119 ST Andrews Avenue-Proposed Roof Structure-S01

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

STEEL SCHEDULE

REF SIZE GRADE STEEL BEARING PLATE

B1 UC 152*152*44 S275 P1: 400*100*20

C1 SHS 90*90*5 S275 -

T1 T1
TIMBER SCHEDULE

PRR1(PITCHED ROOF RAFTERS) 50*175 C24 @400 C/C

PRR1
T2 T2 T2 T2
T1 T1

14
15
FRJ1 (FLAT ROOF JOISTS) 50*150 C24 @400 C/C

16
TRIMMER T1 DOUBLE 50*175 C24 TIMBER
C1 17 18 19 20 21 22 23 24 25 B1
P1 TRIMMER T2 DOUBLE 50*175 C24 TIMBER

FRJ1
ALL MASONRY BLOCKWORK TO BE 7.3N GRADE. M6/ (ii) MORTAR.
DW

VERTICAL MOVEMENT JOINT FOR BLOCKWORK MASONRY TO BE INTRODUCED AT 6m SPACING.


ALL EXISTING INTERNAL SOLID MASONRY PARTITION WALLS ARE ASSUMED TO BE LOAD BEARING.
ALL NEW INTERNAL PARTITION WALLS TO BE BUILT IN TIMBER STUD.

DJ DOUBLE UP TIMBER BOLTED TOGETHER WITH M12 @ 450 C/C


PROVIDE 2NO. TIMBER JOISTS BOLTED TOGETHER WITH M12 BOLTS AT 600C/C UNDER
ALL PARTITIONS

ALL STRUCTURE SETTING OUTS, DIMENSIONS, AND LEVELS TO BE CONFIRMED ON SITE


PROPOSED ROOF STRUCTURE

GENERAL NOTES: FOR STEEL WORK CONNECTION DETAIL REFER TO DRAWING 03

ALL DIMENSIONS ARE IN MILLIMETRES.


DO NOT SCALE THIS DRAWING, WORK TO FIGURED DIMENSIONS ONLY.
THE CONTRACTOR IS RESPONSIBLE FOR THE ACCURACY OF THE SETTING-OUT ON SITE AND THE FABRICATION OF MATERIALS PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL CHECK ALL LEVELS AND DIMENSIONS ON
SITE, ANY ERRORS OR OMISSIONS ARE TO BE REPORTED AT ONCE TO THE STRUCTURAL ENGINEER.
DRAWINGS SHALL BE REFERRED TO FOR STRUCTURAL ENGINEER WORK ONLY, UNLESS OTHERWISE STATED, AND READ IN CONJUNCTION WITH ALL OTHER RELEVANT ENGINEERING, ARCHITECTURAL, SERVICES ENGINEERS
AND SUB-CONTRACTORS AND ANY OTHER RELEVANT CONTRACT DOCUMENTATION.
MATERIALS AND WORKMANSHIP SHALL NOT BE INFERIOR TO THE REQUIREMENTS OF THE RELEVANT BRITISH STANDARDS, CODES OF PRACTICE, BUILDING REGULATIONS OR OTHER RELEVANT DOCUMENTATION REFERRED
TO IN THE SPECIFICATION.

HEALTH AND SAFETY:


AS PART OF THE DESIGN PROCESS THE FOLLOWING RISKS HAVE BEEN IDENTIFIED FOR THE CONTRACTOR.
ELEMENTS DESIGNED IN THESE CALCULATIONS ARE HEAVIER THAN THE MANUAL HANDLING LIMIT OF 25 KG AND THEREFORE THE CONTRACTOR WILL HAVE TO ASSESS THE LIFTING REQUIREMENTS.
CONTRACTOR TO BE RESPONSIBLE TO ENSURE THAT ALL WORKS ARE CARRIED OUT IN A SAFE AND WORKMANLIKE MANNER, TO PROVIDE SATISFACTORY TEMPORARY PROPPING TO MAINTAIN THE STABILITY OF ALL THE Notes:

EXISTING STRUCTURAL ELEMENTS THROUGHOUT THE DURATION OF THE PROPOSED WORKS. *Do not scale from this drawing. *This layout and the information
contained within is the property IAW
ENSURE GAP BETWEEN NEW STEEL BEAMS AND EXISTING MASONRY IS PACKED TIGHT. SOME COSMETIC CRACKING MAY OCCUR AFTER TEMPORARY PROPPING IS TAKEN AWAY AS THE BEAM DEFLECTS SLIGHTLY UNDER *All dimensions, levels and setting Consulting Engineers and may not be
outs to be checked on site. used, transmitted or reproduced
THE NEW LOADING. MAKE GOOD ANY CRACKING. in whole or in part without prior written
*This layout should be used in
consternation from IAW Consulting
ANY WALLS THAT ARE SUPPORTING STEELWORK THAT ARE FOUND NOT TO BE LOAD BEARING MASONRY OR OF POOR CONSTRUCTION SHOULD BE REPORTED TO THE ENGINEER. conjunction with other the
Engineers.
documentation of the same revision.
ADEQUATE TEMPORARY WORKS ARRANGEMENT MUST BE INTRODUCED PRIOR TO DEMOLITION AND CONSTRUCTION WORKS BEGIN.

CIVIL & STRUCTURAL


STEELWORK:
ALL STEEL WORK TO BE S275 GRADE. Kemp House 160
City Road, London
STEELWORK CONTRACTOR MUST VERIFY ALL DIMENSIONS ON SITE BEFORE COMMENCING ANY WORK OR MAKING ANY SHOP DRAWINGS. NO DIMENSIONS TO BE SCALED FROM DRAWINGS. ANY DISCREPANCIES MUST BE EC1V 2NX
REPORTED TO THE ENGINEER. TEL: 07792450933

ALL STEEL BEAMS WHERE SEATED ON MASONRY TO HAVE CONCRETE PADSTONES BENEATH BEAM ENDS. PADSTONES BASED ON ENGINEERING CALCULATION AND TO MATCH WIDTH OF WALL. CONCRETE TO ALL PAD
STONES TO HAVE A MINIMUM STRENGTH OF 30 N/MM2. STEEL BEAMS TO HAVE A MINIMUM END BEARING OF 150MM WHERE SPAN OF BEAM IS PARALLEL TO WALL UNLESS NOTED OTHERWISE ON THE DETAILS. I A Waseem
BE, MSc, CEng MICE
STEELWORK TO BE MILD STEEL GRADE S275, WIRE BRUSHED TO REMOVE ALL OIL, RUST, MILL SCALE ETC. AND PAINTED WITH TWO COATS OF ZINC PHOSPHATE OR SIMILAR APPROVED. CONSULTING ENGINEERS
NEW STEEL BEAMS TO BE ENCASED IN 12.5MM GYPROC FIRELINE BOARD WITH STAGGERED JOINTS, GYPROC FIRECASE OR PAINTED IN NULLIFIRE S OR SIMILAR INTUMESCENT PAINT TO PROVIDE 1/2 HOUR FIRE RESISTANCE
Project: Drawing Title:
AS AGREED WITH BUILDING CONTROL. ALL FIRE PROTECTION TO BE INSTALLED AS DETAILED BY SPECIALIST MANUFACTURER.
ALL STEEL WORK CONNECTIONS TO HAVE 4 NO. M16(8.8)BOLTS. UNO.
BEAM B1 TO COLUMN C1 CONNECTIONS TO BE AS PER DETAIL 03 119 ST ANDREWS PROPOSED ROOF
AVENUE STRUCTURE

STRAPPING FOR PITCHED ROOF:


GABLE WALLS SHOULD BE STRAPPED TO ROOFS AT 2m CENTERS. ALL EXTERNAL WALLS RUNNING PARALLEL TO ROOF RAFTERS TO BE RESTRAINED AT ROOF LEVEL USING 1000mm x 30mm x 5mm GALVANIZED MILD STEEL Date: JULY 2021 Dwg No: 01
HORIZONTAL STRAPS OR OTHER APPROVED TO BSEN 845-1 BUILT INTO WALLS AT 2000mm CENTERS AND TO BE TAKEN ACROSS MINIMUM 3 RAFTERS AND SCREW FIXED. PROVIDE SOLID NOGGINS BETWEEN RAFTERS AT
Scale: 1:50 @A2 Drawn By: VAA
STRAP POSITIONS.
ALL WALL PLATES TO BE 100mm x 50mm FIXED TO INNER SKIN OF CAVITY WALL USING 30mm x 5mm x 1000mm GALVANIZED METAL STRAPS OR OTHER APPROVED TO BSEN 845-1 AT MAXIMUM 2m CENTERS. Checked by: IAW Revision: -
0 1 2 3 4 5 6 7 8 9 10M