A B C D E

ELECTRICAL SYMBOLS:
CEILING LIGHT REFER TO SCHEDULE
E E A E EC CA E
OUTLET
F MANUAL CALL POINT FOR FIRE ALARM
12000 OF LIGHTING
FIXTURES AND LAMPS VIBRATING BELL OUTLET, 230mm
CEILING LIGHT B DIAMETER, 230V, 60HZ TO BE INSTALLED 1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISION OF THE LATEST
3000 3000 3000 3000 OUTLET @ 300mm BELOW CEILING LINE
EDITION OF THE PHILIPPINE ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES, RULES AND
Sa SINGLE POLE WALL SWITCH IN ONE

1
CEILING MOUNTED EXHAUST FAN (15
SWITCH PLATE (10 AMP., 230 VOLTS)
AMP., 230 VOLTS) REGULATIONS OF THE LOCAL GOVERNMENT AND WITH THE REQUIREMENTS OF THE LOCAL
2 SINGLE POLE WALL SWITCHES IN ONE
Sab SWITCH PLATE (10 AMP., 230 VOLTS) CONCEALED OR EMBEDDED CONDUIT POWER COMPANY.
RUN
LAUNDRY AND LAUNDRY AND LAUNDRY AND LAUNDRY AND 3 SINGLE POLE WALL SWITCHES IN ONE
CR DIRTY KITCHEN CR DIRTY KITCHEN CR DIRTY KITCHEN CR DIRTY KITCHEN Sabc SWITCH PLATE (10 AMP., 230 VOLTS)
CONCEALED OR EMBEDDED CONDUIT
RUN TO SWITCHES 2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL BE SINGLE-PHASE, 2-WIRE, 230V, 60
HERTZ, A.C
3000

Sg Sh Sg Sh Sg Sh Sg Sh 3w CIRCUIT HOMERUN
S THREE WAY SWITCH
a

a
AIRCON OUTLET DISTRIBUTION PANELBOARD
3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE
DUPLEX UNIVERSAL CONVENIENCE OUTLET,
FOR CONNECTION TO THE POWER COMPANY SERVICE POINT.
DINING

DINING

DINING

DINING
AREA M ELECTRIC SERVICE METER

AREA

AREA

AREA
Sdef Sdef Sdef Sdef GROUNDING TYPE, "WP" DENOTES

2 WEATHERPROOF OUTLET 20A, 250VOLTS


ELECTRIC SERVICE ENTRANCE
b

b
EL SINGLE CONVENIENCE OUTLET w/ 3W (2x1.5W),
220lm LED EMERGENCY LIGHT, ADJUSTABLE 4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF WIRE AND GALVANIZED RIGID STEEL
EL EL EL EL GROUNDING SYSTEM
LAMP HEADS ON SINGLE PRONG OUTLET
c b c b c b c b
CONDUIT TO BE USED SHALL BE 3.5mm²,THHN AND 15mm NOMINAL DIAMETER, RESPECTIVELY.
LIKEWISE ALL ELECTRICAL WIRES SHALL BE COLOR-CODED.
BEDROOM BEDROOM
3000

5. ALL LIGHTING CIRCUIT HOMERUNS AND CONVENIENCE OUTLETS SHALL BE WIRED WITH NOT LESS
SCHEDULE OF LIGHTING FIXTURES AND LAMPS:
a b b b b THAN 3.5 mm² IN SIZE.
BEDROOM BEDROOM 12W LED Round Panel Downlight, Diecast Aluminum, Powder
Coated, (Daylight) RECESSED MOUNTED
PB1A PB1B PB1C PB1D

3 6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION BOXES SHALL BE INSTALLED AT


Sabc Sabc Sabc Sabc

9W LED Round Panel Downlight, Diecast Aluminum, Powder Coated,


(Daylight) RECESSED MOUNTED CONVENIENT AND INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE NOT SHOWN ON THE
PLAN NOR MENTIONED IN THE SPECIFICATIONS.
1650

a a HALLWAY
a a
18W LED Square Panel Downlight, Diecast Aluminum, Powder
Coated, (Daylight) SURFACE MOUNTED
7. ALL NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE PROPERLY
350

OPEN SPACE/PARKING AREA 15W LED Square Panel Downlight, Outdoor Type, IP20, (Daylight)
SURFACE MOUNTED GROUNDED IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE.

GROUND FLOOR AND SECOND FLOOR 8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION
AND PURPOSE.
LIGHTING LAYOUT(TYPICAL) 9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES, TERMINATIONS AND OTHER
THIS SITE APPURTENANCES FOR THE ENTIRE ELECTRICAL INSTALLATION SHALL BE USED.

A B C D E COURT
10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING HEIGHTS ABOVE THE FINISHED
FLOOR LEVEL UNLESS NOTED IN THE PLAN.

a) WALL SWITCHES @ 1300mm


b) WALL CONVENIENCE OUTLETS @ 300 mm ABOVE FINISH FLOOR LINE
c) WALL FAN OUTLET @ CONVENIENT HEIGHT
12000

3000 3000 3000 3000 11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A
DULY REGISTERED ELECTRICAL ENGINEER.

NATIONAL HIGHWAY
1
LAUNDRY AND LAUNDRY AND LAUNDRY AND LAUNDRY AND
CR DIRTY KITCHEN CR DIRTY KITCHEN CR DIRTY KITCHEN CR DIRTY KITCHEN

CSU CANTEEN
3000

30cm above 30cm above 30cm above 30cm above


Counter Top Counter Top Counter Top Counter Top

CSU CARIG
DINING

DINING

DINING

DINING
AREA

AREA

AREA

AREA

2 BEDROOM BEDROOM
3000

TO CARIG HIGHWAY

TO REGIONAL OFFICES
BEDROOM
PB1A PB1B PB1C PB1D
1650

HALLWAY

3
VICINITY MAP
350

GROUND FLOOR AND SECOND FLOOR POWER


LAYOUT(TYPICAL)
ELECTRICAL ENGINEER: PROPOSED PROJECT TITLE APPROVED BY SHEET No.

PTR. No. :
PROPOSED 2-STOREY COMMERCIAL BUILDING
CELENE HELOISE C. MIGUEL E-1
PRC. REG. No.
OWNER
PLACE ISSUED : DATE ISSUED : LOCATION: CARIG, TUGUEGARAO CITY , CAGAYAN ELECTRICAL