SPECIFICATION

Specification No.
FOR SURFACE PREPARATION B224-000-79-41-PLS-01
AND PROTECTIVE COATING Rev. 6
HRRL PAGE 18 OF 49

TABLE- 2: PAINT MATERIALS (Contd.)

DESCRIPTION F-7 F-8 F-9 (primer) F-11 F-12


Technical name High build coal Self priming Inorganic zinc Heat Heat
tar epoxy type surface silicate resistant resistant
coating. tolerant high Coating synthetic silicone
build epoxy medium Aluminium
coating based two Paint suitable
(complete rust pack up to 540°C
control Aluminium dry temp.
Coating) Paint suitable
up to 250°C
dry temp.

Type & Two pack Two pack A two pack air Heat Single pack
composition polyamide cured epoxy resin drying self resistant silicone resin
epoxy resin based suitable curing solvent synthetic based
blended with pigmented and based medium medium with
coal tar medium, capable of inorganic zinc based two Aluminium
suitably adhering to silicate pack flakes.
pigmented manually coating with Aluminium
prepared minimum 80% paint suitable
surface and old zinc content up to 250°C.
coating. on dry film.
The final cure
of the dry film
shall pass the
MEK rub test
as per ASTM
D4752.
Volume Solids % 62 75 57 35 18
Minimum.
DFT per coat in
100-125 100-125 65-75 15-20 15-20
Theoretical
covering capacity 5.2-6.5 6.0-7.2 8-9 10-12 8-10
in M2/coat/ litre
Weight per liter in
1.40±0.03 1.41±0.03 2.3±0.03 0.95±0.03 1.00±0.03
Kg/litre
Touch dry at 30oC
(maximum), hrs 4 3 0.5 3 0.5
Hard dry at 30oC
(maximum), hrs 48 24 12 12 24

Full cure 30oC (for


immersion /high
5 days 5 days NA NA NA
temperature
service)

Format No. 8-00-0001-F1 Rev. 0 Copyright EIL All rights reserved