IOM Ducted Split DCH YAH 60

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 54

Installation, Operation & Maintenance Manual - 60Hz

Commercial Ducted Split

7.5 to 25 TR - (R410a)

Include YORK Simplicity Controller”

1
YORK STELLAR Commercial Ducted split series

ELECTRIC HEATING SEQUENCE OF OPERATIONS


Table of Contents
................................................................... 30
GENERAL...........................................................3
HEATING OPERATION ERRORS ...................... 30
SAFETY CONSIDERATIONS ............................... 3 SAFETY CONTROLS ......................................... 31
INSPECTION................................................... 3 COMPRESSOR PROTECTION............................. 31
RENEWAL PARTS............................................ 3 NUISANCE TRIP PROTECTION AND STRIKES.... 31
REFRIGERANT R-410a ..................................... 3 ALARMS ...................................................... 31
PERFORMANCE TESTING ................................ 3 RESET .......................................................... 31
PIN NUMBER GUIDELINES............................... 4 REFRIGERANT PIPING CONNECTIONS ............ 31
INSTALLATION ...................................................6 EVACUATION ............................................... 32
CHARGING SYSTEM ...................................... 32
LIMITATIONS ................................................. 6
START UP (COOLING) .................................... 32
LOCATION ..................................................... 6
OPERATING INSTRUCTIONS .......................... 32
CLEARANCES.................................................. 6
POST START CHECK LIST ............................... 32
RIGGING AND HANDLING ............................... 6
DUCTWORK ................................................... 9 SHUT DOWN................................................ 32
CONDENSATE DRAIN ...................................... 9 TROUBLE SHOOTING........................................ 33
COMPRESSORS .............................................. 9 COOLING TROUBLE SHOOTING GUIDE............... 33
FILTERS.......................................................... 9 UNIT ALARMS .............................................. 37
SERVICE ACCESS............................................. 9 UNDERSTANDING LOCAL LCD ....................... 37
THERMOSTAT ................................................ 9 MAINTENANCE ................................................ 41
POWER AND CONTROL W IRING..................... 9
INSTALLATION RECOMMENDATIONS ................ 43
PHASING ..................................................... 10
CHECKING SUPPLY AIR CFM .......................... 10 DX LINE SIZING RECOMMENDATIONS............ 43
TYPICAL WIRING DIAGRAM........................... 12 APPENDIX.................................................... 43
PRODUCT DATA ........................................... 13 ACTUAL PIPING ROUTING VERSUS ORIGINAL
DIMENSIONS & CLEARANCES ........................ 15 PIPING DESIGN ............................................ 43
FAN PERFORMANCE DATA............................ 21 SUCTION LINE .............................................. 43
ELECTRICAL DATA ........................................ 25 LIQUID LINES ............................................... 45
SAFETY ......................................................... 27 BASIC TIPS FOR SUCCESSFUL DESIGNS ........... 47
TERMINOLOGY ............................................ 27 DX COILS ..................................................... 47
OPERATIONAL SAFETY ................................... 27 SUCTION LINE PIPING ................................... 47
OPERATION AND USE OF THE UNIT IN HOT GAS BYPASS ......................................... 47
CONFORMANCE WITH GENERAL STANDARDS AND CONTROLS................................................... 47
PROVISIONS................................................. 27 EXAMPLES OF ACCU-DX COIL PIPING
ADHERENCE OF THE USER/OPERATOR TO THE ARRANGEMENTS ......................................... 48
WARNINGS AND OTHER INSTRUCTIONS ........ 28
STAFF TRAINING............................................ 28
USE OF THE UNIT ......................................... 28
OPERATION ..................................................... 29
SOUND POWER RATINGS ............................... 29
VOLT FREE CONTACT.................................... 29
SEQUENCE OF OPERATIONS OVERVIEW ........ 29
COOLING SEQUENCE OF OPERATION ............ 29
COOLING OPERATION ERRORS......................... 30
HIGH PRESSURE LIMIT SWITCH..................... 30
LOW PRESSURE LIMIT SWITCH...................... 30
EVAPORATOR COIL FREEZE STAT................... 30

2
YORK STELLAR Commercial Ducted split series

GENERAL
YORK® Stellar commercial ducted slpit units have single condensing
units designed for outdoor installation on a rooftop or steel
structure.The units are completely assembled on a rigid base frame.
All piping, refrigerant charge, and electrical wiring is factory installed
and tested and the indoor unit YAH ceiling-mounted air handling units
are terminal points of central air-conditioning systems. The conditioned
air can be delivered to locations across various distances via specially
designed ducts. The units are especially suitable for the air-
conditioning of commercial buildings and industry applications.
units require electric power, duct connections and drain piping
connections at the point of installation.

SAFETY CONSIDERATIONS
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal Observe all precautions in the literature, on labels and tags
injury. accompanying the equipment whenever working on air conditioning
equipment. Be sure to follow all other safety precautions that apply.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION. Wear safety glasses and work gloves, and follow all safety codes. Use
a quenching cloth and have a fire extinguisher available for all brazing
DANGER indicates an imminently hazardous situation, which, if not operations.
avoided, will result in death or serious injury.
INSPECTION
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury. As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the.extent of the damage
CAUTION indicates a potentially hazardous situation, which, if not should be noted on the carrier’s freight bill. A separate request for
avoided may result in minor or moderate injury. It is also used to alert inspection by the carrier’s agent should be made in writing.
against unsafe practices and hazards involving only property damage.
RENEWAL PARTS
Refer to YORK® USER’S MAINTENANCE and SERVICE
INFORMATION MANUAL.
It is strongly suggested that only genuine YORK® Spare Parts are
used to ensure long life, product and operator safety and efficient
working of the unit.

REFRIGERANT R-410a
R-410a refrigerant is highly efficient heat transfer capability and
environment friendly having zero Ozone Depletion Potentail (ODP).
This product is coming with full refrigerant charge from the factory.
Refrigerant charge must be checked before startup to assure design
performance

PERFORMANCE TESTING
Initial break‐in period is required to achieve specification performance,
the break‐in conditions duration shall be either 75 hours at ambient
conditions (≥60°F) or 14Hr 16Hr at 125°F/82.35°F for outdoor
conditions with indoor conditions 80°F/72°F inside the test chamber.
No testing shall commence unit the specified break‐in period is
completed.

3
YORK STELLAR Commercial Ducted split series

PIN NUMBER GUIDELINES


Outdoor unit

D C H 190 C02 2 A 1 1 SP

Series Name SP= for ducted split outdoor units


D = Condensing Unit
Product Generation
1 = First generation
Product Identifier
C = Energy Efficient
(SASO Complaint) Field Installed Options
1 = No Option Installed

H = High Ambient Operation


M = Medium efficiency

Nominal Cooling Capacity Factory Installed Options


090 A = 7.5 Tons A = No Option Installed
100 A = 8.3 Tons B = Heresite coating on condensing coil
120 A = 10 Tons Techno coating on condensing coil
150 = 12.5 Tons (for DCM and DCHA)
190= 16 Tons E =Cu / Cu condenser coil
220 = 18 Tons E-Coating on condenser coil
250 = 21 Tons (for DCM and DCHA)
300 = 25 Tons G = Disconnect Switch
180 = 15 Tons (Medium efficiency) H = Phase Monitor
240 = 20 Tons (Medium efficiency) I = BMS [Building Management System]
300 = 25 Tons (Medium efficiency) N = Low Ambient Kit
X = Volt Free Contact
Mode Y = Pressure Guages
C02 = Cooling only (R-410a)

Power Supply
1 = 230 V /3 Ph / 60 Hz
2 = 380 V /3 Ph / 60 Hz
3 = 460 V /3 Ph / 60 Hz
4 = 380-415 V /3 Ph / 50 Hz

4
YORK STELLAR Commercial Ducted split series

Indoor unit

YAH 12 B 4 0 0 A 0 H C X L 1 D N2

Series Names N1=1circuit (for DCHA) OD unit


YAH-York ceiling mounted N2=2circuits (for DCM and DCH) OD unit
Air handling unit
D: Design Serial

External Static Pressure


1: Rated ESP
A~Z: ESP range table

L: Left pipe connection


Nominal Air flow R: Right pipe connection
04 = 4,000 m3/h (2350 cfm)
05 = 5,000 m3/h (2940 cfm) Air Condition
06 = 6,000 m3/h (3530 cfm) X: Fresh Air
08 = 8,000 m3/h (4700 cfm) 0: Return Air
10 = 10,000 m3/h (5885 cfm)

12 = 12,000 m3/h (7060 cfm) Power Supply
15 = 15,000 m3/h (8828 cfm) C: 380 415V-3Ph-50Hz
D: 460V-3Ph-60Hz
Fan Drive Type E: 380V-3Ph-60Hz
B = Belt drive F: 230V-3Ph-60Hz

Cooling coil 0: Common fin


4 = 4 row heat exchanger coil H: Hydrophilic fin

0: Default
0: Default
0: Default Filter Type
0 = G1 (Nylon)
A = G1 (Aluminum Mesh)

Figure 1: Typical unit configuration for outdoor units

5
YORK STELLAR Commercial Ducted split series

LIMITATIONS
INSTALLATION These units must be installed in accordance with the applicable
Read these instructions before continuing this appliance installation. national and local safety codes.(Refer to Unit Application Data table 1).
This is an outdoor combination heating and cooling unit. The installer
must assure that these instructions are made available to the If components are to be added to a unit to meet local codes, they are
consumer and with instructions to retain them for future reference. to be installed at the dealer’s and/or the customer’s expense. Size of
unit for proposed installation should be based on heat loss/ heat gain.

230V/3ph/60Hz 180-253
Voltage Variation (min/max) 400V/3ph/60Hz 342-418
460V/3ph/60Hz 414-506
Ambient Air Temperature (min/max) °F 50/125 (32/130 with Low Ambient Option)

Table 1: Unit Application Data

LOCATION RIGGING AND HANDLING


Use the following guidelines to select a suitable location for these Exercise care when moving the unit. Do not remove any packaging
units: until the unit is near the place of installation. Rig the unit by attaching
chain or cable slings to the round lifting holes provided in the base
Outdoor unit: rails. Spreaders, whose length exceeds the largest dimension across
1. Unit are designed for outdoor installation only. the unit, MUST BE USED.
2. Condenser coils must have an unlimited supply of air.
3. Where a choice of location is possible, position the unit on either Refer to Figure 2, 3, Units may also be moved or lifted with a forklift,
north or east side of building. from the side only, provided that an accessory skid is used.
4. For ground level installation, use a level concrete slab. The length
and width should be at least 6 inches greater than the unit base rails. Units may be moved or lifted with a forklift. Slotted openings in the
Do not tie slab to the building foundation. base rails are provided for this purpose.(for outdoor unit).
5. Roof structures must be able to support the weight of the unit and its
options and/or accessories. Unit must be installed on a solid level roof During the erection process, be careful to prevent the unit from any
curb. damage due to improper operations,and put a corrugated sheet on the
6. Maintain level tolerance to 1/2 inch maximum across the entire place where the unit lifting rope contacts the unit, avoiding damage to
length or width of the unit. the surface of the unit due to the rope.(for indoor unit)
Indoor unit:
1.Unit should be located in such away that condensate water should
not block with in the drain pan. Check unit level and provide inclination
/slop toward the drain hole.
2.Elevate the unit for proper clearance for piping/wiring servicing
purpose.
3.Locate the unit properly on the suitable vibration absorbing pad or
other recommended gasket between frame and the unit to avoid
transmitting of the vibration to the structure & also to reduce noise
level.

CLEARANCES
All units require certain clearances for proper operation and service.
Installer must make provisions for adequate ventilation air in
accordance with applicable provisions of the local building codes.
Refer to Dimensions and Clearances Page15.

6
YORK STELLAR Commercial Ducted split series

DCH150 DCH190-300

DCM 180-300 DCM180-300

7
YORK STELLAR Commercial Ducted split series

DCH090,100,120 A DCH090,100,120 A

Figure 2 : Typical riging for outdoor DSU units Figure 3: Loading Points for outdoor DSU units

LOCATION lbs (Kgs)


MODEL Four point loading
A B C D Total
DCH090A 159 72 137 62 163 74 172 78 631 286
DCH100A 161 73 137 62 172 78 181 82 650 295
DCH120A 161 73 137 62 172 78 181 82 650 295
DCH150 262 119 284 129 260 118 310 141 1117 507
DCH190 386 175 357 162 357 162 386 175 1485 675
DCH220 386 175 357 162 357 162 386 175 1486 675
DCH250 407 185 363 165 363 165 407 185 1540 700
DCH300 451 205 374 170 374 170 451 205 1650 750
DCM180 353 160 324 147 324 147 353 160 1355 615
DCM240 375 170 331 150 331 150 375 170 1411 640
DCM300 397 180 320 145 320 145 397 180 1433 650

Table 2: Unit Weight data

8
YORK STELLAR Commercial Ducted split series

DUCTWORK
The connecting between the return air duct and the external filter
frame and that between the air outlet flange and the air delivery duct
must be flexible. The hard connection between the unit and the air
outlet flange must be prohibited. During the installation, the air duct
should be provided with a support for its exclusive use and its weight
should not be carried by the unit, avoiding applying any extra load to
the unit.
The hoisting equipment should be equipped with a shock absorber of
good performance, preventing the unit from the production of
resonance and the increasing of low-frequency noise. It is suggested
that the shock absorber be installed at the side near the unit. The
connecting length of the air duct should not be greater than that
defined by the remained pressure in the unit. Moreover, the air duct is
not allowed to bear any load and should be connected to the unit.
The ceiling suspension unit can only be installed in the place where FILTERS
burning is not to be triggered.
The nylon screen filter of 21mm in thickness is provided with the unit,
which can filter dirt such as dust, soot,pollen and other foreign
CONDENSATE DRAIN substances. Filters must always be installed ahead of the evaporator
coil and must be kept clean or replaced with same size and type. Dirty
1.The unit should be installed horizontally in order to ensure free water filters will reduce the capacity of the unit and will result in frosted coils
drainage and a normal operation or safety shutdown
2.There should not be any foreign substance piled up in the water
drain tray; and all foreign matters should be removed from the tray. SERVICE ACCESS
Only if the water drain path is guaranteed to be unobstructed can the
unit be started up. The following removable panels provide access to all serviceable
3.The condensed water discharge duct must be installed with an components:
external water seal device.
•Compressor compartment
•Main control box

Refer to the Dimensions and Clearances Figure 5, 6 for location of


these access panels.

THERM OSTAT
The room thermostat should be located on an inside wall
approximately 56 inches above the floor where it will not be subject to
drafts, sun exposure or heat from electrical fixtures or appliances.
Follow manufacturer’s instructions enclosed with thermostat for
general installation procedure. A minimum of seven color coded
insulated wires (#18 AWG) should be used to connect thermostat to
unit.

POWER AND CONTROL W IRING


COMPRESSORS
Field wiring to the unit must conform to provisions of the National
The scroll compressor used in this product is specifically designed to Electrical Code and/or local ordinances. The unit must be electrically
operate with R-410a Refrigerant and cannot be interchanged. grounded in accordance with NEC and/or local codes.
The compressor also uses a polyolester (POE oil), Mobil 3MA POE.
This oil is extremely hygroscopic, meaning it absorbs water readily. Voltage tolerances, which must be maintained at the compressor
POE oil can absorb 15 times as much water as other oils designed for terminals, during starting and running conditions, are indicated on the
HCFC and CFC refrigerants. Take allnecessary precautions to avoid unit Rating Plate and the Unit Application Data table
exposure of the oil to the atmospheres. A fused disconnect switch should be field provided based on the
Units are shipped with factory adjusted compressor mountings and tabulated rating, with a short circuit capacity of 10K or more, for the
ready for operation. unit. The switch must be separate from all other circuits. Wire entry at
knockout openings require conduit fittings to comply with local codes.
Refer to the Dimensions and Clearances Figures 5, and 6 for
installation location.

If any of the wire supplied with the unit must be replaced, replacement
wire must be of the type shown on the wiring diagram and the same
minimum gauge as the replaced wire.

9
YORK STELLAR Commercial Ducted split series

6.For the belt-driven unit, check the tension of the belt, which should
Electrical line must be sized properly to carry the load. Use copper be in accordance with the following figure (Belt Tension Indicating
conductors only. Each unit must be wired with a separate branch Drawing).
circuit fed directly from the meter panel and properly fused. 7.Check whether the rough filter has been installed in place and
ensure that there is no construction debrisor foreign substances
Emergency stop button should be field installed as per wiring diagram. attached to it.
The activator should be red in colour with a yellow outline background,
and should be easily accessible. The device should be self latching
type and contacts must be of positive opening operation, certified to
EN60947 - 5 – 1

Refer to Typical Wiring Diagram, Figure 4 and to the appropriate unit


wiring diagram for control circuit and power wiring information.

Wire Size Maximum Length (1)


18 AWG 150 feet
Table 3: Control Wire Sizes

From the unit to the thermostat and back to the unit

PHASING FAN PART


1.Switch off the master switch before carry out an internal inspection to
the fan.
2.Check whether the electrical connection device of the unit is in
consistent with all circuit diagrams.
3.Check the motor’s name plate and observe whether the rated
voltage, phase and circuit are in consistent with the power supply
recorded in field.
4.Before the fan starts operation, check first whether there is foreign
YORK Stellar units are properly phased at the factory. Check for
matter in the fan housing, then, rotate the fan blade manually and
proper compressor rotation. If the blower or compressors rotate in the
check whether there is any collision and friction observed between the
wrong direction at start up, the electrical connection to the unit is mis-
fan blades and the housing; listen whether there is abnormal noise
phased. Change the incoming line connection phasing to obtain
produced from the bearing. You can never start it till no abnormality is
proper rotation. (Scroll compressors operate in only one direction. If
found.
the scroll is drawing low amperage, has similar suction and discharge
5.After the power is switched on, start the fan first and check whether it
pressures, or producing a high noise level, the scroll is mis-
rotate in a specified direction. If not,stop the fan and change the power
phaseTable 3: Control Wire Sizes
phase sequence; then, connect it with the power supply formally.
CHECKING SUPPLY AIR CFM 6.Check the motor operating current with an ammeter, and compare
the obtained current value with the data indicated in the motor name
Check before Start up plate.
Check the YAH unit before it is started.
1.Remove the interior and exterior dust from the unit.
2.Check whether there is any component loose in the unit.
3.Check all moveable parts and observe whether they can rotate
freely.
4.Inspect all electrical connecting devices and check whether the
wiring is correct, whether the power supply can meet the requirement.
Arrange the protection devices for short-circuit, overload and phase
loss at the power lead-in side; check all earthed system.
5.Check the fin surface of the coil. If required, card it with a Coil Pipe
Comb .

10
YORK STELLAR Commercial Ducted split series

CHECK THE FAN BEARING


All belt drive fans have been equipped with the permanent leak-proof ADJUSTMENT OF BELT & BELT PULLEY
lubricated bearings. Adjustment of Smoothness:
If the unit starts operation soon after delivered from the factory, no For the belt drive unit, inspect the smoothness of the fan and motor
extra measure should be taken.If the time period during which the unit belts with a ruler, that is, points of A, B,C and D should be in the same
line; otherwise, it is needed to adjust the smoothness of the belt pulley.

Belt Adjustment
1.Before the starting and operation of your unit, check the tension of
the belt.
2.After one-week operation, the belt will be expanded slightly. In this
case, readjust the tensile force applied to the belt and make it comply
with the specifications listed in the belt Tension Indicator.
3.After 30-day operation of the unit, check the tension of the belt again.
4.After one-quarter operation of the unit, make a complete inspection.

Mechanical Inspection
When contacting the air, the grease used to lubricate the bearing will
suffer from oxidation or even deterioration.
If the oxidized lubricating grease is applied to, the bearing of the motor
will be damaged soon.
stands by since it is delivered from/assembled in the factory or before
starts operation is too long, it will depend on how long the unit has Storage Time
been unused and the climate conditions
to decide whether or not take the following measures:
1.Rotate the fan wheel manually once per month at least.
2.After 15 minutes from the unit starts operating, check whether the
bearing runs normally. If the lubricating grease appears white color, fill
into some new grease: open the bearing and remove the used grease,
then,clean the bearing with petrol and dry it; next, fill into new
lubricating grease (bearing grease, taking the lithium as the main
ingredient) Fill into the grease up to the level of 1/3 height of the If the motor is lubricated just before it operates, a more effective
bearing housing from outside. lubricating effect can be obtained.
3.Check the temperature rise of the bearing, which should be less than
40 .
4.If the unit has been unused for a long time or it is under an adverse
weather conditions, the condensed water will result in the rusting of
bearings. In this case, it is required to replace it with a new bearing.
5.Reassemble the bearing, ensuring that the conical socket has been
tighten and is within the specified margin tolerance. Measure the
temperature of the bearing after 15-minute trail operation, which
should not be greater than the ambient temperature.

MOTOR
It is possible to store the rotation equipment for a certain period of time.
Even if the storage time and condition meet the specifications, a series
of electrical and mechanical checks are still necessary.For the motor of
7.5KW or above, it should be equipped with a voltage dropping starter,
avoiding the overstarting-current.

STORAGE CONDITIONS
The motor should be stored in a dry environment, in which if the
humidity exceeds 90%, the motor insulation device will be damaged
soon; when the humidity is up to 100%, the insulation device will lose
its function completely.

11
YORK STELLAR Commercial Ducted split series

TYPICAL WIRING DIAGRAM

Note:This is an example of wiring diagram with shown indoor unit control inside condensing control panel

12
YORK STELLAR Commercial Ducted split series

Figure 4: Typical field wiring schematic

13
YORK STELLAR Commercial Ducted split series

PRODUCT DATA
Condensing Unit Model DCH090A DCH100A DCH120A DCH150 DCH190 DCH220 DCH250 DCH300 DCM180 DCM240 DCM300

Air handling Unit Model YAH04B YAH05B YAH05B YAH06B YAH06B YAH08B YAH08B YAH10B YAH10B YAH12B YAH12B YAH15B YAH12B YAH15B YAH15B YAH10B YAH12B YAH12B YAH15B YAH15B

External static inWg 0.25 0.25 0.25 0.25 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.5 0.4 0.4 0.4 0.4 0.4

Nominal Air Flow CFM 2,350 2,940 2,940 3,530 3,530 4,700 4,700 5,880 5880 7060 7060 8828 7060 8828 8828 5,880 7,060 7,060 8,828 8,828

Gross Capacity @T1 Btu/hr 89,175 94,285 100,397 105,895 119,893 129,660 149,100 158,900 175,800 186,100 195,200 208,100 218,400 226,900 274,800 175,400 190,350 226,975 240,930 297,730

Net Capacity @T1 Btu/hr 86,380 90,539 96,545 100,265 114,277 122,701 142,150 151,600 165,500 176,790 185,890 195,920 209,090 214,720 262,620 167,760 183,185 219,800 230,095 286,895

Total Power Consumption* Watts 8,210 8,538 9,100 9,685 10,980 11,461 15,137 15,437 18,920 18,930 20,230 21,370 21,330 22,470 28,170 18,637 17,300 21,200 22,475 27,775

EER 10.52 10.6 10.61 10.35 10.41 10.71 9.39 9.82 8.75 9.34 9.19 9.17 9.8 9.56 9.32 9 10.58 10.36 10.23 10.32

System refrigerant charge Kg 3.1 3.3 3.0 3.2 3.6 4.0 9.7 11.7 15.0 16.4 16.2 16.3 16.4 16.4 22.2 6.4 6.5 6.8 8.0 7.8

Model DCH090A DCH100A DCH120A DCH150 DCH190 DCH220 DCH250 DCH300 DCM180 DCM240 DCM300

Tube/Fins 2-pass Microchannel Copper/Aluminum 2-pass Microchannel


Condenser
Fins fpi 23 23 23 16 16 16 16 14 23 23 23
Coil
Area ft² ( m²) 25.36 (2.36) 25.36 (2.36) 25.36 (2.36) 35 (3.25) 53.3 ( 5 ) 53.3 ( 5 ) 53.3 ( 5 ) 53.3 ( 5 ) 54.7 (5.08) 54.7 (5.08) 54.7 (5.08)

Type Heavy Duty Propeller Fan

Quantity Nos. 2 2 2 2 2 2 2 2 2 2 2
Condenser
Motor Type 6 Pole, Class F Insulation, Totally Air Over ,IP 55, 1100 rpm
Fan & Motor
Motor size hp ( kW) 3/4 (0.55) 3/4 (0.55) 3/4 (0.55) 3/4 (0.55) 1.0 ( 0.75 ) 1.0 ( 0.75 ) 1.5 ( 1.1 ) 1.5 ( 1.1 ) 2 (1.1) 2 (1.1) 2 (1.1)

Quantity Nos. 2 2 2 2 2 2 2 2 2 2 2

Type Hermetic Scroll


Compressor
Qty Nos. 1 1 1 2 2 2 2 2 2 2 2

Type R410a
Refrigerant
No of Circuits Nos. 1 1 1 2 2 2 2 2 2 2 2

Suction line inch 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 1 3/8 7/8 1 1/8 1 3/8
Pipe line size
Liquid line inch 1/2 1/2 5/8 1/2 1/2 1/2 5/8 5/8 1/2 5/8 5/8

Height inches (mm) 47.9 (1217) 52.2 (1326) 77.2 (1961)

Dimensions Width inches (mm) 32.1 (814) 44.0 (1119) 87.2 (2215)

Length inches (mm) 64.6 (1638) 87.6 (2226) 46.4 (1179)

Weights Basic Unit lbs (Kg) 630.5 (286) 650.4 (295) 650.4 (295) 1117.7 (507) 1485 (675) 1485 (675) 1540 (700) 1650 (750) 1355.8(615) 1411(640) 1433(650)

Model YAH04B YAH05B YAH06B YAH08B YAH10B YAH12B YAH15B

Tube / Fins Enhanced Copper/Aluminum

AHU Coil Fins fpi 13 13 13 13 13 12 12

Area ft² ( m²) 4.43 (0.41) 5.46 (0.50) 6.55 (0.60) 8.74 (0.81) 10.76 (0.99) 12.81 (1.19) 16.06 (1.49)

Fan Type High efficient, double air inlets forward curved

Quantity Nos 2 2 2 2 2 2 2
AHU Fan &
Motor Type 3-ɸ asynchronous motor, F class insulation, IP54
Motor
Motor size hp ( kW) 1.5 (1.1) 2 (1.5) 3 (2.2) 4 (3.0) 5.3 (4) 5.3 (4) 7.3 (5.5)

Quantity Nos 1 1 1 1 1 1 1

Height inches (mm) 16.4 (417) 20 (508) 20 (508) 20 (508) 28.9 (736) 28.9 (736) 28.9 (736)

Dimensions Width Inches (mm) 62.9 (1600) 59 (1500) 68.8 (1750) 88.5 (2250) 72.8 (1850) 84.6 (2150) 103.3 (2625)

Length Inches (mm) 33.8 (860) 37 (940) 37 (940) 38.5 (980) 43.3 (1100) 45.2 (1150) 46 (1170)

Weights Basic Unit lbs (Kg) 330 (150) 365 (166) 412 (187) 522 (237) 582 (264) 707 (321) 831 (377)

Table 4: Product data

14
YORK STELLAR Commercial Ducted split series

DIMENSIONS & CLEARANCES


DCH090A-120A

15
YORK STELLAR Commercial Ducted split series

DCH150

16
YORK STELLAR Commercial Ducted split series

DCH190-300

Figure 5: Dimension and Clearance

17
YORK STELLAR Commercial Ducted split series

DCM180-300

18
YORK STELLAR Commercial Ducted split series

[YAH – 03B TO YAH – 08B]

Airflow m3
Model A B C D E F G H J K L M N p Q S T
/h

YAH 03B 3000 860 1360 417 470 259 228 184 73 227 367 400 173 325 1220 320 381 50

YAH 04B 4000 860 1600 417 520 259 228 184 73 227 367 400 173 325 1460 320 378 50

YAH 05B 5000 940 1500 508 580 232 262 184 107 237 387 400 224 427 1360 411 463 60

YAH 06B 6000 940 1750 508 551 232 262 184 107 225 376 400 224 427 1610 411 431 60

YAH 08B 8000 980 2250 508 705 298 262 244 107 275 425 400 224 427 2110 411 460 83

19
YORK STELLAR Commercial Ducted split series

[YAH – 10B TO YAH – 15B]

Airflow
Model A B C D E F H G J K L M N p Q S T
m3 /h
YAH
l0B 10000 1100 1850 736 690 471 404 112 / 280 430 441 346 639 1710 639 612 82
YAH
12000 1150 2150 736 680 373 404 112 294 280 430 441 314 621 2010 639 692 82
12B
YAH
15000 1170 2625 736 793 373 404 112 294 274 424 441 329 634 2485 639 687 82
15B

YAH10B YAH12/15B

Figure 6: Dimension and Clearance

20
YORK STELLAR Commercial Ducted split series

FAN PERFORMANCE DATA


External static pressure (in Wg)
Air Flow
Unit Model 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8
(CFM)
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1900 969 0.29 1122 0.36 1276 0.45 1420 0.54 1554 0.65 1679 0.76 1795 0.87 1902 0.99 2002 1.11 2096 1.23
2000 1019 0.34 1164 0.41 1312 0.5 1451 0.6 1582 0.71 1705 0.82 1819 0.94 1926 1.06 2026 1.18
YAH04B 2100 1069 0.39 1208 0.47 1350 0.56 1484 0.66 1611 0.77 1731 0.89 1844 1.01 1950 1.14
2200 1120 0.45 1252 0.53 1388 0.62 1519 0.73 1642 0.84 1759 0.96 1870 1.09 1975 1.22
2350 1195 0.55 1319 0.63 1447 0.73 1571 0.84 1689 0.96 1802 1.08 1910 1.21

Downsize Motor 1 HP
Standard Motor 1.5 HP
Oversize Motor 2 HP

External static pressure (in Wg)


Air Flow
Unit Model 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
(CFM)
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2400 853 0.42 943 0.51 1028 0.59 1107 0.67 1183 0.76 1258 0.85 1329 0.94 1401 1.04 1470 1.15 1538 1.26 1605 1.37
2500 888 0.48 975 0.56 1057 0.65 1135 0.74 1208 0.83 1280 0.92 1350 1.01 1418 1.12 1486 1.22 1553 1.33 1618 1.45
2600 923 0.54 1007 0.63 1087 0.72 1162 0.81 1234 0.90 1303 0.99 1371 1.09 1438 1.19 1503 1.30 1568 1.41 1631 1.53
YAH05B
2700 958 0.60 1040 0.69 1117 0.79 1190 0.88 1260 0.98 1327 1.07 1393 1.17 1458 1.28 1521 1.39 1585 1.5 1646 1.62
2800 994 0.67 1073 0.77 1148 0.86 1219 0.96 1287 1.06 1352 1.16 1417 1.26 1479 1.37 1541 1.48 1602 1.59 1663 1.71
2940 1043 0.77 1118 0.88 1191 0.98 1260 1.08 1325 1.18 1388 1.29 1450 1.39 1511 1.5 1570 1.62 1628 1.73

Downsize Motor 1.5 HP


Standard Motor 2 HP
Oversize Motor 3 HP

External static pressure (in Wg)


Air Flow
Unit Model 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
(CFM)
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2900 946 0.64 1034 0.75 1113 0.85 1186 0.96 1255 1.06 1321 1.16 1384 1.26 1446 1.37 1508 1.48 1568 1.59 1627 1.70
3000 979 0.71 1063 0.82 1141 0.93 1213 1.04 1280 1.14 1344 1.24 1406 1.35 1467 1.46 1527 1.57 1585 1.68 1643 1.80
3100 1011 0.78 1093 0.90 1170 1.01 1239 1.12 1305 1.23 1368 1.34 1428 1.45 1488 1.56 1546 1.67 1604 1.79 1660 1.90
YAH06B 3200 1043 0.86 1124 0.98 1198 1.10 1266 1.21 1331 1.32 1393 1.43 1452 1.55 1510 1.66 1567 1.77 1623 1.89 1678 2.01
3300 1076 0.94 1154 1.07 1227 1.19 1294 1.31 1357 1.42 1418 1.54 1476 1.65 1532 1.77 1588 1.89 1643 2.01 1697 2.13
3400 1108 1.03 1184 1.16 1256 1.29 1321 1.41 1383 1.53 1442 1.64 1500 1.76 1555 1.88 1609 2.00 1663 2.12 1716 2.25
3530 1150 1.15 1224 1.29 1293 1.42 1358 1.55 1418 1.67 1476 1.79 1532 1.91 1586 2.04 1638 2.16 1691 2.29 1742 2.42

Downsize Motor 2 HP
Standard Motor 3 HP
Oversize Motor 4 HP

21
YORK STELLAR Commercial Ducted split series

External static pressure (in Wg)


Air Flow
Unit Model 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
(CFM)
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
3600 863 0.67 935 0.74 1006 0.87 1075 1.01 1146 1.14 1217 1.27 1291 1.39 1366 1.52 1442 1.65 1519 1.78 1595 1.93
3800 910 0.79 979 0.86 1046 0.99 1112 1.14 1178 1.28 1246 1.41 1314 1.55 1384 1.68 1456 1.81 1528 1.95 1600 2.09
4000 958 0.92 1024 0.99 1088 1.13 1150 1.28 1213 1.43 1277 1.57 1341 1.71 1407 1.85 1474 1.99 1542 2.13 1610 2.28
YAH08B 4200 1005 1.06 1069 1.13 1130 1.27 1190 1.43 1249 1.59 1309 1.74 1370 1.89 1432 2.04 1496 2.18 1559 2.33 1624 2.48
4400 1053 1.22 1114 1.29 1172 1.43 1230 1.59 1286 1.76 1343 1.92 1402 2.08 1460 2.24 1519 2.39 1580 2.55 1640 2.70
4600 1100 1.39 1159 1.47 1216 1.61 1270 1.77 1325 1.95 1379 2.12 1434 2.29 1490 2.45 1546 2.61 1603 2.77 1661 2.93
4700 1124 1.49 1182 1.56 1237 1.70 1291 1.87 1344 2.05 1398 2.22 1451 2.39 1505 2.56 1560 2.73 1616 2.89 1673 3.06

Downsize Motor 3 HP
Standard Motor 4 HP
Oversize Motor 5.5 HP

External static pressure (in Wg)


Air Flow
Unit Model 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
(CFM)
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
4800 564 0.81 625 0.93 685 1.06 741 1.2 795 1.34 847 1.49 897 1.65 945 1.81 993 1.99 1039 2.17 1085 2.36
5000 587 0.91 646 1.04 704 1.18 759 1.32 811 1.46 861 1.62 910 1.78 957 1.95 1003 2.12 1048 2.31 1093 2.50
5200 611 1.02 667 1.16 723 1.30 776 1.45 827 1.60 876 1.75 923 1.92 969 2.09 1015 2.27 1058 2.45 1102 2.65
YAH10B
5400 634 1.15 688 1.29 743 1.43 794 1.58 844 1.74 891 1.90 937 2.07 982 2.24 1026 2.42 1069 2.61 1112 2.81
5600 657 1.28 710 1.42 763 1.58 813 1.73 861 1.89 907 2.05 952 2.22 996 2.40 1039 2.59 1081 2.78 1122 2.98
5880 690 1.48 740 1.63 791 1.79 839 1.95 885 2.12 930 2.29 974 2.46 1016 2.65 1058 2.84 1098 3.03 1138 3.23

Downsize Motor 3 HP
Standard Motor 4 HP
Oversize Motor 5.5 HP

External static pressure (in Wg)


Air Flow
Unit Model 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
(CFM)
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
5800 482 0.70 556 0.87 627 1.05 692 1.22 754 1.40 814 1.59 874 1.79 932 1.99 991 2.22 1049 2.46 1107 2.71
6100 507 0.82 577 0.99 646 1.18 709 1.36 769 1.55 826 1.74 883 1.94 939 2.16 995 2.38 1050 2.62 1106 2.87
6300 523 0.90 591 1.08 659 1.27 720 1.46 779 1.66 835 1.85 890 2.06 945 2.27 999 2.50 1053 2.73 1107 2.99
YAH12B
6500 540 0.99 606 1.17 671 1.37 732 1.57 789 1.77 844 1.97 898 2.18 951 2.39 1003 2.62 1056 2.86 1108 3.11
6800 564 1.13 627 1.32 691 1.53 750 1.74 805 1.94 858 2.15 910 2.37 961 2.59 1012 2.82 1062 3.06 1112 3.31
7060 586 1.26 646 1.46 708 1.68 766 1.89 820 2.11 871 2.33 922 2.55 971 2.77 1020 3.01 1069 3.25

Downsize Motor 3 HP
Standard Motor 4 HP
Oversize Motor 5.5 HP

22
YORK STELLAR Commercial Ducted split series

External static pressure (in Wg)


Air Flow
Unit Model 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
(CFM)
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
6800 509 0.97 563 1.12 629 1.32 693 1.53 751 1.74 807 1.95 860 2.16 912 2.38 962 2.6 1013 2.83 1063 3.07
7200 538 1.15 589 1.31 651 1.52 712 1.74 769 1.96 823 2.18 874 2.4 924 2.63 973 2.85 1021 3.09 1069 3.33
7400 553 1.25 602 1.41 662 1.62 722 1.85 779 2.08 831 2.31 882 2.53 931 2.76 978 2.99 1025 3.23 1072 3.48
7600 568 1.35 615 1.52 974 1.73 733 1.97 788 2.20 840 2.43 890 2.67 938 2.90 984 3.14 1030 3.38 1076 3.63
7800 583 1.46 628 1.63 685 1.85 743 2.09 797 2.33 849 2.57 898 2.81 945 3.04 991 3.29 1036 3.53 1081 3.78
YAH15B
8000 598 1.57 642 1.75 697 1.97 753 2.21 807 2.46 858 2.71 906 2.95 953 3.20 998 3.44 1042 3.69 1086 3.95
8200 612 1.69 655 1.87 709 2.10 764 2.35 817 2.60 867 2.85 915 3.10 961 3.35 1005 3.60 1049 3.86 1092 4.12
8400 627 1.82 669 2.00 721 2.23 775 2.48 827 2.74 876 3.00 923 3.26 969 3.52 1013 3.77 1055 4.03 1098 4.3
8600 642 1.95 682 2.14 733 2.37 785 2.63 837 2.89 886 3.16 932 3.42 977 3.68 1020 3.95 1063 4.21 1104 4.48
8828 659 2.11 698 2.30 747 2.54 798 2.8 849 3.07 897 3.34 943 3.61 987 3.88 1029 4.15 1071 4.42 1112 4.7

Downsize Motor 4 HP
Standard Motor 5.5 HP
Oversize Motor 7.5 HP

External Static Range


ESP ESP ESP ESP ESP
YAH ESP (in Wg) YAH ESP (in Wg) YAH ESP (in Wg) YAH ESP (in Wg) YAH ESP (in Wg)
Code Code Code Code Code
1 0.9 1 0.7 1 0.9 1 0.8 1 0.9
A 0.0 A 0.0 A 0.0 A 0.0 A 0.0
B 0.1 B 0.1 B 0.1 B 0.1 B 0.1
C 0.2 C 0.2 C 0.2 C 0.2 C 0.2
D 0.3 D 0.3 D 0.3 D 0.3 D 0.3
E 0.4 E 0.4 E 0.4 E 0.4 E 0.4
F 0.5 F 0.5 F 0.5 F 0.5 F 0.5
04
G 0.6 G 0.6 G 0.6 G 0.6 G 0.6
H 0.7 H 0.7 H 0.7 H 0.7 H 0.7
03 I 0.8 I 0.8 I 0.8 I 0.8 I 0.8
J 0.9 J 0.9 05 J 0.9 J 0.9 J 0.9
K 1.0 K 1.0 K 1.0 K 1.0 K 1.0
06
L 1.1 L 1.1 L 1.1 L 1.1 L 1.1
08
M 1.2 M 1.2 M 1.2 M 1.2 M 1.2
N 1.3 N 1.3 N 1.3 N 1.3
O 1.4 O 1.4 O 1.4 O 1.4
P 1.5 P 1.5 P 1.5 P 1.5
Q 1.6 Q 1.6 Q 1.6 Q 1.6
R 1.7 R 1.7 R 1.7 R 1.7
S 1.8 S 1.8 S 1.8
T 1.9 T 1.9 T 1.9
U 2.0 U 2.0
V 2.1 V 2.1
W 2.2 W 2.2
X 2.3
Y 2.4

23
YORK STELLAR Commercial Ducted split series

External Static Range


YAH ESP Code ESP(in Wg) YAH ESP Code ESP(in Wg) YAH ESP Code ESP(in Wg)
1 0.8 1 1 1 0.9
A 0 A 0 A 0
B 0.1 B 0.1 B 0.1
C 0.2 C 0.2 C 0.2
D 0.3 D 0.3 D 0.3
E 0.4 E 0.4 E 0.4
F 0.5 F 0.5 F 0.5
G 0.6 G 0.6 G 0.6
H 0.7 H 0.7 H 0.7
I 0.8 I 0.8 I 0.8
J 0.9 12 J 0.9 J 0.9
15
K 1 K 1 K 1
10
L 1.1 L 1.1 L 1.1
M 1.2 M 1.2 M 1.2
N 1.3 N 1.3 N 1.3
O 1.4 O 1.4 O 1.4
P 1.5 P 1.5 P 1.5
Q 1.6 Q 1.6 Q 1.6
R 1.7 R 1.7 R 1.7
S 1.8 S 1.8 S 1.8
T 1.9 T 1.9 T 1.9
U 2 U 2
V 2.1
W 2.2

24
YORK STELLAR Commercial Ducted split series

ELECTRICAL DATA
COMPRESSOR Downsize Standard Oversize Minimum Minimum Minimum
COND.MOT
MODEL VOLTAGE QTY QTY Blower Blower Blower Circuit MOP (0) Circuit MOP (1) Circuit MOP (2)
RLA LRA OR
Motor (0) Motor (1) Motor (2) Amperes (0) Amperes (1) Amperes (2)

YAH -04B 380/3/60 14.4 110 1 1.6 2 1.63 2.24 3.26 23 35 23 35 24 35


DCHA 90
YAH -05B 380/3/60 14.4 110 1 1.6 2 2.24 3.26 4.5 23 35 24 35 26 40

YAH -05B 380/3/60 17.7 155 1 1.6 2 2.24 3.26 4.5 28 45 29 45 30 45


DCHA 100
YAH -06B 380/3/60 17.7 155 1 1.6 2 3.26 4.5 6.6 29 45 30 45 32 50

YAH -06B 380/3/60 19.2 155 1 1.6 2 3.26 4.5 6.6 30 50 32 50 34 50


DCHA 120
YAH -08B 380/3/60 19.2 155 1 1.6 2 4.5 6.6 7.74 32 50 34 50 35 50

YAH -08B 380/3/60 12.2 88 2 1.7 2 4.5 6.6 7.74 35 45 37 50 39 50


DCH 150
YAH -10B 380/3/60 12.2 88 2 1.7 2 4.5 6.6 7.74 35 45 37 50 39 50

25
YORK STELLAR Commercial Ducted split series

Maximum Maximum
Minimum Maximum Minimum Minimum
Condenser Downsize Standard Oversize Blower Fuse / Fuse /
Model Voltage Compressor Qty Qty Circuit Fuse / Breaker Circuit Circuit
Motor Blower Motor (0) Blower Motor (1) Motor (2) Breaker Size Breaker
Amperes (0) Size (0) Amperes (1) Amperes (2)
(1) Size (2)
RLA Each LRA Each FLA Each FLA FLA FLA Amps Amp Amps Amp Amps Amp

YAH-10B 380/3/60 14.4 110 2 2.85 2 4.50 6.60 7.74 42.6 50.0 44.7 50.0 45.8 50.0

DCM 180

YAH-12B 380/3/60 14.4 110 2 2.85 2 4.50 6.60 7.74 42.6 50.0 44.7 50.0 45.8 50.0

YAH-12B 380/3/60 19.2 155 2 2.85 2 4.50 6.60 7.74 53.4 60.0 55.5 65.0 56.6 65.0

DCM 240

YAH-15B 380/3/60 19.2 155 2 2.85 2 6.60 7.74 10.67 55.5 65.0 56.6 65.0 59.6 65.0

DCM 300 YAH-15B 380/3/60 26.4 168 2 2.85 2 6.60 7.74 10.67 71.7 80.0 72.8 80.0 75.8 90.0

Table 5: Electrical Data

MOTOR RLA @400/3/60


1.1 Kw 2.3 A
1.5 Kw 3.5 A
2.2 Kw 4.5 A
3 Kw 6.6 A
4 Kw 8A
5.5 Kw 11A
7.5 Kw 15 A
11 Kw 21.5 A
15 Kw 29 A
18 Kw 35 A
22 Kw 42 A

Power cable conductor ampacity based on copper material with 75C Insulation minimum , Correction factors of (Ambient Temp , Current carrying
conductors , voltage drop calculation) to be considered as per NEC or equivalent international standard.

Table 6: Electrical Data for field power cable sizes

26
YORK STELLAR Commercial Ducted split series

TERMINOLOGY
SAFETY
The internal section of the unit adjacent to moving parts and electrical
This section of the IOM covers Safety Aspects applicable to the York parts or devices is considered as the ‘danger zone’. Prior to gaining
Stellar Commercial Ducted Split Air Cooled Unit. Adherence to the
access to these parts, it is necessary to acquire the proper tools to
instructions detailed hereunder, will ensure the safety of the operators,
deactivate the safety devices. The operators are responsible for
prevent damage to the equipment and prevent accidents.
transport, installation, start up, service and maintenance, including
cleaning and trouble shooting.

OPERATIONAL SAFETY
York Stellar Commercial Ducted Split Air Cooled Unit in conformance
to the highest standards of operational as well as operator safety.
Nevertheless, hazards may occur if the units are used for purposes
other than the designed use(s), Units are operated by untrained staff
and / or Units are not operated in conformance with general standards
prevalent in the industry.

OPERATION AND USE OF THE UNIT IN


CONFORMANCE WITH GENERAL STANDARDS
AND PROVISIONS
YORK® Stellar Commercial Ducted Split Air Cooled Units are
designed for and are able to cool and operate in the indoor unit.

Any other use is considered not in conformity with general provisions.


The manufacturer is not responsible for any resulting damages. All
responsibility resulting from such non conformity rests with the user.

In order to use the unit according to general provisions proper


instructions for installation, exercise and transport must be observed.
Installation and start up of the unit must satisfy the national codes and
standards having legal validity in the country of use.

The user is responsible for compliance with standards. Additionally,


any type of work that may compromise safety should be avoided.
Arbitrary transformations or modifications to the unit by the user or
operator are not permitted and nullify the warranty of the manufacturer.

The manufacturer will also not be responsible for any damages to the
equipment, to property or to personnel.

Figure 7: Unit Name Plate

Table 7: Motor nameplate

27
YORK STELLAR Commercial Ducted split series

STAFF TRAINING
ADHERENCE OF THE USER/OPERATOR TO
THE WARNINGS AND OTHER INSTRUCTIONS The unit should be started up and serviced (routine and corrective
maintenance) by authorized and trained staff only. This staff must be
Clear signs are placed at appropriate locations on the unit showing: informed about possible hazards regarding:

• Electrical connections
• Piping connections
• Startup

These operations must be executed only by trained persons. who, on


behalf of the user, attend to control and to perform
extraordinary/ordinary maintenance of the unit. It is necessary to
establish and to respect the responsibilities for control and
maintenance to guaranty safety, without confusion

USE OF THE UNIT


The unit must be started up only by means of proper safety devices.
The installer is obliged to install the unit according to installation plans
and conditions. Only authorized persons must operate the unit.

The staff in charge is obliged to immediately inform the user of any


changes that may compromise safety. For this reason it is necessary
to inspect for eventual anomalies or damages at least once a week.

The user or operator must never dismount and deactivate safety


devices. If these have to be removed for maintenance, all safety
devices must be reinstalled at their correct location once the
maintenance is complete. For all operations of maintenance, the
power source must be locked out.

If it is necessary to undertake maintenance activities, the fan must be


switched off, isolated and allowed to run down.

All warnings and signs regarding the units must be absolutely


observed

28
YORK STELLAR Commercial Ducted split series

OPERATION
SOUND POWER RATINGS
A sound power level is a measure of the total noise radiated by the machine in all directions. It is a property of the machine and is essentially independent
of the measuring environment. Sound power levels are useful to equipment manufacturers, buyers, installers, and users for :
• Calculating the sound pressure level from a machine at a given distance in a given environment.
• Comparing the noise output from different machines
• Setting specifications for the maximum permitted noise from a machine
• Comparing machines before and after modifications to reduce the noise

Sound power is measured in watts or picowatts, and sound power levels are traditionally given in decibels (dB re 1pW).
Refer table 8 for sound power level of outdoor unit.
-12
Outdoor Unit Sound Power, dB (10 ) Watts
Model Rating Octave Band Centerline Frequency (Hz)
dB (A) 63 125 250 500 1000 2000 4000 8000
DCH090A 80.5 82 74 72 74 72 73 76 71
DCH100A 82.7 85 76 74 74 74 75 79 73
DCH120A 84.5 86 78 77 77 77 76 80 74
DCH150 82.7 82 70 70 72 75 76 78 73
DCH190 88.1 84 82 82 79 79 82 78 87
DCH220 88.1 84 82 82 79 79 82 78 87
DCH250 86 79 79 78 78 77 80 80 85
DCH300 88.3 80 79 79 78 78 81 80 87
DCM 180 86 87 83 81 80 78 77 80 77
DCM 240 84 85 78 78 77 77 76 79 74
DCM 300 84 85 78 78 77 77 76 79 74
Indoor Unit Sound Power, dB (10-12) Watts
Model Rating Octave Band Centerline Frequency (Hz)
dB (A) 63 125 250 500 1000 2000 4000 8000
YAH03 91.0 88 83 84 79 78 75 71 67
YAH04 89.0 84 81 83 80 78 75 71 66
YAH05 81.0 66 71 77 73 74 73 70 62
YAH06 84.0 71 74 79 75 76 75 72 65
YAH08 85.0 76 77 79 76 78 74 71 63
YAH10 87.0 81 85 78 74 70 68 64 56
Table 8 : Sound Power Levels

VOLT FREE CONTACT COOLING SEQUENCE OF OPERATION


All Stellar Commercial Ducted Split Air Cooled Units are supplied with CONTINUOUS BLOWER
Volt free contact, Refer to Electrical wiring schematic that are pasted By setting the room thermostat fan switch to “ON” the supply air blower
inside the unit. will operate continuously.

INTERMITTENT BLOWER
With the room thermostat fan switch set to “AUTO” and the system
switch set to either the “AUTO” or “HEAT” settings, the blower is
energized whenever a cooling or heating operation is requested. The
blower is energized after any specified delay associated with the
SEQUENCE OF OPERATIONS OVERVIEW operation. When energized, the indoor blower has a minimum run time
of 30 seconds. Additionally, the indoor blower has a delay of 10
For these units, the thermostat makes a circuit between “R” and “Y1” seconds between operations.
for the first stage of cooling. The call is passed to the unit control board
(UCB), which then determines whether the requested operation is NO OUTDOOR AIR OPTIONS
available and, if so, which components to energize. For electric heat When the thermostat calls for the first stage of cooling, the low voltage
units, the UCB passes the call to the electric heater. control circuit from R to YI & G is completed. For first stage of cooling,
compressor 1, condenser fan motor 1 & 2 are energized. After
In both cases, when the “W1” call is sensed, the indoor air blower is completing the specified fan on delay for cooling, the UCB will
energized following a specified heating delay. If at any time a call for energize the blower Motor.When the thermostat calls for 2nd stage of
both heating and cooling are present, the heating operation will be cooling low voltage control circuit from R to Y2 is completed,
performed. If operating, the cooling system is halted as with a compressor 2 is energized, provided it has not been locked out.
completion of a call for cooling. Heating always takes priority.

29
YORK STELLAR Commercial Ducted split series

For third stage of cooling, the low voltage control circuit from”R” to “Y3” EVAPORATOR COIL FREEZE STAT
is completed. Compressor # 3, if there is an initial call for 3 stages of
cooling, the UCB will delay energizing compressor 2 & 3 by 30 During cooling operation, if a freezestat opens, the UCB will de-
seconds each. Once the thermostat has been satisfied it will de‐ energize the associated compressor, initiate the ASCD, and
energize Y1, Y2 & Y3. condenser fans will stop. If the call for cooling is still present at the
conclusion of the ASCD, the UCB will reenergize the halted
When the thermostat calls for fourth stage of cooling, the low voltage compressor. Should a freezestat open three times within two hours of
control circuit from “R” to “Y4” is completed, compressor #4 is operation, the UCB will lock out the associated compressor , flags an
energized. If there is an initial call for 4 stages of cooling, the UCB will alarm on LCD (see Table 8) and condenser fan will stop.
delay energizing compressor # 2, 3 & 4 by 30 seconds each. Once the
thermostat has been satisfied it will de‐energize Y1, Y2, and Y3 & Y4. ELECTRIC HEATING SEQUENCE OF
OPERATIONS
If the compressors have satisfied their minimum run times, the
compressors and condenser fans are de‐energized. Otherwise, the The following sequence describes the operation of the electric heat
unit operates each cooling system until the minimum run times for the section. Two--stage heating (Heaters MUST use a two stage
compressors have been completed. Upon the final compressor de‐ thermostat):
energizing, the blower is stopped following the elapse of the fan off a) Upon a call for first-stage heat by the thermostat, the heater
delay for cooling. contactor will be energized. After completing the specified
fan on delay for heating, the UCB will energize the blower
To be available, a compressor must not be locked out due to a high or motor. If the second stage of heat is required, second
low pressure switch or freezestat trip and the anti-short cycle delay heater contactor will be energized. After completing the
(ASCD) must have elapsed. specified fan on delay for heating, the UCB will energize
the blower motor.
b) The thermostat will cycle the electric heat to satisfy the
COOLING OPERATION ERRORS heating requirements of the conditioned space.

Each cooling system is monitored for operation outside of the intended HEATING OPERATION ERRORS
parameters. Errors are handled as described below. All system errors
override minimum run times for compressors. TEMPERATURE LIMIT
If the UCB senses zero volts from the high temperature limit, the
indoor blower motor is immediately energized. This limit is monitored
HIGH PRESSURE LIMIT SWITCH regardless of unit operation status, i.e. the limit is monitored at all
times. If the temperature limit opens three times within one hour, it will
During cooling operation, if a high pressure limit switch opens, the
lock on the indoor blower motor and a flash code is initiated (See
UCB will de-energize the associated compressor, initiate the ASCD
Table 9).
(anti short cycle delay), and condenser fan will stop. If the call for
cooling is still present at the conclusion of the ASCD, the UCB will re- SAFETY CONTROLS
energize the compressor again . The unit control board monitors the temperature limit switch of electric
A high pressure switch open three times within two hours of operation, heat units. The control circuit includes the following safety controls:
the UCB will lock out the associated compressor , flags an alarm on
LCD (see Table 8). and condenser fan will stop. Temperature Limit Switch (AUTO)
to manually reset the lockout condition , navigate to Reset.LO in LCD , This control is located inside the heater compartment and is set to
change the value from NO to YES open at 120°F. It resets automatically. The limit switch operates when

a high temperature condition, caused by inadequate supply air flow


LOW PRESSURE LIMIT SWITCH occurs, thus shutting down the heater and energizing the blower.
The low pressure limit switch is not monitored during the initial 30 RESET
seconds of a cooling system’s operation.If the low pressure switch fails Remove the call for cooling, by raising thermostat setting higher than
to close after 30 seconds, the UCB will de-energize the associated the conditioned space temperature. This resets any pressure or
compressor, initiate the ASCD, and condenser fan will stop. freezestat flash codes.
Once the low pressure switch has been proven (closed), the UCB will To manually reset the lockout condition , navigate to Reset.LO in LCD
monitor the low pressure limit switch for any openings. If the low , change th value from NO to YES .
pressure switch opens for greater than 5 seconds, the UCB will de- ALARMS
energize the associated compressor, initiate the ASCD, and The UCB will initiate alarm on LCD describing the error.
condenser fan will stop. If the call for cooling is still present at the Refer to unit control board alarm.
conclusion of the ASCD, the UCB will re-energize the halted
compressor. Should a low pressure switch open three times within one
hour of operation, the UCB will lock out the associated compressor ,
flags an alarm on LCD (see Table 8). and condenser fan will stop.
to manually reset the lockout condition , navigate to Reset.LO in LCD ,
change th value from NO to YES .

30
YORK STELLAR Commercial Ducted split series

REFRIGERANT PIPING CONNECTIONS


SAFETY CONTROLS
All refrigerating piping practices when installing these units are to be in
The unit control board monitors the following inputs for each cooling accordance with local codes and the latest standards of safety codes.
system :
To ensure trouble free operation the following conditions should be
1. A suction line freezestat to protect against low evaporator
observed.
temperatures due to a low air flow or a low Installation, return air
temperature. 1.Do not connect this carefully dehydrated unit to tubing and cooling
2. A high pressure switch to protect against excessive discharge
units which have not been dehydrated. Tubing which may be dirty or
pressures due to a blocked condenser coil or a condenser motor
moist must be thoroughly cleaned and dried out.
failure, (Opens at 610±17 psig and resets at 480±29 psig).
3. A low pressure switch to protect against loss of refrigerant charge,
2.When soldering valves, they are to be disassembled or wrapped in
(opens at 58±7 psig and resets at 87±7 psig).
wet cloths to prevent damage by heat. To prevent damage by heat. To
The above pressure switches are hard soldered to the unit. The prevent formation of copper oxide on the inside of copper tubing,
refrigeration systems are independently monitored and controlled.
nitrogen or inert gas must be passed through the piping continuously
On any fault, only the associated system will be affected by any safety
while soldering joints.
/ preventive action. The other refrigerant system will continue in
operation unless it is affected by the fault as well. 3.Moisture in a refrigeration system is one of the main causes of
COMPRESSOR PROTECTION trouble, particularly to the compressor, resulting in the formation of
acids which attack the motor insulation, the valves and valve plates.
The compressors also have inherent (internal) protection. If there is an Stringent precautionary measures are taken at the factory to ensure
abnormal temperature rise in a compressor, the protector will open to that the unit is clean and properly dehydrated. Equal care should be
shut down the compressor. The UCB incorporates features to taken at the time of installation to be sure that the system is as clean
minimize compressor wear and damage. An anti short cycle delay and dry as possible. As an additional safeguard, a drier of the proper
(ASCD) is utilized to prevent operation of a compressor too soon after size should be installed in the liquid line of all units.
its previous run. Additionally, a minimum run time is imposed any time
a compressor is energized. The ASCD is initiated on unit start up and 4.A moisture indicator should also be installed which allows for quick
on any compressor reset or lock out. visible checking of the moisture content of the refrigerant. Indicators
are provided with a sight glass that contains a porous filter paper
NUISANCE TRIP PROTECTION AND STRIKES impregnated with a chemical to change color according the moisture
content.
To prevent nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and low-pressure switches and
5.Suction lines have a great impact on the ability of a unit to run trouble
the freezestats must trip three times within two hours before the unit
free. Improperly piped they can cause slugging, oil dilution and
control board will lock out the associated compressor.
lubrication failure which results in the breakdown of the compressor. It
is usually standard practice to size the suction line to have a pressure
ALARMS drop, due to friction, not greater than equivalent of a 2 degree F
change in saturation temperature for halocarbon refrigerants. (R-22).
The UCB will initiate alarm on LCD describing the error. Where suction rises are necessary, if cooling units are at a lower level
Refer to unit control board alarm table 10. than the condensing unit, a trap should be installed at the bottom of
the riser and the lines sized for the minimum system capacity. All
RESET horizontal runs should be level or pitched towards the condensing unit
to assure oil return.Suction lines should be insulated.
Remove the call for cooling, by raising thermostat setting higher than
the conditioned space temperature. This resets any pressure or
6. Liquid lines should be size to have a pressure drop due to friction,
freezestat flash codes.to manually reset the lockout condition ,
not greater than the equivalent of a 2 degree F change in saturation
navigate to Reset.LO in LCD , change th value from NO to YES .
temperature for halocarbon refrigerants (R-22). Condensing units are
designed to proved subcooled liquid to the expansion valve when
liquid lines are sized as noted above.

7.Expansion valves should be carefully selected to match system


requirements. The valve should be installed according to the
instructions furnished with each valve.

8.All refrigerant connections should be leak tested before the system is


charged with refrigerant. The complete system should be pressurized
to 250 psig with a small charge of refrigerant backed up with dry
nitrogen. The use of an electronic leak detector is recommended
because of its greater sensitivity to small leaks. Leaks should be
repaired as found and the test procedure repeated as necessary.

31
YORK STELLAR Commercial Ducted split series

CHARGING SYSTEM
EVACUATION
1.As all units are shipped with a full charge and service valves to hold
When all refrigeration connections have been made a leak test and the charge, they must be fully charged with the refrigerant which they
evacuation should be performed on the unit by licensed refrigeration
were designed. When a charging a unit you must use a clean and dry
mechanic. A small portable vacuum pump should be used to evacuate
refrigerant.
the system (evaporator coil, drier, lines, etc) after condensing unit has
been installed in the system. Do not use the compressor as a vacuum 2.Open all discharge, suction and liquid line valves. Connect the
pump. Use a vacuum pump that is built for refrigeration evacuation
charging hose to the charge port of the liquid line valve. Be sure to
equipment.
purge the hose of all air. Move the valve off its back seat and add liquid
refrigerant until the unit pressure equalizes the refrigerant cylinder
If the system is properly evacuated, using a good vacuum pump which
pressure. Close the charge of the liquid line valve. Move charging
can pull down into the 50 to 100 micron range, the non condensables
hose to the back seating port of the suction valve and purge hose of all
are eliminated before the system is ever started. A good vacuum air. Start compressor and continue to add refrigerant gas until the liquid
pump with electronic gauge is desirable and highly recommended for
line sight glass is clear and a minimum of 8 degree F sub cooling is
this procedure. The gauge may be showing 50 microns at the pump,
obtained leaving the condenser sub cooling section.
but if a large system is being evacuated, the vacuum level at the end
of the system may be too high. The poorer the vacuum, the poorer the 3.After the system has been completely charged and the compressor
results.
is operating, the system should once again be checked for leaks to
make sure that none have occurred during the handling of equipment.
This situation should not be further complicated by using too small a
connecting line between the vacuum pump and the system as it will
4.The moisture indicator should be checked and filter drier core
create a high pressure drop which will greatly reduce the efficiency of
changed as an added precaution.
the vacuum pump. To use the vacuum pump most efficiently a triple
evacuation method should be used. This involves pulling out the START UP (COOLING)
system down to 100 microns and holding it for a period of three to four
hours and then breaking the vacuum with a dry refrigerant if it is a After installation has been completed:
small system or with nitrogen if it is a larger system. The vacuum is 1.Check the electrical supply voltage being supplied. Be sure that it is
pulled and broken a second time exactly as describe above. Finally a the same as listed on the unit nameplate.
vacuum is pulled down to 50 microns, held for a period of three to four 2.Set the room thermostat to the on position.
hours and broken with the type of refrigerant to be used in the system. 3.Turn unit electrical power on.
At this point the system can be charged, and you can be assured that 4.Set the room thermostat fan switch to on.
virtually all of the non condensable s have been removed. Triple 5.Check indoor blower rotation.
evacuation works on the principle of pulling out a high percentage of • If blower rotation is in the wrong direction. Refer to phasing
the non condensables and/or water on each pull down. As an section in general information section.
example, suppose 90% of the non condensable are removed on the • Check blower drive belt tension.
first pull down. This would leave 10% of 1 % of the original non • Check bearing lubrication. If it requires lubrication, grease
condensable in the system. In addition, breaking the vacuum with dry it.
nitrogen or dry refrigerant has a diluting effect on moisture which has 6.Check the unit supply air (CFM).
been vaporized. 7.Measure evaporator fan motor amp draw.
8.Set the room thermostat fan switch to off.
Besides being sure that the connecting line between the vacuum 9.Turn unit electrical power off.
pump and the refrigeration system is sufficiently large enough to
prevent pressure drop, there are three precautions to be kept in mind: OPERATING INSTRUCTIONS
1.Turn unit electrical power on.
First: an ordinary compound gauge is worthless on a good vacuum
2.Set the room thermostat setting to lower than the room temperature.
pump. The error in the gauge is greater than the amount of vacuum
3.First stage compressors will energize after the built in time delay (five
being measured. There are several very good electronic gauges in the
minutes).
market which are rugged and have a dial on which microns can be
4.The 2nd, 3rd and 4th stage of the thermostat will energize the
read very similar to the reading of an ammeter.
respective compressors (if needed).
Second: be sure that the system, including the factory piping of the POST START CHECK LIST
unit, is good and tight and has been checked for the lightest leak. A
good vacuum pump will stay ahead of a small leak and is simply 1.Verify proper system pressures for both circuits.
means pulling air and moisture in one and pushing it out the other. 2.Measure the temperature drop across the evaporator coil.
3.Measure the system Amperage draw across all legs of 3 phase
Third: it should also be remembered that water trapped under layers of power wires.
oil will stay there regardless of the vacuum pulled and will not be 4. Measure the condenser fan amp draw.
dislodged until the circulating refrigerant takes the oil up and releases
the water. If any leaks are found, make repairs. A halide torch, soap SHUT DOWN
bubbles or electronic detector may be used for leak detection.
1.Set the thermostat to highest temperature setting.
2.Turn off the electrical power to the unit.

32
YORK STELLAR Commercial Ducted split series

6.Failing the above, if there is line voltage supplied at contactor and it


TROUBLE SHOOTING is pulled in, and the supply air blower motor still does not operate,
replace the motor.
COOLING TROUBLE SHOOTING GUIDE
7.If 24 volts is not present at blower contactor, check that 24 volts is
present at the UCB supply air blower motor terminal, “FAN”. If 24 volts
is present at the FAN, check for loose wiring between the UCB and
blower contactor.

8.If 24 volts is not present at the “FAN” terminal, check for 24 volts
from the room thermostat. If 24 volts are not present from the room
thermostat, check for the following:
a) Proper operation of the room thermostat (contact between
R and G with the fan switch in the ON position and in the
AUTO position during operation calls),
b) Proper wiring between the room thermostat and the UCB,
Troubleshooting of components may require opening the electrical and
control box with the power connected to the unit. Use extreme care c) Loose wiring from the room thermostat to the UCB.
when working with live circuits! Check the unit nameplate for the
correct line voltage and set the voltmeter to the correct range before 9.If 24 volts is present at the room thermostat but not at the UCB,
making any connections with line terminals. check for proper wiring between the thermostat and the UCB, i.e. that
the thermostat G terminal is connected to the G terminal of the UCB,
and for loose wiring.

10.If the thermostat and UCB are properly wired, replace the UCB.

On calls for cooling, the supply air blower motor is operating but
compressor # 1 is not (the room thermostat fan switch is in the
“AUTO” position).

1.If compressor # 1 does not energize on a call for cooling, check for
line voltage at the compressor contactor 1, and that the contactor is
When not necessary, shut off all electric power to the unit prior to any pulled in. Check for loose wiring between the contactor and the
of the following maintenance procedures so as to prevent personal compressor.
injury
2.If compressor contactor 1 is pulled in and voltage is supplied, lightly
* On calls for cooling, if the compressors are operating but the supply touch the compressor housing. If it is hot, the compressor may be off
air blower motor does not energize after a short delay (the room on inherent protection. Cancel any calls for cooling and wait for the
thermostat fan switch is in the “AUTO” position). internal overload to reset. Test again when cool.
1.Turn the thermostat fan switch to the ON position. If the supply air 3.If compressor contactor 1 is not pulled in, check for 24 volts at the
blower motor does not energize, go to Step 3. coil. If 24 volts are present and contactor is not pulled in, replace the
contactor.
2.If the blower motor runs with the fan switch in the ON position but will
not run after the first compressor has energized when the fan switch is 4.Failing the above, if voltage is supplied at compressor contactor 1, it
in the AUTO position, check the room thermostat for contact between is pulled in, and the compressor still does not operate, replace the
R and G in the AUTO position during calls for cooling. compressor.
3.If the supply air blower motor does not energize when the fan switch 5.If 24 volts is not present at compressor contactor 1, check for 24
is set to ON, check that line voltage is being supplied to the blower volts at the UCB terminal, C1. If 24 volts is present, check for loose
contactor, and that the contactor is pulled in. Check for loose wiring wiring between C1 and the compressor contactor.
between the contactor and the supply air blower motor.
6.If 24 volts is not present at the C1 terminal, check for 24 volts from
4.If blower contactor is pulled in and voltage is supplied to contactor, the room thermostat at the UCB Y1 terminal. If 24 volts is not present
lightly touch the supply air blower motor housing. If it is hot, the motor from the room thermostat, check for the following:
may be off on internal protection. Cancel any thermostat calls and set • Proper wiring between the room thermostat and the UCB,
the fan switch to AUTO. Wait for the internal overload to reset. Test i.e. Y1 to Y1, Y2 to Y2,Y3 to Y3 & Y4 to Y4.
again when cool.
• Loose wiring from the room thermostat to the UCB.
5.If blower contactor is not pulled in, check for 24 volts at the contactor
coil. If 24 volts are present but it is not pulled in, replace the contactor

33
YORK STELLAR Commercial Ducted split series

7.If 24 volts is present at the UC may be out due to an open high


pressure switch, low pressureB Y1 terminal, the compressor switch, or 7.If 24 volts is present at the UCB Y2 terminal, the compressor may be
freezestat. Check for 24 volts at the HPS1, LPS1, and FS1 terminals out due to an open high pressure switch, low pressure switch, or
of the UCB. If a switch has opened, there should be a voltage potential freezestat. Check for 24 volts at the HPS2, LPS2, and FS2 terminals
between the UCB terminals, e.g. If LPS1 has opened, there will be a of the UCB. If a switch has opened, there should be a voltage potential
24 volt potential between the LPS1 terminals between the UCB terminals, e.g. if LPS2 has opened, there will be 24
volts of potential between the LPS2 terminals.
8.If 24 volts is present at the UCB Y1 terminal and none of the
protection switches have opened, the UCB may have locked out the 8.If 24 volts is present at the UCB Y2 terminal and none of the
compressor for repeat trips. If the compressor is locked out, cancel any protection switches have opened, the UCB may have locked out the
call for cooling. This will reset any compressor lock outs. compressor for repeat trips. If the compressor is locked out, remove
any call for cooling at the thermostat or by disconnecting the
NOTE: While the above step will reset any lockouts, compressor # 1 thermostat wiring at the Y2 UCB terminal. This will reset any
may be held off for the ASCD. See the next step. Installation, compressor lock outs.

9.If 24 volts is present at the UCB Y1 terminal and none of the NOTE:While the above step will reset any lock outs, compressor # 1
switches are open and the compressor is not locked out, the UCB may will be held off for the ASCD, and compressor # 2 may be held off for a
have the compressor in an ASCD. The ASCD should time out within 5 portion of the ASCD. See the next step.
minutes.
9.If 24 volts is present at the UCB Y2 terminal and none of the
10.If none of the above corrected the error, test the integrity of the switches are open and the compressor is not locked out, the UCB may
UCB. Disconnect the C1 terminal wire and jumper it to the Y1 terminal. have the compressor in an ASCD. The ASCD should time out within 5
DO NOT jump the Y1 to C1 terminals. If the compressor engages, the minutes.
UCB has faulted.
10.The UCB can be programmed to lock out compressor operation
11.If none of the above correct the error, replace the UCB. during free cooling and in low ambient conditions. These options are
not enabled by default. Local distributors can test the UCB for this
*On calls for the second stage of cooling, the supply air blower motor programming.
and compressor # 1 are operating but compressor # 2 is not (the room
thermostat fan switch is in the “AUTO” position). 11.If none of the above corrected the error, test the integrity of the
UCB. Disconnect the C2 terminal wire and jumper it to the Y2 terminal.
1.Compressor # 2 will not energize simultaneously with compressor #1 DO NOT jump the Y2 to C2 terminals. If the compressor engages, the
if a call for both stages of cooling is received. The UCB delays UCB has faulted.
compressor # 2 by 30 seconds to prevent a power surge. If after the
delay compressor # 2 does not energize on a second stage call for 12.If none of the above correct the error, replace the UCB.
cooling, check for line voltage at the compressor contactor 2, and that *On a call for cooling, the supply air blower motor and compressor # 2
the contactor is pulled in. Check for loose wiring between the contactor are operating but compressor # 1 is not (the room thermostat fan
and the compressor. switch is in the “AUTO” position).

2.If compressor contactor 2 is pulled in and voltage is supplied, lightly 1.Compressor # 3 will not energize simultaneously with compressor 1
touch the compressor housing. If it is hot, the compressor may be off & 2, if a call for third stage of cooling is received. The UCB delays
on inherent protection. Cancel any calls for cooling and wait for the compressor # 3 by 30 seconds to prevent a power surge, if after the
internal overload to reset.Test again when cool. delay compressor # 3 doesn’t energize on rd. stage call for cooling,
check for line voltage at the compressor contactor 3, and that the
3.If compressor contactor 2 is not pulled in, check for 24 volts at the contactor is pulled in. Check for loose wiring between the contactor
compressor contactor coil. If 24 volts is present and compressor and the compressor.
contactor is not pulled in, replace the contactor.
2.If the compressor contactor 3 is pulled in and voltage is supplied,
4.Failing the above, if voltage is supplied at compressor. lightly touch the compressor housing. If it is hot, the compressor may
be off on inherent protection. Cancel any calls for cooling and wait for
5.Contactor 2, and it is pulled in, and the compressor still does not the internal overload to reset. Test again when cool.
operate, replace the compressor. 5. If 24 volts is not present at
compressor contactor 2, check for 24 volts at the UCB terminal, C2. If 3.If the compressor contactor 3 is not pulled in, check for 24 volts at
24 volts are present, check for loose wiring between C2 and the the compressor contactor coil. If 24 volt is present and compressor
compressor contactor. contactor is not pulled in, replace the contactor.

6.If 24 volts is not present at the C2 terminal, check for 24 volts from
the room thermostat at the UCB Y2 terminal. If 24 volts is not present
from the room thermostat, check for the following :
• 24 volts at the thermostat Y2 terminal.
• Proper wiring between the room thermostat and the UCB,
i.e.Y1 to Y1, Y2 to Y2.
• Loose wiring from the room thermostat to the UCB.

34
YORK STELLAR Commercial Ducted split series

4.Failing the above, if voltage is supplied at the compressor contactor 1.Compressor # 4 will not energize simultaneously with compressor
3, and it is pulled in, and the compressor still doesn’t operate, replace 1,2 & 3 if a call for fourth stage of cooling is received. The UCB delays
the compressor. compressor # 4 by 30 seconds to prevent a power surge, if after the
delay compressor # 4 doesn’t energize on 4th stage call for cooling,
5.If 24 volts is not present at compressor contactor 3, check for 24 check for line voltage at the compressor contactor 4, and that the
volts at the UCB terminal, C3. If 24 volts are present, check for loose contactor is pulled in. Check for loose wiring between the contactor
wiring between C3 and the compressor contactor. and the compressor.

6.If 24 volts is not present at the C3 terminal, check for 24 volts from 2.If the compressor contactor 4 is pulled in and voltage is supplied,
the room thermostat at the UCB Y3 terminal. If 24 volts is not present lightly touch the compressor housing. If it is hot, the compressor may
from the room thermostat, check for the following: be off on inherent protection. Cancel any calls for cooling and wait for
•24 volts at the thermostat Y3 terminal. the internal overload to reset. Test again when cool.
•Proper wiring between the room thermostat and the UCB.
•Loose wiring from the room thermostat to the UCB. 3.If the compressor contactor 4 is not pulled in, check for 24 volts at
the compressor contactor coil. If 24 volt is present and compressor
7.If 24 volts is present at the UCB Y3 terminal, the compressor may be contactor is not pulled in, replace the contactor.
out due to an open high pressure switch, low pressure switch or
freezestat. Check for 24 volts at the 4.Failing the above, if voltage is supplied at the compressor contactor
HPS3, LPS3 and FS3 terminals of the UCB. If a switch has opened, 4, and it is pulled in, and the compressor still doesn’t operate, replace
there should be a voltage potential between the the compressor.
UCB terminals e.g., if LPS3 has opened, there will be 24 volts of
potential between the LPS3 terminals. 5.If 24 volts is not present at compressor contactor 4, check for 24
volts at the UCB terminal, C4. if 24 Volts are present, check for loose
8.If 24 Volts is present at the UCB Y3 terminal and none of the wiring between C4 and the compressor contactor.
protection switches have opened, the UCB may have locked out the
compressor for repeat trips.If the compressor is locked out, remove 6.If 24 volts is not present at the C4 terminal, check for 24 volts from
any call for cooling at the thermostat or by disconnection the the room thermostat at the UCB Y4 terminal. If 24 volts is not present
thermostat wiring at the Y3 UCB terminal. This will reset any from the room thermostat, check for the following:
installation, compressor lock outs. •24 volts at the thermostat Y4 terminal.
•Proper wiring between the room thermostat and the UCB.
NOTE: While the above steps will reset any lockouts, compressor # 1 •Loose Wiring from the room is thermostat to the UCB.
& 2 will be held off for the ASCD, and the compressor # 3 may be held
off for a portion of the ASCD, See the next step. 7.If 24 Volts is present at the UCB Y4 terminal, the compressor may
be out due to an open high pressure switch, low pressure switch or
9.If 24 Volts is present at the UCB Y3 terminal and none of the freezestat. Check for 24 volts at the HPS4, LPS4 and FS4 terminals of
switches are open and the compressor is not locked out, the UCB may the UCB. If a switch has opened, there should be a voltage potential
have the compressor in an ASCD. Check the LED for an indication of between the UCB terminals e.g., if LPS4 has opened, there will be 24
an ASCD cycle. The ASCD should time out within 5 Min. volts of potential between the LPS4 terminals.

10.The UCB can be programmed to lock out compressor operation 8.If 24 volts is present at the UCB Y4 terminal and none of the
during free cooling and in low ambient conditions. These options are protection switches have opened, the UCB may have locked out the
not enabled by default. Local distributors can test the UCB for this compressor for repeat trips. If the compressor is locked out, remove
programming. any call for cooling at the thermostat or by disconnection the
thermostat wiring at the Y4 UCB terminal. This will reset any
11.If none of the above corrected the error, test the integrity of the installation, compressor lock outs.
UCB, disconnect the C3 terminal wire and the jumper it to the Y3
terminal, DO NOT jump the Y3 to C3 terminals. If the compressor NOTE: While the above steps will reset any lockouts, compressor # 1,
engages, the UCB has faulted. 2 & 3 will be held off for the ASCD, and the compressor # 4 may be
held off for a portion of the ASCD.
12.If none of the above correct the error, replace the UCB.
9.If 24 volts is present at the UCB Y4 terminal and none of the
On Call for fourth stage of cooling (50 TR models only) the supply air switches are open and the compressor is not locked out, the UCB may
blower motor & Compressor # 1, 2 & 3 are operating but compressor # have the compressor in an ASCD. The ASCD should time out within 5
4 is not ( the room thermostat fan switch is in the AUTO position). minutes.

35
YORK STELLAR Commercial Ducted split series

10.The UCB Can be programmed to lock out compressor operation NOTE : While the above step will reset any lock outs, compressor # 2
during free cooling and in low ambient conditions. These options are will be held off for the ASCD, and compressor # 1 may be held off for a
not enabled by default. Local distributors can test the UCB for this portion of the ASCD. See the next step
programming.
10.If 24 volts is present at the UCB Y1 terminal and none of the
11.If none of the above corrected the error, test the integrity of the switches are open and the compressor is not locked out, the UCB may
UCB, disconnect the C4 terminal wire and the jumper it to the Y4 have the compressor in an ASCD. The ASCD should time out within 5
terminal, DO NOT jump the Y4 to C4 terminals. If the compressor minutes.
engages, the UCB has faulted.
11.If 24 volts is present at the UCB Y1 terminal and the compressor is
12.If none of the above correct the error, replace the UCB. not out due to a protective switch trip, repeat trip lock out, or ASCD,
the economizer terminals of the UCB may be improperly wired. Check
On a call for cooling, the supply air blower motor and compressor # 2 for 24 volts at the Y1 “OUT” terminal of the UCB. If 24 volts is present,
are operating but compressor # 1 is not (the room thermostat fan trace the wiring from Y1 “OUT” for incorrect wiring. If 24 volts is not
switch is in the “AUTO” position). present at the Y1 “OUT” terminal, the UCB must be replaced.

1.Compressor # 2 is energized in place of compressor # 1 when 12.If none of the above corrected the error, test the integrity of the
compressor # 1 is unavailable for cooling calls. Check the UCB for UCB. Disconnect the C1 terminal wire and jumper it to the Y1 terminal.
alarms indicating that compressor # 1 is locked out. DO NOT jump the Y1 to C1 terminals. If the compressor engages, has
faulted.
2.Check for line voltage at the compressor contactor 1, and that the
contactor is pulled in. Check for loose wiring between the contactor 13.If none of the above correct the error, replace the UCB.
and the compressor.
C- Y-
Cooling Compressor Contactor
3.If compressor contactor 1 is pulled in and voltage is supplied at the Terminal Terminal
contactor 1, lightly touch the compressor housing. If it is hot, the Stage 1 1 1 C1 Y1
compressor may be off on inherent protection. Cancel any calls for
cooling and wait for the internal overload to reset. Test again when Stage 2 2 2 C2 Y2
cool. Stage 3 3 3 C3 Y3
Stage 4 4 4 C4 Y4
4.If compressor contactor 1 is not pulled in, check for 24 volts at the
Table 9: Terminals
coil. If 24 volts is present and compressor contactor 1 is not pulled in,
replace the contactor.
Similarly, if compressor of any stage is not operating, follow the same
procedure as listed above with respective compressor, contactors and
5.Failing the above, if voltage is supplied at compressor contactor 1,
terminal numbers (Refer table 9).
and it is pulled in, and the compressor still does not operate, replace
the compressor.

6.If 24 volts is not present at compressor contactor, check for 24 volts


at the UCB terminal, C1. If 24 volts is present, check for loose wiring
between C1 and the compressor contactor1.

7.If 24 volts is not present at the C1 terminal, check for 24 volts from
the room thermostat at the UCB Y1 terminal. If 24 volts are not present
at the UCB Y1 terminal, the UCB may have faulted. Check for 24 volts
at the Y1 ECON terminal. If 24 volts is not present at Y1 “ECON”, the
UCB has faulted. The UCB should de-energize all compressors on a
loss of call for the first stage of cooling, i.e. a loss if 24 volts at the Y1
terminal.

8.If 24 volts are present at the UCB Y1 terminal, the compressor may
be out due to an open high pressure switch, low pressure switch, or
freezestat. Check for 24 volts at the HPS1, LPS1, and FS1 terminals
of the UCB. If a switch has opened, threshold be a voltage potential
between the UCB terminals, e.g. if LPS1 has opened, there will be a
24 volt potential between the LPS1 terminals.

9.If 24 volts is present at the UCB Y1 terminal and none of the


protection switches have opened, the UCB may have locked out the
compressor for repeat trips.. If the compressor is locked out, remove
any call for cooling. This will reset any compressor lock outs.

36
YORK STELLAR Commercial Ducted split series

UNIT ALARMS C1 Locked out due to Low pressure 3 LPS1 trips within 1 hours
C2 Locked out due to Low pressure 3 LPS2 trips within 1 hours
Various Alarms are utilized by the unit control board (UCB) to aid in C3 Locked out due to Low pressure 3 LPS3 trips within 1 hours
troubleshooting . This is to verify that the UCB is functioning correctly. C4 Locked out due to Low pressure 3 LPS4 trips within 1 hours
C1 shut down due to high pressure HPS1 trip
Current alarms are monitored on the UCB LCD. Checking alarms and C2 shut down due to high pressure HPS2 trip
solve the error will start unit again after anti short cycle delay.you can C3 shut down due to high pressure HPS3 trip
Reset Lockouts manually , navigate to ResetLo in LCD change value
C4 shut down due to high pressure HPS4 trip
from NO to YES. The UCB will cycle through the last five (5) alarms,
C1 shut down due to Low pressure LPS1 trip
most recent to oldest.
In some cases, it may be necessary to “zero” the ASCD for the C2 shut down due to Low pressure LPS2 trip
compressors in order to perform troubleshooting. C3 shut down due to Low pressure LPS3 trip
C4 shut down due to Low pressure LPS4 trip
Note : The mentioned alarms are applicable for both Simplicity® C1 shut down due to coil freeze EC1 trip
control boards. However, the Simplicity 2nd board will represent data C2 shut down due to coil freeze EC2 trip
for circuits / compressors 3 & 4 only C3 shut down due to coil freeze EC3 trip
C4 shut down due to coil freeze EC4 trip
Alarm How it happens 3 EC1 trips within 2 hours
C1 Locked out due to Coil freeze
Unit shut down due to smoke SD input loses 24 VAC Evap_coil T < Evap_coil Tsp
Supply fan shut down due to OL Fan OL trip 3 EC2 trips within 2 hours
C2 Locked out due to Coil freeze
Unit locked out due to supply fan OL 3 fan ovr trips within 2 hours Evap_coil T < Evap_coil Tsp
C1 Locked out due to high pressure 3 HPS1 trips within 2 hours 3 EC3 trips within 2 hours
C3 Locked out due to Coil freeze
C2 Locked out due to high pressure 3 HPS2 trips within 2 hours Evap_coil T < Evap_coil Tsp
C3 Locked out due to high pressure 3 HPS3 trips within 2 hours 3 EC4 trips within 2 hours
C4 Locked out due to Coil freeze
C4 Locked out due to high pressure 3 HPS4 trips within 2 hours Evap_coil T < Evap_coil Tsp

Table 10: Unit Alarm Codes

UNDERSTANDING LOCAL LCD

After you apply power to your Rooftop Unit (RTU), a start-up POWERING THE UNIT
countdown begins on the Unit Control Board (UCB) LCD.
When the controller is ready, the screen will be blank if no When you apply power to the unit (the C and 24V terminals),
faults are present. Use the joystick and the two push buttons the UCB begins a start-up sequence.
below the LCD, to navigate through the menus (Figure 1).
The LCD scrolls the text Johnson Controls on the top line and
JCI on the bottom line (Figure 3).

Up and down movements of the joystick move the > cursor


and scroll through the selections in the active section of the
menu (Figure 2).

Each menu selection represents


either a submenu or a property. The display backlight and green Power LED remain lit as long
Press "ENTER" to display the items as power is applied to the C and 24V terminals.
in the submenu or The red Fault LED lights, goes off briefly, and then flashes throughout the
the values of the selected property. start-up sequence. The green SA Bus LED lights briefly , During the start-up
Press "ENTER" to display sequence, the joystick, the "ENTER" button, and the Cancel button are not
the current value of the selected functional.
property. Move up or down
with the joystick to display the values After approximately 15 seconds, the green SA Bus LED does one of the
of other properties. following:
- Lights to indicate the UCB has not established communication and is
awaiting communication from SA Bus devices
- Flashes to indicate the UCB established communication
with SA Bus devices

37
YORK STELLAR Commercial Ducted split series

After the start-up sequence finishes (90 - 120 seconds), the display shows the current operating status. I.E. Idle, startup delay, cooling... on both lines if
no alarm is active. The red Fault LED stops flashing and turns off. The joystick, "ENTER", and Cancel buttons are operational.

COMMISSIONING WITH THE LOCAL LCD


Figure 5 shows the Commissioning view second level menus. The Commissioning view consists of 9 main menus and several sub-menus.

COMMISSIONING VIEW SUBMENUS

Your equipment configuration determines which menus appear in the Commissioning view. Use the joystick to move between the menu options. Press
"ENTER" to select an option. table of all menus, sub-menus and properties.

VALIDATING YOUR CONFIGURATION


Use the Details > Service > Inputs menu to ensure your configuration parameters are correct. This view shows the input values for each input. You can
view the Sensors and Coil Sensors values. If no input value appears, the input states No Input. This is a convenient way to ensure all your configuration
parameters are set and reading properly.

SIMPLICITY™ BASIC UNIT CONTROL BOARD NAVIGATION

The following information provides a step-by-step demonstration on how to navigate the basic status menu and how to change basic configuration
settings. The basic navigation steps outlined in this short demonstration applies to most menus within the Simplicity SE control.

UNDERSTANDING THE LOCAL LCD


After you apply power to your Rooftop Unit (RTU), a start-up countdown begins on the Unit Control Board (UCB) LCD. When the controller is ready, the
screen is blank because no faults are present. Use the joystick and the two push buttons below the LCD, to navigate through the menus.

Step 1 - After the start-up countdown is


Complete the first screen displayed is the “Status & Alarms” screen. When the cursor
is on the top “Status” line hit the ““ENTER””
button. This action steps the LCD display into
the status mode. Hit ““ENTER”” to view the
status menu.

Step 2 The first item under the Step 3 - When the cursor is on the “DVent-Mode” Step 4 - To exit out of the
status menu is “DVent-Mode”. This hit “ENTER” to view the status of this mode. In “DVent-Mode status screen
is the demand ventilation mode. this case a CO2 sensor is not installed, thus push “Cancel”. The screen
Demand Ventilation or DVent is disabled. returns to that shown below.

38
YORK STELLAR Commercial Ducted split series

Step 5- By pushing the joystick down, the cursor toggles to OprST if sensors are located.
(Operating Space Temp).

When the "Cancel" button is pressed multiple times to exit each menu level and the screen returns to the first "Status, Alarms"
display the next demonstration can begin.

The information below steps through the "Commissioning"menu.

Step 1- Beginning at the status/alarm screen toggle the joystick down three times. This accesses Step 2- Once commission appears next to
the “Commissioning “ screen. In this menu section various settings can be changed. the cursor, press “ENTER” to begin
Please see the menu table that follows this demonstrationfor a list of parameters that can be modified viewing parameters.

Step 3- After “ENTER” Step 4- After toggling the Step 5- At the “Clg” screen Step 6- By toggling down
is pressed the various joystick down two times once “ENTER” is pushed the twice the screen reaches
parameter sections “Clg” appears. This allows status indicates if cooling the “ClgOcc-SP” screen
appear, such as: HVAC items, such as lead-lag is engaged/disengaged or “Cooling Occupied Set
zone, Indoor Fan, Clg, and OCC/UNOCC and lead-lag is engaged/ Point”.
Htg, others. cooling set points, to be disengaged.
changed.

Step 7- After pressing Step 8- In order to change set points push the
“ENTER” at toggle switch left or right. Note: The screen
the “ClgOCC-SP” screen the flashes . left decreases the value , right
space temperature set point increases. In this demonstration the ClgOCC
appears. NOTE: set point is changed from 72F to 95F.
Only applies to units
controlled by a space sensor.

Step 9- The joystick was toggled right


to increase the set point temperature.
The screen flashes when in the
change mode. Once the desired
set point/value is reached press the
““ENTER”” button to save the value.

39
YORK STELLAR Commercial Ducted split series

UNIT OPERATION IS BASED ON CONSTANT VOLUME SEQUENCES.

Set points and Related Data

• Thermostat Only Control Enable (Tstat-Only) ON

Inputs

• 24 VAC to limit switch safety terminal LIMIT, LIM2, LIM3


• 24 VAC to Main Valve verification terminal MV
• 24 VAC to HPS1 thru HPS4 and LPS1 thru LPS4
• evaporator coil temperature sensor EC1, EC2, EC3, and EC4
• 24 VAC to terminals Y1 through Y4
• 24 VAC to terminals W1 through W4
• operational outdoor air temperature (OprOAT) from the senor to the OAT terminal or a
communicated value

Outputs

• 24 VAC from C1, C2, C3, and C4 compressor outputs


• 24 VAC from CN-Fan and CF2 condenser fan outputs
• 24 VAC from H1, H2, and H3 heat outputs
• 24 VAC from FAN

40
YORK STELLAR Commercial Ducted split series

MAINTENANCE
Outdoor unit:
The Stellar Air Cooled Condensing Units are premium quality machines with very low maintenance requirements.
Compressors used in Units are of Scroll type and are charged with the correct amount of refrigerant and lubricating oil.
Unless there is a leak in the system, no topping up is generally required.

Every 6 months
In addition to the maintenance done every three months :

• The condenser coils should be cleaned by spraying water over it at low pressure or with a brush while ensuring that the fins are not damaged.
• Check all electrical connections and tighten them if required.
• Clean all accessible electrical panels of dirt and dust. Before cleaning the control panels , ENSURE that the electrical power to the unit is
switched off.

Every 12 months
In addition to the maintenance done every six months :

• Use a proper cleaning cloth to clean fan blades and motors.


• Ensure that the unit is working properly by checking, current, voltages, pressures and temperatures.
• Check the earthing or grounding of the unit.
• Check the exterior of the unit for any signs of corrosion. Even though it is highly unlikely, if any corrosion that is seen, should be removed by
proper sanding the surface. Repaint the unit with proper touch up paint, available from YORK®.
• Check the unit for any unusual vibrations or noise, locate the cause and rectify it by changing mounts, base.

Indoor unit:

Filter Part
When cleaning the filter, beat the accumulated foreign matters off it. If required, clean it with the warm water filled with liquid detergent, dry it and
reassemble it back to the filter frame.The filter can be removed from the unit only by dissemble the cover plate in the side or on the bottom of the
filter frame.

Operating
1.Remove the filter with dust collected in the metal frame away from the slip fitting carefully. Be careful not
to dirty other parts.
2.Shake the filter and wash it in the soap solution of 40 .
3.Replace the filter if it has been damaged.
4.For the installation of a new filter, operate according to steps above in reverse order.

Fan Part
1.Before repair the internal part of the fan, switch off the control switch.
2.Check the V-belt and its tension regularly. If it is found that the tensile force applied to the belt is not enough, retighten it. For correct tension data, refer
to the Belt Tension Indicator.
3.Check the alignment of motor, fan V-belt and pulley.
4.Check whether the interior flexible device is fixed firmly.
5.Check whether the motor can operate freely.
6.Inspect the maintenance instruction provided by the motor supplier.
7.Check whether the fan can operate unobstructedly.
8.Clean the fan blade regularly.

41
YORK STELLAR Commercial Ducted split series

Fan Bearing
The double suction forward fan used in the YAH unit is designed with the sealed bearing, the normal service life of which can be up to 75,000 working
hours at least.During the constantly improvement and development, we reserve the right of changing the technical specification, size without notice in
advance.

Motor
Any maintenance should be carried out in comply according to the motor instructions. This manual is just one part of the technical information provided.

Replacement of Motor
Replace the motor from one side of the unit or after the top or side frame panel is removed.
Points for Attention during Maintenance

1.The full-time technicians should be assigned for the maintenance of the air conditioner unit and also should be responsible for the daily inspection and
regular repairing. It is necessary to formulate a strict job responsibility system and lay down operating rules to strength the regular maintenance and
service repair
2.Clean the inside of the unit regularly.
3.Check the electrical equipment of the unit regularly.
4.Lubricate the parts needing lubricating with grease additionally after 6-month to one-year operation of the
unit.
5.Before the unit is repaired, switch off the power and set a warning sign to avoid risk due to mis-operation.

Failure Analysis

Low Air Flow Rate


The actual static pressure needed in the outside of the unit is greater than the design static pressure and the air flow rate is turned into the static
pressure.Thus, the air flow rate is lower than the normal.The loose belt reduces the rotation speed of the fan, resulting in a low air flow rate.

High Air Flow Rate


The actual static pressure needed in the outside of the unit is lower than the design static pressure,and the static pressure is turned into the air flow
rate, making the air flow rate higher than the normal.The increased air flow rate makes the wind speed increase, and the unit noise level is rising
accordingly.

High-level Noise
Check whether there is a flexible connection between the air return and delivery duct; whether the lifting device is supplied with a shock absorber;
whether the wind speed at the air outlet is over high and whether there is any part loose

Belt Breaking
In this case, check whether the belt is under overtension;whether there is dis-alignment between the fan and the motor belt pulley or the belt quality is
poor..

42
YORK STELLAR Commercial Ducted split series

Proper refrigerant pipe selection and design is crucial for efficient and
reliable operation of the refrigeration system. It is also important to
INSTALLATION RECOMMENDATIONS keep liquid refrigerant/oil slugs from entering the compressor and for
assuring oil return. Over-sizing the piping reduces the refrigerant
DX LINE SIZING RECOMMENDATIONS pressure drop, but can inhibit oil return and adds unnecessary first
The piping must conform to the local codes. For the best pipe sizing cost. On the other hand, under-sizing the piping increases the
and design practices, refer to either the information in this manual or refrigerant pressure drop, which affects system performance and
the ASHRAE Refrigeration Handbook. These contain refrigerant line lowers the efficiency.
sizing for full and minimum capacities and other pertinent engineering
information for a wide application range. For best results, use long radius elbows (short radius elbows have
The tables listed below are presented for the 35, 45 and 55°F higher pressure drops) for everything except oil traps. Also, clean
saturated suction temperatures, which are typical for these systems. copper tubing for refrigeration and air conditioning application should
The tables are included at the end of this manual in the Appendix. be used throughout. Provisions must be made for piping contraction
and expansion of 3/4” per 100’ of pipe.
APPENDIX
SUCTION LINE
Table 12 – Table 12: Additional Refregirant Charge
Table 12: Capacity reduction precentage according to extra piping Table 12 shows suction line sizing recommendations, which are
length typically based on 2°F (Nominal 4.5 PSI for R-410a) loss.
Table 12: Additional oil charge according to extra piping length As was illustrated in SECTION 2 - EQUIPMENT SELECTION, a
Table 13 – Fitting Losses in Equivalent Feet of Pipe typical 2°F drop in suction pressure can reduce the system capacity by
(Screwed, Welding Flanged and Brazed Connections) about 3%. Therefore, it is good practice to design the suction piping
Table 14 – Special Fitting Losses in Equivalent Feet of Pipe with no more than a 2°F line loss at full load.
(ASHRAE).
Table 15 – Valve Losses in Equivalent Feet of Pipe (ASHRAE).
Table 16 – HGBP Line Sizing for R-410a
Keeping the condensing unit and air-handler as close
together as possible is recommended. This is important for
assuring oil return and compressor reliability.
It is also important that the total equivalent feet of piping be 150 feet or
less (Always review IOM for maximum limitations).

ACTUAL PIPING ROUTING VERSUS


ORIGINAL PIPING DESIGN
It is extremely important that the piping design on a ACCU system is
correct to assure oil is returned and liquid slugging does not result.
Often during installation, piping is not routed according to the original
designer’s specifications. Problems can often result when piping is
rerouted around obstacles. Whenever a change is made to the routing
of the piping, the installer should consult with the designer prior to
Additionally, care must be taken not to oversize the suction piping,
making the change. This will assure that the change will not affect
because oil return can be compromised to the compressors. The
system oil return or cause liquid slugging.
horizontal suction line runs should be sloped ½” per 10 linear feet in
the direction of refrigerant flow to promote moving oil toward the
compressors. Trapped sections of the suction line must be avoided.

Oil and refrigerant, which condenses in the line during off periods,
must drain into the compressor and will be boiled off by the
compressor heater. This prevents oil and liquid refrigerant slugging of
the compressors.

43
YORK STELLAR Commercial Ducted split series

Figure 8: EXAMPLES OF CORRECT AND INCORRECT TRAPPED SECTIONS OF SUCTION LINE

Figure 9: EXAMPLE OF NON-ACCEPTABLE UNDERGROUND (OR ABOVE GROUND) PIPING

44
YORK STELLAR Commercial Ducted split series

Figure 10: PIPING WITH DX COIL ABOVE COMPRESSOR


Orders should never be accepted without underground piped details LIQUID LINES
worked out, and having Application Engineering SQ (Special
Quotation) acceptance. Figure 9 offers an example of when Table 12 (see Appendix) provides liquid line sizing recommendations,
underground piping is never acceptable. which is typically based on 1°F (3 PSI) line loss for 4.75 PSI for R-
Many systems require suction risers, because the DX coil is located at 410a. Liquid lines carry liquid refrigerant from the condensing unit to
a lower level than the condensing unit. These suction risers must be the DX coil.
sized to ensure oil entrainment up the riser at the lowest step of Liquid line routing is typically not as crucial as suction line routing,
loading. In some cases double suction risers may be required. since oil is flowing with the liquid refrigerant, oil movement is not a
All suction lines with a vertical rise exceeding 3’ should have an oil trap problem. However, the line slope should always be in the direction of
at the bottom and top (inverted) of the riser. A maximum suction line refrigerant flow to assure oil flow during off periods is toward the
rise of 40’ is recommended (Always consult Application Engineering compressors. Pressure losses occur due to the filter drier, liquid line
on risers over 40 feet). Any riser in excess of 20’ should have a trap solenoid valve, sight glass, and friction in the piping.
installed mid-way up the riser (e.g. 14’ for a 28’ total rise). An inverted Typical pressure loss can be found in SECTION 6 - NECESSARY
trap should be placed at the top of a single suction riser. Use long COMPONENTS for the liquid line solenoid valve, filter/drier, and sight
radius elbows wherever possible, except when fabricating oil return glass.
traps at the bottom of the vertical riser, which should use short radius If the pressure of the liquid refrigerant falls below its saturation
45° street elbows. Short radius elbows will minimize the amount of oil temperature, some of the liquid will flash into vapor and bubbles will
trapped in the system. See Figure 11. develop in the liquid. Such vapor bubbles cause the TXV to operate
erratically, which reduces not only performance and capacity, but can
cause reliability problems.
Therefore, it is important that only liquid refrigerant reaches the TXV.
To ensure this, the liquid refrigerant should be sub-cooled by 15-17°F,
before it leaves the condenser. The sub-cooling should be adjusted
when the ACCU is operating fully loaded at the 95°F ambient and
saturated suction temperature design conditions. Keep in mind that
lower ambient temperatures will reflect higher subcooling numbers.
The liquid line piping and components must be properly sized not to
exceed 63 PSI for R-410a (maximum limits based on 11% safety at
15°F subcooling design). Liquid pressure drop (or gain) due to a
vertical section of liquid line must be taken into consideration when
determining total pressure drop (or gain) of the liquid line.
Figure 11: Suction Oil line trap The nominal value that must be included in the liquid line loss (or gain)
If the DX coil is above the ACCU, the suction piping must rise above is 0.5 PSI/foot of rise or gain (typical R-410a). To assure sub-cooled
the top of the coil to form an inverted trap. See Figure 10. The inverted liquid to the TXV, it is recommended that the DX coil be no more than
trap will keep liquid refrigerant from condensing in the evaporator, the distances above the condensing unit shown in Table 11.
during the off cycle, and draining into the compressors. An oil trap
should be installed at the bottom of the vertical rise. This is
recommended by expansion valve manufacturers to keep the oil away
from the bulb during operation.
Table 11 – Maximum Vertical Liquid Line Riser
* Includes allowance for loss on liquid line solenoid valve, filter/dryer
and sight glass. (Total 5 PSI).
** Contact application engineer when over these limits.

45
YORK STELLAR Commercial Ducted split series

Pipe Sizing , % capacity reduction, additional oil and refrigerant charge for DSUs

Pipe Length - Feet


Std. Unit Charge
Max 25 50 75 100 175
Capacity System Add. Add. Add. Add. Add.
Models SOC/ AOR AOR AOR AOR AOR
per Ref %Cap Charge/ %Cap Charge/ %Cap Charge/ %Cap Charge/ %Cap Charge/
circuit Charge/Cir Cir Liquid Suction Red (per cir) /Cir Liquid Suction Red (per cir) /Cir Liquid Suction Red (per cir) /Cir Liquid Suction Red (per cir) /Cir Liquid Suction Red (per cir) /Cir
(oz) (oz) (oz) (oz) (oz) (oz)
(lbm) lbm lbm lbm lbm lbm
YAH04B DCH090A 89,200 3.42 52 1/2 7/8 3 0.6 N/A 5/8 1 1/8 1.5 2.5 N/A 5/8 1 1/8 2 4.4 N/A 5/8 1 1/8 3 9.6 N/A 3/4 1 3/8 2 27.5 5.44
YAH05B DCH090A 94,300 3.64 52 1/2 7/8 3 0.6 N/A 5/8 1 1/8 1.5 3.9 N/A 5/8 1 1/8 2 6.7 N/A 5/8 1 1/8 3 9.6 N/A 3/4 1 3/8 2 27.5 5.55
YAH05B DCH100A 100,400 3.31 81 1/2 1 1/8 1 0.7 N/A 5/8 1 1/8 2 3.9 N/A 5/8 1 1/8 2.5 6.7 N/A 5/8 1 1/8 3.5 9.6 N/A 3/4 1 3/8 2 27.5 5.38
YAH06B DCH100A 105,900 3.53 81 1/2 1 1/8 1 0.7 N/A 5/8 1 1/8 2 3.9 N/A 5/8 1 1/8 2.5 6.7 N/A 5/8 1 1/8 3.5 9.6 N/A 3/4 1 3/8 2 27.5 5.49
YAH06B DCH120A 119,900 3.97 109 5/8 1 1/8 1 1.0 N/A 5/8 1 1/8 2.5 3.9 N/A 5/8 1 3/8 1 7.1 N/A 3/4 1 3/8 1 14.5 N/A 3/4 1 5/8 1 27.5 5.71
YAH08B DCH120A 129,700 4.41 109 5/8 1 1/8 1 1.0 N/A 5/8 1 1/8 2.5 3.9 N/A 5/8 1 3/8 1 7.1 N/A 3/4 1 3/8 1 14.5 N/A 3/4 1 5/8 1 28.6 6.53
YAH08B DCH150 74,550 10.69 56 1/2 7/8 2 0.6 N/A 1/2 7/8 3 2.4 N/A 1/2 1 1/8 1.5 4.4 N/A 5/8 1 1/8 2 9.6 0.15 5/8 1 3/8 1 19.3 5.01
YAH10B DCH150 79,450 12.90 56 1/2 7/8 2 0.6 N/A 1/2 7/8 3 2.4 N/A 1/2 1 1/8 1.5 4.4 N/A 5/8 1 1/8 2 9.6 1.26 5/8 1 3/8 1 19.3 6.11
YAH10B DCH190 89,350 16.53 56 1/2 7/8 3 0.6 N/A 5/8 1 1/8 1.5 3.9 0.20 5/8 1 1/8 2 6.7 1.64 5/8 1 1/8 2.5 9.6 3.07 3/4 1 3/8 2 27.5 12.00
YAH12B DCH190 94,050 18.08 56 1/2 7/8 3 0.6 N/A 5/8 1 1/8 1.5 3.9 0.97 5/8 1 1/8 2 6.7 2.41 5/8 1 1/8 2.5 9.6 3.85 3/4 1 3/8 2 27.5 12.77
YAH12B DCH220 98,600 17.86 56 1/2 7/8 3 0.6 N/A 5/8 1 1/8 2 3.9 0.86 5/8 1 1/8 2.5 6.7 2.30 5/8 1 1/8 3.5 9.6 3.74 3/4 1 3/8 2 27.5 12.66
YAH15B DCH220 105,000 17.97 56 1/2 7/8 3 0.6 N/A 5/8 1 1/8 2 3.9 0.92 5/8 1 1/8 2.5 6.7 2.35 5/8 1 1/8 3.5 9.6 3.79 3/4 1 3/8 2 27.5 12.71
YAH12B DCH250 110,350 18.08 85 5/8 1 1/8 1 1.0 N/A 5/8 1 1/8 2 3.9 0.97 5/8 1 3/8 1 6.7 2.41 3/4 1 3/8 1.5 9.6 3.85 3/4 1 3/8 2.5 27.5 12.77
YAH15B DCH250 114,350 18.08 85 5/8 1 1/8 1 1.0 N/A 5/8 1 1/8 2 3.9 0.97 5/8 1 3/8 1 7.1 2.61 3/4 1 3/8 1.5 14.5 6.28 3/4 1 3/8 2.5 27.5 12.77
YAH15B DCH300 138,650 24.47 110 5/8 1 3/8 1 1.0 2.76 5/8 1 3/8 1 4.1 4.28 3/4 1 3/8 1.5 10.1 7.31 3/4 1 3/8 2 14.5 9.47 3/4 1 5/8 1.5 28.6 16.56
YAH10B DCM180 87,700 7.1 52 1/2 7/8 2.5 0.6 N/A 5/8 1 1/8 1 3.9 N/A 5/8 1 1/8 2 6.7 N/A 5/8 1 1/8 2.5 9.6 N/A 3/4 1 3/8 1.5 27.5 7.26
YAH12B DCM180 95,200 7.2 52 1/2 7/8 2.5 0.6 N/A 5/8 1 1/8 1 3.9 N/A 5/8 1 1/8 2 6.7 N/A 5/8 1 1/8 2.5 9.6 N/A 3/4 1 3/8 1.5 27.5 7.31
YAH12B DCM240 113,500 7.5 81 5/8 1 1/8 1 1.0 N/A 5/8 1 1/8 2 3.9 N/A 5/8 1 3/8 1 7.1 N/A 3/4 1 3/8 1.5 14.5 0.98 3/4 1 3/8 2.5 27.5 7.48
YAH15B DCM240 120,500 8.8 81 5/8 1 1/8 1 1.0 N/A 5/8 1 1/8 2 3.9 N/A 5/8 1 3/8 1 7.1 N/A 3/4 1 3/8 1.5 14.5 1.65 3/4 1 3/8 2.5 27.5 8.14
YAH15B DCM300 148,850 8.6 109 5/8 1 3/8 1 1.0 N/A 5/8 1 3/8 1 4.1 N/A 3/4 1 3/8 2 10.1 N/A 3/4 1 3/8 2.5 14.5 1.54 3/4 1 5/8 1.5 28.6 8.62

Note:
• SOC/Cir (oz) - system oil charge available in the compressor initially. Value is per compressor
• AOR/Cir (oz) - additional oil required per circuit
• System Ref Charge/Cir (lbm) - refrigerant charge per circuit
• Add. Charge/ (per cir.) lbm - additional refrigerant charge per circuit
• N/A - if the value for AOR is "N/A", that means no additional oil is required for that length of piping
• %Cap Red- precentage capacity reduction per piping length.

Table 12 : Suction andLiquid line sizes

46
YORK STELLAR Commercial Ducted split series

BASIC TIPS FOR SUCCESSFUL DESIGNS •If the DX coil is above the ACCU, the Suction Piping must rise above
the top of the Coil to form an inverted trap. See Figure 10.
The following tips apply to all piping examples shows in
Figure 12 HOT GAS BYPASS
•Assure hot gas piping enters the distributor (or auxiliary side
Liquid Line Piping, Liquid Line Solenoid Valve, and TXV’s
connection-ASC) tap on each coil from the top.
•The total equivalent feet of piping should be 150 feet or less.
•Hot gas piping should always slope to drain into the coils.
•Slope piping toward coils for oil return during the off cycle.
•Hot gas piping should be designed to not allow oil and refrigerant to
be trapped during the off cycle. Trapping liquid and oil creates the
•Use long radius elbows to reduce pressure drop.
danger of a liquid slug when the hot gas is energized.
•Use only one liquid line solenoid valve per ACCU Refrigerant System.
•Size hot gas to approx. 100% capacity of the minimum stage of
cooling.
•Size TXV’s according to individual coil capacity. Minimum capacity
must not exceed 30% of valves rated capacity.
•Activate hot gas whenever any compressor is running. This may
involve rewiring the HGBP to be in parallel with the LLSV, providing full
•Mount TXV bulb on clean pipe at 4 or 8 o’clock position with 2 copper
time HGBP.
straps on the outlet of the respective coil. Insulate the TXV bulb.
•Ιnsulate the hot gas bypass line.
•The equalizing line for each TXV must enter the top of the suction
pipe.
•Always install check valves at the ASC side connection when multiple
branch circuits are utilized.
•See Table 11 for the Maximum Vertical Height (ft.) for the DX Coil
above the ACCU. CONTROLS
DX COILS • Avoid, when possible, running the ACCU when in economizer mode.
•DX coils in a system should always be configured for full face If operating the ACCU in economizer mode, hot gas must be installed
operation. Otherwise, TXV control and liquid slugging will damage to assure a minimum load.
compressors.

•Assure distributor nozzles are properly sized for the coil capacity.

SUCTION LINE PIPING


•The total equivalent feet of piping should be 150 feet or less.

•Slope suction piping toward the compressors for oil return and to
assure that liquid condensing in the suction line drains into the
compressors and is boiled off by the heaters. Do not allow the suction
line to create a liquid and oil trap between the coil and the
compressors.

•Use long radius elbows to reduce pressure drop except for oil traps.

•Ιnstall a P-trap on the outlet of the DX coil.

•Insulate the suction line.

•Never run suction piping underground.

•Use double risers whenever refrigerant velocity falls below 1000 FPM.

•Use inverted traps at the top of suction risers.

•Always consult Application Engineering on risers that exceed 40 feet.

•Make oil traps as small as possible in suction risers.

•Use intermediate oil traps on suction risers greater than 20 ft, located
midway on the riser.

47
YORK STELLAR Commercial Ducted split series

EXAMPLES OF ACCU-DX COIL PIPING


ARRANGEMENTS Double suction risers are shown for illustration only. Most applications
This illustration figure 12 shows one refrigerant circuit when the ACCU will need only single risers. In lieu of double suction risers, the vertical
is 20 feet or more above the AHU, DX coil. An oil trap is required mid suction riser can be downsized for proper oil entrainment at minimum
way up the vertical rise. The horizontal suction line must be sloped a reduced load, providing the overall suction line pressure drop doesn’t
minimum of ½" per 10 ft. toward the compressors for oil flow. exceed a nominal 2°F.

Note: Hot gas bypass and it’s accessories, check valve , liquid line solenoid valve , sight glass moisture equalizer are all
optional, suction gas risers are for ilustration only in case velocity<1000 FPM.
Figure 12: PIPING WHEN ACCU IS LESS THAN 20 FT. ABOVE THE DX COIL

48
YORK STELLAR Commercial Ducted split series

This illustration figure 13 shows one refrigerant circuit when the ACCU In lieu of double suction risers, the vertical suction riser can be
is at the same level as the AHU interlaced DX coil. Again the horizontal downsized for proper oil entrainment at minimum reduced load,
suction line must be sloped a minimum of ½" per 10 ft. toward the providing the overall suction line pressure drop doesn’t exceed a
compressors for oil flow. nominal 2°F.

Note: Hot gass bypass and it’s accessories, check valve , liquid line solenoid valve , sight glass moisture indicator are all
optional.

Figure 13: PIPING WHEN ACCU IS AT THE SAME LEVEL AS THE DX COIL

49
YORK STELLAR Commercial Ducted split series

This illustration figure 14 shows one refrigerant circuit when the ACCU In lieu of double suction risers, the vertical suction riser can be
is lower than the AHU interlaced DX coil. Again the horizontal suction downsized for proper oil entrainment at minimum reduced load,
line must be sloped a minimum of ½" per 10 ft. toward the providing the overall suction line pressure drop doesn’t exceed a
compressors for oil flow. nominal 2°F

Note: Hot gass bypass and it’s accessories, check valve , liquid line solenoid valve , sight glass moisture indicator are all
optional.

Figure 14: PIPING WHEN ACCU IS LOWER THAN THE DX COIL

50
YORK STELLAR Commercial Ducted split series

Table 13: FITTING LOSSES IN EQUIVALENT FEET OF PIPE (SCREWED, WELDED, FLANGED AND BRAZED CONNECTIONS)

Table 14: SPECIAL FITTING LOSSES IN EQUIVALENT FEET OF PIPE (ASHRAE)

Table 15: VALVE LOSSES IN EQUIVALENT FEET OF PIPE (ASHRAE)

51
YORK STELLAR Commercial Ducted split series

Table 16: HGBP LINE SIZING FOR R-22, R-407C AND R-410A REFRIGERANTS

52
YORK STELLAR Commercial Ducted split series

Application Considerations:

The lines should be installed so that they will not obstruct service access to the indoor coil, air handling system or
filter. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the
tubing. Care must also be used to isolate the refrigerant lines to minimize noise transmission from the equipment to
the structure. Never solder vapor and liquid lines together. They can be taped together for convenience and support
purposes, but they must be completely insulated from each other. Use long radius elbows wherever possible. Insulate
all vapor lines with a minimum of 1/2 inch of foam rubber. Liquid lines that will be exposed to direct sunlight or high
ambient temperatures such as an attic must also be insulated.

INDOOR UNIT ABOVE OUTDOOR UNIT


With this configuration, a common problem with the cooling cycle is that the amount of liquid sub-cooling varies
as operating conditions change (such as outdoor ambient). Under some conditions, it is possible that flashing
will actually occur in the liquid riser. As long as only liquid is present in the liquid riser, the liquid static pressure
loss can be calculated at 1/2 psi per foot of rise. When the indoor unit is above the outdoor unit, the pressure
loss in the liquid line during the cooling cycle will limit the amount of elevation difference allowed. Since both
friction and static head contribute to pressure loss, it can be stated that the elevation difference allowed
decreases as the total equivalent line length (horizontal plus vertical) increases. The elevation difference should
not exceed 66 ft.

OUTDOOR UNIT ABOVE INDOOR UNIT


When the outdoor unit is above the indoor unit, the static pressure gain in the liquid line vertical drop (1/2 psi per
foot) may overcome the frictional pressure loss resulting in a total pressure gain. A pressure gain in the liquid
line is not detrimental to the performance of the system. With this configuration, gas velocity in the vapor riser
must be kept above 1000 feet per minute for proper oil return and below 3000 feet per minute to avoid noise
and vibration problems.

REFRIGERANT OIL MANAGEMENT


Inherent to all refrigeration systems is the presence of refrigerant oil required for proper and continuous
lubrication of the compressor(s) bearings. All refrigeration systems, whether they are packaged or split-systems
circulate oil throughout the system due to the miscibility of refrigerant oil. Split-systems, due to their propensity
for long piping lengths, can circulate more refrigerant oil than packaged units, which can become a problem if
not recognized and managed. It is not unusual for a given system to circulate as much as 15% of the original
compressor oil charge. Yet another side-effect of long piping runs on split-systems is the aspect of system oil
logging which can occur even in the best of installations. Even the best piping practices can inadvertently create
oil traps in the system especially when elevation differences between the indoor and outdoor units occur.

53
YORK STELLAR Commercial Ducted split series

Johnson Controls provides comfortable environments wherever you


Live, Work or Travel

Whether you’re at home, in a car, or in an office or workplace, chances are there’s a Johnson
Controls product or service nearby, helping to make your environment more comfortable, safe and
sustainable.
Johnson Controls creates smart environments that improve the places where people spend most of
their time – their homes, workplaces and vehicles. We anticipate consumer needs, and then
integrate technologies, products and services to make life better and easier.
For Johnson Controls, sustain ability matters at every level and through our products, service
operations and community involvement, we promote the efficient use of resources to benefit all
people and the world. Our triple bottom line of sustain ability that is, economic prosperity,
environmental stewardship and social responsibility impacts each and every aspect of our business.
York products are now a premier brand manufactured by Johnson Controls. The acquisition of York,
gives us a unique insight into designing HVAC products that match your exact requirements. We
provide solutions for today's most critical concerns - energy efficiency, refrigerant alternatives and
indoor air quality.

Johnson Controls has a wide range of York products for residential, light commercial and
commercial applications. Our offering includes package & split air conditioners and heat pumps. In
addition, Johnson Controls offers chillers, air handling units, ventilation equipment and controls for
larger projects.
Our advanced technology is leading the way in developing efficient and environment friendly
solutions for your homes, offices and places of leisure.

Let us create the ideal environment for you

Installation, Operation & Maintenance Manual # IOM-7.525-60-1221

We reserve the right to change in part or in whole the specifications without prior notice.

Al Salem Johnson Controls (Head Office)


P.O. Box 15019 Jeddah 21444
Kingdom of Saudi Arabia
Tel.: +966 12 690 0999
Fax: +966 12 690 0909

54

You might also like