Protective Device Setting Rev2
Protective Device Setting Rev2
Protective Device Setting Rev2
Project: Replacement of Backup Electrical Supply Source for King Khalid Hospital Date: 5/19/2024
Engineer MOH
Page 1 of 8
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance
Siemens
MDB 4 ACB 4 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
Siemens
MDB 12 ACB 12 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25
Siemens
MDB 12 ACB 12 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
Siemens
MDB 13 ACB 13 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25
Siemens
MDB 13 ACB 13 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
Siemens
MDB 11 ACB 11 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25
Siemens
MDB 11 ACB 11 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
Siemens
MDB 10 ACB 10 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25
Siemens
MDB 10 ACB 10 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
Siemens
MDB 8 ACB 8 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25
Siemens
MDB 8 ACB 8 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
Siemens
MDB 3 ACB 3 ETU600 2500 2500 Phase 0.4 1000 1 3.05 7625 0.1 OUT 5 12500
3WA12 25
Siemens
MDB 3 ACB 3 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
Siemens
MDB 1 ACB 1 ETU600 4000 4000 Phase 0.4 1600 1 3 12000 0.1 OUT 5 20000
3WA13 40
Siemens
MDB 1 ACB 1 ETU600 4000 4000 Ground 0.1 400 0.1 OUT
3WA13 40
Page 2 of 8
Protective Device Settings - Low Voltage Circuit Breaker with Solid State / Microprocessor Trip Device
Long Time Short-Time / Ground Inst. / Maintenance
Siemens
MDB 2 ACB 2 ETU600 4000 4000 Phase 0.4 1600 2 3 12000 0.1 OUT 5 20000
3WA13 40
Siemens
MDB 2 ACB 2 ETU600 4000 4000 Ground 0.1 400 0.1 OUT
3WA13 40
Siemens
MDB 9 ACB 9 ETU600 2500 2500 Phase 0.4 1000 1 3 7500 0.1 OUT 5 12500
3WA12 25
Siemens
MDB 9 ACB 9 ETU600 2500 2500 Ground 0.1 250 0.1 OUT
3WA12 25
5/14/2024
Page 3 of 8
Protective Device Settings - Relay
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)
Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model
CB supplying
RMU3 TR 3 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 3
CB supplying
RMU3 TR 3 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 3
CB supplying
RMU1 TR 1 FANOX /SIA-B 250:1 Overcurrent Phase OC1 Inverse 0.557 139.250 0.050 4.000 1000.00 0.01 s
transformer 1
CB supplying
RMU1 TR 1 FANOX /SIA-B 250:1 Overcurrent Ground OC1 Inverse 0.060 15.000 0.100 0.200 50.00 0.01 s
transformer 1
CB supplying
RMU2 TR 2 FANOX /SIA-B 250:1 Overcurrent Phase OC1 Inverse 0.557 139.250 0.050 4.000 1000.00 0.01 s
transformer 2
CB supplying
RMU2 TR 2 FANOX /SIA-B 250:1 Overcurrent Ground OC1 Inverse 0.060 15.000 0.100 0.200 50.00 0.01 s
transformer 2
CB supplying
RMU4 TR 4 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01
transformer 4
CB supplying
RMU4 TR 4 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 4
CB supplying
RMU9 TR 9 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 9
CB supplying
RMU9 TR 9 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 9
CB supplying
RMU8 TR 8 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 8
Page 4 of 8
Protective Device Settings - Relay
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)
Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model
CB supplying
RMU8 TR 8 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 8
CB supplying
RMU12 TR 12 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 12
CB supplying
RMU12 TR 12 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 12
CB supplying
RMU13 TR 13 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 13
CB supplying
RMU13 TR 13 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 13
CB supplying
RMU11 TR 11 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 11
CB supplying
RMU11 TR 11 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 11
CB supplying
RMU10 TR 10 FANOX /SIA-B 75:1 Overcurrent Phase OC1 Inverse 0.700 52.500 0.050 8.000 600.00 0.01 s
transformer 10
CB supplying
RMU10 TR 10 FANOX /SIA-B 75:1 Overcurrent Ground OC1 Inverse 0.070 5.250 0.100 0.400 30.00 0.01 s
transformer 10
Page 5 of 8
Protective Device Settings - Relay
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)
Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model
INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay17 1250:1 Overcurrent Phase OC1 Inverse 0.28 350.000 0.08 1.28 1600 0.02 s
GEAR BUS1 SECONDARY SW IRFA
GEAR
INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay17 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS1 SECONDARY SW IRFA
GEAR
INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay18 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.080 1.280 1600.00 0.02 s
GEAR BUS2 SECONDARY SW IRFA
GEAR
INCOMER FROM
SECONDARY SW NATIONAL GRID TO ZIV
Relay18 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS2 SECONDARY SW IRFA
GEAR
Page 6 of 8
Protective Device Settings - Relay
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)
Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model
SECONDARY SW
SECONDARY SW ZIV
GEAR BUS TIE Relay25 1250:1 Overcurrent Phase OC1 Inverse 0.200 250.000 0.080 1.280 1600.00 0.011 s
GEAR BUS2 IRFA
BREAKER
SECONDARY SW
SECONDARY SW ZIV
GEAR BUS TIE Relay25 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS2 IRFA
BREAKER
MAIN INCOMING
PRIMARY SW ZIV
BREAKER FROM Relay26 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.120 1.280 1600.00 0.05 s
GEAR BUS1 IRFA
NATIONAL GRID
MAIN INCOMING
PRIMARY SW ZIV
BREAKER FROM Relay26 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.120 0.200 250.00 0.01 s
GEAR BUS1 IRFA
NATIONAL GRID
OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay27 1200:5 Overcurrent Phase OC1 IEC Inverse 0.292 350.400 0.075 1.500 1800.00 0.03 s
REF 615
GEN SYNCH BUS
OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay27 1200:5 Overcurrent Ground OC1 IEC Inverse 0.050 60.000 0.100 0.250 300.00 0.02 s
REF 615
GEN SYNCH BUS
OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay28 1200:5 Overcurrent Phase OC1 IEC Inverse 0.292 350.400 0.075 1.500 1800.00 0.03 s
REF 615
GEN SYNCH BUS
OUT GOING
ABB
GEN SET PANEL BREAKER FROM Relay28 1200:5 Overcurrent Ground OC1 IEC Inverse 0.050 60.000 0.100 0.250 300.00 0.02 s
REF 615
GEN SYNCH BUS
INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay29 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.075 1.400 1750.00 0.01 s
GEAR BUS1 IRFA
SECONDARY SW
GEAR
INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay29 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS1 IRFA
SECONDARY SW
GEAR
Page 7 of 8
Protective Device Settings - Relay
OCR (51, 51V), OLR (49, Acc.) OCR (50), OLR (50, Jam)
Manufacturer
CB WHICH CT Level Prim. Prim. Time
Designation Relay ID & Device Function Trip Element Curve Pickup Time Delay Pickup
CONNECTED TO Ratio /Stage Amps Amps Delay
Model
INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay30 1250:1 Overcurrent Phase OC1 Inverse 0.280 350.000 0.075 1.400 1750.00 0.02 s
GEAR BUS2 IRFA
SECONDARY SW
GEAR
INCOMER FROM
GEN SET SYNCH
SECONDARY SW ZIV
BUS TO Relay30 1250:1 Overcurrent Ground OC1 Inverse 0.040 50.000 0.050 0.200 250.00 0.01 s
GEAR BUS2 IRFA
SECONDARY SW
GEAR
Page 8 of 8