Quote No:SSLG/2024-25/22321 Date: 04/06/2024

Annexure C

TECHNICAL SPECIFICATION & DETAILS

Technical Specifications
Number of Phase : 3 Phase
Applicable Standard : IS1180 EE Level 1
Number of Winding : 2 Nos
Installation Type : Outdoor
Cooling Type : ONAN
Terminal Arrangement : Bare Bushing for HV & Cable Box LV Side
Vector Group : Dyn 11
Ambient Temperature : 50° C
Temperature Rise of Oil : 40° C
Temperature Rise of Winding : 45° C
Impedance : 5.00% (Subject to +/-10% Tolerance)
Transformer Oil : "A Grade" tested & certified as per IS:335 Standard.
Total Losses at 50% Load : As per as IS1180 EE Level 1
Total Losses at 100% Load : As per as IS1180 EE Level 1
Copper : Pure Electrolytic Grade.
Tapping Mode : +5% to -10% in steps of 2.5% by Off Circuit Tap
Changer
Basic Insulation Level for HV : 75 KV peak / 28 KV rms
Basic Insulation Level for LV : - / 3 KV rms
Output Voltage : 433 V
Input Voltage : 11 KV
Capacity : 1250 KVA
Make : Servokon
Standard Fittings - Oil Conservator with Oil Filling Hole : 1 Nos
and Drain Plug
Standard Fittings - Rotary Type Off Circuit Tap Changer : 1 Nos
(OCTC) with Locking Arrangement & Tap Indication
Standard Fittings - Porcelain Type Bare Bushing with : 3 Nos
Brass Stud & Fitting Accessories for HV Termination
Standard Fittings - Epoxy Insulator for LV Termination : 1 Nos
Standard Fittings - Rating Plate/Diagram Plate : 1 Nos
Standard Fittings - Monogram Plate : 1 Nos
Standard Fittings - Explosion Vent with Diaphragm : 1 Nos
Standard Fittings - Thermometer Pockets : 1 Nos
Standard Fittings - Additional thermometer Pocket : 1 Nos

Page 1 of 2
Quote No:SSLG/2024-25/22321 Date: 04/06/2024
Standard Fittings - Drain cum Bottom Filter Valve : 1 Nos
Standard Fittings - Cable Box for LV Side : 1 Nos
Standard Fittings - Uni-Directional Flat Wheels : 4 Nos
Standard Fittings - Buchholz Relay with Alarm & Trip : 1 Nos
Contacts
Standard Fittings - Magnetic Oil Level Gauge with : 1 Nos
Alarm Contact
Standard Fittings - Marshalling Box : 1 Nos
Standard Fittings - CT for WTI : 1 Nos
Standard Fittings - Prismatic Oil Level Gauge with : 1 Nos
Minimum, Normal & Maximum Marking
Standard Fittings - Winding Temperature Indicator with : 1 Nos
Alarm & Trip Contacts
Standard Fittings - Lifting Lugs : 4 Nos
Standard Fittings - Earthing Terminals : 2 Nos
Standard Fittings - Dehydrate Silica Gel Breather : 1 Nos
Assembly
Standard Fittings - Top Filter Valve : 1 Nos
Standard Fittings - Air Release Plug : 1 Nos
Standard Fittings - Jacking Pads : 1 Nos
Standard Fittings - Top Cover Lifting Eyes : 2 Nos
Standard Fittings - Oil Temperature Indicator with Alarm : 1 Nos
& Trip Contacts
Standard Fittings - Conservator Shut Off Valve : 1 Nos
Standard Fittings - Drain Valve for Conservator : 1 Nos
Standard Fittings - Neutral Bushing for LV Cable Box : 1 Nos
Standard Fittings - First Filling of Fresh Mineral Oil as : 1 Nos
per IS:335
Standard Fittings - Detachable Type Pressed Steels : 1 Nos
Radiators for Natural Cooling
Standard Fittings - CT Neutral : 1 Nos