Eaton 9145 10-15-20 kVA UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3
IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA
Subclause
Parameters 10 kVA 15 kVA 20 kVA
Model Long Back UP Model Safety Paremeter CE Marking EN 62040-1:2008, EN60950-1:2006 Protection IP 20 : EN 60529:1991/A1:2000, IEC 60529:1989/A1:1999 EMC Parameter Conduction IEC 62040-2:2005 Radiation IEC 62040-2:2005 Low frequency conducted disturbances IEC61000-2-2:2002 Harmonic current EN61000-3-2:2006+A1 :2009+A2:2009 ESD IEC 61000-4-2:2008 RS IEC 61000-4-3:2006+A1:20 07+A2:2010 EFT IEC 61000-4-4:2004+A1:20 10 Surge IEC 61000-4-5:2005 C/S IEC61000-4-6:2008 M/S IEC61000-4-8:2009 Environmental Parameter Operating Temperature 0°C ~ 40 °C Range Storage Temperature -15°C~60°C Relative Humidity 0-95% No condensates Altitude <1000m Acoustic Noise <55dB <55dB <55dB Cooling Forced air cooling by the internal fans Wiring Parameter AC power distribution system TN-S system, If used in IT system, site fault function should be disable. compatibility Output wiring type Line (Connect L1+L2+L3 Together) + Neutral + PE Input wiring type 3 Phases + Neutral + PE Battery wiring battery positive +battery negative+battery neutral+1 PE Input Socket Terminal Output Socket Terminal Input Parameter Rated Input Voltage 380/400/415 Vac
The technical specification is subject to change without notice.
Author: Pankaj Paliw al Page 1 of 4 Updated: 15.04.2020 Document: Eaton 9145 10-15-20 kVA Data Sheet.docx Eaton 9145 10-15-20 kVA UPS Technical Specification Manufacturer’s declaration in accordance with IEC 62040-3
IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA
Subclause
Maximum working input voltage 304V~478V Resistive load>80%
range 190V~478V Resistive load <50% Comeback voltage Line Low Loss + 10V Line High Loss -10V Maximum turn on UPS input voltage 208V~460V @ 0% Load range Maximum input leakage current IEC 62040-1-1 Input voltage detective error ±3% Rated input frequency 50Hz Input Frequency Range 45 Hz– 55 Hz Freq. Low Loss 45 Hz Freq. Low Comeback Freq. Low Loss + 0.5 Hz Freq. High Loss 55 Hz Freq. High Comeback Freq. High Loss - 0.5 Hz Frequency System Auto Detection ≥40Hz&≤55Hz, start with 50Hz system Frequency Detection Tolerance ±0.05 Hz Input Power Factor ≥ 0.95 Input THDi% <5.5% Input Inrush current Less than 8 times of rated input current Generator Set 1.5 times of UPS Rated Power Bypass Parameter Bypass input/Output Voltage Range 304~458V The range can be set by user via dedicated software.The maximum range is 110~276V Bypass Low Comeback Low Loss + 10V Bypass High Comeback High Loss -10V Bypass input/Output Frequency Range 45~55 Hz Default value for 50Hz system range can be set by user via dedicated software.The maximum range is 50*(1±15%) Hz Freq. Low Comeback Freq. Low Loss + 0.5 Hz Freq. High Comeback Freq. High Loss - 0.5 Hz Frequency System Auto Detection ≥40Hz&55Hz,start with 50Hz system Bypass Over Load Capability <125% continue working 1 Min @ 125% to 150% rated load 10 sec @ > 150% rated load Output Parameter Rated kVA 10000VA 15000 VA 20000 VA Rated kW 9000 W 13500 W 18000 W Load type Resistive load/ lagging load/ non-linear load/ transformer load/ lighting load Load power factor range 0.5~1 lagging The technical specification is subject to change without notice. Author: Pankaj Paliw al Page 2 of 4 Updated: 15.04.2020 Document: Eaton 9145 10-15-20 kVA Data Sheet.docx Eaton 9145 10-15-20 kVA UPS Technical Specification Manufacturer’s declaration in accordance with IEC 62040-3
IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA
Subclause
Load Crest Ratio 3:1
Output wave type Pure sine wave Rated output voltage 220V/230V/240V Voltage Accuracy ±2 % THDV <5% for Non- Linear Load <2% for Linear Load DC Offset ±100 mV Output Frequency 50Hz Output Frequency accuracy ±0.1Hz Phase Error of synchronization < 3 degrees Frequency Slew rate <1Hz/s MAX Load detective error ±3% Maximum Voltage deviation responding ±7% 0%->100%->0% Resistive Load to resistive load step Dynamic output performance to resistive Dynamic output performance classification 1, as per IEC62040-3 Editon 2 step load and non-linear step load :2011 reference Dynamic output performance classification 1 Recovery time after reference Non-linear 100ms recover to ±10% 0%->100%->0% Load load step Over Load Memory Overload time up occurs 3 times in 10min, the UPS will lock on bypass mode and keep alarming. Transfer Time 0ms Input power interrupt Line mode Battery mode 0ms input power recover Battery mode Line mode 0ms Turn off or common fault occurs Inverter output Bypass output 0ms Turn on/System recoveryBypass output Inverter output 0ms Line mode -> ECO mode <10ms (Typical) Input Voltage or frequency out of Range or Loss ECO mode line mode or battery mode Inverter Output short stand time No less than 100ms
Inverter Output short limit current Rate output current * 3
Efficiency 93% Line Mode, rated input and output voltage, battery is fully charged, 100% resistive load 92% Battery mode, rated output voltage, battery voltage 12V/pc, 100% resistive load 97% ECO Mode, Nominal input and output voltage, battery is fully charged, 100% resistive load Overload Warning point >105% rated load Overload Warning Comeback point <100% rated load Battery Parameter Rated Battery Voltage 288 Vdc Battery Type VRLA (Valve Regulated Lead Acid Battery), 12VDC The technical specification is subject to change without notice. Author: Pankaj Paliw al Page 3 of 4 Updated: 15.04.2020 Document: Eaton 9145 10-15-20 kVA Data Sheet.docx Eaton 9145 10-15-20 kVA UPS Technical Specification Manufacturer’s declaration in accordance with IEC 62040-3
IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA
Subclause
Battery Shutdown Voltage 10.7 V/pcs
Battery over voltage warning point 14.4V/pcs Battery over voltage Warning Comeback 13.7V/pcs Voltage Battery low Voltage Warning point 11.4 V/pcs Battery low voltage Warning Comeback Battery warning voltage + 0.5V Voltage Battery Voltage detective tolerance ±2 % Maximum Battery LeakageCurrent 500uA Small Current Discharge Protection Default setting: 14.5 hours Battery short protection Protected by battery fuse Maximum charging current 4A± 0.5A Floating charging voltage 13.65V/block Charge Voltage Accuracy ± 2% Recharging time 8 hours to 90% rated capability Over charger protection point 14.4V/block Features ECO Mode Manual Enable via dedicated software Default Setting Off Communication (Independent SCI) RS232/ USB 1.1 Intelligent Card slot (Independent SCI) SNMP card optional RS232 card optional USB1.1 card optional RS485 card (CMC) optional AS400 card optional EPO Function Yes Intelligent Fans Speed control Yes Auto restart function Default Yes Cold start Yes Mechanical Features Dimension(Unit DIM (W*H*D mm)) 350*890*650 Dimension(Package DIM (W*H*D mm) 475*1125*815 ) Net Weight(kg) 48.1 58.1 58.1 Gross Weight(kg) 65.1 74.1 74.1 color Pantone Process Black C
The technical specification is subject to change without notice.
Author: Pankaj Paliw al Page 4 of 4 Updated: 15.04.2020 Document: Eaton 9145 10-15-20 kVA Data Sheet.docx