DB en Axc F Il Adapt With Atex Relevant Printing 108629 en 01
DB en Axc F Il Adapt With Atex Relevant Printing 108629 en 01
Data sheet
108629_en_01 © PHOENIX CONTACT 2021-09-22
1 Description
The Inline adapter terminal (INTERBUS master) is designed
NOTE: Device defect due to impermissible
to be aligned to the right of an Axiocontrol series PLCnext
firmware version
Control device.
The Inline adapter terminal can be used to set up an Inline The Inline adapter terminal is designed to be
station for PLCnext Technology and to integrate INTERBUS aligned to the right of PLCnext controllers with
devices. specific firmware versions. If you align the Inline
adapter terminal next to a PLCnext controller with
Features a firmware version that is not permitted, this can
cause a device defect to the PLCnext controller.
– Automatic detection of the transmission speed in
INTERBUS (500 kbps or 2 Mbps) Make sure that the Inline adapter terminal is only
aligned next to a PLCnext controller with a
– Up to 63 INTERBUS local bus devices can be
firmware version that is permitted.
connected
AXC F ... PLCnext controllers with the following
– Diagnostic and status indicators
firmware versions are permitted:
– Inline I/O adapter terminal specifically developed for all
– AXC F 2152 with firmware Version 2019.0
PLCnext Control devices of the Axiocontrol series
– AXC F 3152 with firmware Version 2020.6
– A variety of functional I/Os creates options for flexible
automation solutions
Please note:
– Convert existing machines and systems to the new,
open PLCnext Technology ecosystem Align the Inline adapter terminal directly on the
controller. Axioline F modules may not be aligned
on the controller.
This data sheet is only valid in association with the Axioline F system manual and the user manual for the Axioline F
controller being used.
2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 4
5 Module components ................................................................................................................ 7
6 Internal circuit diagram ............................................................................................................ 8
7 Installation in potentially explosive area................................................................................... 9
8 UL notes .................................................................................................................................. 9
8.1 UL Hazardous Location ......................................................................................................... 9
3 Ordering data
4 Technical data
119,8
71,5
Width 12.2 mm
Height 119.8 mm
Depth 71.5 mm
General data
Weight 66 g
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 10 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Mounting type DIN rail mounting
System limits
Amount of process data max. 4096 Bit (INTERBUS input/output data)
max. 2048 Bit (INTERBUS input data)
max. 2048 Bit (INTERBUS output data)
Number of local bus devices that can be connected max. 63 (observe current consumption)
Number of devices with parameter channel max. 24
24 V supply UILC
Supply voltage 24 V DC -15 % / +20 % (acc. to EN 61131-2)
Current consumption 20 mA
24 V main supply UM
Supply voltage 24 V DC -15 % / +20 % (acc. to EN 61131-2)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit max. 8 A DC (sum of UM + US)
24 V segment supply US
Supply voltage 24 V DC -15 % / +20 % (in accordance with EN 61131)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit max. 8 A (sum of UM + US)
Protective circuit
Polarity reversal protection of the supply voltage Polarity protection diode
Transient protection Suppressor diode
Protection
NOTE: Damage to the electronics
Provide external protection for the module to protect it against polarity reversal. The power supply unit and the
external fuse must be coordinated so that safe tripping is ensured in the event of an error.
Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN 60068-2-27/ 10g
IEC 60068-2-27
Vibration resistance in acc. with EN 60068-2-6/ 5g
IEC 60068-2-6
Approvals
For the latest approvals, refer to: phoenixcontact.net/product/1020304
ATEX TÜV 20 ATEX 8617 X
II 3 G Ex ec IIC T4 Gc
EN IEC 60079-0:2018
EN IEC 60079-7:2015+A1:2018
IECEx IECEx TUR 20.0097X
Ex ec IIC T4 Gc
IEC 60079-0:2017, Edition 7
IEC 60079-7:2017, Edition 5.1
UL, USA / Canada E238705
cULus
UL Ex, USA / Canada E366272
Class I, Zone 2, AEx nA IIC T4, Ex nA IIC Gc T4
Class I, Div. 2, Groups A, B, C, D
UL 60079-0:2013, Edition 6
UL 60079-15:2017, Edition 4
CSA C22.2 NO. 60079-0:2015, Edition 3
CSA C22.2 NO. 60079-15:16
5 Module components
Figure 1 Module components
Y
RD
A
IL
S
B
FA
U
PF
1
1 Bus base module
2 Electronics module
3 Inline connector
4 Terminal points
5 Diagnostic and status indicators
3,3V
IB
5V
RDY
UL+
UANA
FAIL
UL-
BSA
& U
PF
7,5V 24V
24V 24V
US
P UM
Local bus S US
UL
UM
PWR
Key:
Protocol chip
IB
LED
AND gates
&
Parallel-to-serial converters
P
S
2 3 4 5
F 2152
SD-CARD
1 RDY
FAIL
1
BSA
PF
U
X2
X1
Please note:
Mount all the necessary modules before B
supplying power to the PLCnext Inline station.
Modules to which power is only supplied following
the controller boot process are not detected or
may result in a malfunction. • Place the bus base module of the Inline adapter
To ensure that the Inline adapter terminal is terminal on the DIN rail (A).
detected correctly, proceed as follows: • Push the bus base module of the Inline adapter terminal
- Switch on the power to the Inline adapter terminal into the connection of the bus base module on the
before switching on the power to the controller controller (B).
or
- Switch on the power to the Inline adapter terminal Please note:
and the controller simultaneously
Align the Inline adapter terminal directly on the
controller. Axioline F modules may not be aligned
10.1 Removing the controller on the controller.
The controller must be removed in order to mount the bus
base module of the Inline adapter terminal. 10.3 Snapping on the controller
Figure 4 Removing the controller Figure 6 Snapping on the controller
A
52
21
F
C
X
X
.X
A
X
.X
7
26
X
.X
04
S
X
D
24
.X
-C
R
X
A
o.
R
.X
D
.N
X
:X
rd
X
O
r.
4
dd
A
C
A
M
B
X
1
X
2
52
21
F
C
X
2
X
X
.X
A
X
.X
67
X
42
X
.X
1
S
0
D
24
.X
-C
R
X
A
o.
R
.X
D
.N
X
X
rd
r.:
X
O
4
dd
A
C
A
M
A
X
1
X
2
X
2
X
1
• Insert a suitable tool (e.g., bladed screwdriver) into the • Place the controller vertically on the first bus base
upper and lower snap-on mechanisms (base latches) of module and the DIN rail until it snaps into place with a
the controller one after the other and release it (A). click.
The base latches are latched in place in the open • Make sure that the device connector for the bus base
position. connection is situated above the corresponding socket
• Remove the controller perpendicular to the DIN rail (B). on the bus base module.
A
• Insert the Inline connectors in the specified order (A, B).
A 8
2.1
1.1 2.1
1.1
2.2
1.2 2.2
1.2
B 1.3
1.3 2.3
2.3
2.4
1.4 2.4
1.4
C
• Strip 8 mm off the cables. Terminal point Assignment
• Release the spring by pressing with the screwdriver. 1.1 US (24 V DC)
• Insert the cable into the terminal point. 1.2 UILC (24 V DC)
• Secure the cable by removing the screwdriver. 1.3 GND UILC
Recommended: flat-bladed screwdriver with blade 1.4 FE
dimensions of 0.6 mm x 3.5 mm x 100 mm (e. g., SZF 1- 2.1 UM (24 V DC)
0,6X3,5, Order No. 1204517) 2.2 UM (24 V DC)
2.3 GND UM/US
2.4 FE
Key:
12 Connection example
Figure 11 Connection example
AXC F IL ADAPT
AXC F...
I/O
I/O
I/O
Key:
RDY
FAIL
BSA
PF
U
15 PCP communication
The Inline adapter terminal (INTERBUS master) supports
the Peripherals Communication Protocol (PCP) Version 2.0
with Peripherals Message Specification (PMS).
Peripherals Network Management 7 (PNM7) services are
not supported.
Code Service
(hex)
0081 Read_Request
4081 Read_Indication
C081 Read_Response
8081 Read_Confirmation
0082 Write_Request
4082 Write_Indication
C082 Write_Response
8082 Write_Confirmation
0885 Information_Report_Request
4885 Information_Report_Indication
0086 Status_Request
8086 Status_Confirmation
0087 Identify_Request
8087 Identify_Confirmation
008B Initiate_Request
408B Initiate_Indication
C08B Initiate_Response
808B Initiate_Confirmation
088D Abort_Request
488D Abort_Indication
488E Reject_Indication
0264 Load_CRL_Attribute_Loc_Request
8264 Load_CRL_Attribute_Loc_Confirmation
108629_en_01 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 20/20
phoenixcontact.com