13 10 1. SECONDARY BOX M.S. 1 3 2. LIFTING LUGS M.S. 4 11 P.R.V. SYSTEM M.S. 1 14 3. 4. OIL LEVEL GAUGE AL. 1 4 2 OIL DRAIN PLUG M.S. 1 5. 6. EARTHING TERMINALS M.S. 2 7. MOUNTING BASE M.S. 2 1 8. MAIN TANK BODY M.S. 1 6 15 9. CABLE GLAND M.S. 1 12 600 8 10. PRIMARY TERMINALS BRASS 6 375 7 11. PORCELIAN BUSHING PORC. 6 5 12. RATING PLATE M.S. 1 13. OIL FILLING CAP M.S. 1 14. TOP COVER M.S. 1 380 15. SECONDARY FUSE . 3 9 260 SPECIFICATIONS :- 480 325 11kV CT SINGLE PHASE 3 Nos. 11kV PT 3 PHASE 1 Nos. Burden Ratio Burden Class Ratio per phase Class 10VA 1.0 11kV/110V 50VA 1.0 800-600/1A ELECTRICALS CLEARANCE :- PHASE TO PHASE - 265mm (min.) PHASE TO EARTH - 200mm (min.) WEIGHT OF UNIT - 115kg (+/_10%) WEIGHT OF OIL - 40 Ltr. (+/_10%) 400 4 Hole of 16mm Dia 260 at 350x350 +/-5mm
380
All dimensions are in mm
550 Manufacturer:- MINI ENGINEERING WORKS Title: GA Drawing of 11kV O/D Oil Cooled CTPT Unit Design Tolerance Scale Drawn by Mohd Akram +/-10% 18-03-2024 Check by Drawing. No. REV. App. by MEW-11CTPT-01 00