 that the
through the infrared thermal imaging equipment. temperature difference between the center points of
During detection, the infrared thermal imaging the upper and lower vents is about 27.2°C in the steady
equipment can view the detection target and state. The error between actual measurement and simu­
record the imaging changes. Through the color lation is mainly due to the small amount of outdoor cold
contrast or change on the imaging, we can check air infiltration caused by the air tightness of the experi­
whether there is a thermal bridge at the target, mental room, causing the temperature near the ground

Table 6. Physical parameters of building materials.


Material name Temperature (°C) Density (kg/m3) Thermal conductivity (W/m⋅K) Specific heat capacity (J/Kg⋅K)
Ordinary clay brick 23 1795 0.83 876
air - Incompressible ideal gas - -
Blue painted aluminum plate 23 2816 201.5 831
Flat glass 23 2635 0.72 760
EPS benzene board 23 34 0.46 1.37
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING 409

Figure 3. Schematic diagram of section temperature distribution at y = 0.25 m, x = 1.5 m, z = 1.5 m.

Figure 4. Schematic diagram of section temperature distribution at x = −0.47 m.

layer, that is, the lower vent to be lower than the simula­ surface of the collector wall: Figure 4 and Figure 5 are
tion result, and the temperature difference between the the distribution cloud diagrams of the temperature field
upper and lower vents is larger than the simulation and the density field on the outer surface of the collec­
result. 3) Analysis of the temperature field on the outer tor wall (ie x = −0.47 m section).

Figure 5. Schematic diagram of section air density distribution at x = −0.47 m.


410 J. ZHANG

Density (Kg/m3)

Figure 6. Schematic diagram of temperature and density distribution on the outside of solar wall.

It can be seen from Fig. 4 and 5 that when the be stable; the wall width is in the range of [0.25 m,
indoor air enters the cavity through the air inlet, the 2.75 m], and the density decreases linearly. On the
temperature is low and the density is high, and then straight line N, the temperature at the center point of
flows upward under the action of buoyancy. While the air outlet is 316.04 K, the temperature at the same
heat exchange occurs with the wall, the temperature height point as the air outlet on the straight line L is
increases and the density decreases. The contours of 325.38 K, and the temperature difference between the
temperature and density are distributed uniformly and two points is 9.34°C. The upper part of the wall has
symmetrically. The highest temperature area is not a temperature about 10°C higher than the air outlet
near the air outlet. The hot air gathers up to the center area.
of the wall during the upward flow. After being
blocked by the top of the wall, it is forced to flow
around on both sides. The density distribution near
6.2. Velocity field analysis
the air outlet is vortex-like. Insert 13 detection points According to the test results in Figure 7, the wind
uniformly on the line L intersecting the section with speeds at the center points of the upper and lower
y = 1.5 m and the line N intersecting with the y = 0.25 m vents are 0.61 m/s and 0.48 m/s, respectively, in oppo­
section respectively, and process the distribution char­ site directions.
acteristics of the wall temperature and density along The distribution of wind speed can be divided into
the Z axis, as shown in Figure 6. three characteristic areas, the first is located in the
As shown in Figure 6, there is an inflection point at upper (hot air area), the second in the bottom (cold
h = 0.4 m and h = 2.0 m, indicating that the tempera­ air convergence area), and the third is the relatively
ture near the upper and lower vents is lower than the stable wind speed under volume force (thermal strati­
adjacent areas, the temperature gradient is larger, and fication area), where the speed is very low, about
the density change rate is larger. When the wall height 0.009 m/s. From the distribution characteristics of tem­
is in the range of [1 m, 2 m], the temperature tends to perature field and wind speed field, it can be seen that

Figure 7. Schematic diagram of section wind speed profile at y = 0.25 m.


JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING 411

in winter heating period, starting from the rising of the 6.3.1. Dynamic analysis of the temperature field of
sun, with the increase of the temperature of the heat the collector wall
collecting wall, the air in the cavity is heated, the heat At the outer surface (wallout) 0.34 m, 1.5 m, 2.46 m and
cycle begins to strengthen with the delay of time, and the inner surface (wallin) 0.34 m, 1.5 m, 2.46 m of the
the speed of the vent also increases. When the velocity solar collector wall (that is, compared with the mea­
field of the vent is stable, the corresponding tempera­ sured A/B/C/A’/B’/ C’ corresponding point) to insert 6
ture field also reaches the maximum value. However, temperature detection points to extract the test data
whether the thermal cycle efficiency between the of the wall temperature distribution when the solar
indoor and the air interlayer changes due to the irradiance changes in 24 hours. Among them, Ts-
change of the diameter of the vent is not directly wallout represents the transient test value of the exter­
displayed in the steady-state wind speed distribution nal surface of the solar collector wall, and Ts-wallin
graph, and further dimensional simulation analysis of represents the transient test value of the internal sur­
the vent is needed. It is worth noting that when the face of the solar collector wall. After data processing, it
wind speed slows down to the thermal cycle stop, if is as shown in Figure 8.
the vent is not closed in time, the cold air “backflow” As time goes by, the temperature gradient on the
phenomenon (ie reverse thermal cycle) will occur. This inner surface of the wall is significantly higher than
process can quickly take away the indoor heat, that on the outer surface. The temperature gradient
increase the temperature difference between day and on the outer surface of the wall increases rapidly from
night in the room, and reduce Indoor thermal com­ 7.2°C at 10:00 to 46.8°C at 15:00. The inner surface of
fort [30]. the wall increases from 4.1 °C at 10:00 to 11.3 °C at
Taking into account the great thermal inertia of 15:00. With the attenuation of radiant illuminance, the
the wall structure of the collector wall, in order to temperature on both the inside and outside of the wall
simulate as accurately as possible the influence of decreases to different degrees. Among them, the tem­
the outdoor solar illuminance on the heat collection perature on the outside of the heat-collecting wall
performance of the collector wall in winter, the decreases most obviously, from the peak value of
transient simulation analysis of the above model is 46.8°C to 20.3 °C at 20:00, and then decreases slowly.
carried out to study the wall and the law of tem­ The inner surface temperature of the wall decreases
perature change in the cavity. slowly from the highest point of 11.3 °C to 7.1 °C, and
then basically tends to be stable. This is because the
thermal inertia of the wall affects its heat storage and
6.3. Analysis of thermal environment test results heat transfer process.
under transient conditions in winter
Considering the great thermal inertia of the wall
6.4. Experimental results
structure of the heat collection wall, in order to
test the influence of outdoor solar irradiance on The research project in this paper is located in the cold
the heat collection performance of the heat collec­ area of China’s architectural climate division. This area
tion wall in winter as accurately as possible, the belongs to the continental climate area. The coldest
transient test analysis of the above model is carried January average temperature is – 15.2 °C; the lowest
out to study the temperature change law in the temperature is – 28.5 °C; the hottest July average
wall and cavity [29]. temperature is 24.3 °C; the highest temperature is

600

450
Solar radiation (W/m2)

300

150

0
10:00 12:00 14:00 16:00 18:00

Time

Figure 8. Schematic diagram of dynamic distribution of temperature on inner and outer surface of heat-collecting wall.
412 J. ZHANG

Table 7. Heat transfer coefficient of optimized structure.


Structure Exterior wall Roofing Floor Interior wall Outer window
K(W/(m2.K)) 0.12 0.11 0.27 0.90 0.82

34.4 °C; and the annual temperature difference is more indicators of passive buildings in this area. Figure 10
than 30 °C. The water fall is mostly concentrated in shows the hourly peak temperature change diagram of
summer, and the snow cover time in winter is long for the building, and analyzes the annual load energy-
more than 4 months. This area belongs to a typical cold saving performance of the building.
climate. It is cold and lasts a long time in winter. It can be seen from Figure 9 that after adopting
Although the maximum temperature in summer also the building envelope system with high-efficiency
reaches more than 30 °C, but the duration is short. thermal insulation, the thermal insulation perfor­
Moreover, based on the architectural characteristics mance of the optimized building is significantly
of this scheme, the school is on holiday in the hottest enhanced. In the coldest season, the indoor tem­
time in summer, and the building will also be closed. perature of the building can be maintained above
Therefore, the general design strategy of this scheme is 10 °C. Only efficient fresh air heat exchange can
to consider only thermal insulation in winter, not ther­ meet the requirements of human comfort without
mal insulation. The total area of the project is about additional main heating equipment.
3800 m2, with a total of 3 floors. The passive building It can be seen from Table 8 that for the passive
design concept and ultra-low energy consumption building after optimizing the main design para­
design standard are demonstrated for public buildings meters of the outer envelope, the unit area load
and residential buildings respectively. in the cooling period is 9.28 kw · H/m2, which is
The key parameters of passive building envelope 38.10% of the standard index. The unit area load in
and thermal bridge structure involved in this paper the heating period is 19.21, which is lower than the
are optimized. Table 7 shows the key parameters of standard index of 1.42 kw · H/m2. Compared with
passive building envelope after optimization. Based on the initial benchmark building performance index,
the climate characteristics of the northern city, the the energy saving rate of the building body can
energy consumption of the building model is simu­ reach 72.34%. Among them, the saving ratio of
lated and the results are summarized. Figure 9 shows heating load is 77.35%, and the energy-saving rate
the variation curve of indoor average temperature and of power consumption is 86.32%.
outdoor average temperature after optimization in In summary, the hourly and outdoor temperature of
winter, Table 8 is the summary of building energy buildings changes greatly, but in the passive buildings
efficiency rate, which summarizes the performance with efficient insulation system and strict air tightness,

Figure 9. Comparison of indoor and outdoor average temperature in winter.

Table 8. Building energy efficiency after optimization.


performance Refrigeration energy Functional energy Total energy Average power CO2Emissions
index consumption (KW.h/m2) consumption (KW.h/m2) consumption (KW.h/m2) consumption (KW.h/m2) (Kg/m2)
Unit area index 9.28 19.21 27.84 28.76 51.08
Energy saving 32.14 77.35 72.34 86.32 61.02
rate (%)
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING 413

the indoor temperature is basically constant at 25 °C, average indoor temperature of the room of the new
which meets the requirements of human comfort and louver collector wall system is 3.1°C higher than that of
indicates that the stability of buildings is high. the room with the traditional collector wall; The max­
imum temperature of the room of the new louver
collector wall system and the room with the traditional
7. Conclusion
collector wall is worse. It is 2.4°C. Therefore, in different
This paper mainly studies and analyzes the teaching weather conditions, the room with the new louvered
buildings in severe cold areas. According to the climate collector wall system can not only increase the average
characteristics of severe cold areas and the timeliness indoor temperature but also reduce the fluctuation of
of such buildings, it is determined to focus on thermal the indoor temperature, compared with the room with
insulation. Through the building energy-saving soft­ the traditional collector wall, and the indoor thermal
ware, the application of passive low-energy technol­ comfort has been significantly improved.
ogy suitable for severe cold areas in teaching buildings The next research goal is to promote the promotion
is studied, the passive low-energy technology is and application of ultra-low-energy buildings as soon
applied to the building scheme, and the energy effi­ as possible, so that our country’s energy-saving cause
ciency is analyzed. It is concluded that the passive low continues to develop, and zero-energy buildings and
energy consumption technology is very suitable for high-capacity buildings are the new research goals.
use in severe cold areas. It will bring huge economic
benefits and has a good application prospect.
This paper chooses a model of campus buildings in
Disclosure statement
severe cold areas, which will be helpful to promote No potential conflict of interest was reported by the
technology and improve people’s awareness of passive author(s).
low energy consumption technology. However, the
passive low energy consumption technology in teach­
Notes on contributor
ing buildings in severe cold areas studied in this paper
not only has regional problems, but also has limita­ I am Zhang Jizhi. I come from China . I am forty years old. I am
tions, so it is difficult to generalize. It is also hoped that a teacher of southeast university Chenxian College. I have
there will be more research on different types of build­ worked there since 2007. Now, I am an associate professor.
ings in the future.
(1) Thermal inertia has a great influence on the heat References
storage and heat transfer process of the collector wall.
Bai, L. G., X. Fu, Z. Y. Mo, and Y. L. Liu. 2018. “Study on the
Geographical location and wall thermal inertia directly
Effect of Fly Ash on the Workability and Mechanical
affect the opening and closing time of the vents during Properties of Concrete [J].” Journal of Beihua Aerospace
the winter heating period of the passive solar house. In Institute of Technology , no. (5).
Xinjiang, the vents should be opened about 2 hours Chen, L. 2017. “Discuss the Application of Building Fire
after the sun rises, and the vents should be closed 1– Protection Technology in Civil Building Design [J].”
2 hours before the sun sets. Beware of cold air “back­ Jiangxi Building Materials , no. (21).
Chen, Z. G. 2019. “Economic Research on Green Building
flowing” and affecting indoor thermal comfort. Technology Based on New Energy-saving Building
(2) In severe cold areas, uneven indoor heating is Materials [J].” Green Environmental Protection Building
the key to improving the indoor thermal environment Materials , no. (3).
of passive solar houses. The indoor heat flow circula­ Chen, Y. W., Q. J. Wen, and H. Z. Ding. 2017. “Research on the
tion should be increased as much as possible, and the Properties of High-volume Fly Ash concrete[J].“ Sichuan
Building Materials (10).
air tightness of windows and glass covers should be
Deng, J. J. 2019. “Development Trend and Development
improved to promote relatively uniform temperature Trend of Green Building Energy-saving New materials[J].”
distribution. The upper middle area of the traditional Green Environmental Protection Building Materials , no. (3).
solar collector wall has a higher temperature than the Guo, H. Y. 2019. “Application of External Thermal Insulation
air outlet area. It is recommended to add an air outlet Energy-saving Construction Technology in Building
here to improve the indoor thermal cycle efficiency Exterior Wall engineering[J].” Shanxi Architecture , no. (9).
Hao, J., Y. D. Ma, and W. Geng. 2018. “Thermal Insulation and
and achieve the effect of improving the indoor thermal Structural Integration Technology of Concrete Thermal
environment. Insulation Curtain Wall-demonstration Application of CCW
(3) Weather conditions (solar radiation) have Building System [J].” Construction Technology , no. (11).
a greater impact on the heat collection efficiency of Huang, H. S., H. Q. Wu, and T. Zhang. 2018. “Preparation of
the heat collection wall. Specifically, the average tem­ Porous Sound-absorbing Ceramsite and Controllable Pore
structure[J].” Journal of Guangxi University (Natural Science
perature difference between a room with a new louver
Edition) , no. (6).
collector wall system and a room with a traditional Huang, X. L., Y. T. Xie, and Y. L. Chen. 2019. “Research on the
collector wall is quite different under sunny and cloudy Innovative Application of Straw in Building Wall Materials
weather conditions. During the entire test period, the [J].” Construction Technology , no. (1).
414 J. ZHANG

Jiang, J., and B. D. Yin. 2019. “Research and Analysis of New Wall Tang, J. M., G. Y. Zhong, and Z. M. Yang. 2018. “Technical
Materials Made by Shield muck[J].” Brick and Tile , no. (3). Measures to Improve the Thermal Insulation
Li, Y. H., J. Yao, R. Li, Z. W. Zhang, and J. L. Zhang. 2017. Energy-saving Effect, Thermal Performance Analysis and
“Thermal and Energy Performance of a Steel-bamboo Durability of Sandwich Walls [J].” Theoretical Research on
Composite Wall structure[J] .” Energy & Buildings 156: Urban Construction (Electronic Version), no. (23).
225–237. Wang, X. H. 2019. “Trial Discussion on the Application of
Liguang, X., and M. Jinyu. 2019. “Research on Cement-based Green Energy-saving Construction Technology in
Porous Sound-absorbing Material [J].” North Building, no. (1). Housing Construction Projects [J].” Green Environmental
Ma, Y. D., and M. G. Lu. 2017. “The Integrated Technology Protection Building Materials, no. (3).
System of Concrete Insulation Curtain Wall Structure Wang, F., Y. Zhang, and Z. M. Yu. 2019. “Preparation and
Realizes the Compatibility of Building Insulation and Fire Performance of Sound-absorbing and Heat-insulating
Protection [J].” Wall Material Innovation and Energy Saving Orn Stalk Reed board[J].” Forest Products Industry, no. (5).
in Buildings, no. (9). Wei, Y. L., and W. X. Zhu. 2018. “Xu Jinfeng’s Experimental
McMahon, M. A., T. P. Prakash, D. W. Cleveland, C. Frank Study on the Thermal Performance of Precast Concrete
Bennett, and M. Rahdar. 2018. “Chemically Modified Sandwich Wall Panels [J.” Jiangsu Architecture, no. (S1).
Cpf1-CRISPR RNAs Mediate Efficient Genome Editing in Yao, M. 2017. “Explore the Effect of Surface Fire Protection on
Mammalian Cells[J] .” Molecular Therapy , no. (5). the Combustion Performance of Building Materials [J].”
Rathore, P. K. S., and S. Kumar Shukla. 2021. “Improvement in Building Materials and Decoration, no. (45).
Thermal Properties of PCM/Expanded Vermiculite/ Yu, B. 2018. “Application of Thermal Insulation Energy-saving
expanded Graphite Shape Stabilized Composite PCM for Construction Technology in the Construction of External
Building Energy Applications.” Renewable Energy 176: Walls of Civil Buildings [J].” Low Carbon World, no. (10).
295–304. Zhong, X., Z. Y. Wang, and Q. Jiang. 2017. “Research on
Rathore, P. K. S., and S. K. Shukla. 2021. “Enhanced Out-of-plane Flexural Performance of Glass Fiber
Thermophysical Properties of Organic PCM through Reinforced Composite Reinforced Prefabricated Concrete
Shape Stabilization for Thermal Energy Storage in Sandwich Wall panels[J].” Industrial Construction, no. (7).
Buildings: A State of the Art Review.” Energy and Zhou, H. M., J. P. Bu, and W. X. Zhu. 2019. “Numerical
Buildings 110799. Simulation Analysis of Noise Reduction of Near-rail
Rathore, P. K. S., S. K. Shukla, and N. K. Gupta. 2020. “Synthesis Sound Absorption Low Wall of Urban Rail transit[J].”
and Characterization of the Paraffin/expanded Perlite Railway Standard Design, no. (8).
Loaded with Graphene Nanoparticles as a Thermal Zhu, W. X., Y. L. Wei, and H. X. Zhang. 2018. “Simulation
Energy Storage Material in Buildings.” Journal of Solar Analysis of Thermal Performance of Precast Concrete
Energy Engineering 142 (4): 041006. Sandwich Wall panel[J].” New Building Materials, no. (10).

You might also like