Professional Documents
Culture Documents
BR-10R Series Control DNP3 Device Profile & Point Map (V1.03) - BH-PMDRV21050001
BR-10R Series Control DNP3 Device Profile & Point Map (V1.03) - BH-PMDRV21050001
This document reserves copyright for the distributors and users of BH System, containing
an intellectual property of BH System. Any act of copy or use without an approval of BH
System is restricted.
The is a trademark of BH System and shall not be used under any circumstance
without an approval of BH System.
Table of Content
DNP V3.0
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
None None
Analog Deadbands:
Configurable Analog Deadbands:
Fixed
Not Applicable
Configurable:
Configuration Software
☑ Per Point
Using Object 34 from the master station
Per Analog Type
☑ Both configuration software and Object 34
Global
The maximum number of objects supported in a single control request for objects 12 and 41.
Number of objects allowed for object 12 : 1
Number of objects allowed for object 41 : within 1 frame
10 1 Binary Output
Binary Input Points include information such as the status of the automatic switch and the control, the status of
the distribution line, the setting status of function keys, etc.
17 Indicates whether alternate settings functionality is enabled. The active operation settings group is
automatically selected in accordance with the direction of power flow when the alternate settings is
enabled.
Manual Lock Handle Locked Unlock 01/01,01/02,02/02 -
- Indicates whether recloser's operating handle is locked. If the lever is in locked state, all closing and
opening operations through the control are not permitted.
Gas Pressure Low Normal 01/01,01/02,02/02 -
- Indicates the recloser tank's gas pressure status. Applies only to gas insulated reclosers; operation
of all protection elements is stopped immediately when low gas state is detected.
Battery Status Low Normal 01/01,01/02,02/02 -
-
Displays the result for battery test.
Charger Status Abnormal Normal 01/01,01/02,02/02 -
-
Displays whether the output voltage of the charger is within rated range.
Points marked dash for default index items are assigned point index automatically, if their points are edited by
the operating program. For more details, refer to the operating program.
Default Class could be edited by the operating program. If set, ‘0’, event does not occur. Binary Input Point
could be selectable for 0, 1, or 2 class.
Binary Input Points can select event type to use either variation 1 or variation 2.
Binary Counter Points
The binary count points include information such as operation count per protection element, recloser's
operation count, accumulated interruption duration due to the operation of protection elements, number of
power outage and accumulated duration of power outage, kWh, etc.
Object
Point No. Point Name Unit
Variation
Number of Last Month's Over-Current Sequence number 20/02,20/06
0
Previous month's operation count of reclosing sequence due to phase or ground O/C elements
Number of Last Month's SEF Sequence number 20/02,20/06
1
Previous month's operation count of reclosing sequence due to SEF elements
Number of Last Month's NPS Sequence number 20/02,20/06
2
Previous month's operation count of reclosing sequence due to negative sequence OC elements
Number of Last Month's Voltage Sequence number 20/02,20/06
3
Previous month's operation count due to voltage elements
Number of Last Month's Frequency Sequence number 20/02,20/06
4
Previous month's operation count due to frequency elements
Total Number of Last Month's Fault Sequence number 20/02,20/06
5 Previous month's total operation count of reclosing sequence and tripping due to operations of
protection elements.
Number of This Month's Over-Current Sequence number 20/02,20/06
6
This month's operation count of reclosing sequence due to phase or ground O/C elements
Number of This Month's SEF Sequence number 20/02,20/06
7
This month's operation count of reclosing sequence due to SEF elements
Number of This Month's NPS Sequence number 20/02,20/06
8
This month's operation count of reclosing sequence due to negative sequence OC elements
Number of This Month's Voltage Sequence number 20/02,20/06
9
This month's operation count due to voltage elements
Number of This Month's Frequency Sequence number 20/02,20/06
10
This month's operation count due to frequency elements.
Total Number of This Month's Fault Sequence number 20/02,20/06
11
This month's total operation count of reclosing and tripping due to protection element operation
Binary output points include recloser's open and close control, control inhibit settings, operation activation
setting for all protection elements and ground protection elements, auto reclosing activation settings, hot line tag
functionality activation settings, remote reset targets for resetting fault information, remote alarm reset for
resetting alarm information, remote count reset for resetting various count information, etc.
If the On Time to close and open the recloser is not appropriate, operation may be failed due to
insufficient operation time. Thus, read the related manual provided by the manufacturer of recloser carefully
to set the On Time to at least the operation time. On Time is defined as the maximum holding time of
control output to open or close the main contact of the recloser.
The default Close Pulse of 90ms and Open Pulse of 70ms specified in 7.1.3 control time of the instruction
manual are applied to the On Time as an operating time to open or close the main contact of the recloser.
The operation of points other than open and close points are not affected by the on time. Generally,
control is performed if on time is more than 0.
It does not support any special code for latch. But, spare points which are on by pulse on command,
they keep on status until pulse off command via operating program or control panel operates.
Changed status would be applied equally when devices restart. Point status can be checked remotely
or locally through Obj:10, Var:2 Binary Output Status command.
Default Condition Object
Point Name
Index Trip(0x81h) Close(0x41h) Variation
Open/Close Command Open Close 12/01
Command used to open or close the main contact of the recloser.
0 Supported control codes : Close - 0x41h, Open(Trip) - 0x81h
To perform close and open control for recloser through remote control, a suitable On Time setting
is required; it has to be set higher than the minimum operation time of the recloser.
Auto-Reclosing Enable Blocking 12/01
1
Used to enable or disable auto-reclosing sequence.
13 Used to reset power outage count and accumulated power outage duration. Power outage are
identified if at least one phase is below the set level and the condition continues for more than the
set time.
14 Reset Operations Count Command NA Reset 12/01
Default Condition Object
Point Name
Index Trip(0x81h) Close(0x41h) Variation
Command used to reset recloser's operation counts.
Reset Energy Command NA Reset 12/01
15
Used to reset the accumulated kWh and kVAR information.
Reset Trip Count Command NA Reset 12/01
16 Used to reset the accumulated trip counter and duration during which power was shut down on
one side according to recloser operation.
- Spare output Point 1 - Close 12/01
- Spare output Point 2 - Close 12/01
- Spare output Point 3 - Close 12/01
- Spare output Point 4 - Close 12/01
Used to control spare output points.
Binary Output Points can be select whether to use each point through the operating program. Basically, Points
marked dash for default index items are set not to use.
Analog Input Points
Analog input points include current and voltage of each phase, and various demand values calculated based on
those values, sequence components, THD and voltage/current unbalance ratio, power and power factor, battery
test voltage and charge voltage, control's internal temperature, recent fault information, self-diagnostics info, etc.
Class : 0, 2, 3 class can be selected for analog input points. For Points supported by deadband report, refer to
deadband items on the table above. Points assigned in Class 0 does not occur, only static data are supported.
Deadband settings are available for all analogue points in remote or on site through the operating program. But,
information mentioned on the table above are only applied to deadband functions. Deadband events occur only
when point and event items are selected ‘available’.
Deadband : It is used to generate events for analog input points. Event data are generated at Analog Input Points
which have had changes in excess of the preset deadband values. Deadband values can be set individually for
points which support this Object. Event does not occur when deadband values become 65535 which is full range.
7 6 5 4 3 2 1 0
Forward(1),
Lockout(1), Operation Failed(1)
4 3 2 1 Reverse(2),
Unresolved(0) Operation Successful(0)
Unresolved(0)
The operation result shows failure of trip or failure of reclosing operation; the final state indicates the
state of lockout or initialization of auto reclosing sequence.
Trip count shows the number of recloser operations in the recent sequence.
The fault type info indicates the faulty phase and detailed fault info.
A,B,C refer to phase where the fault occurred; N refers to neutral.
SEF - sensitive earth fault, NPS - negative sequence OC, HCT - high current trip/lockout, VT - voltage
element.
7 6 5 4 3 2 1 0
Analog output points include protection element setting parameters per group, setting parameters for line
operation, various parameters for the operation of the recloser and control. These are used for setting and
verification of parameters.
Object
Point No. Database ID Condition Remark
Variation
Default Range
1 Sets the directional control for the phase O/C element. If 1, operation is only performed on forward
fault location; if 2, operation is only performed on reverse fault location; if 0, operation is performed
regardless of fault direction. (0: Bi-direction,1:Forward,2:Reverse)
Directional Control Blocking 1 0~1 40/02,41/02 Disable/Enable
2 If the polarizing quantity is below the set Threshold, set whether it operate or not. If the item is set to
‘Enable’, the control performs trip operation even if the polarizing quantity is less than the set
threshold.
V1 Threshold 0.20pu 0.01~1pu 40/02,41/02 V1
3 Sets the threshold of the polarizing quantity(V1) for phase directional OC element's fault direction
detection. Operation is not performed if V1 is below the set threshold. Operation quantity becomes
I1.
Maximum torque angle 315° 0~359° 40/02,41/02
4 Sets the maximum torque angle for detecting phase directional OC element's fault direction. It has a
CCW phase angle based on V1.
Operations Settings - Phase OC Element
Operations to Lockout 4 1~4 40/02,41/02
5
Sets the total no. of operations for phase OC elements.
Operations - Fast Curve 2 0~4 40/02,41/02
6
Sets the no. of fast curve operations from phase OC element's total no. of operations.
26 Sets the directional control for the phase O/C element. If 1, operation is only performed on forward
fault location; if 2, operation is only performed on reverse fault location; if 0, operation is performed
regardless of fault direction. (0: Bi-direction,1:Forward,2:Reverse)
Directional Control Blocking 1 0~1 40/02,41/02 Disable/Enable
27 Set whether to operate when Polarizing Quantity is below the set Threshold. If the item is set to
‘Enable’, the control performs trip operation even if the polarizing quantity is less than the set
threshold.
3Vo Threshold 0.20pu 0.01~1pu 40/02,41/02 V1
28 Sets the threshold of the polarizing quantity(3Vo) for phase directional OC element's fault direction
detection. Operation is not performed if 3Vo is below the set threshold. Operation quantity becomes
3Io.
Maximum torque angle 135° 0~359° 40/02,41/02
29 Sets the maximum torque angle for detecting ground directional OC element's fault direction. It has a
CCW phase angle based on Vo.
Operations Settings – Ground OC Element
Operations to Lockout 4 1~4 40/02,41/02
30
Sets the total no. of operations for ground OC elements.
Operations - Fast Curve 2 0~4 40/02,41/02
31
Sets the no. of fast curve operations from ground OC element's total no. of operations.
56 The threshold for of the ground OC cold load pickup element; set to a multiple of ground OC
element's pickup current. If the current over the set threshold is detected, the delayed curve is
operated.
57 Restore Time - Ground 3,600s 0~18,000s 40/02,41/02
Curve Type - Ground 31(14) 0~43 40/02,41/02
58
Selects the TCC curve for the ground OC cold load pickup element.
Multiplier - Ground 1 0.05~2.00 40/02,41/02
59
Sets the multiplier(time dial) for the ground OC cold load pickup element’s TCC curve.
Time Adder - Ground 0 0~1.00s 40/02,41/02 0 : Not Used
60
Sets the time adder for the ground OC cold load pickup element’s TCC curve.
Min. Response Time - Ground 0 0~1.00s 40/02,41/02 0 : Not Used
61
Sets the minimum response time for the ground OC cold load pickup element’s TCC curve.
Natural time 15s 0~18,000s 40/02,41/02
62 Time to release cold load pickup element; released if the current is maintained lower than the OC
element’s pickup current for the set time.
Loss of Load Diversity Time 3,600s 0~18,000s 40/02,41/02
63 Time to enable operation of cold load pickup element; starts upon lockout. When this time is
completed, the fast curve is disabled and the delayed curve operates. If the recloser is successfully
closed before this time is completed, the cold load pickup element does not operate.
Inrush Restraint Settings
Restraint Level 0 0, 5-50% 40/02,41/02 0 = Off
64 Sets the threshold of the 2nd harmonic content for the harmonic restraint operation. If the content
exceeds the set value, inrush restraint elements operate.
Detection Time 0.02s 0.02-1s 40/02,41/02
65 Sets the time width for detecting harmonic content. If the 2nd harmonic content exceeds the set
threshold level and is maintained for the detection time, the inrush restrain element is operated.
Restraint Time 2.00s 0-10.00s 40/02,41/02
66 Sets the time for operating the inrush restraint element.
If inrush current is detected by the setting, fault detection is inhibited during the set inhibition time.
Sequence Coordination
70 Sequence Coordination 0 0,1 40/02,41/02 Disable/Enable
Set to enable functions so that multiple reclosers connected in series don't operate simultaneously for
the same fault. Enabled if set to 1.
Sequence Coordination Mode 0 0,1 40/02,41/02 Fast/All
71 Set sequence which is applied to Sequence Coordination function. If set ‘Fast(0)’, it only applies to
Fast curve. If set, ‘All’, it is applied to all curves.
Ground Trip Precedence
Ground Trip Precedence 0 0,1 40/02,41/02 Disable/Enable
72 Sets the no. of ground OC element's operations to precede that of phase OC elements from the total
no. of operations. Enabled if set to 1.
SEF Element Settings
Operation Mode 0 0,1 40/02,41/02 Disable/Enable
73
Sets the SEF element's operation mode. If 0, the SEF element does not operate..
Use of Zero Sequence CT 0 0,1 40/02,41/02 Disable/Enable
74 Sets whether to use zero sequence CT(ZCT). The Pickup Current-3Io set range changes according to
this setting. Set to Enable to use ZCT; set to Disable if ZCT should not be used.
Directional Control 0 0~2 40/02,41/02 BI/F/R
75
Sets the SEF element's direction of operation. (0:Bi-Direction,1:Forward, 2:Reverse,)
Directional Control Blocking 1 0~1 40/02,41/02 Disable/Enable
76 Set whether to operate when Polarizing Quantity is below the set threshold. If the item is set to
‘Enable’, the control performs trip operation even if the polarizing quantity is less than the set
threshold.
3Io Pickup Current 2A 2~20A 40/02,41/02
77 Sets the pickup current of the operating quantity(3Io) for the SEF element's operation. If ZCT is used,
the set range is 0.1A ~20A; if not, the set range is 2A ~ 20A.
3Vo Threshold 0.20pu. 0.01~1pu 40/02,41/02 3Vo
78
Sets the threshold of the Polarizing Quantity(3Vo) for the SEF element's operation.
Maximum Torque Angle 270° 0~359° 40/02,41/02
79 Sets the maximum torque angle for the detection of directional SEF. It has a CCW phase angle based
on Vo.
Operations to Lockout 4 1~4 40/02,41/02
80
Sets the total no. of operations for SEF elements.
Operations - Fast Curve 2 0~4 40/02,41/02
81
Sets the no. of fast curve operations from total no. of operations for SEF elements.
Definite Time - Fast Curve 1.00s 0~180.00s 40/02,41/02 0 : Off
82
Sets the definite time of the SEF element's fast curve operation.
Curve Type - Fast Curve 19(1) 0~43 40/02,41/02
83 Sets the TCC curve of the SEF curve's fast curve. It operates by TCC curve only when definite time set
‘0’.
Multiplier - Fast Curve 1 0.05~2.00 40/02,41/02
84
Sets the multiplier for the SEF element's fast curve.
Time Adder - Fast Curve 0 0~1.00s 40/02,41/02 0 : Not Used
85
Sets the time adder for the SEF element's fast curve.
Min. Response Time – Fast Curve 0 0~1.00s 40/02,41/02 0 : Not Used
86
Sets the minimum response time for the SEF element's fast curve.
Max. Response Time – Fast Curve 0 0~100.0s 40/02,41/02 0 : Not Used
87
Sets the maximum response time for the SEF element's fast curve.
Reset Time – Fast Curve 0 0~180.00s 40/02,41/02
88 It is as corresponding to reset time of electromagnetic relay, only immediate reset and definite time
reset is provided.
89 Definite Time - Delayed Curve 1.00s 0~180.00s 40/02,41/02 0 : Off
90 Curve Type - Delayed Curve 31(14) 0~43 40/02,41/02
91 Multiplier - Delayed Curve 1 0.05~2.00 40/02,41/02
92 Time Adder - Delayed Curve 0 0~1.00s 40/02,41/02 0 : Not Used
93 Min. Response Time - Delayed Curve 0 0~1.00s 40/02,41/02 0 : Not Used
Max. Response Time - Delayed Curve 0 0~100.0s 40/02,41/02 0 : Not Used
94
Sets parameters related to the fast and delayed curve for the SEF element.
Reset Time - Delayed Curve 0 0~180.00s 40/02,41/02
95 It is as corresponding to reset time of electromagnetic relay, only immediate reset and definite time
reset is provided.
Reclosing Interval Settings – SEF Element
96 1st Reclosing Interval 0.6s 0.5~180.0s 40/02,41/02
97 2nd Reclosing Interval 2s 1~180s 40/02,41/02
101 Set whether to operate when Polarizing Quantity is below the set threshold. If the item is set to
‘Enable’, the control performs trip operation even if the polarizing quantity is less than the set
threshold.
I2 Pickup Current 100A 5~960A 40/02,41/02
102
Sets the pickup current of the operating quantity(I2) for the NPS element's operation.
V2 Threshold 0.10pu 0.10~1pu 40/02,41/02
103
Sets the threshold of the Polarizing Quantity(V2) for the NPS element's operation.
104 Maximum torque angle 135° 0~359° 40/02,41/02
Sets the maximum torque angle for the detection of directional NPS element. It has a CCW phase
angle based on V2.
Operations to Lockout 4 1~4 40/02,41/02
105
Sets the total no. of operations for NPS elements.
Operations - Fast Curve 2 0~4 40/02,41/02
106
Sets the no. of fast curve operations from total no. of operations for NPS elements.
Definite Time - Fast Curve 0.10s 0~180.00s 40/02,41/02 0 : Off
107
Sets the definite time of the NPS element's fast curve operation.
Curve Type - Fast Curve 0(A) 0~43 40/02,41/02
108 Sets the TCC curve of the NPS curve's fast curve. It operates by TCC curve only when Definite Time
set ‘0’.
Multiplier - Fast Curve 1 0.05~2.00 40/02,41/02
109
Sets the multiplier for the NPS element's fast curve.
Time Adder - Fast Curve 0 0.01~1s 40/02,41/02
110
Sets the time adder for the NPS element's fast curve.
Min. Response Time - Fast Curve 0 0~1.00s 40/02,41/02
111
Sets the minimum response time for the NPS element's fast curve.
Max. Response Time - Fast Curve 0 0~10.0s 40/02,41/02
112
Sets the minimum response time for the NPS element's delayed curve.
Reset Time – Fast Curve 0 0~180.00s 40/02,41/02
113 It is as corresponding to reset time of electromagnetic relay, only immediate reset and definite time
reset is provided.
114 Definite Time - Delayed Curve 0.10s 0~180.00s 40/02,41/02 0 : Off
115 Curve Type - Delayed Curve 1(B) 0~43 40/02,41/02
116 Multiplier - Delayed Curve 1 0.05~2.00 40/02,41/02
117 Time Adder - Delayed Curve 0 0~1.00s 40/02,41/02 0 : Not Used
118 Min. Response Time - Delayed Curve 0 0~1.00s 40/02,41/02 0 : Not Used
Max. Response Time - Delayed Curve 0 0~100.0s 40/02,41/02 0 : Not Used
119
Sets parameters related to the fast and delayed curve for the NPS element.
Reset Time - Delayed Curve 0 0~180.00s 40/02,41/02
120 It is as corresponding to reset time of electromagnetic relay, only immediate reset and definite time
reset is provided.
Reclosing Interval Settings – NPS Element
121 1st Reclosing Interval 0.6s 0.5~180.0s 40/02,41/02
122 2nd Reclosing Interval 2s 1~180s 40/02,41/02
123 3rd Reclosing Interval 15s 1~180s 40/02,41/02
Set reclose intervals for NPS elements.
Current and Voltage Unbalance Element Settings
Operation Mode - Voltage
124 0 0~2 40/02,41/02 D(0)/T(1)/A(2)
Unbalance
125 Threshold - Voltage Unbalance 20% 0, 5~100% 40/02,41/02
126 Delay Time - Voltage Unbalance 30s 1~180s 40/02,41/02
127 Reset Time - Voltage Unbalance 3s 1~180s 40/02,41/02
128 Operation Mode - Current Unbalance 0 0~2 40/02,41/02 D(0)/T(1)/A(2)
129 Threshold - Current Unbalance 20% 0, 5~100% 40/02,41/02
130 Delay Time - Current Unbalance 30s 1~180s 40/02,41/02
131 Reset Time - Current Unbalance 3s 1~180s 40/02,41/02
The voltage and current unbalance is defined as the percentage of the negative sequence component
to the positive sequence component. If maintained over the Threshold Delay Time, an alarm is
generated.
Operation Mode: Disable(0)-no operation, Trip(1) – trip, Alarm(2) – only alarm at set conditions.
Loss of Phase Protection Element Settings
132 Operation Mode 0 0~2 40/02,41/02 D(0)/T(1)/A(2)
133 Definite Time 30s 1~180s 40/02,41/02
134 Reset Time 3s 1~180s 40/02,41/02
Setting for loss of phase element; this element only operates by definite time characteristics when line
is in loss of phase state. Loss of phase state is determined based on the set Off Level.
Operation Mode: Disable(0)-no operation, Trip(1) – trip, Alarm(2) – only alarm at set conditions. at
set conditions.
Http://www.bh-system.com