18'x65' THREE STOREY RESIDENTIAL RC BUILDING STRUCTURAL DRAWING

DRAWING CONTENT

01. STRUCTURAL CONSIDERATION

02. GENERAL SPECIFICATION

03. FOOTING PLAN S-01

04. FOOTING SCHEDULE & DETAIL S-02 & S-03

05. RETAINING WALL PLAN & SECTION S-04 & S-05

06. COLUMN LAYOUT PLAN S-06 to S-08

07. COLUMN SCHEDULE & DETAIL S-09

08. BEAM PLAN S-10 to S-14

09. BEAM SCHEDULE & DETAIL S-15 & S-18

10. SLAB PLAN S-19 to S-22

11. SLAB SCHEDULE & DETAIL S-23

12. ELEVATIONS S-24 to S-30

13. STAIR S-31 to S-37

14. STIFFENER COLUMN S-38

PROJECT NO: HM 2022-26 CLIENT:


PRIVATE
ISSUED DATE: 02/12/2022
CONSTRUCTION:
LOCATION: MANDALAY RADIANT CONSTRUCTION
STRUCTURAL CONSIDERATION
1. Material Properties 5. Frame Analysis Software
Cylindrical strength of concrete (fc') = 2,500 psi ETABS 2016 Ultimate (Version16.2.1 Build 1727)
Cube strength of concrete (fcu') = 3,250 psi
6. Rebar Specification
Yield strength of main bar (fy) = 58 ksi
Yield strength of confinement bar (fy) = 40 ksi Rebar Specification
Modulus of elasticity of concrete (Ec) = 2,850 ksi Equivalent
Equivalent Area Weight
Poisson ratio of concrete = 0.18 Diameter
Type
(mm) (in) (mm2) (in2) kg/m kg/pics
2. Load Consideration
Unit weight of reinforced concrete = 150 pcf 8mm 6.500 0.256 33.196 0.051 0.26
Unit weight of water = 62.4 pcf 10mm 8.219 0.324 53.077 0.082 0.42 5.0
4 21" thick brick wall = 50 psf
16mm 13.253 0.522 138.004 0.214 1.08 13.0
9" thick brick wall = 100 psf
Floor finishing = 20 psf The actual weight [kg/m] of rebar shall be at least 94 % of the specified weight
Suspended load = 10 psf (kg/m) of rebar according to ASTM 615 and ASTM 706.
Live load on floor = 40 psf
Live load on roof = 20 psf
Live load on stair = 60 psf
Effective soil bearing capacity = 1.5 tsf

3. Load Combination for Frame Analysis (Gravity Load Only)


COMBO 01 1.4D
COMBO 02 1.2D + 1.6L

4. Code
ACI 318-08
General Requirement for Reinforced Concrete ld f ya
= for 22mm and larger bars
db 20 fc'
(1) Material Strength
f'c,cube ≈ fc ' ÷ 0.78 (fc ' ≤ 3,500 psi) where α = 1.3 for top bars (i.e 12" or more of concrete is cast in a single concreting below the development
f'c,cube ≈ fc ' ÷ 0.80 (3,500 <fc' ≤ 5,000 psi) length or splice length)
f'c,cube ≈ fc ' ÷ 0.81 (5,000 < fc' ≤ 6,000 psi) = 1 (for other bars)
f'c,cube ≈ fc ' ÷ 0.83 (fc ' > 6,000 psi)
Modification factor = As(required)/As(provided) and ld ≥ 12" (for all cases)
where f'c,cube = cube compressive strength of concrete
fc ' = cylindrical compressive strength of concrete (05) Lap Splice in Tension
Class A splice = 1.0 ld
(2) Concrete Clear Cover Class B splice = 1.3 ld
where ld = simplified tension development length
Exposed directly to weather or in
Not exposed to weather or not in Note: (a) ld does not apply the modification factor As(required)/As(provided)
Particulars contact with
contact with ground
ground (b) Lap splice are generally Class B, except when As(provided) ≥ 2 x As(required) over the length of the
splice, and ≤ 50% of the total reinforcement is spliced within the lap length
Slabs and Walls 3
" 2" but 1 21 " for 16mm and smaller
4 (c) lsplice ≥ 12" (in all cases)
bars

Beams and Columns 1 21 " 2" (06) Lap Splice in Compression


lsplice,com = 0.0005.fy.db

(03) Bar Spacing (For maximum size of aggregate 1")


Note: (a) For fc' < 3,000 psi increase by one-third
Type of member Minimum clear spacing Maximum c/c spacing (b) Minimum lsplice,com is 12"
(c) If lateral ties are used throughout the splice length having an area of ties of at least 0.0015hs where
Beam 1 31 " - s = tie bar spacing and
h = larger dimension of the member section,
Column 1.5 db (or) 1.5" - the splice length may be modified by the factor 0.83 but ≥ 12"

3h (or) 18" (one-way slab) (7) Standard Bar Hooks


Slab / Stair 3" 2h (or) 18" (two-way slab)
Temp & Shr: 5h (or) 18" 12db
4db or min: 2.5"

where db = diameter of the larger bar, h = thickness of slab


Notes: clear distance between layers of beam reinforcement must not be less than 1" and the bars in the upper
layer should be placed directly above those in the lower layer. Bars in beams must be placed symmetrically
about the vertical centerline. r r

db db
(04) Simplified Tension Development Length
ld f ya
= for 20mm and smaller bars Main Reinforcement
db 25 fc'
6db 12db 6db (or) ≥ 2h lsplice,tension ≥ 2h
135° ≥ 3" for seismic hook

r r r l/3
l
db (16mm or db (16mm to db (25mm or
smaller) 25mm) smaller) Splice Zone for Bottom Bar

Stirrup and Ties Lap splice confined


with s ≤ d/4 (or) 4"
Minimum diameter of bend for standard hooks (main bar)
d
Bar size, db Minimum diameter (inside)

For main bar (10mm to 25mm) 6db


Stirrup Spacing for Beam Lap Splice

For confinement bar ≤ 16mm 4db


Notes:(1) Do not splice more than 50% of the total at any section.
(2) Do not splice any bar within the cantilever span.

(08) Development Length of Standard Bar Hooks (3) Both top and bottom bars are not to be spliced within the joint and a distance of twice the member

ldh fy depth from the face of the joint.


= (4) If possible, bottom bars should not be spliced at mid span and at the beams that supporting the
db 50 fc'
secondary beams.
Modification factors (to multiply);
(a) If side cover of main bars ≥ 2.5" clear and for 90° hook if clear cover
on bar extension also ≥ 2"............................................................................0.7 (09.b) Slab Bar Splice
(b) If hook is enclosed within closed stirrups at spacing ≤ 3db along ldh..........0.8
(c) Reinforcement in excess of that required...........................As(required)/As(provided)
lsplice,tension
Note: Minimum ldh = 8 db ≥ 6" ≥ 2h

h
(09.a) Beam Bar Splice

≥ 2h lsplice,tension ≥ 2h
l/3
l
h
Splice Zone for Slab Bottom Bar

Splice Zone for Top Bar


(09.c) Column Bar Splice

Upper Floor
Upper Floor

lsplice,tension
h2/3
h

h/3 h2
Splice Zone

h2/3
Landing Floor

Splice Zone Dowel bar Lap splice


h confined with
s ≤ h/4 (or) 6"
h1/3
If ≥ 3"
lsplice,tension use dowel bar
h1
h/3
h1/3 lsplice,tension
Lower Floor Lower Floor

Column Main Bar Splice Tie Spacing for


Splice Zone for Column Main Bar Without Landing Floor Splice Zone for Column Main Bar With Landing Floor for Column Offset ≥ 3" Column Lap Splice

(10.a) Beam Cut-off Point (10.b) Slab Cut-off Point

l/3 l*/3
l/3 l*/3

l l
*If adjacent spans are different in span lengths, use the larger of the two. *If adjacent spans are different in span lengths, use the larger of the two.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
67' CLIENT PRIVATE
3'-6" 17'-6" 8' 18' 17'-6" 2'-6"
1'-6" 1'-721"
RADIANT
CONSTRUCTION
CONSTRUCTION
2
ISSUED DATE 02/12/2022
F-1 F-1 F-1 F-3 F-2
HM 2022-26

PROJECT THREE STOREY


20' 17' 17' 20'-3" RESIDENTIAL RC
BUILDING
4'-6"
F-1 F-1 F-1 F-3 F-2 LOCATION MANDALAY

1 SHEET NO. S- 01

1'-6" 1'-721"
Property Line TITLE FOOTING PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION
F-1 6@5'-0"x7'-0"x12"
F-2 2@5'-0"x7'-0"x12" Footing Plan (-8'-0" from N.G.L) NO. DATE
F-3 2@5'-0"x8'-0"x15"
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Isolated Footing Schedule

Type Quantity Thickness Dimension Layer *Bottom Cover Side Cover Short Direction Long Direction Assumed Qe

F-1 6 12" 5'-0"x7'-0" Bottom 2" 3" 16mm@6"c/c 16mm@6"c/c 1.50 tsf

F-2 2 12" 5'-0"x7'-0" Bottom 2" 3" 16mm@6"c/c 16mm@6"c/c 1.50 tsf

F-3 2 15" 5'-0"x8'-0" Bottom 2" 3" 16mm@6"c/c 16mm@6"c/c 1.50 tsf
CLIENT PRIVATE

F-1 Section (Shorter Direction) F-1 Section (Longer Direction) RADIANT


CONSTRUCTION
CONSTRUCTION
N.G.L
ISSUED DATE 02/12/2022
HM 2022-26

PROJECT THREE STOREY


RESIDENTIAL RC
BUILDING

**8' LOCATION MANDALAY


12" Footing 16m@6"c/c 12" Footing 16m@6"c/c
Thickness both way Thickness both way SHEET NO. S- 02
6"
3" thk: Lean 3" thk: Lean
Concrete Concrete FOOTING SCHEDULE
TITLE
& DETAIL

F.L
SCALE AS SHOWN
9" thk: 9" thk: DESIGNED
5' Hardcore 7' Hardcore -
BY

DRAWN BY -

CHECKED
-
BY
REVISION
*If lean concrete is not included, the bottom cover is 3".
**The foundation depth shown in the drawing is only for suggestion. The NO. DATE
actual depth is where the effective bearing capacity of soil is 1.50 tsf.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

F-2 Section (Shorter Direction) F-2 Section (Longer Direction)


N.G.L

**8'
12" Footing 16m@6"c/c 12" Footing
Thickness both way Thickness
6" 4'-6" 2'-6" CLIENT PRIVATE
16m@6"c/c
3" thk: Lean
both way
Concrete RADIANT
CONSTRUCTION
CONSTRUCTION
3" thk: Lean
F.L
Concrete ISSUED DATE 02/12/2022
9" thk: 9" thk: HM 2022-26
5' Hardcore 7' Hardcore
PROJECT THREE STOREY
F-3 Section (Shorter Direction) F-3 Section (Longer Direction) RESIDENTIAL RC
BUILDING
N.G.L

LOCATION MANDALAY

SHEET NO. S- 03

TITLE FOOTING DETAIL

**8'
15" Footing 15" Footing
16m@6"c/c 16m@6"c/c SCALE AS SHOWN
Thickness Thickness
6" both way both way DESIGNED
-
BY
3" thk: Lean 3" thk: Lean
Concrete Concrete DRAWN BY -

CHECKED
F.L -
BY
9" thk: 9" thk: REVISION
5' Hardcore 8' Hardcore
NO. DATE
**The foundation depth shown in the drawing is only for suggestion. The actual depth is where the effective bearing capacity of soil is 1.50 tsf.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
61' CLIENT PRIVATE
17'-6" 8' 18' 17'-6"
RADIANT
CONSTRUCTION
CONSTRUCTION
2
ISSUED DATE 02/12/2022
HM 2022-26

PROJECT THREE STOREY


17' RESIDENTIAL RC
BUILDING
12'-2"

A LOCATION MANDALAY

1 SHEET NO. S- 04

A
RETAINING WALL
TITLE
PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION

Retaining Wall Plan NO. DATE


9" thk: Wall
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

6" 3"
9"thk:
retaining wall
N.G.L

2'
CLIENT PRIVATE
Lean Concrete
RADIANT
CONSTRUCTION
CONSTRUCTION

2' ISSUED DATE 02/12/2022


Section A-A HM 2022-26

PROJECT THREE STOREY


RESIDENTIAL RC
BUILDING

LOCATION MANDALAY

SHEET NO. S- 05

RETAINING WALL
TITLE
SECTION

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION
NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
61' CLIENT PRIVATE
17'-6" 8' 18' 17'-6"
RADIANT
CONSTRUCTION
C-1 C-1 C-1 C-1 C-1 CONSTRUCTION
2
2'-5" ISSUED DATE 02/12/2022
C-3 C-3 HM 2022-26

PROJECT THREE STOREY


17' RESIDENTIAL RC
BUILDING

LOCATION MANDALAY
C-1 C-2 C-2 C-1 C-1
1 SHEET NO. S- 06

COLUMN LAYOUT
TITLE PLAN
(OVERALL)

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION

Column Layout Plan (Overall) NO. DATE


fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
61' CLIENT PRIVATE
17'-6" 8' 18' 17'-6"
RADIANT
CONSTRUCTION
C-1 C-1 C-1 C-1 C-1 CONSTRUCTION
2
ISSUED DATE 02/12/2022
HM 2022-26

PROJECT THREE STOREY


17' RESIDENTIAL RC
BUILDING

LOCATION MANDALAY
C-1 C-2 C-2 C-1 C-1
1 SHEET NO. S- 07

COLUMN LAYOUT
PLAN
TITLE (FOOTING TO ROOF
FLOOR)
SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION
C-1 8@12"x12" Column Layout Plan (Footing to Roof Floor) NO. DATE
C-2 2@12"x12"
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
61' CLIENT PRIVATE
17'-6" 8' 18' 17'-6"
RADIANT
CONSTRUCTION
CONSTRUCTION
2
2'-5" ISSUED DATE 02/12/2022
C-3 C-3 HM 2022-26

PROJECT THREE STOREY


17' RESIDENTIAL RC
BUILDING

LOCATION MANDALAY
C-2 C-2
1 SHEET NO. S- 08

COLUMN LAYOUT
PLAN
TITLE (ROOF FLOOR TO
ROOF)
SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION
C-2 2@10"x10" Column Layout Plan (Roof Floor to Roof) Rebar configuration NO. DATE
C-3 2@10"x10" for 10"x10" column.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Column Schedule

Tie Bar
Type Quantity Size Cover Main Bar Storey
Support Mid

C-1 8 12"x12" 1.5" 8-16mm 1.189% 1-8mm@6"c/c 1-8mm@6"c/c Footing to Roof Floor

12"x12" 1.5" 8-16mm 1.189% 1-8mm@6"c/c 1-8mm@6"c/c Footing to Roof Floor


C-2 2
10"x10" 1.5" 6-16mm 1.284% 1-8mm@5"c/c 1-8mm@5"c/c Roof Floor to Roof

C-3 2 10"x10" 1.5" 6-16mm 1.284% 1-8mm@5"c/c 1-8mm@5"c/c Roof Floor to Roof
CLIENT PRIVATE

Column Detail RADIANT


CONSTRUCTION
Storey CONSTRUCTION
Type Footing to Roof Floor Roof Floor to Roof
ISSUED DATE 02/12/2022
Size 12"x12"
HM 2022-26

PROJECT THREE STOREY


C-1 RESIDENTIAL RC
BUILDING
Main Bar Tie Bar
8-16mm 8mm@6"c/c LOCATION MANDALAY

Size 12"x12" Size 10"x10"


SHEET NO. S- 09

COLUMN SCHEDULE
C-2 TITLE
& DETAIL

Main Bar Tie Bar Main Bar Tie Bar SCALE AS SHOWN
8-16mm 8mm@6"c/c 6-16mm 8mm@5"c/c
DESIGNED
-
Size 10"x10" BY

DRAWN BY -

C-3 CHECKED
-
BY

Main Bar Tie Bar REVISION


6-16mm 8mm@5"c/c NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
61' CLIENT PRIVATE
17'-6" 8' 18' 17'-6"
RADIANT
GB-1b GB-1a GB-1b GB-1b CONSTRUCTION
CONSTRUCTION
2
2'
ISSUED DATE 02/12/2022
5'-3"
GB-1a HM 2022-26

THREE STOREY
*GB-1b

*GB-1b
PROJECT
GB-1b

GB-1a

GB-1a
17' 13' RESIDENTIAL RC
BUILDING

LOCATION MANDALAY
2'
1 SHEET NO. S- 10
GB-1b GB-1a GB-1b GB-1b

TITLE GROUND BEAM PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION

Ground Beam Plan (+2'-0" from N.G.L) NO. DATE


GB-1 10"x10" *Both Top & Bottom Bars 3-16mm
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
Stiffener Column
3'-6" 17'-6" 8' 18' 17'-6"
(See Detail in S-38)
RADIANT
FB-5 FB-4a FB-4a FB-4a FB-4a CONSTRUCTION
CONSTRUCTION
2
FB-3 ISSUED DATE 02/12/2022
5'-3"
FB-3 FB-3 FB-3 FB-3 HM 2022-26

PROJECT THREE STOREY


FB-6a

FB-6b

FB-6b

FB-6b

FB-6a
FB-5

17' RESIDENTIAL RC
BUILDING
FB-2

FB-2
LOCATION MANDALAY
5'-1" 10'-1"
1 SHEET NO. S- 11
FB-5 FB-4b FB-4a FB-4b FB-4b

FIRST FLOOR BEAM


TITLE
PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
FB-1 6"x12" -
BY
FB-2 10"x10"
FB-3 10"x12" REVISION
FB-4 10"x14"
FB-5 12"x12" First Floor Beam Plan (+12'-0" from GF) NO. DATE
FB-6 12"x14"
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
Stiffener Column
3'-6" 17'-6" 8' 18' 17'-6"
(See Detail in S-38)
RADIANT
FB-5 FB-4a FB-4a FB-4a FB-4a CONSTRUCTION
CONSTRUCTION
2
FB-1

FB-3 ISSUED DATE 02/12/2022


5'-3"
FB-3 FB-3 FB-3 FB-3 HM 2022-26

PROJECT THREE STOREY


FB-6a

FB-6b

FB-6b

FB-6b

FB-6a
17' RESIDENTIAL RC
FB-5

BUILDING

LOCATION MANDALAY

1 SHEET NO. S- 12
FB-5 FB-4a FB-4a FB-4a FB-4b

SECOND FLOOR
TITLE
BEAM PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
FB-1 6"x12" -
BY
FB-2 10"x10"
FB-3 10"x12" REVISION
FB-4 10"x14"
FB-5 12"x12" Second Floor Beam Plan (+11'-0" from 1F) NO. DATE
FB-6 12"x14"
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
Stiffener Column
3'-6" 17'-6" 8' 18' 17'-6"
(See Detail in S-38)
RADIANT
RB-5 RB-4 RB-4 RB-4 RB-4 CONSTRUCTION
CONSTRUCTION
2
RB-1

RB-3 ISSUED DATE 02/12/2022


5'-3"
RB-3 RB-3 RB-3 RB-3 HM 2022-26

THREE STOREY
**RB-6b

**RB-6b

*RB-6b
PROJECT
RB-6a

RB-6a
17' RESIDENTIAL RC
RB-5

BUILDING

LOCATION MANDALAY

1 SHEET NO. S- 13
RB-5 RB-4 RB-4 RB-4 RB-4

ROOF FLOOR BEAM


TITLE
PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
RB-1 6"x12" -
BY
RB-2 10"x10"
RB-3 10"x12" REVISION
RB-4 10"x14"
RB-5 12"x12" Roof Floor Beam Plan (+10'-0" from 2F) *Top Bar 4-16mm NO. DATE
RB-6 12"x14" **Stirrup 2-10mm@8"c/c
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
3'-6" 17'-6" 8' 18' 17'-6"
RADIANT
CONSTRUCTION
CONSTRUCTION
2
2'-5" RB-3
ISSUED DATE 02/12/2022
HM 2022-26

PROJECT THREE STOREY


17' RB-2 RESIDENTIAL RC
RB-3

RB-3
BUILDING

LOCATION MANDALAY

1 SHEET NO. S- 14
RB-3

TITLE ROOF BEAM PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
RB-1 6"x12" -
BY
RB-2 10"x10"
RB-3 10"x12" REVISION
RB-4 10"x14"
RB-5 12"x12" Roof Beam Plan (+10'-0" from RF) NO. DATE
RB-6 12"x14"
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Beam Schedule

Top Bar Bottom Bar Stirrup


Storey Type Size Cover Torsion
Support Mid Support Mid Support Mid

GB-1a 10"x10" 1.5" 2-16mm 2-16mm 2-16mm 2-16mm - 8mm@5"c/c 8mm@5"c/c


GF
GB-1b 10"x10" 1.5" 3-16mm 3-16mm 2-16mm 2-16mm - 8mm@5"c/c 8mm@5"c/c

FB-1 6"x12" 1.5" 2-16mm 2-16mm 2-16mm 2-16mm - 8mm@4"c/c 8mm@4"c/c

FB-2 10"x10" 1.5" 2-16mm 2-16mm 3-16mm 3-16mm - 8mm@5"c/c 8mm@5"c/c


CLIENT PRIVATE
FB-3 10"x12" 1.5" 3-16mm 2-16mm 2-16mm 2-16mm - 8mm@6"c/c 8mm@6"c/c
RADIANT
FB-4a 10"x14" 1.5" 3-16mm 3-16mm 3-16mm 3-16mm - 8mm@6"c/c 8mm@6"c/c CONSTRUCTION
CONSTRUCTION
1F & 2F
FB-4b 10"x14" 1.5" 5-16mm 3-16mm 3-16mm 3-16mm - 8mm@4"c/c 8mm@6"c/c
ISSUED DATE 02/12/2022
FB-5 12"x12" 1.5" 3-16mm 3-16mm 3-16mm 3-16mm - 8mm@6"c/c 8mm@6"c/c HM 2022-26

FB-6a 12"x14" 1.5" 4-16mm 4-16mm 4-16mm 4-16mm - 8mm@4"c/c 8mm@6"c/c PROJECT THREE STOREY
RESIDENTIAL RC
FB-6b 12"x14" 1.5" 6-16mm 4-16mm 6-16mm 6-16mm - 8mm@4"c/c 8mm@6"c/c BUILDING

RB-1 6"x12" 1.5" 2-16mm 2-16mm 2-16mm 2-16mm - 8mm@4"c/c 8mm@4"c/c


LOCATION MANDALAY
RB-2 10"x10" 1.5" 2-16mm 2-16mm 2-16mm 2-16mm - 8mm@5"c/c 8mm@5"c/c
SHEET NO. S- 15
RB-3 10"x12" 1.5" 2-16mm 2-16mm 2-16mm 2-16mm - 8mm@6"c/c 8mm@6"c/c

RF & R RB-4 10"x14" 1.5" 3-16mm 2-16mm 2-16mm 2-16mm - 8mm@6"c/c 8mm@6"c/c
TITLE BEAM SCHEDULE
RB-5 12"x12" 1.5" 3-16mm 3-16mm 3-16mm 3-16mm - 8mm@6"c/c 8mm@6"c/c

RB-6a 12"x14" 1.5" 3-16mm 3-16mm 4-16mm 4-16mm - 8mm@4"c/c 8mm@6"c/c SCALE AS SHOWN
DESIGNED
RB-6b 12"x14" 1.5" 6-16mm 4-16mm 6-16mm 6-16mm - 8mm@4"c/c 8mm@6"c/c -
BY
LB-1a 10"x12" 1.5" 2-16mm 2-16mm 2-16mm 2-16mm - 8mm@6"c/c 8mm@6"c/c DRAWN BY -
Landing
LB-1b 10"x12" 1.5" 5-16mm 5-16mm 3-16mm 3-16mm - 8mm@4"c/c 8mm@4"c/c CHECKED
-
BY
REVISION
The maximum beam main bar clear spacing between top layer and bottom layer is 1.5". NO. DATE
*The spacing of stirrup is 4"c/c and stirrup hook is placed downward for cantilever beams.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Beam Detail (Ground Beam)


Location GB-1a GB-1b

SIZE 10"x10" SIZE 10"x10"


TOP BAR 2-16mm TOP BAR 3-16mm
SUPPORT BOT BAR: 2-16mm BOT BAR: 2-16mm
STIRRUP 8mm@5"c/c STIRRUP 8mm@5"c/c

SIZE 10"x10" SIZE 10"x10"


TOP BAR 2-16mm TOP BAR 3-16mm
MID BOT BAR: 2-16mm BOT BAR: 2-16mm
STIRRUP 8mm@5"c/c STIRRUP 8mm@5"c/c CLIENT PRIVATE

Beam Detail (1F & 2F) RADIANT


CONSTRUCTION
CONSTRUCTION
Location FB-1 FB-2 FB-3
ISSUED DATE 02/12/2022
SIZE 6"x12" SIZE 10"x10" SIZE 10"x12" HM 2022-26
TOP BAR 2-16mm TOP BAR 2-16mm TOP BAR 3-16mm
SUPPORT BOT BAR: 2-16mm BOT BAR: 3-16mm BOT BAR: 2-16mm
PROJECT THREE STOREY
STIRRUP 8mm@4"c/c STIRRUP 8mm@5"c/c STIRRUP 8mm@6"c/c RESIDENTIAL RC
BUILDING
SIZE 6"x12" SIZE 10"x10" SIZE 10"x12"
TOP BAR 2-16mm TOP BAR 2-16mm TOP BAR 2-16mm LOCATION MANDALAY
MID BOT BAR: 2-16mm BOT BAR: 3-16mm BOT BAR: 2-16mm
STIRRUP 8mm@4"c/c STIRRUP 8mm@5"c/c STIRRUP 8mm@6"c/c SHEET NO. S- 16

Beam Detail (1F & 2F) TITLE BEAM DETAIL


Location FB-4a FB-4b FB-5

SIZE 10"x14" SIZE 10"x14" SIZE 12"x12" SCALE AS SHOWN


TOP BAR 3-16mm TOP BAR 5-16mm TOP BAR 3-16mm DESIGNED
SUPPORT -
BOT BAR: 3-16mm BOT BAR: 3-16mm BOT BAR: 3-16mm BY
STIRRUP 8mm@6"c/c STIRRUP 8mm@4"c/c STIRRUP 8mm@6"c/c
DRAWN BY -

SIZE 10"x14" SIZE 10"x14" SIZE 12"x12" CHECKED


-
TOP BAR 3-16mm TOP BAR 3-16mm TOP BAR 3-16mm BY
MID BOT BAR: 3-16mm BOT BAR: 3-16mm BOT BAR: 3-16mm
REVISION
STIRRUP 8mm@6"c/c STIRRUP 8mm@6"c/c STIRRUP 8mm@6"c/c
NO. DATE
The maximum beam main bar clear spacing between top layer and bottom layer is 1.5". The spacing of stirrup is 4"c/c and stirrup hook is placed downward for cantilever beams.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Beam Detail (1F & 2F)


Location FB-6a FB-6b

SIZE 12"x14" SIZE 12"x14"


TOP BAR 4-16mm TOP BAR 6-16mm
SUPPORT BOT BAR: 4-16mm BOT BAR: 6-16mm
STIRRUP 8mm@4"c/c STIRRUP 8mm@4"c/c

SIZE 12"x14" SIZE 12"x14"


TOP BAR 4-16mm TOP BAR 4-16mm
MID BOT BAR: 4-16mm BOT BAR: 6-16mm
STIRRUP 8mm@6"c/c STIRRUP 8mm@6"c/c CLIENT PRIVATE

Beam Detail (RF & R) RADIANT


CONSTRUCTION
CONSTRUCTION
Location RB-1 RB-2 RB-3
ISSUED DATE 02/12/2022
SIZE 6"x12" SIZE 10"x10" SIZE 10"x12" HM 2022-26
TOP BAR 2-16mm TOP BAR 2-16mm TOP BAR 2-16mm
SUPPORT BOT BAR: 2-16mm BOT BAR: 2-16mm BOT BAR: 2-16mm
PROJECT THREE STOREY
STIRRUP 8mm@4"c/c STIRRUP 8mm@5"c/c STIRRUP 8mm@6"c/c RESIDENTIAL RC
BUILDING
SIZE 6"x12" SIZE 10"x10" SIZE 10"x12"
TOP BAR 2-16mm TOP BAR 2-16mm TOP BAR 2-16mm LOCATION MANDALAY
MID BOT BAR: 2-16mm BOT BAR: 2-16mm BOT BAR: 2-16mm
STIRRUP 8mm@4"c/c STIRRUP 8mm@5"c/c STIRRUP 8mm@6"c/c SHEET NO. S- 17

Beam Detail (RF & R) TITLE BEAM DETAIL


Location RB-4 RB-5 RB-6a

SIZE 10"x14" SIZE 12"x12" SIZE 12"x14" SCALE AS SHOWN


TOP BAR 3-16mm TOP BAR 3-16mm TOP BAR 3-16mm DESIGNED
SUPPORT -
BOT BAR: 2-16mm BOT BAR: 3-16mm BOT BAR: 4-16mm BY
STIRRUP 8mm@6"c/c STIRRUP 8mm@6"c/c STIRRUP 8mm@4"c/c
DRAWN BY -

SIZE 10"x14" SIZE 12"x12" SIZE 12"x14" CHECKED


-
TOP BAR 2-16mm TOP BAR 3-16mm TOP BAR 3-16mm BY
MID BOT BAR: 2-16mm BOT BAR: 3-16mm BOT BAR: 4-16mm
REVISION
STIRRUP 8mm@6"c/c STIRRUP 8mm@6"c/c STIRRUP 8mm@6"c/c
NO. DATE
The maximum beam main bar clear spacing between top layer and bottom layer is 1.5". The spacing of stirrup is 4"c/c and stirrup hook is placed downward for cantilever beams.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Beam Detail (RF & R)


Location RB-6b

SIZE 12"x14"
TOP BAR 6-16mm
SUPPORT BOT BAR: 6-16mm
STIRRUP 8mm@4"c/c

SIZE 12"x14"
TOP BAR 4-16mm
MID BOT BAR: 6-16mm
STIRRUP 8mm@6"c/c CLIENT PRIVATE

Beam Detail (Landing) RADIANT


CONSTRUCTION
CONSTRUCTION
Location LB-1a LB-1b
ISSUED DATE 02/12/2022
SIZE 10"x12" SIZE 10"x12" HM 2022-26
TOP BAR 2-16mm TOP BAR 5-16mm
SUPPORT BOT BAR: 2-16mm BOT BAR: 3-16mm
PROJECT THREE STOREY
STIRRUP 8mm@6"c/c STIRRUP 8mm@4"c/c RESIDENTIAL RC
BUILDING
SIZE 10"x12" SIZE 10"x12"
TOP BAR 2-16mm TOP BAR 5-16mm LOCATION MANDALAY
MID BOT BAR: 2-16mm BOT BAR: 3-16mm
STIRRUP 8mm@6"c/c STIRRUP 8mm@4"c/c SHEET NO. S- 18

TITLE BEAM DETAIL

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION
NO. DATE
The maximum beam main bar clear spacing between top layer and bottom layer is 1.5". The spacing of stirrup is 4"c/c and stirrup hook is placed downward for cantilever beams.
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
3'-6" 17'-6" 8' 18' 17'-6"
RADIANT
CONSTRUCTION
CONSTRUCTION
2
ISSUED DATE 02/12/2022
5'-3"
9" HM 2022-26

PROJECT THREE STOREY


17' 3'-6" RESIDENTIAL RC
BUILDING
Stair
LOCATION MANDALAY

1 SHEET NO. S- 19

FIRST FLOOR SLAB


TITLE
PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION

4" Slab Thickness First Floor Slab Plan (+12'-0" from GF) NO. DATE
6" Slab Thickness
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
3'-6" 17'-6" 8' 18' 17'-6"
6" RADIANT
CONSTRUCTION
CONSTRUCTION
2
3' ISSUED DATE 02/12/2022
5'-3"
1'-6" HM 2022-26

PROJECT THREE STOREY


17' 3'-6" RESIDENTIAL RC
BUILDING
Stair
LOCATION MANDALAY

1 SHEET NO. S- 20

SECOND FLOOR
TITLE
SLAB PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION

4" Slab Thickness Second Floor Slab Plan (+11'-0" from 1F) NO. DATE
6" Slab Thickness
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
3'-6" 17'-6" 8' 18' 17'-6"
6" RADIANT
CONSTRUCTION
CONSTRUCTION
2
3' ISSUED DATE 02/12/2022
5'-3"
1'-6" HM 2022-26

PROJECT THREE STOREY


17' RESIDENTIAL RC
BUILDING
Stair
LOCATION MANDALAY

1 SHEET NO. S- 21

ROOF FLOOR SLAB


TITLE
PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION

4" Slab Thickness Roof Floor Slab Plan (+10'-0" from 2F) NO. DATE
6" Slab Thickness
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi
E
N S
W

A B C D E
64'-6" CLIENT PRIVATE
3'-6" 17'-6" 8' 18' 17'-6"
RADIANT
CONSTRUCTION
CONSTRUCTION
2
2'-5" ISSUED DATE 02/12/2022
HM 2022-26

PROJECT THREE STOREY


17' RESIDENTIAL RC
BUILDING

LOCATION MANDALAY

1 SHEET NO. S- 22

TITLE ROOF SLAB PLAN

SCALE AS SHOWN
DESIGNED
-
BY

DRAWN BY -

CHECKED
-
BY
REVISION
4" Slab Thickness
Water Tank Location on 4" Thk: Slab Roof Slab Plan (+10'-0" from RF) NO. DATE
(Max: Allowable Water Volume = 1,200 gal)
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Slab Schedule

Short Direction Long Direction


Storey Thickness Cover Layer Remark
Support Mid Support Mid

Top 10mm@8"c/c - 10mm@8"c/c -


All one way & two
*All Storey 4" 0.75" way slabs
Bottom 10mm@8"c/c 10mm@8"c/c 10mm@8"c/c 10mm@8"c/c

Top
All Storey 6" 0.75" Same as Waist Slab Reinforcement - CLIENT PRIVATE
Bottom

RADIANT
Y CONSTRUCTION
CONSTRUCTION

ISSUED DATE 02/12/2022


HM 2022-26

PROJECT THREE STOREY


RESIDENTIAL RC
BUILDING

X X
LOCATION MANDALAY

SHEET NO. S- 23

SLAB SCHEDULE &


TITLE
DETAIL

SCALE AS SHOWN
Bottom Steel Plan Top Steel Plan DESIGNED
-
Y BY

DRAWN BY -
lu/3 **lu/3 lu/3 **lu/3
CHECKED
-
BY
lu lu REVISION
Section X-X *Top bars in both directions are
SLAB DETAIL Section Y-Y NO. DATE
not cut under water tank.
**Length of the largest clear span
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

A B C D E

64'-6"
3'-6" 17'-6" 8' 18' 17'-6"
R
+45'-0"

10'

RF CLIENT PRIVATE

+35'-0"
5' RADIANT
CONSTRUCTION
CONSTRUCTION
10'
5' ISSUED DATE 02/12/2022
2F HM 2022-26
+25'-0"
45' 5'-6" PROJECT THREE STOREY
RESIDENTIAL RC
11' BUILDING

5'-6"
1F LOCATION MANDALAY

+14'-0"
SHEET NO. S- 24
6'

12'
GF TITLE ELEVATION-1
6' +2'-0"
SCALE AS SHOWN
2' N.G.L
DESIGNED
+0'-0" -
BY
8' DRAWN BY -
F.L
CHECKED
-
-8'-0" BY
REVISION
Elevation-1 NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

A B C D E

64'-6"
3'-6" 17'-6" 8' 18' 17'-6"
R
+45'-0"

10'

RF CLIENT PRIVATE

+35'-0"
RADIANT
CONSTRUCTION
CONSTRUCTION
10'
ISSUED DATE 02/12/2022
2F HM 2022-26
+25'-0"
45' PROJECT THREE STOREY
RESIDENTIAL RC
11' BUILDING

1F LOCATION MANDALAY

+14'-0"
SHEET NO. S- 25

12'
GF TITLE ELEVATION-2
+2'-0"
SCALE AS SHOWN
2' N.G.L
DESIGNED
+0'-0" -
BY
8' DRAWN BY -
F.L
CHECKED
-
-8'-0" BY
REVISION
Elevation-2 NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

1 2

17'
R
+45'-0"

10'

RF CLIENT PRIVATE

+35'-0"
RADIANT
CONSTRUCTION
CONSTRUCTION
10'
ISSUED DATE 02/12/2022
2F HM 2022-26
+25'-0"
45' PROJECT THREE STOREY
RESIDENTIAL RC
11' BUILDING

1F LOCATION MANDALAY

+14'-0"
SHEET NO. S- 26

12'
GF TITLE ELEVATION-A
+2'-0"
SCALE AS SHOWN
2' N.G.L
DESIGNED
+0'-0" -
BY
8' DRAWN BY -
F.L
CHECKED
-
-8'-0" BY
REVISION
Elevation-A NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

1 2

17'
R
+45'-0"

10'

14'-7" 2'-5" CLIENT PRIVATE


RF
+35'-0"
RADIANT
CONSTRUCTION
CONSTRUCTION
10'
ISSUED DATE 02/12/2022
2F HM 2022-26
+25'-0"
45' PROJECT THREE STOREY
RESIDENTIAL RC
11' BUILDING

1F LOCATION MANDALAY

+14'-0"
SHEET NO. S- 27

12'
GF TITLE ELEVATION-B
+2'-0"
SCALE AS SHOWN
2' N.G.L
DESIGNED
+0'-0" -
BY
8' DRAWN BY -
F.L
CHECKED
-
-8'-0" BY
REVISION
Elevation-B NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

1 2

17'
R
+45'-0"

10'

14'-7" 2'-5" CLIENT PRIVATE


RF
+35'-0"
RADIANT
CONSTRUCTION
CONSTRUCTION
10'
ISSUED DATE 02/12/2022
2F HM 2022-26
+25'-0"
45' PROJECT THREE STOREY
RESIDENTIAL RC
11' BUILDING

1F LOCATION MANDALAY

+14'-0"
SHEET NO. S- 28

12'
GF TITLE ELEVATION-C
+2'-0"
SCALE AS SHOWN
2' N.G.L
DESIGNED
+0'-0" -
BY
8' DRAWN BY -
F.L
CHECKED
-
-8'-0" BY
REVISION
Elevation-C NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

1 2

17'
R
+45'-0"

10'

RF CLIENT PRIVATE

+35'-0"
RADIANT
CONSTRUCTION
CONSTRUCTION
10'
ISSUED DATE 02/12/2022
2F HM 2022-26
+25'-0"
45' PROJECT THREE STOREY
RESIDENTIAL RC
11' BUILDING

1F LOCATION MANDALAY

+14'-0"
SHEET NO. S- 29

12'
GF TITLE ELEVATION-D
+2'-0"
SCALE AS SHOWN
2' N.G.L
DESIGNED
+0'-0" -
BY
8' DRAWN BY -
F.L
CHECKED
-
-8'-0" BY
REVISION
Elevation-D NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

1 2

17'
R
+45'-0"

10'

RF CLIENT PRIVATE

+35'-0"
RADIANT
CONSTRUCTION
CONSTRUCTION
10'
ISSUED DATE 02/12/2022
2F HM 2022-26
+25'-0"
45' PROJECT THREE STOREY
RESIDENTIAL RC
11' BUILDING

1F LOCATION MANDALAY

+14'-0"
SHEET NO. S- 30

12'
GF TITLE ELEVATION-E
+2'-0"
SCALE AS SHOWN
2' N.G.L
DESIGNED
+0'-0" -
BY
8' DRAWN BY -
F.L
CHECKED
-
-8'-0" BY
REVISION
Elevation-E NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

1 2

17'

RF
+35' - 0"

5'

3'-7"
10'

6" 2'-8"
5' CLIENT PRIVATE

1'-6" 5'-8" 6"


2F RADIANT
CONSTRUCTION
+25' - 0" CONSTRUCTION

ISSUED DATE 02/12/2022


5'-6"
HM 2022-26
3'-7"
PROJECT THREE STOREY
11' RESIDENTIAL RC
BUILDING
6" 2'-8"
5'-6"
LOCATION MANDALAY
9"
5'-8" 6"
1F SHEET NO. S- 31
+14' - 0"

6' TITLE STAIR ELEVATION

3'-7" SCALE AS SHOWN


12'
DESIGNED
-
BY
6" 2'-8"
6' DRAWN BY -

CHECKED
-
GF BY
+2' - 0" REVISION
NO. DATE
Stair Elevation
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

B C

8'

6" 3'-6" 3'-6" 6"

CLIENT PRIVATE

RADIANT
CONSTRUCTION
CONSTRUCTION

ISSUED DATE 02/12/2022


HM 2022-26

8'-3" PROJECT THREE STOREY


8'-8"
RESIDENTIAL RC
BUILDING

11'-4"
11'-10" LOCATION MANDALAY

SHEET NO. S- 32

STAIR PLAN
TITLE
(GF TO 1F)

LB-1a SCALE AS SHOWN


DESIGNED
LB-1b

3'-7" LB-1b 2'-8" -


BY
LB-1a
DRAWN BY -
1
6" CHECKED
-
BY
REVISION
Stair Plan (GF to 1F) NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

B C

8'

6" 3'-6" 3'-6" 6"


6" thk:
Floor Slab

CLIENT PRIVATE

RADIANT
CONSTRUCTION
CONSTRUCTION

ISSUED DATE 02/12/2022


HM 2022-26

PROJECT THREE STOREY


7'-6" RESIDENTIAL RC
7'-11"
BUILDING

LOCATION MANDALAY
10'-7"
11'-1"
SHEET NO. S- 33

STAIR PLAN
TITLE
(1F TO 2F)

LB-1a SCALE AS SHOWN


DESIGNED
LB-1b

3'-7" LB-1b 2'-8" -


BY
LB-1a
DRAWN BY -
1
6" CHECKED
-
BY
REVISION
Stair Plan (1F to 2F) NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

B C

8'

6" 3'-6" 3'-6" 6"


6" thk:
Floor Slab

CLIENT PRIVATE

RADIANT
CONSTRUCTION
CONSTRUCTION

ISSUED DATE 02/12/2022


HM 2022-26

PROJECT THREE STOREY


RESIDENTIAL RC
6'-9" BUILDING
7'-2"

LOCATION MANDALAY
9'-10"
10'-4" SHEET NO. S- 34

STAIR PLAN
TITLE
(2F TO RF)

LB-1a SCALE AS SHOWN


DESIGNED
LB-1b

3'-7" LB-1b 2'-8" -


BY
LB-1a
DRAWN BY -
1
6" CHECKED
-
BY
REVISION
Stair Plan (2F to RF) NO. DATE
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

11'-9"
24
1F
23
+14'-0"
22
21
20
19
18
6' 17 Distribution Bar
16 10mm@8"c/c
CLIENT PRIVATE
15
14 RADIANT
13 CONSTRUCTION
CONSTRUCTION
3'-7" Main Bar
GF Landing ISSUED DATE 02/12/2022
10mm@6"c/c
+8'-0" HM 2022-26
Rise = 6"
Run = 9" PROJECT THREE STOREY
Waist Slab Thickness = 5" RESIDENTIAL RC
Landing Slab Thickness = 4" BUILDING

12 LOCATION MANDALAY
GF Landing
11
+8'-0"
10 SHEET NO. S- 35
9
3'-2" 5" 8 STAIR DETAIL
TITLE
6" 7 (GF TO 1F)
6
6' Distribution Bar 5 SCALE AS SHOWN
10mm@8"c/c 4 DESIGNED
-
3 BY
2 DRAWN BY -
1
Main Bar CHECKED
GF -
10mm@6"c/c BY
+2'-0" REVISION
NO. DATE
Stair Detail (GF to 1F)
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

11'-9"

9" 22
2F
21
+25'-0"
20
19
18
17
16 Distribution Bar
5'-6"
15 10mm@8"c/c CLIENT PRIVATE
14
13 RADIANT
12 CONSTRUCTION
CONSTRUCTION
3'-7"
Main Bar 1F Landing ISSUED DATE 02/12/2022
10mm@6"c/c
+19'-6" HM 2022-26
Rise = 6"
Run = 9" PROJECT THREE STOREY
11'-9" Waist Slab Thickness = 5" RESIDENTIAL RC
Landing Slab Thickness = 4" BUILDING

11 LOCATION MANDALAY
1F Landing
10
+19'-6"
9 SHEET NO. S- 36
8
3'-2" 5" 7 STAIR DETAIL
TITLE
6" 6 (1F TO 2F)
5
5'-6"
Distribution Bar 4 SCALE AS SHOWN
10mm@8"c/c 3 DESIGNED
-
2 BY
1 DRAWN BY -
Main Bar 1F
10mm@6"c/c CHECKED
-
+14'-0" BY

9" REVISION
NO. DATE
Stair Detail (1F to 2F)
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

11'-9"

1'-6" 20
RF
19
+35'-0"
18
17
16
15
5' 14 Distribution Bar
13 10mm@8"c/c
CLIENT PRIVATE
12
11 RADIANT
3'-7" CONSTRUCTION
2F Landing CONSTRUCTION
Main Bar
10mm@6"c/c +30'-0" ISSUED DATE 02/12/2022
HM 2022-26
Rise = 6"
Run = 9" PROJECT THREE STOREY
11'-9" Waist Slab Thickness = 5" RESIDENTIAL RC
Landing Slab Thickness = 4" BUILDING

LOCATION MANDALAY
10
2F Landing
9 SHEET NO. S- 37
+30'-0"
8
7 STAIR DETAIL
TITLE
3'-2" 5" 6 (2F TO RF)
6" 5
5' 4 SCALE AS SHOWN
Distribution Bar 3 DESIGNED
10mm@8"c/c -
2 BY
1 DRAWN BY -
Main Bar 2F
CHECKED
10mm@6"c/c -
+25'-0" BY

1'-6" REVISION
NO. DATE
Stair Detail (2F to RF)
fc ' = 2,500 psi fy(main bar) = 58,000 psi fy(confinement bar) = 40,000 psi

Upper Floor Level


-

CLIENT PRIVATE

10mm Main Bar Dowel Bar


for Brick Layer RADIANT
CONSTRUCTION
CONSTRUCTION

ISSUED DATE 02/12/2022


6.5mm@6"c/c 11'-0" height for 1F to 2F
Tie Bar HM 2022-26
10'-0" heightfor 2F to RF
3'-0" height for RF to R THREE STOREY
PROJECT
RESIDENTIAL RC
BUILDING

6"x6" Stiffener Column LOCATION MANDALAY

SHEET NO. S- 38
6"

4" Thk: Floor Slab TITLE STIFFENER COLUMN


min: 6"
Lower Floor Level 6"
10mm Main Bar SCALE AS SHOWN
-
DESIGNED
-
BY

6.5mm@6"c/c DRAWN BY -
12"x12" Floor Beam Tie Bar
CHECKED
Stiffener Column Elevation Stiffener Column Section -
BY
REVISION
NO. DATE