Wiring 6642VBT

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

NOTE: TERMINAL L1 MUST 120V. 50/60HZ.

BE POWERED BEFORE FUSED POWER SUPPLY.


L1 L2
TERMINAL 12
UV
FORM 6642 VBT GROUP M3101 SEE X X
E FLAME RELAY (F)
INTERCONNECTION FLAME-PAK
PROTECTOFIER ELECT.
COIL IS ENERGIZED
DIAGRAM BELOW. WHEN FLAME IS
SINGLE BURNER, AUTOMATIC G NETWORK
OPERATION,INCLUDES TIMER ESTABLISHED AND
ACF
DETECTED.
FOR PURGE AND IGNITION F
TRIAL. 13 12
D.C.ua TEST JACK
SS100A FLAME PAK LS 12 F X X
CTP1 8 1 (CHECK) ACF
C-CHECK RELAY C
ACF 3 1 4 3 4 13 12
F-FLAME RELAY C
* 9 CTP2 LOCKOUT
SWITCH
CTP-U300A AUTOMATIC TIMOFIER N.O. 2
C 8 10 4 ALARM HORN
HELD 10 AH
3 4 7 9 13 CLOSED
2 5 TIMER
MOTOR
CTP
NO CONNECTIONS 7 1

NOTE: TIMER CAMS (CTP) SHOWN C F C 11 TIMER


IN ZERO TIME POSITION.
CTP2 AND CTP3 CLOSE AT 1 7 2 5 3 9
END OF PURGE FOR IGNITION. 5 IGN.TRANS.
CTP3 IT

* - SAFETY INTLK.SERIES CIRCUIT.


FUEL AND AIR PRESS.SWS.,
VENT.FANS,ETC.AS REQ'D.
6

F
11

6
F

3
SPARK IGNITOR

6 PILOT VALVE(S) PV
INTERNAL WIRING 9 3 N.C.
EXTERNAL WIRING F 8
MAIN VALVE(S) MV
2 N.C.
WIRING DIAGRAM 8
FLAME ON

(NEON LIGHT)

NOTE: TERMINAL L1 MUST LOCKOUT


BE POWERED BEFORE
120V. SWITCH D.C.TEST ua
50/60HZ. L1 JACK
TERMINAL 12 L1
FUSED L2 FLAME
L2
SINGLE BURNER PROTECTOFIER POWER 3 U300A PAK

SUPLY AUTOMATIC
4
(FORM 6642 VBT GROUP M3101) TIMOFIER
5
LS G
NOTES:
FLAME WIRE TO BE NO. 14 TYPE TW. 600V.
* 6
7
8
TRANS.

INSULATED WIRE OR EQUAL. FLAME WIRE MUST


NOT BE IN SAME CONDUITS WITH POWER WIRING. 9 UV
10
IGNITION CABLE MUST BE RUN IN SEPARATE
CONDUIT TO SPARK ELECTRODE. 11 ACF ACF
E
(DO NOT MIX WITH 115V.WIRING.) 12
13 (CHECK) (FLAME)
ALL WIRING AND EQUIPMENT EXTERNAL TO
PROTECTOFIER TO BE FURNISHED BY
OTHERS UNLESS OTHERWISE SPECIFIED. FLAME ELECTRODE
ASSY. (IF USED) FLAME OPERATING
INSTALLATION, OPERATION AND MAINTENANCE SHALL WIRE SIGNAL
CONFORM WITH NATIONAL FIRE PROTECTION ASSOCIATION BURNER E FROM
STANDARDS, NATIONAL AND LOCAL CODES AND AUTHORITIES P-C II OR
HAVING JURISDICTION. ANY MODIFICATION VOIDS APPROVAL. PURPLE UV FLAME
ROD
GAS YELLOW
PILOT
P-C II ULTRA- G
VIOLET SCANNER
(IF USED) TIMER

U300A AUTOMATIC TIMOFIER TIMING ALARM HORN AH


RANGE PURGE(MIN.) IGN.(SEC.) IGN.TRANS. IT
A MIN. SEC. SPARK IGNITOR
IGN.CABLE
PROTECTION CONTROLS, INC. MV
SKOKIE, ILLINOIS MAIN VALVE(S) N.C.

WIRING DIAGRAM FOR: PILOT VALVE(S) PV


PROTECTOFIER FORM 6642VBT GROUP M3101 N.C.

JOB NO. REVISED DRAWING NO.


INTERCONNECTION DIAGRAM
10-03
X-244