22mm Ø

RSB Sp. @
44cm O.C.

10mm Ø HOR. BAR SP. 30cm O.C.

See Bar 22mm Ø


Detail RSB Sp. @
44cm O.C.

22mm Ø RSB
10mm Ø HOR. BAR SP. 30cm O.C. Sp. @ 22cm
O.C.

12mm Ø Vert. 10mm Ø BAR


Bar sp. 30cm SP. 30cm O.C.
O.C.

22mm Ø Bar sp. @


13cm O.C. (EVERY
OTHER BAR CUT @
B/2)

R=27cm
10mm Ø HOR. BAR SP. 30cm O.C.

Bar Detail
Section

5.00mINVERTED-T Retaining Wall Detail


SCALE 1 : 50 MTS.

22mm Ø 10mm Ø HOR. BAR SP. 30cm O.C.


RSB Sp. @
36cm O.C.

See Bar Detail

22mm Ø 12mm Ø Vert. Bar sp. 30cm O.C.


RSB Sp. @
36cm O.C.

10mm Ø HOR. BAR SP. 30cm O.C.


22mm Ø RSB
Sp. @ 18cm 10mm Ø BAR SP. 30cm O.C.
O.C.

22mm Ø Bar sp. @


11cm O.C. (EVERY
OTHER BAR CUT @
B/2)

R=34cm
10mm Ø HOR. BAR SP. 30cm O.C.

Bar Detail Section

5.50m INVERTED-T Retaining Wall Detail


SCALE 1 : 50 MTS.
REV APPROVED
DATE NATURE OF REVISION BY CHECKED RECOM.
NO NIA

GENERAL NOTES-1: GENERAL NOTES-2:


All Dimensions are in centimeters unless A. IN THE INTERPRETATION OF THIS DRAWING INDICATED DIMENSIONS SHALL GOVERN
otherwise specified. AND DISTANCES OR SIZES SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES.
Minimum concrete protective covering
between reinforcement and surface of B. BARS OF REINFORCED CONCRETE EXPOSED TO THE WEATHER SHALL PREPARABLY
vertical wall shall be 4cms. and 7.5cms. for BE PROTECTED WITH AT LEAST 38mm AND NO CASE LESS THAN 25mm CONCRETE.
the footing. THIS PROVISION MAYBE WAVED WHEN ADEQUATE WATERPROOFING IS PROVIDED.
All exposed edges of the concrete shall
be rounded or chamfered. C. ALL REINFORCING BAR SHALL BE DEFORMED (C0NFORMING TO ASTM A-615) AND SHALL
Lapping of bars shall be 24D for BE GRADE 40 (Fy = 275 MPa) FOR 20 mmØ BARS & BELOW 25mmØ AND ABOVE, GRADE
deformed bars and 48D for plain bars. 60 (Fy = 414 MPa) SHALL BE USED.
Heel of retaining wall will be omitted if
two walls are placed toe to toe and D. ALL CONCRETE WORK SHALL BE DONE IN ACCORDANCE WITH THE ACI-318-89 BUILDING
symmetrical about a vertical axis. CODE FOR REINFORCED CONCRETE AND ALL STRUCTURAL STEEL WORK IN
All concrete shall be 3,000 psi. ACCORDANCE WITH THE ASEP HANDBOOK OF STRUCTURAL STEEL SHAPES AND
SECTIONS AND A.I.S.C. SPECIFICATION. LATEST EDITION IN SO FAR AS THEY DO NOT DRAFTING DESIGN
DESIGN CRITERIA: CONFLICT WITH THEV LOCAL BUILDING CODE REQUIREMENTS.
Design for 1 foot level surcharge. For CADD : DESIGNED :
greater surcharge special design shall be E. CONTRACTOR SHALL COORDINATE WITH THE AR, ME, SE, EE, AND OTHER UTILITY AND
EQUIPMENT PLANS FOR THE EXACT SIZE AND LOCATION OF HOLES THRU FLOOR
required. REVIEWED : REVIEWED :
SLABS AND WALLS.
Assumed angle of internal friction of
soil, φ RECOMMENDED BY :
F. ALL CONCRETE SHALL BE 3000 PSI CONCRETE UNLESS OTHERWISE SPECIFIED
wt. of earth backfill= 100 PCF
ϥ
ϥ ALL BARS WHEN REQUIRED SHALL BE BENT COLD.
HOOKS OR BENDS SHALL HAVE THE FOLLOWING
WORKING STRESSES:
DIMENSIONS.
RECOMMENDING APPROVAL :

APPROVED :

SHEET 1 OF 7

C:\Users\ASUS\Documents\Downloads\Repair_seguinan_dam.dwg, 19/06/2024 4:04:28 pm, DWG To PDF.pc3