Metal-Enclosed Switchgear
Selection and Application Guide
www.usa.siemens.com/switchgear
3
Type WL Low Voltage Metal-Enclosed Switchgear
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Construction Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 5
WL Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electronic Trip Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- 9
Time/Current Characteristic Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 - 12
Breaker Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 - 21
WL Secondary Terminal Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
WL Communication Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Section Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 - 25
Shipping Weights and Dimensional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 - 30
VT, CPT, CT Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Guide Form Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 - 36
Type WL Low Voltage Metal-Enclosed Switchgear
General Information
2
Type WL Low Voltage Metal-Enclosed Switchgear
Construction Details
General Standard finish color is light gray ANSI Each complete vertical section contains
The Siemens Type WL switchgear 61. The standard painting process is a three compartments.
assembly consists of one or more UL approved electrostatic powder coat (1) Front compartment containing
metal-enclosed vertical sections. The paint system utilizing a polyester powder breakers and/or auxiliary equipment
end sections are designed to allow coat paint. The completed finish has a (2) Bus compartment containing
installation of future sections. nominal 2 mils dry film thickness. horizontal and vertical bus
(3) Rear cable compartment containing
Each vertical section consists of up to Assembly Construction the load side runbacks connecting
four individually enclosed breaker or Siemens Type WL metal-enclosed low the load side of the breaker to the
auxiliary compartments which are sized voltage switchgear is constructed of load cable terminals
to provide uniform height. a rigid internal frame structure that
minimizes the possibility of damage Within the front compartment, each
Included in each assembly are various during shipment and supports multiple breaker is barriered and compartmented
components such as circuit breakers, installation methods – rolling or lifting. from all other breakers in the front
instrumentation and control equipment, Lifting eyes are integrated into the compartment. This design also isolates
transformers, relays, three-phase bus internal frame design and ensure the breakers in the front compartment
work, and all internal wiring, connectors, the structural integrity of the lifting from the bus compartment.
and other supporting equipment. assembly is always adequate for the
weight of the total structure. Optional barriers can be supplied to
In accordance with ANSI C37.20.1, the isolate the bus compartment from the
maximum temperature for parts that If requested in advance, the switchgear rear cable compartment. Other optional
are handled is 50°C. The main bus structure can be shipped so that the barriers include: (1) Full depth section
maximum temperature rise is 65°C unit can be tilted onto its back during barriers to isolate one section from the
above 40°C ambient. The temperature installation. This is an option that must adjacent section(s). (2) Barriers to isolate
rise of the air surrounding the cable be specified at order entry. the incoming line side connections to the
connection points is limited to 45°C main breaker(s) from the load side bus
above 40°C ambient. and connections in the switchgear section.
(Line/load barriers are provided as a
Finish 1 standard feature for service equipment
During construction, the structural steel main breakers.)
parts, panels, and compartments are all 2
prepared for painting by a five-stage
wash system.
11
9
10
3
Type WL Low Voltage Metal-Enclosed Switchgear
Construction Details
Main and Ground Bus Control and Communication Wiring Circuit Breaker Compartments
The standard main bus is silver-plated Standard control and communication Typical circuit breaker compartments
copper. Tin-plated copper bus is wiring is #14 AWG extra-flexible, include primary disconnects, drawout
optionally available. Vertical and stranded copper type SIS. Control rails, secondary disconnects, vertical
horizontal bus bar utilize a channel and communication wiring is installed wireway, horizontal wireway and,
shape design to maximize short circuit and accessed from the front of the if applicable, TOC switch operator,
withstand capability and minimize heat switchgear structure. Each breaker MOC switch operator and associated
rise. All bus joints include Grade 5 bolts compartment has a dedicated horizontal interlocks. Draw-out rails allow the
and conical spring washers. Provisions and vertical wireway. breaker to be withdrawn from the
for future extension of the main bus compartment without additional
include plated joints and high tensile For devices not having screw-type extensions or adapters. Up to six (2
strength steel hardware. terminals, pressure terminals are used. sets of three) current transformers for
metering or relaying can be mounted
The main three-phase horizontal bus Insulation in each compartment.
is arranged vertically one phase above The insulation used is a UL recognized
the other with edge-to-edge alignment thermoset material that has excellent heat A variety of auxiliary devices such as
to provide high, short circuit strength. resistance, flame retardance, dimensional breaker control switches, indicating
Insulated main bus with isolated vertical stability and low moisture absorption. lights and pushbuttons can be mounted
bus is optional. on the breaker compartment door.
5 6 7 8
4
Type WL Low Voltage Metal-Enclosed Switchgear
Construction Details
5
Type WL Low Voltage Metal-Enclosed Switchgear
WL Circuit Breaker
WL Circuit Breaker:
Superior individual products for low-voltage power distribution systems
2 6 7
3
5 8
4
9
1
21
11
25 10
19
22
18
23
12
24
17 13
20 15
14
16
6
Type WL Low Voltage Metal-Enclosed Switchgear
Electronic Trip Unit
Electronic Trip Unit It allows the WL breaker, as a family, This is where the Extended
During development of our electronic across the entire range of ampacities Instantaneous Protection feature
trip units we have consistently striven to be applied at the withstand of the WL can offer the next level
to ensure modularity. The following rating of the breaker with minus 0% of coordination and protection
are just some of the modules that are tolerance; that means no instantaneous functionality. Unlike an instantaneous
simple to retrofit at any time: override. EIP further enables the circuit override, Extended Instantaneous
• Ground fault protection breaker to be applied up to the full Protection (EIP) allows the full
• Communication interrupting rating of the breaker on withstand rating — in fact up to the
systems where the available fault tolerance of plus 20% higher. Of
• Metering function current exceeds the withstand rating, course, EIP still provides the ability
• Displays even with LS-only trip units. Why is of the breaker to be applied at the
• Rating plugs this feature important? The answer interrupting level, as high as 150kA
is reliable power. in a Frame Size III, non-fused breaker.
This enables fast local adaptation to This unique combination enables
new system conditions. At the same The coordination of the main breaker the system designer to achieve the
time, the ETUs are provided with new, and the first level of feeder breakers highest possible level of coordination
innovative functions, and all trip is especially important because of the in the industry and also allows
units are completely interchangeable wide spread outage that will occur if application of the WL on modern
independent of breaker ratings. one of these breakers trips unnecessarily. power systems with extremely high
levels of available fault current.
Rating Plug Conventional practice is to specify
The Rating Plug is a replaceable electronic trip beakers with “LS” type A further benefit offered by EIP, over
module that enables users to reduce trip units in critical power systems. a standard LS trip unit equipped
the rated device current for optimum These ‘Long-Time’ and ‘Short-Time’ only breaker, is that it provides an extra
adaptation to the system; e.g. during trip units forgo the fast tripping times measure of protection in the event
startup of a plant section. The Rating given by an ‘Instantaneous’ function. that the available fault current
Plug should be selected so that it The justification for this delay is the increases at some time during the life
corresponds to the rated current of benefit of allowing a downstream of the system beyond the withstand
the system. breaker to open first to clear a high level. This would typically be due to
magnitude fault. The main or feeder a utility transformer change but
Switch-selectable I2t or I4t stays closed to keep the remainder of could also be due to the addition
Characteristic Curve Improved the loads operating. of generators or large motors that
Overload Protection contribute fault current. EIP provides
The best possible protection is assured However, a circuit breaker with an the breaker the ability to react in an
when all protective devices in the LS-only trip unit may never be applied instantaneous fashion to a high level
system are optimally coordinated. on a system capable of delivering fault fault instead of having to rely on
To achieve optimum selectivity and current higher than the breaker’s with- the slower reaction time of the
coordination, the long-time characteristic stand rating, commonly 85kA or less. short-time function.
can be switched between l2t and l4t. Where the available fault current is
above this level, a breaker with
Switchable Parameter Sets an additional function must be
Sample Configuration of an ETU745
To allow the protection to adapt to used — an instantaneous override.
This instantaneous override function Manual Trip Indicator with
changes in system needs such as optional remote RESET
switching between utility and generator trips the breaker instantly when
feeds, WL Circuit Breakers support ETUs the fault current reaches a
with two independent parameter sets. pre-determined level below the LCD display with
withstand rating, usually around adjustable-angle
Switching between the parameter sets viewing
occurs in less than 100 ms and can be 20% lower. The benefit of this
override is to allow application of Micro switches
done remotely or via a contact input to for switch
an optional CubicleBUS module. the breaker up to the interrupting selectable
rating, which may be as high as characteristic
Extended Instantaneous Protection 150kA. The disadvantage is that curve adjustments
The electronic trip units designed it compromises the coordination
for use with the WL circuit breaker benefit because the main will
Rating Plug
provide a feature we call “Extended probably trip at the same time as
Instantaneous Protection” a downstream branch breaker in
Ground Fault
(Patent Pending). that 20% lower override window. Protection
Module
(field installable)
7
Type WL Low Voltage Metal-Enclosed Switchgear
Electronic Trip Unit
Additional Functions
Protective Functions of the circuit
Selectable neutral protection -- 쏹
breaker. These are determined by the
selection of the appropriate trip unit. Defeatable short-time delay -- --
Defeatable instantaneous protection -- --
Dynamic Arc-Flash Sentry (Patent Selectable thermal memory -- --
Pending) A unique feature of the WL
Zone selective interlocking -- --
trip unit allows the system designer to
achieve lower levels of arc flash energy Selectable I2t or fixed short-time delay -- --
and delayed tripping for selective trip Adjustable instantaneous pick-up 1 --
coordination purposes. Selectable I2t or I4t long-time delay -- --
Adjustable short-time delay and pick-up 쏹 쏹
Dynamic Arc-Flash Sentry (DAS) employs
Selectable and adjustable neutral protection -- --
the unique dual protective setting
capability of the 755 and 776 trip units, Dual protective setting capability -- --
coupled with the ability to easily toggle to Extended instantaneous protection 쏹 쏹
a lower arc flash parameter set. A normal
Parameterization and Displays
operation parameter set can be optimized
for selective trip coordination, while the Parameterization by rotary switches (10 steps) 쏹 쏹
second set is optimized for lower arc Parameterization by communication (absolute values) -- --
flash energy levels. The dynamic action Parameterization by menu/keypad (absolute values) -- --
comes from the ability to switch from Remote parameterization of the basic functions -- --
the normal operation set to the arc flash
limiting set based on the presence of Remote parameterization of the additional functions -- --
personnel as they approach the flash Alphanumeric LCD -- --
protection boundary. A wide variety of Graphical LCD -- --
switching methods may used based on
Metering Function
the needs of a particular facility. The
capabilities range from fully automatic Metering function Plus -- --
switching using appropriate occupancy Communication
sensors to manual switching via a
key operation. CubicleBUS -- --
Communication via PROFIBUS-DP -- --
Communication via the MODBUS -- --
Communication via the Ethernet (BDA) -- --
쏹 standard -- not available optional 1 Fixed short-time delay only
8
Type WL Low Voltage Metal-Enclosed Switchgear
Electronic Trip Unit
Neutral protection N 쏹 쏹 쏹 쏹
Additional Functions
Selectable neutral protection 쏹 쏹 쏹 쏹
Alphanumeric LCD -- --
Graphical LCD -- -- -- 쏹
Metering Function
Metering function Plus
Communication
CubicleBUS 쏹 쏹 쏹 쏹
9
Type WL Low Voltage Metal-Enclosed Switchgear
Time / Current Characteristic Curves
Tripping Characteristics
Every trip unit and every trip function has To obtain a complete release characteristic, by a current already flowing before trip-
its own characteristic. You will find just a the appropriate characteristic functions ping. If the overcurrent trip takes place
small section of these illustrated below. must be determined. immediately after closing and the overcur-
The characteristics show the respective rent release is therefore not yet activated,
greatest and smallest setting range of The characteristics show the behavior of the opening time is prolonged by about
WL Circuit Breakers. the overcurrent release when it is activated 3 to 10 ms, depending on the value of
the overcurrent.
10
Type WL Low Voltage Metal-Enclosed Switchgear
Time / Current Characteristic Curves
Tripping Characteristics
ETU745
ETU748
11
Type WL Low Voltage Metal-Enclosed Switchgear
Time / Current Characteristic Curves
Tripping Characteristics
ETU776
12
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
Breaker Ratings
Frame Size II
Frame Rating 800 1600 2000 3200
Rating Class N S H L F N S H L F S H L F S H L
Instantaneous Short-circuit Current 1 254VAC 50 65 85 100 200 50 65 85 100 200 65 85 100 200 65 85 100
(kA RMS) 50/60 Hz 508VAC 50 65 85 100 200 50 65 85 100 200 65 85 100 200 65 85 100
635VAC 50 65 65 85 200 50 65 65 85 200 65 65 85 200 65 65 85
Short-time Withstand
Current Icw
(kA RMS) 50/60 Hz 0.5s 50 65 65 85 — 50 65 65 85 — 65 65 85 — 65 65 85
Extended Instantaneous
Protection
(kA RMS -0% to +20%) 50 65 65 85 — 50 65 65 85 — 65 65 85 — 65 65 85
Close and Latch Ratings
(kA RMS) 50/60 Hz 50 65 65 85 65 50 65 65 85 65 65 65 85 65 65 65 85
Rating Plug Range 200, 225, 250, 300, 315, 350, 200, 225, 250, 300, 315, 350, 200, 225, 250, 300, 315, 200, 225, 250,
400, 450, 500, 600, 630, 700, 400, 450, 500, 600, 630, 700, 350, 400, 450, 500, 600, 300, 315, 350,
800 amps 800, 1000, 1200, 1250, 630, 700, 800, 1000, 400, 450, 500,
1600 amps 1200, 1250, 1600, 600, 630, 700,
2000 amps 800, 1000, 1200,
1250, 1600, 2000,
2500, 3000,
3200 amps
Endurance Rating
(switching operations Mechanical 15,000 15,000 15,000 15,000
with maintenance) 2 Electrical 15,000 15,000 15,000 15,000
13
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
Ratings
WL Circuit Breakers
Rated maximum voltage VAC 635 635 635 635 635 635 635
Permissible ambient
temperature
operation
(for operation with
LCD max. 55°C) °C -25 / +70 -25 / +70 -25 / +70 -25 / +70 -25 / +70 -25 / +70 -25 / +70
Storage
(observe special
conditions for LCD) °C -40 / +70 -40 / +70 -40 / +70 -40 / +70 -40 / +70 -40 / +70 -40 / +70
Power loss at Rated Current W 85 320 500 1150 700 1100 1650
with 3-phase 2 130 520 850
symmetrical load (fused) (fused) (fused)
Operating times
Make-time ms 35 35 35 35 35 35 35
Break-time ms 34 34 34 34 34 34 34
Make-time, electrical
(via closing solenoid) ms 50 50 50 50 50 50 50
Break-time, electrical
(via shunt trip) ms 40 40 40 40 40 40 40
Break-time, electrical
(via instantaneous UVR) ms 73 73 73 73 73 73 73
14
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
WL Circuit Breakers
Mounting position
Auxiliary secondary wire Bare
size (Cu) max # of aux. wire 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14
connecting leads x cross pressure or or or or or or or
section (solid or stranded) terminal 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16
Tension
spring
terminal 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14
Ring tongue 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14 2 x AWG 14
terminal 1 x AWG 10 2 1 x AWG 10 2 1 x AWG 10 2 1 x AWG 10 2 1 x AWG 10 2 1 x AWG 10 2 1 x AWG 10 2
(standard) 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16 2 x AWG 16
TOC wire connection size Bare
(Cu) max # of aux. wire
connecting leads x cross pressure
section (solid or stranded) terminal 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14
Weight 3
Circuit Breaker kg/lb 72/159 72/159 75/165 95/209 155/341 155/341 155/341
Guide Frame kg/lb 51/112 51/112 60/132 69/152 139/306 139/306 139/306
MOC wire connection Bare
size (Cu) max # of aux. wire
connecting leads x cross pressure
section (solid or stranded) terminal 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14 1 x AWG 14
1 Maintenance consists of replacing main contacts and arc chutes (see operating instructions.)
2 For use only with Siemens supplied ring terminals (WL10RL).
3 Fused Breaker Weights (kg/lb) Frame Size II (fused) Frame Size III (fused)
Breaker 103/227 same as table above
Guide Frame 68/150 130/275
Fuse Carriage – 102/225
15
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
Short-circuit protection
Standard slow-blow cartridge fuse 24 - 60 V 6A
110 - 250 V 3A
Auxiliary Release
Undervoltage release Operating values ≥ 85% (circuit breaker can be closed)
(UVR) 35 - 70% (circuit breaker opens)
AC Coil voltage tolerance at 120V AC, 240V AC 85 - 110%
DC Extended tolerance for battery operation at 24V DC, 48V DC, 125V DC, 250V DC 85 - 126%
Rated control supply voltage AC 50/60Hz V 120, 240
DC V 24, 48, 125, 250
Power consumption (inrush / continuous) AC VA 200 / 5
DC W 200 / 5
Opening time of the circuit breaker for AC / DC ms 200
UVR (no time delay), 2 settings
Setting 1 ms 80
Setting 2 ms 200
UVR (with time delay)
Adjustable delay s 0.2 to 3.2
Reset by additional NC direct opening ms ≤ 100
16
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
17
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
1 Extended Instantaneous Protection (EIP) allows the WL breaker to be applied at the withstand rating of the breaker
available
with minus 0% tolerance; that means no instantaneous override whatsoever. EIP further enables the circuit breaker
– not available
tobe applied up to the full instantaneous rating of the breaker on systems where the available fault current exceeds
the withstand rating. optional
2 Ground Fault Module cannot be removed after installation.
18
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
Step for Settings via Communications or ETU Key Pad Setting range of the Ig
from … to step from … to step Frame Size II Frame Size III
0…1 0.1 1000 … 1600 50 A 100 A 400 A
1 … 100 1 1600 … 10000 100 B 300 A 600 A available
– not available
100 … 500 5 10000 … max 1000 C 600 A 800 A
optional
500 … 1000 10 D 900 A 1000 A
E 1200 A 1200 A
19
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
Ground fault protection 2 (field installable module) (field installable module) (field installable module)
Trip and alarm function (via communications) (via key pad or communications)
Detection of the ground fault current
by residual summing method
Detection of the ground fault current
by direct summing method
Setting range of the Ig for trip A, B, C, D, E A … E (step: 1A) A … E (step: 1A)
G Setting range of the Ig for alarm A, B, C, D, E A … E (step: 1A) A … E (step: 1A)
Setting range of the time delay tg
(seconds) 0.1, 0.2, 0.3, 0.4, 0.5 0.1 … 0.5 (step: 0.001s) 0.1 … 0.5 (step: 0.001s)
Switch-selectable
ground fault protection
(I 2t / fixed)
Setting range time delay tg at I 2t 0.1, 0.2, 0.3, 0.4, 0.5 0.1 … 0.5 (step: 0.001s) 0.1 … 0.5 (step: 0.001s)
ZSI ground function per CubicleBUS module per CubicleBUS module per CubicleBUS module
1 Extended Instantaneous Protection (EIP) allows the WL breaker to be applied at the withstand rating of the breaker with available
minus 0% tolerance; that means no instantaneous override whatsoever. EIP further enables the circuit breaker to be applied – not available
up to the full instantaneous rating of the breaker on systems where the available fault current exceeds the withstand rating.
2 Ground Fault Module cannot be removed after installation. optional
Notes: M = Motor protection setting (20 ms)
Communications = Setting the parameters of the trip unit via the Breaker Data Adapter, MODBUS, or PROFIBUS
Key pad = Direct input at the trip unit
20
Type WL Low Voltage Metal-Enclosed Switchgear
Breaker Technical Data
21
Type WL Low Voltage Metal-Enclosed Switchgear
WL Secondary Terminal Assignments
22
Type WL Low Voltage Metal-Enclosed Switchgear
WL Communication Overview
Connection Diagram
3 WL Circuit Breaker
4 COM 16 MODBUS Ethernet
module or COM 15
PROFIBUS module
5 Breaker Status Sensor 9510 Meter*
(BSS) MODBUS Master (Ethernet Gateway)
PLC or Supervisory
6 Electronic Trip Unit Software
MODBUS 12
7 Metering function PLUS Optional 8 9 10 11 15
BDA Plus*
8 Zone Selective 14
Interlocking (ZSI) module
9 Digital output module 4
with relay or optocoupler 5
outputs 2 1 6 3
Features
• Industry standard MODBUS or • The ability to connect additional input • Innovative software products for local
PROFIBUS communication available and output modules to the breaker- configuration, operation, monitoring
on all WL breakers from 200A to internal CubicleBUS of the WL opens and diagnostics of WL Circuit Breakers
5000A. up a range of opportunities to reduce using MODBUS, PROFIBUS or via
• The high modularity of the WL Circuit secondary device count and wiring and Ethernet/Intranet/Internet.
Breakers and accessories allows simple to increase functionality implemented • Complete integration of WL Circuit
retrofitting of all communication in switchgear. Breakers in all Totally Integrated Power
components. and Totally Integrated Automation
Solutions.
23
Type WL Low Voltage Metal-Enclosed Switchgear
Section Configurations
• Non-fused walk-in outdoor – 60” standard Main Breaker Main Breaker Feeder Breaker
and 75” optional Feeder Breaker Main Breaker
800, 1600, 800, 1600, 800,1600, 2000,
800, 1600, 4000, 5000
3200, 4000
• Fused walk-in outdoor – 65” standard and 2000, 3200 2000, 3200 2000, 3200
Refer to Note 1
Refer to Note 3
75” optional
Feeder Breaker Blank or Feeder Breaker Feeder Breaker
• Walk-in outdoor aisle is 42" deep 800, 1600, Instrument 800, 1600, 800,1600, 2000
Feeder Breaker
800, 1600, 2000
Compartment 2000
• Sections with cable connected main, tie 2000 Refer to Note 1
and/or feeder breakers that are 3200 amp 22 in. 22 in. 22 in. 32 in. 32 in.
or greater must be minimum depth of (559 mm) (559 mm) (559 mm) (813 mm) (813 mm)
70" for unfused breakers and 75" for
fused breakers.
Note 1 – If a 4000 amp feeder breaker is installed in
Compartment C, Compartment D must be a Blank or
Instrument Compartment.
Note 2 – If a 4000 amp breaker is installed in Main Sections – Fused Breakers
Compartment B, Compartment A must be a Blank or
Instrument Compartment.
Blank or Blank or Blank or Blank or
Note 3 – If incoming is bottom, feeder breakers can Instrument Instrument Instrument Instrument
mount in compartments A and/or B. Compartment Compartment Compartment Compartment
24
Type WL Low Voltage Metal-Enclosed Switchgear
Section Configurations
Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Blank or
800, 1600, 800, 1600, 800,1600, 2000 800,1600, 2000 800, 1600, 800, 1600, 800, 1600, Instrument
2000 2000 Refer to Note 2 2000 2000 2000 Compartment
Tie Breaker Feeder Breaker Feeder Breaker Tie Breaker Feeder Breaker
Tie Breaker 800,1600, 2000,
800, 1600, 800, 1600, 4000 800, 1600, 800, 1600,
2000, 3200 2000 3200, 4000 2000 2000
Refer to Note 2
Tie Breaker
Feeder Breaker 3200, 4000
Feeder Breaker Tie Breaker Tie Breaker Feeder Breaker Tie Breaker Tie Breaker
800,1600, 2000, 800, 1600,
800, 1600, 800, 1600, 4000, 5000 800, 1600, 5000
3200, 4000 2000
2000, 3200 2000, 3200 Refer to Note 1
2000
Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker
Feeder Breaker
800, 1600, 800, 1600, 800,1600, 2000 800, 1600, 800, 1600, 800, 1600,
Refer to Note 1
800,1600, 2000
2000 2000 2000 2000 2000
22 in. 22 in. 32 in. 32 in. 22 in. 22 in. 32 in. 32 in.
(559 mm) (559 mm) (813 mm) (813 mm) (559 mm) (559 mm) (813 mm) (813 mm)
Main and Tie Sections – Non-Fused Breakers Main and Tie Sections – Fused Breakers
Blank or Feeder Breaker Blank or Blank or Blank or Feeder Breaker Feeder Breaker
Instrument Feeder Breaker
Instrument 800, 1600, Instrument Instrument 800, 1600, 800, 1600,
Compartment 800,1600, 2000
Compartment 2000 Compartment Compartment 2000 2000
Main Breaker Tie Breaker Main Breaker Main Breaker Main Breaker Tie Breaker
Main Breaker Tie Breaker
800, 1600, 800, 1600, 800, 1600, 800, 1600, 800, 1600, 800, 1600,
4000 4000
2000, 3200 2000, 3200 2000 2000 2000 2000
Tie Breaker Main Breaker Tie Breaker Tie Breaker Main Breaker
Tie Breaker Tie Breaker Main Breaker
800, 1600, 800, 1600, 800, 1600, 4000 4000 800, 1600, 800, 1600, 800, 1600,
2000, 3200 2000, 3200 2000 2000 2000 2000
Feeder Breaker Feeder Breaker Main Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker Feeder Breaker
800, 1600, 800, 1600, 800, 1600, 800,1600, 2000 800,1600, 2000 800, 1600, 800, 1600, 800, 1600,
2000 2000 2000 2000 2000 2000
Feeder Breaker Feeder Breaker Blank or Feeder Breaker Feeder Breaker Blank or
800, 1600, 800, 1600, Instrument 800, 1600, 800, 1600, Instrument
2000 2000 Compartment 2000 Compartment
2000 Refer to Note 6
25
Type WL Low Voltage Metal-Enclosed Switchgear
Shipping Weights and Dimensional Information
Siemens Type WL Low Voltage Switchgear assembly with a 60 in. (1524 mm) internal
can be configured in many ways by structure is 82.3 in. (2090 mm) and the
combining different section types. Up depth of a walk-in outdoor assembly with
to five vertical sections plus a transition a 60 in. (1524 mm) internal structure is
section can be shipped together as a unit. 110.7 in. (2812 mm). Maximum shipping
Maximum shipping split length for indoor split length for outdoor structures is 66 in.
structures is 110 in. (2794 mm). If all (1676 mm).
vertical sections are not to be shipped as
a unit, specifications need to be provided The major assembly sections include:
that describe the limiting factors (e.g., • Transition Sections — used as
low door or narrow hallway). transition to liquid filled transformer
or to outdoor dry type transformers.
Normal indoor vertical sections are 96 in. • Auxiliary Sections — used as incoming
(2438 mm) high and a minimum 60 in. bus duct or cable entrance when a
(1524 mm) deep for non-fused breakers main breaker is not used.
and 65 in. (1651 mm) deep for fused
breakers. A top-mounted hoist, which • Main Sections — used to contain main
breaker and may house metering and
is shipped as an accessory in a separate feeder breakers.
container, adds 6.2 in. (157 mm) for a
total installed height of 102.2 in. • Feeder Sections — used to contain
(2596 mm). feeder breakers and other equipment
such as instrumentation.
Transition Section For Liquid Filled and
The outdoor switchgear assembly • Tie Sections — used to contain tie Outdoor Dry Type Transformers
contains the indoor assembly in an breaker and other equipment such
outdoor housing. The overall height is as feeder breakers.
112.8 in. (2865 mm) for non walk-in Dimension A Weight
designs and 114 in. (2896 mm) for in inches (mm) in lbs. (kg)
walk-in designs. The depth of a Indoor 55 (1397) 500 (227)
non walk-in outdoor Outdoor 61 (1549) 550 (250)
Section Type 22" 22" 32" 32" 38" 38" 48" 48"
Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor
26
Type WL Low Voltage Metal-Enclosed Switchgear
Dimensional Information
1.50 5.86
(38) (149) 7.88 1
.86 (200)
(22)
Note 4.82
3 B
(122)
4.00
(102)
Transformer
Throat
Liquid filled &
outdoor dry type Maximum available 4.00 2
transformers only space in top or bottom (102)
of unit for customer's
power cables
1.00 End Trim Panel (typ.)
A CL (25) Required on left and
(4) Holes for
.50 (12mm) right end of switchboard
Grade 5 lineup — adds 2”
anchor bolts to total lineup width
5.00
Space for (127)
secondary 2.12
leads from (54)
above
14.9 3.00 (76)
(378)
2.00 (51)
D Space for
secondary 7.00 C
leads from (179)
below
4.40 (112)
2.37 (60)
1.00 (25)
Note 4
2.00 (51)
1.00 (25) W
W = 22 (559) or 32 (813)
Optional Hoist
Lifting Holes (3) Vent stack
4.0 (102)
24.9
(632)
hoist
Extension
92.0
(2337)
42.0 (1067)
Minimum
Aisle Space
Recommended
Floor Line
2.37 G
(60)
A
A E F G
Equipment Depth Breaker Compartment Depth Rear Compartment Depth Anchor Bolt Spacing
60 (1524) Non-fused breakers 19.8 (503) 22.4 (569) 59.13 (1502)
65 (1651) Fused breakers 24.8 (630) 22.4 (569) 64.13 (1629)
70 (1778) Non-fused breakers 19.8 (503) 32.4 (823) 69.13 (1756)
75 (1905) Fused breakers 24.8 (630) 32.4 (823) 74.13 (1883)
80 (2032) Non-fused breakers 19.8 (503) 42.4 (1077) 79.13 (2010)
80 (2032) Fused breakers 24.8 (630) 37.4 (950) 79.13 (2010)
Note: Dimensions shown in inches and (mm).
28
Type WL Low Voltage Metal-Enclosed Switchgear
Dimensional Information
1 60" is representative for a 60" deep switchgear internal structure. For other 3 Refer to appropriate indoor plan view for available customer conduit information.
internal structure depths (65 or 75) add extra depth to 60" that is shown.
2 75.37 is representative for a 60" deep internal structure. For other internal
structure depths (65 or 75) add extra depth to 75.37 that is shown.
1
2
1 60" is representative for a 60" deep switchgear internal structure. For other 3 Refer to appropriate indoor plan view for available customer conduit information.
internal structure depths (65 or 75) add extra depth to 60" that is shown.
2 103.8" is representative for a 60" deep internal structure. For other internal
structure depths (65 or 75) add extra depth to 103.8" that is shown.
Dimensions shown in inches (mm) 3 60.43 dimension is based on 60" internal frame structure and if a deeper
1 110.7 dimension is based on 60" internal frame structure and if a deeper internal frame structure is used (65 or 75) the extra depth should be added
internal frame structure is used (65 or 75) the extra depth should be added to the 60.43 dimension.
to the 110.7 dimension. 4 102.2 dimension is based on 60" internal frame structure and if a deeper
2 103.8 dimension is based on 60" internal frame structure and if a deeper internal frame structure is used (65 or 75) the extra depth should be added
internal frame structure is used (65 or 75) the extra depth should be added to the 102.2 dimension .
to the 103.8 dimension.
30
Type WL Low Voltage Metal-Enclosed Switchgear
VT, CPT, CT Data
Primary Secondary
kVA Phase Voltage Voltage
3
5
Single 240/480 120/240
10 1
15 1
Current Transformers for FSII WL Breaker Applications - External Metering and Relaying 2
Current Transformers for FSIII WL Breaker Applications – External Metering and Relaying 2
31
Type WL Low Voltage Metal-Enclosed Switchgear
Guide Form Specifications
SECTION 16435 – LOW VOLTAGE E. [Manufacturer Seismic Qualification]: 1.5 DELIVERY, STORAGE, AND HANDLING
SWITCHGEAR Switchgear, and associated breakers, A. Deliver products in factory labeled
shall meet and be certified to seismic packages. Shipping groups shall not
PART 1 - GENERAL requirements specified in the [UBC exceed 15 ft. in length.
1.1 SCOPE Uniform Building Code Zone 2] [UBC B. Circuit breakers shall be shipped
A. This section defines low voltage Uniform Building Code Zone 4] [CBC inside their respective cells in which
metal-enclosed switchgear assemblies California Building Code Zone 4] [IBC they were factory acceptance tested.
with drawout circuit breaker elements International Building Code] [SBC C. Store and handle in strict compliance
for use in ac systems, rated 600 V Standard Building Code] [BOCA with manufacturer’s instructions
or less. Building Code] [IEEE 693]. Mounting and recommendations. Protect from
and anchorage requirements shall be potential damage from weather and
1.2 RELATED DOCUMENTS supplied by the switchgear manufacturer. construction operations. Store so
A. Drawings and general provisions of condensation will not form on or in
the Contract, including General and 1.4 QUALITY ASSURANCE switchgear and if necessary, apply
Supplementary Conditions and A. Manufacturer Qualifications: temporary heat where required to
Division 1 Specification Sections, Manufacturer of this equipment shall obtain suitable service conditions.
apply to this Section. have a minimum of 5 years experience
B. Related Sections (where applicable) producing similar electrical equipment. PART 2 - PRODUCTS
include the following: The manufacturer of the switchgear 2.1 MANUFACTURERS
1. Section 16345 - Medium Voltage assembly shall be the same A. The low voltage switchgear
Load Break Switches manufacturer as the breakers. The assembly shall be manufactured
2. Section 16470 - Dry Type manufacturer shall be ISO 9001 or by Siemens or approved equal.
Substation Transformers 9002 certified.
3. Section 16490 - Liquid Type B. Comply with requirements of latest 2.2 RATINGS
Substation Transformers revisions of applicable industry A. System Configuration: Switchgear
4. Section 16XXX - Power Monitoring, standards, specifically including the suitable for application in [one-phase]
Control and Communication following: [three-phase] [60 Hz] [50 Hz], [3 wire]
5. Section 16XXX - TVSS Devices 1. ANSI/IEEE C37.20.1 – Metal- [4 wire] [grounded-neutral] [3 wire
6. Section 16XXX – Coordination Enclosed Low Voltage Power Circuit ungrounded] [3 wire high-impedance
Study Breaker Switchgear grounded] system.
2. ANSI/IEEE C37.50 – Test Procedure B. Electrical Ratings:
1.3 SUBMITTALS for Low Voltage AC Power Circuit 1. Nominal System Voltage: [600 V]
A. Submit shop drawings and product Breakers Used in Enclosures [480 V] [240 V] [208 V] [OTHER].
data for approval and final 3. ANSI/IEEE C37.51 – Conformance 2. Maximum Design Voltage: [635
documentation in the quantities Testing of Metal-Enclosed Low volts with non-fused breakers]
listed according to the Conditions of Voltage AC Power Circuit Breaker [600 volts with fused breakers]
the Contract. Customer name, customer Switchgear Assemblies 3. Short-Circuit Current:
location, and customer order number 4. ANSI/IEEE C37.13 – Low Voltage [100kA] [150kA] [200kA]
shall identify all transmittals. AC Power Circuit Breakers Used in 4. Main-Bus Continuous Current:
B. Documents for Approval: General Enclosures [1600] [2000] [3200] [4000]
arrangement drawing showing 5. ANSI C37.16 – Preferred Ratings, [5000] [6000] A.
dimensioned elevation, floor plan, Related Requirements, and 5. [Neutral Bus Continuous Current:]
side view and foundation details, Application for Low Voltage Power [50] [100] percent of main
one-line diagram showing major Circuit Breakers and AC Power phase bus.
features, nameplate legends, schematic Circuit Protectors
diagrams and bill of material. 6. ANSI/IEEE C37.17 - Trip Devices for 2.3 SWITCHGEAR GENERAL
C. Final Documents: Record documentation AC and General Purpose DC Low CONSTRUCTION
to include those in 1.3.B and wiring Voltage Power Circuit Breakers A. The switchgear shall be factory
diagrams, list of recommended spare 7. UL 1558 – Metal-Enclosed Low assembled and tested, and comply
parts, instruction and installation Voltage Power Circuit Breaker with applicable industry standards. It
manuals [and certified test reports] Switchgear shall be a coordinated design so that
D. Product Data: Include features, 8. UL 1066 – Low Voltage AC and DC shipping groups are easily connected
characteristics, and ratings of individual Power Circuit Breakers Used together at the site into a continuous
circuit breakers and other components. in Enclosures line-up. Necessary connecting materials
Also, time-current characteristic curves 9. NEMA SG5 – Power Switchgear shall be furnished. All power circuit
for over current protective devices, Assemblies breakers and assemblies shall be
including circuit-breaker trip devices 10. NEMA SG3 – Low Voltage Power produced by a single manufacturer.
and fusible devices. Circuit Breakers
32
Type WL Low Voltage Metal-Enclosed Switchgear
Guide Form Specifications
B. The switchgear assembly shall consist 4. Secondary control and communication I. [Incoming line isolation barriers shall
of one or more metal-enclosed sections connections, when required, shall be be arranged to isolate the incoming
in an [indoor NEMA 1 enclosure] [out- located in a separately accessed area line connections from the main
door NEMA 3R non walk-in enclosure] that is accessible from the front of horizontal and vertical bus].
[outdoor NEMA 3R walk-in enclosure]. the switchgear without opening J. Main bus shall connect vertical
1. End sections shall include provisions breaker compartment door or the sections and shall be uniform capacity
for main bus extension and exposing any power cables or the entire length of assembly. Vertical
installation of future vertical sections. bussing. The secondary control and horizontal bus bar shall utilize a
2. The design shall incorporate contacts shall be of the sliding channel shape design to maximize
preformed steel channels, angles, contact design, silver plated and short circuit withstand capability and
and structural components bolted engage the drawout circuit breaker minimize heat rise. The main horizontal
together and reinforced to form a element in the “connected” and bus shall be run in a vertical, edge-to-
rigid, self-supporting assembly. “test” positions. edge arrangement for high short circuit
3. Fabricate enclosure with removable, F. All control wiring within the assembly strength. Access to the rear cable
[rear cover panels, secured by shall be continuous and shall terminate termination area shall be possible
captive screws], [hinged rear doors on each end at a suitable terminal without reaching over the main and
with captive screws] [hinged rear block. Control wiring shall be 14-gauge vertical bus.
doors with three-point latch and minimum, stranded type SIS, and 1. Bus shall be [98 % minimum
[pad-lockable] to allow access to shall be labeled at each end with conductivity copper silver-plated over
rear interior of switchgear. sleeve-type wire markers. entire length of the bus bar] [98%
C. Front breaker doors must be free of 1. Wire markers shall be machine conductivity copper tin-plated over
any ventilation openings. imprinted with the wire name as entire length of the bus bar].
D. Horizontal barriers are to be provided indicated on the wiring diagrams. 2. Feeder Circuit-Breaker Load
to form individual circuit breaker or 2. Terminals shall be insulated locking Terminals: Plated copper bus
metering compartments. Circuit fork or ring tongue type except extensions equipped with pressure
breaker compartments are to be where connecting to components connectors for outgoing circuit
barriered from the bus compartment that do not accept these conductors.
through a primary disconnect assembly. terminations. Control wiring for 3. Ground Bus shall be copper of
Each circuit breaker or metering external connections shall be 98% minimum conductivity,
compartment shall be provided with a terminated in a separate front minimum size 1/4 by 3 inches.
hinged front door secured with hand- accessible compartment for ease 4. Bus bracing shall be equal to the
operated [pad-lockable][key-lockable] of access. short circuit interrupting rating
rotary latches. G. Finish: Painted steel parts shall be of the lowest rated circuit breaker
E. Circuit breaker compartments shall prepared for painting by a five-stage applied in the assembly or 100kA
include stationary primary contact wash system consisting of an alkaline minimum.
disconnects that shall be silver-plated cleaner, fresh water rise, iron phosphate 5. Provide for future extensions from
copper at the connection points and treatment, fresh water rise and non- either end of main phase, neutral,
of one-piece construction. chromate sealer. After cleaning and and ground bus by means of pre-
1. The upper set of disconnects shall stabilization, the steel parts shall drilled bolt holes and connecting
bolt directly to the main bus and, be coated with a thermosetting links.
for feeder circuit breakers, the lower polyester powder applied with K. [Bus/Cable compartment barriers:
set shall extend to the rear cable electrostatic equipment at a nominal Barriers shall be supplied to isolate
area and shall be insulated where 2 mils dry film thickness and then the rear cable area from the main
they pass through the main cured properly. The paint finish shall bus area.]
bus compartment. have a salt spray rating as defined in L. [Insulated bus bar shall consist of
2. Primary disconnects shall be sized ASTM B-117. Paint color shall be bus bars enclosed in factory-applied,
for the maximum continuous ANSI 61 light gray. flame-retardant UL recognized
current for the frame size of the H. Bus isolation barriers shall be arranged insulation system. Bolted bus joints
circuit breaker which is located in to isolate the buses on either side of shall be insulated with secure joint
the compartment. each main and tie circuit breaker from covers that can easily be removed and
3. Interlocks shall be provided to each other. reinstalled.]
prevent a circuit breaker element
of the incorrect frame size or
interrupting rating from being
inserted into the compartment.
33
Type WL Low Voltage Metal-Enclosed Switchgear
Guide Form Specifications
M.[Low Voltage High-Resistance O. [Outdoor NEMA 3R Walk-In enclosure Units shall be mounted in the
Grounding System] [Installed in the shall consist of indoor switchgear instrument compartment door
switchgear assembly] [Contained in assemblies in weather-resistant steel and as follows:
separate NEMA 1 enclosure] for use housing having an operating aisle 1. Incoming monitoring or main
on [480 V] [600 V] [wye] [delta] source, space of approximately 42 inches. breakers: Included in the circuit
including the following components: Enclosure shall be painted steel, integral breaker trip unit device or
1. Meter relay (MR) structural-steel base frame with Siemens Model [PAC 3200] [9200]
2. 3 Indicating lights: white for factory-applied asphalt undercoating. [9300][9330][9340][9350][9360]
“Normal,” red for “Ground Fault” Each section shall be equipped with [9510][9610]digital meters.
green for “Pulsing” the following features:] 2. Feeder breakers: Included in the
3. “Reset” push button 1. Structural design and anchorage circuit breaker trip device or
4. “Test” push button adequate to resist loads imposed Siemens Model [PAC 3200][9200]
5. On - Off switches for system by 125-mph wind. [9300][9330]digital meters.
and pulse 2. Space heater operating at [full] C. Provision for Future Devices: Equip
6. Repeat cycle timer, set to produce [one-half of] rated voltage, sized future circuit breaker compartments
approx. 30 current pulses per minute to prevent condensation. with rails, mounting brackets, supports,
7. Neutral grounding resistor assembly 3. Louvers equipped with insect/rodent necessary appurtenances, and
8. Pulse resistor assembly screen and filter and arranged to bus connections.
9. Test resistor assembly permit air circulation while excluding D. Control Power Supply: Control power
10. Relay for repeat cycle timer exterior dust and rodents. transformer supplying 120-V control
11. Alarm relay, with extra interlocks 4. Internal aisle of sufficient width to circuits through secondary disconnect
for remote alarm (59X) permit protective-device withdrawal, devices are to be dry-type transformers
12. Control power transformer disassembly, and servicing in aisle. with primary and secondary fuses.
13. Neutral ammeter and current 5. Aisle access doors with outside 1. Transformers shall be mounted in
transformer pad-locking provisions and interior auxiliary compartments.
14. Optional Portable clamp on ammeter panic latches. 2. [Multiple source with control
15. [3 Grounding transformers for 6. Adequate incandescent lighting power transfer.] Two control power
generating a neutral CPT] (For Delta receptacles with three-way switch transformers located in separate
System without a system neutral) at each access door. compartments with necessary
N. [Outdoor NEMA 3R Non Walk-In 7. A duplex receptacle with ground interlocking relays shall be provided.
enclosure shall consist of indoor fault protection, at aisle access door. a.Each transformer shall be
switchgear assemblies in weather- 8. A load center shall be supplied for connected to line side of
resistant steel housing. Enclosure shall distribution of power to lights, associated main circuit breaker.
be painted steel, integral structural-steel receptacles and heaters. b.[Secondary windings connected
base frame with factory-applied asphalt 9. [Aisle ventilation louvers equipped through a relay or relays to
undercoating. Each section shall be with insect/rodent screen and control bus to effect an automatic
equipped with the following features:] filter and arranged to permit air control power transfer scheme.]
1. Structural design and anchorage circulation while excluding exterior 3. [(24) (48) (125) volt DC battery
adequate to resist loads imposed dust and rodents. system]
by 125-mph wind. E. [Mimic Bus]: Continuous mimic
2. Space heater operating at [full] 2.4 COMPONENTS bus applied to front of switchgear,
[one-half of] rated voltage, sized A. Instrument Transformers: Comply with arranged in single-line diagram format,
to prevent condensation. IEEE C57.13. shall indicate the arrangement of the
3. Louvers equipped with insect/rodent 1. Potential Transformers: Secondary- circuit breakers in the power circuit.
screen and filter and arranged voltage rating of 120 V and NEMA
to permit air circulation while accuracy class of 0.6 with burdens 2.5 CIRCUIT BREAKERS
excluding exterior dust and rodents. of W, X, and Y. A. Circuit breakers shall comply with
4. Internal aisle of sufficient width to 2. Current Transformers: Ratios as the requirements of IEEE/ANSI
permit protective-device withdrawal. indicated; burden and accuracy C37.13/16/17/50,UL1066, NEMA SG3.
5. [Load center for distribution of class suitable for connected relays, All breakers shall be three-pole,
power to lights, receptacles and meters, and instruments. 100% rated type WL low voltage
heaters.] B. Multifunction Digital-Metering Monitors power breaker manufactured by
6. [Incandescent lighting receptacles shall be UL-listed or recognized, Siemens Energy & Automation, or
with three-way switch.] microprocessor-based unit suitable approved equal.
7. [Duplex receptacle with ground for three or four wire systems.
fault protection.]
34
Type WL Low Voltage Metal-Enclosed Switchgear
Guide Form Specifications
35
Type WL Low Voltage Metal-Enclosed Switchgear
Guide Form Specifications
PART 3 - EXECUTION
3.1 EXAMINATION AND INSTALLATION
A. Examine elements and surfaces to
receive switchgear for compliance
with installation tolerances and other
conditions affecting performance.
Proceed with installation only after
unsatisfactory conditions have
been corrected.
B. Install and anchor switchgear in
accordance with manufacturer’s
instructions.
3.2 CONNECTIONS
A. Tighten bus joints, electrical
connectors, and terminals according
to manufacturer's published
torque-tightening values. Install
equipment-grounding conductors
for switchgear with ground continuity
to main electrical ground bus.
36
Note: This guide does not purport to cover all details in equipment, or to provide for every possible contingency. Should further
information be desired or should particular problems arise, which are not covered sufficiently for the purchaser’s purposes, the matter
should be referred to the local Siemens sales office. The contents of this guide shall not become part of or modify any prior or existing
agreement, commitment or relationship.
Siemens Industry, Inc. © 2008 Siemens Industry, Inc. All rights reserved.
Building Technologies Division Order No.: LVSA-00100-0808 Siemens is a registered trademark
3333 Old Milton Parkway Printed in USA of Siemens AG. Product names mentioned may be
Alpharetta, GA 30005 trademarks or registered trademarks of their
respective companies. Specifications are subject
1-800-964-4114 to change without notice.
info.us@siemens.com
www.usa.siemens.com/switchgear