Protective Device Settings Report

Project: Replacement of Backup Electrical Supply Source for King Khalid Hospital Date: 5/19/2024

Location: KSA-Hail Revision: 2

Contract: 120230000001315 Contractor: Nour Energy

Engineer MOH

Filename: King Khalid Hospital-HAIL

Page 1 of 8
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance

Breaker Pickup Pickup Pickup


Manufacturer
Trip Device Sensor/ Rating Trip Trip Trip
Designation LVCB ID & Function Setting Band Setting Band Ixt Setting
Model Frame Plug (Amps) (Amps) (Amps)
Model
Siemens
MDB 4 ACB 4 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 4 ACB 4 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

Siemens
MDB 12 ACB 12 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 12 ACB 12 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

Siemens
MDB 13 ACB 13 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 13 ACB 13 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

Siemens
MDB 11 ACB 11 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 11 ACB 11 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

Siemens
MDB 10 ACB 10 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 10 ACB 10 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

Siemens
MDB 8 ACB 8 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 8 ACB 8 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

Siemens
MDB 3 ACB 3 ETU600 2500 2500 Phase 0.4 1000 1 3.05 7625 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 3 ACB 3 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

Siemens
MDB 1 ACB 1 ETU600 4000 4000 Phase 0.4 1600 1 3 12000 0.1 OUT 5 20000
3WA13 40

Siemens
MDB 1 ACB 1 ETU600 4000 4000 Ground 0.1 400 0.1 OUT
3WA13 40

Page 2 of 8
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance

Breaker Pickup Pickup Pickup


Manufacturer
Trip Device Sensor/ Rating Trip Trip Trip
Designation LVCB ID & Function Setting Band Setting Band Ixt Setting
Model Frame Plug (Amps) (Amps) (Amps)
Model

Siemens
MDB 2 ACB 2 ETU600 4000 4000 Phase 0.4 1600 2 3 12000 0.1 OUT 5 20000
3WA13 40

Siemens
MDB 2 ACB 2 ETU600 4000 4000 Ground 0.1 400 0.1 OUT
3WA13 40

Siemens
MDB 9 ACB 9 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25

Siemens
MDB 9 ACB 9 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25

5/14/2024

Page 3 of 8
Protective Device Settings - Relay

OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)

Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model

CB supplying
RMU3 TR 3 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 3

CB supplying
RMU3 TR 3 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 3

CB supplying
RMU1 TR 1 FANOX /SIA-B 250:1 Overcurrent Phase OC1 Inverse 0.557 139.250 0.050 4.000 1000.00 0.01 s
transformer 1

CB supplying
RMU1 TR 1 FANOX /SIA-B 250:1 Overcurrent Ground OC1 Inverse 0.060 15.000 0.100 0.200 50.00 0.01 s
transformer 1

CB supplying
RMU2 TR 2 FANOX /SIA-B 250:1 Overcurrent Phase OC1 Inverse 0.557 139.250 0.050 4.000 1000.00 0.01 s
transformer 2

CB supplying
RMU2 TR 2 FANOX /SIA-B 250:1 Overcurrent Ground OC1 Inverse 0.060 15.000 0.100 0.200 50.00 0.01 s
transformer 2

CB supplying
RMU4 TR 4 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01
transformer 4

CB supplying
RMU4 TR 4 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 4

CB supplying
RMU9 TR 9 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 9

CB supplying
RMU9 TR 9 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 9

CB supplying
RMU8 TR 8 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 8

Page 4 of 8
Protective Device Settings - Relay

OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)

Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model

CB supplying
RMU8 TR 8 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 8

CB supplying
RMU12 TR 12 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 12

CB supplying
RMU12 TR 12 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 12

CB supplying
RMU13 TR 13 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 13

CB supplying
RMU13 TR 13 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 13

CB supplying
RMU11 TR 11 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 11

CB supplying
RMU11 TR 11 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 11

CB supplying
RMU10 TR 10 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 10

CB supplying
RMU10 TR 10 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 10

PRIMARY SW OUT GOING FROM ZIV


Relay15 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.100 1.280 1600.00 0.03 s
GEAR BUS1 PRIMARY SW GEAR IRFA

PRIMARY SW OUT GOING FROM ZIV


Relay15 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.100 0.200 250.00 0.01 s
GEAR BUS1 PRIMARY SW GEAR IRFA

PRIMARY SW OUT GOING FROM ZIV


Relay16 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.100 1.280 1600.00 0.03 s
GEAR BUS2 PRIMARY SW GEAR IRFA

PRIMARY SW OUT GOING FROM ZIV


Relay16 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS2 PRIMARY SW GEAR IRFA

Page 5 of 8
Protective Device Settings - Relay

OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)

Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model

INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay17 1250:1 Overcurrent Phase OC1 Inverse 0.28 350.000 0.08 1.28 1600 0.02 s
GEAR BUS1 SECONDARY SW IRFA
GEAR
INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay17 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS1 SECONDARY SW IRFA
GEAR
INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay18 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.080 1.280 1600.00 0.02 s
GEAR BUS2 SECONDARY SW IRFA
GEAR
INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay18 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS2 SECONDARY SW IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay19 800:1 Overcurrent Phase OC1 Inverse 0.320 256.000 0.070 1.500 1200.00 0.01 s
GEAR BUS1 IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay19 800:1 Overcurrent Ground OC1 Inverse 0.050 40.000 0.100 0.200 160.00 0.01 s
GEAR BUS1 IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay20 800:1 Overcurrent Phase OC1 Inverse 0.287 229.600 0.050 1.500 1200.00 0.01 s
GEAR BUS1 IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay20 800:1 Overcurrent Ground OC1 Inverse 0.050 40.000 0.050 0.200 160.00 0.01 s
GEAR BUS1 IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay21 800:1 Overcurrent Phase OC1 Inverse 0.287 229.600 0.070 1.500 1200.00 0.01 s
GEAR BUS2 IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay21 800:1 Overcurrent Ground OC1 Inverse 0.050 40.000 0.050 0.200 160.00 0.01 s
GEAR BUS2 IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay22 800:1 Overcurrent Phase OC1 Inverse 0.320 256.000 0.050 1.500 1200.00 0.01 s
GEAR BUS2 IRFA
GEAR

OUT GOING FROM


SECONDARY SW ZIV
SECONDARY SW Relay22 800:1 Overcurrent Ground OC1 Inverse 0.050 40.000 0.100 0.200 160.00 0.01 s
GEAR BUS2 IRFA
GEAR

Page 6 of 8
Protective Device Settings - Relay

OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)

Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model

PRIMARY SW PRIMARY SW GEAR ZIV


Relay23 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.120 1.280 1600.00 0.05 s
GEAR BUS2 BUS TIE BREAKER IRFA

PRIMARY SW PRIMARY SW GEAR ZIV


Relay23 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.120 0.200 250.00 0.01 s
GEAR BUS2 BUS TIE BREAKER IRFA

SECONDARY SW
SECONDARY SW ZIV
GEAR BUS TIE Relay25 1250:1 Overcurrent Phase OC1 Inverse 0.200 250.000 0.080 1.280 1600.00 0.011 s
GEAR BUS2 IRFA
BREAKER

SECONDARY SW
SECONDARY SW ZIV
GEAR BUS TIE Relay25 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS2 IRFA
BREAKER

MAIN INCOMING
PRIMARY SW ZIV
BREAKER FROM Relay26 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.120 1.280 1600.00 0.05 s
GEAR BUS1 IRFA
NATIONAL GRID

MAIN INCOMING
PRIMARY SW ZIV
BREAKER FROM Relay26 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.120 0.200 250.00 0.01 s
GEAR BUS1 IRFA
NATIONAL GRID

OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay27 1200:5 Overcurrent Phase OC1 IEC Inverse 0.292 350.400 0.075 1.500 1800.00 0.03 s
REF 615
GEN SYNCH BUS

OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay27 1200:5 Overcurrent Ground OC1 IEC Inverse 0.050 60.000 0.100 0.250 300.00 0.02 s
REF 615
GEN SYNCH BUS

OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay28 1200:5 Overcurrent Phase OC1 IEC Inverse 0.292 350.400 0.075 1.500 1800.00 0.03 s
REF 615
GEN SYNCH BUS

OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay28 1200:5 Overcurrent Ground OC1 IEC Inverse 0.050 60.000 0.100 0.250 300.00 0.02 s
REF 615
GEN SYNCH BUS

INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay29 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.075 1.400 1750.00 0.01 s
GEAR BUS1 IRFA
SECONDARY SW
GEAR
INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay29 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS1 IRFA
SECONDARY SW
GEAR

Page 7 of 8
Protective Device Settings - Relay

OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)

Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model

INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay30 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.075 1.400 1750.00 0.02 s
GEAR BUS2 IRFA
SECONDARY SW
GEAR
INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay30 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS2 IRFA
SECONDARY SW
GEAR

GEN 1 SYNCH ABB


GEN SET PANEL Relay31 1200:5 Overcurrent Phase OC1 IEC Inverse 0.085 102.000 0.082 0.300 360.00 3.00 s
BREAKER REG 630

GEN 1 SYNCH ABB


GEN SET PANEL Relay31 1200:5 Overcurrent Ground OC1 IEC Inverse 0.010 12.000 0.080 0.100 120.00 0.02 s
BREAKER REG 630

GEN 1 SYNCH ABB


GEN SET PANEL Relay31 1200:5 Overload Phase OL T2PTTR (p=0) 0.100 120.000 60.000
BREAKER REG 630

GEN2 SYNCH ABB


GEN SET PANEL Relay32 1200:5 Overcurrent Phase OC1 IEC Inverse 0.085 102.000 0.082 0.300 360.00 3.00 s
BREAKER REG 630

GEN 2 SYNCH ABB


GEN SET PANEL Relay32 1200:5 Overcurrent Ground OC1 IEC Inverse 0.010 12.000 0.080 0.100 120.00 0.02 s
BREAKER REG 630

GEN 2 SYNCH ABB


GEN SET PANEL Relay32 1200:5 Overload Phase OL T2PTTR (p=0) 0.100 120.000 60.000
BREAKER REG 630

GEN 3 SYNCH ABB


GEN SET PANEL Relay33 1200:5 Overcurrent Phase OC1 IEC Inverse 0.085 102.000 0.082 0.300 360.00 3.00 s
BREAKER REG 630

GEN 3 SYNCH ABB


GEN SET PANEL Relay33 1200:5 Overcurrent Ground OC1 IEC Inverse 0.010 12.000 0.080 0.100 120.00 0.02 s
BREAKER REG 630

GEN 3 SYNCH ABB


GEN SET PANEL Relay33 1200:5 Overload Phase OL T2PTTR (p=0) 0.100 120.000 60.000
BREAKER REG 630

Page 8 of 8