Professional Documents
Culture Documents
IOM Ducted Split DCH YAH 60
IOM Ducted Split DCH YAH 60
IOM Ducted Split DCH YAH 60
7.5 to 25 TR - (R410a)
1
YORK STELLAR Commercial Ducted split series
2
YORK STELLAR Commercial Ducted split series
GENERAL
YORK® Stellar commercial ducted slpit units have single condensing
units designed for outdoor installation on a rooftop or steel
structure.The units are completely assembled on a rigid base frame.
All piping, refrigerant charge, and electrical wiring is factory installed
and tested and the indoor unit YAH ceiling-mounted air handling units
are terminal points of central air-conditioning systems. The conditioned
air can be delivered to locations across various distances via specially
designed ducts. The units are especially suitable for the air-
conditioning of commercial buildings and industry applications.
units require electric power, duct connections and drain piping
connections at the point of installation.
SAFETY CONSIDERATIONS
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal Observe all precautions in the literature, on labels and tags
injury. accompanying the equipment whenever working on air conditioning
equipment. Be sure to follow all other safety precautions that apply.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION. Wear safety glasses and work gloves, and follow all safety codes. Use
a quenching cloth and have a fire extinguisher available for all brazing
DANGER indicates an imminently hazardous situation, which, if not operations.
avoided, will result in death or serious injury.
INSPECTION
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury. As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the.extent of the damage
CAUTION indicates a potentially hazardous situation, which, if not should be noted on the carrier’s freight bill. A separate request for
avoided may result in minor or moderate injury. It is also used to alert inspection by the carrier’s agent should be made in writing.
against unsafe practices and hazards involving only property damage.
RENEWAL PARTS
Refer to YORK® USER’S MAINTENANCE and SERVICE
INFORMATION MANUAL.
It is strongly suggested that only genuine YORK® Spare Parts are
used to ensure long life, product and operator safety and efficient
working of the unit.
REFRIGERANT R-410a
R-410a refrigerant is highly efficient heat transfer capability and
environment friendly having zero Ozone Depletion Potentail (ODP).
This product is coming with full refrigerant charge from the factory.
Refrigerant charge must be checked before startup to assure design
performance
PERFORMANCE TESTING
Initial break‐in period is required to achieve specification performance,
the break‐in conditions duration shall be either 75 hours at ambient
conditions (≥60°F) or 14Hr 16Hr at 125°F/82.35°F for outdoor
conditions with indoor conditions 80°F/72°F inside the test chamber.
No testing shall commence unit the specified break‐in period is
completed.
3
YORK STELLAR Commercial Ducted split series
D C H 190 C02 2 A 1 1 SP
Power Supply
1 = 230 V /3 Ph / 60 Hz
2 = 380 V /3 Ph / 60 Hz
3 = 460 V /3 Ph / 60 Hz
4 = 380-415 V /3 Ph / 50 Hz
4
YORK STELLAR Commercial Ducted split series
Indoor unit
YAH 12 B 4 0 0 A 0 H C X L 1 D N2
0: Default
0: Default
0: Default Filter Type
0 = G1 (Nylon)
A = G1 (Aluminum Mesh)
5
YORK STELLAR Commercial Ducted split series
LIMITATIONS
INSTALLATION These units must be installed in accordance with the applicable
Read these instructions before continuing this appliance installation. national and local safety codes.(Refer to Unit Application Data table 1).
This is an outdoor combination heating and cooling unit. The installer
must assure that these instructions are made available to the If components are to be added to a unit to meet local codes, they are
consumer and with instructions to retain them for future reference. to be installed at the dealer’s and/or the customer’s expense. Size of
unit for proposed installation should be based on heat loss/ heat gain.
230V/3ph/60Hz 180-253
Voltage Variation (min/max) 400V/3ph/60Hz 342-418
460V/3ph/60Hz 414-506
Ambient Air Temperature (min/max) °F 50/125 (32/130 with Low Ambient Option)
CLEARANCES
All units require certain clearances for proper operation and service.
Installer must make provisions for adequate ventilation air in
accordance with applicable provisions of the local building codes.
Refer to Dimensions and Clearances Page15.
6
YORK STELLAR Commercial Ducted split series
DCH150 DCH190-300
7
YORK STELLAR Commercial Ducted split series
DCH090,100,120 A DCH090,100,120 A
Figure 2 : Typical riging for outdoor DSU units Figure 3: Loading Points for outdoor DSU units
8
YORK STELLAR Commercial Ducted split series
DUCTWORK
The connecting between the return air duct and the external filter
frame and that between the air outlet flange and the air delivery duct
must be flexible. The hard connection between the unit and the air
outlet flange must be prohibited. During the installation, the air duct
should be provided with a support for its exclusive use and its weight
should not be carried by the unit, avoiding applying any extra load to
the unit.
The hoisting equipment should be equipped with a shock absorber of
good performance, preventing the unit from the production of
resonance and the increasing of low-frequency noise. It is suggested
that the shock absorber be installed at the side near the unit. The
connecting length of the air duct should not be greater than that
defined by the remained pressure in the unit. Moreover, the air duct is
not allowed to bear any load and should be connected to the unit.
The ceiling suspension unit can only be installed in the place where FILTERS
burning is not to be triggered.
The nylon screen filter of 21mm in thickness is provided with the unit,
which can filter dirt such as dust, soot,pollen and other foreign
CONDENSATE DRAIN substances. Filters must always be installed ahead of the evaporator
coil and must be kept clean or replaced with same size and type. Dirty
1.The unit should be installed horizontally in order to ensure free water filters will reduce the capacity of the unit and will result in frosted coils
drainage and a normal operation or safety shutdown
2.There should not be any foreign substance piled up in the water
drain tray; and all foreign matters should be removed from the tray. SERVICE ACCESS
Only if the water drain path is guaranteed to be unobstructed can the
unit be started up. The following removable panels provide access to all serviceable
3.The condensed water discharge duct must be installed with an components:
external water seal device.
•Compressor compartment
•Main control box
THERM OSTAT
The room thermostat should be located on an inside wall
approximately 56 inches above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or appliances.
Follow manufacturer’s instructions enclosed with thermostat for
general installation procedure. A minimum of seven color coded
insulated wires (#18 AWG) should be used to connect thermostat to
unit.
If any of the wire supplied with the unit must be replaced, replacement
wire must be of the type shown on the wiring diagram and the same
minimum gauge as the replaced wire.
9
YORK STELLAR Commercial Ducted split series
6.For the belt-driven unit, check the tension of the belt, which should
Electrical line must be sized properly to carry the load. Use copper be in accordance with the following figure (Belt Tension Indicating
conductors only. Each unit must be wired with a separate branch Drawing).
circuit fed directly from the meter panel and properly fused. 7.Check whether the rough filter has been installed in place and
ensure that there is no construction debrisor foreign substances
Emergency stop button should be field installed as per wiring diagram. attached to it.
The activator should be red in colour with a yellow outline background,
and should be easily accessible. The device should be self latching
type and contacts must be of positive opening operation, certified to
EN60947 - 5 – 1
10
YORK STELLAR Commercial Ducted split series
Belt Adjustment
1.Before the starting and operation of your unit, check the tension of
the belt.
2.After one-week operation, the belt will be expanded slightly. In this
case, readjust the tensile force applied to the belt and make it comply
with the specifications listed in the belt Tension Indicator.
3.After 30-day operation of the unit, check the tension of the belt again.
4.After one-quarter operation of the unit, make a complete inspection.
Mechanical Inspection
When contacting the air, the grease used to lubricate the bearing will
suffer from oxidation or even deterioration.
If the oxidized lubricating grease is applied to, the bearing of the motor
will be damaged soon.
stands by since it is delivered from/assembled in the factory or before
starts operation is too long, it will depend on how long the unit has Storage Time
been unused and the climate conditions
to decide whether or not take the following measures:
1.Rotate the fan wheel manually once per month at least.
2.After 15 minutes from the unit starts operating, check whether the
bearing runs normally. If the lubricating grease appears white color, fill
into some new grease: open the bearing and remove the used grease,
then,clean the bearing with petrol and dry it; next, fill into new
lubricating grease (bearing grease, taking the lithium as the main
ingredient) Fill into the grease up to the level of 1/3 height of the If the motor is lubricated just before it operates, a more effective
bearing housing from outside. lubricating effect can be obtained.
3.Check the temperature rise of the bearing, which should be less than
40 .
4.If the unit has been unused for a long time or it is under an adverse
weather conditions, the condensed water will result in the rusting of
bearings. In this case, it is required to replace it with a new bearing.
5.Reassemble the bearing, ensuring that the conical socket has been
tighten and is within the specified margin tolerance. Measure the
temperature of the bearing after 15-minute trail operation, which
should not be greater than the ambient temperature.
MOTOR
It is possible to store the rotation equipment for a certain period of time.
Even if the storage time and condition meet the specifications, a series
of electrical and mechanical checks are still necessary.For the motor of
7.5KW or above, it should be equipped with a voltage dropping starter,
avoiding the overstarting-current.
STORAGE CONDITIONS
The motor should be stored in a dry environment, in which if the
humidity exceeds 90%, the motor insulation device will be damaged
soon; when the humidity is up to 100%, the insulation device will lose
its function completely.
11
YORK STELLAR Commercial Ducted split series
Note:This is an example of wiring diagram with shown indoor unit control inside condensing control panel
12
YORK STELLAR Commercial Ducted split series
13
YORK STELLAR Commercial Ducted split series
PRODUCT DATA
Condensing Unit Model DCH090A DCH100A DCH120A DCH150 DCH190 DCH220 DCH250 DCH300 DCM180 DCM240 DCM300
Air handling Unit Model YAH04B YAH05B YAH05B YAH06B YAH06B YAH08B YAH08B YAH10B YAH10B YAH12B YAH12B YAH15B YAH12B YAH15B YAH15B YAH10B YAH12B YAH12B YAH15B YAH15B
External static inWg 0.25 0.25 0.25 0.25 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.4 0.4 0.4 0.4 0.4
Nominal Air Flow CFM 2,350 2,940 2,940 3,530 3,530 4,700 4,700 5,880 5880 7060 7060 8828 7060 8828 8828 5,880 7,060 7,060 8,828 8,828
Gross Capacity @T1 Btu/hr 89,175 94,285 100,397 105,895 119,893 129,660 149,100 158,900 175,800 186,100 195,200 208,100 218,400 226,900 274,800 175,400 190,350 226,975 240,930 297,730
Net Capacity @T1 Btu/hr 86,380 90,539 96,545 100,265 114,277 122,701 142,150 151,600 165,500 176,790 185,890 195,920 209,090 214,720 262,620 167,760 183,185 219,800 230,095 286,895
Total Power Consumption* Watts 8,210 8,538 9,100 9,685 10,980 11,461 15,137 15,437 18,920 18,930 20,230 21,370 21,330 22,470 28,170 18,637 17,300 21,200 22,475 27,775
EER 10.52 10.6 10.61 10.35 10.41 10.71 9.39 9.82 8.75 9.34 9.19 9.17 9.8 9.56 9.32 9 10.58 10.36 10.23 10.32
System refrigerant charge Kg 3.1 3.3 3.0 3.2 3.6 4.0 9.7 11.7 15.0 16.4 16.2 16.3 16.4 16.4 22.2 6.4 6.5 6.8 8.0 7.8
Model DCH090A DCH100A DCH120A DCH150 DCH190 DCH220 DCH250 DCH300 DCM180 DCM240 DCM300
Quantity Nos. 2 2 2 2 2 2 2 2 2 2 2
Condenser
Motor Type 6 Pole, Class F Insulation, Totally Air Over ,IP 55, 1100 rpm
Fan & Motor
Motor size hp ( kW) 3/4 (0.55) 3/4 (0.55) 3/4 (0.55) 3/4 (0.55) 1.0 ( 0.75 ) 1.0 ( 0.75 ) 1.5 ( 1.1 ) 1.5 ( 1.1 ) 2 (1.1) 2 (1.1) 2 (1.1)
Quantity Nos. 2 2 2 2 2 2 2 2 2 2 2
Type R410a
Refrigerant
No of Circuits Nos. 1 1 1 2 2 2 2 2 2 2 2
Suction line inch 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 1 3/8 7/8 1 1/8 1 3/8
Pipe line size
Liquid line inch 1/2 1/2 5/8 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8
Dimensions Width inches (mm) 32.1 (814) 44.0 (1119) 87.2 (2215)
Weights Basic Unit lbs (Kg) 630.5 (286) 650.4 (295) 650.4 (295) 1117.7 (507) 1485 (675) 1485 (675) 1540 (700) 1650 (750) 1355.8(615) 1411(640) 1433(650)
Area ft² ( m²) 4.43 (0.41) 5.46 (0.50) 6.55 (0.60) 8.74 (0.81) 10.76 (0.99) 12.81 (1.19) 16.06 (1.49)
Quantity Nos 2 2 2 2 2 2 2
AHU Fan &
Motor Type 3-ɸ asynchronous motor, F class insulation, IP54
Motor
Motor size hp ( kW) 1.5 (1.1) 2 (1.5) 3 (2.2) 4 (3.0) 5.3 (4) 5.3 (4) 7.3 (5.5)
Quantity Nos 1 1 1 1 1 1 1
Height inches (mm) 16.4 (417) 20 (508) 20 (508) 20 (508) 28.9 (736) 28.9 (736) 28.9 (736)
Dimensions Width Inches (mm) 62.9 (1600) 59 (1500) 68.8 (1750) 88.5 (2250) 72.8 (1850) 84.6 (2150) 103.3 (2625)
Length Inches (mm) 33.8 (860) 37 (940) 37 (940) 38.5 (980) 43.3 (1100) 45.2 (1150) 46 (1170)
Weights Basic Unit lbs (Kg) 330 (150) 365 (166) 412 (187) 522 (237) 582 (264) 707 (321) 831 (377)
14
YORK STELLAR Commercial Ducted split series
15
YORK STELLAR Commercial Ducted split series
DCH150
16
YORK STELLAR Commercial Ducted split series
DCH190-300
17
YORK STELLAR Commercial Ducted split series
DCM180-300
18
YORK STELLAR Commercial Ducted split series
Airflow m3
Model A B C D E F G H J K L M N p Q S T
/h
YAH 03B 3000 860 1360 417 470 259 228 184 73 227 367 400 173 325 1220 320 381 50
YAH 04B 4000 860 1600 417 520 259 228 184 73 227 367 400 173 325 1460 320 378 50
YAH 05B 5000 940 1500 508 580 232 262 184 107 237 387 400 224 427 1360 411 463 60
YAH 06B 6000 940 1750 508 551 232 262 184 107 225 376 400 224 427 1610 411 431 60
YAH 08B 8000 980 2250 508 705 298 262 244 107 275 425 400 224 427 2110 411 460 83
19
YORK STELLAR Commercial Ducted split series
Airflow
Model A B C D E F H G J K L M N p Q S T
m3 /h
YAH
l0B 10000 1100 1850 736 690 471 404 112 / 280 430 441 346 639 1710 639 612 82
YAH
12000 1150 2150 736 680 373 404 112 294 280 430 441 314 621 2010 639 692 82
12B
YAH
15000 1170 2625 736 793 373 404 112 294 274 424 441 329 634 2485 639 687 82
15B
YAH10B YAH12/15B
20
YORK STELLAR Commercial Ducted split series
Downsize Motor 1 HP
Standard Motor 1.5 HP
Oversize Motor 2 HP
Downsize Motor 2 HP
Standard Motor 3 HP
Oversize Motor 4 HP
21
YORK STELLAR Commercial Ducted split series
Downsize Motor 3 HP
Standard Motor 4 HP
Oversize Motor 5.5 HP
Downsize Motor 3 HP
Standard Motor 4 HP
Oversize Motor 5.5 HP
Downsize Motor 3 HP
Standard Motor 4 HP
Oversize Motor 5.5 HP
22
YORK STELLAR Commercial Ducted split series
Downsize Motor 4 HP
Standard Motor 5.5 HP
Oversize Motor 7.5 HP
23
YORK STELLAR Commercial Ducted split series
24
YORK STELLAR Commercial Ducted split series
ELECTRICAL DATA
COMPRESSOR Downsize Standard Oversize Minimum Minimum Minimum
COND.MOT
MODEL VOLTAGE QTY QTY Blower Blower Blower Circuit MOP (0) Circuit MOP (1) Circuit MOP (2)
RLA LRA OR
Motor (0) Motor (1) Motor (2) Amperes (0) Amperes (1) Amperes (2)
25
YORK STELLAR Commercial Ducted split series
Maximum Maximum
Minimum Maximum Minimum Minimum
Condenser Downsize Standard Oversize Blower Fuse / Fuse /
Model Voltage Compressor Qty Qty Circuit Fuse / Breaker Circuit Circuit
Motor Blower Motor (0) Blower Motor (1) Motor (2) Breaker Size Breaker
Amperes (0) Size (0) Amperes (1) Amperes (2)
(1) Size (2)
RLA Each LRA Each FLA Each FLA FLA FLA Amps Amp Amps Amp Amps Amp
YAH-10B 380/3/60 14.4 110 2 2.85 2 4.50 6.60 7.74 42.6 50.0 44.7 50.0 45.8 50.0
DCM 180
YAH-12B 380/3/60 14.4 110 2 2.85 2 4.50 6.60 7.74 42.6 50.0 44.7 50.0 45.8 50.0
YAH-12B 380/3/60 19.2 155 2 2.85 2 4.50 6.60 7.74 53.4 60.0 55.5 65.0 56.6 65.0
DCM 240
YAH-15B 380/3/60 19.2 155 2 2.85 2 6.60 7.74 10.67 55.5 65.0 56.6 65.0 59.6 65.0
DCM 300 YAH-15B 380/3/60 26.4 168 2 2.85 2 6.60 7.74 10.67 71.7 80.0 72.8 80.0 75.8 90.0
Power cable conductor ampacity based on copper material with 75C Insulation minimum , Correction factors of (Ambient Temp , Current carrying
conductors , voltage drop calculation) to be considered as per NEC or equivalent international standard.
26
YORK STELLAR Commercial Ducted split series
TERMINOLOGY
SAFETY
The internal section of the unit adjacent to moving parts and electrical
This section of the IOM covers Safety Aspects applicable to the York parts or devices is considered as the ‘danger zone’. Prior to gaining
Stellar Commercial Ducted Split Air Cooled Unit. Adherence to the
access to these parts, it is necessary to acquire the proper tools to
instructions detailed hereunder, will ensure the safety of the operators,
deactivate the safety devices. The operators are responsible for
prevent damage to the equipment and prevent accidents.
transport, installation, start up, service and maintenance, including
cleaning and trouble shooting.
OPERATIONAL SAFETY
York Stellar Commercial Ducted Split Air Cooled Unit in conformance
to the highest standards of operational as well as operator safety.
Nevertheless, hazards may occur if the units are used for purposes
other than the designed use(s), Units are operated by untrained staff
and / or Units are not operated in conformance with general standards
prevalent in the industry.
The manufacturer will also not be responsible for any damages to the
equipment, to property or to personnel.
27
YORK STELLAR Commercial Ducted split series
STAFF TRAINING
ADHERENCE OF THE USER/OPERATOR TO
THE WARNINGS AND OTHER INSTRUCTIONS The unit should be started up and serviced (routine and corrective
maintenance) by authorized and trained staff only. This staff must be
Clear signs are placed at appropriate locations on the unit showing: informed about possible hazards regarding:
• Electrical connections
• Piping connections
• Startup
28
YORK STELLAR Commercial Ducted split series
OPERATION
SOUND POWER RATINGS
A sound power level is a measure of the total noise radiated by the machine in all directions. It is a property of the machine and is essentially independent
of the measuring environment. Sound power levels are useful to equipment manufacturers, buyers, installers, and users for :
• Calculating the sound pressure level from a machine at a given distance in a given environment.
• Comparing the noise output from different machines
• Setting specifications for the maximum permitted noise from a machine
• Comparing machines before and after modifications to reduce the noise
Sound power is measured in watts or picowatts, and sound power levels are traditionally given in decibels (dB re 1pW).
Refer table 8 for sound power level of outdoor unit.
-12
Outdoor Unit Sound Power, dB (10 ) Watts
Model Rating Octave Band Centerline Frequency (Hz)
dB (A) 63 125 250 500 1000 2000 4000 8000
DCH090A 80.5 82 74 72 74 72 73 76 71
DCH100A 82.7 85 76 74 74 74 75 79 73
DCH120A 84.5 86 78 77 77 77 76 80 74
DCH150 82.7 82 70 70 72 75 76 78 73
DCH190 88.1 84 82 82 79 79 82 78 87
DCH220 88.1 84 82 82 79 79 82 78 87
DCH250 86 79 79 78 78 77 80 80 85
DCH300 88.3 80 79 79 78 78 81 80 87
DCM 180 86 87 83 81 80 78 77 80 77
DCM 240 84 85 78 78 77 77 76 79 74
DCM 300 84 85 78 78 77 77 76 79 74
Indoor Unit Sound Power, dB (10-12) Watts
Model Rating Octave Band Centerline Frequency (Hz)
dB (A) 63 125 250 500 1000 2000 4000 8000
YAH03 91.0 88 83 84 79 78 75 71 67
YAH04 89.0 84 81 83 80 78 75 71 66
YAH05 81.0 66 71 77 73 74 73 70 62
YAH06 84.0 71 74 79 75 76 75 72 65
YAH08 85.0 76 77 79 76 78 74 71 63
YAH10 87.0 81 85 78 74 70 68 64 56
Table 8 : Sound Power Levels
INTERMITTENT BLOWER
With the room thermostat fan switch set to “AUTO” and the system
switch set to either the “AUTO” or “HEAT” settings, the blower is
energized whenever a cooling or heating operation is requested. The
blower is energized after any specified delay associated with the
SEQUENCE OF OPERATIONS OVERVIEW operation. When energized, the indoor blower has a minimum run time
of 30 seconds. Additionally, the indoor blower has a delay of 10
For these units, the thermostat makes a circuit between “R” and “Y1” seconds between operations.
for the first stage of cooling. The call is passed to the unit control board
(UCB), which then determines whether the requested operation is NO OUTDOOR AIR OPTIONS
available and, if so, which components to energize. For electric heat When the thermostat calls for the first stage of cooling, the low voltage
units, the UCB passes the call to the electric heater. control circuit from R to YI & G is completed. For first stage of cooling,
compressor 1, condenser fan motor 1 & 2 are energized. After
In both cases, when the “W1” call is sensed, the indoor air blower is completing the specified fan on delay for cooling, the UCB will
energized following a specified heating delay. If at any time a call for energize the blower Motor.When the thermostat calls for 2nd stage of
both heating and cooling are present, the heating operation will be cooling low voltage control circuit from R to Y2 is completed,
performed. If operating, the cooling system is halted as with a compressor 2 is energized, provided it has not been locked out.
completion of a call for cooling. Heating always takes priority.
29
YORK STELLAR Commercial Ducted split series
For third stage of cooling, the low voltage control circuit from”R” to “Y3” EVAPORATOR COIL FREEZE STAT
is completed. Compressor # 3, if there is an initial call for 3 stages of
cooling, the UCB will delay energizing compressor 2 & 3 by 30 During cooling operation, if a freezestat opens, the UCB will de-
seconds each. Once the thermostat has been satisfied it will de‐ energize the associated compressor, initiate the ASCD, and
energize Y1, Y2 & Y3. condenser fans will stop. If the call for cooling is still present at the
conclusion of the ASCD, the UCB will reenergize the halted
When the thermostat calls for fourth stage of cooling, the low voltage compressor. Should a freezestat open three times within two hours of
control circuit from “R” to “Y4” is completed, compressor #4 is operation, the UCB will lock out the associated compressor , flags an
energized. If there is an initial call for 4 stages of cooling, the UCB will alarm on LCD (see Table 8) and condenser fan will stop.
delay energizing compressor # 2, 3 & 4 by 30 seconds each. Once the
thermostat has been satisfied it will de‐energize Y1, Y2, and Y3 & Y4. ELECTRIC HEATING SEQUENCE OF
OPERATIONS
If the compressors have satisfied their minimum run times, the
compressors and condenser fans are de‐energized. Otherwise, the The following sequence describes the operation of the electric heat
unit operates each cooling system until the minimum run times for the section. Two--stage heating (Heaters MUST use a two stage
compressors have been completed. Upon the final compressor de‐ thermostat):
energizing, the blower is stopped following the elapse of the fan off a) Upon a call for first-stage heat by the thermostat, the heater
delay for cooling. contactor will be energized. After completing the specified
fan on delay for heating, the UCB will energize the blower
To be available, a compressor must not be locked out due to a high or motor. If the second stage of heat is required, second
low pressure switch or freezestat trip and the anti-short cycle delay heater contactor will be energized. After completing the
(ASCD) must have elapsed. specified fan on delay for heating, the UCB will energize
the blower motor.
b) The thermostat will cycle the electric heat to satisfy the
COOLING OPERATION ERRORS heating requirements of the conditioned space.
Each cooling system is monitored for operation outside of the intended HEATING OPERATION ERRORS
parameters. Errors are handled as described below. All system errors
override minimum run times for compressors. TEMPERATURE LIMIT
If the UCB senses zero volts from the high temperature limit, the
indoor blower motor is immediately energized. This limit is monitored
HIGH PRESSURE LIMIT SWITCH regardless of unit operation status, i.e. the limit is monitored at all
times. If the temperature limit opens three times within one hour, it will
During cooling operation, if a high pressure limit switch opens, the
lock on the indoor blower motor and a flash code is initiated (See
UCB will de-energize the associated compressor, initiate the ASCD
Table 9).
(anti short cycle delay), and condenser fan will stop. If the call for
cooling is still present at the conclusion of the ASCD, the UCB will re- SAFETY CONTROLS
energize the compressor again . The unit control board monitors the temperature limit switch of electric
A high pressure switch open three times within two hours of operation, heat units. The control circuit includes the following safety controls:
the UCB will lock out the associated compressor , flags an alarm on
LCD (see Table 8). and condenser fan will stop. Temperature Limit Switch (AUTO)
to manually reset the lockout condition , navigate to Reset.LO in LCD , This control is located inside the heater compartment and is set to
change the value from NO to YES open at 120°F. It resets automatically. The limit switch operates when
30
YORK STELLAR Commercial Ducted split series
31
YORK STELLAR Commercial Ducted split series
CHARGING SYSTEM
EVACUATION
1.As all units are shipped with a full charge and service valves to hold
When all refrigeration connections have been made a leak test and the charge, they must be fully charged with the refrigerant which they
evacuation should be performed on the unit by licensed refrigeration
were designed. When a charging a unit you must use a clean and dry
mechanic. A small portable vacuum pump should be used to evacuate
refrigerant.
the system (evaporator coil, drier, lines, etc) after condensing unit has
been installed in the system. Do not use the compressor as a vacuum 2.Open all discharge, suction and liquid line valves. Connect the
pump. Use a vacuum pump that is built for refrigeration evacuation
charging hose to the charge port of the liquid line valve. Be sure to
equipment.
purge the hose of all air. Move the valve off its back seat and add liquid
refrigerant until the unit pressure equalizes the refrigerant cylinder
If the system is properly evacuated, using a good vacuum pump which
pressure. Close the charge of the liquid line valve. Move charging
can pull down into the 50 to 100 micron range, the non condensables
hose to the back seating port of the suction valve and purge hose of all
are eliminated before the system is ever started. A good vacuum air. Start compressor and continue to add refrigerant gas until the liquid
pump with electronic gauge is desirable and highly recommended for
line sight glass is clear and a minimum of 8 degree F sub cooling is
this procedure. The gauge may be showing 50 microns at the pump,
obtained leaving the condenser sub cooling section.
but if a large system is being evacuated, the vacuum level at the end
of the system may be too high. The poorer the vacuum, the poorer the 3.After the system has been completely charged and the compressor
results.
is operating, the system should once again be checked for leaks to
make sure that none have occurred during the handling of equipment.
This situation should not be further complicated by using too small a
connecting line between the vacuum pump and the system as it will
4.The moisture indicator should be checked and filter drier core
create a high pressure drop which will greatly reduce the efficiency of
changed as an added precaution.
the vacuum pump. To use the vacuum pump most efficiently a triple
evacuation method should be used. This involves pulling out the START UP (COOLING)
system down to 100 microns and holding it for a period of three to four
hours and then breaking the vacuum with a dry refrigerant if it is a After installation has been completed:
small system or with nitrogen if it is a larger system. The vacuum is 1.Check the electrical supply voltage being supplied. Be sure that it is
pulled and broken a second time exactly as describe above. Finally a the same as listed on the unit nameplate.
vacuum is pulled down to 50 microns, held for a period of three to four 2.Set the room thermostat to the on position.
hours and broken with the type of refrigerant to be used in the system. 3.Turn unit electrical power on.
At this point the system can be charged, and you can be assured that 4.Set the room thermostat fan switch to on.
virtually all of the non condensable s have been removed. Triple 5.Check indoor blower rotation.
evacuation works on the principle of pulling out a high percentage of • If blower rotation is in the wrong direction. Refer to phasing
the non condensables and/or water on each pull down. As an section in general information section.
example, suppose 90% of the non condensable are removed on the • Check blower drive belt tension.
first pull down. This would leave 10% of 1 % of the original non • Check bearing lubrication. If it requires lubrication, grease
condensable in the system. In addition, breaking the vacuum with dry it.
nitrogen or dry refrigerant has a diluting effect on moisture which has 6.Check the unit supply air (CFM).
been vaporized. 7.Measure evaporator fan motor amp draw.
8.Set the room thermostat fan switch to off.
Besides being sure that the connecting line between the vacuum 9.Turn unit electrical power off.
pump and the refrigeration system is sufficiently large enough to
prevent pressure drop, there are three precautions to be kept in mind: OPERATING INSTRUCTIONS
1.Turn unit electrical power on.
First: an ordinary compound gauge is worthless on a good vacuum
2.Set the room thermostat setting to lower than the room temperature.
pump. The error in the gauge is greater than the amount of vacuum
3.First stage compressors will energize after the built in time delay (five
being measured. There are several very good electronic gauges in the
minutes).
market which are rugged and have a dial on which microns can be
4.The 2nd, 3rd and 4th stage of the thermostat will energize the
read very similar to the reading of an ammeter.
respective compressors (if needed).
Second: be sure that the system, including the factory piping of the POST START CHECK LIST
unit, is good and tight and has been checked for the lightest leak. A
good vacuum pump will stay ahead of a small leak and is simply 1.Verify proper system pressures for both circuits.
means pulling air and moisture in one and pushing it out the other. 2.Measure the temperature drop across the evaporator coil.
3.Measure the system Amperage draw across all legs of 3 phase
Third: it should also be remembered that water trapped under layers of power wires.
oil will stay there regardless of the vacuum pulled and will not be 4. Measure the condenser fan amp draw.
dislodged until the circulating refrigerant takes the oil up and releases
the water. If any leaks are found, make repairs. A halide torch, soap SHUT DOWN
bubbles or electronic detector may be used for leak detection.
1.Set the thermostat to highest temperature setting.
2.Turn off the electrical power to the unit.
32
YORK STELLAR Commercial Ducted split series
8.If 24 volts is not present at the “FAN” terminal, check for 24 volts
from the room thermostat. If 24 volts are not present from the room
thermostat, check for the following:
a) Proper operation of the room thermostat (contact between
R and G with the fan switch in the ON position and in the
AUTO position during operation calls),
b) Proper wiring between the room thermostat and the UCB,
Troubleshooting of components may require opening the electrical and
control box with the power connected to the unit. Use extreme care c) Loose wiring from the room thermostat to the UCB.
when working with live circuits! Check the unit nameplate for the
correct line voltage and set the voltmeter to the correct range before 9.If 24 volts is present at the room thermostat but not at the UCB,
making any connections with line terminals. check for proper wiring between the thermostat and the UCB, i.e. that
the thermostat G terminal is connected to the G terminal of the UCB,
and for loose wiring.
10.If the thermostat and UCB are properly wired, replace the UCB.
On calls for cooling, the supply air blower motor is operating but
compressor # 1 is not (the room thermostat fan switch is in the
“AUTO” position).
1.If compressor # 1 does not energize on a call for cooling, check for
line voltage at the compressor contactor 1, and that the contactor is
When not necessary, shut off all electric power to the unit prior to any pulled in. Check for loose wiring between the contactor and the
of the following maintenance procedures so as to prevent personal compressor.
injury
2.If compressor contactor 1 is pulled in and voltage is supplied, lightly
* On calls for cooling, if the compressors are operating but the supply touch the compressor housing. If it is hot, the compressor may be off
air blower motor does not energize after a short delay (the room on inherent protection. Cancel any calls for cooling and wait for the
thermostat fan switch is in the “AUTO” position). internal overload to reset. Test again when cool.
1.Turn the thermostat fan switch to the ON position. If the supply air 3.If compressor contactor 1 is not pulled in, check for 24 volts at the
blower motor does not energize, go to Step 3. coil. If 24 volts are present and contactor is not pulled in, replace the
contactor.
2.If the blower motor runs with the fan switch in the ON position but will
not run after the first compressor has energized when the fan switch is 4.Failing the above, if voltage is supplied at compressor contactor 1, it
in the AUTO position, check the room thermostat for contact between is pulled in, and the compressor still does not operate, replace the
R and G in the AUTO position during calls for cooling. compressor.
3.If the supply air blower motor does not energize when the fan switch 5.If 24 volts is not present at compressor contactor 1, check for 24
is set to ON, check that line voltage is being supplied to the blower volts at the UCB terminal, C1. If 24 volts is present, check for loose
contactor, and that the contactor is pulled in. Check for loose wiring wiring between C1 and the compressor contactor.
between the contactor and the supply air blower motor.
6.If 24 volts is not present at the C1 terminal, check for 24 volts from
4.If blower contactor is pulled in and voltage is supplied to contactor, the room thermostat at the UCB Y1 terminal. If 24 volts is not present
lightly touch the supply air blower motor housing. If it is hot, the motor from the room thermostat, check for the following:
may be off on internal protection. Cancel any thermostat calls and set • Proper wiring between the room thermostat and the UCB,
the fan switch to AUTO. Wait for the internal overload to reset. Test i.e. Y1 to Y1, Y2 to Y2,Y3 to Y3 & Y4 to Y4.
again when cool.
• Loose wiring from the room thermostat to the UCB.
5.If blower contactor is not pulled in, check for 24 volts at the contactor
coil. If 24 volts are present but it is not pulled in, replace the contactor
33
YORK STELLAR Commercial Ducted split series
9.If 24 volts is present at the UCB Y1 terminal and none of the NOTE:While the above step will reset any lock outs, compressor # 1
switches are open and the compressor is not locked out, the UCB may will be held off for the ASCD, and compressor # 2 may be held off for a
have the compressor in an ASCD. The ASCD should time out within 5 portion of the ASCD. See the next step.
minutes.
9.If 24 volts is present at the UCB Y2 terminal and none of the
10.If none of the above corrected the error, test the integrity of the switches are open and the compressor is not locked out, the UCB may
UCB. Disconnect the C1 terminal wire and jumper it to the Y1 terminal. have the compressor in an ASCD. The ASCD should time out within 5
DO NOT jump the Y1 to C1 terminals. If the compressor engages, the minutes.
UCB has faulted.
10.The UCB can be programmed to lock out compressor operation
11.If none of the above correct the error, replace the UCB. during free cooling and in low ambient conditions. These options are
not enabled by default. Local distributors can test the UCB for this
*On calls for the second stage of cooling, the supply air blower motor programming.
and compressor # 1 are operating but compressor # 2 is not (the room
thermostat fan switch is in the “AUTO” position). 11.If none of the above corrected the error, test the integrity of the
UCB. Disconnect the C2 terminal wire and jumper it to the Y2 terminal.
1.Compressor # 2 will not energize simultaneously with compressor #1 DO NOT jump the Y2 to C2 terminals. If the compressor engages, the
if a call for both stages of cooling is received. The UCB delays UCB has faulted.
compressor # 2 by 30 seconds to prevent a power surge. If after the
delay compressor # 2 does not energize on a second stage call for 12.If none of the above correct the error, replace the UCB.
cooling, check for line voltage at the compressor contactor 2, and that *On a call for cooling, the supply air blower motor and compressor # 2
the contactor is pulled in. Check for loose wiring between the contactor are operating but compressor # 1 is not (the room thermostat fan
and the compressor. switch is in the “AUTO” position).
2.If compressor contactor 2 is pulled in and voltage is supplied, lightly 1.Compressor # 3 will not energize simultaneously with compressor 1
touch the compressor housing. If it is hot, the compressor may be off & 2, if a call for third stage of cooling is received. The UCB delays
on inherent protection. Cancel any calls for cooling and wait for the compressor # 3 by 30 seconds to prevent a power surge, if after the
internal overload to reset.Test again when cool. delay compressor # 3 doesn’t energize on rd. stage call for cooling,
check for line voltage at the compressor contactor 3, and that the
3.If compressor contactor 2 is not pulled in, check for 24 volts at the contactor is pulled in. Check for loose wiring between the contactor
compressor contactor coil. If 24 volts is present and compressor and the compressor.
contactor is not pulled in, replace the contactor.
2.If the compressor contactor 3 is pulled in and voltage is supplied,
4.Failing the above, if voltage is supplied at compressor. lightly touch the compressor housing. If it is hot, the compressor may
be off on inherent protection. Cancel any calls for cooling and wait for
5.Contactor 2, and it is pulled in, and the compressor still does not the internal overload to reset. Test again when cool.
operate, replace the compressor. 5. If 24 volts is not present at
compressor contactor 2, check for 24 volts at the UCB terminal, C2. If 3.If the compressor contactor 3 is not pulled in, check for 24 volts at
24 volts are present, check for loose wiring between C2 and the the compressor contactor coil. If 24 volt is present and compressor
compressor contactor. contactor is not pulled in, replace the contactor.
6.If 24 volts is not present at the C2 terminal, check for 24 volts from
the room thermostat at the UCB Y2 terminal. If 24 volts is not present
from the room thermostat, check for the following :
• 24 volts at the thermostat Y2 terminal.
• Proper wiring between the room thermostat and the UCB,
i.e.Y1 to Y1, Y2 to Y2.
• Loose wiring from the room thermostat to the UCB.
34
YORK STELLAR Commercial Ducted split series
4.Failing the above, if voltage is supplied at the compressor contactor 1.Compressor # 4 will not energize simultaneously with compressor
3, and it is pulled in, and the compressor still doesn’t operate, replace 1,2 & 3 if a call for fourth stage of cooling is received. The UCB delays
the compressor. compressor # 4 by 30 seconds to prevent a power surge, if after the
delay compressor # 4 doesn’t energize on 4th stage call for cooling,
5.If 24 volts is not present at compressor contactor 3, check for 24 check for line voltage at the compressor contactor 4, and that the
volts at the UCB terminal, C3. If 24 volts are present, check for loose contactor is pulled in. Check for loose wiring between the contactor
wiring between C3 and the compressor contactor. and the compressor.
6.If 24 volts is not present at the C3 terminal, check for 24 volts from 2.If the compressor contactor 4 is pulled in and voltage is supplied,
the room thermostat at the UCB Y3 terminal. If 24 volts is not present lightly touch the compressor housing. If it is hot, the compressor may
from the room thermostat, check for the following: be off on inherent protection. Cancel any calls for cooling and wait for
•24 volts at the thermostat Y3 terminal. the internal overload to reset. Test again when cool.
•Proper wiring between the room thermostat and the UCB.
•Loose wiring from the room thermostat to the UCB. 3.If the compressor contactor 4 is not pulled in, check for 24 volts at
the compressor contactor coil. If 24 volt is present and compressor
7.If 24 volts is present at the UCB Y3 terminal, the compressor may be contactor is not pulled in, replace the contactor.
out due to an open high pressure switch, low pressure switch or
freezestat. Check for 24 volts at the 4.Failing the above, if voltage is supplied at the compressor contactor
HPS3, LPS3 and FS3 terminals of the UCB. If a switch has opened, 4, and it is pulled in, and the compressor still doesn’t operate, replace
there should be a voltage potential between the the compressor.
UCB terminals e.g., if LPS3 has opened, there will be 24 volts of
potential between the LPS3 terminals. 5.If 24 volts is not present at compressor contactor 4, check for 24
volts at the UCB terminal, C4. if 24 Volts are present, check for loose
8.If 24 Volts is present at the UCB Y3 terminal and none of the wiring between C4 and the compressor contactor.
protection switches have opened, the UCB may have locked out the
compressor for repeat trips.If the compressor is locked out, remove 6.If 24 volts is not present at the C4 terminal, check for 24 volts from
any call for cooling at the thermostat or by disconnection the the room thermostat at the UCB Y4 terminal. If 24 volts is not present
thermostat wiring at the Y3 UCB terminal. This will reset any from the room thermostat, check for the following:
installation, compressor lock outs. •24 volts at the thermostat Y4 terminal.
•Proper wiring between the room thermostat and the UCB.
NOTE: While the above steps will reset any lockouts, compressor # 1 •Loose Wiring from the room is thermostat to the UCB.
& 2 will be held off for the ASCD, and the compressor # 3 may be held
off for a portion of the ASCD, See the next step. 7.If 24 Volts is present at the UCB Y4 terminal, the compressor may
be out due to an open high pressure switch, low pressure switch or
9.If 24 Volts is present at the UCB Y3 terminal and none of the freezestat. Check for 24 volts at the HPS4, LPS4 and FS4 terminals of
switches are open and the compressor is not locked out, the UCB may the UCB. If a switch has opened, there should be a voltage potential
have the compressor in an ASCD. Check the LED for an indication of between the UCB terminals e.g., if LPS4 has opened, there will be 24
an ASCD cycle. The ASCD should time out within 5 Min. volts of potential between the LPS4 terminals.
10.The UCB can be programmed to lock out compressor operation 8.If 24 volts is present at the UCB Y4 terminal and none of the
during free cooling and in low ambient conditions. These options are protection switches have opened, the UCB may have locked out the
not enabled by default. Local distributors can test the UCB for this compressor for repeat trips. If the compressor is locked out, remove
programming. any call for cooling at the thermostat or by disconnection the
thermostat wiring at the Y4 UCB terminal. This will reset any
11.If none of the above corrected the error, test the integrity of the installation, compressor lock outs.
UCB, disconnect the C3 terminal wire and the jumper it to the Y3
terminal, DO NOT jump the Y3 to C3 terminals. If the compressor NOTE: While the above steps will reset any lockouts, compressor # 1,
engages, the UCB has faulted. 2 & 3 will be held off for the ASCD, and the compressor # 4 may be
held off for a portion of the ASCD.
12.If none of the above correct the error, replace the UCB.
9.If 24 volts is present at the UCB Y4 terminal and none of the
On Call for fourth stage of cooling (50 TR models only) the supply air switches are open and the compressor is not locked out, the UCB may
blower motor & Compressor # 1, 2 & 3 are operating but compressor # have the compressor in an ASCD. The ASCD should time out within 5
4 is not ( the room thermostat fan switch is in the AUTO position). minutes.
35
YORK STELLAR Commercial Ducted split series
10.The UCB Can be programmed to lock out compressor operation NOTE : While the above step will reset any lock outs, compressor # 2
during free cooling and in low ambient conditions. These options are will be held off for the ASCD, and compressor # 1 may be held off for a
not enabled by default. Local distributors can test the UCB for this portion of the ASCD. See the next step
programming.
10.If 24 volts is present at the UCB Y1 terminal and none of the
11.If none of the above corrected the error, test the integrity of the switches are open and the compressor is not locked out, the UCB may
UCB, disconnect the C4 terminal wire and the jumper it to the Y4 have the compressor in an ASCD. The ASCD should time out within 5
terminal, DO NOT jump the Y4 to C4 terminals. If the compressor minutes.
engages, the UCB has faulted.
11.If 24 volts is present at the UCB Y1 terminal and the compressor is
12.If none of the above correct the error, replace the UCB. not out due to a protective switch trip, repeat trip lock out, or ASCD,
the economizer terminals of the UCB may be improperly wired. Check
On a call for cooling, the supply air blower motor and compressor # 2 for 24 volts at the Y1 “OUT” terminal of the UCB. If 24 volts is present,
are operating but compressor # 1 is not (the room thermostat fan trace the wiring from Y1 “OUT” for incorrect wiring. If 24 volts is not
switch is in the “AUTO” position). present at the Y1 “OUT” terminal, the UCB must be replaced.
1.Compressor # 2 is energized in place of compressor # 1 when 12.If none of the above corrected the error, test the integrity of the
compressor # 1 is unavailable for cooling calls. Check the UCB for UCB. Disconnect the C1 terminal wire and jumper it to the Y1 terminal.
alarms indicating that compressor # 1 is locked out. DO NOT jump the Y1 to C1 terminals. If the compressor engages, has
faulted.
2.Check for line voltage at the compressor contactor 1, and that the
contactor is pulled in. Check for loose wiring between the contactor 13.If none of the above correct the error, replace the UCB.
and the compressor.
C- Y-
Cooling Compressor Contactor
3.If compressor contactor 1 is pulled in and voltage is supplied at the Terminal Terminal
contactor 1, lightly touch the compressor housing. If it is hot, the Stage 1 1 1 C1 Y1
compressor may be off on inherent protection. Cancel any calls for
cooling and wait for the internal overload to reset. Test again when Stage 2 2 2 C2 Y2
cool. Stage 3 3 3 C3 Y3
Stage 4 4 4 C4 Y4
4.If compressor contactor 1 is not pulled in, check for 24 volts at the
Table 9: Terminals
coil. If 24 volts is present and compressor contactor 1 is not pulled in,
replace the contactor.
Similarly, if compressor of any stage is not operating, follow the same
procedure as listed above with respective compressor, contactors and
5.Failing the above, if voltage is supplied at compressor contactor 1,
terminal numbers (Refer table 9).
and it is pulled in, and the compressor still does not operate, replace
the compressor.
7.If 24 volts is not present at the C1 terminal, check for 24 volts from
the room thermostat at the UCB Y1 terminal. If 24 volts are not present
at the UCB Y1 terminal, the UCB may have faulted. Check for 24 volts
at the Y1 ECON terminal. If 24 volts is not present at Y1 “ECON”, the
UCB has faulted. The UCB should de-energize all compressors on a
loss of call for the first stage of cooling, i.e. a loss if 24 volts at the Y1
terminal.
8.If 24 volts are present at the UCB Y1 terminal, the compressor may
be out due to an open high pressure switch, low pressure switch, or
freezestat. Check for 24 volts at the HPS1, LPS1, and FS1 terminals
of the UCB. If a switch has opened, threshold be a voltage potential
between the UCB terminals, e.g. if LPS1 has opened, there will be a
24 volt potential between the LPS1 terminals.
36
YORK STELLAR Commercial Ducted split series
UNIT ALARMS C1 Locked out due to Low pressure 3 LPS1 trips within 1 hours
C2 Locked out due to Low pressure 3 LPS2 trips within 1 hours
Various Alarms are utilized by the unit control board (UCB) to aid in C3 Locked out due to Low pressure 3 LPS3 trips within 1 hours
troubleshooting . This is to verify that the UCB is functioning correctly. C4 Locked out due to Low pressure 3 LPS4 trips within 1 hours
C1 shut down due to high pressure HPS1 trip
Current alarms are monitored on the UCB LCD. Checking alarms and C2 shut down due to high pressure HPS2 trip
solve the error will start unit again after anti short cycle delay.you can C3 shut down due to high pressure HPS3 trip
Reset Lockouts manually , navigate to ResetLo in LCD change value
C4 shut down due to high pressure HPS4 trip
from NO to YES. The UCB will cycle through the last five (5) alarms,
C1 shut down due to Low pressure LPS1 trip
most recent to oldest.
In some cases, it may be necessary to “zero” the ASCD for the C2 shut down due to Low pressure LPS2 trip
compressors in order to perform troubleshooting. C3 shut down due to Low pressure LPS3 trip
C4 shut down due to Low pressure LPS4 trip
Note : The mentioned alarms are applicable for both Simplicity® C1 shut down due to coil freeze EC1 trip
control boards. However, the Simplicity 2nd board will represent data C2 shut down due to coil freeze EC2 trip
for circuits / compressors 3 & 4 only C3 shut down due to coil freeze EC3 trip
C4 shut down due to coil freeze EC4 trip
Alarm How it happens 3 EC1 trips within 2 hours
C1 Locked out due to Coil freeze
Unit shut down due to smoke SD input loses 24 VAC Evap_coil T < Evap_coil Tsp
Supply fan shut down due to OL Fan OL trip 3 EC2 trips within 2 hours
C2 Locked out due to Coil freeze
Unit locked out due to supply fan OL 3 fan ovr trips within 2 hours Evap_coil T < Evap_coil Tsp
C1 Locked out due to high pressure 3 HPS1 trips within 2 hours 3 EC3 trips within 2 hours
C3 Locked out due to Coil freeze
C2 Locked out due to high pressure 3 HPS2 trips within 2 hours Evap_coil T < Evap_coil Tsp
C3 Locked out due to high pressure 3 HPS3 trips within 2 hours 3 EC4 trips within 2 hours
C4 Locked out due to Coil freeze
C4 Locked out due to high pressure 3 HPS4 trips within 2 hours Evap_coil T < Evap_coil Tsp
After you apply power to your Rooftop Unit (RTU), a start-up POWERING THE UNIT
countdown begins on the Unit Control Board (UCB) LCD.
When the controller is ready, the screen will be blank if no When you apply power to the unit (the C and 24V terminals),
faults are present. Use the joystick and the two push buttons the UCB begins a start-up sequence.
below the LCD, to navigate through the menus (Figure 1).
The LCD scrolls the text Johnson Controls on the top line and
JCI on the bottom line (Figure 3).
37
YORK STELLAR Commercial Ducted split series
After the start-up sequence finishes (90 - 120 seconds), the display shows the current operating status. I.E. Idle, startup delay, cooling... on both lines if
no alarm is active. The red Fault LED stops flashing and turns off. The joystick, "ENTER", and Cancel buttons are operational.
Your equipment configuration determines which menus appear in the Commissioning view. Use the joystick to move between the menu options. Press
"ENTER" to select an option. table of all menus, sub-menus and properties.
The following information provides a step-by-step demonstration on how to navigate the basic status menu and how to change basic configuration
settings. The basic navigation steps outlined in this short demonstration applies to most menus within the Simplicity SE control.
Step 2 The first item under the Step 3 - When the cursor is on the “DVent-Mode” Step 4 - To exit out of the
status menu is “DVent-Mode”. This hit “ENTER” to view the status of this mode. In “DVent-Mode status screen
is the demand ventilation mode. this case a CO2 sensor is not installed, thus push “Cancel”. The screen
Demand Ventilation or DVent is disabled. returns to that shown below.
38
YORK STELLAR Commercial Ducted split series
Step 5- By pushing the joystick down, the cursor toggles to OprST if sensors are located.
(Operating Space Temp).
When the "Cancel" button is pressed multiple times to exit each menu level and the screen returns to the first "Status, Alarms"
display the next demonstration can begin.
Step 1- Beginning at the status/alarm screen toggle the joystick down three times. This accesses Step 2- Once commission appears next to
the “Commissioning “ screen. In this menu section various settings can be changed. the cursor, press “ENTER” to begin
Please see the menu table that follows this demonstrationfor a list of parameters that can be modified viewing parameters.
Step 3- After “ENTER” Step 4- After toggling the Step 5- At the “Clg” screen Step 6- By toggling down
is pressed the various joystick down two times once “ENTER” is pushed the twice the screen reaches
parameter sections “Clg” appears. This allows status indicates if cooling the “ClgOcc-SP” screen
appear, such as: HVAC items, such as lead-lag is engaged/disengaged or “Cooling Occupied Set
zone, Indoor Fan, Clg, and OCC/UNOCC and lead-lag is engaged/ Point”.
Htg, others. cooling set points, to be disengaged.
changed.
Step 7- After pressing Step 8- In order to change set points push the
“ENTER” at toggle switch left or right. Note: The screen
the “ClgOCC-SP” screen the flashes . left decreases the value , right
space temperature set point increases. In this demonstration the ClgOCC
appears. NOTE: set point is changed from 72F to 95F.
Only applies to units
controlled by a space sensor.
39
YORK STELLAR Commercial Ducted split series
Inputs
Outputs
40
YORK STELLAR Commercial Ducted split series
MAINTENANCE
Outdoor unit:
The Stellar Air Cooled Condensing Units are premium quality machines with very low maintenance requirements.
Compressors used in Units are of Scroll type and are charged with the correct amount of refrigerant and lubricating oil.
Unless there is a leak in the system, no topping up is generally required.
Every 6 months
In addition to the maintenance done every three months :
• The condenser coils should be cleaned by spraying water over it at low pressure or with a brush while ensuring that the fins are not damaged.
• Check all electrical connections and tighten them if required.
• Clean all accessible electrical panels of dirt and dust. Before cleaning the control panels , ENSURE that the electrical power to the unit is
switched off.
Every 12 months
In addition to the maintenance done every six months :
Indoor unit:
Filter Part
When cleaning the filter, beat the accumulated foreign matters off it. If required, clean it with the warm water filled with liquid detergent, dry it and
reassemble it back to the filter frame.The filter can be removed from the unit only by dissemble the cover plate in the side or on the bottom of the
filter frame.
Operating
1.Remove the filter with dust collected in the metal frame away from the slip fitting carefully. Be careful not
to dirty other parts.
2.Shake the filter and wash it in the soap solution of 40 .
3.Replace the filter if it has been damaged.
4.For the installation of a new filter, operate according to steps above in reverse order.
Fan Part
1.Before repair the internal part of the fan, switch off the control switch.
2.Check the V-belt and its tension regularly. If it is found that the tensile force applied to the belt is not enough, retighten it. For correct tension data, refer
to the Belt Tension Indicator.
3.Check the alignment of motor, fan V-belt and pulley.
4.Check whether the interior flexible device is fixed firmly.
5.Check whether the motor can operate freely.
6.Inspect the maintenance instruction provided by the motor supplier.
7.Check whether the fan can operate unobstructedly.
8.Clean the fan blade regularly.
41
YORK STELLAR Commercial Ducted split series
Fan Bearing
The double suction forward fan used in the YAH unit is designed with the sealed bearing, the normal service life of which can be up to 75,000 working
hours at least.During the constantly improvement and development, we reserve the right of changing the technical specification, size without notice in
advance.
Motor
Any maintenance should be carried out in comply according to the motor instructions. This manual is just one part of the technical information provided.
Replacement of Motor
Replace the motor from one side of the unit or after the top or side frame panel is removed.
Points for Attention during Maintenance
1.The full-time technicians should be assigned for the maintenance of the air conditioner unit and also should be responsible for the daily inspection and
regular repairing. It is necessary to formulate a strict job responsibility system and lay down operating rules to strength the regular maintenance and
service repair
2.Clean the inside of the unit regularly.
3.Check the electrical equipment of the unit regularly.
4.Lubricate the parts needing lubricating with grease additionally after 6-month to one-year operation of the
unit.
5.Before the unit is repaired, switch off the power and set a warning sign to avoid risk due to mis-operation.
Failure Analysis
High-level Noise
Check whether there is a flexible connection between the air return and delivery duct; whether the lifting device is supplied with a shock absorber;
whether the wind speed at the air outlet is over high and whether there is any part loose
Belt Breaking
In this case, check whether the belt is under overtension;whether there is dis-alignment between the fan and the motor belt pulley or the belt quality is
poor..
42
YORK STELLAR Commercial Ducted split series
Proper refrigerant pipe selection and design is crucial for efficient and
reliable operation of the refrigeration system. It is also important to
INSTALLATION RECOMMENDATIONS keep liquid refrigerant/oil slugs from entering the compressor and for
assuring oil return. Over-sizing the piping reduces the refrigerant
DX LINE SIZING RECOMMENDATIONS pressure drop, but can inhibit oil return and adds unnecessary first
The piping must conform to the local codes. For the best pipe sizing cost. On the other hand, under-sizing the piping increases the
and design practices, refer to either the information in this manual or refrigerant pressure drop, which affects system performance and
the ASHRAE Refrigeration Handbook. These contain refrigerant line lowers the efficiency.
sizing for full and minimum capacities and other pertinent engineering
information for a wide application range. For best results, use long radius elbows (short radius elbows have
The tables listed below are presented for the 35, 45 and 55°F higher pressure drops) for everything except oil traps. Also, clean
saturated suction temperatures, which are typical for these systems. copper tubing for refrigeration and air conditioning application should
The tables are included at the end of this manual in the Appendix. be used throughout. Provisions must be made for piping contraction
and expansion of 3/4” per 100’ of pipe.
APPENDIX
SUCTION LINE
Table 12 – Table 12: Additional Refregirant Charge
Table 12: Capacity reduction precentage according to extra piping Table 12 shows suction line sizing recommendations, which are
length typically based on 2°F (Nominal 4.5 PSI for R-410a) loss.
Table 12: Additional oil charge according to extra piping length As was illustrated in SECTION 2 - EQUIPMENT SELECTION, a
Table 13 – Fitting Losses in Equivalent Feet of Pipe typical 2°F drop in suction pressure can reduce the system capacity by
(Screwed, Welding Flanged and Brazed Connections) about 3%. Therefore, it is good practice to design the suction piping
Table 14 – Special Fitting Losses in Equivalent Feet of Pipe with no more than a 2°F line loss at full load.
(ASHRAE).
Table 15 – Valve Losses in Equivalent Feet of Pipe (ASHRAE).
Table 16 – HGBP Line Sizing for R-410a
Keeping the condensing unit and air-handler as close
together as possible is recommended. This is important for
assuring oil return and compressor reliability.
It is also important that the total equivalent feet of piping be 150 feet or
less (Always review IOM for maximum limitations).
Oil and refrigerant, which condenses in the line during off periods,
must drain into the compressor and will be boiled off by the
compressor heater. This prevents oil and liquid refrigerant slugging of
the compressors.
43
YORK STELLAR Commercial Ducted split series
44
YORK STELLAR Commercial Ducted split series
45
YORK STELLAR Commercial Ducted split series
Pipe Sizing , % capacity reduction, additional oil and refrigerant charge for DSUs
Note:
• SOC/Cir (oz) - system oil charge available in the compressor initially. Value is per compressor
• AOR/Cir (oz) - additional oil required per circuit
• System Ref Charge/Cir (lbm) - refrigerant charge per circuit
• Add. Charge/ (per cir.) lbm - additional refrigerant charge per circuit
• N/A - if the value for AOR is "N/A", that means no additional oil is required for that length of piping
• %Cap Red- precentage capacity reduction per piping length.
46
YORK STELLAR Commercial Ducted split series
BASIC TIPS FOR SUCCESSFUL DESIGNS •If the DX coil is above the ACCU, the Suction Piping must rise above
the top of the Coil to form an inverted trap. See Figure 10.
The following tips apply to all piping examples shows in
Figure 12 HOT GAS BYPASS
•Assure hot gas piping enters the distributor (or auxiliary side
Liquid Line Piping, Liquid Line Solenoid Valve, and TXV’s
connection-ASC) tap on each coil from the top.
•The total equivalent feet of piping should be 150 feet or less.
•Hot gas piping should always slope to drain into the coils.
•Slope piping toward coils for oil return during the off cycle.
•Hot gas piping should be designed to not allow oil and refrigerant to
be trapped during the off cycle. Trapping liquid and oil creates the
•Use long radius elbows to reduce pressure drop.
danger of a liquid slug when the hot gas is energized.
•Use only one liquid line solenoid valve per ACCU Refrigerant System.
•Size hot gas to approx. 100% capacity of the minimum stage of
cooling.
•Size TXV’s according to individual coil capacity. Minimum capacity
must not exceed 30% of valves rated capacity.
•Activate hot gas whenever any compressor is running. This may
involve rewiring the HGBP to be in parallel with the LLSV, providing full
•Mount TXV bulb on clean pipe at 4 or 8 o’clock position with 2 copper
time HGBP.
straps on the outlet of the respective coil. Insulate the TXV bulb.
•Ιnsulate the hot gas bypass line.
•The equalizing line for each TXV must enter the top of the suction
pipe.
•Always install check valves at the ASC side connection when multiple
branch circuits are utilized.
•See Table 11 for the Maximum Vertical Height (ft.) for the DX Coil
above the ACCU. CONTROLS
DX COILS • Avoid, when possible, running the ACCU when in economizer mode.
•DX coils in a system should always be configured for full face If operating the ACCU in economizer mode, hot gas must be installed
operation. Otherwise, TXV control and liquid slugging will damage to assure a minimum load.
compressors.
•Assure distributor nozzles are properly sized for the coil capacity.
•Slope suction piping toward the compressors for oil return and to
assure that liquid condensing in the suction line drains into the
compressors and is boiled off by the heaters. Do not allow the suction
line to create a liquid and oil trap between the coil and the
compressors.
•Use long radius elbows to reduce pressure drop except for oil traps.
•Use double risers whenever refrigerant velocity falls below 1000 FPM.
•Use intermediate oil traps on suction risers greater than 20 ft, located
midway on the riser.
47
YORK STELLAR Commercial Ducted split series
Note: Hot gas bypass and it’s accessories, check valve , liquid line solenoid valve , sight glass moisture equalizer are all
optional, suction gas risers are for ilustration only in case velocity<1000 FPM.
Figure 12: PIPING WHEN ACCU IS LESS THAN 20 FT. ABOVE THE DX COIL
48
YORK STELLAR Commercial Ducted split series
This illustration figure 13 shows one refrigerant circuit when the ACCU In lieu of double suction risers, the vertical suction riser can be
is at the same level as the AHU interlaced DX coil. Again the horizontal downsized for proper oil entrainment at minimum reduced load,
suction line must be sloped a minimum of ½" per 10 ft. toward the providing the overall suction line pressure drop doesn’t exceed a
compressors for oil flow. nominal 2°F.
Note: Hot gass bypass and it’s accessories, check valve , liquid line solenoid valve , sight glass moisture indicator are all
optional.
Figure 13: PIPING WHEN ACCU IS AT THE SAME LEVEL AS THE DX COIL
49
YORK STELLAR Commercial Ducted split series
This illustration figure 14 shows one refrigerant circuit when the ACCU In lieu of double suction risers, the vertical suction riser can be
is lower than the AHU interlaced DX coil. Again the horizontal suction downsized for proper oil entrainment at minimum reduced load,
line must be sloped a minimum of ½" per 10 ft. toward the providing the overall suction line pressure drop doesn’t exceed a
compressors for oil flow. nominal 2°F
Note: Hot gass bypass and it’s accessories, check valve , liquid line solenoid valve , sight glass moisture indicator are all
optional.
50
YORK STELLAR Commercial Ducted split series
Table 13: FITTING LOSSES IN EQUIVALENT FEET OF PIPE (SCREWED, WELDED, FLANGED AND BRAZED CONNECTIONS)
51
YORK STELLAR Commercial Ducted split series
Table 16: HGBP LINE SIZING FOR R-22, R-407C AND R-410A REFRIGERANTS
52
YORK STELLAR Commercial Ducted split series
Application Considerations:
The lines should be installed so that they will not obstruct service access to the indoor coil, air handling system or
filter. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the
tubing. Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equipment to
the structure. Never solder vapor and liquid lines together. They can be taped together for convenience and support
purposes, but they must be completely insulated from each other. Use long radius elbows wherever possible. Insulate
all vapor lines with a minimum of 1/2 inch of foam rubber. Liquid lines that will be exposed to direct sunlight or high
ambient temperatures such as an attic must also be insulated.
53
YORK STELLAR Commercial Ducted split series
Whether you’re at home, in a car, or in an office or workplace, chances are there’s a Johnson
Controls product or service nearby, helping to make your environment more comfortable, safe and
sustainable.
Johnson Controls creates smart environments that improve the places where people spend most of
their time – their homes, workplaces and vehicles. We anticipate consumer needs, and then
integrate technologies, products and services to make life better and easier.
For Johnson Controls, sustain ability matters at every level and through our products, service
operations and community involvement, we promote the efficient use of resources to benefit all
people and the world. Our triple bottom line of sustain ability that is, economic prosperity,
environmental stewardship and social responsibility impacts each and every aspect of our business.
York products are now a premier brand manufactured by Johnson Controls. The acquisition of York,
gives us a unique insight into designing HVAC products that match your exact requirements. We
provide solutions for today's most critical concerns - energy efficiency, refrigerant alternatives and
indoor air quality.
Johnson Controls has a wide range of York products for residential, light commercial and
commercial applications. Our offering includes package & split air conditioners and heat pumps. In
addition, Johnson Controls offers chillers, air handling units, ventilation equipment and controls for
larger projects.
Our advanced technology is leading the way in developing efficient and environment friendly
solutions for your homes, offices and places of leisure.
We reserve the right to change in part or in whole the specifications without prior notice.
54