Configuración de Relé - SE N1 - Celda Principal
Configuración de Relé - SE N1 - Celda Principal
Properties
Customer : MERCADO MAYORISTA
Project : PRUEBAS
Switchboard :
Cubicle :
Print date : 27/11/22
SE 1_LLEGADA (23/11/2022) Page 2
Program logic
Circuit breaker control : No
Logic discrimination : No
Set up outputs
Used Shunt coil Undervoltage coil Impulsed mode
O1 Yes X X
O2 Yes X
O3 Yes X
O4 Yes X
O11 - - - -
O12 - - - -
O13 - - - -
O14 - - - -
SE 1_LLEGADA (23/11/2022) Page 4
General characteristics
Network frequency : 60 Hz
Setting group : A
Remote setting enabled : No
Sepam working language : Customized language
CT rating : LPCT
Number of CTs : I1, I2, I3
Rated current (In) : 100 A
Base current (Ib) : 100 A
Integration period : 5 mn
Residual current : 3I sum
Rated residual current (In0) : 100 A
Number of periods which are memorised before the fault recording trigger : 36 Periods
SE 1_LLEGADA (23/11/2022) Page 5
Setting group A
Tripping curve : IEC EIT /C
Threshold current : 45 A
Delay : 600 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Icc current : 6300 A
Setting group B
Tripping curve : Definite time
Threshold current : 335 A
Delay : 90 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Icc current : 6300 A
Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Pulse
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L1, L9
SE 1_LLEGADA (23/11/2022) Page 6
Setting group A
Tripping curve : Definite time
Threshold current : 315 A
Delay : 90 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Icc current : 6300 A
Setting group B
Tripping curve : Definite time
Threshold current : 1400 A
Delay : 50 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Icc current : 6300 A
Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Pulse
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L2, L9
SE 1_LLEGADA (23/11/2022) Page 7
Setting group A
Tripping curve : IEC EIT /C
Threshold current : 40 A
Delay : 500 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Setting group B
Tripping curve : Definite time
Threshold current : 304 A
Delay : 90 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Pulse
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L3, L9
SE 1_LLEGADA (23/11/2022) Page 8
Setting group A
Tripping curve : Definite time
Threshold current : 304 A
Delay : 90 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Setting group B
Tripping curve : Definite time
Threshold current : 600 A
Delay : 50 ms
Timer hold curve : Definite time
Timer hold delay : 0 ms
Harmonic 2 restraint : Yes
Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Pulse
Latching : Yes
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L4, L9
SE 1_LLEGADA (23/11/2022) Page 9
Setting group
Tripping curve : Definite time
Threshold current : 60 % of Ib
Delay : 3000 ms
Tripping behavior
Output O1 - Type : Shunt coil
Output O1 - Mode: Pulse
Latching : No
Activate output O1 : Yes
Trigger fault recording : With
Activate indicators : L9
SE 1_LLEGADA (23/11/2022) Page 10