Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

design the system with razor-thin margins to reduce steam

1st stage ejector Cooling water and CW consumption. They do this in part because selec-
vapour inlet outlet (typically
10˚F higher than inlet) tion criteria will often include utility consumption compari-
Tube bundles
sons. In many cases, the MDP is so low that even small
changes in design conditions or underperformance of the
first-stage inter-condenser will lead to performance break.
Even worse, when the first-stage inter-condenser fails to
sub-cool there is a guarantee that the system will experi-
‘Long air
Vapour ence performance break.
baffle’ Tube support outlet
Condensate Cooling water
outlet inlet (coldest) First-stage inter-condenser design evolution
Modern large first-stage inter-condensers are supplied as
Figure 3 X-shell long air baffle X-type shells that include a sub-cooling zone. This design
is an evolution from older and smaller designs that used
vacuum system design focuses on first-stage design con- E-shells. The advantage of the X-shell is that it decreases
ditions because the first stage costs more and consumes pressure drop compared to E-shell, lowering steam con-
more steam and CW than the rest of the system. For that sumption. The X-type first-stage inter-condenser is
reason, they represent the biggest opportunity for optimi- designed to sub-cool the outlet vapour below the bulk out-
sation and savings. let condensate (see Figure 3).1 This is accomplished with
An ejector uses motive steam at a much higher pressure the ‘long air baffle’. The long air baffle’s function is to force
than the suction pressure to entrain the process stream into the outlet vapour across exchanger tubes with the coldest
the steam chest (see Figure 2), where it is boosted from suc- CW, thereby sub-cooling the gas below its condensate.
tion pressure Ps to discharge Pd at the ejector outlet. Ejector Roughly 20-25% of the exchanger tubes are located under
operating discharge pressure Pd is set by the downstream the long air baffle and are dedicated to sub-cooling.
ejector process load and system pressure drop. An ejec- The sub-cooling zone is critical. When working as
tor’s design and performance can be related by a set of key intended, the sub-cooled zone minimises second-stage
parameter ratios, compression, entrainment, and expan- ejector gas load. The selection of the ejector MDP is based
sion, as defined in Figure 2. These ratios are used to specify on the load to the second-stage ejector commensurate
the required size, shape, and motive steam requirement. with the sub-cooled zone working as intended. In practice,
For a given suction load and pressure, two parameters when the first-stage inter-condenser does not sub-cool
that impact first-stage ejector sizing are motive steam pres- the outlet vapour, the outlet vapour to the second-stage
sure and MDP. Higher pressure motive steam will generally ejector increases above its design point. The higher load
require less steam than lower pressure steam. However, in increases the suction pressure of the second-stage ejec-
most refineries, steam header pressure levels are set, and tor, which ultimately leads to higher first-stage ejector
the ability to optimise is limited. In rare cases, the selection discharge pressure. When the first-stage ejector discharge
of steam conditions can be used to optimise ejector design. pressure exceeds its MDP, performance break will occur.
Once the motive steam pressure is set, the first-stage Mechanical design flaws that fail to seal the long air baffle
ejector discharge pressure is optimised to minimise the or damage, corrosion, or improper installation of the seal
size of the ejector and the amount of motive steam it will strips are the root cause of the inter-condenser’s inability
use. This relationship is reflected in the compression ratio to sub-cool outlet vapour and overload the second-stage
Pd/Ps, where Pd is MDP and Ps is the suction pressure. As the ejector. A performance break is guaranteed if the ejector
compression ratio increases, so does the required motive system was designed with minimal or inadequate pressure
steam. Designing for higher MDP increases motive steam drop margin. Therefore, the first-stage inter-condenser
consumption. With end users not providing adequate or must perform as intended and sub-cool outlet vapour to
any design margin guidance, vacuum system suppliers avoid performance break.

1st stage ejector


Easy to diagnose, hard to troubleshoot
106
outlet vapour Long air baffle bypass is easy to diagnose because the
105
vapour leaving the first-stage inter-condenser should be
78
CW outlet colder than the condensate draining from the bottom of
87 the shell. When the temperatures are inverted, that is an
87 Gas outlet indication of a bypass around the sub-cooling zone (see
109
72 Figure 4). Troubleshooting vacuum systems is inherently
113
CW intlet
101 difficult because much of the information required is not
94
104 readily available. It is more the norm than the exception for
Temperature, ˚F 78 vacuum systems to be poorly instrumented. Flow meters
Condensate to hotwell for key streams are often missing. Conclusions made with
incomplete data or data based on design first-stage gas
Figure 4 Long air baffle bypass loads or using original vacuum system design information

30 PTQ Q1 2023 www.digitalrefining.com

Q1 PCS.indd 30 13/12/2022 11:37:33

You might also like