CÓDIGO DOC.PSSA CÓDIGO PROYECTO PÁGINAS: CÓDIGO CONTRATISTA Rev.
PDD-I-5081-41-2518-D005-07 5081 EPTI-13242-E-DWG-0019-GSYS 2
1 of 21
E.Lopez/
2 03/06/16 21 As Commissioned GSYS E.Peraza S.Hernandez N.Perez
H.Salazar
E.Lopez/
1 13/07/15 21 As Built GSYS E.Peraza L.Pena N.Perez
H.Salazar
E.Lopez/
0 19/05/15 20 As Built GSYS E.Peraza L.Pena N.Perez
H.Salazar
CHQ’D APR´D CHQ’D APR´D
REV. FECHA PAG EMISIÓN PREP’D
ARCO ARCO PSSA PSSA
PetroSinovensa
JB009 Circuit Diagram &
General Arrangement
PETROSINOVENSA
Early production Facility
Venezuela
4. CABLE COLOURS
THERE ARE AGREED DEPARTURES FROM THE CABLE COLOURS SPECIFIED IN IEC 60204-1 13.2.4,
WHICH ARE AS FOLLOWS: 360
DC CONTROL: MODULE 1 MODULE 2 MODULE 3 MODULE 4 MODULE 5 MODULE 6 MODULE 7
6. PLEASE NOTE, THE CLEARANCE DISTANCES AROUND ALL PLC AND HEAT GENERATING
COMPONENTS TO ANY OTHER COMPONENT OR TRUNKING SHALL BE A MINIMUM OF 40mm .
7. TERMINAL SYMBOLS:
NODE ADDRESS XXX
XS5
1. SIEMENS PLC EQUIPMENT, DETAILS LISTED BELOW:
30 x 100 TRUNKING
1x 16 CHANNEL DIGITAL INPUT MODULE
30 x 60 TRUNKING
30 x 60 TRUNKING
1x 8 CHANNEL DIGITAL OUTPUT MODULE
1x 8 CHANNEL ANALOGUE INPUT MODULE
1x 4 CHANNEL ANALOGUE OUTPUT MODULE XS2
1x 24 CHANNEL FS DIGITAL INPUT MODULE
1x 10 CHANNEL FS DIGITAL OUTPUT MODULE
1x 6 CHANNEL FS ANALOGUE INPUT MODULE
XS3
2. JUNCTION BOXES SHALL BE BASED UPON A DEPTH OF 200mm AND FITTED WITH A BOTTOM GLAND PLATE.
4. IN ADDITION TO THE ENCLOSURE THE VENDOR IS IS RESPONSIBLE FOR, BUT NOT LIMITED TO, THE SUPPLY OF THE
ADDITIONAL EQUIPMENT AND ALL OTHER MISCELLANEOUS ITEMS REQUIRED TO COMPLETE THE THIS JUNCTION
BOX.
ALL TERMINALS, CABLING AND CABLE CONTAINMENT AS DETAILED WITHIN THESE DRAWINGS
2 x INSULATED EARTH BARS.
5. CABLES & CABLE CORES SHALL CARRY THE INSTRUMENT DEVICE TAG REFERENCES AS DETAILED WITHIN THESE
DRAWINGS.
7. THE CABLE SCREEN AT THE FIELD INSTRUMENT SHALL BE TAPED BACK AND ISOLATED FROM EARTH POTENTIAL.
8. ALL INTERNAL JUNCTION BOX BONDING CONDUCTORS TO BE 2.5mm^ Y/G TO IEC 60332-3-24 INTERNAL LAYOUT
PROJECT No. P044
REV DESCRIPTION DATE AUTH CHKD APPD CLIENT NOTES:
CLIENT EXPRO PTI / PDVSA
TITLE:
0 AS BUILT 14/05/15 JP MPR JPM - CLIENT No.
SITE NAME
13242
P.SINOVENSA
JB DETAILS COALESCER B
1 P&ID REV 1 & F&G TERMINAL CHANGE 19/06/15 MPR JP JPM - LOCATION VENEZUELA JB LAYOUT AND
2 AS COMMISSIONED 03/06/16 RDM MPR JPM - GENERAL DETAILS
24V
24V5
0V 24VDC FOR MODULE 5 +24V
SHEET 7/8 0V5
0V
NODE ADDRESS XX
24V6
24VDC FOR MODULE 6 +24V
SHEET 9 0V6
0V
24V7
24VDC FOR MODULE 7 +24V
SHEET 10 0V7
0V
0V
24V
24V1
24V2
24V3
24V4
24V5
24V6
24V7
24V8
0V1
0V2
0V3
0V4
0V6
0V7
0V8
24V
0V5
0V
X1
INSULATED EARTH BAR
1-2 1-2
3-4 3-4 2 FEEDER
5-6 5-6 24Vdc
7-8 7-8
BK BN
9 - 10 9 - 10
11 - 12 11 - 12
2
13 - 14 13 - 14
15 - 16 15 - 16
17 - 18
XS1 17 - 18
19 - 20 19 - 20
21 - 22 21 - 22
23 - 24 23 - 24
25 - 26 25 - 26
27 - 28 27 - 28 XS5
29 - 30 29 - 30
31 - 32 31 - 32
1-2 33 - 34
3-4 35 - 36
5-6 37 - 38
7-8 39 - 40
9 - 10
XS2 41 - 42
11 - 12 43 - 44
13 - 14 45 - 46
15 - 16 47 - 48
1-2 1-2
3-4 3-4
5-6 5-6
7-8 7-8
9 - 10 XS3 9 - 10
11 - 12 11 - 12
13 - 14 13 - 14
15 - 16 15 - 16 XS6
1-2 17 - 18
3-4 19 - 20
5-6
XS4 1-2
24V1
TML
0V1
XS1 XS1
1 2 C1
ZSC-V3006 2 0 LCV-V3006 SOLENOID VALVE CLOSED
(T) (B) LIMIT
3 4 C2
ZSO-V3006 3 1 LCV-V3006 SOLENOID VALVE OPENED
(T)
2 (B) LIMIT
5 6 C3
4 2 COALESCER B TRANSFORMER A START BUTTON
2
HS-V3002A
(T) (B)
7 8 C4
HS-V3002B 5 3 COALESCER B TRANSFORMER B START BUTTON
(T) (B)
9 10 C5
SPARE 6 4 SPARE
(T) (B)
11 12 C6
SPARE 7 5 SPARE
(T) (B)
13 14 C7
SPARE 8 6 SPARE
(T) (B)
15 16 C8
SPARE 9 7 SPARE
(T) (B)
17 18 C9
SPARE 12 8 SPARE
(T) (B)
19 20 C10
SPARE 13 9 SPARE
(T) (B)
21 22 C11
SPARE 14 10 SPARE
(T) (B)
23 24 C12
SPARE 15 11 SPARE
(T) (B)
25 26 C13
SPARE 16 12 SPARE
(T) (B)
27 28 C14
SPARE 17 13 SPARE
(T) (B)
29 30 C15
SPARE 18 14 SPARE
(T) (B)
31 32 C16
SPARE 19 15 SPARE
(T) (B)
0V1
20 M 0V COMMON
SHEET 2 SHEET 2
I/O SLOT 2 24V2 0V2
8 CH DIGITAL OUTPUT MODULE X1 X1
6ES7322-1BF01-0AA0
24V2
0V2
FUNCTION CH TML DOUBLE TIER FEED THROUGH
24V2 TOP TERMINALS BOTTOM
1L+ 1
XS2 XS2
C1 1 2
COALESCER B LEVEL CONTROL 0 3 XV-V3006
SOLENOID VALVE (T) (B)
C2 3 4
SPARE
1 5 SPARE
(T) (B)
C3 5 6
SPARE
2 7 SPARE
(T) (B)
C4 7 8
SPARE
3 9 SPARE
(T) (B)
0V2
1M 10
2L+ 24V2
11
C5 9 10
SPARE 4 13 SPARE
(T) (B)
11 12
C6 SPARE
SPARE 5 15
(T) (B)
C7 13 14
SPARE 6 17 SPARE
(T) (B)
15 16
C8 SPARE
SPARE 7 19
(T) (B)
2M 20 0V2
C-S2
12c 0.5mm^ YY
24V3
6ES7331-7TF01-0AB0
0V3
TML CH FUNCTION
DOUBLE TIER FEED THROUGH
TERMINALS 1 L+
1 C1
2 0+
(T)
0 COALESCER B INTERFACE LEVEL
LIT-V3005
2 C2
3 0-
(B) INSTRUMENT
C-S3C0
EARTH BAR
0.5MM CY
3 C3
4 1+
(T)
1 COALESCER B OIL LEVEL
LIT-V3006
4 C4
5 1-
(B) INSTRUMENT C-S3C1
EARTH BAR 0.5MM CY
5 C5
6 2+
(T)
2 COALESCER B WATER FLOW
FIT-V3002
6 C6
7 2-
(B) INSTRUMENT C-S3C2
EARTH BAR 0.5MM CY
7 C7
8 3+
(T)
3 COALESCER B TRANSFORMER A
ET-V3002A
8 VOLTAGE
C8
9 3-
(B) INSTRUMENT C-S3C3
EARTH BAR 0.5MM CY
10 M
11 M
9 C9
12 4+
(T)
4 COALESCER B TRANSFORMER A
IT-V3002A CURRENT
10 C10
13 4-
(B) INSTRUMENT C-S3C4
EARTH BAR 0.5MM CY
11 C11
14 5+
(T)
5 COALESCER B TRANSFORMER B
ET-V3002B VOLTAGE
12 C12
15 5-
(B) INSTRUMENT C-S3C5
EARTH BAR 0.5MM CY
13 C12
16 6+
(T)
6 COALESCER B TRANSFORMER B
IT-V3002B CURRENT
14 C14
17 6-
(B) INSTRUMENT C-S3C6
EARTH BAR 0.5MM CY
15 C15
18 7+
(T)
7 SPARE
SPARE
16 C16
19 7-
(B) INSTRUMENT C-S3C7
EARTH BAR
0.5MM CY
20 M
FUNCTION CH TML
COM+ L+ 1
XS4
C1 1
Q0 3
(T)
S0+ 4
GAS RELEASE 0
CONTROL VALVE S0- 5 LCV-V3005
C2 2
M0 6
INSTRUMENT (B)
C-S4C0
EARTH BAR
0.5MM CY
C3 3
Q1 7
(T)
S1+ 8
SPARE 1
S1- 9 SPARE
C4 4
M1 10
INSTRUMENT (B)
C-S4C1
EARTH BAR
0.5MM CY
C5 5
Q2 11
(T)
S2+ 12
SPARE 2
S2- 13 SPARE
C6 6
M2 14
INSTRUMENT (B)
C-S4C2
EARTH BAR
0.5MM CY
C7 7
Q3 15
(T)
S3+ 16
SPARE 3
S3- 17 SPARE
C8 8
M3 18
INSTRUMENT (B)
C-S4C3
EARTH BAR
0.5MM CY
M 20
24V5
0V5
SLOT 5
24 CH FS DIGITAL INPUT MODULE - GROUP 1
X1
6ES7326-1BK02-0AB0
TML CH FUNCTION
1 1L+
2 1M
4 1Vs
XS3 XS3
1 2 C1 SDV-V3004 SHUTDOWN VALVE CLOSED
ZSC-V3004 5 0 LIMIT
5 6 C3
FD-009 7 2 FIRE DETECTOR FD-009
7 8 C4
PSH-V3002A 8 3 COALESCER B TRANSFORMER A HIGH
PRESSURE
9 10 C5
TSH-V3002A 9 4 COALESCER B TRANSFORMER A HIGH
TEMPERATURE
11 12 C6
LSL-V3002A 10 5 COALESCER B TRANSFORMER A LOW
LEVEL
11 2Vs
13 14 C7
PSH-V3002B 12 6 COALESCER B TRANSFORMER B HIGH
PRESSURE
15 16 C8
TSH-V3002B 13 7 COALESCER B TRANSFORMER B HIGH
TEMPERATURE
17 18 C9
LSL-V3002B 14 8 COALESCER B TRANSFORMER B LOW
LEVEL
19 20
HS-TX-V3002A C10 COALESCER B TRANSFORMER A ESTOP
15 9
21 22
HS-TX-V3002B C11 COALESCER B TRANSFORMER B ESTOP
16 10
2
2
23 24 C12
SPARE 17 11 SPARE
C-S5
18c 0.5mm^ YY
PROJECT No. P044
REV DESCRIPTION DATE AUTH CHKD APPD CLIENT NOTES:
CLIENT EXPRO PTI / PDVSA
TITLE:
0 AS BUILT 14/05/15 JP MPR JPM - CLIENT No.
SITE NAME
13242
P.SINOVENSA
JB DETAILS COALESCER B
1 P&ID REV 1 & F&G TERMINAL CHANGE 19/06/15 MPR JP JPM - LOCATION VENEZUELA MODULE 5 - 1
2 AS COMMISSIONED 03/06/16 RDM MPR JPM - CONNECTION DIAGRAM
24V5
0V5
SLOT 5
24 CH FS DIGITAL INPUT MODULE - GROUP 2
X1
6ES7326-1BK02-0AB0
TML CH FUNCTION
21 2L+
22 2M
24 3Vs
XS3 XS3
25 26 C1
SPARE 25 12 SPARE
27 28 C2
SPARE 26 13 SPARE
29 30 C3
SPARE 27 14 SPARE
31 32 C4
SPARE 28 15 SPARE
33 33 C5
SPARE 29 16 SPARE
35 36 C6
SPARE 30 17 SPARE
31 4Vs
37 38 C7
SPARE 32 18 SPARE
39 40 C8
SPARE 33 19 SPARE
41 42 C9
SPARE 34 20 SPARE
43 44 C10 SPARE
SPARE 35 21
44 46
C11 SPARE
SPARE 36 22
47 48 C12
SPARE 37 23 SPARE
C-S5
18c 0.5mm^ YY
PROJECT No. P044
REV DESCRIPTION DATE AUTH CHKD APPD CLIENT NOTES:
CLIENT EXPRO PTI / PDVSA
TITLE:
0 AS BUILT 14/05/15 JP MPR JPM - CLIENT No.
SITE NAME
13242
P.SINOVENSA
JB DETAILS COALESCER B
1 P&ID REV 1 & F&G TERMINAL CHANGE 19/06/15 MPR JP JPM - LOCATION VENEZUELA MODULE 5 - 2
2 AS COMMISSIONED 03/06/16 RDM MPR JPM - CONNECTION DIAGRAM
24V6
6ES7326-2BF10-0AB0
0V6
FUNCTION CH TML
XS6 XS6
C1 1 2
3 SDV-V3004
COALESCER B WATER OUTLET 0 (T) (B)
SHUTDOWN VALVE 4
C2 3 4
SPARE 6 SPARE
1 (T) (B)
7
C3 5 6
SPARE 9 SPARE
2 (T) (B)
10
C4 7 8
SPARE 12 SPARE
3 (T) (B)
13
C5 9 10
SPARE 15 SPARE
4 (T) (B)
16
24V6
2L+ 17
2L+ 18
0V6
2M 19
2M 20
24V6
1L+ 21
0V6
1M 22
C6 11 12
SPARE 23 SPARE
5 (T) (B)
24
C7 13 14
SPARE 26 SPARE
6 (T) (B)
27
15 16
C8
29 SPARE
SPARE 7 (T) (B)
30
17 18
C9
32 SPARE
SPARE 8 (T) (B)
33
C10 19 20
35 SPARE
SPARE 9 (T) (B)
36
24V6 C-S6
3L+ 37 12c 0.5mm^ YY
3L+ 38
0V6
3M 39
3M 40
24V7
0V7
TML CH FUNCTION
1 L+
DOUBLE TIER FEED THROUGH
TERMINALS 2 M
XS7
1 C1
3 Vs0
(T)
LIT-V3004
2 C2
4 0 M0+ COALESCER B INTERFACE LEVEL (SD)
(B)
C-S7C0
INSTRUMENT
EARTH BAR
5 M0-
3 C3
6 Vs1
(T)
SPARE
4 C4
7 1 M1+ SPARE
(B)
C-S7C1
INSTRUMENT
EARTH BAR
8 M1-
5 C5
9 Vs2
(T)
SPARE
6 C6
10 2 M2+ SPARE
(B)
C-S7C2
INSTRUMENT
EARTH BAR
11 M2-
7 C7
12 Vs3
(T)
SPARE
8 C8
13 3 M3+ SPARE
(B)
C-S7C3
INSTRUMENT
EARTH BAR
14 M3-
9 C9
15 Vs4
(T)
SPARE
10 C10
16 4 M4+ SPARE
(B)
C-S7C4
INSTRUMENT
EARTH BAR
17 M4-
11 C11
18 Vs5
(T)
SPARE
12 C12
19 5 SPARE
M5+
(B)
C-S7C5
INSTRUMENT
EARTH BAR
20 M5-
XS1
24V1 +ZSC-V3006 BK BK +ZSC-V3006
1 T PR1 C-ZSC/O-V3006 PR1 +
-ZSC-V3006 BL BL -ZSC-V3006 ZSC-V3006
2 B -
3 T +ZSO-V3006 BK BK +ZSO-V3006 +
PR2 PR2
-ZSO-V3006 BL BL -ZSO-V3006 ZSO-V3006
4 B -
5 T +HS-V3002A BK BK +HS-V3002A X2-1
C-HS-V3002A
-HS-V3002A WH WH -HS-V3002A HS-V3002A
6 B X2-2
7 T +HS-V3002B BK BK +HS-V3002B X2-5
C-HS-V3002B
-HS-V3002B WH WH -HS-V3002B HS-V3002B
8 B X2-6
9 T 2
10 B
11 T
12 B
13 T
14 B
15 T
16 B
17 T
18 B
19 T
20 B
21 T
22 B
23 T
24 B
25 T
26 B
27 T
28 B
29 T
30 B
31 T
32 B
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
PROJECT No. P044
REV DESCRIPTION DATE AUTH CHKD APPD CLIENT NOTES:
CLIENT EXPRO PTI / PDVSA
TITLE:
0 AS BUILT 14/05/15 JP MPR JPM - CLIENT No.
SITE NAME
13242
P.SINOVENSA
JB DETAILS COALESCER B
1 P&ID REV 1 & F&G TERMINAL CHANGE 19/06/15 MPR JP JPM - LOCATION VENEZUELA MODULE 1
2 AS COMMISSIONED 03/06/16 RDM MPR JPM - TERMINATION DIAGRAM
FIELD
TERMINATIONS
XS2
1 T +XV-V3006 BK BK +XV-V3006 +
C-XV-V3006
0V2 -XV-V3006 BL BL -XV-V3006 XV-V3006
2 B -
3 T
4 B
5 T
6 B
7 T
8 B
9 T
10 B
11 T
12 B
13 T
14 B
15 T
16 B
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
FIELD
TERMINATIONS
XS3
1 T +LIT-V3005 BK BK +LIT-V3005 +
C-LIT-V3005
-LIT-V3005 BL BL -LIT-V3005 LIT-V3005
2 B -
3 T +LIT-V3006 BK BK +LIT-V3006 +
C-LIT-V3006
-LIT-V3006 BL BL -LIT-V3006 LIT-V3006
4 B -
5 T +FIT-V3002 BK BK +FIT-V3002 +
C-FIT-V3002
-FIT-V3002 BL BL -FIT-V3002 FIT-V3002
6 B -
7 T +ET-V3002A BK BK +ET-V3002A X4-3
C-ET-V3002A
-ET-V3002A BL BL -ET-V3002A ET-V3002A
8 B X4-4
9 T +IT-V3002A BK BK +IT-V3002A X4-1
C-IT-V3002A
-IT-V3002A BL BL -IT-V3002A IT-V3002A
10 B X4-2
11 T +ET-V3002B BK BK +ET-V3002B X4-7
C-ET-V3002B
-ET-V3002B BL BL -ET-V3002B ET-V3002B
12 B X4-8
13 T +IT-V3002B BK BK +IT-V3002B X4-5
C-IT-V3002B
-IT-V3002B BL BL -IT-V3002B IT-V3002B
14 B X4-6
15 T 2
16 B
2
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
FIELD
TERMINATIONS
XS4
+LCV-V3005 BK BK +LCV-V3005 +
1 T C-LCV-V3005
-LCV-V3005 BL BL -LCV-V3005 LCV-V3005
2 B -
3 T
4 B
5 T
6 B
7 T
8 B
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
XS5
1 T +ZSC-V3004 BK BK +ZSC-V3004 +
PR1 C-ZSC/O-V3004 PR1
-ZSC-V3004 BL BL -ZSC-V3004 ZSC-V3004
2 B -
+ZSO-V3004 BK BK +ZSO-V3004
3
4
T
-ZSO-V3004 BL
PR2 PR2
BL -ZSO-V3004
+
-
ZSO-V3004 2
5
B
T 4 FD-009 BK 2 BK 4FD-009 4 5
PR1 C-FD-009 PR1
5 FD-009 WH WH 5 FD-009 LINK
F&G 24V 6 B 8 7
1 FD-009 BK FD-009
1 T PR2 BK 1FD-009 1
2 FD-009 WH PR2
2 WH 2 FD-009
B
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
XS3
25 T
26 B
27 T
28 B
29 T
30 B
31 T
32 B
33 T
34 B
35 T
36 B
37 T
38 B
39 T
40 B
41 T
42 B
43 T
44 B
45 T
46 B
47 T
48 B
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
PROJECT No. P044
REV DESCRIPTION DATE AUTH CHKD APPD CLIENT NOTES:
CLIENT EXPRO PTI / PDVSA
TITLE:
0 AS BUILT 14/05/15 JP MPR JPM - CLIENT No.
SITE NAME
13242
P.SINOVENSA
JB DETAILS COALESCER B
1 P&ID REV 1 & F&G TERMINAL CHANGE 19/06/15 MPR JP JPM - LOCATION VENEZUELA MODULE 5 - 2
2 AS COMMISSIONED 03/06/16 RDM MPR JPM - TERMINATION DIAGRAM
FIELD
TERMINATIONS
XS6
+SDV-V3004 BK BK +SDV-V3004 +
1 T C-SDV-V3004
0V6 -SDV-V3004 BL BL -SDV-V3004 SDV-V3004
2 B -
3 T
4 B
5 T
6 B
7 T
8 B
9 T
10 B
11 T
12 B
13 T
14 B
15 T
16 B
17 T
18 B
19 T
20 B
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
FIELD
TERMINATIONS
XS7
+LIT-V3004 BK BK +LIT-V3004 +
1 T C-LIT-V3004
-LIT-V3004 BL BL -LIT-V3004 LIT-V3004
2 B -
3 T
4 B
5 T
6 B
7 T
8 B
9 T
10 B
11 T
12 B
INSTRUMENT
EARTH BAR
JUNCTION BOX
MAIN EARTH
SHEET 2
24V8
0V8
F&G 24V
X1
1
10