NOTES:-

IRCON INTERNATIONAL LIMITED SECTION: FL - RKB


1. ALL DIMENSIONS ARE IN MM,UNLESS OTHERWISE MENTIONED. (A Govt. of India Undertaking) WIND PRESSURE 155 Kgf/m²
2. THE LAYOUT IS TENTATIVE ACTUAL WORK SHALL BE DONE AS PER SITE CONDITIONS. C-4, DISTRICT CENTRE, SAKET, DATE- 12.06.2024
3. CABLE LAYING SHALL BE DONE AS PER IS 1255, 1983. NEW DELHI-110017 DRAWING NO.- IRCON/5032/NAW/TSS/OI
4. LT WIRING AND CABLING SHALL BE DONE AS PER IS-732-1989, NBC. SHEET NO.-1 OF 4
5. ALL LIGHT FIXTURE SHALL BE LED TYPE OUTDOOR LUMINARIES SHALL BE IP-65 TYPE.
6. AREA LIGHTING ALONG FENCING IS DIVIDED INTO TWO CIRCUIT WITH ALTERNATE LIGHTS CONNECTED ON TO SAME
CIRCUIT.
7. FLOOD LIGHTS WILL HAVE INDIVIDUAL CONTROL SWITCHES LOCATED IN THE SWITCH BOX AT THE BASE OF THE L.T. LEGEND
MAST. REF
DESCRIPTION QTY. SYMBOL
8. APPROVED VENDOR LIGHT IS INSTALLED. NO.
9. CABLE LAYING AND DETAILS OF CLEATING THE CABLE ON THE MAST ETC. MAY BE DECIDED AS PER SITE CONDITIONS.
10. THE ANGLE OF MOUNTING OF THE FLOOD LIGHT FITTINGS FOR LIGHT PROJECTION SHOWN IN THE DRAWING IS FOR 1. FOR AREA LED LIGHT(60 watt) 13
GUIDANCE AND MAY BE CHANGED REQUIREMENT AT SITE.
11. FIXTURES FOR FLOOD LIGHTING AND AREA LIGHTING ON CONTROL ROOM BUILDING WILL BE SIMILAR TO THOSE 2. FOR FLOOD LED LIGHTING (200 Watt) 04
SHOWN FOR POSTS, BUT WILL BE FIXED BY CLAMPS GROUTED IN THE PARAPET WALL ON THE ROOF OF THE
CONTROL ROOM BUILDING.
3. 2C X 16 Sqmm. ALUMINIUM ARMOURD CABLE WIRE 450 Mtr( approx )
12. FOUNDATION OF LIGHT MAST SHALL BE AS PER MANUFACTURER.
13. FROM JB TERMINAL TO LIGHT FIXTURE Cu FRLS WIRE OF 3RX1CX1.5 SQMM SHALL BE USED.
14. LIGHT POLE SHALL CONFIRM TO IS-2713-1980. ERECTION OF POLE SHALL BE AS PER VENDOR RECOMMENDATION 4. GI SWG CONDUCTOR 52 Mtr( approx )
SUITABLE FOR APPLICABLE ENVIRONMENT CONDITION.
15. GI SWG CONDUCTOR USED FOR EARTHING OF POLE TO COMMON EARTH GRID AT TSS.
16. LOCATION OF LDB-2 AS SHOWN IN THIS DRAWING IS INDICATIVE ACTUAL LOCATION SHALL BE FINALIZED AS PER
CONTROL ROOM INTERNAL EQUIPMENT LAYOUT DRAWING.
17. LIGHT POST AT FENCING AREA HAS BEEN PLACED IN LINE WITH RDSO DRAWING AND RATING OF LED LIGHTING
FIXTURE IS SELECTED BASED ON THE EQUIVALENT LUMEN OUTPUT OF HALOGEN FIXTURE USED IN RDSO DRAWING.
YARD AREA LIGHTING IS ALSO PROVIDED IN LINE WITH THE RDSO DRAWING. YARD AREA LIGHTING IS TRANSFORMER
AREA WITH THE LAMP WATTAGE EQUIVALENT TO THE LUMEN OUTPUT OF CORRESPONDING HALOGEN FIXTURE GIVEN
IN RDSO REFERENCE DRAWING.
18. ELECTRICAL FIXTURE & MATERIAL SHALL BE OF APPROVED MANUFACTURER.

NAWA T.S.S. (O.I.)


ABBREVIATION :-
1. X-LEDYY X Y - YY
DESIGNATION DATE SIGNATURE

GM/E/PH/IRCON
OUTDOOR
ILLUMINATION OF PROOF CHECKER/IRCON

NAWA TSS
132/ 27 KV JGM/E/IRCON

AM/E/IRCON
2. DP - Double Pole
3. Sp - Single Pole
4. SPN - Single Pole Phase Neutral
5. LDB - Light Distribution Board
6. MCB - Miniature circuit Breaker
PROOF CONSULTANT/TPL
7. ELCB - Earth Leakage circuit Breaker (A.K SAMANTA)
8. PH - Phase
9. N - Neutral CLIENT: IRCON INTERNATIONAL LTD.
10. Mtrs - Meter REF DRG.- ETI/PSI/0216
11.
12.
MM - Millimeter
SWG - Standard Wire
NORTH WESTERN RAILWAY
13. GI - Galvanized Iron NATURE OF MOD CONTRACTOR:
MOD DATE NAME SIG
14. JB - Junction Box TΛTΛ PROJECTS LIMITED
1st Floor, Tower-1,
15. Cu - Copper Scrutiny HK
Okaya Center, B-5, Sector-62
16. AL - Aluminium Noida-201301
TATA
PROJECTS Checked HSR
SCALE : 1.50

Draftsman SG SUB SCALE: 1.20 IR