Professional Documents
Culture Documents
Installation, Testing& Commissioning of FM - 200 System
Installation, Testing& Commissioning of FM - 200 System
Installation
Completion
Commissioning
BKR-1512a
Installation
Follow Standards
Follow Manuals
Drawings
Wiring Information
Other Documents
• Detection / release system
• Pressure venting
• Room integrity
Details provided?
Details provided?
Resetting actuators
• all actuators need manual reset!
Resetting actuators
• electric actuator (spring loaded)
Reset Tool
Resetting actuators
• pneumatic actuator (O-ring friction only)
Resetting actuators
• manual actuator (3 steps)
fired lift strike knob insert safte clip push pin back
Details provided?
Details provided?
Important
• Pressure rating
• Material
cast iron and non-metallic pipes and fittings shall
not be used
• Finish
black, galvanised, stainless steel
System Pressure
Side Tee
Correct Side Tee
Incorrect
Pipe Hangers
• from non-combustible material
• spacing according engineering rules and standards
ISO 14520 & EN 15004 § 6.3.4:
≤25 mm pipe ≤100 mm
>25 mm pipe ≤250 mm
Pipe Hanger
• not a good idea
Correct Wrong
Nozzle orientation?
NPT or BSP
Nozzle placement?
Installation options
• pilot line
Installation options
• distribution pipe
Always required
• local language
• at all exit doors
=?
=?
Fixings / connections
• container battery
Fixings / connections
• pipes, nozzles
Container pressure
Container label
• correct container?
Warning signs
Electric actuator(s)
Leakage
?
Pressure vents
System is operable
If ...
• system complete and checked
• system operable
• documentation ready
• commissioning schedule available