Professional Documents
Culture Documents
B0193vu e
B0193vu e
*B0193VU* *E*
B0193VU
Rev E
December 15, 2013
Invensys, Foxboro, I/A Series, SPEC 200, SPECTRUM, INTERSPEC, Micro-I/A, VIDEOSPEC, and the
Invensys logo are trademarks of Invensys plc, its subsidiaries, and affiliates.
All other brand names may be trademarks of their respective owners.
Figures................................................................................................................................... vii
Tables..................................................................................................................................... ix
Preface.................................................................................................................................... xi
Revision Information ............................................................................................................... xi
Safety Considerations ............................................................................................................... xi
Reference Documents .............................................................................................................. xi
3. Configuration.................................................................................................................... 9
System Configuration ............................................................................................................... 9
I/A Series Software v4.x vs. v6.x ......................................................................................... 10
Module Identifier (Letterbug) Assignments ........................................................................ 10
System Configuration (or System Definition) Procedure .................................................... 10
Integrated Control Configuration ........................................................................................... 11
Off-Line Integrated Control Configuration ........................................................................ 11
On-Line Integrated Control Configuration ........................................................................ 16
Fail-Safe Operation ................................................................................................................. 22
Fail-Safe Functionality ....................................................................................................... 22
Fail-Safe for Type 1 Failures – Control Integrator OFF-LINE ...................................... 22
Fail-Safe for Type 2 Failures – COMM FAIL ................................................................ 22
Fail-Safe Examples ......................................................................................................... 22
4. Equipment Installation.................................................................................................... 25
Pre-Installation Requirements ................................................................................................. 25
SSFBI Installation ................................................................................................................... 27
iii
B0193VU – Rev E Contents
5. Maintenance.................................................................................................................... 67
Operating Status ..................................................................................................................... 67
LED Indicators ....................................................................................................................... 67
Technical Support ................................................................................................................... 68
Module Return Procedure ....................................................................................................... 68
iv
Contents B0193VU – Rev E
Index .................................................................................................................................... 87
v
B0193VU – Rev E Contents
vi
Figures
1-1. Typical SPEC 200 CCM Control Integrator Subsystem Implementation ..................... 2
2-1. Local Fieldbus Cabling Configuration ........................................................................... 8
3-1. Typical Editing Display for S2CM17 Control Integrator ECB ................................... 14
3-2. Typical Control Scheme, S2CM17 with CUIC INTERSPEC Connections ............... 15
3-3. Typical Editing Display for an AIN Block .................................................................. 17
3-4. Typical Editing Display for an AOUT Block .............................................................. 18
3-5. Typical Editing Display for a PID Block ..................................................................... 18
3-6. Typical Editing Display for a Setpoint Select (AIN) Block .......................................... 19
3-7. Typical Editing Display for a Track (AIN) Block ........................................................ 19
3-8. Typical Editing Display for an Auto/Manual (CIN) Block .......................................... 20
3-9. Typical Editing Display for a Cable Interrupt (CIN) Block ......................................... 20
3-10. Typical Editing Display for a Computer Fail (CIN) Block .......................................... 21
3-11. Typical Editing Display for a Computer Status (COUT) Block .................................. 21
4-1. Typical CCM Control Integrator Subsystem Hardware Configuration ....................... 26
4-2. SSFBI Installation ....................................................................................................... 27
4-3. Cable Connections, SSFBI Powered Using Cable P0913ZY ....................................... 28
4-4. Non-Fault-Tolerant CP30/40 and Non-Redundant Fieldbus, Cable Connections ...... 29
4-5. Non-Fault-Tolerant CP30/40 and Redundant Fieldbus, Cable Connections .............. 30
4-6. Fault-Tolerant CP30/40 and Redundant Fieldbus, Cable Connections ....................... 31
4-7. TCA Termination Assembly Block Assembly and Mounting ...................................... 32
4-8. Fieldbus Cabling to the CP60 (Typical) ...................................................................... 33
4-9. Cabling Fieldbus Isolator Cards to an FCP280 Baseplate ............................................ 36
4-10. TCA Termination Block Assembly Mounting ............................................................. 37
4-11. TCA Termination Block Removal .............................................................................. 37
4-12. Remote Redundant Fieldbus Cabling (FCP280 End) ................................................. 38
4-13. Example of Extending Fieldbus in Two Directions from FCP280 ............................... 39
4-14. Cabling Fieldbus Isolator Cards to an FCP270 Baseplate ............................................ 41
4-15. TCA Cable Connection to 268 Kbps Fieldbus Splitter/Terminator ............................ 42
4-16. TCA Termination Block Assembly Mounting ............................................................. 42
4-17. TCA Termination Block Removal .............................................................................. 43
4-18. Remote Redundant Fieldbus Cabling (FCP270 End) ................................................. 44
4-19. Example of Extending Fieldbus in Two Directions from FCP270 ............................... 45
4-20. FCM100E to Splitter/Combiner to ZCP270 Cabling - Direct Connection - Overview 47
4-21. FCM100E to Splitter/Combiner to ZCP270 Cabling - Direct Connection - Wiring .. 48
4-22. Cabling Fieldbus Isolator Cards to an FCM100E Baseplate ........................................ 51
4-23. TCA Cable Connection to 268 Kbps Fieldbus Splitter/Terminator ............................ 52
4-24. TCA Termination Block Assembly Mounting ............................................................. 52
4-25. TCA Termination Block Removal .............................................................................. 53
4-26. Remote Redundant Fieldbus Cabling (FCM100E End) .............................................. 54
4-27. Example of Extending Fieldbus in Two Directions from FCM100E ........................... 55
4-28. Remote Fieldbus Cabling, SSFBI Not at End of Fieldbus Run .................................... 57
4-29. Remote Fieldbus Cabling, SSFBI at End of Fieldbus Run ........................................... 58
4-30. Module Identifier (Letterbug) Assembly and Insertion ................................................ 59
4-31. S2CM17 Jumper Locations, P0913CX Revision B ..................................................... 60
vii
B0193VU – Rev E Figures
4-32. S2CM17 Jumper Locations, P0913CX Revisions C/D and Above .............................. 61
5-1. LED Indicators ........................................................................................................... 68
B-1. Control Integrator and 2DC-J or 2DC-JR CUIC with Panel Display Station ............. 75
B-2. Control Integrator and 2DC-J or 2DC-JR CUIC without Panel Display Station ....... 76
B-3. Control Integrator and 2DC-K or 2DC-KR CUIC with Panel Display Station .......... 77
B-4. Control Integrator and 2DC-K or 2DC-KR CUIC without Panel Display Station ..... 78
B-5. Control Integrator and 2DC-Q CUIC ........................................................................ 79
B-6. Parallel Communications CCM Configuration without Panel Display Station ........... 80
viii
Tables
3-1. S2CM17 ECB Parameter Descriptions ....................................................................... 12
4-1. Cables for Connections between the Splitter/Combiners
and the FCM100E/ZCP270 ....................................................................................... 48
4-2. Control Integrator Jumper Settings, P0913CX Revision B .......................................... 60
4-3. Control Integrator Jumper Settings, P0913CX Revisions C/D and Above .................. 62
5-1. Control Integrator Operating Status LEDs ................................................................. 68
A-1. S2CM17 Input Resolution .......................................................................................... 69
ix
B0193VU – Rev E Tables
x
Preface
This document describes all aspects of the I/A Series® system SPEC 200™ CCM Control Inte-
grator subsystem, including:
♦ Configuration
♦ Installation
♦ Maintenance.
The document is intended for use by process engineering and operations personnel.
Revision Information
For this revision of the document (B0193VU-E), the following changes were made:
Global
♦ Added Field Control Processor 280 (FCP280).
Preface
♦ Moved “Reference Documents” on page xi to this chapter.
Chapter 1 “Concept and Overview”
♦ Added the FCP280 to “I/A Series Hardware/Software Support” on page 3 and “Ter-
minology” on page 3.
Chapter 3 “Configuration”
♦ Updated “System Configuration” on page 9.
♦ Added FCP280 to “I/A Series Software v4.x vs. v6.x” on page 10.
Chapter 4 “Equipment Installation”
♦ Added “Fieldbus Cabling at the FCP280” on page 34.
Appendix D “FCP280 or FCP270 Upgrade”
♦ Added the FCP280.
Safety Considerations
Safe use of this product depends largely upon proper installation, use, and maintenance by you,
the customer. This manual provides the information needed to properly install, use, and maintain
the SPEC 200 CCM Control Integrator subsystem.
Reference Documents
You should be familiar with the I/A Series documentation listed below:
♦ Field Control Processor 280 (FCP280) User’s Guide (B0700FW)
♦ Field Control Processor 280 (FCP280) Upgrade Guide (B0700GC)
♦ Field Control Processor 270 (FCP270) User’s Guide (B0700AR)
xi
B0193VU – Rev E Preface
xii
1. Concept and Overview
This chapter provides an overview of the SPEC 200™ CCM Control Integrator subsystem,
including its function, specifications, and components. It also provides a general overview of
planning an I/A Series® system.
The I/A Series system SPEC 200 CCM Control Integrator subsystem provides a means of migrat-
ing control of SPEC 200 loops from the Controller Communication Module (CCM) equipment
rack to the I/A Series system. As part of the equipment upgrade, Control Integrators plug directly
into CCM rack in place of the existing control cards, Models 2AX+A4 and 2AX+A5. All CCM
configurations1 (INTERSPEC™, SPECTRUM™, and parallel communications CCMs) are sup-
ported, and all associated functions remain unaffected:
♦ All associated Control Unit Interface Cards (CUIC) can remain in place.
♦ INTERSPEC/SPECTRUM system communication with VIDEOSPEC™ systems or
a host computer can remain unaffected.
♦ SPEC 200 control stations associated with the affected control loops may remain in
use.2
♦ SPEC 200 field interface modules and I/O wiring are unaffected.
The Control Integrators pass 0 to 10 volt process measurement and output signals between an
I/A Series control station and the CCM. I/A Series control and management software provides
advanced control, display, and system management capabilities for the affected control loops.
Connection between the newly mounted Control Integrators and the I/A Series control station is
via the I/A Series Fieldbus, which can be implemented in either a single or redundant configura-
tion. Figure 1-1 shows a typical CCM Control Integrator subsystem.
The CCM Control Integrator subsystem consists of the following components:
♦ S2CM17 Control Integrator – Serving as a replacement for the 2AX+A4 or 2AX+A5
control card, this component passes the 0 to 10 volt measurement and output signals
to/from the I/A Series control station via the Fieldbus. It provides four analog (0 to 10
volt) inputs, two analog (0 to 10 volt) outputs, four logic (contact) inputs, and four
logic (contact) outputs. For detailed hardware specifications, refer to Appendix A
“Hardware Specifications”.
♦ SPEC 200 Single Fieldbus Isolator (SSFBI) and redundant SPEC 200 Dual Fieldbus
Isolator (SDFBI) – These components provide isolation between the local Fieldbus,
which interconnects the Control Integrators, and the remote Fieldbus, which con-
nects to the I/A Series control station. The SSFBI (or SDFBI, which consists of two
SSFBIs) mounts in the area of the CCM’s connector panel. A minimum of one SSFBI
module per CCM rack is required. For detailed hardware specifications, refer to
Appendix A “Hardware Specifications”.
1. Serial communications CCMs (INTERSPEC and SPECTRUM) include model codes 2DNC-A,
2DNC-B, and 2DNC-C; parallel communications CCMs are model coded 2DNU-C.
2. If the CCM configuration uses a 240SJ/261PJ station with a Model 2DC-J CUIC, there is no loop
manual operation support from the 240SJ/261PJ station once migration to S2CM17 control is
completed.
1
B0193VU – Rev E 1. Concept and Overview
Fieldbus Cable A
*
Fieldbus Cable B
*
To I/A Series
Control Station *
A B
BUS
RUN SSFBI A
Control Integrators
FAIL
SSFBI
(S2CM17s)
A B
BUS
Cables**
P0913ZY P0913ZZ
To
Control Station To CCM To Next To Available Connectors
(If Applicable)***
Connector Panel Control Integrator (J1 - J16)***
(If Applicable) on CCM Connector Panel
* Terminating resistors (not shown) are used at both ends of the remote Fieldbus.
** The use of either CUIC interconnection cable (P0913ZY or P0913ZZ) is required to provide
communication between the Control Integrator and the CUIC. (P0913ZY also provides
connection to the control station, if applicable.) If no CUIC is present, neither cable is used.
*** If a connector (J1 - J16) is not available for powering an SSFBI, the control station
connector on cable P0913ZY can be used for this purpose. (Provided, of course, it is not used
for connection to a control station.)
Figure 1-1. Typical SPEC 200 CCM Control Integrator Subsystem Implementation
♦ CUIC interconnection cables – Two different cables are provided for interconnection
of control signals between the Control Integrator and the associated CUIC:
2
1. Concept and Overview B0193VU – Rev E
NOTE
For the Control Processor 60, I/A Series software v6.3.2, v6.5 and higher are
required for CCM Migration Integrator support. I/A Series software v6.4 does not
include this support for the CP60. However, I/A Series software v6.4 supports all
other competitive migration products. For the FCP280, I/A Series software v9.0 (or
higher) is required. For the FCP270, I/A Series software v8.1.1 (or higher) is
required.
Terminology
This document uses certain terms specific to the CCM Control Integrator subsystem. Under-
standing these terms is essential to understanding this document:
Control Station Any I/A Series module, application workstation, or subsystem that effects
process control via the I/A Series Fieldbus. Examples include the Control
Processors, WSTA70s (70 Series workstations), WSVR70s (70 Series serv-
ers), 50 Series Application Workstations, 70 Series Application Worksta-
tions, and Micro-I/A®. The control station controls process variables
3. If
the CCM configuration uses a 240SJ/261PJ station with a Model 2DC-J CUIC, there is no loop
manual operation support from the 240SJ/261PJ station once migration to S2CM17 control is
completed.
3
B0193VU – Rev E 1. Concept and Overview
FBM Fieldbus Modules (FBMs) provide the interface between process sen-
sors/actuators and the Fieldbus in a standard I/A Series system.
Fieldbus An optionally redundant serial bus conforming to the EIA standards gen-
eral requirements for RS-485. The Fieldbus carries data communications
on a twinaxial cable between the I/A Series input/output modules on the
Fieldbus (Fieldbus Modules, FBP Integrators, and so forth), and their
associated control stations.
Letterbug In the I/A Series system, a letterbug is a label consisting of six interlocked
plastic characters with pin connectors at the back, that are read electrically
by the computer and visually by the user. The letterbug for the FCP280 is
set via the buttons on its faceplate. The FCP270, ZCP270 FCM100Et,
and FCM100E use the Letterbug Configurator to electronically set and
read the letterbug.
Planning Ahead
Personnel who should be involved with the planning process include sales support personnel, sys-
tem engineers, software engineers, and process control engineers. For throughput and sizing infor-
mation tailored to your system, consult your Foxboro engineering or sales support representative.
There are three major areas of concern when planning a system:
♦ System Configuration – During system configuration you select and define the hard-
ware and software for your system. The end product of this configuration is a diskette
that defines the network equipment packaging, documents the configuration, pro-
vides a list of material for the Quotation System, and enables software installation.
Prior to undertaking this configuration, you should determine the number and types
of loops and blocks in your process control scheme. Determine memory and through-
put requirements based on block definition, scan rates, and other block-related
functions that can affect the number and selection of hardware items.
♦ Process Control Configuration – With the FCS Configuration Tools, Integrated Con-
trol Configurator (ICC) or the I/A Series Configuration Component (IACC), you
define compounds, blocks (continuous and sequential) and ladder logic. Lay out the
schemes for your compounds and blocks prior to actually performing a configuration
on the system. Use the resulting information in conjunction with information on the
4
1. Concept and Overview B0193VU – Rev E
System Configuration worksheets to arrive at a final plan for hardware and software,
and a final process control strategy.
♦ Equipment Installation – Equipment installation does not require any special tools.
However, it does require a basic knowledge of I/A Series Nodebus and Fieldbus hard-
ware concepts.
5
B0193VU – Rev E 1. Concept and Overview
6
2. Product Implementation
This chapter covers the implementation of the SPEC 200 CCM Control Integrator subsystem,
including Fieldbus Isolators, their location and powering, and remote and local Fieldbus
definitions, locations, and specifications.
Up to 16 S2CM17 Control Integrators may be installed on the local Fieldbus (see Figure 2-1).
Implementation of the CCM Control Integrator subsystem need not affect current SPEC 200
process configuration or wiring. No rewiring of process control signals is required. The existing
Control Unit Interface Cards (CUICs) are reused if INTERSPEC system interfaces (display sta-
tions, VIDEOSPEC systems, or supervisory computer) are to remain.
Upon implementation of the CCM Control Integrator subsystem, all operator adjustments pro-
vided by the original SPEC 200 display stations may be replaced by I/A Series workstation func-
tions. However, the SPEC 200 control stations may be reused by simply connecting a Foxboro
supplied cable (P0913ZY) between the display station and the newly installed S2CM17 Control
Integrator. (Use of the CUICs is required when INTERSPEC system communications are to
remain effective and/or the SPEC 200 display stations are to be used.)
The CCM Control Integrator subsystem can be configured to interface with any standard
I/A Series control station, 50 Series Application Workstation, 70 Series Application Workstation,
or Micro-I/A system). The CCM Control Integrator subsystem operates with any version of the
standard I/A Series software.
Fieldbus Isolators
The Fieldbus Isolators (SSFBIs) must be located in the same rack (CCM rack) as the connected
Control Integrators. They may be mounted on the CCM rack rails along either side of the con-
nector panel, and are powered from spare connectors on the CCM connector panel.
7
B0193VU – Rev E 2. Product Implementation
non-redundant Fieldbus communication is opted for, SSFBI B is omitted and the “B” portion of
the local Fieldbus cabling, while connected to the Control Integrators, remains unused.
Local Fieldbus
Cable (P0913ZX)
S2CM17
CUICs (Reused
Control Integrator
from Original
(1 of up to 16)
Hardware
Configuration)*
A B Cable Connector A B
Marked “A”
BUS
* CUICs are reused if INTERSPEC system communication and/or SPEC 200 control
station interfacing is required.
8
3. Configuration
This chapter provides procedures for configuring your I/A Series system, including assigning
letterbugs and using System Configurator or System Definition to perform an off- or on-line
integrated control configuration. This chapter also covers the functionality of fail-safe
operation.
In general, configuration means specifying, to the I/A Series system software, the types of hard-
ware and software modules that comprise the newly added CCM Control Integrator subsystem,
and the control blocks that will be used in conjunction with it. Prior to performing configuration
procedures, you must develop loop drawings to determine the control scheme, and a detailed
equipment plan that identifies all the equipment required to control the process.
System Configuration
NOTE
1. To minimize interruption of the process, it is advisable to perform System Con-
figuration (or System Definition) prior to installing the CCM Control Integrator
subsystem equipment, as described in Chapter 4 “Equipment Installation”.
2. If the host I/A Series system is on-line (currently controlling the process), it may
be desirable to perform Integrated Control Configuration on-line, prior to updating
the System Configuration. With this method, process control using the CCM Con-
trol Integrator subsystem equipment can commence immediately (following equip-
ment installation), with the System Configuration update being deferred until a
more convenient time.
To perform Integrated Control Configuration on-line, refer to “On-Line Integrated
Control Configuration” on page 16.
System Configuration (or System Definition) is the process of selecting and identifying the hard-
ware and software for a particular I/A Series system. It is initially performed prior to installation
of the system equipment, and it is updated with any hardware/software system changes.
♦ For a step-by-step procedure for defining an I/A Series system configuration using the
System Definition (SysDef ) software, refer to System Definition: A Step-By-Step Proce-
dure (B0193WQ).
♦ IACC allows you to import system configuration information from an I/A Series sys-
tem using SysDef Export media created with a previous instance of the System
Definition configuration application. For importing procedures, refer to I/A Series Sys-
tem Configuration Component (IACC) User's Guide (B0700FE).
♦ To use the Foxboro Control Software (FCS) Configuration Tools to define the system,
refer to the “System Development” and “Security” manuals listed under “Foxboro
Control Software and I/A Series System Specific Documentation” in Foxboro Control
Software Deployment Guide (B0750BA). Refer to Foxboro Control Software Hardware
Configuration User’s Guide (B0750BB) to define the I/A Series hardware.
9
B0193VU – Rev E 3. Configuration
Reports produced by System Configuration (or System Definition) define the network, define the
overall packaging of the system, and provide information that may be used in conjunction with
equipment installation and system quotation. The System Configuration database can be updated
at any time to reflect changes made to the initial hardware layout.
10
3. Configuration B0193VU – Rev E
The Integrated Control Configurator, which is accessed through the process engineer’s environ-
ment at an I/A Series workstation, allows you to configure control blocks relating, in this case, to
the CCM Control Integrator subsystem equipment. The general procedure is to create a com-
pound name under which the blocks will be created and run, and then create and integrate the
desired control blocks.
Using the Control Configurator, you create an Equipment Control Block (ECB) for each
S2CM17 in the CCM Control Integrator subsystem. The ECB serves as a “holding place” for the
device’s software data. You then go on to configure the necessary control blocks and compounds
for the desired control scheme.
The Control Configurator lets you modify configuration data for on-line stations (for example, a
CP) or off-line library volumes. (A library volume is a “dummy” configuration which may be
loaded into the CP when creation and/or editing are completed.) As a compound/block editor,
the Control Configurator provides compound/block-building templates along with a full range of
editing functions.
Integrated control configuration for the CCM Control Integrator subsystem is divided into two
separate procedures:
♦ “Off-Line Integrated Control Configuration” on page 11 is intended for use when a
new system is being configured – typically, when the CCM Control Integrator subsys-
tem is being included in new (overall) system configuration.
♦ “On-Line Integrated Control Configuration” on page 16 is intended for use when a
previous I/A Series configuration is being updated to include the CCM Control Inte-
grator subsystem.
NOTE
As indicated in the note on page 9, if the host I/A Series system is on-line (currently
controlling the process), it may be desirable to perform Integrated Control Config-
uration on-line, prior to updating the System Configuration. If this is the case, refer
to “On-Line Integrated Control Configuration” on page 16.
11
B0193VU – Rev E 3. Configuration
NOTE
1. This procedure assumes that system configuration (or System Definition) has
been performed (see “System Configuration” on page 9).
2. This procedure is intended for use with an I/A Series system having Version 4.0
or higher software. If your system has software of a previous version, refer to the
appropriate version of the I/A Series Integrated Control Configurator document
(B0193AV), and configure the S2CM17 in a manner similar to an FBM17. Use the
ECB parameters shown in Table 3-1 and block parameter settings shown in
Figure 3-2 on page 15.
1. Using the System Management displays (accessible at an I/A Series workstation), boot
up the CP to which the CCM Control Integrator subsystem equipment will be
attached. This creates two compounds:
♦ Station compound (cplbug_STA)1 containing the station block
(cplbug_STA_STATION)1
♦ ECB compound (cplbug_ECB)1 containing the primary ECB
(cplbug_ECB:PRIMARY_ECB).1
2. Access the Integrated Control Configurator. From the Process Engineer’s environ-
ment, select Config and then Control_Cfg.
3. Use the Control Configurator’s Fix All function to create ECB(s) for the Control
Integrators added previously to the system configuration via the System
Configurator.
4. If required, edit the S2CM17 ECB(s) if the default parameters provided are not satis-
factory. (See NOTE immediately following this step.) Figure 3-1 shows a typical edit-
ing display for the S2CM17 Control Integrator ECB. Table 3-1 describes the
S2CM17 ECB parameters.
NOTE
For ready reference, ECB parameter information appears in a “show window” along
the right side of the ECB editing displays (see Figure 3-1). The show window is
accessed by selecting Show in the menu bar, and then selecting Legal FBM/ECB
Combos.
Parameter Description
NAME User-defined 12-character (maximum) name
TYPE ECB type: ECB9
DESCRP 32-character description of the ECB
PERIOD Scan period (minimum is 0.5 seconds)
PHASE Desired scan phase
1.
The CP letterbug (cplbug) is filled in by the station being configured.
12
3. Configuration B0193VU – Rev E
Parameter Description
DEV_ID Derived from S2CM17 letterbug
HWTYPE Hardware type: 17
SWTYPE Software type: 9
EXTYPE Not applicable
FSENAB Enables the fail-safe setting (0 = No, 1 = Yes)*
FSDLAY Delay time for communications to have ceased before the fail-safe values
are asserted on outputs. Default = 1000 (10 seconds).*
BUSWDS Bus Switch Disable. Enables (= 0) or disables (= 1) S2CM17 I/A Series
Fieldbus switching.
BADRNG Determines whether raw count violations will cause the channel status to
be set bad, and, if so, whether high, low, or both types of violations will be
considered.
RES02/09 Resolution. (See Table A-1, “S2CM17 Input Resolution” on page 69.)
FPM09 Filter Period Main*
FSMM02/09 Fail-safe Mask Main*
FSDM09 Fail-safe Data Main*
FSnD0n Fail-safe fallback value for channel n output. For example, FS5D02 is
Channel 5 data for ECB type 2.*
SMPM09 Sustain-Momentary-Pulse mask for ECB type 9**
P13N09 Pulse, Channel 13 on time for ECB Type 9**
P13F09 Pulse, Channel 13 off time for ECB Type 9**
ROCn Rate-of-change limit for Channel n**
* For additional information, refer to “Fail-Safe Operation” on page 22.
** For additional information, refer to the I/A Series Integrated Control Block Descriptions
document (B0193AX).
NOTE
Figure 3-3 through Figure 3-11, referenced below, are examples only. Actual param-
eter settings require specific application engineering expertise. Contact your local
Foxboro field service representative for further information.
13
B0193VU – Rev E 3. Configuration
Figure 3-3 through Figure 3-5 show typical block editing displays for a simple control loop (AIN,
AOUT, and PID blocks).
Figure 3-6 through Figure 3-11 show typical block editing displays for blocks that are required for
interfacing the Control Integrator with the CUIC and maintaining communication with existing
stations (for example, VIDEOSPEC systems, control stations, or a supervisory control computer).
These include Selected Setpoint (AIN block), Track (AIN block), Auto/Manual (CIN block),
Cable Interlock (CIN block), Computer Fail (CIN block), and Computer Status (COUT block).
For additional information on maintaining communication with existing INTERSPEC inter-
faces, contact Foxboro application engineering.
Figure 3-1. Typical Editing Display for S2CM17 Control Integrator ECB
14
3. Configuration B0193VU – Rev E
Input
S2CM17
To/From
ECB09
CUIC
Process Switch
CIN
Input
Switch
CIN
C Input
O Switch
N CIN
Input
T Switch
A CIN
C Output CALC
T Switch
COUT
Output
I Switch
/ COUT
Output
O Switch
COUT
Output
Switch
COUT
Main Logic
Control Compound
SPEC 200/CCM Equipment Rack (I/A Series Software)
PNT PNT
No S2CM17 FBM17** Function No S2CM17 FBM17** Function
1 AI1 AI1 Measurement 8 CI2 CI2 Comp. On/Off from Disp.
2 AI2 AI2 Select Setpoint 9 CI3 CI3 Cable Interlock
3 AI3 AI3 Track In 10 CI4 CI4 Auto/Manual from CUIC
4 AI4 AI4 Unselect Setpoint 11 CO1 CO1 Comp. On/Off from I/A
5 AO1 AO1 Out 12 CO2 CO2 Rem/Loc or SP/OP
6 AO2 AO2 I/A Setpoint 13 CO3 CO3 Pulse On/Off
7 CI1 CI1 Fail to Disp. 14 CO4 CO4 Ramp Up/Down
Figure 3-2. Typical Control Scheme, S2CM17 with CUIC INTERSPEC Connections
15
B0193VU – Rev E 3. Configuration
NOTE
This procedure is intended for use with an I/A Series system having Version 4.0 or
higher software. If your system has software of a previous version, refer to the appro-
priate version of the I/A Series System Configurator document (B0193JH), and con-
figure the S2CM17 in a manner similar to an FBM17. Use the ECB parameters
shown in Table 3-1 on page 12 and block parameter settings shown in Figure 3-2.
1. Using the System Management displays (accessible at an I/A Series workstation), boot
up the CP to which the CCM Control Integrator subsystem equipment will be
attached. This creates two compounds:
♦ Station compound (cplbug_STA)2 containing the station block
(cplbug_STA_STATION)2
♦ ECB compound (cplbug_ECB)2 containing the primary ECB
(cplbug_ECB:PRIMARY_ECB).2
2. To access the Integrated Control Configurator, from the Process Engineer’s environ-
ment, select Config and then Control_Cfg.
3. Using the Control Configurator’s Insert New Block/ECB function, create an ECB
for each S2CM17 Control Integrator in the subsystem.
4. Access the editing displays for the newly created S2CM17 ECBs (see Figure 3-1 on
page 14) and set the parameters (refer to Table 3-1 on page 12).
NOTE
For ready reference, ECB parameter information appears in a “show window” along
the right side of the ECB editing displays (see Figure 3-1 on page 14). The show
window is accessed by selecting Show in the menu bar, and then selecting Legal
FBM/ECB Combos.
2.
The CP letterbug (cplbug) is filled in by the station being configured.
16
3. Configuration B0193VU – Rev E
Figure 3-3 through Figure 3-5 show typical block editing displays for a simple control
loop (AIN, AOUT, and PID blocks). Figure 3-6 through Figure 3-11 show typical
block editing displays for blocks that are required for interfacing the Control Integra-
tor with the CUIC:
Setpoint Select (AIN block)
Track (AIN block)
Auto/Manual (CIN block)
Cable Interrupt (CIN block)
Computer Fail (CIN block)
Computer Status (COUT block).
NOTE
For additional information on maintaining communication with existing INTER-
SPEC interfaces, contact Foxboro application engineering.
17
B0193VU – Rev E 3. Configuration
18
3. Configuration B0193VU – Rev E
Figure 3-6. Typical Editing Display for a Setpoint Select (AIN) Block
19
B0193VU – Rev E 3. Configuration
Figure 3-9. Typical Editing Display for a Cable Interrupt (CIN) Block
20
3. Configuration B0193VU – Rev E
Figure 3-10. Typical Editing Display for a Computer Fail (CIN) Block
Figure 3-11. Typical Editing Display for a Computer Status (COUT) Block
21
B0193VU – Rev E 3. Configuration
Fail-Safe Operation
Fail-safe parameters in the controlling ECB (S2CM17) specify the outputs in the event of a break
in communication with the I/A Series control processor (CP). All fail-safe operations are initiated
by the S2CM17 Control Integrator.
Each time the Control Integrator receives a write request, it resets a fail-safe timer for its ECB.
The Control Integrator asserts a fail-safe condition if it does not receive another output command
within a specified time. The fail-safe condition can be either of the following:
♦ Hold the current output value, that is, the value sent in the most recent output com-
mand from the CP.
♦ Use a value specified for the output (value specified in the ECB).
The ECBs for the Control Integrators include parameters for enabling and disabling the fail-safe
function and for setting a fail-safe delay for the outputs. When a fail-safe condition is enabled for
a specific output, the Control Integrator asserts fail-safe actions. When normal operation resumes,
the current output values are read by the CP and stored in the ECBs. These values, in turn, are
used by the I/O blocks as the starting point for new output commands.
Fail-Safe Functionality
What the Control Integrator does during various failed conditions is dependent upon two condi-
tions: configuration of several fail-safe parameters, and the type of failure. Two basic types of Con-
trol Integrator failures can occur: those that cause the Control Integrator to go off-line (such as
EEPROM update or download), and those that cause loss of communications (COMM FAIL).
Fail-Safe Examples
The following examples are fail-safe operations for a S2CM17 type I/O ECB with analog outputs.
The operation is performed for the first output point, which is point number 1. An AOUT block
is used, and the output is driven at a value of 75 percent of full scale. The fallback value is config-
ured to be 25 percent of full scale (FSD01 = 16000). FSDLAY is set to 1000, which is equal to a
delay time of 10 seconds.
22
3. Configuration B0193VU – Rev E
23
B0193VU – Rev E 3. Configuration
24
4. Equipment Installation
This chapter provides detailed procedures for installing and configuring the SPEC 200 CCM
Control Integrator subsystem. A general installation checklist is also included in this chapter.
A typical CCM Control Integrator subsystem configuration is shown in Figure 4-1. Use this fig-
ure as a general reference when performing the following installation procedures.
Pre-Installation Requirements
Before starting the actual equipment installation (as described in the following subsections) per-
form the following:
1. Determine, from system engineering and sales order documentation, which A-4 con-
trol cards are to be replaced with Control Integrators. Also, determine the module ID
(letterbug) numbers the replacement Control Integrators will contain.
2. Perform the system configuration for the new (soon to be installed) Control Integra-
tors (refer to Chapter 3 “Configuration”).
3. Perform the integrated control configuration for the new (soon to be installed) Con-
trol Integrators (refer to Chapter 3 “Configuration”).
4. The procedures in this chapter assume that power is removed from the CCM rack.
! CAUTION
When removing power from the CCM rack, ensure that such action does not
adversely affect the process under control.
25
B0193VU – Rev E 4. Equipment Installation
To I/A Series
Control Station
TERM
TERM
See Notes 2 and 3
A B A B A B A B
BUS BUS BUS BUS
Notes:
1. Up to 16 Control Integrators are allowed per SSFBI (or redundant SSFBI pair).
2. Termination resistors are required if the SSFBIs are the last devices in the Fieldbus run.
Installation is described later in this chapter.
3. The remote Fieldbus shield(s) must be earthed at the last device(s) in the Fieldbus run.
Earth cable connections are described later in this chapter.
4. A close connection must be made between the earth bus bar and building steel
(or a driven earth rod) to provide the necessary electrostatic discharge and
electromagnetic interference (EMI) drain.
Figure 4-1. Typical CCM Control Integrator Subsystem Hardware Configuration
26
4. Equipment Installation B0193VU – Rev E
SSFBI Installation
1. Referring to Figure 4-2, install the SSFBI A as shown.
2. Referring to Figure 4-2, connect the SSFBI power cable to any unused display station
connector (J1-J16). If one of these connectors is not available, power the SSFBI using
display interface cable P0913ZY. See Figure 4-3 for connection details.
3. If applicable, repeat Steps 1 and 2 for the other SSFBI (SSFBI B), mounting it on the
left rail.
4. Set the A/B bus indicator (shown in Figure 4-2) to the proper position on each of the
SSFBIs. (The SSFBI on the right is SSFBI A, and the one on the left is SSFBI B.)
Note: This indicator is for operator reference only; it has no switching function.
A B
BUS
Nut Clip
RUN
FAIL
(X0169LF)
SSFBI
SSFBI A
Bracket
Note: 10 x 32 Screw
(P0914BW)
If a second SSFBI 10 x 32 Screw (X0127DF)
(SSFBI B) is to be (X0127DF)
included, install it SSFBI A Power Cable – Connect to any available
here in like manner. connector, J1 to J16. If connector is not available,
power SSFBI using display station interface cable
P0913ZY. (See next figure for connection details.)
27
B0193VU – Rev E 4. Equipment Installation
From S2CM17
Control Integrator
Display Interface From SSFBI
Cable P0913ZY
Power Cable
To CCM (Part of SSFBI)
Connector Panel
28
4. Equipment Installation B0193VU – Rev E
4. If the termination resistor (supplied with each TCA) is not already in place, add it as
shown in Figure 4-4, Figure 4-5, or Figure 4-6.
CP Term. Cable
Assembly P0800DB
A B C D
Note 1
Note 2
Blk
1 2 3 To
Wht
Shield 100 Ω Twinaxial SSFBI
Non-Fault 1 2 3
Tolerant Cable P0170GF, P0170GG,
CP30/40 Or Equivalent
F F- S
F F- S
Notes:
Field 1. Route cable over strain relief bracket
Note 3 and secure using cable tie.
Bus PO
2. Wire colors shown (black and white)
are for reference only (actual colors
may vary).
3. Attach earth strap to screw on DIN rail.
29
B0193VU – Rev E 4. Equipment Installation
Field Field
Bus Note 3 Bus Note 3
PO PO
Notes:
1. Route cable over strain relief bracket and
secure using cable tie.
2. Wire colors shown (black and white) are for
reference only (actual colors may vary).
3. Attach earth strap to screw on DIN rail.
30
4. Equipment Installation B0193VU – Rev E
Field Field
Bus Note 3 Bus Note 3
PO PO
Notes:
1. Route cable over strain relief bracket and
secure using cable tie.
2. Wire colors shown (black and white) are for
reference only (actual colors may vary).
3. Attach earth strap to screw on DIN rail.
31
B0193VU – Rev E 4. Equipment Installation
Earth
Wire
TCA
Termination
Block
Strain
Relief
Bracket
DIN Rail
32
4. Equipment Installation B0193VU – Rev E
NOTE
Refer to Appendix C “CP60 Upgrade” for information regarding control processor
upgrades from CP30/CP40 to CP60.
Ethernet Trunk
DCM10E
Fieldbus (10Mbps)
From CP60 Converters
TCAs (P0903VY) 2
(Fault - Tolerant (P0926DJ) 1 2
pair) B A
F+
A
F-
SH
SH
F-
F+
24V dc -
+
3
T-Connectors
(P0912ZV)
F+
B
F-
SH
SH
F-
F+
24V dc -
+
3
Connect StoSSSFBI as described in
HDLC F- F
- FCabling, SSFBI
B A
Fieldbus F
End” on page 55
To other DCM10E/ (268.75 Kbps) RU N
F AI L
or terminate using
P0912SY terminators.
SSFBI
(A or B)
I/A Series Equipment Rack
CCM Equipment Rack
Notes:
1 A configuration using DCM10Ef converters (P0926DP) is similar, but with the Ethernet Trunk fiber optic
cables connecting to the ST type connectors on the units.
2 Terminating resistors, included with the DCM10E/DCM10Ef converters and the corresponding TCAs, are
used only if these devices exist at the ends of the Fieldbus run.
3 If the TCAs are the last TCAs in the Fieldbus run, the Fieldbus shields must be connected to
the earth bus bar in the equipment rack (which, in turn, must be connected to solid earth ground).
Check to ensure that these connections are in place.
33
B0193VU – Rev E 4. Equipment Installation
NOTE
The Fieldbus splitter (RH928CV) is used instead of the two legacy TCAs
(P0903VY) and the Extended Fieldbus Splitter/Terminator (P0926LC), which are
used with legacy control processors for their twinaxial cabling.
Before starting this procedure, plan which Fieldbus port on the FCP280 baseplate you will
connect the TCA cable to. The FCP280 considers the S2CM17 as a 100 Series FBM17, so it
must connect to the SSFBI from a Fieldbus port on the FCP280 baseplate which is dedicated to
268 Kbps HDLC fieldbus connections. Each fieldbus port on the FCP280 baseplate may connect
to either 100 Series or 200 Series modules exclusively - not both.
You can mount the FCP280 module(s) on either the two-position, vertical DIN rail mounted
baseplate (RH924YF) or the two-position, horizontal DIN rail mounted baseplate (RH924YL).
For FCP280 baseplate mounting procedures, refer to DIN Rail Mounted Subsystem User's Guide
(B0400FA). For FCP280 installation procedures, refer to Field Control Processor 280 (FCP280)
User’s Guide (B0700FW).
NOTE
Refer to Appendix D “FCP280 or FCP270 Upgrade” for information regarding
control processor upgrades from CP30/CP40 to FCP280.
NOTE
If you intend to use an FBI200 to extend the twinaxial cabling to the SSFBI TCA
from the FCP280 baseplate, refer to DIN Rail Mounted Subsystem User's Guide
(B0400FA) for site planning and installation instructions.
34
4. Equipment Installation B0193VU – Rev E
2. Connect the splitter (RH928CV) to the appropriate port on the FCP280 baseplate.
The splitter includes both a plug for the Fieldbus port and the TCA termination block
which you installed in the previous step (see Figure 4-9). Refer to “Fieldbus Splitter
(RH928CV)” in DIN Rail Mounted FBM Subsystem User’s Guide (B0400FA) for
instructions on how to make this connection.
If you are upgrading a legacy control processor with an FCP280 and the site has two
P0903VY TCAs on it, be sure to remove the P0903VY TCA termination blocks
before installing the splitter, as explained in Figure 4-11.
Finish making the cable connection(s) to the fieldbus splitter/terminator or fieldbus
splitter as shown in Figure 4-9 and described in “Remote Fieldbus Cabling, SSFBI
End” on page 55.
3. Make the fieldbus cable connections between termination cable assemblies (see
Figure 4-12).
4. Terminate the HDLC fieldbus according to the following rules:
♦ Terminating resistors are used only at the SSFBI TCA end of the bus. Add the ter-
minating resistors (supplied with the termination cable assemblies) to the
P0903VY termination cable assemblies as shown in Figure 4-9.
♦ To terminate Fieldbus port 1 in the FCP280 baseplate end of the HDLC fieldbus
(if needed), set both the termination DIP switches on the FCP280 baseplate to
“ON”, as described in “Setting Termination Switches for FCP280 Baseplates” in
Field Control Processor 280 (FCP280) User’s Guide (B0700FW).
Fieldbus ports 2-4 in the FCP280 baseplate are terminated internally and do not
require any external hardware for termination. No action is needed to terminate
the FCP280 baseplate end of the HDLC fieldbus for Fieldbus ports 2-4.
♦ The Fieldbus can be extended in two directions from the FCP280. (Refer to
Figure 4-13 on page 39.)
5. Connect an insulated 14 AWG green wire between connection point 3 (shield) on the
last Fieldbus Isolator termination cable assembly (or assemblies) and the earth bus in
the enclosure. For I/A Series system earthing requirements, refer to Power, Earthing
(Grounding), EMC and CE Compliance (B0700AU).
35
B0193VU – Rev E 4. Equipment Installation
Ground Wire
Wire Connection to
Enclosure Earth Bus
Fieldbus Isolator
Termination Cable
Assemblies (P0903VY)
36
4. Equipment Installation B0193VU – Rev E
Slide strain relief bracket(s) onto TCA Connect ground wire to DIN rail using
1 3
termination block. (RH928CV has two screw, lock washer and nut (customer
brackets, not shown.) supplied).
Snap assembled termination block
2
onto DIN rail.
TCA Termination Block
(P0903VY Shown - RH928CV has two))
Screw
Lock Washer
Strain Relief Bracket
DIN Rail
Ring Lug
1 Disconnect the earth wire from 2b Move the screw drive handle in the
from the DIN rail. direction shown, while lifting the TCA
termination block from the DIN rail.
For each strain relief bracket, insert a For RH928CV, repeat for the other
2a strain relief bracket.
medium-size flat-head screwdriver as shown.
Lift
Screw
Washer
Move
TCA Termination Block
(P0903VY Shown - RH928CV has two)
37
B0193VU – Rev E 4. Equipment Installation
Control Processor
Termination Cable Assemblies (2)
(RH928CV or P0903VY)
100 Ohm Twinaxial
Cable P0170GF,
P0170GG, or
Note 1
Equivalent
Note 2
Note 3 Note 3
BK BK
Fieldbus A
W W To
SSFBI
SH SH Fieldbus B
F F- S F F- S
F F- S Note 5 F F- S
Fieldbus Fieldbus
Note 4 Note 4
B A
B B
BR G/Y BR G/Y
F+ F- SH F+ F- SH
To Splitter (RH928CV) or
Splitter/Terminator (P0926LC)
Notes:
1. For cable strain relief, it is recommended that the Fieldbus cable(s) be routed over the strain
relief bracket and secured using nylon cables ties.
2. TCAs can be daisy chained as indicated by the dashed cable lines, but terminating resistors
(110 ohms) must be installed on the SSFBI TCA end of the fieldbus (not the FCP280 end). For
the FCP280 end of the fieldbus, Fieldbus ports 2-4 are auto-terminated internally. Fieldbus port 1
is terminated with the DIP switches on the FCP280’s baseplate as described in “Setting Termina-
tion Switches for FCP280 Baseplates” in Field Control Processor 280 (FCP280) User’s Guide
(B0700FW).
3. Wire colors shown (BK and W) are for reference purposes only.
4. Earth (ground) the surge protection network contained within the TCAs by attaching the green
earth wire to a screw on the DIN rail connected to system earth. For more information on earth-
ing, refer to Power, Earthing (Grounding), EMC and CE Compliance (B0700AU). Splitter
(RH928CV) has only one green earth wire.
5. The shield of the twinaxial cable (terminal 3) should be earthed at the farthest end from the
FCP280 baseplate. The fieldbus shield must be earthed at one end only. (See text for
earthing instructions.)
Figure 4-12. Remote Redundant Fieldbus Cabling (FCP280 End)
38
4. Equipment Installation B0193VU – Rev E
Control Processor
Termination Cable Assembly
(RH928CV or P0903VY)
SH
To Next Fieldbus
Isolator Termination W BK
Cable Assembly* To Next Fieldbus
BK W Isolator Termination
Cable Assembly*
SH
F F- S
F F- S
Fieldbus
A
39
B0193VU – Rev E 4. Equipment Installation
NOTE
Refer to Appendix D “FCP280 or FCP270 Upgrade” for information regarding
control processor upgrades from CP30/CP40 to FCP270.
40
4. Equipment Installation B0193VU – Rev E
No Terminator on
this connector
Wire Connection to
Enclosure Earth Bus
Fieldbus Isolator
Termination Cable
Assemblies (P0903VY)
41
B0193VU – Rev E 4. Equipment Installation
Fieldbus A TCA
Cable Connector
Baseplate (P0926HW)
Fieldbus B TCA
Cable Connector
Slide strain relief bracket onto TCA Connect ground wire to DIN rail using
1 3
termination block. screw, lock washer and nut (customer
supplied).
Snap assembled termination block
2
onto DIN rail.
Screw
Lock Washer
Strain Relief Bracket
DIN Rail
Ring Lug
42
4. Equipment Installation B0193VU – Rev E
1 Disconnect the earth wire from 3 Move the screw drive handle in the
from the DIN rail. direction shown, while lifting the TCA
termination block from the DIN rail.
Lift
Screw
Washer
Move
TCA Termination Block
43
B0193VU – Rev E 4. Equipment Installation
Control Processor
Termination Cable Assemblies (2)
(P0903VY)
100 Ohm Twinaxial
Cable P0170GF,
P0170GG, or
Note 1
Equivalent
Note 2
Note 3 Note 3
BK BK
Fieldbus A
W W To
SSFBI
SH SH Fieldbus B
F F- S F F- S
F F- S Note 5 F F- S
Fieldbus Fieldbus
Note 4 Note 4
B A
B B
BR G/Y BR G/Y
F+ F- SH F+ F- SH
To Splitter/Terminator
(P0926LC)
Notes:
1. For cable strain relief, it is recommended that the Fieldbus cable(s) be routed over the strain
relief bracket and secured using nylon cables ties.
2. TCAs can be daisy chained as indicated by the dashed cable lines, but terminating resistors
(110 ohms) must be installed at the ends of the fieldbus.
3. Wire colors shown (BK and W) are for reference purposes only.
4. Earth (ground) the surge protection network contained within the TCAs by attaching the green
earth wire to a screw on the DIN rail connected to system earth. For more information on earth-
ing, refer to Power, Earthing (Grounding), EMC and CE Compliance (B0700AU).
5. The shield of the twinaxial cable (terminal 3) should be earthed at the farthest end from the
FCP270 baseplate. The fieldbus shield must be earthed at one end only. (See text for
earthing instructions.)
44
4. Equipment Installation B0193VU – Rev E
Control Processor
Termination Cable Assembly
(P0903VY)
SH
To Next Fieldbus
Isolator Termination W BK
Cable Assembly* To Next Fieldbus
BK W Isolator Termination
Cable Assembly*
SH
F F- S
F F- S
Fieldbus
A
Connections between a redundant ZCP270 to the SSFBI requires the following to facilitate com-
munications:
♦ ZCP270 connects to a redundant pair of DIN rail mounted Fieldbus Communica-
tions Module 100Es (FCM100Es) via fiber optic cabling, either directly with standard
LC to LC cables or indirectly via The Mesh control network
♦ The FCM100Es connect to the SSFBI
Cabling a FCM100E baseplate to the SSFBI consists of extending the remote 268 Kbps fieldbus
from the isolators (see Figure 4-22). This extension, used between enclosures, involves the use of
termination cable assemblies (TCAs) to provide cable connections between primary and extended
45
B0193VU – Rev E 4. Equipment Installation
fieldbus segments, for a maximum fieldbus length of 1830 m (6000 ft). If the fieldbus is non-
redundant, only one TCA is connected to the fieldbus splitter/terminator (P0926LC) which is
shown in Figure 4-23. TCA part number P0903VY includes a strain relief bracket, labels for bus
A and B, and a 110 ohm terminating resistor. You must install one of the labels on the TCA (see
Figure 4-22 for label orientation)
You can mount the FCM100E module(s) on either the two-position, vertical DIN rail mounted
baseplate (P0926KE) or the two-position, horizontal DIN rail mounted baseplate (P0926KH).
For FCM100E installation procedures, refer to Z-Module Control Processor 270 (ZCP270) User’s
Guide (B0700AN).
! WARNING
Prior to connecting the direct connect cables to the FCM100E, install the letterbug
into the ZCP270. Refer to the I/A Series Letterbug Configurator (B0700AY).
46
4. Equipment Installation B0193VU – Rev E
FCM100E Pair
Bus A
Bus B
Port 2*
47
B0193VU – Rev E 4. Equipment Installation
FCM100Es
To/From Time Strobe Orange Duplex
B
Ethernet Fieldbus Time Strobe
Converter (Optional) Fiber Cable
Cat 5 Cable with See Table 4-1
RJ-45 Connectors
A
Ethernet Fieldbus Time Strobe
A
Splitter/
B
1+2 1+2
A
Combiners
1 1
B
2 2
Orange Duplex
Fiber Cable
See Table 4-1
Gray Duplex
Fiber Cable
See Table 4-1
Part
Number Length Material Use
P0972UN 0.5 m (1.65 ft) MMF 62.5/125 micron, gray Fiber Optic Splitter mounted
riser. LC connectors on each end. on DIN rail or shelf mounted
to ZCP270. Recommended
for use on the “B” network.
48
4. Equipment Installation B0193VU – Rev E
Part
Number Length Material Use
P0972VG 0.5 m (1.65 ft) MMF 62.5/125 micron, orange Fiber Optic Splitter mounted
riser. LC connectors on each end. on DIN rail or shelf mounted
to ZCP270. Recommended
for use on the “A” network.
P0972UJ 1.0 m (3.3ft) MMF 62.5/125 micron. LC con- Fiber Optic Splitter mounted
nectors on each end. on DIN rail or shelf mounted
to ZCP270.
P0972TN 3.0 m (9.9 ft) MMF 62.5/125 micron. LC con- Fiber Optic Splitter mounted
nectors on each end. on DIN rail or shelf mounted
to ZCP270.
P0972TP 15 m (49.5 ft) MMF 62.5/125 micron. LC con- Fiber Optic Splitter mounted
nectors on each end. on DIN rail or shelf mounted
to FCM100E or ZCP270.
P0972TQ 50 m (164 ft) MMF 62.5/125 micron. LC con- Fiber Optic Splitter mounted
nectors on each end. on DIN rail or shelf mounted
to FCM100E or ZCP270.
After you have installed and cabled the FCM100E module, you need to assign their letterbugs
through the infrared port using the I/A Series Letterbug Configurator. For information on using
this device and procedures for assigning letterbugs, see the Letterbug Configurator User’s Guide
(B0700AY).
49
B0193VU – Rev E 4. Equipment Installation
50
4. Equipment Installation B0193VU – Rev E
No Terminator on
this connector
Wire Connection to
Enclosure Earth Bus
Fieldbus Isolator
Termination Cable
Assemblies (P0903VY)
51
B0193VU – Rev E 4. Equipment Installation
Fieldbus A TCA
Cable Connector
Baseplate (P0926KE)
Fieldbus B TCA
Cable Connector
Slide strain relief bracket onto TCA Connect ground wire to DIN rail using
1 3
termination block. screw, lock washer and nut (customer
supplied).
Snap assembled termination block
2
onto DIN rail.
Screw
Lock Washer
Strain Relief Bracket
DIN Rail
Ring Lug
52
4. Equipment Installation B0193VU – Rev E
1 Disconnect the earth wire from 3 Move the screw drive handle in the
from the DIN rail. direction shown, while lifting the TCA
termination block from the DIN rail.
Lift
Screw
Washer
Move
TCA Termination Block
53
B0193VU – Rev E 4. Equipment Installation
Note 2
Note 3 Note 3
BK BK
Fieldbus A
W W To
Fieldbus B SSFBI
SH SH
F F- S F F- S
F F- S Note 5 F F- S
Fieldbus Fieldbus
Note 4 Note 4
B A
B B
BR G/Y BR G/Y
F+ F- SH F+ F- SH
To Splitter/Terminator
(P0926LC)
Notes:
1. For cable strain relief, it is recommended that the Fieldbus cable(s) be routed over the strain
relief bracket and secured using nylon cables ties.
2. TCAs can be daisy chained as indicated by the dashed cable lines, but terminating resistors
(110 ohms) must be installed at the ends of the fieldbus.
3. Wire colors shown (BK and W) are for reference purposes only.
4. Earth (ground) the surge protection network contained within the TCAs by attaching the green
earth wire to a screw on the DIN rail connected to system earth. For more information on earth-
ing, refer to Power, Earthing (Grounding), EMC and CE Compliance (B0700AU).
5. The shield of the twinaxial cable (terminal 3) should be earthed at the farthest end from the
FCM100E Modular Baseplate. The fieldbus shield must be earthed at one end only. (See text for
earthing instructions.)
54
4. Equipment Installation B0193VU – Rev E
Control Processor
Termination Cable Assembly
(P0903VY)
SH
To Next Fieldbus
Isolator Termination W BK
Cable Assembly* To Next Fieldbus
BK W Isolator Termination
Cable Assembly*
SH
F F- S
F F- S
Fieldbus
A
55
B0193VU – Rev E 4. Equipment Installation
! CAUTION
The Fieldbus shield, if left uncovered, could short against the SSFBI chassis. Fox-
boro recommends covering the shield wire (the use of shrink tubing is recom-
mended). It is the installer’s responsibility to provide this protection.
2. If the SSFBI is at the end of the Fieldbus run (for example, the rack at the right in
Figure 4-1 on page 26), refer to Figure 4-29 on page 58 and make the connections as
shown, taking note of the following:
a. Provide the necessary cable strain relief for the remote Fieldbus cable by securing
the cable to the CCM rack at a location near the SSFBI.
b. The jumpers on the connector strip (shown in Figure 4-29 on page 58) must
remain in place.
c. For the purpose of electromagnetic interference (EMI) drain, make an earth wire
connection between the remote Fieldbus shield and the CCM rack earth bus bar
using customer-supplied 14 AWG insulated wire.
d. Install the 110 Ω terminating resistor as shown in the figure. This resistor is sup-
plied with the SSFBI.
e. The cable connections for Fieldbus A (to SSFBI A) and Fieldbus B (to SSFBI B)
are identical.
! CAUTION
The Fieldbus shield and terminating resistor leads, if left uncovered, could pose a
potential short-circuit risk. Invensys recommends covering the shield wire and ter-
minating resistor leads (the use of shrink tubing is recommended). It is the
installer’s responsibility to provide this protection.
56
4. Equipment Installation B0193VU – Rev E
S Jumper
S (1 of 3)
F-
A B F-
F Shields*
BUS F
Black**
To Next SSFBI
SSFBI
or Other Fieldbus Device
(A or B)
Figure 4-28. Remote Fieldbus Cabling, SSFBI Not at End of Fieldbus Run
57
B0193VU – Rev E 4. Equipment Installation
Jumper
S (1 of 3)
S
F-
A B F- Shield*
F
BUS F
Fieldbus
A or B
White**
RUN
FAIL Black** Black**
SSFBI
110 Ω To Rack
Terminating Earth Bus Bar
Resistor*
(P.N. E0157CZ)
SSFBI
(A or B)
58
4. Equipment Installation B0193VU – Rev E
NOTE
It is important to wear a properly connected electrostatic discharge (ESD) wrist
strap while removing, handling, and installing the Control Integrator modules.
Connect the ESD strap to the rack ground bar.
It is also good practice to observe the following steps when handling electronic cir-
cuitry:
1. Use the static shielding bags supplied with the Control Integrator modules.
2. Ground the bag before opening.
3. Avoid touching the Control Integrator module circuitry.
1. Referring to the I/A Series configuration reports, determine the module identifier (let-
ter/number combination) that pertains to the Control Integrator in question.
2. Gather the six letterbugs that will form the module identifier and assemble them by
inserting the dovetail end of one letterbug into the mating end of the next, until all six
letterbugs have been assembled in the proper order (see Figure 4-30).
3. Insert the assembled module identifier into the receptacle on the Control Integrator as
shown in Figure 4-30. (Letterbugs read from top to bottom.) Exercise care, ensuring
that the pins properly align with the holes in the receptacle.
4. Repeat Steps 1, 2, and 3 for all Control Integrators to be installed.
59
B0193VU – Rev E 4. Equipment Installation
P9
TB1-1
P19 P8 P10 P16 P4 TB1
P3 TB1-2
P20 P7 P6 P11 P17 P5 P13 P12 P14 P15
W6 W1 W13 W5 W2 W3 W4 W7
60
4. Equipment Installation B0193VU – Rev E
P9
Figure 4-32. S2CM17 Jumper Locations, P0913CX Revisions C/D and Above
61
B0193VU – Rev E 4. Equipment Installation
Table 4-3. Control Integrator Jumper Settings, P0913CX Revisions C/D and Above
62
4. Equipment Installation B0193VU – Rev E
Power Switch-On
Power to the CCM may be switched on after all CCM Control Integrator subsystem equipment
has been installed. The Control Integrators and SSFBIs have status indicators that report operat-
ing conditions (see “LED Indicators” on page 67).
When power is first applied, the Control Integrator undergoes a power-on self-diagnostic test that
tests its operating status. (The SSFBIs have no self-diagnostics, but LEDs indicate the run/fail sta-
tus and any local/remote Fieldbus activity.) When power is applied, the LED indicators on the
Control Integrators and SSFBIs should light as described in the Maintenance section. If normal
run conditions are not indicated following power switch-on, refer to Chapter 5 “Maintenance”
for corrective action.
EEPROM update This action sends a new EEPROM image to the Control Integrator. Prior
to EEPROM update and download, the CP sets the Control Integrator to
off-line (the GO ON-LINE option on the equipment change display
turns white), so that all outputs go to HOLD while EEPROM update
takes place. You may perform any number of EEPROM updates (for any
number of Control Integrators) without waiting for the completion of
each EEPROM update request. However, you must be sure that, for each
Control Integrator, the EEPROM update has completed successfully prior
to requesting a download.
63
B0193VU – Rev E 4. Equipment Installation
Cable Dressing
When all Control Integrator subsystem equipment has been installed and the subsystem is opera-
tional, dress any excess local and remote Fieldbus cables for neatness using the rack wireways.
Installation Checklist
Complete the following checklist before applying power to the CCM and performing the final
installation operations:
Local and remote Fieldbus installed and connected.
Fieldbus shield lead(s) and terminating resistor leads at Control Integrator end of Field-
bus covered to prevent against short circuits.
SSFBIs installed.
The Control Integrators have been switched to on-line status at the I/A Series System
Management displays.
64
4. Equipment Installation B0193VU – Rev E
EEPROM update and downloading of the Control Integrator image and database have
been performed.
65
B0193VU – Rev E 4. Equipment Installation
66
5. Maintenance
This chapter describes general maintenance for CCM equipment racks. It provides detailed
explanations of LED indicators and their associated meanings, as well as technical support
information.
The original maintenance and preventive maintenance philosophies for the CCM equipment
racks are maintained. This includes periodic inspection and cleaning, checking the status of LED
indicators, and checking for loose cable connections.
Operating Status
The operating status of the Control Integrators is reported by the I/A Series software using on-
screen messages. [The I/A Series software regards the Control Integrators as standard Fieldbus
Modules (FBMs).] Refer to the following I/A Series documents for information on the reporting
of equipment operating status and errors:
♦ System Maintenance (B0193AD)
♦ System Manager (B0750AP)
♦ System Management Displays (B0193JC).
LED Indicators
LED indicators at the front of the SSFBI Isolators and the Control Integrators indicate the opera-
tional status of these devices (see Figure 5-1). The functions of the SSFBI Isolator LEDs are as fol-
lows:
♦ Remote Fieldbus Activity – When illuminated, indicates the existence of communica-
tion activity on the remote Fieldbus (that is, external to the CCM)
♦ Local Fieldbus Activity – When illuminated, indicates the existence of communica-
tion activity on the local Fieldbus (that is, internal to the CCM)
♦ Run – When illuminated, indicates that the SSFBI Isolator is running
♦ Fail – When illuminated, indicates that the SSFBI Isolator has failed.
67
B0193VU – Rev E 5. Maintenance
Remote
Fieldbus A B Local
Activity BUS Fieldbus
Activity
Run RUN
Fail Operating Status
FAIL
(See Table 5-1)
SSFBI
S2CM17
Control Integrator
SSFBI
Fieldbus Isolator
Two status LEDs (red and green) at the front of the S2CM17 Control Integrator provide indica-
tions of operating status, as listed in Table 5-1
Technical Support
If technical support is needed, call Global Product Support at 1-866-746-6477) or contact the
Invensys Global Customer Support website (http://support.ips.invensys.com).
68
Appendix A. Hardware
Specifications
This appendix gives the hardware specifications for the SPEC 200 CCM Control Integrator
subsystem, including S2M17 functional and physical specifications, SSFBI/SDFBI physical
specifications, and common environmental specifications.
Analog Inputs
Channels 4
Analog Input Range -0.256 to 10.256 V dc
Rated Mean Accuracy ±0.150% of span
Temperature Stability ±0.150% of span
Input Resolution 12 to 15 bits, programmable (see Table A-1)
69
B0193VU – Rev E Appendix A. Hardware Specifications
Analog Outputs
Capacity Two outputs
Range -0.256 to 10.256 V dc
Current 2 mA (maximum)
Rated Mean Accuracy ±0.150% of span
Temperature Stability ±0.150% of span
Settling Time 150 ms maximum (to 1% of final value for
10 to 90% step change)
Linearity Error ±0.025% of span
Resolution 12 bits
Digital Inputs
Capacity 4 inputs
Input 1:
Input Range Max. Low Level Input = 1.5 V dc ± 1%
(Low = Fail to Display, output to gate array = High)
High Level Input Threshold = 2.5 V dc ± 0.375 V dc
(High = OK, output to gate array = Low)
Input Open, Open Circuit Voltage = 5 V dc
(Open = OK, output to gate array = Low)
Max. Sink Current 1 mA
Input 2:
Input Range Max. Low Level Input = 1.5 V dc ± 1%
(Low = Computer ON, output to gate array = Low)
High Level Input Threshold = 8 V dc ± 1.2 V dc
(High = Computer OFF, output to gate array = High)
Input Open, Open Circuit Voltage = 5 V dc
(Open = Computer ON, output to gate array = Low)
Max. Sink Current 50 micro amps
Input 3:
Input Range Max. Low Level Input = 0.5 V dc ± 0.1 V dc
(Low = Interlock connected, output to gate array = High)
High Level Input Threshold = 2.1 V dc ± 0.315 V dc
(High = Interlock connected, output to gate array = Low)
Input Open, Open Circuit Voltage = 4.35 V dc
(Open = Interlock connected, output to gate array = Low)
Max. Sink Current 50 micro amps
70
Appendix A. Hardware Specifications B0193VU – Rev E
Input 4:
Input Range Max. Low Level Input = -15 V dc to +1 V dc
(Low = AUTO, output to gate array = High)
Min. High Level Input = 2.1 V dc ± 0.315 V dc
(High = MANUAL, output to gate array = Low)
Input Open, Open Circuit Voltage = 4.35 V dc
(Open = AUTO, output to gate array = High)
Max. Sink Current 1 nano amp
Max Source Current 30 micro amps
Digital Outputs
Communication
Redundant IEEE P1118 Fieldbus
Indicators
Red and green light-emitting diodes (LEDs)
71
B0193VU – Rev E Appendix A. Hardware Specifications
Connections
10-pin male redundant Fieldbus connector
14-pin male control station connector
Communication
Single IEEE P1118 Fieldbus
Local Fieldbus Length 10 m (30 ft) (maximum)
Fieldbus Devices 16 (maximum)
Indicators
Red and green light-emitting diodes (LEDs)
Remote and local Fieldbus communication indicators
Connections
Power cable – 30-pin standard SPEC 200 display connector
Local Fieldbus – DB9 9-pin male redundant IEEE P1118 Fieldbus connector
Remote Fieldbus – 6-terminal quick-disconnect terminal block
72
Appendix A. Hardware Specifications B0193VU – Rev E
Storage
Temperature -40 to +70°C (-40 to 158°F)
Relative Humidity 5 to 95% (Noncondensing)
Altitude -300 to +12000 m (-1000 to +40000 ft)
Contamination
ISA Standard S74.04, Class G1 (mild)
73
B0193VU – Rev E Appendix A. Hardware Specifications
74
Appendix B. Control
Integrator/CUIC Signal Flow
Diagrams
This appendix provides Control Integrator/CUIC signal flow diagrams for the two major CCM
configurations, serial communications (INTERSPEC) and parallel communications.
Control Integrator
(S2CM17) MEAS FROM SPEC 200 I/O
J27
2DC-J or 2DC-JR
MEAS AI1 1
J27
6+ CUIC CARD
5-
AO2 P9 16
I/A SPT SETPOINT J27 UNSEL SPT REMOTE
P7 P8 SETPOINT
AI4 J28 36
FIELDBUS UNSEL + 15 J28
SPT TB1 SP R/L SW PULSE ENABLE
P6 - AUTO = -15V
DI4 14 MAN = +15V 17 35 PULSE
A/M FROM A/M R/L
COMP 4 ADDRESS
J2
DI3 5 33 AM STATUS
CABLE INTERLOCK 3 A/M
OPEN = 0 14 A=H 26 AUTO
GND = 1 M=L 21 PULSE
DI1 1 PULSE 27 MAN
FAIL TO DISPLAY UP=H
DN=L 1 UP/DN 25 UP/DN
P14 P15 UP/DN
UP/DN DO4 11
SP=H 2 SP/OP 6 SP/OUT
OP=L SP/OP
DO3 P13 P12 5 LOCAL
10 22 R/L
PULSE CIRCUIT 24 REMOTE
R=H R/L FROM MUX
DO2 P4 R/L DISPLAY 7 R/L STATUS
7 L=L
COMP ON/OFF or I/A ON-OFF
23
FROM DISPLAY P3 COMP 34 COMP FAIL
STATION P5 SP/OP 13 13 COMP ON/OFF (OFF=H, ON=L)
OPEN ON = L DRIVER 14 ON/OFF COMP
OPEN OFF = H FAIL TO DISPLAY (L=FAIL)
OPEN = COMP ON = L
DI2 2
DISPLAY CONNECTOR ON CCM TTL FROM
RELAY2 P1 MAIN LOGIC
DO1 6 78
COMP ON/OFF CUIC/DISPLAY
FROM I/A CABLE ASSEMBLY DISPLAY STATION
1
A/M 12
+15V
8 - S2CM17 RELAYS 1 & 2 REMAIN OPEN UNTIL THE S2CM17 IS OPERATIONAL,
+5V 2AK CABLE I.E., APPROXIMATELY 10 SECONDS AFTER THE RED LED GOES OFF.
9 J1
GND - ANALOG SWITCHES ON AO1 OPEN WHEN DI4 INDICATES MANUAL AND CLOSE
TO CABLE RELAY AFTER 2 SECONDS WHEN DI4 TRANSITIONS TO AUTO INDICATION.
COIL PINS 2 & 6 - CABLE RELAY 1 IS CLOSED (PIN 13-13) WHEN S2CM17 IS NON-OPERATIONAL,
I.E., CARD POWER IS OFF OR CARD IS REMOVED FROM CCM NEST, TO ENABLE
COMPUTER ON/OFF SIGNAL TO BE DRIVEN DIRECTLY FROM DISPLAY STATION.
- CABLE RELAY 2 (PIN 9) IS OPEN WHEN THE DISPLAY STATION POWER IS OFF
OR WHEN THE DISPLAY STATION IS UNPLUGGED.
- JUMPER P10 - P11, P6 - P7 IN 2DNC-C CONFIGURATION
Figure B-1. Control Integrator and 2DC-J or 2DC-JR CUIC with Panel Display Station
75
B0193VU – Rev E Appendix B. Control Integrator/CUIC Signal Flow Diagrams
Control Integrator
(S2CM17) MEAS FROM SPEC 200 I/O
J27
2DC-J or 2DC-JR
MEAS AI1 1
J27
6+ CUIC CARD
5-
AO2 P9 16
I/A SPT SETPOINT J27 UNSEL SPT REMOTE
P7 P8 SETPOINT
AI4 J28 36
FIELDBUS UNSEL + 15 J28
SPT TB1 SP R/L SW PULSE ENABLE
P6 - AUTO = -15V
DI4 14 MAN = +15V 17 35 PULSE
A/M FROM A/M R/L
COMP 4 ADDRESS
J2
DI3 5 33 AM STATUS
CABLE INTERLOCK 3 A/M
OPEN = 0 14 A=H 26 AUTO
GND = 1 M=L 21 PULSE
DI1 1 PULSE 27 MAN
FAIL TO DISPLAY UP=H
DN=L 1 UP/DN 25 UP/DN
P14 P15 UP/DN
UP/DN DO4 11
SP=H 2 SP/OP 6 SP/OUT
OP=L SP/OP
DO3 P13 P12 5 LOCAL
10 22 R/L
PULSE CIRCUIT 24 REMOTE
R=H R/L FROM MUX
DO2 P4 R/L DISPLAY 7 R/L STATUS
7 L=L
COMP ON/OFF or I/A ON-OFF
23
FROM DISPLAY P3 COMP 34 COMP FAIL
STATION
P5 SP/OP 13 COMP ON/OFF (OFF=H, ON=L)
OPEN ON = L 13
DRIVER 14 ON/OFF COMP
OPEN OFF = H
OPEN = COMP ON = L FAIL TO DISPLAY (L=FAIL)
(NOT USED) DI2 2
A/M 12
+15V - S2CM17 RELAYS 1 & 2 REMAIN OPEN UNTIL THE S2CM17 IS OPERATIONAL,
8 I.E., APPROXIMATELY 10 SECONDS AFTER THE RED LED GOES OFF.
+5V
- ANALOG SWITCHES ON AO1 OPEN WHEN DI4 INDICATES MANUAL AND CLOSE
9
GND AFTER 2 SECONDS WHEN DI4 TRANSITIONS TO AUTO INDICATION.
- JUMPER P10 - P11, P6 - P7 IN 2DNC-C CONFIGURATION
Figure B-2. Control Integrator and 2DC-J or 2DC-JR CUIC without Panel Display Station
76
Appendix B. Control Integrator/CUIC Signal Flow Diagrams B0193VU – Rev E
Control Integrator
(S2CM17) MEAS FROM SPEC 200 I/O
J27
2DC-K or 2DC-KR
MEAS AI1 1
J27
6+ CUIC CARD
5-
RELAY1
AO1
19 20
100 100
TO PIN 11 OUTPUT
ON DISP STA 30 TO CCM
17 38
ANALOG SWITCH: 2DNC-C ONLY
TRACK INPUT
CLOSED - AUTO 39 11 DISABLED WHEN STORAGE INTEGRATOR
OPEN - MANUAL INTERLOCK OPEN
INTERLOCK 40 32
OUT
12 GND
SEL SPT AI2 P11 P10
21 SEL SPT
AO2 P9 16
I/A SPT SETPOINT J27 UNSEL SPT REMOTE
P7 P8 SETPOINT
AI4 J28 36
FIELDBUS UNSEL + 15 J28
SPT TB1 SP R/L SW PULSE ENABLE
P6 - AUTO = -15V
DI4 14 MAN = +15V 17 35 PULSE
A/M FROM A/M R/L
COMP 4 ADDRESS
J2
DI3 5 33 AM STATUS
CABLE INTERLOCK 3 A/M
OPEN = 0 14 A=H 26 AUTO
GND = 1 M=L 21 PULSE
DI1 1 PULSE 27 MAN
FAIL TO DISPLAY UP=H
DN=L 1 UP/DN 25 UP/DN
P14 P15 UP/DN
UP/DN DO4 11
SP=H 2 SP/OP 6 SP/OUT
OP=L SP/OP
DO3 P13 P12 5 LOCAL
10 22 R/L
PULSE CIRCUIT 24 REMOTE
R=H R/L FROM MUX
DO2 P4 R/L DISPLAY 7 R/L STATUS
7 L=L
COMP ON/OFF or I/A ON-OFF
23
FROM DISPLAY P3 COMP 34 COMP FAIL
STATION P5 SP/OP 13 13 COMP ON/OFF (OFF=H, ON=L)
OPEN ON = L DRIVER 14 ON/OFF COMP
OPEN OFF = H
FAIL TO DISPLAY (L=FAIL)
OPEN = COMP ON = L
DI2 2
DISPLAY CONNECTOR ON CCM TTL FROM
RELAY2 P1 MAIN LOGIC
DO1 6 78
COMP ON/OFF CUIC/DISPLAY
FROM I/A CABLE ASSEMBLY DISPLAY STATION
1
A/M 12
+15V
8 2AK CABLE - S2CM17 RELAYS 1 & 2 REMAIN OPEN UNTIL THE S2CM17 IS OPERATIONAL,
+5V I.E., APPROXIMATELY 10 SECONDS AFTER THE RED LED GOES OFF.
9 J1
GND - ANALOG SWITCHES ON AO1 OPEN WHEN DI4 INDICATES MANUAL AND CLOSE
TO CABLE RELAY AFTER 2 SECONDS WHEN DI4 TRANSITIONS TO AUTO INDICATION.
COIL PINS 2 & 6 - CABLE RELAY 1 IS CLOSED (PIN 13-13) WHEN S2CM17 IS NON-OPERATIONAL,
I.E., CARD POWER IS OFF OR CARD IS REMOVED FROM CCM NEST, TO ENABLE
COMPUTER ON/OFF SIGNAL TO BE DRIVEN DIRECTLY FROM DISPLAY STATION.
- CABLE RELAY 2 (PIN 9) IS OPEN WHEN THE DISPLAY STATION POWER IS OFF
OR WHEN THE DISPLAY STATION IS UNPLUGGED.
- JUMPER P10 - P11, P6 - P7 IN 2DNC-C CONFIGURATION
Figure B-3. Control Integrator and 2DC-K or 2DC-KR CUIC with Panel Display Station
77
B0193VU – Rev E Appendix B. Control Integrator/CUIC Signal Flow Diagrams
Control Integrator
(S2CM17)
J27 MEAS FROM SPEC 200 I/O
2DC-K or 2DC-KR
AI1 1 6+
MEAS J27
5-
CUIC CARD
OUTPUT TO SPEC 200 I/O
AI3 TRK OUT
31 19
TRK IN
RELAY1
AO1
19 20
100 100
TO PIN 11 ON OUTPUT
30
17 DISPLAY STATION 38 TO CCM
ANALOG SWITCH: 2DNC-C ONLY
TRACK INPUT
CLOSED - AUTO 39 11 DISABLED WHEN STORAGE INTEGRATOR
OPEN - MANUAL INTERLOCK OPEN
INTERLOCK 40 32
OUT
12 GND
SEL SPT AI2 P11 P10
21 SEL SPT
AO2 P9 16
I/A SPT SETPOINT J27 UNSEL SPT REMOTE
P7 P8 SETPOINT
AI4 J28 36
FIELDBUS UNSEL + 15 J28
SPT TB1 SP R/L SW PULSE ENABLE
P6 - AUTO = -15V
DI4 14 MAN = +15V 17 35 PULSE
A/M FROM A/M R/L
COMP 4 ADDRESS
J2
DI3 5 33 AM STATUS
CABLE INTERLOCK 3 A/M
OPEN = 0 14 A=H 26 AUTO
GND = 1 M=L 21 PULSE
DI1 1 PULSE 27 MAN
FAIL TO DISPLAY UP=H
DN=L 1 UP/DN 25 UP/DN
P14 P15 UP/DN
UP/DN DO4 11
SP=H 2 SP/OP 6 SP/OUT
OP=L SP/OP
DO3 P13 P12 5 LOCAL
10 22 R/L
PULSE CIRCUIT 24 REMOTE
R=H R/L FROM MUX
DO2 P4 R/L DISPLAY 7 R/L STATUS
7 L=L
COMP ON/OFF or I/A ON-OFF
23
FROM DISPLAY P3 COMP 34 COMP FAIL
STATION
P5 SP/OP 13 COMP ON/OFF (OFF=H, ON=L)
OPEN ON = L 13
OPEN OFF = H DRIVER 14 ON/OFF COMP
OPEN = COMP ON = L FAIL TO DISPLAY (L=FAIL)
(NOT USED) DI2 2
A/M 12
+15V - S2CM17 RELAYS 1 & 2 REMAIN OPEN UNTIL THE S2CM17 IS OPERATIONAL,
8 I.E., APPROXIMATELY 10 SECONDS AFTER THE RED LED GOES OFF.
+5V
- ANALOG SWITCHES ON AO1 OPEN WHEN DI4 INDICATES MANUAL AND CLOSE
9
GND AFTER 2 SECONDS WHEN DI4 TRANSITIONS TO AUTO INDICATION.
- JUMPER P10 - P11, P6 - P7 IN 2DNC-C CONFIGURATION
Figure B-4. Control Integrator and 2DC-K or 2DC-KR CUIC without Panel Display Station
78
Control Integrator
(S2CM17)
AI1 1
2DC-Q
MEAS J27 CUIC CARD
MEAS
AI3 J27
TRK IN OUTPUT
RELAY1
AO1
19 OUTPUT
20 30
100 TO CCM
2DNC-C ONLY
17
ANALOG SWITCH:
CLOSED - AUTO 39
OPEN - MANUAL
INTERLOCK 40
AO2 P9
I/A SPT
P7 P8
AI4 J27
UNSEL +
SPT TB1
P6 -
A/M FROM DI4 14
COMP
GND J2
DI3 5
CABLE INTERLOCK SETPOINT
OPEN = 0 14
GND = 1
DI1 1
FAIL TO DISPLAY
P14 P15
UP/DN DO4 11
DO2 P4 R/L 7
P3
P5 SP/OP 13
DI2 2
RELAY2
DO1 6
NOTES:
A/M 12
+15V - JUMPER P10 - P11 AND DI4 TO GND WHEN USED WITH 2DNC-Q
8
+5V
9
GND
79
B0193VU – Rev E Appendix B. Control Integrator/CUIC Signal Flow Diagrams
NOTE
There is no backplane connection from the output of the S2CM17 card to the
SPEC 200 output TB. When a CUIC card is in the configuration, the S2CM17
output is sent across the backplane to the CUIC, and then the CUIC routes the
output to TB-5 and 6. To allow I/A Series to track the output, a hard-wire connec-
tion must be made from TB-5 and 6 to TB1-1 and 2 on the S2CM17 card. Then,
with S2CM17 jumper W1-7 and 8 in place, analog input #4 can be used as the
TRACK input for the PIDA block.
RELAY1
AO1
19 20
100 100
30
17 38
ANALOG SWITCH:
CLOSED - AUTO 39 11 STORAGE INTEGRATOR
OPEN - MANUAL
40 32
OUT
12 GND
SEL SPT AI2 P11 P10 21 SEL SPT
AO2 P9 16
I/A SPT TB# - 7+ REMOTE
P7 P8 SETPOINT
AI4 SETPOINT 36
FIELDBUS UNSEL + 15 TB#
SPT TB1 SP R/L SW PULSE ENABLE
P6 - AUTO = -15V
DI4 14 MAN = +15V 17 35 PULSE
A/M FROM A/M R/L
COMP 4 ADDRESS
J2
DI3 5 33 AM STATUS
CABLE INTERLOCK 3 A/M
OPEN = 0 14 A=H 26 AUTO
GND = 1 M=L 21 PULSE
DI1 1 PULSE 27 MAN
FAIL TO DISPLAY UP=H
DN=L 1 UP/DN 25 UP/DN
P14 P15 UP/DN
UP/DN DO4 11
SP=H 2 SP/OP 6 SP/OUT
OP=L SP/OP
DO3 P13 P12 5 LOCAL
10 22 R/L
PULSE CIRCUIT 24 REMOTE
R=H R/L FROM MUX
DO2 P4 R/L DISPLAY 7 R/L STATUS
7 L=L
COMP ON/OFF or I/A ON-OFF
23
FROM DISPLAY P3 COMP 34 COMP FAIL
STATION
P5 SP/OP 13 COMP ON/OFF (OFF=H, ON=L)
OPEN ON = L 13
OPEN OFF = H DRIVER 14 ON/OFF COMP
OPEN = COMP ON = L FAIL TO DISPLAY (L=FAIL)
(NOT USED) DI2 2
A/M 12
+15V - S2CM17 RELAYS 1 & 2 REMAIN OPEN UNTIL THE S2CM17 IS OPERATIONAL,
8 I.E., APPROXIMATELY 10 SECONDS AFTER THE RED LED GOES OFF.
+5V
- ANALOG SWITCHES ON AO1 OPEN WHEN DI4 INDICATES MANUAL AND CLOSE
9
GND AFTER 2 SECONDS WHEN DI4 TRANSITIONS TO AUTO INDICATION.
Figure B-6. Parallel Communications CCM Configuration without Panel Display Station
80
Appendix C. CP60 Upgrade
This appendix provides the procedure to upgrade CP30 or CP40 Control Processors to CP60
Control Processors on existing I/A Series systems.
NOTE
CP60 support for SPEC 200 products is presently limited to the V6.3.2 and V6.5
releases. The CP60 image (V6.4) supplied with the V6.4 and V7.0 releases does not
support SPEC 200 Migration products. Releases that use the V6.5 or later versions
of CP60 software will provide support for SPEC 200 Migration products.
81
B0193VU – Rev E Appendix C. CP60 Upgrade
82
Appendix D. FCP280 or FCP270
Upgrade
This appendix provides the procedure to upgrade CP30, CP40, or CP60 control processors to
FCP280 or FCP270 control processors on existing I/A Series systems.
If upgrading from the CP60 to the FCP280 or FCP270, there is no need to EEPROM update
the Control Integrators or other FBMs.
To replace CP30, CP40, or CP60 control processors with the FCP280 or FCP270, perform the
following:
NOTE
The FCP280 is supported by I/A Series software v9.0 or later.
The FCP270 is supported by I/A Series software v8.1.1 or later.
1. Install the appropriate version of the I/A Series software on the I/A Series system
which contains your control processors - see the note above. Refer to the Invensys
Global Customer Support website (http://support.ips.invensys.com) for the latest version
of I/A Series software and its documentation.
2. After the system has been upgraded to the appropriate version of the I/A Series soft-
ware, the CP30s, CP40s or CP60s can be replaced with the FCP280 or FCP270.
♦ To install the FCP280, refer to Field Control Processor 280 (FCP280) Upgrade
Guide (B0700GC) for instructions on replacing the CP30s, CP40s or CP60s, and
refer to the chapter “Installing the Field Control Processor 280” in Field Control
Processor 280 (FCP280) User’s Guide (B0700FW) for instructions on installing the
FCP280.
♦ To install the FCP270, follow the instructions in Field Control Processor 270
(FCP270) User’s Guide (B0700AR).
♦ To cable the Fieldbus to the FCP280, follow the instructions in “Fieldbus Cabling
at the FCP280” on page 34.
♦ To cable the Fieldbus to the FCP270, follow the instructions in “Fieldbus Cabling
at the FCP270” on page 40.
83
B0193VU – Rev E Appendix D. FCP280 or FCP270 Upgrade
84
Appendix E. ZCP270 Upgrade
This appendix provides the procedure to upgrade CP30, CP40, or CP60 control processors to
ZCP270 control processors on existing I/A Series systems.
If upgrading from the CP60 to the ZCP270, there is no need to EEPROM update the Control
Integrators or other FBMs.
To replace CP30, CP40, or CP60 control processors with the ZCP270, perform the following:
1. Install V8.3 or later System Software on the existing system.
2. After the system has been upgraded to V8.3 or later, the CP30s, CP40s or CP60s can
be replaced with ZCP270 control processors. To install the FCP270, follow the
instructions in Z-Module Control Processor 270 (ZCP270) User’s Guide (B0700AN).
To cable the Fieldbus to the ZCP270, follow the instructions in “Fieldbus Cabling at
the ZCP270” on page 45.
85
B0193VU – Rev E Appendix E. ZCP270 Upgrade
86
Index
A
Auto/manual 17, 20
B
Block, see Control block
C
Cable dressing 64
Cable interrupt 17, 20
Cabling
FCM100E 48
fiber optic 49
Cabling, fieldbus at FCP270 34, 40
Cabling, fieldbus at ZCP270 45
Checklist
installation 64
Checkpointing 64
COMM Fail 22
Computer fail 17, 21
Computer status 17, 21
Configuration 9
Control block 11, 13, 16
Control configuration, see Integrated control configuration
Control integrator
description 1
I/O jumper settings 61
Control Processor (CP) 3
Control processor (CP) 26
Control scheme 15
Control station 3, 7
CUIC jumper settings 79
CUIC signal flow diagrams 75
D
Download (of control integrator image) 63
E
ECB 11, 12, 16
ECB parameters 12
EEPROM update 63
Electrostatic discharge 59
Equipment control block 11, 12, 16
Equipment installation 5, 25
87
B0193VU – Rev E Index
ESD 59
F
Fail-safe
examples 22
operation 22
FCM100E cabling 48
Fiber optic cabling 49
Fieldbus 2, 4, 28, 33
description 1, 7
Fieldbus isolator 1, 7
Fieldbus module 4
Final installation operations 61
Fix All function 12
H
Hardware specifications 69
I
I/A Series Control Processor (CP) 3
I/A Series control processor (CP) 26
I/A Series personal workstation (PW-FB) 26
Indicators, LED 63, 67
Installation
checklist 64
equipment 25
Integrated control configuration
description 4, 11
off-line 11
on-line 16
INTERSPEC communications 7
Invensys Global Customer Support xii
J
Jumper settings
control integrator I/O 61
CUIC 79
L
LED indicators 63, 67
Letterbug 10, 59
Local fieldbus 2, 7, 8
M
Maintenance 67
Module identifier, see Letterbug
88
Index B0193VU – Rev E
O
Operating status 67
Overview 1
P
Panel display station 75, 77
Parameters, setting 12
Personal workstation (PW-FB) 26
Power switch-on 63
Pre-installation requirements 25
Product implementation 7
R
Reference documents xi
Release
4.1 81
4.2 81
Remote fieldbus extension 34, 40, 45
Remote fieldbus, see Fieldbus
Revision information xi
S
Safety considerations xi
Setpoint select 17, 19
Signal flow diagrams, CUIC 75
Software installation 10
Software requirements 7, 10, 12, 16
Specifications, hardware 69
SSFBI
description 1, 2
installation 27
System configuration 4
System Definition 9
System definition 9
System management displays 63
T
TCA 4, 28, 32
Technical support 68
Termination cable assembly 4, 28, 32
Track 17, 19
Type 1 failures 22
Type 2 failures 22
89
B0193VU – Rev E Index
U
UCM SPECTRUM Migration Integrator subsystem
hardware/software support 3
V
VIDEOSPEC 1, 14
90
Index B0193VU – Rev E
91
Invensys
10900 Equity Drive
Houston, TX 77041
United States of America
http://www.invensys.com