Eaton 9145 10-15-20 kVA UPS Technical Specification

Manufacturer’s declaration in accordance with IEC 62040-3

IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA


Subclause

Parameters 10 kVA 15 kVA 20 kVA


Model Long Back UP Model
Safety Paremeter
CE Marking EN 62040-1:2008, EN60950-1:2006
Protection IP 20 : EN 60529:1991/A1:2000, IEC 60529:1989/A1:1999
EMC Parameter
Conduction IEC 62040-2:2005
Radiation IEC 62040-2:2005
Low frequency conducted disturbances IEC61000-2-2:2002
Harmonic current EN61000-3-2:2006+A1
:2009+A2:2009
ESD IEC 61000-4-2:2008
RS IEC
61000-4-3:2006+A1:20
07+A2:2010
EFT IEC
61000-4-4:2004+A1:20
10
Surge IEC 61000-4-5:2005
C/S IEC61000-4-6:2008
M/S IEC61000-4-8:2009
Environmental Parameter
Operating Temperature 0°C ~ 40 °C
Range
Storage Temperature -15°C~60°C
Relative Humidity 0-95%
No condensates
Altitude <1000m
Acoustic Noise <55dB <55dB <55dB
Cooling Forced air cooling by the internal fans
Wiring Parameter
AC power distribution system TN-S system, If used in IT system, site fault function should be disable.
compatibility
Output wiring type Line (Connect L1+L2+L3 Together) + Neutral + PE
Input wiring type 3 Phases + Neutral + PE
Battery wiring battery positive +battery negative+battery neutral+1 PE
Input Socket Terminal
Output Socket Terminal
Input Parameter
Rated Input Voltage 380/400/415 Vac

The technical specification is subject to change without notice.


Author: Pankaj Paliw al Page 1 of 4
Updated: 15.04.2020
Document: Eaton 9145 10-15-20 kVA Data Sheet.docx
Eaton 9145 10-15-20 kVA UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3

IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA


Subclause

Maximum working input voltage 304V~478V Resistive load>80%


range 190V~478V Resistive load <50%
Comeback voltage Line Low Loss + 10V Line High Loss -10V
Maximum turn on UPS input voltage 208V~460V @ 0% Load
range
Maximum input leakage current IEC 62040-1-1
Input voltage detective error ±3%
Rated input frequency 50Hz
Input Frequency Range 45 Hz– 55 Hz
Freq. Low Loss 45 Hz
Freq. Low Comeback Freq. Low Loss + 0.5 Hz
Freq. High Loss 55 Hz
Freq. High Comeback Freq. High Loss - 0.5 Hz
Frequency System Auto Detection ≥40Hz&≤55Hz, start with
50Hz system
Frequency Detection Tolerance ±0.05 Hz
Input Power Factor ≥ 0.95
Input THDi% <5.5%
Input Inrush current Less than 8 times of rated input current
Generator Set 1.5 times of UPS Rated Power
Bypass Parameter
Bypass input/Output Voltage Range 304~458V The range can be set by user via dedicated software.The maximum
range is 110~276V
Bypass Low Comeback Low Loss + 10V
Bypass High Comeback High Loss -10V
Bypass input/Output Frequency Range 45~55 Hz Default value for 50Hz system range can be set by user via
dedicated software.The maximum range
is 50*(1±15%)
Hz
Freq. Low Comeback Freq. Low Loss + 0.5 Hz
Freq. High Comeback Freq. High Loss - 0.5 Hz
Frequency System Auto Detection ≥40Hz&55Hz,start with 50Hz system
Bypass Over Load Capability <125% continue working
1 Min @ 125% to 150% rated load
10 sec @ > 150% rated load
Output Parameter
Rated kVA 10000VA 15000 VA 20000 VA
Rated kW 9000 W 13500 W 18000 W
Load type Resistive load/ lagging load/ non-linear load/ transformer load/ lighting load
Load power factor range 0.5~1 lagging
The technical specification is subject to change without notice.
Author: Pankaj Paliw al Page 2 of 4
Updated: 15.04.2020
Document: Eaton 9145 10-15-20 kVA Data Sheet.docx
Eaton 9145 10-15-20 kVA UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3

IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA


Subclause

Load Crest Ratio 3:1


Output wave type Pure sine wave
Rated output voltage 220V/230V/240V
Voltage Accuracy ±2 %
THDV <5% for Non- Linear Load
<2% for Linear Load
DC Offset ±100 mV
Output Frequency 50Hz
Output Frequency accuracy ±0.1Hz
Phase Error of synchronization < 3 degrees
Frequency Slew rate <1Hz/s MAX
Load detective error ±3%
Maximum Voltage deviation responding ±7% 0%->100%->0% Resistive Load
to resistive load step
Dynamic output performance to resistive Dynamic output performance classification 1, as per IEC62040-3 Editon 2
step load and non-linear step load :2011 reference Dynamic output performance classification 1
Recovery time after reference Non-linear 100ms recover to ±10% 0%->100%->0% Load
load step
Over Load Memory Overload time up occurs 3 times in 10min, the UPS will lock on bypass mode
and keep alarming.
Transfer Time 0ms Input power interrupt Line mode Battery mode
0ms input power recover Battery mode Line mode
0ms Turn off or common fault occurs Inverter output Bypass output
0ms Turn on/System recoveryBypass output Inverter output
0ms Line mode -> ECO mode
<10ms (Typical) Input Voltage or frequency out of Range or Loss ECO mode
line mode or battery mode
Inverter Output short stand time No less than 100ms

Inverter Output short limit current Rate output current * 3


Efficiency 93% Line Mode, rated input and output voltage, battery is fully charged, 100%
resistive load
92% Battery mode, rated output voltage, battery voltage 12V/pc, 100%
resistive load
97% ECO Mode, Nominal input and output voltage, battery is fully charged,
100% resistive load
Overload Warning point >105% rated load
Overload Warning Comeback point <100% rated load
Battery Parameter
Rated Battery Voltage 288 Vdc
Battery Type VRLA (Valve Regulated Lead Acid Battery), 12VDC
The technical specification is subject to change without notice.
Author: Pankaj Paliw al Page 3 of 4
Updated: 15.04.2020
Document: Eaton 9145 10-15-20 kVA Data Sheet.docx
Eaton 9145 10-15-20 kVA UPS Technical Specification
Manufacturer’s declaration in accordance with IEC 62040-3

IEC 62040-3 MODEL RATING (0.9 PF) 10-15-20 kVA


Subclause

Battery Shutdown Voltage 10.7 V/pcs


Battery over voltage warning point 14.4V/pcs
Battery over voltage Warning Comeback 13.7V/pcs
Voltage
Battery low Voltage Warning point 11.4 V/pcs
Battery low voltage Warning Comeback Battery warning voltage + 0.5V
Voltage
Battery Voltage detective tolerance ±2 %
Maximum Battery LeakageCurrent 500uA
Small Current Discharge Protection Default setting: 14.5 hours
Battery short protection Protected by battery fuse
Maximum charging current 4A± 0.5A
Floating charging voltage 13.65V/block
Charge Voltage Accuracy ± 2%
Recharging time 8 hours to 90% rated capability
Over charger protection point 14.4V/block
Features
ECO Mode Manual Enable via dedicated software Default Setting Off
Communication (Independent SCI) RS232/ USB 1.1
Intelligent Card slot (Independent SCI) SNMP card optional
RS232 card optional
USB1.1 card optional
RS485 card (CMC) optional
AS400 card optional
EPO Function Yes
Intelligent Fans Speed control Yes
Auto restart function Default Yes
Cold start Yes
Mechanical Features
Dimension(Unit DIM (W*H*D mm)) 350*890*650
Dimension(Package DIM (W*H*D mm) 475*1125*815

Net Weight(kg) 48.1 58.1 58.1
Gross Weight(kg) 65.1 74.1 74.1
color Pantone Process Black C

The technical specification is subject to change without notice.


Author: Pankaj Paliw al Page 4 of 4
Updated: 15.04.2020
Document: Eaton 9145 10-15-20 kVA Data Sheet.docx