AXC F IL ADAPT

PLCnext Technology, Inline adapter terminal


(INTERBUS master), right-alignable

Data sheet
108629_en_01 © PHOENIX CONTACT 2021-09-22

1 Description
The Inline adapter terminal (INTERBUS master) is designed
NOTE: Device defect due to impermissible
to be aligned to the right of an Axiocontrol series PLCnext
firmware version
Control device.
The Inline adapter terminal can be used to set up an Inline The Inline adapter terminal is designed to be
station for PLCnext Technology and to integrate INTERBUS aligned to the right of PLCnext controllers with
devices. specific firmware versions. If you align the Inline
adapter terminal next to a PLCnext controller with
Features a firmware version that is not permitted, this can
cause a device defect to the PLCnext controller.
– Automatic detection of the transmission speed in
INTERBUS (500 kbps or 2 Mbps) Make sure that the Inline adapter terminal is only
aligned next to a PLCnext controller with a
– Up to 63 INTERBUS local bus devices can be
firmware version that is permitted.
connected
AXC F ... PLCnext controllers with the following
– Diagnostic and status indicators
firmware versions are permitted:
– Inline I/O adapter terminal specifically developed for all
– AXC F 2152 with firmware Version  2019.0
PLCnext Control devices of the Axiocontrol series
– AXC F 3152 with firmware Version  2020.6
– A variety of functional I/Os creates options for flexible
automation solutions
Please note:
– Convert existing machines and systems to the new,
open PLCnext Technology ecosystem Align the Inline adapter terminal directly on the
controller. Axioline F modules may not be aligned
on the controller.

This data sheet is only valid in association with the Axioline F system manual and the user manual for the Axioline F
controller being used.

Make sure you always use the latest documentation.


It can be downloaded at: phoenixcontact.net/product/1020304
AXC F IL ADAPT

2 Table of contents
1 Description .............................................................................................................................. 1
2 Table of contents ..................................................................................................................... 2
3 Ordering data .......................................................................................................................... 3
4 Technical data ......................................................................................................................... 4
5 Module components ................................................................................................................ 7
6 Internal circuit diagram ............................................................................................................ 8
7 Installation in potentially explosive area................................................................................... 9
8 UL notes .................................................................................................................................. 9
8.1 UL Hazardous Location ......................................................................................................... 9

9 Design of a PLCnext Inline station ......................................................................................... 10


10 Mounting................................................................................................................................ 11
10.1Removing the controller ...................................................................................................... 11
10.2Mount bus base module ...................................................................................................... 11
10.3Snapping on the controller ................................................................................................... 11
10.4Snapping on electronics modules .......................................................................................... 12
10.5Mount Inline connector ........................................................................................................ 12

11 Connecting the supply voltage............................................................................................... 13


12 Connection example.............................................................................................................. 14
13 Diagnostics and status indicators .......................................................................................... 15
14 Supported INTERBUS master services ................................................................................. 16
15 PCP communication .............................................................................................................. 20

108629_en_01 PHOENIX CONTACT 2/20


AXC F IL ADAPT

3 Ordering data

Description Type Order No. Pcs./Pkt.


Right-alignable Inline adapter terminal (INTERBUS AXC F IL ADAPT 1020304 1
master) for one PLCnext Control device for setting up a
PLCnext Technology Inline station

Accessories Type Order No. Pcs./Pkt.


PLCnext Control for the direct control of Axioline F I/Os. AXC F 2152 2404267 1
With two Ethernet interfaces. Complete with connector
and bus base module.

Documentation Type Order No. Pcs./Pkt.


User manual, English, Axioline F: System and installation UM EN AXL F SYS INST - -
User manual, English, Automation terminals of the Inline IL SYS INST UM E - -
product range
User Manual, English, for diagnosis in Generation 4 IBS SYS DIAG DSC UM E 2747293 1
controller boards
User manual, English, for the Peripherals Communication IBS PCP UM E 2753931 1
Protocol (PCP), only available as a download.
User manual, English, for the Peripherals Communication IBS SYS PCP G4 UM E 2745169 1
Protocol (PCP), only available as a download.

108629_en_01 PHOENIX CONTACT 3/20


AXC F IL ADAPT

4 Technical data

Dimensions (nominal sizes in mm)

119,8
71,5

Width 12.2 mm
Height 119.8 mm
Depth 71.5 mm

General data
Weight 66 g
Ambient temperature (operation) -25 °C ... 55 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport) 10 % ... 95 % (non-condensing)
Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 10 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Mounting type DIN rail mounting

Connection data: Inline connector


Connection method Spring-cage connection
Conductor cross section, rigid 0.08 mm² ... 1.5 mm²
Conductor cross section, flexible 0.08 mm² ... 1.5 mm²
Conductor cross section [AWG] 28 ... 16
Stripping length 8 mm

System limits
Amount of process data max. 4096 Bit (INTERBUS input/output data)
max. 2048 Bit (INTERBUS input data)
max. 2048 Bit (INTERBUS output data)
Number of local bus devices that can be connected max. 63 (observe current consumption)
Number of devices with parameter channel max. 24

108629_en_01 PHOENIX CONTACT 4/20


AXC F IL ADAPT

24 V supply UILC
Supply voltage 24 V DC -15 % / +20 % (acc. to EN 61131-2)
Current consumption 20 mA

7.5 V communications power UL (potential jumper)


Supply voltage 7.5 V DC ±5 %
Power supply unit max. 0.8 A DC (observe derating)

24 V analog supply UANA (potential jumper)


Supply voltage 24 V DC -15 % / +20 %
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit 0.5 A DC (observe derating)

24 V main supply UM
Supply voltage 24 V DC -15 % / +20 % (acc. to EN 61131-2)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit max. 8 A DC (sum of UM + US)

24 V segment supply US
Supply voltage 24 V DC -15 % / +20 % (in accordance with EN 61131)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply unit max. 8 A (sum of UM + US)

Protective circuit
Polarity reversal protection of the supply voltage Polarity protection diode
Transient protection Suppressor diode

Protection
NOTE: Damage to the electronics
Provide external protection for the module to protect it against polarity reversal. The power supply unit and the
external fuse must be coordinated so that safe tripping is ensured in the event of an error.

Error messages to the higher level control or computer system


Bus error in INTERBUS Yes
Peripheral fault in INTERBUS Yes

Mechanical tests
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse
Continuous shock according to EN 60068-2-27/ 10g
IEC 60068-2-27
Vibration resistance in acc. with EN 60068-2-6/ 5g
IEC 60068-2-6

108629_en_01 PHOENIX CONTACT 5/20


AXC F IL ADAPT

Conformance with EMC Directive 2014/30/EU


Noise immunity test in accordance with EN 61000-6-2
EN 61000-4-2 (ESD) Criterion B, 4 kV contact discharge, 8 kV air discharge
Electrostatic discharge (ESD) EN 61000-4-2/
IEC 61000-4-2
EN 61000-4-3 (electromagnetic fields) Criterion A, Field intensity: 10 V/m
Electromagnetic fields EN 61000-4-3/
IEC 61000-4-3
EN 61000-4-4 Criterion B, 2 kV
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
EN 61000-4-5 (surge) Criterion B, DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/
Transient overvoltage (surge) EN 61000-4-5/ asymmetrical)
IEC 61000-4-5
EN 61000-4-6 (line noise immunity) Criterion A, Test voltage 10 V
Conducted interference EN 61000-4-6/IEC 61000-4-6
Noise emission test as per EN 61000-6-4

Approvals
For the latest approvals, refer to: phoenixcontact.net/product/1020304
ATEX TÜV 20 ATEX 8617 X
 II 3 G Ex ec IIC T4 Gc
EN IEC 60079-0:2018
EN IEC 60079-7:2015+A1:2018
IECEx IECEx TUR 20.0097X
Ex ec IIC T4 Gc
IEC 60079-0:2017, Edition 7
IEC 60079-7:2017, Edition 5.1
UL, USA / Canada E238705
cULus
UL Ex, USA / Canada E366272
Class I, Zone 2, AEx nA IIC T4, Ex nA IIC Gc T4
Class I, Div. 2, Groups A, B, C, D
UL 60079-0:2013, Edition 6
UL 60079-15:2017, Edition 4
CSA C22.2 NO. 60079-0:2015, Edition 3
CSA C22.2 NO. 60079-15:16

108629_en_01 PHOENIX CONTACT 6/20


AXC F IL ADAPT

5 Module components
Figure 1 Module components

Y
RD
A

IL
S
B

FA
U
PF

1
1 Bus base module
2 Electronics module
3 Inline connector
4 Terminal points
5 Diagnostic and status indicators

108629_en_01 PHOENIX CONTACT 7/20


AXC F IL ADAPT

6 Internal circuit diagram


Figure 2 Basic circuit diagram

3,3V
IB
5V

RDY
UL+
UANA
FAIL
UL-
BSA

& U
PF
7,5V 24V

24V 24V
US
P UM

Local bus S US
UL

UM

PWR

Key:

Power supply unit

Protocol chip
IB

LED

AND gates
&
Parallel-to-serial converters
P
S

108629_en_01 PHOENIX CONTACT 8/20


AXC F IL ADAPT

7 Installation in potentially explosive Installation in zone 2


area 1. The device must be installed in an area that is classified
as no higher than pollution degree 2 in accordance with
Approval in accordance with ATEX directive IEC 60664-1.
2014/34/EU and IECEx scheme 2. If the device is used in a zone 2 environment, it must be
installed in a housing that at least meets the
WARNING: Explosion hazard requirements of IP54 degree of protection in
accordance with IEC 60079-7 or another recognized
Before using the device in a potentially explosive
degree of protection in accordance with IEC 60079-0,
area, make sure that your device has the required
section 1.
approval.
3. Observe the specified conditions for use in potentially
The approvals are printed on the device.
explosive areas.
4. Also observe the requirements of EN 60079-14.
WARNING: Explosion hazard
5. Follow the installation instructions as described.
Please make sure that the following notes and
6. The following work is only permitted in potentially
instructions are observed.
explosive areas when the power is disconnected:

Installation notes - Snapping the device onto the DIN rail


- Removing the device from the DIN rail
1. The category 3 device is designed for installation in
zone 2 potentially explosive areas. - Connection and disconnection of cables
The device satisfies the requirements of
7. Connect the DIN rail to the protective earth ground.
EN/IEC 60079-0 and EN/IEC 60079-7.
8. Repair any damaged connectors immediately.
2. Installation, operation, and maintenance may only be
carried out by qualified specialists. 9. For safe operation, all interfaces on the device must be
used or covered.
3. The IP20 degree of protection (IEC 60529/EN 60529) of
the device is intended for use in a clean and dry 10. Observe the device temperature derating depending on
environment. the installation altitude:
4. Do not subject the device to mechanical and/or thermal
Altitude (above Max. ambient temperature
stress that exceeds the specified limits.
mean sea level)
5. The device must be stopped and immediately removed
up to 2000 m 55°C
from the Ex area if it is damaged, was subjected to an
impermissible load, stored incorrectly or malfunctions. 2000 m ... 3000 m 49 °C
6. The device is not designed for use in atmospheres with 3000 m ... 4000 m 44 °C
a danger of dust explosions. 4000 m ... 5000 m 38 °C
7. When installing and operating the device, the
applicable safety directives (including national safety
directives), accident prevention regulations, as well as 8 UL notes
general technical regulations, must be observed.
8. Please refer to the corresponding documentation (user 8.1 UL Hazardous Location
manual, data sheet, package slip) and the certificates – Ambient temperature: -25 °C < Tamb < 60 °C
(declaration of conformity and other approvals, if
– This device must be installed within an area of not more
applicable) for safety-related data.
than pollution degree 2, as defined in IEC 60664-1.
9. Opening or modifying the device is prohibited. Do not
– This device must be installed in a tool only accessible
repair the device yourself; replace it with an equivalent
enclosure certified for use in Class I, Zone 2, minimum,
device.
and rated IP54, minimum, in accordance with
Repairs may only be carried out by the manufacturer.
UL/CSA 60079-0 when used in a Class I, Zone 2
The manufacturer is not liable for damage resulting from
environment.
non-compliance.

108629_en_01 PHOENIX CONTACT 9/20


AXC F IL ADAPT

9 Design of a PLCnext Inline station


Figure 3 Design of a PLCnext Inline station

2 3 4 5

F 2152
SD-CARD

MAC Addr.: XX.XX.XX.XX.XX.XX


R

Ord. No. 2404267 AXC X4

1 RDY
FAIL
1
BSA
PF
U

X2

X1

1 End clamp (e.g., CLIPFIX 35-5, Order No. 3022276)


2 PLCnext controller for Axioline F (in the example:
AXC F 2152)
3 Inline adapter terminal
4 Inline terminals corresponding to the application
5 End plate (snap onto the DIN rail as station end)

108629_en_01 PHOENIX CONTACT 10/20


AXC F IL ADAPT

10 Mounting 10.2 Mount bus base module


Figure 5 Mounting the bus base module
Please note:
On a controller for Axioline F, only one Inline A
adapter terminal may be aligned to the right.

Please note:
Mount all the necessary modules before B
supplying power to the PLCnext Inline station.
Modules to which power is only supplied following
the controller boot process are not detected or
may result in a malfunction. • Place the bus base module of the Inline adapter
To ensure that the Inline adapter terminal is terminal on the DIN rail (A).
detected correctly, proceed as follows: • Push the bus base module of the Inline adapter terminal
- Switch on the power to the Inline adapter terminal into the connection of the bus base module on the
before switching on the power to the controller controller (B).
or
- Switch on the power to the Inline adapter terminal Please note:
and the controller simultaneously
Align the Inline adapter terminal directly on the
controller. Axioline F modules may not be aligned
10.1 Removing the controller on the controller.
The controller must be removed in order to mount the bus
base module of the Inline adapter terminal. 10.3 Snapping on the controller
Figure 4 Removing the controller Figure 6 Snapping on the controller

A
52
21
F
C

X
X

.X
A

X
.X
7
26

X
.X
04

S
X

D
24

.X

-C
R
X

A
o.

R
.X

D
.N

X
:X
rd

X
O

r.

4
dd
A
C
A
M

B
X
1
X
2
52
21
F
C

X
2
X
X

.X
A

X
.X
67

X
42

X
.X

1
S
0

D
24

.X

-C
R
X

A
o.

R
.X

D
.N

X
X
rd

r.:

X
O

4
dd
A
C
A
M

A
X
1
X
2

X
2
X
1

• Insert a suitable tool (e.g., bladed screwdriver) into the • Place the controller vertically on the first bus base
upper and lower snap-on mechanisms (base latches) of module and the DIN rail until it snaps into place with a
the controller one after the other and release it (A). click.
The base latches are latched in place in the open • Make sure that the device connector for the bus base
position. connection is situated above the corresponding socket
• Remove the controller perpendicular to the DIN rail (B). on the bus base module.

108629_en_01 PHOENIX CONTACT 11/20


AXC F IL ADAPT

10.4 Snapping on electronics modules


Figure 7 Snapping on the electronics module of the
Inline adapter terminal

• Place the electronics module of the Inline adapter


terminal vertically on the corresponding bus base
module and on the DIN rail until it snaps into place with
a click.
• Make sure that the device connector for the bus base
connection is situated above the corresponding socket
on the bus base module.
• Mount the electronics modules of all necessary Inline
terminals. Note the assembly instructions in the device-
specific packing slip.

10.5 Mount Inline connector


Figure 8 Insert Inline connector

A
• Insert the Inline connectors in the specified order (A, B).

108629_en_01 PHOENIX CONTACT 12/20


AXC F IL ADAPT

11 Connecting the supply voltage Terminal point assignment


Figure 10 Terminal point assignment
Figure 9 Connecting cables

A 8

2.1
1.1 2.1
1.1

2.2
1.2 2.2
1.2

B 1.3
1.3 2.3
2.3

2.4
1.4 2.4
1.4
C
• Strip 8 mm off the cables. Terminal point Assignment
• Release the spring by pressing with the screwdriver. 1.1 US (24 V DC)
• Insert the cable into the terminal point. 1.2 UILC (24 V DC)
• Secure the cable by removing the screwdriver. 1.3 GND UILC
Recommended: flat-bladed screwdriver with blade 1.4 FE
dimensions of 0.6 mm x 3.5 mm x 100 mm (e. g., SZF 1- 2.1 UM (24 V DC)
0,6X3,5, Order No. 1204517) 2.2 UM (24 V DC)
2.3 GND UM/US
2.4 FE

Key:

US (24 V DC) 24 V supply for segment circuit


UM (24 V DC) 24 V supply for main circuit
UILC (24 V DC) 24 V main voltage / 7.5 V logic supply /
24 V analog supply
GND Ground
FE Functional ground

108629_en_01 PHOENIX CONTACT 13/20


AXC F IL ADAPT

12 Connection example
Figure 11 Connection example

AXC F IL ADAPT
AXC F...

I/O

I/O

I/O

Key:

AXC F ... AXC F ... PLCnext controller


AXC F IL ADAPT Inline adapter terminal
I/O Inline terminals corresponding to your application
INTERBUS INTERBUS devices according to your application

108629_en_01 PHOENIX CONTACT 14/20


AXC F IL ADAPT

13 Diagnostics and status indicators


Figure 12 Diagnostic and status indicators

RDY

FAIL

BSA

PF
U

Designa- Color Meaning State Description


tion
RDY Green INTERBUS master On INTERBUS master in the RUN state
Flashing INTERBUS master in the READY or ACTIVE state
Off INTERBUS master is not ready to operate
FAIL Red Error On Bus, controller or user error
Off No error
BSA Yellow Bus segment On At least one bus segment aborted
Off No bus segment aborted
PF Yellow I/O error On Peripheral fault on at least one device in INTERBUS
Off No peripheral fault
U Green Supply voltages US, On Supply voltages US, UM, UL present
UM, UL
Off At least one of the supply voltages US, UM or UL is not pres-
ent

108629_en_01 PHOENIX CONTACT 15/20


AXC F IL ADAPT

14 Supported INTERBUS master services

For more detailed information on the INTERBUS


G4 services, please refer to the
IBS SYS FW G4 UM E user manual. The user
manual can be downloaded at
phoenixcontact.net/products.

The following restrictions apply for the INTERBUS


master:
- Support for INTERBUS devices with slave
protocol chip SUPI3 or higher
- No FO diagnostics
- No single-channel diagnostics
- No support for LPC1 or LPC2
- No isolated disconnection possible

Firmware services are used to carry out the configuration,


parameterization, and diagnostics of INTERBUS.
The Inline adapter terminal (INTERBUS master) supports
the following INTERBUS G4 services (some of which have
a limited scope of functions):

Code (hex) Service Description


0306 Initiate_Load_Configuration Create configuration frame for data transmission
- Max. 127 characters
- Can only be set when New_Config = 1
0307 Load_Configuration Transmit the device data for a configuration
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number (always FFFFhex)
Bits 5 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
0308 Terminate_Load_Configuration Terminate the transmission of configuration data (only for au-
tomatic parameterization)
Default_Parameter:
The PCP channel is always parameterized automatically.
The process data channel is only parameterized automati-
cally if bit 0 is set.

108629_en_01 PHOENIX CONTACT 16/20


AXC F IL ADAPT

Code (hex) Service Description


0309 Read_Configuration Read various entries of the configuration directory
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number
Bits 5 ... 7: reserved
Bit 8: global_bus_error
Bit 9: separate_bus_error (Reconf and Watchdog not sup-
ported)
Bit 10: device status
Bits 11 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
030A Complete_Load_Configuration Transmit all the device data for a configuration
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number (always FFFFhex)
Bits 5 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
030B Complete_Read_Configuration Read all the device data for a configuration
Used_Attributes:
Bit 0: device number
Bit 1: device code
Bit 2: reserved
Bit 3: device level
Bit 4: logical group number (always FFFFhex)
Bits 5 ... 13: reserved
Bit 14: extended device information
Bit 15: reserved
030C Delete_Configuration Delete inactive configuration frames from the configuration
directory
030E Control_Parameterization Start or end the parameterization phase
030F Control_Statistics Control statistical diagnostics
0314 Control_Device_Function_Not_Exclusive Send control commands to local bus device
Device_Function:
0003hex: Conf_Dev_Err
0004hex: Conf_Dev_Err_All
0315 Read_Device_State Read status of local bus devices
Device_State_Mask:
Bits 0 ... 10: reserved
Bit 11: peripheral fault
Bits 12 ... 15: reserved
0316 Get_Error_Info Request additional error information

108629_en_01 PHOENIX CONTACT 17/20


AXC F IL ADAPT

Code (hex) Service Description


0328 Compact_Load_Process_Data_Refer- Configure controller board without software support
ence_List
- Permitted addresses: 0000hex ... 03FFhex
- No overlapping or duplication possible
- Modules up to max. 8 bits with Byte-Cons at every address,
modules > 8 bits only at even addresses
0329 Compact_Read_Process_Data_Refer- Read address lists of the control or computer system that
ence_List were configured using the “Compact_Load_Process_-
Data_Reference_List” service (3028hex)
032A Get_Version_Info Read version information
032B Get_Diag_Info Read local bus counter
0351 Read_Value Read system parameter
Supported values for the Variable_ID parameter: see next
table
0701 Start_Data_Transfer Start data transfer
0702 Stop_Data_Transfer Stop data transfer
0710 Create_Configuration Read the connected bus
0711 Activate_Configuration Check the configuration frame matches the connected bus
and whether addresses overlap
0712 Deactivate_Configuration Deactivate configuration frame
0713 Control_Active_Configuration Switch INTERBUS device on or off.
Only Switch_Codes 0004hex (Device_Disable) and 0005hex
(Device_Enable) are supported.
Switching or bridging has no influence on the position of the
process data in the memory or the CR assignment of the
PCP devices.
0714 Control_Device_Function Send control commands to local bus device
Device_Function:
0003hex: Conf_Dev_Err
0004hex: Conf_Dev_Err_All
0750 Set_Value Assign new values to system parameters
Supported values for the Variable_ID parameter: see next
table
0760 Confirm_Diagnostics Update diagnostic display and diagnostic register
1303 Alarm_Stop Reset local bus

108629_en_01 PHOENIX CONTACT 18/20


AXC F IL ADAPT

Supported values for the Variable_ID parameter

Variable_ID System parameter Value/note


(hex)
0101 State of the system management Read access only
0104 Contents of the diagnostic status register Read access only
0105 Contents of the diagnostic parameter register Read access only
010D Contents of the extended diagnostic parameter regis- Read access only
ter
2204 Control the behavior of the input data in the event of a 0: input data in the MPM is frozen (default setting)
bus error 1: input data in the MPM is set to zero
2210 Specified process data cycle time in s (32-bit value) Permissible value range:
0000 0000hex: off
0000 0100hex ... 0001 FB00hex
2211 Bus timeout in s (32-bit value) Permissible value range:
Default setting: 200 ms 0000 0000hex: Off
0000 0100hex ... 000F FF00hex
2212 Bus warning time in s (32-bit value) Permissible value range:
Default setting: 0 (not activated) 0000 0000hex: Off
0000 0100hex ... 000F FF00hex
2216 Actual process data cycle time in s (32-bit value) Read access only
2218 Data cycle time in s (32-bit value) Read access only
A228 Read baud rate Read access only
0: 2 Mbaud
1: 500 kBaud

108629_en_01 PHOENIX CONTACT 19/20


AXC F IL ADAPT

15 PCP communication
The Inline adapter terminal (INTERBUS master) supports
the Peripherals Communication Protocol (PCP) Version 2.0
with Peripherals Message Specification (PMS).
Peripherals Network Management 7 (PNM7) services are
not supported.

For information on PCP communication, please


refer to the PCP user manuals (see Ordering
data).

Code Service
(hex)
0081 Read_Request
4081 Read_Indication
C081 Read_Response
8081 Read_Confirmation
0082 Write_Request
4082 Write_Indication
C082 Write_Response
8082 Write_Confirmation
0885 Information_Report_Request
4885 Information_Report_Indication
0086 Status_Request
8086 Status_Confirmation
0087 Identify_Request
8087 Identify_Confirmation
008B Initiate_Request
408B Initiate_Indication
C08B Initiate_Response
808B Initiate_Confirmation
088D Abort_Request
488D Abort_Indication
488E Reject_Indication
0264 Load_CRL_Attribute_Loc_Request
8264 Load_CRL_Attribute_Loc_Confirmation

108629_en_01 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 20/20
phoenixcontact.com