MJ-X Voltage Regulator Control Panel: Installation and Operations Manual
MJ-X Voltage Regulator Control Panel: Installation and Operations Manual
IMPORTANT
The information contained herein is general in nature and not intended for specific
application purposes. It does not relieve the user of responsibility to use sound prac-
tices in application, installation, operation, and maintenance of the equipment pur-
chased. Siemens reserves the right to make changes at any time without notice of
obligations. Should a conflict arise between the general information contained in this
publication and the contents of drawings or supplementary material, or both, the latter
shall take precedence.
QUALIFIED PERSON
For the purposes of this manual, a qualified person is one who is familiar with the
installation, construction, or operation of the equipment and the hazards involved. In
addition, this person has the following qualifications:
(a) is trained and authorized to de-energize, clear, ground, and tag circuits and
equipment in accordance with established safety practices.
(b) is trained in the proper care and use of protective equipment such as rubber
gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accor-
dance with established safety procedures.
NOTE
These instructions do not purport to cover all details or variations in equipment, not to
provide for every possible contingency to be met in connection with installation, opera-
tion, or maintenance. Should further information be desired or should particular prob-
lems arise which are not covered sufficiently for the purchaser’s purposes, the matter
should be referred to the local sales office.
The contents of the instruction manual shall not become part of or modify any prior or
existing agreement, commitment or relationship. The sales contract contains the entire
obligation of Siemens Power Transmission & Distribution, Inc. The warranty contained
in the contract between parties is the sole warranty of Siemens Power Transmission &
Distribution, Inc. Any statements contained herein do not create new warranties or
modify the existing warranty.
Table of Contents
D Menu Parameters.............................57
D.1 <CONFIGURE> Menu:
Leading and Lagging Regulators ................ 57
D.2 <REGULATOR> Menu:
Line Drop Compensation ............................. 57
D.3 <CONFIGURE> Menu:
Transformer Polarity..................................... 59
E Hazards of Bypassing a Regulator
off Neutral .........................................63
F Communications Module
Installation ........................................64
G Menu Structure Quick Reference....65
G.1 Navigating the Menu and Fast-Path Keys . 65
G.2 MJ-XL Menu Structure................................ 66
H MJ-XL Firmware Versions...............68
I Terminal Strip Wiring ......................69
J MJ-XL Jumpers and
Battery Replacement .......................70
J.1 MJ-XL Jumpers ........................................... 70
J.2 Battery Replacement ................................... 71
K Terminal Strip Connections ............72
L MJ-XL Operating Procedures .........75
1 Introduction
The MJ-XL(TM) Control Panel is a member of the Siemens mately equivalent to MJ-X software version
Accu/Stat® series of digital controls, designed for use 2.4507.
with many regulators and load tap changer models.
1.1 About This Manual Reverse Power Flow Detection and Operation
This manual is designed to help you become acquainted In many systems, power only flows in one direction; how-
with all aspects of the MJ-XL Control Panel. The manual ever, in some systems power flow reverses from time to
starts with the operator panel and controls, followed by time. To accommodate power flow reversal, the MJ-XL
physical installation considerations, setup procedures, Control Panel monitors power flow direction and adjusts
day-to-day operations, and finally, troubleshooting. The its operation accordingly. Six different Power Flow Modes
Appendixes provide further information about MJ-XL Con- allow flexibility in selecting a control algorithm which best
trol Panel operation and setup. matches the power flow needs of the system.
Barrier Terminal Strips Contact your Siemens representative or visit the Siemens
L
Terminal contacts on the back of the MJ-X Control Panel T&D website for a complete list of Application Notes and
allow for external control over certain functions such as other supporting documentation.
VRC activation and tap changing. These terminals can be
used to provide an electrical interface to a SCADA system 1.8 Siemens Website
for remote control applications and/or other desired con- The Siemens website contains information about all of the
trol functions. Siemens transmission and distribution products, including
regulators and controls.
1.3 Mounting onto Siemens
Regulators The web address is www.siemenstd.com. Once you are
connected to the website, select the Products and Solu-
The MJ-XL Control Panel is mechanically and electrically tions link and then the Voltage Regulators link.
compatible and interchangeable with earlier MJ-X, MJ, IJ
and SJ series and earlier control units. It can be mounted Browse this section for information about the regulators,
in the existing enclosure by simply swinging the control to regulator accessories, upgrades, downloadable files, and
be replaced outward on its hinges, disconnecting the more.
polarized disconnect switch (PDS), then removing the unit
and inserting the new unit. (See Appendix B.)
Accu / Stat MJ - XL
Indicators
Alert High Band Raise
Reverse Power Flow In Band Lower
Remote Auto Inhibit Low Band Menu Selection
16-Character and Scroll Keys
Display
Menu
Quick Menu Key
Change Keys
Cancel Max Op counter
Change Save Fast-path Key
Reset Min
Alert Status
Data Port Data Port Fast-Path Key
Op Alert
Quick
Count Status
Sensing Fuse
• Use the fast-path keys to jump directly to frequently- Use this key to place the panel in the Change mode. In
used data items without scrolling. Change mode, you can make changes to setpoints and
other stored configuration information.
2. Press the Change key. The displayed data item For example, if you wish to see the minimum load voltage
flashes to indicate that it can be changed. since the last reset, use the Menu Selection keys to
select Vld from the Meter Menu. The current voltage
3. Use the Scroll keys to make the desired change. value is displayed on the screen. Press the Max/Min key.
The maximum value will display for a short time. Press the
Save Key Max/Min key again to view the minimum value.
Max
The Bandwidth setpoint defines a voltage range (on either
Min side of the Voltage Level setpoint) which you consider to
be acceptable. When regulator output voltage falls outside
this value, the MJ-XL Control Panel activates the tap
Use this key to view max/min values for meter parame- changer motor to restore the voltage to an in-band condi-
ters. First view the desired data item, then press the Max/ tion. Use this key to view the Bandwidth setpoint. Once
Min key to view the maximum value. Press the Max/Min you display the Bandwidth, press the Change key to mod-
key again to see the minimum value, Press the Max/Min ify the value.
key a third time to exit the Max/Min mode without reset-
ting the values.
Resis-
tance VLC
Select
Press this key to view the Resistive LDC component. Press this key to view the VLC Enable data items. Press
Once you display the Resistive LDC, press the Change
the VLC key repeatedly to step through the VLC - Upper
key to modify the value. Voltage setpoint, and the VLC - Lower Voltage setpoint
and then repeat the sequence. See Section 4.4.4 for a dis-
Reactance Key cussion of these data items.
Op
Count
Press this key to view the Reactive LDC component.
Once you display the Reactive LDC, press the Change key
to modify the value. Press this key to select the <COUNTERS> Menu. The
first parameter displayed is the Total Operations count.
+/- Polarity Select Key Press this key repeatedly to step through the
<COUNTERS> Menu data items. See Section 5.7 for a
discussion of this Menu.
Other Fast-Path Keys Press the U2/P2 key to toggle the output voltage between
the “U2Cal” and the P2 Cal” values. Concurrently, the dis-
Alert Status Key play shows the corresponding metered value (U2 Cal or
P2 Cal). Refer to Section 8.4 for calibration instructions.
Alert
Status Note: The MJ-X required the operator to use the U2/
P2 slide switch on side of the panel to change
the voltage coming to the front-panel test ter-
Power Switch
This three-position switch selects the power source for
the MJ-XL Control Panel.
"Low" Band
Indicator
• In the upper (Normal) position, the regulator Utility
(tertiary) winding provides power through the polar-
ized disconnect switch (PDS).
1v • In the lower (External Source) position, the External
VLC Lower
Source terminals (described below) provide power.
VLC Lower
Indicator
• In the middle (Off) position, the MJ-XL Control Panel
is turned off. This is also called the By-Pass Position.
Figure 2.2 Band Indicators and VLC Indicators
This three-position switch determines whether the MJ-XL External Source Binding Posts
Control Panel is under manual control, microprocessor
control, or remote control. Note that the ultimate determi- These binding posts can be used to apply 120 V external
nation of the point of control is established manually; this power to the MJ-XL Control Panel when the power source
switch setting cannot be overridden from a remote loca- switch is in the External Source position. The binding
tion. posts are dual banana-style receptacles.
• Manual (By-Pass Position), The operator has control Note: Ensure that any voltage source attached to
of the regulator’s tap changer motor; automatic tap these binding posts is properly polarized.
changes are disabled. In this mode, a local operator
can use the Tap Raise/Lower switch to adjust the tap
position. A remote operator cannot exercise control
of the tap changer motor or the microprocessor, but
MJ-XL Control Panel data can be obtained.
CAUTION
• Local-Auto. The microprocessor has control of the tap
changer motor and manual tap changes are disabled. Improper external source connection will
In this mode, a remote operator can obtain MJ-XL place 120V on the ground circuit.
Control Panel data. However, the remote operator
cannot make configuration changes or exercise con- May result in minor or moderate injury
trol of the tap changer motor. including equipment damage.
To prevent:
• Remote (Enable). The microprocessor has control of
the tap changer motor and manual tap switch Observe proper polarity of external power
changes are disabled. In this mode, a remote opera- supply.
tor has access to all functions available to the local
operator, including the ability to override automatic
control of the tap changer motor. Voltage Calibration (Test) Binding Posts
Tap Raise/Lower Switch These binding posts can be used with an external voltme-
ter to monitor regulator P2 or U2 voltage. The Voltage Cal-
When the Remote/Manual/Auto switch is in Manual posi- ibration Key (U2/P2) defines which voltage (U2 or P2) you
tion, this three-position switch activates the tap changer can read at these binding posts. The binding posts are
motor to raise or lower the tap position. dual banana-style receptacles.
Switch Positions for Bypassing Note that the voltage measured at these binding posts is
The front panel switches must be in the following posi- not turns-ratio corrected. By contrast, the metered voltage
tions before bypassing the regulator. presented on the display screen (under <METER>) is cor-
rected by control-program software. (See Section 4.3.6
• Power Switch - OFF and Section 4.3.7 for configuring the voltage transformer
U2/P2 turns ratio).
• R/A/M Switch - Manual
External Power Source Protection Fuse Do not operate with CT secondary open.
Short circuit or apply burden at CT
This 4.0 Amp fuse protects against the “hot” side of the secondary (C2-C) during operation.
120 V external source being connected to the front panel
ground (white) binding post.
WARNING
Hazardous voltage will be present on
various control leads when regulator is
energized.
Could result in death or serious injury
including equipment damage from
contact with live line conductors.
To prevent:
The terminal strips include four terminal pairs for VRC con-
trol and external inhibit function. The terminal strips
include the Current Circuit terminal pair.
Manual
Connections for "Terminal Block" (T.B.) Remote Control
Automatic Automatic T.B. Remote Control for T.B. Remote Enable/Disable of
"Lower" "Raise" R/A/M Switch in Remote Automatic Operations
Relay* Relay* U-REM U-REM U-REM
K5 K4 P2B
5 5 T.B. 5
J22 J22 Remote J22
Raise P2B Raise
Manual 4 4 4
Tap Off
Raise/Lower P2B J21 J21 J21
Relay
Switch 3 3 Contacts 3
Lower
P2B U-REM U-REM U-REM Relay
6 6 6 Contacts
T.B. Open - Disable
P2B K22 K22 Remote K22 Close - Enable
*Auto relays disabled when R/A/M 7 7 Lower 7
switch is in Manual position
P2B K21 K21 K21
8 8 8
3.2 Understanding Menus • the <LOG> Menu, which contains historical data.
MJ-XL Control Panel information is organized into lists
(Menus) of related data. Each specific piece of information 3.3 Using the Menu Selection Keys to
in MJ-XL memory is known as a data item. To view or View Data Items
change a specific data item, you must select the Menu
that contains the desired item. Appendix G provides a This section describes how the Menu Selection and Scroll
Menu Structure Quick Reference for help in locating a spe- keys can be used to view data items.
cific data item.
Think of the Menu arrangement as a table of data items
For example, the <LOG SETUP> Menu contains data on a sheet of paper as illustrated in Table 3.1.
items that you can use to define logging requirements. To
define logging requirements, view the <LOG SETUP> Each column of the table has a heading (Menu name).
Menu; then display the particular data item from that Since you are viewing this “table” through a 16-character
Menu. As another example, the <METER> Menu con- window, you must scroll through the table to view the
tains meter-reading data. To determine the present load desired data item. The following scrolling rules apply:
voltage meter reading, view the <METER> Menu and
then the Load Voltage data item from that Menu. The • At the heading level, scroll through the Menu head-
<METER> Menu is considered the home position in the ings with the left and right Scrolling keys.
MJ-XL Control Panel's menu structure.
• Within a selected menu, use the up and down Scroll-
MJ-XL Control Panel Menus are divided into two major ing keys to step through the various data items.
categories:
data item 3 data item 3 data item 3 data item 3 data item 3
. . . . .
. . . . .
S i e m e n s P o w e r Tr a n s m i s s i o n & D i t r i b u t i o n , I n c .
P2PT: 7620:120 Made in U S A
Jackson, MS 21-115905-002
Figure 4.1 Typical Siemens Regulator Nameplate for older ANSI Type B (Inverted) Regulator
(Regulator type not identified on nameplate)
Note: Items are not highlighted on actual nameplate.
CAUTION
To prevent minor or moderate injury
including damage to the regulator or
control components: use the example
diagrams only for illustration purposes.
Refer to the regulator nameplate for the
proper control diagram to use with a
particular installation.
Figure 4.2 Typical Siemens Regulator Nameplate for ANSI Type A (Straight) regulator
Note: Items are not highlighted on actual nameplate.
M
7620 122 V P2-P4 21 23 120 V
7200 115 V P2-P4 25 20 120 V 0
A B
87654 3 21 Tap Changer
5000
4330
122 V
122 V
P2-P5
P2-P6
23
23
20
20
125 V
125 V
Preventive
2500 118 V P2-P7 27 20 125 V
P7
P6
P5
P4
P3
E2 Autotransformer
Control diag : 21-203-980-468 Utility Pol NORM
U2PT: 7620: 122 Nameplate : 21-115-905-464
(E2 to right of
CT sec conn C2 to C3
Copper conductor in shunt winding.
Aluminum conductor in series winding. P Terminals)
Tank withstands full vacuum
Basis volts 120 DATE:
Figure 4.3 Typical Siemens Regulator Nameplate for ANSI Type B (Inverted) Regulator
Note: Items are not highlighted on actual nameplate.
*VRC Stat is a view-only item. It appears in the <REGULATOR> menu for viewing convenience.
VRC Stage2:XX.X
VRC Stage3:XX.X
4.4.3 Voltage Reduction Control Items Information displayed includes: percent reduction pres-
ently in effect (nn.n%), the VRC mode (L - Local, A - Auto-
Voltage Reduction Control (VRC) is used to reduce output
matic, R - Remote), and the present step/stage (0-3). For
voltage. When activated, VRC has the effect of lowering example, if VRC is presently at 5%, Remote, and MJ-XL
the Voltage Level setpoint. Voltage reduction is accom- mode Stage 3, the display panel would show VRC
plished in one or more discrete steps which are defined as
Stat=05.0%R3.
a percentage of the voltage level setpoint (Fwd Volts, Rev
Volts). VRC operates immediately to reduce output volt-
age without waiting for completion of the Time Delay.
VRC1 In
This item defines which feature is implemented when the
The following sections describe each of the VRC menu external terminal block contacts (VRC1) are closed. Select
items, and explain how to set them. VRC to enable remote Voltage Reduction Control. Choose
X-COMP to enable reactive compensation polarity control.
ALT Delay When VRC1 contacts are closed, the LDC polarity is
reversed.
When the VRC2 In item is set for ALT DELAY, an alternate
time delay is used before commanding a tap change when
VRC2 In
the VRC2 contacts are closed. When the VRC2 contacts
are open, the standard (Fwd Delay) time delay is used. This item defines which feature is implemented when the
VRC2 contacts are closed. Choose VRC to enable remote
VRC Status Voltage Reduction Control. Choose ALTDELAY to use the
ALT Delay feature described above. Choose LO XBATT to
The VRC Status data item displays present VRC informa- accept the battery status input at these terminals.
tion in the display panel. It can be directly accessed with
the VRC fast-path key, or viewed from the <REGULA-
TOR> Menu.
To enable VRC Remote mode, view VRC Mode and select unlatched none none
REMOTE. Then to activate voltage reduction, you must
close the appropriate VRC contacts. For example, if you specify Fwd Volts=120 V, and MJ-3A
VRC% = 10%, the total reduction value is 12 V. This 12 V
Remote mode is further subdivided into MJ-XL mode, and reduction value is further subdivided into thirds, so a sin-
MJ-3A mode (compatible with the previous-generation gle pulse would result in a 4 V reduction; a second pulse
control). Both modes use the VRC terminal pairs; the dif- would produce an 8 V reduction, and a third pulse would
ference is in the way the terminal pairs are used. produce a total of 12 V reduction. Contact activation of
three seconds or longer is considered to be a “latched
MJ-X Mode (“Static” Inputs) condition” and would (in this example) produce a full 12 V
In MJ-X mode, you can specify up to three Stages of volt- reduction.
age reduction— each with a different reduction value. View
VRC Remote and select MJ-X. Then view VRC Stage1, Automatic Mode VRC with Remote Override
VRC Stage2, and VRC Stage3 to set the VRC percentage In Automatic mode, voltage reduction is activated auto-
reduction values. matically whenever load current exceeds a predefined per-
centage.
Two terminal pairs (VRC1 and VRC2) on the external termi-
nal block are used to trigger the three Stages (see Table There are two automatic VRC setpoints (AutoVRC1 and
4.3). AutoVRC2). When load current exceeds the percentage
specified in either of the AutoVRC %I data items, regula-
Table 4.3 VRC Indicator Flashing Pattern for MJ-X Mode tor output voltage is reduced by the percentage specified
Stage VRC Terminal VRC LED flashing in the corresponding AutoVRCset data item.
Pairs pattern
Only one set is active at a time; they are not additive.
Stage 1 VRC1 active; long-short
VRC2 in-active AutoVRC remains active until the load current falls below a
value that is the lower of:
Stage 2 VRC1 in-active; long-short-short
VRC2 active AutoVRCn% ·(1-2 ·AutoVRCsetn(%))
Stage 3 VRC1 active; long-short-short
VRC2 active or
Present, max, and min values for: 2. A Level 2 password is associated with a specific
Menu. When a Menu is protected at Level 2, the
Power Factor Power Factor at KVAmax
Level 2 password must be entered before changes/
Power Factor at KVAmin Tap position resets can be made to data items within that Menu.
Total Operations Entering any Level 2 password provides access to all Level
1 protected data items as well as to data items contained
To activate Interval logging, view Log Interval; then select in Menus that are protected by that specific Level 2 pass-
ON. word. In other words, when a Level 2 (Menu) password
has been entered, the change/reset function is enabled for
To define the time between logs, view Interval; then spec- any data item that is not protected by another Level 2
ify the time as HHhrMMmin. password.
To reset the minimum and maximum values at the start of Either Level can be activated independent of the other.
each interval, view ResLogMinMax; then select ON.
Security activation and password assignment are separate
Interval logging is synchronized to the time of day. Interval functions. In other words, even though you have assigned
logging occurs when “seconds” is zero. For 15 and 30 a password to a Level, password checking can be active or
minute intervals, the MJ-XL logs data at even quarter and inactive for that Level.
half-hour increments, respectively. For a 1-hour setting,
the MJ-XL logs data on the hour. For 4 and 6-hour settings, With this flexible structure you can set up a security sys-
the MJ-XL logs data synchronized to 12:00:00 midnight. tem with:
4.5.3 Clearing Event/Interval Log Data • A single Level 1 password.
To clear the entire Event Log, view the Clr Event Log item,
toggle to Y, then press the Save key. • A Level 1 password with additional Level 2 pass-
words for specific Menus.
To clear the entire Interval Log, view the Clr IntervLog
item, toggle to Y, then press the Save key. • No Level 1 password, but one or more level 2 (Menu)
passwords.
• No passwords at all.
See Section 8 for information about the test and calibra- The <DIAGNOSTICS> Menu also includes the Serial
tion items: Number and Product Revision code for the MJ-XL Control
Panel. These are set at the factory and cannot be
U2 Cal changed.
The kVARhr F and kVARhr R data items display Kilovar To retrieve Demand data, select the appropriate
Hour values. They are accumulated separately for forward <FW DEMAND> or <REV DEMAND> Menu; then use
and reverse power flow conditions. The kVARhr is updated the Ù and Ú keys to sequence through the Demand data
once per second, using the formula: items. To view the minimum and maximum values for a
given Demand data item, first view the present value;
kVARnew = kVARold + kVAR*1/3600(hours)
then use the Max/Min key to display the respective maxi-
The microprocessor computes and accumulates kVARhr mum and minimum values recorded since the last reset.
values for each of the four quadrants of the voltage/current
phase-angle relationships. These parameters are pre- Demand calculations are initialized at the time of system
sented as shown in Figure 5.1. power up, when configuration items are changed, and on
any power flow reversal. Un-initialized data items are pre-
sented as dashes (— ) on the display screen. Demand val-
kVAR (reactive power)
ues remain un-initialized until completion of the first
-kW (reverse) kVA +kW (forward) subperiod. Power factor is stored whenever a new kVA
+kVAR (forward) +kVAR (forward) maximum or minimum demand value is reached. These
-PF (leading) +PF (lagging) Power Factor values are reset when kVA max or kVA min
values are reset.
II I
-kW (reverse) kW (real power)
5.5 Event Log - the <EVENT LOG>
III IV
Menu
-kW (reverse) +kW (forward)
-kVAR (reverse) -kVAR (reverse) The MJ-XL can be set up to record meter data at the time
+PF (lagging) -PF (leading) of an “Event.” Events can include: power up, parameter
changes, tap changes, etc. Use the <LOG SETUP> Menu
to enable the Events you want logged. (See Section 4.5).
Figure 5.1 Power Quadrant Conventions
Table 5.5 describes the data that is to be logged whenever
an Event occurs.
5.4 Demand Data—
the <DEMAND> Menus Table 5.5 <EVENT LOG> Data Items
Demand measurements are time integration functions of <EVENT LOG> Data items
the metered values. The MJ-XL Control Panel performs Event: Event number1 NNNNNNN
demand calculations for the following data items: voltage, Date: Date NN/NN/NN
current, power factor and power. Time: Time NN:NN:NN
Cause: Cause of Event CAUSE
Demand data is maintained separately for forward and (Alert, tap change, etc.)
reverse power flow conditions (see Table 5.4). During for- Vld rms regulator load voltage NNNN.N
ward power flow conditions, the microprocessor does not Vsrc rms regulator source voltage NNNN.N
accumulate reverse measurements. During reverse power Ild rms regulator load current NNNN.N
PF Present Power Factor N.NN
flow conditions, the microprocessor does not accumulate
KWld Present Real power NNNNN
forward measurements. KVAR Present Reactive power ± NNNNN
KVAld Present Apparent power NNNNN
You can select one of two methods of measuring demand: Tap Tap position NN Raise/lower
the Sliding Window method and the Thermal Averaging
method. (See DmdType in Section 4.3.18.) 1. The Event number is a sequential number used for maintain-
ing and referencing the <EVENT LOG>
5.5.2 Clearing Individual Events from the Event If the specified interval elapses while you are viewing
Log <INTERVAL LOG> data, the MJ-XL saves the new data,
but it is not available for viewing until you return to the
Since you can now view all of the <EVENT LOG> data Menu level and subsequently scroll into the <INTERVAL
from the front panel, or download it via the data port, it is LOG> Menu again. Data for all of the Intervals can be
unnecessary to delete individual <EVENT LOG> items. viewed from the <INTERVAL LOG> Menu. Data for the
The MJ-XL no longer supports deleting individual log 800 most recent Intervals is stored and can also be
records. If the <EVENT LOG> memory is full, the oldest retrieved through the front-panel Data Port or the Commu-
record is overwritten when a new event occurs. nication Port.
The first set of data items in the <HARMONICS> Menu PNE RX Point Number Error (Invalid point
number) received
are the three Total Harmonics Distortion values for: load
voltage (Vld THD: NNN.N%), source voltage (Vs THD:
NNN.N%), and load current (Ild THD: NNN.N%). The sec- 5.11 VRC Status - the <REGULATOR>
ond set of data items in the <HARMONICS> Menu are Menu
Show Harm: and Show As:. These data items allow you to
select the format of the data to be viewed: The VRC Status items indicate the present level of Voltage
Reduction Control (VRC). The VRC Status item is indi-
Show Harm: Odd Show odd harmonics only cated as:
Ev/Odd Show both even and odd har-
monics. VRC Stat = XX.X%MY
where: XX.X% is the amount of voltage reduction
Show As: %TOTAL. Show harmonics as percent- (0.0% to 10.0%)
age of total signal magnitude.
%FUND. Show harmonics as percent- M is the VRC Mode
age of the fundamental. where: L = Local
RMS Val. Show harmonics as signal R = Remote
magnitude. A = Auto (w/Remote Override)
Use the Ù and Ú keys in the <HARMONICS> Menu to Y is the presently active VRC step
view the harmonics data. The harmonics data items for: Local - not applicable
appear after configuration items Show Harm and Show Remote - 1, 2, or 3
As. The harmonics data items always include the rms and Auto - 1 or 2
% Total values for the fundamental (i.e., the 1st harmonic).
This data item can be accessed using the VRC Select fast-
Data for even harmonics is only shown if configuration path key.
item Show Harm is set for EV/OD. Data for harmonics
above the 1st harmonic are shown as % Total, % Funda-
mental, or rms depending on which is selected in the
Show As configuration item.
9. Load power factor • the utility winding of the regulator, which generally
requires correction to deliver 120 VAC at the nominal
10. Power flow operating mode system voltage.
11. Power flow direction. The control program senses regulator output (i.e., “load”)
voltage depending on power flow operating mode (see
Because coinciding events might introduce conflicts, an Table 6.2):
operational hierarchy must be established. This hierarchy
is maintained when the unit is under automatic control. Table 6.2 Regulator Output Voltage Sensing
Manual mode always takes precedence over automatic
Regulator Design Winding Used for Voltage Sensing
control.
ANSI Type
Forward Power Reverse Power
Conflicts are resolved according to the following priority Flow Operation Flow Operation
scheme (from highest to lowest): A (Straight) Voltage Utility winding
transformer
1. Automatic tap change inhibit (implemented with ter-
B (Inverted) Utility winding Voltage
minal strip jumpers or Comm Link command).
transformer
2. Voltage Limit Control (defined in regulator settings).
Since the control program routinely senses both the volt-
3. Current inhibit (determined by %I Threshold of con- age transformer and the utility winding, it is a straightfor-
figuration setting; as % of full scale CT rating). ward process for the control program to select which
source is “active” (depending on power flow mode and
4. Voltage Reduction Control. regulator design).
R • • Reverse
Neut R F • • Forward
• • Return to Neutral*
Idle R F • • Forward
F Lock F • • Forward
F • • Forward
R Lock R • • Reverse
R • • Reverse
Forward Reverse
In this mode, the controller always operates in forward In this mode, the controller always operates in reverse
mode. The tap changer operates unless reverse current mode. The tap changer operates unless forward current
magnitude exceeds the I Threshold % setpoint, at which magnitude exceeds the I Threshold % setpoint, at which
time further tap changes are inhibited. The tap changer time further tap changes are inhibited. The tap changer
resumes operation when the reverse current drops below resumes operation when forward current magnitude
the I Threshold % setpoint. drops below the I Threshold % setpoint.
If the I Threshold % setpoint is set to zero, the regulator If the I Threshold % setpoint is set to zero, the regulator
operates as above, using the 1% operational limits in operates as above, using the 1% operational limits in
place of the I Threshold % setpoints. place of the I Threshold % setpoints.
In this mode, if power flow does reverse, Demand values In this mode, when power flow is Forward, Demand val-
are not computed. ues are not calculated.
View Pwr Flow: F LOCK on the <CONFIGURE> Menu. View Pwr Flow: R LOCK on the <CONFIGURE> Menu.
RPF indicator
flashing
Band indicators
flashing
I Threshold % 1% 0 1% 1% 0 1% I Threshold %
Current Current
Figure 6.2 Forward Locked Mode Figure 6.3 Reverse Locked Mode
In this mode, the tap changer operates when current mag- In this mode, the controller always operates in forward
nitude exceeds the I Threshold % setpoint. The tap mode. When forward current magnitude drops below the
changer operates in forward mode when forward current I Threshold % setpoint, tap changes are inhibited and the
magnitude exceeds the I Threshold % setpoint, and in regulator idles at the last tap position. Tap changer opera-
reverse mode when reverse current magnitude exceeds tion resumes when forward current magnitude exceeds
the I Threshold % setpoint. the I Threshold % setpoint.
If the I Threshold % setpoint is set to zero, the regulator If the I Threshold % setpoint is set to zero, the regulator
operates as above, using the 1% operational limits in operates as above, using the 1% operational limits in
place of the I Threshold % setpoints. place of the I Threshold % setpoints.
View Pwr Flow: Bi-dir on the <CONFIGURE> Menu. Select Pwr Flow: IDLE R on the <CONFIGURE> Menu.
RPF indicator on RPF indicator off RPF indicator on RPF indicator off
I Threshold % 1% 0 1% I Threshold %
Current
2. Ensure that the fault is not due to improper jumper • External Source fuse (if External Source Terminals are
arrangements or some other user-correctable condi- used to power the unit)
tion.
• Fuse connectors not mated properly
3. Determine whether the fault can be locally repaired
(e.g., by replacing a fuse or the Neutralite indicator). • Jumpers not in their correct positions
Troubleshooting approaches depend upon the problem. • Terminal Strip connectors not mated properly
Among other indicators, you should consider:
• Terminal Strip connector jumpers missing or screws
• Visual review of the unit. not tightened properly
8.4.1 Checking the U2 Voltage Calibration Note: If password protection is in effect, you must
enter the password to enable calibration. The
Note: You can check the U2 voltage calibration while default password for the <DIAGNOSTICS>
the panel is installed on a regulator. Menu is “3333”.
To check U2 calibration, apply an AC voltage (in the range 8.4.5 Calibrating the P2 Voltage
of 115 to 135 VAC) from U2 to E. Monitor the Voltage Cali-
bration/Test Terminals with a true RMS voltmeter. View Connect an external true rms voltmeter at the front panel
the “U2 Cal” screen on the MJ-XL (i.e., press the “U2/P2” “Voltage Calibration/Test Terminal.” Apply the nominal cal-
fast-path key until “U2 Cal” appears on the MJ-XL display.) ibration voltage (per Table 8.2.) Press the “U2/P2” fast-
Verify that the “U2 Cal” reading matches the applied volt- path key to view the “P2 Cal” screen. To calibrate, press
age (within ± 0.5 VAC) If calibration is off, recalibrate (see the Change key, then the Ú or Ù key to make the value
below.) shown on the MJ-XL display agree with the external volt-
meter value. When the change is complete, press the
8.4.2 Checking the P2 Voltage Calibration Save key.
Note: If the regulator provides the “source” voltage Note: If password protection is in effect, you must
signal, you can check the P2 voltage calibration enter the password to enable calibration. The
while the panel is installed on the regulator. (If default password for the <DIAGNOSTICS>
the regulator lacks a “source” voltage signal, Menu is “3333”.
then there is no need to calibrate the P2 input.)
8.4.6 Calibrating the Load Current
To check P2 calibration, apply an AC voltage (in the range
of 115 to 135 VAC) from P2 to E. Monitor the Voltage Cal- Note: To calibrate the current, remove the panel
ibration/Test Terminals with a true RMS voltmeter. View from the tap changer apparatus. Remove on-
the “P2 Cal” screen on the MJ-XL (i.e., press the “U2/P2” board jumper J1 (see Figure J.1) and Terminal
fast-path key until “P2 Cal” appears on the MJ-XL display.) Strip jumper at P3B-11 & 12. Connect an exter-
Verify that the “P2 Cal” reading matches the applied volt- nal ammeter, and apply an external AC current
age (within ± 0.5 VAC) If calibration is off, recalibrate (see source, per Table 8.2. After calibration, replace
below.) J1 and Terminal Strip jumper at P3B-11 & 12.
8.4.3 Checking the Load Current Calibration The Load Current (Ild) has three calibration set-points:
C/C2 Low, C/C2 Medium, and C/C2 High. Calibrate all
Note: To check the current calibration, remove the three setpoints with an external true rms ammeter con-
panel from the tap changer apparatus, connect nected at the rear panel (terminal strip contacts P3B-11 &
an external ammeter, and apply an external AC 12.) Connect a (nominal) 0-200 mA AC current source at
current source. C/C2 (terminal strip contacts P2A-5 & 7.)
To check C/C2 Low calibration, apply a nominal 5 mA AC Apply the C/C2 Low calibration current (per Table 8.2).
current at C2/E1 and verify that “C/C2low” reads within ± Use the Menu and Scroll keys to view the “C/C2low”
.2 mA of the applied value (as displayed on external screen. To calibrate, press the Change key, then the Ú or
Ammeter connected at C/C2.) Ù key to make the value shown at the MJ-XL display
agree with the external ammeter value. When the change
To check C/C2 Medium calibration, apply a nominal 80 mA is complete, press the Save key.
AC current at C2/E1 and verify that “C/C2med” reads
Note 1: Prior to calibration, disconnect panel from regulator, and remove on-board jumper J1 (see Figure J.1) and Terminal Strip jumper at
P3B-11 & 12. After calibration, replace J1 and Terminal Strip Jumper at P3B-11 & 12.
8.5 MJ-XL Self Testing A checksum failure indicates a problem with the unit. A
checksum or other self-test failure will activate the “Self
After reset, the MJ-XL runs through an internal diagnostics Test Fault” alert. If this alert occurs, contact your Siemens
routine. The start-up diagnostics routine includes a front Power Transmission & Distribution representative for
panel indicator test— the LED indicators simultaneously instructions.
flash three times so that an operator can verify them. Dur-
ing the LED test, the MJ-XL displays “Testing...” on the 8.6 Communications Module
front panel screen.
Troubleshooting
The start-up diagnostics routine consists of several checks In the <DIAGNOSTICS> Menu, the MJ-XL Control Panel
and internal tests, including a ROM (program memory) provides data items for testing the Communications Mod-
checksum calculation. The MJ-XL displays the results of ule and verifying its operation. Please refer to the MJ-XL
the checksum test (PASS or FAIL) in the “Checksum=” Communications Module Installation Manual for verifying
item under the <DIAGNOSTICS> Menu. the Communications Module operations using the
<DIAGNOSTICS> Menu data items.
A Specifications
Operational Requirements Accuracy
Temperature Metering accuracy*: ± 0.5% over the -40°C to +85°C oper-
ating range.
Operating: -40°C to +85°C
Storage: -40°C to +85°C * Basic accuracy of the MJ-XL (excludes Potential Trans-
former or Current Transformer errors).
Humidity
Electrical transient immunity
Operating: Relative humidity of 5% to 95% non-condens-
ing The MJ-XL Current Transformer (CT) withstands a sudden
open circuit without damage to the control circuit. How-
Storage: Relative humidity of 5% to 95% non-condensing
ever, an open CT circuit can result in dangerously high
voltage, and should be avoided.
(U2 and P2 range)
The MJ-XL Control Panel is impervious to electrical tran-
80 to 145 volts RMS sients as defined by the following:
Frequency
Surge: ANSI/IEEE C37.90.1-1989
All PDS and terminal strip connections
45 to 65 Hz
High Energy Surge: ANSI/IEEE C62.41-1980
U2 and P2 inputs only
Replacing Older Control Units with the MJ-X L Note 6: Regardless of the panel type being replaced, the
Control Panel MJ-XL Control Panel must be configured to operate with
the particular regulator on which it is being installed. (See
If the original control has modifications such as Auxiliary Chapter 4).
Transformer, Auxiliary CT, Reverse Power Flow Detector,
Voltage Limit Control, or other accessories mounted in the Replacing existing MJ-XL Control Panels
enclosure, special engineering instructions will be
required before the existing control is replaced. To replace an already-installed MJ-XL Control Panel, the
procedure is similar to that described above.
Note 1: Some older controllers do not provide the neces-
sary signals to support all MJ-X L functions. (i.e., tap posi- Polarized Disconnect Switch
tion indication, operations counter, Neutralite, drag hands Unplug the PDS from the existing unit and replug it into
reset.) the new unit.
To prevent:
Only authorized personnel should work
on this equipment including installation,
operation and maintenance.
D Menu Parameters
D.1 <CONFIGURE> Menu: D = 3 24 x 24 x 48 = 30 inches
Leading and Lagging Regulators
R=0.592 ohms/mile X=0.692 ohms/mile
The following steps will help you determine which of the
two regulators in a Delta configuration is “leading” and
2. Determine compensation multiplier, k, as
which is “lagging” on an open Delta installation:
• Single phase
1. Disable automatic control of tap changer. Set Raise/
Lower tap switch to OFF. Set Remote/Auto/Manual
switch on both controllers to Manual.
Current Transformer Rating
k = 2.0x
2. Use the Configuration Keys to temporarily set both Voltage Transformer Ratio
controllers to System type = WYE. This will be cor-
rected in step 7.
• Wye Connected
3. Assure that there is load current on the line. Load cur-
rent must be of sufficient magnitude to cause a defi-
nite response of the line drop compensation circuit. Current Transformer Rating
Normally, 25% of the regulator setting will be ade-
k = 1.0x
Voltage Transformer Ratio
quate.
4. Adjust both front panel controls to the same settings: • Delta Connected
Bandwidth 2.0 V
Voltage Level 120 V Current Transformer Rating
Time Delay 0 Seconds k = 1.73x
Voltage Transformer Ratio
Resistance Volts 0V
Reactance Volts (+) 12
EXAMPLE: The regulators involved are 3 - 333 kVA at 7.2
5. Set the Remote/Auto/Manual switch to AUTO on both kV configured in a wye-connected three phase bank. (The
controllers. CT primary for this regulator is 400 A.)
Note: The amount of tapchange excursion can be Note: Multipliers for many common system voltages
made more or less, if desired, by appropriate and regulator ratings are included in tables D.4
adjustment of the reactance volts setting. and D.5 below.
7. Use the Configuration keys to set the System type to 3. Determine the Line Drop Compensation Settings
Delta Lead for the leading regulator and to Delta Lag
for the lagging regulator, as determined in step 6. Resistive Compensation Setting = k x line length (mi) x
resistance (ohms/mi)
D.2 <REGULATOR> Menu:
Reactive Compensation Setting = k x line length (mi) x
Line Drop Compensation reactance (ohms/mi)
There are several methods used to determine line drop
compensation settings, The “Load Center” method is EXAMPLE: The line is 3 miles long.
probably the most commonly used and most clearly illus-
trates the procedure. Resistance Setting = 6.67 x 3 x 0.592 = 12V
1. Using knowledge of the distribution feeder and the Reactance Setting = 6.67 x 3 x 0.692 = 14V
tables below, establish the conductor resistance and
reactance per mile of feeder.
Table D.1 Line Drop Compensation Table - Distribution Line Resistance and Reactance
Ohms per Conductor per Mile at 60 Hz
Copper - Hard Drawn Aluminum - Steel Reinforced
Cond. Res. Reactance (See Note 1) Cond. Res. Reactance (See Note 1
Size at Size at
Distance “D” Between Centers of Conductors Distance “D” Between Centers of Conductors
50oC 50o C
MCM 18” 24” 30” 36” 42” 48” 54” 60” MCM 18” 24” 30” 36” 42” 48” 54” 60”
1000 .0685 .449 .484 .511 .533 .552 .568 .593 .595 1272.0 .0851 .421 .456 .483 .505 .524 .540 .555 .567
750 .0888 .466 .501 .529 .550 .569 .585 .600 .612 954.0 .1128 .439 .474 .501 .523 .542 .553 .573 .585
600 .1095 .481 .516 .543 .565 .584 .600 .615 .627 795.0 .1373 .450 .485 .512 .534 .553 .569 .584 .596
500 .1303 .492 .527 .554 .576 .595 .611 .626 .638 556.5 .1859 .469 .504 .531 .553 .572 .588 .603 .615
400 .1619 .507 .542 .569 .591 .610 .626 .641 .653 477.0 .216 .479 .514 .541 .563 .582 .598 .613 .625
350 .1845 .515 .550 .577 .599 .618 .634 .649 .661 397.5 .259 .490 .525 .555 .574 .593 .609 .624 .636
300 .215 .525 .560 .587 .609 .628 .644 .659 .671 336.4 .306 .500 .535 .562 .584 .603 .619 .634 .646
250 .257 .536 .571 .598 .620 .639 .655 .670 .682 266.8 .385 .514 .549 .576 .598 .617 .633 .648 .660
AWG AWG
4/0 .303 .546 .581 .603 .630 .649 .665 .630 .692 4/0 .592 .630 .665 .692 .714 .733 .749 .767 .776
3/0 .382 .554 .589 .616 .638 .657 .673 .688 .700 3/0 .723 .670 .705 .732 .754 .773 .789 .804 .816
2/0 .481 .581 .616 .643 .665 .684 .700 .715 .727 2/0 .895 .690 .725 .752 .774 .793 .809 .824 .836
1/0 .607 .595 .630 .657 .679 .698 .714 .729 .741 1/0 1.12 .705 .740 .767 .789 .808 .824 .839 .851
1 .757 .609 .644 .671 .693 .712 .728 .743 .755 2 1.69 .714 .749 .776 .798 .817 .833 .848 .860
2 .964 .623 .658 .685 .707 .726 .742 .757 .769 4 2.57 .708 .743 .770 .792 .811 .827 .842 .854
4 1.518 .648 .683 .710 .732 .751 .767 .782 .794 6 3.98 .722 .757 .784 .806 .825 .841 .856 .868
6 2.41 .677 .712 .739 .761 .780 .796 .811 .823
8 3.80 .714 .749 .776 .798 .817 .833 .848 .860
Note: 1. 60 Hertz reactance in ohms per mile of each conductor of a single phase, or of a three phase, symmetrical tri-
angular spacing. For other arrangements of conductors see below. The reactance for other frequencies is F/60
times the table values. Reactance values for copper wire are for concentric standard copper conductors. Reac-
tance values for aluminum cable conductors are approximately correct.
A B
A B
3
D= ABC
C C
The Siemens Line Drop Calculator software application Contact your Siemens representative about obtaining this
simplifies the calculation of these parameters. Simply application. You may also download this application from
enter the system values and the application automatically the Siemens web site. Go to www.siemenstd.com, select
calculates the resistive and reactive components for you. Products, and then the Voltage Regulator item. This
Enter these values in the MJ-XL <REGULATOR> menu, application is available on the Download page.
and the MJ-XL automatically compensates for the line
drop when adjusting the output voltage of the regulator.
If the Un - - Ux taps are to the left of E2 with no taps to D.3.1.3 Single-Phase Straight design regulators
the right of E2, and the polarity mark is on one of the (ANSI type A) with forced air cooling
U taps, specify Utility Pol: NORM. (See Figure D.1.)
For these regulators, the Utility winding not only provides
power to the controller — it also provides power for the
forced air fan(s). The E2 tap is located between the Un - -
Ux terminals on the regulator’s nameplate schematic. The
U5 tap is normally used for fan voltage and can be either
to the left or to the right of E2. To determine whether the
U4 U3 E2 polarity is ‘normal’or ‘reverse’, you must examine both the
schematic diagram and the connection table on the name-
Polarity mark plate. From the connection table, determine the tap to
E2 on right which U2 should be connected.
E2 U3 U4
E2 on left
Table D.3 Nameplate for Single-Phase Straight Regulator with Cooling Fan
Single Phase Straight Regulator with Cooling Fan
Load Volt Tran Control Panel P to Basis Aux Volts Motor Fan Connection
Volts Sec Conn P14 to Volts Conn U2 to Volts
+/-10% P2 to
U21 to U15 to Volts
14400 P3 - 120 20 20 120 U3 126 U3 U7 240
13200 P4 - 120 20 20 120 U4 126 U53 U7 242
7200 P5 - 120 20 20 120 U6 126 U6 U8 240
From the table, the system load voltage is 7200 volts; therefore, U2 would be connected to U6. Now check the connection
diagram:
U6 U4 U3 E2 U5 U7 U8 U9
D.3.2.2 Multiple Utility Windings the “B” and “C” phase windings for fan(s) power. For this
case, use the Single phase procedure, defined above for
Regulators with more than one utility winding utilize the the “A” phase winding.
“A” phase utility winding for control and motor power, and
Figure D.6 U2 Connects to a “U” Terminal (U7 or U8) Which is to the Left of E2
Figure D.7 U2 Connects to a “U” Terminal (U7 or U8) Which is to the Right of E2
To prevent:
Methods other than the ones described above are also
used; however, the ones described above are the most
common and are recommended.
The regulator must be placed in neutral
before by-passing. The regulator must be placed in neutral before bypassing.
If there is any doubt as to the location of neutral, the line
should be dropped before bypassing the regulator.
Proper regulator bypassing procedure is of critical impor- Deactivating the MJ-XL Before Bypassing
tance. Regulators that are not in the neutral position when
bypassed frequently fail. This failure is the result of Consult your voltage regulator instruction manual for
extremely high circulating current inside the regulator bypassing instructions.
caused by what is effectively a short circuit being placed
across the series winding. The result of such a failure To eliminate the possibility of inadvertent (and possibly
can be catastrophic. catastrophic) tap operations during bypassing operations,
it is mandatory that you completely disable the control
Methods of Determining Neutral Tap Position panel.
Since the tap changing mechanism is submerged in a tank Disable the control panel as follows:
full of oil, some external means of determining tap posi-
tion is mandatory. Methods most commonly used include: 1. Disconnect the Polarized Disconnect Switch (PDS).
Ground 120 VAC 4.0 / 6.0A .4A 4.0 / 6.0A Ground Voltage
Press here to view the U2 voltage
Circuit Protection Fuses at the PDS. Press again to view
the P2 voltage at the PDS. Use
this key for calibrating the panel.
See Section 8.4 for details.
Vs Max/Min F Dmd Vs Max/Min R Dmd Vs Max/Min Reset Date Fwd BW Bandwidth Type ...
Vcomp Max/Min FDmd Vcomp Max/Min RDmd Vcomp Max/Min Reset time Fwd Delay Time Delay Syst Last Alert
Ild Max/Min F Dmd Ild Max/Min R Dmd Ild Max/Min Elapsed Ops Fwd Comp(R) Resistance DeltaPwr
PF Max/Min PFKVA max PFKVA max 24 Hr Ops Fwd Comp(X) Reactance Utility Pol Alerts:
KVA Max/Min PFKVA min PFKVA min 30 Day Ops U2 PT Low current
KW Max/Min F Dmd KW Max/Min R Dmd KW Max/Min MTD Ops Rev Volts P2 PT Auto inhibit
KVAR Max/Min F Dmd KVAR Max/Min R Dmd KVAR Max/Min Last Month Ops Rev BW CT ratio Tap track error
Freq Max/Min F Dmd KVA Max/Min R Dmd KVA Max/Min YTD Ops Rev Delay Meter Volts Neutral sig. err.
KWHR F Last Year Ops Rev Comp(R) I Threshold % Tap position???
KVAR HR F lead Tap position Max/Min Rev Comp(X) I Shift Low PT Thresh
KVAR HR F lag Alt Delay I Load Max Overcurrent
KWHR R VRC Stat VRC Select I Full Load NV RAM Reset
KVAR HR R lead VRC1 In Pwr Flow (mode) Low Battery
KVAR HR R lag VRC2 In PT Threshold High Voltage
VRC Mode Time Not in Auto
Local VRC% Date R Limit Reached
Format (Date) L Limit Reached
VRC Stage 1 Dmd Type Pseudo Manual
VRC Stage 2 Dmd Time
VRC Stage 3 Dmd Subperiods
VRC Remote Reset Min/Max?
MJ-3A VRC% Min/Max t.o.
Screen t.o.
AutoVRCset1 Function t.o.
AutoVRCset2 Basis Volts
AutoVRC1 %I R Limit
AutoVRC2 %I L Limit
TapAlert
VLC Enable VLC Select TapPosHold
VLC Upper Version
VLC Lower Memo 1
Memo 2
PDS
U11
Terminal Strip Wiring
U10
U2
E1
C2
P2
U12
69
Appendix I: Terminal Strip Wiring
Appendix J: MJ-XL Jumpers and Battery Replacement
2 SIEMENS MJX
1 1 2
JP9 J2
1 1
2 2
3 3
J23 J22
Battery (BT1)
2 1
1
J1 J9
2
2 1
J9
Note: The following jumpers are not installed: 2. Remove the MJ-XL from the weather-proof enclosure
J2 (factory use only) (i.e., lift it off of the hinges.)
JP9 (microprocessor reset for factory use). 3. Remove the side screws from the unit. (There are 4.)
4. Curl back the cable clamp on the back of the unit and
J.2 Battery Replacement remove the cable bundle from the reusable cable
This section provides instructions for replacing the MJ-XL clamp.
battery. For more information about the battery, see MJ-X 5. Lift and move the rear cover away from the front
Application Note AN-10: Replacing the MJ-X battery.
panel.
Note: Replace the MJ-X L battery within 1 month of 6. Remove the coin-cell battery (BT1) from its socket.
an active "Low Battery" alert to avoid data loss. See Figure J.1 on the previous page for battery loca-
tion.
To replace the MJ-XL battery, you will: 7. Put the new coin-cell battery in the battery socket,
making sure you have the proper orientation ("+" side
1. Remove the MJ-XL rear cover, up.)
2. Remove and replace the coin-cell battery.
8. Close the unit by reversing the steps outlined above.
3. Close up the unit and reconnecting power.
9. Turn the power on and verify that the unit comes up
Replacement Battery and displays the <METER> menu heading. If the unit
fails to come up, retrace the above steps to make
Radio Shack carries replacement batteries for the MJ-XL. sure that the battery has been properly oriented and
The battery is a coin-cell type Lithium cell, Panasonic inserted.
BR2032 or equivalent.
Verifying the Replacement Battery
Replacement Procedure
After replacing the battery, verify the Low Battery Alert is
During the following procedure, use proper Electro-Static no longer active.
Discharge (ESD) precautions. If possible, use an ESD wrist
strap. If no wrist strap is available, touch a grounded sur-
face before beginning. (Two accessible ground points are
the screw jacks of the Data Port connector.)
Bold indicates standard "Polarized Disconnect Switch (PDS)" signals. For Siemens regulators, these ten signals connect to
the corresponding pins of the PDS connector block.
Table K.2 below describes the connections for terminal strip P2B. See Table 2.5 for complete descriptions of these terminal
connections. See Figure 2.3 for simplified schematic drawing of remote control connections.
Table K.3 below describes the connections for terminal strip P3A
Table K.4 below describes the connections for terminal strip P3B
Use the following instructions as a quick reference for per- 1. Press Time Delay Fast-Path key
forming many of the standard MJ-XL operating proce-
dures. 2. Read time delay on display
View Instantaneous Load Voltage (Vld) 3. Press Change key - right hand digit will flash
1. Press Menu key twice 4. Press Left Arrow key to move left on display or Right
Arrow key to move right on display
2. Press Down Arrow once
5. Press Up/Down Arrow key to increase or decrease
3. Read voltage (Vld) on display time delay on display - flashing digit will change
View/Reset Max/Min Values 6. Press Save key to save the new time delay value
1. View Meter value or tap position View/Set Line Drop Compensation Values
3. Read maximum value on display 2. Read resistive compensation voltage (R) on display
4. To reset maximum value on display, press Cancel 3. Press Change key - right hand digit will flash
Reset key once
4. Press Left Arrow key to move left on display or Right
5. Press Max/Min key again Arrow key to move right on display
6. Read minimum value on display 5. Press Up/Down Arrow key to increase or decrease
compensation voltage on display - flashing digit will
7. To reset minimum value on display, press Cancel change
Reset key once
6. Press Save key to save the new resistive compensa-
View/Set Forward Voltage Level Value tion voltage value
1. Press Menu key twice Note: Do not use voltage readings at the Voltage Cal-
ibration (Test) terminals as an indication of the
2. Press Right Arrow key five times to view the <CON- regulated load voltage
FIGURE> menu
1. Connect true-rms-reading voltmeter to Voltage Cali-
3. Press Up/Down Arrow key to display the desired bration (Test) terminals
item.
2. Press U2 P2 key to display U2 (or P2) Cal item on the
4. Press Change key display.
5. Press Left Arrow or Right Arrow to step through digits 3. If voltmeter reading is not the same as U2 (or P2) Cal
in numeric values item, press Change
6. Press Up/Down Arrow to toggle through text choices 4. At password prompt, press Up/Down Arrow key to
or to increase or decrease numeric values enter first digit of password (See Manual Chapter 4)
7. Press Save key to save the new value 5. Press Right Arrow key to step through remaining dig-
its and enter values
8. Repeat steps 3 through 7 for all desired configuration
items 6. Press Save key to submit password
View/Set the MJ-X L Clock (Time and Date) 7. If password is correct, press Change key - right hand
digit will flash
1. Press Menu key twice
8. Press Up/Down Arrow key to increase or decrease
2. Press Right Arrow key five times to view the <CON- value until U2 (or P2) Cal value is equal to the voltme-
FIGURE> menu ter value
3. Press Down Arrow until the TIME item is displayed. 9. Press Save key to save the new calibration value
4. Press Change key - the left hand digit will flash 10. See Manual Chapter 6 for additional calibration proce-
dures
5. Press Up/Down Arrow key to increase or decrease
the value Set Tap Position
6. Press Right Arrow to step to next digit 1. Place Remote/Auto/Manual switch in Manual position
7. When all of the digits are set, press Right Arrow key 2. Use Raise/Lower switch to return regulator to neutral
until A or P is flashing position
8. Press Up/Down Arrow key to toggle between A and P 3. Place Remote/Auto/Manual switch in Auto position
10. Press Down Arrow key to display the DATE item 1. Display Tap= in <COUNTERS> menu
11. Press Change key - the left hand digit will flash 2. Press Change key
12. Press Up/Down Arrow key to increase or decrease 3. Press Up/Down Arrow key until reading matches reg-
the value ulator Position Indicator value
13. Press Right Arrow to step to the next digit to be 4. Press Save key to save new value
changed
J P
Jumpers 70 P2 Calculation 33
P2 Potential Transformer 19
K Parity 12
kVAR 35 PASSWORD Menu 16, 27–30
kW 34 Password Security Activated 29
PDS 53
L Polarized Disconnect Switch 53
L Limit 20 Potential Transformer 19
Leading and Lagging Regulators 57 Potential Transformer Threshold 21
Line Drop Calculator 58 Power Flow Direction 42
Line Drop Compensation 24, 34, 57 Power Flow Modes 20, 44–47
Load Volts 34 Bi-directional 21, 46
Local Data Port 12 Co-generation 21, 47
LOG SETUP Menu 16, 26 Forward Locked 21, 45
Logging Requirements 16 Idle Reverse 21, 46
Low Current Threshold 20 Neutral Reverse 21, 47
LTCs 2 Reverse Locked 45
Reversed Locked 21
M Tap Changer Direction 44
Main Processor Board Version 32 Power Fuse 10
W
Website 2
Manual No. 21-115527-010-04 © 2000 Siemens Power Transmission & Distribution Inc..