Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

TRANSMISSION LINE MODELS FOR SWITCHING STUDIES: DESIGN CRITERIA

II. SELECTION OF SECTION LENGTH, MODEL DESIGN AND TESTS


G.L. Wilson and K.A. Schmidt
Massachusetts Institute of Technology
Cambri dge, Massachusetts

ABSTRACT range.
A criterion is presented and evaluated for estab- With the goal of providing some insight into the
lishing the relation between section length of atrans- expected behavior of a model, we consider the natural
mission model and the desired accuracy over afrequency frequencies of an exact lossy single phase transmis-
band. This criterion along with those established in sion line of length Q with either an open or short
a companion paperl are used to design a transmission circuit at the receiving end of the line. Then the
line model. The details of the design are presented. impedance seen at the sending end for the two cases of
Test results made on a newly constructed model are open and short circuited termination are given by
presented to establish the validity of the design
criteria. Zs.c. = ZO coth yQ (1)
I. INTRODUCTION Zo.c. = ZO tanh yt (2)
In a companion paper the effects of nontransposi- where
tion are evaluated in terms of modeling power transmis-
sion line switching operations. It was shown that
nontransposition and model parameter variations with (3)
frequency are important in processing overvoltage fre-
quency components.
The number of lumped sections used to model a y = R + sL)sC (4)
given transmission line is seldom discussed in the
literature and is apparently somewhat arbitrary. This
paper is an effort to evaluate the effect of section where R, L and C are the line parameters per unit
length, to present criteria for designing accurate length and s is the complex frequency. For the short
transmission line models and to evaluate their accuracy circuit case, the poles of the impedance occur when
over the frequency spectrum. An analysis which results sinh Yt = 0, for the open circuit case they occur when
in an evaluation of model performance as a function of cosh yZ = 0.
the number of sections employed is first presented.
The results lead to design criterion for choosing sec- The resulting natural frequencies can be found
tion length. Using all the criteria developed in this from these conditions with the result
and the companion paper, a transmission line model is
designed. A description of the transmission line
model design is presented with a series of measure-
ments made on the model to evaluate its performance. ss.c =
R
= - R(L 4+( R__) -
- ( ) + (2n+l)2Tr2
LC n = 0,1,2... (5)
As in the companion paper, the characteristics of
a 765 kV line is used as an example of the modeling
performance and evaluation. However the final M.I.T.
model is useful for transmission line modeling of
lines in the 200 kV to 1100 kV range. So. C. = -
c2) ± i- - 2C n = 0,1,2... (6)

II. EFFECT OF NUMBER OF MODEL SECTIONS ON ACCURACY The natural frequencies of a continuous line are
given by Eqs. (5) and (6). One method of evaluating
In modeling a continuum system like a transmis- the behavior of a given lumped model and that of a
sion line with a finite number of discrete or lumped continuous line is to compare the natural frequencies
sections, certain inaccuracies exist due to the dis- of the two systems. This is not a rigid criteria, but
crete nature of the modeling process. Transmission since the natural frequencies play an important role
line models employed at present consist of a number of in the entire switching transient, the criterion is
sections representing a fixed length of line. Thus if certainly reasonable.
a model of a 100 mile line contained 10 sections; that
of a 200 mile line would contain 20 sections. To the During this study a number of transmission line
authors' knowledge no criteria or tests have been pub- models (L's, T's, Tr's, r's) were considered. The
lished to establish or demonstrate the accuracy of results are quite similar for all cases, and the L
such a modeling technique. It is a fundamental fact section analysis only is presented. A schematic dia-
that the model is completely inaccurate above the cut- gram of a single phase L-section model is shown in
off frequency, which is the natural frequency of one Fig. 1 with a shorted termination. The lumped element
section. Even at frequencies well below cutoff, the parameters of Fig. 1 are related to those of a contin-
frequency performance of the line can be quite inac- uous line by
curate. The above should be tempered by the fact that
the higher frequency response of a line may form a
very small part of the spectral content of a switching s m (7)
waveform. However when line models are used to pre-
dict switching surges,which have considerable spectral
content in the kilohertz range, some criteria should s m (8)
be available to evaluate the model in that frequency
Paper C 72 2124, recommended and approved by the Transmission and Distribution Committee of the IEEE Power Engineering Society for presentation atthe
IEEE PES Winter Meeting, New York, N.Y., January 28-February 2, 1973. This paper was upgraded to transactions status, T 72 2124, for presentation by title for written
discussion at the IEEE PES Summer Meeting, Vancouver, B.C., Canada, July 15-20, 1973. Manuscript submitted September 17, 1971; made available for printing May 14,
1973.
389

Authorized licensed use limited to: J.R.D. Tata Memorial Library Indian Institute of Science Bengaluru. Downloaded on June 05,2024 at 06:37:10 UTC from IEEE Xplore. Restrictions apply.
C5 = __ (9) Equation (17) is a polynominal in the real vari-
able cosh X so that solutions, [cosh Airoots yield
the complex propagation constants in the expression
where m is the number of sections in the model. The for the short circuit termination natural frequencies
given by

ssec. - R) ±
s.c. ( 2L-) [ELC21-[coshX] root]
2.~~~~ ro (18)

An error criteria can then be developed by defin-


ing the % error in the pole location as
Im[Eq. 18]-Im[Eq.
Ple ro =mm
5]
Percent (19)

This is plotted as a function of the pole number


in Fig. 2 for the lossless case. When losses are zero
the pole error is not a function of line length para-
meters. Note that Fig. 2 consists of continuous
curves for ease of comprehension. In actuality each
curve should be represented as a series of discrete
points at each pole number.
Fig. 1 Schematic of L-Section Model.
Shorted Termination 8

equations for the model are given by

VN VNl = sLs In + RsIn (10)


4
IN+l IN - = sCs VN (11)

where solutions of the form 2

VN = Re[VN et] (12)


0 0

IN = Re[tIN
e (13) LL
-0
0-

have been assumed.


If solutions of the form Sections
Sections
VN = A cosh An + B sinh An (14) Sections
are assumed, then Eqs. (10) and (11) impose the condi - Sections
tion on the complex propagation constant A.
c A 2L C sRsCs
cosh A=lI+ s (15)
2 2-T
Fig. 2 Plot of Pole Error Vs. Pole Number,
When the boundary condition at the termination L Section Line, Shorted Termination
VO = 0 is applied, the impedance seen at n = m in Fig.
1 is found to be
For a particular line, the natural frequency
(R +sL s ) sinh mA corresponding to a pole number is found from the
z
s.c. sinh mA-sinh(m-l)X (16) imaginary part of Eq. (5). Figure 2 indicates that
for a low number of sections, the error in the pole
location is high at both low (<3) and high (>3) pole
The poles of Eq. (16) are found by setting the numbers. This is explained by the fact that the
denominator equal to zero shorted termination on a L section line, removes the
capacitor from one section and therefore increases the
spectral location of the low order pole. This phenom-
sinh mA-sinh(m-l)A = 0 (17) enon at low pole numbers can be an important factor.

390

Authorized licensed use limited to: J.R.D. Tata Memorial Library Indian Institute of Science Bengaluru. Downloaded on June 05,2024 at 06:37:10 UTC from IEEE Xplore. Restrictions apply.
For example, the first pole of a 100 mile 765 kV line
would occur at 456 Hz. If this line were modeled with
say 15 mile sections, the error of the pole location
at this frequency would be on the order of 8%. As the
number of sections increases, this error is of course
reduced as is the error at high pole numbers. 6
If a similar plot is made for an open circuited 50/o Boundary
L-section model, the plot of Fig. 3 results. In this
case the low pole number error is zero for a very few
number of sections, since no part of an L-section is
removed by the termination.
10
2
1%. \- 12 L-Sections(Shorted)
r
5 0
0 2 3\ 4 10
0LJ
5 6 7 8 9
-0
0-
POLE NUMBER
0 \ \ 12
i L-Sections (Nominal)
-2 -

0
-5

0`2 5% Boundary

5°/% Boundary
-to -6

-15 Fig. 4 Example of an "Error Band-Error Bound"


Plot for a Twelve Section L-Model

-20 region between these lines is the "error band" of the


twelve section L model. If twelve sections are used
to model a sixty mile line, the error band lies within
the error bounds up to about the fifth pole. For a
sixty mile line, the fifth pole corresponds to about
6000 Hz. One could say then "the 12-section model is
good to within five percent" up to 6000 Hz. For a
Fig. 3 Plot of Pole Error Vs. Pole Number, four hundred mile line, the same analysis indicates
L-Section Line, Open Termination that a forty section model is "good to within five
percent" up to the fifteenth pole corresponding to a
frequency of about 3100 Hz.
Thus it is concluded that the error in using few
L sections to model lossless lines can be appreciable For most lines, especially EHV and UHV lines, Q
when the line terminations look like short circuits at or X/R ratio of the lines is relatively high at most
the frequency of interest. frequencies. Thus a given resonance is a very sharp,
narrow band region in the frequency spectrum. An
If zero sequence parameters are used to model the error in natural frequency location can result in an
line, the assumption of no loss is invalid. The same appreciable error in the impedance at that frequency
analysis is still applicable and the results are still due to high Q.
very similar to those of Figs.2 and 3 for a wide range
of line lengths. The above analysis is in the frequency domain and
in order to meaningfully interpret the results it is
The authors made similar studies for iT, T and r desirable to relate the errors presented in Figs. 2, 3
sections. The same general results occur. In the case and 4 to switching surge voltage. This is of course
of T sections for example, the low pole number error difficult to do in the general case due to the nonlin-
for open circuit terminations is nonzero although less earities of transformers and reactors present in the
than that of Fig. 3 since only one half of a section circuit. However a representative interpretation can
inductance is removed by open circuiting the end of be made as follows. Consider a 195 mile line which is
the line. modeled with 13 fifteen mile sections. The error at
the first pole is found from Fig. 2 to be 3.5%.
A suggested method of using the pole error plots
is shown in Fig. 4 in which the pole error "curves" Using this frequency shift relative to the pole
of a twelve section L model are taken from Figs. 2 for a typical 765 kV line, the impedance ratio of that
and 3. A five percent error bound is suggested by the at resonance to that at a frequency 3.5% off of reso-
dotted lines at the top and bottom of the figure. The nance can be calculated from Eqs. (1), (3) and (4) and

391

Authorized licensed use limited to: J.R.D. Tata Memorial Library Indian Institute of Science Bengaluru. Downloaded on June 05,2024 at 06:37:10 UTC from IEEE Xplore. Restrictions apply.
is found to be 14. The fourier spectrum of a switch-
on cosinusoidal wave contains a 17% harmonic at 240
Hz, the first natural frequency of the line. If the
source reactance of the line and leakage reactances
of the transformer are given typical values, the fre-
quency error will cause only 8% of this harmonic to
appear across the sending end of the line as compared
to the full 17% when there is no error in modeling.
This change in the 240 Hz-harmonic can cause an equiv-
alent change in the switching surge peak, or a change
of .09 p.u.
If nonlinear effects are included, the transform-
er harmonics, which are considerable at 180 and 300
Hz, could be affected in the same way as in the exam-
ple above by the line modeling error discussed.
In conclusion then, it is not satisfactory to
model transmission lines with fixed length sections
alone. For lines on the order of sixty miles, the Fig. 5 One Section of Nontransposed Line Model
authors feel that at least fifteen sections should be
used, while for four hundred mile lines, a minimum of For each system to be modeled an impedance scal-
forty sections should be used, to keep the accuracy of ing factor is used to bring the parameter values for a
the model within reasonable limits at frequencies up given line within those for the model. This is espe-
to 3 kilohertz.
cially important with regard to model inductors. A
VI. DESIGN OF A TRANSMISSION LINE MODEL wide range of inductance values could be achieved from
a given magnetic circuit using taps. However for a
In view of the above analysis and that in the wide range of taps, the Q of the inductor deteriorates
companion paper, several conditions or criteria are at the lower taps. One of the constraints in the mod-
evident for the design and performance of an accurate eling procedure is the high X/R ratios required for
transmission line model. phase inductance modeling. An alternative to tapping
is the use of many cores which is expensive and space
consuming. The best solution then is to scale the line
1) The line must model the effects of impedances which result in phase inductance model
transposition in order to accurately values that require only 13% variation in inductance
predict overvoltage behavior for lines while the actual line values vary by a factor of two.
in the 300 kV to 1500 kV voltage
range. A study was made to evaluate various materials
for the magnetic core. Mo-Ni toroidal cores were
2) The effects of parameter variation chosen for the high Q values they produce as well as
with frequency must be modeled. This the small variation in core permeability with fre-
variation is somewhat important in quency and current that they exhibit. This resulted
modeling phase resistance and produces in maximum phase inductor 60 Hz Q's of 30 for the
large variations in both neutral induc- model. The phase A and B inductors have second tapped
tance and resistance over a wide range windings tD model the mutual inductance between phases.
of frequencies. The self inductance of each phase is independent of
frequency up to 5 kilohertz.
3) The number of sections used must be
compatible with the desired accuracy The resistance in each phase varies with fre-
of the model. For short lines (on the quency due to the core characteristics of the mag-
order of tens of miles) fifteen to netic toroids used. By adding external resistances to
twenty sections must be used to achieve the core, the correct value of model phase resistance
accuracies of 5% up to 6 kilohertz. as a function of frequency is achieved within + 5% up
For longer lines (on the order of to % 2 kilohertz.
hundreds of miles) the number of sec-
tions used should reflect some Phase to phase and phase to neutral capacitances
criterion like that in the above are modeled with a combination of polystyrene and
analysis of impedance poles. mylar capacitors to achieve the low dissipation fac-
tors required during high speed reclosure operations
With these guidelines, a model was designed by wherein the line may resonate with high Q(%300) com-
the authors which achieves these goals. Each section pensating reactors.
of line model is like that of Fig. 5 in order to model
the effects of nontransposition for both horizontal The important variations of neutral resistance
and vertical configurations. and inductance with frequency are modeled with spe-
A careful study was made of the parameter values cially designed cores in which the skin effect phe-
nomenon is affected by inserting appropriately sized
necessary to model 345, 500, 765 and projected 1100 conducting sheets in the air gaps of the cores. This
and 1500 kV lines. Both horizontal and delta config- effectively creates a frequency dependent air gap.
urations were considered for EHV and UHV lines while For various earth resistivities, different size con-
hori zontal and verti cal confi gurati ons were cons i dered ducting sheets are used. The details of this design
for lower voltage systems. In order to model each of are rather involved and will be reported in a later
the parameters within 5% of the nominal value, every paper along with performance tests in switching opera-
attempt is made to construct a model with as narrow a tions.
range of parameter values at a particular frequency as
possible. The result is a model which is designed to In order to meet the requirements on section
operate at a nominal voltage of 138 volts. length outlined above, the MIT line model consists of
392

Authorized licensed use limited to: J.R.D. Tata Memorial Library Indian Institute of Science Bengaluru. Downloaded on June 05,2024 at 06:37:10 UTC from IEEE Xplore. Restrictions apply.
35 four mile sections and 30 eight mile sections. Preliminary tests have been made on a portion of
This results in line models that are within 5% error the transmission line model. Since the neutral com-
bounds up to 10 kilohertz for long lines. A view of ponents have not yet been constructed, tests in which
one section is shown in Fig. 6. Parameter values are model line behavior are compared with theoretical pre-
selected by using banana jacks. This method was dictions for a continuum line will be made and report-
chosen over switches in order to more carefully con- ed in the future.
trol contact resistance. A view of one cabinet of
line sections is shown in Fig. 7. Two preliminary sets of measurements were made on
a horizontal linel76 miles long using twenty-two eight
mile sections. Each set consisted of measuring the
impedance of phase a to neutral with the receiving end
phases and phases b and c of the sending end shorted
to neutral. By measuring the impedance as a function
of frequency, the natural frequencies of the line can
be observed. The impedance in the region of the first
natural frequency for the case where the model is con-
nected to represent the transposed line is presented
in Fig. 8.
It is seen that the first pole occurs at 266 Hz.
The second major pole occurring at 768 Hz is shown
along with an intermediate resonance due to the slow
propagation mode occurring at 570 Hz. The location of
this intermediate pole would change with neutral leg
inductance variations.

Fig. 6 MIT Transmission Line Section The same line when modeled as a nontransposed
circuit results in measured impedance values near the
first pole as presented in Fig. 9.

FREQUENCY (HZ)

Fig. 8 Measured Impedance Near First Pole


Fig. 7 View of Bank of 8 Mile Model Sections for Transposed Line

393
orized licensed use limited to: J.R.D. Tata Memorial Library Indian Institute of Science Bengaluru. Downloaded on June 05,2024 at 06:37:10 UTC from IEEE Xplore. Restrictions a
and therefore 'harmonic imbalance, are important in
transient behavior of power lines with nonlinear ter-
minations.

ACKNOWLEDGEMENT
This work was supported in part by the American
Electric Power Service Corporation and in part by the
sponsors of the Philip Sporn Professorship in Energy
Processing at the Massachusetts Institute of Technol-
ogy.

REFERENCES

1. G.L. Wilson, R.F. Challen, D.J. Bosack, "Transmis-


sion Line Models for Switching Studies: Design Crite-
ria, I. Effects of Nontransposition and Frequency,"
submitted to IEEE, September 1971.

Combined Discussion 1,2


Dr. K.R. Shah (Commonwealth Associates Inc., Jackson, Mich. 49201):
The authors should be commended for their work. This paper gives, for
the first time, a sound analysis for selecting required number of lumped
sections for simulating distributed parameter transmission line behavior
over a large frequency range. In the past, selection of a number of
sections to simulate certain transient behavior was based on trial and
error methods. As pointed out by the authors, there is very little
published work on this aspect.
I believe that using the approach given in this paper one should be
FREQUENCY (HZ) able to make an intelligent selection of numberof sections required for
Fig. 9 Measured Impedance Near First Pole a given length, voltage rating of a line and desired frequency response.
In view of the above, I believe that this work should be kept as a
for Nontransposed Line permanent record, that is, it should be up-graded as a Transactions
paper.
Few typographical errors:
The first pole occurs at 268 Hz as in the case of (i) Pt. I, p. 3, fig. 3, the ordinate should read:
the transposed line. The second major pole is measur- V receiving
ed at 780 Hz. However in this case, there are two in- V sending
termediate poles as expected for the nontransposed (ii) Pt. II, Eqn. (6), - it seems Q is missing.
case, one at 520 Hz and a second at 563 Hz. Measure-
ments made on the same nontransposed model also indi- Manuscript received August 3, 1973.
cate the imbalances of phase to neutral potential as
expected.
The cutoff frequency for the line as modeled
with 22 sections occurred at 7170 kilohertz. Above
this frequency the model ceases to behave as a trans- M. Ramamoorty, (University of Waterloo, Waterloo, Ontario, N2L
mission line. The pole locations of the model in 3G1, Canada): The authors discuss a criterion for accurate modelling of
this frequency range are quite different from those of transmission lines for transient analysis.' They also bring about the
the continuum line to be modeled. effects of non transposition of conductors and the frequency depend-
ency of line parameters on the accuracy of transmission line models.
VII. SUMMARY AND CONCLUSIONS The authors are not correct in their statement that very little work has
been done to assess the inaccuracies resulting from simplified representa-
A series of analyses are presented to develop tions of line models ignoring asymmetry of conductors and assuming
criteria for designing accurate transmission line frequency independent parameters. There is much published literature
in this field which the authors have not included in their references.
models for switching study applications. Recently Magnussonl and Perzl have published data on modal
components for different frequencies and line configurations.
A criterion for evaluating the number of sec- The authors used a criterion based on the comparison of poles of
tions to be used for modeling a power transmission the open and short circuit impedance functions for a lumped parameter
line is developed. The results indicate that models model and a distributed line. An identical procedure is described in
on some existing switching analyzers may be inade- reference 3 by the discusser. An approprimate method for including the
quate, especially for short lines. ground effect on wave propagation is given in reference 4. In this paper
A transmission line model has been designed using Manuscript received August 6, 1973.
the criteria presented in the paper. Initial tests on
the model in the absence of neutral impedance repre- 1Transmission Line Models for Switching Studies: Design Criteria Part 1:
sentation illustrate the splitting of poles due to the Effects of Nontransposition and Frequency, G.L. Wilson, R.F. Challen, and D.J.
effects of nontransposition. Bosack, this issue, pp. 3 83
2Transmission Line Mvodels for Switching Studies: Design Criteria Part II:
It is expected that the effects of nontransposi- Selection of Section Length, Model Design and Tests, G.L. Wilson and K.A.
tion on pole splitting as well as on voltage imbalance Schmidt, this issue, PP- 389
394

Authorized licensed use limited to: J.R.D. Tata Memorial Library Indian Institute of Science Bengaluru. Downloaded on June 05,2024 at 06:37:10 UTC from IEEE Xplore. Restrictions apply.
the discusser considers the line parameter variation with frequency and ordinate in Figure 2 is correct and is the ratio of the sending end to
the effect of line asymmetry. source voltage. Similar curves can be obtained for the ratio of receiving
end to sending end voltage, but these were not included in the paper.
REFERENCES Dr. Shah is correct that an £ is missing in equation 6.
The authors stand by their statement that "Very little has been
[11 P.C. Magnussion. "Travelling waves on multi conductor open wire published concerning the justification for ignoring the effects of non-
lines" T72 5684. Presented at IEEE, Summer power meeting transposition and parameter variations with frequency." Since the paper
1972. was submitted in September of 1971, it would have been very difficult
[21 M.C. Perz et al. "Effects of earth resistivity on Modal parameters to include the papers (1), (2), and (4) referred to by Dr. Ramamoorty
of an EHV Horizontal line" T73 2284, Presented at IEEE winter all of which were published or presented after the paper under
power meeting 1973. discussion. The authors are not aware of data in the previous literature
[3] M. Ramamoorty et al, High Speed Protection of Power Systems that contradicts our statement.
based on Improved models." CIGRE 1968 Session 10. We were unfortunately not aware of Dr. Ramamoorty's paper in
-[4] M. Ramamoorty, "An approximate method to include ground CIGRE which briefly discusses pole comparisons for lumped lines. We
effect on Travelling waves, Proc. IEE Vol. 120, 1973. do not claim to have developed the procedure; the procedure is
standard. We do claim to have employed the procedure for a variety of
section lengths and frequencies and presented it in a form for use in
transmission line model design. The paper of reference 3 gives Series
Impedance and Shunt Admittance information, not pole frequency
G.L. Wilson, R.F. Challen, D.J. Bosack, and K.A. Schmidt. The authors error, and does so for a 25 km section only at discrete frequencies up to
appreciate Dr. Shah's comments and particularly his corrections. The 1 kilohertz. Figures 2 and 3 of Part II of the paper under discussion
contain information in a form that we have found to be useful for
Manuscript received September 28, 1973. transmission line model design.

395

Authorized licensed use limited to: J.R.D. Tata Memorial Library Indian Institute of Science Bengaluru. Downloaded on June 05,2024 at 06:37:10 UTC from IEEE Xplore. Restrictions apply.

You might also like