PACKAGED HEAT PUMP

KH
LANDMARKE ROOFTOP UNITS
50 HZ
ENGINEERING DATA Bulletin No. 490122
April 2008

10.5 to 17.5 kW (3 to 5 Tons)


Net Cooling Capacity − 9.3 to 15.5 (31 900 to 53 000 Btuh)
Net Heating Capacity − 9.6 to 16.0 (32 700 to 54 500 Btuh)
Optional Electric Heat − 5.7 to 17.2 kW

MODEL NUMBER IDENTIFICATION


K h A 060 S 4 B N 1 M
Voltage
Brand/Family M = 380/420V−3 phase−50hz
K = Landmark Product Line
Minor Design Sequence
Unit Type 1 = 1st Revision
H = Packaged Heat Pump 2 = 2nd Revision
3 = 3rd Revision
Major Design Sequence
A = 1st Generation Factory Installed Electric Heat
B = 2nd Generation N = No Heat

Blower Type
Nominal Cooling Capacity
B = Belt Drive
036 = 10.5 kW (3 Tons)
048 = 14 kW (4 Tons)
060 = 17.5 kW (5 Tons) Refrigerant Type
4 = R−410A
Cooling Efficiency
S = Standard Efficiency
CONTENTS
Accessory Air Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
Blower Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 10−13
Cooling/Heating Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 9
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 18−25
Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 14
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 2−4
Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
Model Number Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 5−7
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pages 8
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
Temperature Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 16
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 17

FEATURES AND BENEFITS


TESTING CABINET OPTIONS/ACCESSORIES
Factory Installed
Components bonded for grounding to B Construction Corrosion Protection
meet safety standards for servicing Heavy−gauge steel panels and full
perimeter heavy−gauge galvanized A completely flexible immersed coating
required by Underwriters Laboratories
steel base rail provides structural with an electrodeposited dry film
(UL) and the International process. (AST ElectroFin E−Coat)
Electrotechnical Commission (IEC). integrity for transportation, handling,
Meets Mil Spec MIL−P−53084, ASTM
3 thru 5 ton models cooling performance and installation. B117 Standard Method Salt Spray
is rated at test conditions included in Base rails have rigging holes. Three Testing, ASTM 1153 Standard
Air−Conditioning and Refrigeration sides of the base rail have fork slots. Specification for Methyl Isobutyl Ketone.
Institute (ARI) Standard 210/240−2005 Raised edges around duct and power
entry openings in the bottom of the unit
F Hinged Access Panels
while operating at rated voltage and air Large access panels are hinged and
volumes. provide additional protection against have quarter−turn, latching handles for
International Organization for water entering the building. quick and easy access to maintenance
Standardization (ISO) 9001 Registered Air−Flow Choice areas (economizer / filter, compressor /
Manufacturing Quality System. Units are shipped in down−flow (vertical) controls, heating / blower).
configuration, can be field converted to Field Installed
horizontal air flow configuration without Coil Guards
the need of a kit. Painted, galvanized steel wire guards to
C Power Entry protect outdoor coil. Not used with Hail
Electrical lines can be brought through Guards.
the unit base or through horizontal Hail Guards
access knock−outs. Constructed of heavy gauge steel,
D Exterior Panels painted to match cabinet, helps protect
Constructed of heavy−gauge, outdoor coils from hail damage. Not
galvanized steel with a two−layer used with Coil Guards.
enamel paint finish.
E Insulation
All panels adjacent to conditioned air are
fully insulated with non−hygroscopic
fiberglass insulation.
Unit base is fully insulated. The
insulation also serves as an air seal to
the roof curb, eliminating the need to
add a seal during installation.
Access Panels
Access panels are provided for the
economizer/filter section,
heating/blower section, and the
compressor/controls section.

Landmark® Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) 50hz / Page 2


FEATURES AND BENEFITS

B E
D J L K

N H

M
I
G
F
C
KHA060S
(Heat Pump)
Shown With Optional Economizer, Power Exhaust and
Hinged Access Panels

COOLING / HEATING SYSTEM Filter/Drier REQUIRED SELECTIONS


Designed to maximize sensible and High capacity filter/drier protects the Cooling Capacity
latent cooling performance at design system from dirt and moisture. Specify nominal cooling capacity of the
conditions. Freezestat unit.
System can operate from −1°C to 52°C Protects the evaporator coil from OPTIONS/ACCESSORIES
(30°F to 125°F) without any additional damaging ice build−up due to conditions
Field Installed
controls. such as low/no air flow, or low refrigerant
Condensate Drain Trap
G Compressor charge.
Field installed only.
Resiliently mounted
grommets for quiet operation.
on rubber
J Coil Construction Available in copper or polyvinyl chloride
Copper tube construction, enhanced (PVC).
Copeland Scroll compressors for rippled−edge aluminum fins, flared
high performance, reliability and quiet Low Ambient Kit
shoulder tubing connections, silver
operation. Cycles the outdoor fan while allowing
soldered construction for improved heat
Compressor Crankcase Heater compressor operation in the cooling
transfer. Factory leak tested.
Protects against refrigerant migration cycle. This intermittent fan operation
Indoor Coil allows the system to operate without
that can occur during low ambient Cross row circuiting with rifled copper
operation. icing the evaporator coil and losing
tubing optimizes both sensible and capacity. Designed for use in ambient
High Pressure Switch latent cooling capacity. temperatures no lower than −18°C (0°F).
Protects the compressor from overload
Outdoor Coil
conditions such as dirty condenser
Two independent formed coils allow
coils, blocked refrigerant flow, or loss of
separation for cleaning.
outdoor fan operation.
Condensate Drain Pan
H Check/Thermal Expansion Valves
Plastic pan, sloped to meet drainage
Assures optimal performance
throughout the application range. requirements of American Society of
Removable element head. Heating Refrigeration and Air
Conditioning Engineers 62.1.
Reversing Valves
Side or bottom drain connections.
4-way interchange reversing valve
Reversible to allow connection at back
effects a rapid change in direction of
of unit.
refrigerant flow resulting in quick
changeover from cooling to heating and K Outdoor Coil Fan Motor
vice versa. Thermal overload protected, totally
I Defrost Control enclosed, permanently lubricated
sleeve (−036 and −048 models) or ball
Provides a defrost cycle, if needed, every
30 or 60 or 90 minutes (adjustable) of bearings (−060 model), shaft up, wire
compressor on" time at outdoor coil basket mount.
temperature below 35°F. Temperature Outdoor Coil Fan
switch mounted on outdoor coil liquid line Polyvinyl chloride (PVC) coated fan
terminates defrost cycle. guard furnished.

Landmark® Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) 50hz / Page 3


FEATURES AND BENEFITS
CONTROLS AIR FILTERS SERVICEABILITY
Unit Control Disposable 51 mm (2 inch) filters Designed to streamline general
All control voltage is provided via a 24V furnished as standard. maintenance and decrease
(secondary) transformer with built−in troubleshooting time.
circuit breaker protection. OPTIONS/ACCESSORIES Marked & Color−Coded Wiring
Heat/Cool Staging − Capable of up to 2 Field Installed All electrical wiring is color−coded and
heat / 2 cool staging with a third party Indoor Air Quality (CO2) Sensor marked to identify which components it
DDC control system or thermostat. Monitors CO2 levels adjusts is connecting.
Low Voltage Terminal Block − economizer dampers as needed for Electrical Plugs
Provides screw terminal connections Demand Control Ventilation. Positive connection electrical plugs are
for thermostat or controller wiring. ELECTRICAL used to connect common accessories or
Night Setback Mode − Saves energy maintenance parts for easy removal or
by closing outdoor air dampers and OPTIONS/ACCESSORIES installation.
operating supply fan on thermostat Field Installed Blower Access
demand only. Supply air blower parts are located near
Disconnect Switch up to 150 Amp
OPTIONS / ACCESSORIES Accessible from outside of unit, spring the access door for easy servicing and
Field Installed loaded weatherproof cover furnished. adjustment.
Dirty Filter Switch Main power to the unit is field connected Thermal Expansion Valves
Senses static pressure increase to the disconnect which allows all power Thermal expansion valves are located
indicating dirty filter condition. to be shut off for service. See near the perimeter of the unit for easier
Smoke Detector Electrical/Electric Heat tables for access.
Photoelectric type, installed in supply or ordering information, Pages 14. Removable element head allows
return air section Electric Heat change out of element and bulb without
Thermostats Helix wound nichrome elements, removing the TXV.
Control system and thermostat options. individual element limit controls, wiring Coil Cleaning
Aftermarket unit controller options. See harness. Unit Fuse Block must be Independently formed condenser coils
Page 16. ordered extra. See Electrical/Electric allow separation for easier cleaning.
Heat tables for ordering information,
L BLOWER Page 14.
Compressor Compartment
Compressor is located near the
A wide selection of supply air blower
options are available to meet a variety of perimeter of the unit for easier access.
air flow requirements. Compressor is isolated from the
condenser air flow allowing system
Motor
operation checks to be done without
Equipped with ball bearings.
changing the air flow across the outdoor
External overload protector.
coils.
Belt drive motors are offered on all
models.
Supply Air Blower
Forward curved blades, blower wheel is
statically and dynamically balanced.
All belt drive motors have adjustable
pulley for speed change.
Ordering Information
Specify drive kit number when base unit
is ordered.
REQUIRED SELECTIONS
Supply Air Blower
Order one drive kit (See Blower Data
Table for specifications)

Landmark® Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) 50hz / Page 4


OPTIONS / ACCESSORIES
ECONOMIZER/OUTDOOR AIR/EXHAUST OPTIONS
Factory or Field Installed Economizer Temperature Control − CEILING DIFFUSERS
M Economizer, Down−Flow Differential
Order two single, temperature control Ceiling Diffusers (Flush and
Parallel gear−driven action return air and
outdoor air dampers, plug-in connections kits. One is field installed in the return air Step−Down)
to unit, nylon bearings, neoprene seals, section, the other in the outdoor air Aluminum grilles, large center grille,
24−volt, fully−modulating, spring return section. Allows the economizer control insulated diffuser box with flanges,
motor, adjustable minimum damper board to select between outdoor air or hanging rings furnished, interior
position. Economizer includes return air, whichever has lower transition (even air flow), internally
barometric relief dampers. temperature. sealed (prevents recirculation), adapts
Barometric Relief Dampers allow relief Horizontal Conversion Kit to T-bar ceiling grids or plaster ceilings.
of excess air, aluminum blade dampers Insulated panel covers the bottom Transitions (Supply and Return)
prevent blow back and outdoor air return air opening on the unit base to Used with diffusers, installs in roof curb,
infiltration during off cycle, bird screen convert down−flow economizer to galvanized steel construction, flanges
furnished. horizontal air flow. furnished for duct connection to
Outdoor Air Hoods are included when
economizer is factory installed and are
N Power Exhaust Fan diffusers, fully insulated.
Installs internal to unit for down-flow ROOF CURB
furnished with economizer when ordered applications only with economizer
for field installation. option. Provides exhaust air pressure Roof Curb, Down−Flow
Choice of single (factory installed) or relief. Interlocked to run when supply air Nailer strip furnished, mates to unit, US
differential (optional) enthalpy blower is operating, fan runs when National Roofing Contractors
economizer control is available. outdoor air dampers are 50% open Approved, shipped knocked down.
Horizontal conversion kit available for (adjustable), motor is overload protected. Available in 203, 356, 457 and 610 mm
field installation. Requires Economizer and Outdoor Air (8, 14, 18, and 24 inch) heights.
Single Enthalpy Control Hood (ordered separately). Fan is 406 Standard roof curb corners fasten
Outdoor air enthalpy sensor enables mm (16 inches) diameter with 4 fan together with furnished hardware.
economizer if the outdoor enthalpy is blades (T1PWRE10A) or 508 mm (20 Hinged curb corners fasten together
less than the setpoint of the board. inches) diameter with 5 blades with furnished hinge pins.
Furnished with Economizer. (T1PWRE10N). Both include a 560 watt Cliplock curbs use interlocking tabs to
Field Installed (3/4 hp) motor. fasten together. No tools required.
Outdoor Air Damper − Manual
Two sliding dampers provide 0 to 35%
outdoor air, installs internal to unit.
Includes Outdoor Air Hood.
Outdoor Air Damper Motorized Kit
Used to convert Manual Outdoor Air
Dampers to motorized dampers. Kit
includes linked mechanical dampers
and spring return damper motor with
plug−in connection.
Differential Enthalpy Control
An optional, return air, solid-state
enthalpy sensor can be ordered extra
for field installation. Allows the
economizer control board to select
between outdoor air or return air,
whichever has lower enthalpy. Field
installed.
Economizer Temperature Control −
Single
An optional, solid-state temperature
sensor can be ordered extra for field
installation. Enables the economizer
when the outdoor air temperature is
below the configured setpoint.

Landmark® Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) 50hz / Page 5


OPTIONs / ACCESSORIES
Item Catalog 036 048 060
No.
COOLING SYSTEM
Condensate Drain Trap Polyvinyl Chloride (PVC) − LTACDKP03/07 37K69 x x x
Copper − LTACDKC03/07 45K67 x x x
Efficiency Standard   

Low Ambient Kit K1SNSR33AN1 41W33 x x x


Refrigerant Type R−410A   
Blower − SUPPLY AIR
Motors Belt Drive − 1.5 kW (2 hp) Standard Efficiency   

Drive Kits Drive Kit # 1 − T1DRKT001−1 − 561 − 842 rev/min 20W81 f


See Blower Data Tables for
selection Drive Kit # 2 − T1DRKT002−1 − 621 − 931 rev/min 20W82 f
Drive Kit # 3 − T1DRKT003−1 − 694 − 1042 rev/min 20W83 f
Drive Kit # 5 − T1DRKT005−1 − 748 − 1142 rev/min 20W85 f
Drive Kit # 6 − T1DRKT006−1 − 893 − 1191 rev/min 20W86 f
Drive Kit # 7 − T1DRKT007−1 − 1010 − 1290 rev/min 20W87 f
CABINET
Coil Guards T1GARD20A−1 17W87 x x
T1GARD20N−1 17W88 x
Corrosion Protection   

Hail Guards T1GARD10A−1 17W89 x x


T1GARD10N−1 17W90 x
Hinged Access Panels   
CONTROLS
Dirty Filter Switch COSWCH00AE−1 30K48 x x x
Smoke Detector − Supply/Return T1SNSR41AN1 39W16 x x x
ELECTRICAL
Disconnect See Electric Data Tables for usage x x x
Voltage − 50 hz with neutral 380/420V − 3 phase   
1 ELECTRIC HEAT
5.7 kW T1EH0075AN1 14W39 x x x
11.5 kW T1EH0150AN1 14W40 x x x
17.2 kW T1EH0225AN1 14W41 x
ELECTRIC HEAT ACCESSORIES/OPTIONS − See Electrical/Electric Heat Tables for selection
Unit Fuse Block x x x
INDOOR AIR QUALITY
Indoor Air Quality (Co2) Sensors
Sensor − white case CO2 display C0SNSR50AE1L 77N39 x x x
Sensor − duct−mount, black case, no display C0SNSR53AE1L 87N54 x x x
CO2 Sensor Duct Mounting Kit C0MISC19AE1− 85L43 x x x
NOTE − The catalog numbers that appear here are for ordering field installed accessories only.
1 Nominal kW at 420V−3ph−50hz. Electric heat model numbers are based on nominal kW for US applications.
⊗ − Field Installed or Configure to Order (factory installed)
 − Configure to Order (Factory Installed)
X − Field Installed.

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 6


OPTIONs / ACCESSORIES
Item Catalog 036 048 060
No.
ECONOMIZER
Economizer
Economizer, Single Enthalpy Control T1ECON30A−1 36W96 f f
Includes Outdoor Air Hood and Barometric Relief Dampers
T1ECON30N−1 36W97 f
Horizontal Economizer Conversion Kit T1HECK00AN1 17W45 x x x
Economizer Controls
Differential Enthalpy Sensor T1SNSR60AN1 17W71 x x x
Single Temperature Control TASEK10/15 76M37 x x x
Differential Temperature Control Order 2 − TASEK10/15 76M37 x x x
OUTDOOR AIR
Outdoor Air Dampers
Damper Section − Manual, Includes Outdoor Air Hood T1DAMP11A−1 16W88 x x
T1DAMP11N−1 16W91 x
Damper Motorized Kit − Order Manual Outdoor Air Damper Separately T1DAMP21AN1 16W92 x x x
POWER EXHAUST FANS
Standard Static T1PWRE10A−1G 17W40 x x
380/420V
T1PWRE10N−1G 17W43 x
CEILING DIFFUSERS
Step−Down − Order one RTD9−65 27G87 x x x
Flush − Order one FD9−65 27G86 x x x
Transitions (Supply and Return) − Order one T1TRAN10AN1 17W53 x x x
ROOF CURBS − down−Flow
Cliplock 1000
203 mm (8 in.) height T1CURB23AN1 16W93 x x x
356 mm (14 in.) height T1CURB20AN1 16W94 x x x
457 mm (18 in.) height T1CURB21AN1 16W95 x x x
610 mm (24 in.) height T1CURB22AN1 16W96 x x x
Hinged
203 mm (8 in.) height T1CURB30AN1 17W46 x x x
457 mm (18 in.) height T1CURB32AN1 17W47 x x x
610 mm (24 in.) height T1CURB33AN1 17W48 x x x
Standard
356 mm (14 in.) height T1CURB10AN1 13W27 x x x
NOTE − The catalog numbers that appear here are for ordering field installed accessories only.
⊗ − Field Installed or Configure to Order (factory installed)
X − Field Installed.

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 7


SPECIFICATIONS − BELT DRIVE BLOWER 10.5 − 17.5 kW (3 − 5 Ton)
General Nominal Tonnage 10.5 kW (3 Ton) 14 kW (4 Ton) 17.5 kW (5 Ton)
Data Model No. KHA036S4B KHA048S4B KHA060S4B
Efficiency Type Standard Standard Standard
Cooling Gross Cooling Capacity − kW (Btuh) 9.8 (33 400) 13.0 (44 300) 16.3 (55 500)
Performance 1 Net Cooling Capacity − kW (Btuh) 9.3 (31 900) 12.4 (42 300) 15.5 (53 000)
ARI Rated Air Flow − L/s (cfm) 545 (1160) 755 (1600) 935 (1985)
2 Sound Rating Number (dB) 75 75 82
Total Unit Power − kW 2.9 3.9 4.8
1 EER (Btuh/Watt) 10.9 10.7 11
Refrigerant Type R−410A R−410A R−410A
Charge Furnished 5.67 5.95 kg 7.26 kg
(12 lbs. 8 oz.) (13 lbs. 2 oz.) (16 lbs 0 oz.)
Heating Total High Heating Capacity − kW (Btuh) 9.6 (32 700) 12.6 (43 000) 16.0 (54 500)
Performance Total Unit Power − kW 2.6 3.5 4.2
1 COP 3.7 3.7 3.8
Total Low Heating Capacity − kW (Btuh) 5.8 (19 700) 7.7 (26 400) 9.5 (32 400)
Total Unit Power − kW 2.4 3.1 3.6
COP 2.4 2.5 1 2.7

Electric Heating Options See Electric Heat Tables Page NO TAG


Compressor Type (no.) Scroll (1) Scroll (1) Scroll (1)
Outdoor Net face area − m2 (sq. ft.) 1.45 (15.6) 1.45 (15.6) 1.79 (19.27)
Coil Tube diameter − mm (in.) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8)
Number of rows 2 2 2
Fine per meter (Fins / inch) 788 (20) 788 (20) 788 (20)
Outdoor Motor W (HP) 186 (1/4) 186 (1/4) 248 (1/3)
Coil Fan Motor rev/min 690 690 900
Total motor watts 190 190 310
Diameter − mm (in.) / No. of blades 610 (24) − 3 610 (24) − 3 610 (24) − 3
Total air volume − L/s (cfm) 1300 (2750) 1300 (2750) 1890 (4000)
Indoor Coil Net face area − m2 (sq. ft.) 0.72 (7.78) 0.72 (7.78) 0.90 (9.70)
Tube diameter − mm (in.) 9.5 (3/8) 9.5 (3/8) 9.5 (3/8)
Number of rows 3 3 4
Fins per meter (Fins / inch) 552 (14) 552 (14) 552 (14)
Drain Connection (no. and size) − in. (1) 3/4 NPT
Expansion device type Balanced Port Thermostatic Expansion Valve, removeable power head
3 Indoor Nominal Motor kW (HP) 1.5 (2)
Blower & Maximum Usable Motor kW (HP) 1.7 (2.3)
Drive
Wheel nom. diameter x width − in. (mm) 254 x 254 (10 x 10)
Selection
Available Drive Kits Drive Kit #1 Drive Kit #2 Drive Kit #3
561 − 842 rev/min 621 − 931 rev/min 694 − 1042 rev/min
Drive Kit #5 Drive Kit #6 Drive Kit #7
748 − 1142 rev/min 893 − 1191 rev/min 1010 − 1290 rev/min
Filters Type Disposable
Number and size − mm (in.) (4) 406 x 508 x 51 (16 x 20 x 2)
Electrical Characteristics − 50 hz 380/420V − 3 phase with neutral
NOTE − Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1 Rating test conditions are those included in Air−Conditioning and Refrigeration Institute (ARI) Standard 210/240 while operating at rated voltage and air volumes
Cooling Ratings − 35°C (95°F) outdoor air temperature and 27°C (80°F) db/19°C (67°F) wb entering indoor coil air.
High Temperature Heating Ratings − 8°C (47°F) db/6°C (43°F) wb outdoor air temperature and 21°C (70°F) entering indoor coil air.
Low Temperature Heating Ratings − -8°C (17°F) db/-9°C (15°F) wb outdoor air temperature and 21°C (70°F) entering indoor coil air.
2 Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
3 Using total air volume and system static pressure requirements determine from blower performance tables rev/min and motor size required. Maximum usable size of motors
furnished is shown. If motors of comparable size are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 8


COOLING / HEATING RATINGS
NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
10.6 kW (3 Ton) STANDARD EFFICIENCY − COOLING CAPACITY KHA036S4
Outdoor Air Temperature Entering Outdoor Coil
Total 27C (80F) 35C (95F) 43C (110F) 52C (125F)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Temperat Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ure Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb CapacityMotor Dry Bulb
kW kW kW kW
24C 27C 29C 24C 27C 29C 24C 27C 29C 24C 27C 29C
m3/s cfm kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input
75F 80F 85F 75F 80F 85F 75F 80F 85F 75F 80F 85F
.45 960 9.6 32.7 1.88 .74 .88 1.00 8.9 30.4 2.27 .76 .92 1.00 8.2 27.9 2.76 .79 .96 1.00 7.4 25.1 3.37 .84 1.00 1.00
17C .56 1200 10.0 34.0 1.88 .80 .97 1.00 9.3 31.8 2.28 .83 1.00 1.00 8.6 29.4 2.77 .87 1.00 1.00 7.8 26.7 3.37 .93 1.00 1.00
(63F)
.68 1440 10.4 35.4 1.89 .86 1.00 1.00 9.7 33.2 2.29 .90 1.00 1.00 9.0 30.7 2.78 .94 1.00 1.00 8.1 27.8 3.38 1.00 1.00 1.00
.45 960 10.2 34.9 1.89 .57 .71 .85 9.5 32.4 2.29 .58 .73 .88 8.7 29.7 2.77 .60 .76 .93 7.8 26.5 3.37 .63 .81 .98
19C .56 1200 10.6 36.0 1.90 .61 .77 .94 9.8 33.4 2.30 .63 .80 .97 8.9 30.5 2.78 .65 .85 1.00 8.0 27.3 3.38 .68 .90 1.00
(67F)
.68 1440 10.8 36.8 1.91 .65 .84 1.00 10.0 34.2 2.31 .67 .87 1.00 9.2 31.3 2.79 .70 .92 1.00 8.2 27.9 3.38 .74 .98 1.00
.45 960 10.9 37.2 1.91 .42 .55 .68 10.2 34.7 2.31 .43 .57 .71 9.3 31.7 2.79 .44 .59 .74 8.3 28.3 3.39 .45 .62 .79
22C .56 1200 11.2 38.3 1.92 .44 .60 .75 10.4 35.6 2.32 .44 .61 .78 9.5 32.5 2.80 .46 .64 .82 8.5 29.0 3.40 .47 .68 .88
(71F)
.68 1440 11.5 39.1 1.93 .45 .64 .82 10.6 36.2 2.33 .46 .66 .85 9.7 33.1 2.81 .47 .69 .90 8.6 29.4 3.41 .49 .74 .96
10.6 kW (3 Ton) STANDARD EFFICIENCY − HEATING CAPACITY KHA036S4
Air Temperature Entering Outdoor Coil
Indoor Coil
Air Volume 18C (65F) 7C (45F) minus 4C (25F) minus 15C (5F) minus 28C (minus 15F)
21C db Comp. Comp. Comp. Comp. Comp.
(70F db) Total Heating Total Heating Total Heating Total Heating Total Heating
Capacity Motor Capacity Motor Capacity Motor Capacity Motor Capacity Motor
kW kW kW kW kW
m3/s cfm kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input
0.46 960 11.6 39.6 2.20 8.8 30.1 2.05 5.8 19.9 1.88 4.1 14.1 1.71 2.0 6.9 1.28
0.57 1200 11.8 40.4 2.07 9.1 30.9 1.92 6.1 20.7 1.76 4.4 14.9 1.58 2.3 7.7 1.15
0.68 1440 12.0 41.1 1.99 9.3 31.6 1.84 6.3 21.4 1.68 4.6 15.6 1.50 2.5 8.4 1.07
14.1 kW (4 Ton) STANDARD EFFICIENCY − COOLING CAPACITY KHA048S4
Outdoor Air Temperature Entering Outdoor Coil
Total 27C (80F) 35C (95F) 43C (110F) 52C (125F)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
24C 27C 29C 24C 27C 29C 24C 27C 29C 24C 27C 29C
m3/s cfm kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input
75F 80F 85F 75F 80F 85F 75F 80F 85F 75F 80F 85F
.60 1280 12.8 43.7 2.55 .72 .88 1.00 11.9 40.6 3.11 .75 .92 1.00 10.9 37.2 3.77 .78 .97 1.00 9.9 33.7 4.57 .83 1.00 1.00
17C .75 1600 13.3 45.5 2.55 .78 .97 1.00 12.4 42.3 3.13 .82 1.00 1.00 11.5 39.2 3.78 .86 1.00 1.00 10.4 35.6 4.59 .92 1.00 1.00
(63F)
.90 1920 13.9 47.3 2.55 .85 1.00 1.00 12.9 44.1 3.14 .89 1.00 1.00 12.0 40.8 3.80 .94 1.00 1.00 10.8 36.9 4.61 .99 1.00 1.00
.60 1280 13.6 46.5 2.55 .56 .70 .84 12.6 43.0 3.14 .57 .72 .88 11.5 39.3 3.79 .59 .75 .93 10.3 35.2 4.59 .62 .80 .99
19C .75 1600 14.1 48.0 2.56 .60 .76 .93 13.0 44.3 3.15 .62 .79 .98 11.8 40.4 3.81 .64 .84 1.00 10.6 36.2 4.61 .68 .90 1.00
(67F)
.90 1920 14.3 48.9 2.56 .63 .83 1.00 13.2 45.2 3.16 .66 .87 1.00 12.1 41.3 3.82 .69 .92 1.00 10.8 37.0 4.62 .73 .98 1.00
.60 1280 14.5 49.6 2.56 .41 .54 .67 13.5 45.9 3.16 .42 .56 .70 12.3 41.9 3.83 .43 .58 .73 11.0 37.5 4.63 .44 .61 .78
22C .75 1600 14.9 51.0 2.56 .43 .58 .74 13.8 47.0 3.17 .44 .60 .77 12.6 42.9 3.84 .45 .63 .81 11.2 38.3 4.64 .46 .67 .88
(71F)
.90 1920 15.2 51.9 2.56 .44 .62 .80 14.0 47.8 3.18 .45 .65 .85 12.7 43.5 3.85 .47 .68 .90 11.4 38.8 4.65 .48 .73 .97
14.1 kW (4 Ton) STANDARD EFFICIENCY − HEATING CAPACITY KHA048S4
Air Temperature Entering Outdoor Coil
Indoor Coil
Air Volume 18C (65F) 7C (45F) minus 4C (25F) minus 15C (5F) minus 28C (minus 15F)
21C db
Total Heating Comp. Total Heating Comp. Total Heating Comp. Total Heating Comp. Total Heating Comp.
(70F db)
Capacity Motor Capacity Motor Capacity Motor Capacity Motor Capacity Motor
kW kW kW kW kW
m3/s cfm kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input
0.61 1280 15.2 51.9 3.01 11.6 39.5 2.77 7.7 26.2 2.52 5.6 19.1 2.26 2.8 9.4 1.69
0.76 1600 15.5 52.9 2.84 11.9 40.5 2.60 8.0 27.2 2.35 5.9 20.1 2.09 3.0 10.4 1.53
0.91 1920 15.8 53.8 2.75 12.1 41.4 2.51 8.2 28.1 2.26 6.2 21.0 2.00 3.3 11.3 1.43
17.5 kW (5 Ton) STANDARD EFFICIENCY − COOLING CAPACITY KHA060S4
Outdoor Air Temperature Entering Outdoor Coil
Total 27C (80F) 35C (95F) 43C (110F) 52C (125F)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
24C 27C 29C 24C 27C 29C 24C 27C 29C 24C 27C 29C
m3/s cfm kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input
75F 80F 85F 75F 80F 85F 75F 80F 85F 75F 80F 85F
.75 1600 16.0 54.7 3.11 .73 .87 1.00 14.8 50.6 3.74 .75 .92 1.00 13.5 46.1 4.52 .78 .97 1.00 12.1 41.2 5.49 .84 1.00 1.00
17C .94 2000 16.7 56.9 3.13 .79 .97 1.00 15.5 52.8 3.77 .82 1.00 1.00 14.2 48.6 4.55 .87 1.00 1.00 12.8 43.7 5.51 .94 1.00 1.00
(63F)
1.13 2400 17.4 59.3 3.15 .85 1.00 1.00 16.2 55.3 3.79 .90 1.00 1.00 14.9 50.8 4.57 .95 1.00 1.00 13.3 45.4 5.53 1.00 1.00 1.00
.75 1600 17.1 58.2 3.15 .56 .70 .84 15.8 53.8 3.78 .58 .73 .88 14.3 48.9 4.55 .60 .76 .93 12.6 43.1 5.51 .63 .82 1.00
19C .94 2000 17.6 60.1 3.17 .60 .76 .93 16.3 55.5 3.80 .62 .80 .98 14.7 50.3 4.58 .65 .85 1.00 13.0 44.4 5.53 .69 .92 1.00
(67F)
1.13 2400 18.0 61.5 3.19 .64 .83 1.00 16.6 56.7 3.82 .66 .88 1.00 15.1 51.5 4.59 .70 .93 1.00 13.3 45.5 5.55 .75 1.00 1.00
.75 1600 18.2 62.2 3.19 .42 .55 .68 16.8 57.4 3.83 .42 .56 .70 15.3 52.1 4.60 .43 .59 .74 13.5 46.0 5.55 .44 .62 .79
22C .94 2000 18.8 64.0 3.22 .43 .59 .74 17.3 59.0 3.85 .44 .61 .77 15.6 53.4 4.62 .45 .64 .82 13.8 47.0 5.57 .47 .68 .89
(71F)
1.13 2400 19.1 65.2 3.23 .45 .63 .81 17.6 60.0 3.87 .46 .66 .85 15.9 54.3 4.64 .47 .69 .91 14.0 47.7 5.59 .50 .74 .98
17.5 kW (5 Ton) STANDARD EFFICIENCY − HEATING CAPACITY KHA060S4
Air Temperature Entering Outdoor Coil
Indoor Coil
Air Volume 18C (65F) 7C (45F) minus 4C (25F) minus 15C (5F) minus 28C (minus 15F)
21C db
Total Heating Comp. Total Heating Comp. Total Heating Comp. Total Heating Comp. Total Heating Comp.
(70F db)
Capacity Motor Capacity Motor Capacity Motor Capacity Motor Capacity Motor
kW kW kW kW kW
m3/s cfm kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input kW kBtuh Input
0.76 1600 19.5 66.6 3.53 14.8 50.6 3.28 9.9 33.7 3.03 6.8 23.3 2.68 3.4 11.6 2.01
0.95 2000 19.8 67.7 3.33 15.2 51.7 3.08 10.2 34.8 2.83 7.2 24.4 2.48 3.7 12.7 1.81
1.14 2400 20.3 69.2 3.21 15.6 53.2 2.96 10.6 36.3 2.71 7.6 25.9 2.36 4.2 14.2 1.69
LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 9
BLOWER DATA − BELT DRIVE 10.5 kW (3 Ton)
Blower tables include resistance for base unit with wet indoor coil & 51 mm (2 in.) disposable air filters in place.
FOR ALL UNITS ADD:
1 − Any factory installed options air resistance (economizer, etc.) See page 13
2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 13
Then determine from table the blower motor output and drive required.
50 to 200 Pa 10.5 kW (3 Ton) Standard Efficiency (Down−Flow) KHA036S
Air External Static − Pa (in.w.g.)
Volume 50 (0.20) 100 (0.40) 150 (0.60) 200 (0.80)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm Low Static − Drive Kit #1 High Static − Drive Kit #5
425 900 595 0.15 0.11 780 0.30 0.22 930 0.50 0.37 1065 0.75 0.56
470 1000 615 0.20 0.15 790 0.35 0.26 945 0.55 0.41 1075 0.75 0.56
520 1100 640 0.20 0.15 805 0.35 0.26 955 0.55 0.41 1085 0.80 0.60
565 1200 665 0.25 0.19 825 0.40 0.30 965 0.60 0.45 1095 0.85 0.63
615 1300 695 0.30 0.22 845 0.45 0.34 980 0.65 0.48 1105 0.90 0.67
660 1400 730 0.35 0.26 865 0.50 0.37 995 0.70 0.52 1120 0.95 0.71
705 1500 760 0.40 0.30 890 0.55 0.41 1015 0.75 0.56 1135 1.00 0.75
250 to 400 Pa 10.5 kW (3 Ton) Standard Efficiency (Down−Flow) KHA036S
Air External Static − Pa (in.w.g.)
Volume 250 (1.00) 300 (1.20) 350 (1.40) 400 (1.60)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm Field Furnished
425 900 1180 1.00 0.75 1285 1.25 0.93 1380 1.50 1.12 1465 1.80 1.34
470 1000 1190 1.00 0.75 1295 1.30 0.97 1390 1.60 1.19 1475 1.85 1.38
520 1100 1200 1.05 0.78 1300 1.35 1.01 1400 1.65 1.23 1485 1.95 1.45
565 1200 1210 1.10 0.82 1310 1.40 1.04 1410 1.70 1.27 1495 2.00 1.49
615 1300 1220 1.15 0.86 1320 1.45 1.08 1415 1.75 1.31 1505 2.05 1.53
660 1400 1230 1.20 0.90 1330 1.50 1.12 1425 1.80 1.34 1515 2.15 1.60
705 1500 1240 1.25 0.93 1345 1.55 1.16 1435 1.90 1.42 1525 2.20 1.64
50 to 200 Pa 10.5 kW (3 Ton) Standard Efficiency (Horizontal) KHA036S
Air External Static − Pa (in.w.g.)
Volume 50 (0.20) 100 (0.40) 150 (0.60) 200 (0.80)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm Low Static − Drive Kit #1 High Static − Drive Kit #5
425 900 570 0.15 0.11 735 0.30 0.22 875 0.45 0.34 1000 0.65 0.48
470 1000 595 0.15 0.11 750 0.30 0.22 890 0.50 0.37 1010 0.70 0.52
520 1100 625 0.20 0.15 765 0.35 0.26 900 0.50 0.37 1020 0.75 0.56
565 1200 660 0.25 0.19 790 0.40 0.30 915 0.55 0.41 1030 0.75 0.56
615 1300 690 0.30 0.22 810 0.40 0.30 930 0.60 0.45 1045 0.80 0.60
660 1400 730 0.35 0.26 840 0.50 0.37 950 0.65 0.48 1060 0.85 0.63
705 1500 765 0.40 0.30 870 0.55 0.41 970 0.70 0.52 1075 0.95 0.71
250 to 400 Pa 10.5 kW (3 Ton) Standard Efficiency (Horizontal) KHA036S
Air External Static − Pa (in.w.g.)
Volume 250 (1.00) 300 (1.20) 350 (1.40) 400 (1.60)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm High Static − Drive Kit #5 Field Furnished
425 900 1105 0.90 0.67 1200 1.10 0.82 1285 1.35 1.01 1365 1.60 1.19
470 1000 1115 0.90 0.67 1210 1.15 0.86 1300 1.40 1.04 1380 1.70 1.27
520 1100 1125 0.95 0.71 1220 1.20 0.90 1310 1.50 1.12 1395 1.75 1.31
565 1200 1135 1.00 0.75 1235 1.25 0.93 1320 1.55 1.16 1405 1.85 1.38
615 1300 1145 1.05 0.78 1245 1.30 0.97 1330 1.60 1.19 1415 1.90 1.42
660 1400 1160 1.10 0.82 1255 1.40 1.04 1340 1.65 1.23 1425 1.95 1.45
705 1500 1175 1.15 0.86 1265 1.45 1.08 1355 1.75 1.31 1435 2.05 1.53

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 10


BLOWER DATA − BELT DRIVE 14 kW (4 Ton)
Blower tables include resistance for base unit with wet indoor coil & 51 mm (2 in.) disposable air filters in place.
FOR ALL UNITS ADD:
1 − Any factory installed options air resistance (economizer, etc.) See page 13
2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 13
Then determine from table the blower motor output and drive required.
50 to 200 Pa 14 kW (4 Ton) Standard Efficiency (Down−Flow) KHA048S
Air External Static − Pa (in.w.g.)
Volume 50 (0.20) 100 (0.40) 150 (0.60) 200 (0.80)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm Low Static − Drive Kit #2 High Static − Drive Kit #6
565 1200 665 0.20 0.15 820 0.35 0.26 955 0.53 0.40 1080 0.73 0.54
615 1300 690 0.25 0.19 835 0.40 0.30 970 0.58 0.43 1090 0.78 0.58
660 1400 725 0.30 0.22 860 0.45 0.34 990 0.63 0.47 1105 0.83 0.62
705 1500 755 0.35 0.26 884 0.50 0.37 1005 0.68 0.51 1120 0.88 0.66
755 1600 790 0.40 0.30 910 0.55 0.41 1025 0.73 0.54 1140 0.93 0.69
800 1700 825 0.48 0.36 935 0.60 0.45 1050 0.80 0.60 1155 1.03 0.77
850 1800 860 0.53 0.40 970 0.70 0.52 1075 0.88 0.66 1175 1.08 0.81
895 1900 895 0.63 0.47 995 0.78 0.58 1100 0.95 0.71 1200 1.18 0.86
945 2000 930 0.68 0.51 1030 0.88 0.66 1125 1.05 0.78 1220 1.28 0.95
250 to 400 Pa 14 kW (4 Ton) Standard Efficiency (Down−Flow) KHA048S
Air External Static − Pa (in.w.g.)
Volume 250 (1.00) 300 (1.20) 350 (1.40) 400 (1.60)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm High Static − Drive Kit #6 Field Furnished
565 1200 1190 0.95 0.71 1290 1.20 0.90 1380 1.43 1.07 1470 1.70 1.27
615 1300 1200 1.00 0.75 1300 1.25 0.93 1395 1.50 1.12 1480 1.78 1.33
660 1400 1215 1.05 0.78 1310 1.30 0.97 1405 1.57 1.17 1490 1.83 1.37
705 1500 1225 1.10 0.82 1325 1.35 1.01 1415 1.63 1.22 1500 1.93 1.44
755 1600 1240 1.18 0.88 1340 1.45 1.08 1430 1.70 1.27 1515 2.00 1.49
800 1700 1260 1.25 0.93 1355 1.50 1.12 1440 1.78 1.33 1525 2.08 1.55
850 1800 1275 1.33 0.99 1370 1.60 1.19 1455 1.85 1.38 1540 2.18 1.63
895 1900 1290 1.43 1.07 1385 1.70 1.27 1470 1.95 1.45 1555 2.28 1.70
945 2000 1315 1.53 1.14 1400 1.78 1.33 1485 2.05 1.53 1565 2.38 1.78
50 to 200 Pa 14 kW (4 Ton) Standard Efficiency (Horizontal) KHA048S
Air External Static − Pa (in.w.g.)
Volume 50 (0.20) 100 (0.40) 150 (0.60) 200 (0.80)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm Low Static − Drive Kit #2 High Static − Drive Kit #6
565 1200 655 0.20 0.15 780 0.35 0.26 905 0.50 0.37 1020 0.68 0.51
615 1300 685 0.25 0.19 805 0.38 0.28 925 0.52 0.39 1034 0.70 0.52
660 1400 725 0.30 0.22 835 0.43 0.32 945 0.53 0.40 1050 0.75 0.56
705 1500 760 0.35 0.26 860 0.50 0.37 965 0.63 0.47 1065 0.80 0.60
755 1600 800 0.43 0.32 895 0.55 0.41 990 0.70 0.52 1085 0.88 0.66
800 1700 835 0.50 0.37 925 0.63 0.47 1015 0.78 0.58 1105 0.95 0.71
850 1800 875 0.58 0.43 960 0.70 0.52 1045 0.85 0.63 1130 1.03 0.77
895 1900 920 0.68 0.51 995 0.80 0.60 1075 0.95 0.70 1155 1.13 0.84
945 2000 960 0.78 0.58 1030 0.90 0.67 1105 1.05 0.78 1180 1.23 0.92
250 to 400 Pa 14 kW (4 Ton) Standard Efficiency (Horizontal) KHA048S
Air External Static − Pa (in.w.g.)
Volume 250 (1.00) 300 (1.20) 350 (1.40) 400 (1.60)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm High Static − Drive Kit #6 Field Furnished
565 1200 1120 0.85 0.63 1215 1.08 0.88 1300 1.30 0.97 1380 1.55 1.16
615 1300 1135 0.90 0.67 1225 1.13 0.84 1310 1.35 1.01 1390 1.60 1.19
660 1400 1145 0.98 0.73 1240 1.18 0.88 1324 1.43 1.07 1405 1.68 1.25
705 1500 1160 1.03 0.77 1250 1.23 0.92 1335 1.48 1.10 1415 1.73 1.29
755 1600 1175 1.08 0.81 1265 1.33 0.99 1350 1.55 1.16 1425 1.80 1.34
800 1700 1195 1.15 0.86 1280 1.38 1.03 1365 1.63 1.22 1440 1.88 1.40
850 1800 1215 1.23 0.92 1300 1.48 1.10 1380 1.73 1.29 1455 1.98 1.48
895 1900 1235 1.33 0.99 1315 1.55 1.16 1395 1.78 1.33 1470 2.08 1.55
945 2000 1260 1.43 1.07 1340 1.68 1.25 1415 1.93 1.44 1485 2.18 1.63

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 11


BLOWER DATA − BELT DRIVE 17.5 kW (5 Ton)
Blower tables include resistance for base unit with wet indoor coil, & 51 mm (2 in.) disposable air filters in place.
FOR ALL UNITS ADD:
1 − Any factory installed options air resistance (economizer, etc.) See page 13
2 − Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 13
Then determine from table the blower motor output and drive required.
50 to 200 Pa 17.5 kW (5 Ton) Standard Efficiency (Down−Flow) KHA060S
Air External Static − Pa (in.w.g.)
Volume 50 (0.20) 100 (0.40) 150 (0.60) 200 (0.80)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm Low Static − Drive Kit #3
755 1600 730 0.35 0.26 835 0.45 0.34 935 0.60 0.45 1030 0.70 0.52
800 1700 760 0.40 0.30 860 0.50 0.37 960 0.65 0.48 1050 0.80 0.60
850 1800 795 0.50 0.37 890 0.60 0.45 980 0.70 0.52 1070 0.85 0.63
895 1900 830 0.55 0.41 920 0.65 0.48 1010 0.80 0.60 1090 0.95 0.71
945 2000 865 0.65 0.48 950 0.75 0.56 1035 0.90 0.67 1115 1.05 0.78
990 2100 900 0.70 0.52 980 0.85 0.63 1060 1.00 0.75 1140 1.15 0.86
1040 2200 935 0.80 0.60 1010 0.95 0.71 1090 1.10 0.82 1165 1.25 0.93
1085 2300 970 0.90 0.67 1045 1.05 0.78 1120 1.20 0.90 1190 1.35 1.01
1130 2400 1005 1.05 0.78 1075 1.15 0.86 1150 1.30 0.97 1220 1.50 1.12
250 to 400 Pa 17.5 kW (5 Ton) Standard Efficiency (Down−Flow) KHA060S
Air External Static − Pa (in.w.g.)
Volume 250 (1.00) 300 (1.20) 350 (1.40) 400 (1.60)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm High Static − Drive Kit #7 Field Furnished
755 1600 1120 0.85 0.63 1200 1.05 0.78 1280 1.20 0.90 1355 1.35 1.01
800 1700 1135 0.95 0.71 1215 1.10 0.82 1295 1.30 0.97 1365 1.45 1.08
850 1800 1155 1.00 0.75 1230 1.20 0.90 1310 1.35 1.01 1380 1.55 1.16
895 1900 1170 1.10 0.82 1250 1.25 0.93 1325 1.45 1.08 1395 1.65 1.23
945 2000 1195 1.20 0.90 1270 1.35 1.01 1340 1.55 1.16 1410 1.75 1.31
990 2100 1215 1.30 0.97 1290 1.45 1.08 1360 1.65 1.23 1425 1.85 1.38
1040 2200 1240 1.40 1.04 1310 1.60 1.19 1380 1.80 1.34 1445 1.95 1.45
1085 2300 1260 1.50 1.12 1330 1.70 1.27 1400 1.90 1.42 1465 2.10 1.57
1130 2400 1285 1.65 1.23 1355 1.85 1.38 1420 2.05 1.53 1480 2.20 1.64
50 to 200 Pa 17.5 kW (5 Ton) Standard Efficiency (Horizontal) KHA060S
Air External Static − Pa (in.w.g.)
Volume 50 (0.20) 100 (0.40) 150 (0.60) 200 (0.80)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm Low Static − Drive Kit #3 High Static − Drive Kit #7
755 1600 845 0.45 0.34 955 0.55 0.41 1060 0.70 0.52 1160 0.90 0.67
800 1700 880 0.50 0.37 990 0.65 0.48 1090 0.80 0.60 1185 0.95 0.71
850 1800 920 0.60 0.45 1020 0.75 0.56 1120 0.90 0.67 1210 1.05 0.78
895 1900 960 0.70 0.52 1060 0.85 0.63 1150 1.00 0.75 1240 1.15 0.86
945 2000 1000 0.80 0.60 1095 0.95 0.71 1185 1.10 0.82 1265 1.25 0.93
990 2100 1040 0.90 0.67 1130 1.05 0.78 1215 1.20 0.90 1300 1.40 1.04
1040 2200 1085 1.00 0.75 1170 1.15 0.86 1250 1.35 1.01 1330 1.50 1.12
1085 2300 1125 1.15 0.86 1205 1.30 0.97 1285 1.45 1.08 1360 1.65 1.23
1130 2400 1165 1.25 0.93 1245 1.45 1.08 1320 1.60 1.19 1395 1.80 1.34
250 to 400 Pa 17.5 kW (5 Ton) Standard Efficiency (Horizontal) KHA060S
Air External Static − Pa (in.w.g.)
Volume 250 (1.00) 300 (1.20) 350 (1.40) 400 (1.60)
rev/min BHP kW rev/min BHP kW rev/min BHP kW rev/min BHP kW
L/s cfm High Static − Drive Kit #7 Field Furnished
755 1600 1255 1.05 0.78 1350 1.30 0.97 1440 1.55 1.16 1530 1.80 1.34
800 1700 1275 1.15 0.86 1365 1.35 1.01 1455 1.60 1.19 1540 1.85 1.38
850 1800 1300 1.25 0.93 1385 1.45 1.08 1470 1.70 1.27 1550 1.95 1.45
895 1900 1325 1.35 1.01 1405 1.55 1.16 1485 1.75 1.31 1565 2.00 1.49
945 2000 1350 1.45 1.08 1430 1.65 1.23 1505 1.85 1.38 1585 2.15 1.60
990 2100 1375 1.55 1.16 1455 1.80 1.34 1530 2.00 1.49 1605 2.25 1.68
1040 2200 1405 1.70 1.27 1480 1.90 1.42 1555 2.15 1.60 1625 2.40 1.79
1085 2300 1435 1.85 1.38 1510 2.05 1.53 1580 2.30 1.72 1650 2.55 1.90
1130 2400 1465 2.00 1.49 1535 2.20 1.64 1605 2.45 1.83 1675 2.70 2.01

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 12


BLOWER DATA

FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS


Motor rev/min Range
Nominal Maximum Drive 1 Drive 2 Drive 3 Drive 5 Drive 6 Drive 7
1.5 kW 1.7 kW
2 hp 2.3 hp 561 − 842 621 − 931 694 − 1042 748 − 1142 893 − 1191 1010 − 1290
*Using total air volume and system static pressure requirements determine from blower performance tables rev/min and motor kW required. Maximum usable kW of motors
furnished by Lennox are shown. If motors of comparable kW are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

POWER EXHAUST FANS PERFORMANCE


Return Air System Air Volume Exhausted
Static Pressure T1PWRE10A T1PWRE10N
Low Medium High Low Medium High
Pa in. w.g. L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm
0 0 510 1085 515 1085 510 1080 1525 3235 1625 3445 1705 3615
25 0.1 410 865 415 875 415 880 1280 2710 1395 2960 1475 3130
50 0.2 315 670 320 675 320 675 855 1810 1185 2510 1275 2700
75 0.3 235 495 230 490 230 485 865 1835 9985 2085 1090 2310
100 0.4 160 335 155 335 160 340 665 1405 790 1675 915 1935
125 0.5 95 200 100 210 120 250 440 935 595 1260 740 1570
150 0.6 35 75 65 135 115 240 185 390 390 825 360 760

OPTIONS / ACCESSORIES AIR RESISTANCE CEILING DIFFUSER AIR THROW DATA


Air Volume Economizer Electric Heat Air Volume 1 Effective Throw

L/s cfm Pa in. w.g. Pa in. w.g. Model No. RTD9−65 FD9−65
470 1000 10 0.04 7 0.03 L/s cfm m ft. m ft.
565 1200 10 0.04 15 0.06 470 1000 3−5 10 − 17 5−6 15 − 20
660 1400 10 0.04 22 0.09 565 1200 3−5 11 − 18 5−7 16 − 22
755 1600 10 0.04 30 0.12 660 1400 4−6 12 − 19 5−7 17 − 24
850 1800 12 0.05 37 0.15 755 1600 4−6 12 − 20 5−8 18 − 25
945 2000 12 0.05 45 0.18 850 1800 4−6 13 − 21 6−9 20 − 28
1040 2200 12 0.05 50 0.20 945 2000 4−7 14 − 23 6−9 21 − 29
1130 2400 12 0.05 55 0.22 1040 2200 5−8 16 − 25 7−9 22 − 30
1 Effective throw based on terminal velocities of 23 m per minute ( 75 ft. per minute).

CEILING DIFFUSERS AIR RESISTANCE


RTD9−65 Step-Down Diffuser
FD9−65 Flush
Air Volume 2 Ends 1 Side & Diffuser
Open 2 Ends Open All Ends & Sides Open

L/s cfm Pa in. w.g. Pa in. w.g. Pa in. w.g. Pa in. w.g.
470 1000 47 0.19 40 0.16 35 0.14 35 0.14
565 1200 62 0.25 50 0.20 42 0.17 42 0.17
660 1400 82 0.33 65 0.26 50 0.20 50 0.20
755 1600 107 0.43 80 0.32 50 0.20 50 0.24
850 1800 139 0.56 99 0.40 75 0.30 75 0.30
945 2000 182 0.73 124 0.50 90 0.36 90 0.36
1040 2200 236 0.95 157 0.63 109 0.44 109 0.44

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 13


ELECTRICAL/ELECTRIC HEAT DATA 10.5 − 17.5 kW (3 − 5 Ton)
KHA036S KHA048S KHA060S
Voltage − 50hz 380/420V−3ph 380/420V−3ph 380/420V−3ph
Compressor Rated Load Amps 5.4 6.1 7.8
Locked Rotor Amps 38 43 51.5
Outdoor Fan Full Load Amps 1.1 1.1 1.3
Motor
Locked Rotor Amps 2.2 2.2 2.4
Power W (Horsepower) (1) 561 (0.75) (1) 561 (0.75) (1) 561 (0.75)
Exhaust
Fan Full Load Amps 2.2 2.2 2.2
Locked Rotor Amps 3.4 3.4 3.4
Indoor Blower kW (Horsepower) 1.5 (2) 1.5 (2) 1.5 (2)
Motor
Full Load Amps 3.5 3.5 3.5
Locked Rotor Amps 16.2 16.2 16.2
1 Maximum Unit Only 15 15 20
Overcurrent
Protection Unit with 5.7 kW 25 25 30
3 electric
heat
no exhaust fan 11.5 kW 35 35 35
17.2 kW −−− −−− 45
1 Maximum Unit with exhaust fan 15 20 20
Overcurrent
Protection Unit with 5.7 kW 25 25 30
3 electric
heat
and exhaust fan 11.5 kW 35 35 40
17.2 kW −−− −−− 50
2 Minimum Unit Only 12 13 15
Circuit
Ampacity Unit with 5.7 kW 22 23 25
3 electric
heat
no exhaust fan 11.5 kW 32 32 35
17.2 kW −−− −−− 45
2 Minimum Unit with exhaust fan 14 15 17
Circuit
Ampacity Unit with 5.7 kW 24 25 27
3 electric
heat
and exhaust fan 11.5 kW 34 35 37
17.2 kW −−− −−− 47
Unit Fuse Block Unit Only 18W06 18W06 18W07
with exhaust fans 18W06 18W07 18W07
Disconnect Standard Access − 0 kW 20W17 20W17 20W17
Hinged Access − 0 kW 20W23 20W23 20W23
Standard Access − 5.7−17.2 kW 20W15 20W15 20W15
Hinged Access − 5.7−17.2 kW 20W21 20W21 20W21
NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage.
1 Heating, Air Conditioning, Refrigeration type breaker or fuse.
2 Refertolocalelectricalcodestodeterminewire,fuseanddisconnectsizerequirements.
3 Nominal kW based on 420V−3ph−50hz.

ELECTRIC HEAT CAPACITIES


5.7 kW 11.5 kW 17.2 kW
Input
Voltage kW Btuh kW Btuh kW Btuh
No of Steps input Output No of Steps input Output No of Steps input Output
380 1 4.7 16,100 1 9.4 32,100 1 14.1 48,200
400 1 5.2 17,800 1 10.4 35,500 1 15.6 53,300
420 1 5.7 19,500 1 11.5 39,300 1 17.2 58,800

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 14


UNIT CLEARANCES − mm (INCHES)

OUTDOOR AIR B
HOOD

A B C D Top
1 Unit Clearance
mm in. mm in. mm in. mm in. Clearance

Service Clearance 914 36 914 36 934 36 914 36


Unobstructed
Minimum Operation Clearance 914 36 914 36 914 36 914 36
NOTE − Entire perimeter of unit base requires support when elevated above the mounting surface.
1 Service Clearance − Required for removal of serviceable parts.
Minimum Operation Clearance − Required clearance for proper unit operation.

OUTDOOR SOUND DATA


Octave Band Sound Power Levels dBA, re 10−12 Watts Sound
1
Unit Operating Rating
Center Frequency − HZ
Model No. Mode Number
125 250 500 1000 2000 4000 8000 (dB)
Cooling 63 66 70 71 68 62 53 75
036 and 048
Heating 63 66 71 70 68 62 54 75
Cooling 67 72 77 76 73 68 61 82
060
Heating 70 72 77 76 73 69 60 82
Note The octave power sound data does not include tonal correction.
1 Tested according to ARI Standard 270-95 test conditions and ANSI Standard S1.32-1981.

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 15


OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − FIElD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT

C0STAT02AE1L
Intuitive Touchscreen Interface − Two Stage Heating / Two Stage Cooling Conventional or
Heat Pump − Seven Day Programmable − Four Time Periods/Day − Economizer Output − Title 24
Compliant − ENERGY STAR® Qualified − Backlit Display − Automatic Changeover

Sensors For Touchscreen Thermostat


1 Remote non−adjustable wall mount 20k temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN01AE1−
1 Remote non−adjustable wall mount 10k averaging temperature sensor . . . . . . . . . . . . . . . . . . . . . C0SNZN73AE1−
1 Remote non−adjustable duct mount temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNDC00AE1−

Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR03AE1−

Accessories For Touchscreen Thermostat

Locking cover (clear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC15AE1−


1 Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1)
C0SNZN01AE1−, (2) C0SNZN73AE1−, (2) C0SNZN01AE1− and (1) C0SNZN73AE1−, (4)
C0SNZN01AE1−, (3) C0SNZN01AE1− and (2) C0SNZN73AE1.

DIGITAL NON−PROGRAMMABLE THERMOSTATS

Intuitive Interface − Automatic Changeover − Simple Up and Down Temperature Control

Two−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT10AE1L

Sensor For Digital Non−Programmable Thermostats Above

Remote wall mounted temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN00AE1−

Intuitive Interface − Automatic Changeover − Backlit Display − Simple Up and Down Temperature
Control

One−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT12AE1L

Sensor For Digital Non−Programmable Thermostats Above

Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNSR04AE1−

Accessories For Digital Non−Programmable Thermostats Above

Optional wall mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC17AE1−

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 16


WEIGHT DATA
Model Number Net Shipping
Base Maximum Base Maximum
kg lbs. kg lbs. kg lbs. kg lbs.
036 243 535 293 647 270 595 325 716
048 253 557 303 669 280 617 335 738
060 303 667 349 770 330 727 382 842
Base Unit − The unit with NO OPTIONS.
Maximum Unit − The unit with ALL OPTIONS Installed (Economizer, etc.)

OPTIONs / ACCESSORIES
Shipping Weights
kg lbs.
ECONOMIZER / OUTDOOR AIR
Economizer
Economizer, Includes Outdoor Air Hood and T1ECON30A−1 56 123
Barometric Relief Dampers with Hood
T1ECON30N−1 64 142
ELECTRIC HEAT
Electric Heat 5.7 kW − T1EH0075AN1 14 31
11.5 kW − T1EH0150AN1 14 31
17.2 kW − T1EH0225AN1 16 35
OUTDOOR AIR
Outdoor Air Dampers
Outdoor Air Damper Motorized Kit T1DAMP11A−1 12 25
T1DAMP11N−1 14 29
Damper Section Manual T1DAMP21AN1 9 18
POWER EXHAUST FANS
Standard Static T1PWRE10A−1 17 35
T1PWER10N−1 19 39
ROOF CURBS − DOWN−FLOW
Cliplock 1000
203 mm (8 in.) height T1CURB23AN1 35 78
356 mm (14 in.) height T1CURB20AN1 44 96
457 mm (18 in.) height T1CURB21AN1 49 108
610 mm (24 in.) height T1CURB22AN1 57 126
Hinged
203 mm (8 in.) height T1CURB30AN1 35 78
457 mm (18 in.) height T1CURB32AN1 49 108
610 mm (24 in.) height T1CURB33AN1 57 126
Standard
356 mm (14 in.) height T1CURB10AN1 44 96
CEILING DIFFUSERS
Step−Down RTD9−65 30 67
Flush FD9−65 17 37
Transitions (Supply and Return) T1TRAN10AN1 10 22

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 17


DIMENSIONS − MM (INCHES)
CORNER WEIGHTS CENTER OF GRAVITY
Model
No. AA BB CC DD EE FF
Base Max. Base Max. Base Max. Base Max. Base Max. Base Max.
kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. mm in. mm in. mm in. mm in.
036 42 93 53 116 51 112 60 132 82 181 96 212 68 149 85 187 978 38−1/2 1016 40 457 18 457 18
048 44 96 55 120 53 117 62 136 86 188 100 219 71 155 88 194 978 38−1/2 1016 40 457 18 457 18
060 52 115 63 138 64 140 71 157 103 226 115 252 84 166 101 223 978 38−1/2 1016 40 457 18 457 18
Base Unit − The unit with standard heat exchanger NO OPTIONS.
Max. Unit − The unit with ALL OPTIONS Installed. (Economizer, etc.)
143
279 413 457
(5−5/8)
(11) (16−1/4) (18)

AA BB
178 (7) BOTTOM 102 (5)
RETURN
AIR
OPENING
508
BOTTOM (20)
737
SUPPLY
(29)
AIR
1192 (47 ) OPENING
BASE CENTER
OF 654
GRAVITY (25−3/4)
FF 241
168 (9−1/2)
(6−5/8)
DD CC
673 EE
(26−1/2)
BOTTOM BOTTOM POWER ENTRY
CONDENSATE OUTLET 76 X 203 (3 X 8)
TOP VIEW (Base)
1143 2115
(45) (83−1/4)
987 (38−7/8) 036−048

ELECTRICAL
899 (35−3/8) 036−048

INLET
1191 (46−7/8) 060

1102 (43−3/8) 060

CONDENSATE
OUTLET
(EITHER SIDE)

140
25 (1) (5−1/2) 25 (1)
89 (3−1/2)

1192 (47) 673 686


BASE (26−1/2) (27)
LIFTING HOLES
(For rigging) 2165 (85−1/4)
END VIEW BASE
SIDE VIEW
495 467
(19−1/2) (18−3/8) 279 51 (2)
(11)

737
(29)
508
(20)

FORKLIFT SLOTS HORIZONTAL 140 HORIZONTAL 140


(Front, Back and SUPPLY AIR (5−1/2) RETURN AIR (5−1/2)
Blower End) OPENING OPENING
(Without Economizer)
BACK VIEW

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 18


ACCESSORY DIMENSIONS − MM (INCHES)

OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Down−Flow Applications) 298 (11−3/4) 036−048
400 (15−3/4) 060

OUTDOOR AIR HOOD


(Furnished with Economizer)

305
(12)

BAROMETRIC RELIEF HOOD


(Furnished with Economizer)

SIDE VIEW

OUTDOOR AIR HOOD FOR ECONOMIZER BAROMETRIC RELIEF HOOD FOR ECONOMIZER
(Furnished) (Furnished)

32 64
(1−1/4) (2−1/2)
305
(12)
C 775
838
(33) (30−1/2)
32
(1−1/4)
64
(2−1/2)

38 19 (3/4)
(1−1/2)
B
A

25 (1)
10 (3/8)

Model A B C
No.
mm in. mm in. mm in.
036, 048 489 19−1/4 330 13 298 11−3/4
060 591 23−1/4 432 17 400 15−3/4

OUTDOOR AIR DAMPER HOOD DETAIL FOR OPTIONAL MANUAL OR MOTORIZED OUTDOOR AIR DAMPERS
(Down−Flow or Horizontal Applications)

889
267 OPTIONAL (35)
(10−1/2) OUTDOOR
AIR DAMPERS
AND PANEL
343
(13−1/2)

OUTDOOR AIR
DAMPER HOOD
889 (35)
036−048

1092 (43)
OUTDOOR AIR 060
DAMPER HOOD
(Furnished)
SIDE VIEW 419
(16−1/2) 267
(10−1/2)

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 19


ACCESSORY DIMENSIONS − mm (INCHES)

OUTDOOR AIR HOOD DETAIL FOR OPTIONAL ECONOMIZER AND BAROMETRIC RELIEF DAMPERS
(Horizontal Applications)
ECONOMIZER DAMPERS

Barometric Relief Hood


and Dampers
RETURN AIR DUCT
(Field Fabricated − Must be sized to
accommodate Barometric Relief
Hood and Return Air Requirements)
RETURN AIR
SUPPLY AIR DUCT DUCT TRANSITION
BAROMETRIC RELIEF HOOD DIMENSIONS
(Field Provided) (Field fabricated and
Width − 902 mm (35−1/2 in.)
SUPPLY installed on unit) RETURN Height − 533 mm (21 in.) (036, 048)
AIR AIR 635 (25 in.) (060)
OUTLET INLET See previous page for details.

TOP VIEW
OUTDOOR AIR HOOD
(Furnished with Economizer)

495 743 B
(29−1/4) BAROMETRIC RELIEF HOOD
(19−1/2)
(Shipped with Economizer and
Field Installed on Field fabricated
Return Air Duct)

OUTDOOR 22
This opening AIR (7/8)
not used in
Horizontal
Applications
with 57
HORIZONTAL 508 Economizer HORIZONTAL
SUPPLY AIR RETURN AIR (2−1/4) A 57
OPENING (20) OPENING 773
(30−7/16) (2−1/4)
EXHAUST
AIR
22
(7/8)
127 (5) RETURN AIR RETURN AIR DUCT INLET UNIT RETURN AIR DUCT
DUCT TRANSITION (Field Fabricated − Must be sized to OPENING WITH ECONOMIZER
(Field fabricated and accommodate Barometric Relief INSTALLED
installed on unit) Hood and Return Air Requirements)
BACK VIEW END VIEW

NOTE − Return Air Duct and Transition must be supported.

Model A B
No.
mm in. mm in.
036, 048 476 18−3/4 298 11−3/4
060 572 22−1/2 400 15−3/4

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 20


ACCESSORY DIMENSIONS − MM (INCHES)

CLIPLOCK 1000 ROOF CURBS − DOUBLE DUCT OPENING


46
(1−13/16)

1054
537 (41−1/2)
1934 (21−1/8)
(76−1/8)
962
2026 (37−7/8)
(79−3/4)

486
(19−1/8) 203 (8)
356 (14)
457 (18)
384 610 (24)
SUPPLY
(15−1/8) OPENING

321
(12−5/8)

46
(1−13/16) RETURN
OPENING

813
(32)

NOTE  Roof deck may be omitted within confines of curb.

TYPICAL FLASHING DETAIL FOR ROOF CURB DETAIL ROOF CURB


46
BASE BOTTOM PACKAGED (1−13/16)
UNIT

13 (1/2)
FIBERGLASS
INSULATION COUNTER FLASHING
(Furnished) (Field Supplied)
FACTORY INSTALLED
NAILER STRIP PERIMETER WOOD
(Furnished) NAILER STRIP
CANT STRIP 203 (8)
ROOF CURB
(Field Supplied) 356 (14)
(Extends around entire
perimeter of unit) 457 (18)
ROOFING 610 (24)
MATERIAL
RIGID INSULATION
(Field Supplied)
46
(1−13/16)

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 21


ACCESSORY DIMENSIONS − MM (INCHES)

HINGED ROOF CURBS − DOUBLE DUCT OPENING


46
(1−13/16)

1054
537 (41−1/2)
(21−1/8)
1934
(76−1/8)
962
2026 (37−7/8)
(79−3/4)
486
(19−1/8)
203 (8)
457 (18)
384 610 (24)
(15−1/8) SUPPLY
OPENING
321
(12−5/8)

46
(1−13/16) RETURN
OPENING

813
(32)

NOTE  Roof deck may be omitted within confines of curb.

TYPICAL FLASHING DETAIL FOR ROOF CURB DETAIL ROOF CURB


46
BASE BOTTOM PACKAGED (1−13/16)
UNIT

13 (1/2)
FIBERGLASS
INSULATION COUNTER FLASHING
(Furnished) (Field Supplied)
FACTORY INSTALLED
NAILER STRIP PERIMETER WOOD
(Furnished) NAILER STRIP
CANT STRIP 203 (8)
ROOF CURB
(Field Supplied) 457 (18)
(Extends around entire
perimeter of unit) 610 (24)
ROOFING
MATERIAL
RIGID INSULATION
(Field Supplied)
46
(1−13/16)

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 22


ACCESSORY DIMENSIONS − MM (INCHES)

STANDARD ROOF CURBS − DOUBLE DUCT OPENING


46
(1−13/16)

1054
537 (41−1/2)
76−1/8 (21−1/8)
(1934)
962
2026 (37−7/8)
(79−3/4)
486
(19−1/8) 346
(14)
384 SUPPLY
(15−1/8) OPENING
321
(12−5/8)

46
(1−13/16) RETURN
OPENING

813
(32)

NOTE  Roof deck may be omitted within confines of curb.

TYPICAL FLASHING DETAIL FOR ROOF CURB DETAIL ROOF CURB


46
BASE BOTTOM (1−13/16)
PACKAGED
UNIT

25 (1)
FIBERGLASS
INSULATION COUNTER FLASHING
(Furnished) (Field Supplied)
FACTORY INSTALLED
NAILER STRIP PERIMETER WOOD
(Furnished) NAILER STRIP
CANT STRIP
ROOF CURB (Field Supplied)
(Extends around entire 356 (14)
perimeter of unit) ROOFING
MATERIAL

RIGID INSULATION
(Field Supplied)

51 (2)

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 23


ACCESSORY DIMENSIONS − INCHES (MM)

TRANSITIONS
T1TRAN10AN−1 − FOR 457 MM (18 INCH) DUCT

305
(12) 800
(31−1/2)

203 (8)

38 mm (1−1/2 inch) T1TRAN10AN−1

RETURN TRANSITION

321 486
(12−5/8) (19−1/8)
OPENING
RETURN

SUPPLY 521
OPENING (21−1/8) T1TRAN10AN−1 − FOR 457 MM (18 INCH) DUCT
813
(32)
470 521
(18−1/2) (20−1/2)

203 (8)

38 mm (1−1/2 inch) T1TRAN10AN−1

SUPPLY TRANSITION

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 24


ACCESSORY DIMENSIONS − MM (INCHES)

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS


STEP-DOWN CEILING DIFFUSER FLUSH CEILING DIFFUSER

G H D G H D
E E
F H F H

G C G C

51 (2) 51 (2)

L A A
B
B
J
K

Model Number RTD9−65 Model Number FD9−65


mm 1159 mm 1159
A A
in. 47−5/8 in. 47−5/8
in. 23−5/8 mm 600
B B
mm 600 in. 23−5/8
mm 289 mm 343
C C
in. 11−3/8 in. 13−1/2
mm 546 mm 533
D D
in. 21−1/2 in. 21
mm 1156 mm 1143
E E
in. 45−1/2 in. 45
mm 572 mm 572
F F
in. 22−1/2 in. 22−1/2
mm 292 mm 286
G G
in. 11−1/2 in. 11−1/4
mm 273 mm 267
H H
in. 10−3/4 in. 10−1/2
mm 1156 mm 457 round
J Duct Size
in. 45−1/2 in. 18 round
mm 546
K
in. 21−1/2
mm 181
L
in. 7−1/8
mm 457 round
Duct Size
in. 18 round

LandmarkE Packaged Heat Pump 10.5 to 17.5 kW (3 to 5 Ton) − 50hz / Page 25


Visit us at www.lennox.com
For the latest technical information, www.lennoxcommercial.com
Contact us at 1−800−4−LENNOX

NOTE − Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. ©2008 Lennox Industries Inc.