White paper
=
Abstract Electronic systems require conditioned,
Increasingly, organizations are finding that the risk of running off straight utility power— continuous power—and they get it from
even briefly—is too great to ignore. So they deploy multiple UPS modules to ensure uninterruptible power systems (UPSs). But
conditioned power even if one UPS fails. what happens if a UPS is offline for any
reason? In that case, the UPSs switches to
In paralleling, two or more UPSs are electrically and mechanically connected to form a unified an internal bypass path, and power bypasses
system with one output—either for extra capacity or redundancy. In an N+1 redundant the internal power quality circuitry inside the
configuration, you would have at least one more UPS module than needed to support the UPS. Protected loads run off utility power
load. As a conjoined system, each UPS stands ready to take over the load from another UPS until the UPS can be brought online.
whenever necessary, without disrupting protected loads.
Increasingly, organizations are finding that the
Eaton’s patented HotSync paralleling offers particular advantages, compared to traditional risk of running off unfiltered utility power—
paralleling approaches. For one, there is no system-level single point-of-failure. With a peer- with no ability to mitigate disturbances—is
to-peer control strategy, each UPS module operates independently and is not reliant on an too great to ignore. So they deploy several
external primary controller or a complex web of inter-module control wiring UPS modules to ensure conditioned power
even if one UPS fails.
Contents In paralleling, two or more UPSs are
The growing trend toward Selective tripping— Identifying electrically and mechanically connected to
parallel UPS systems. . . . . . . . . . . . . . . . 2 and temporarily isolating a UPS form a unified system with one output—
How do parallel UPS systems work?. . . 2 with a problem. . . . . . . . . . . . . . . . . . . . . 4 either for extra capacity or redundancy. In an
Design for reliability. . . . . . . . . . . . . . . . . 5 N+1 redundant configuration, you would have
Four key challenges in parallel at least one more UPS module than needed
UPS systems. . . . . . . . . . . . . . . . . . . . . . . 3 Deploying parallel UPS systems . . . . . . 5 to support the load. As a conjoined system,
Primary control— Paralleling BladeUPS modules. . . . . . . . 6 each UPS stands ready to take over the load
Who’s running the show?. . . . . . . . . . . . 3 Customization options for from another UPS whenever necessary,
Synchronizing the output of large parallel systems . . . . . . . . . . . . . . . 6 without disrupting protected loads.
individual UPSs into shared output. . . . 3 Other options for establishing Eaton uses a patented paralleling technology
Balancing the load equally among redundant UPS protection . . . . . . . . . . . 6 that is simpler to deploy yet more reliable
the paralleled UPSs . . . . . . . . . . . . . . . . . 4 than other vendors’ approaches. Field-tested
Closing thoughts . . . . . . . . . . . . . . . . . . . 6 and installed in thousands of installations
About Eaton Electrical. . . . . . . . . . . . . . . 6 around the world, Eaton’s Hot Sync
About the author. . . . . . . . . . . . . . . . . . . 6 paralleling has become the global reliability
standard. This technology enables multiple
UPS modules to operate in parallel without
inter-module control wiring. This approach
eliminates the system-level single-point-
of-failure inherent in traditional parallel
configurations. More on that later.
Let’s take a closer look at parallel UPS topologies—how they
work, what challenges must be overcome in establishing parallel
configurations, how Eaton paralleling technology goes beyond the
industry norm, and what difference it makes in your power protection
scheme. UPS Tie UPS
Cabinet
Utility
input
UPS Tie UPS
Cabinet
UPS UPS UPS
Tie
Cabinet
Should a failure of any kind occur with either module, the critical load Figure 4: Power flows to critical loads, even if all
is still UPS-protected. Internal diagnostics immediately isolate the three modules were offline.
faulty UPS module from the critical bus while the other UPS assumes
the full load.
Primary control—Who’s running the show? Synchronizing the output of individual UPSs into shared
In a conventional parallel UPS system… output
Control is usually managed with a primary-secondary UPSs in a parallel configuration must deliver output at a
arrangement that relies on a veritable spiderweb of control specified voltage and frequency—have their sine waves
wiring between UPS modules. A primary controller serves as completely aligned with each other. If their output is not
the brain of the entire system, determining how UPS modules synchronized, the voltage disparity would cause a large and
synchronize their outputs, how they share loads, and where potentially damaging surge current from UPSs to the load.
they get this information. In a conventional parallel UPS system…
Good parallel systems will have redundant primary controls, Synchronization depends on a primary controller. All UPS
and the better ones will have a “moving primary, sliding modules in the parallel configuration look to that primary
secondary” configuration—a round-robin of rotating leadership. controller to get their synchronization information. If that primary
If the primary controller fails, one of the other UPS modules is controller goes offline—or there is a glitch in the tangle of
designated as the new primary, and the other UPS modules inter-module control wires—the whole system is in trouble.
must look to the new source for their commands. If multiple UPS modules would get out of sync with each other, causing
modules fail, a new primary is designated based on some overload conditions on one or more modules and perhaps
pre-negotiated scheme. triggering those modules to go offline in self-protection.
This process of shifting leadership is fraught with peril, and it is In an Eaton HotSync parallel UPS system….
easy to see why. The change of command must be smoothly
Each UPS synchronizes to the bypass source, which is common
executed by every module. A simple glitch with inter-module
to all the modules. If one module loses bypass feed, it can
wiring can foul the works. For example, if control wiring to UPS
still synchronize to another module’s bypass. In the absence
#5 goes down, paralleling won’t work for UPSs #1 through #4
of a bypass source, the module simply looks at its own output
either.
and makes adjustments based on what it sees. The process
When customers look closely at parallel UPS configurations, is completely autonomous and intrinsic, thanks to inventive
they immediately identify this process as the Achilles heel. The software and very fast microprocessors. In this design, there is
more closely they look at it, the more they’re appalled at the no need to distribute synchronization signals, so the system is
vulnerability of it. According to GE Industrial, “a failure of the not at the mercy of a single potential point of failure.
control system to automatically switch to a redundant path is
the leading cause (32%)
of failures in mission critical power systems.”
In an Eaton HotSync parallel UPS system…
Instead of using a primary-secondary arrangement, a peer-to-
peer control system manages the multiple UPS modules, very
similar to peer-to-peer computing networks. Each UPS assesses
its own operating parameters and determines how to interface
with the others. There is no need for control wiring among the
UPS modules. No matter what happens to other modules, the
parallel system still functions, because each module contains
the intelligence it needs to be a functioning member of the
group.
Balancing the load equally among the paralleled UPSs All of these factors will affect the operation of the load-share
UPS modules in a parallel configuration should share the load function and will frequently conflict with one another. The
evenly with each other. In a two-module configuration, the load HotSync load-share algorithm makes careful selection of priority
would be distributed 50-50. In a four-module configuration, and gain to take the most beneficial action. Precise load-share
25-25-25-25, and so on. Load-sharing ensures that no UPS control—considering both active and reactive power—is made
module is overloaded, nor is any module unnecessarily stressed possible by a digital signal processing technique known as
by suddenly bursting from low load to high load as conditions direct digital synthesis to control inverter frequency.
change.
In a conventional parallel UPS system… Selective tripping—Identifying and temporarily isolating a
UPS with a problem
Load-sharing typically depends on a load-share loop, whereby
UPS modules continually communicate their status to each When UPS modules are paralleled, it can be difficult to identify
other through a web of control wiring. This communication is the root cause of a failure. You might see a drop in voltage on
complex, critical to the operation of the system—and fragile. the shared output bus, but which UPS is the culprit? You need
If any part of the communication web fails, so does the system. to find out which module is causing the problem, and isolate
it quickly before it drags down other modules and causes the
A common problem in this arrangement is electrical noise. Any whole system to switch to bypass mode.
time you loop communication wires among UPSs—a high-
power, high-frequency environment—they are prone to picking In a conventional parallel UPS system…
up electrical noise every step of the way. A communication A faulty module may be signified by the whole system going
interference can be disastrous to the operation of the system, to bypass. Though most module failures are benign, a failed
but it is also very difficult to troubleshoot. inverter IGBT or shorted capacitor may appear as a fault on the
What happens when the load becomes unbalanced among UPS critical bus. For this type of failure, it could be difficult to quickly
modules? Suppose you have a three-module parallel system, identify the root cause and remove the failed module from
and due to a faulty load-sharing mechanism, modules #1 and the critical bus. The system could go to bypass, leaving loads
#2 are each carrying 40 percent of the load, and module #3 is exposed to straight utility power for as long it takes for service
carrying only 20 percent. Chances are, UPS #2 will gradually to arrive.
assume more and more of the load, become overloaded and go In an Eaton HotSync parallel UPS system…
offline. The load is then shifted unevenly to the other two UPS Each module need only look at itself to see if it has failed. An
modules, which will likely become overloaded, and the whole algorithm assesses the difference in current/voltage in each
system switches to bypass—thereby undermining the benefits phase and detects failures based on a running record of this
of a redundant parallel system. information—continually comparing present waveforms with
In an Eaton HotSync parallel UPS system…. previously recorded waveforms. Based on this high-speed
Load-share control algorithms in internal UPS software maintain calculation, the unit detects a fault even before typical hardware
load balance by constantly making adjustments in response sensors would detect it. The affected UPS module turns off its
to variations in output power requirements. Each module inverter IGBT transistors within microseconds (millionths of a
conforms to demand and is not in conflict with the others for second). The result is a “selective trip” that instantly isolates
the load. As with synchronization, this process requires no the faulty unit from the system until the problem can be
inter-module communication. The result is true “wireless” resolved.
paralleling. Since this process does not require communication links among
HotSync paralleling can maintain load balance even under modules, the module is swiftly removed from the critical bus
adverse conditions, such as: before the problem can affect critical loads and before the
system sees the need to go to bypass.
• W hen modules are synchronized to an alternate source
• W hen power backfeed results from the removal of a load
• W hen some but not all modules lose their synchronizing
reference
• W hen the frequency of the alternate synchronization source
oscillates
All you need is two or more compatible UPS modules and an electromechanical tie
cabinet that connects the output of those UPS modules together. No special circuitry
or software is required in the UPSs themselves. That means existing UPSs in the field
can become part of a parallel system without retrofitting or replacement.
An X-slot communication card can be installed in paralleled UPS modules to enable
monitoring of any module in the parallel system from any other module. With optional
Web/SMTP communications, administrators have at-a-glance views of overall system
performance and detail, such as the temperature of an inverter in a specific UPS
module.