INSTRUMENT

GENERAL
INSTRUMENT SPECIFICATION SHEET- 133

START UP VENT CONTROL VALVE


,,
TAG NUMBER 1-HV-106 (BOILER# 1)
2-HV-106 (BOILER# 2)

ITEM CODE 13300004


SERVICE START UP VENT CONTROL
LINE SIZE\ SCHEDULE\ MATERIAL 100 NB\ 20 MM THICK\ SA335 P22 (INLET)
VTC (OUTLET)
QUANTITY 2 NUMBERS

SERVICE CONDITIONS
FLUID\ STATE SUPERHEATED STEAM
FLOW- TPH MINIMUM 5.1\ NORMAL 25.8 \ MAXIMUM
28.4
INLET PRESSURE AT FLOW CONDITIONS--- 94.5 AT MINIMUM FLOW\ 93.5 AT NORMAL
KG/CM2G FLOW\ 92.5 AT MAXIMUM FLOW
PRESSURE AT LO-DB PLATE OUTLET - 1 KG/CM2G
DELTA P SHUTOFF - KG/CM2 - 108
TEMPERATURE OPERA TING - DEG C - 535
[ T�MPERATURE DESIGN - DEG C - 540
. PRESSURE DESIGN - KG/CM2G - 108
NOISE --- <85 DBAAT 1 METER
(USING LOW DB PLATES)
DISCHARGE TO -- ATMOSPHERE THROUGH SILENCER

BODY
TYPE GLOBE
BODY SIZE VTC
GUIDING VTC
END CONNECTIONS BUTTWELDED (REFER NOTE 1)
BODY RATING -- ANSI 250 0#�
BODY MATERIAL -- ASTM A217 GR WC9
BONNET TYPE --- STANDARD
GLAND PACKING MATERIAL --- VTC
GASKET MATERIAL VTC
LUBRICATOR\ ISOLATION VALVE -- NO
TRIM FORM -- PLUG AND SEAT
TRIM MATERIAL
PLUG & SEAT -- VTC
ANSI LEAKAGE CLASS -- V

ACTUATOR
TYPE -- DIAPHRAGM
MODEL -- VTC
SPRING RANGE --- VTC
ACTION REVERSE (AIR TO OPEN)
FAILURE POSITION STAYPUT/TENDS TO CLOSE

POSITIONER
AIR SUPPLY PRESSURE 4.5 KG/CM2 (MINIMUM AVAILABLE)
MODEL VTC
SIGNAL 0.2-1 KG/CM2
OUTPUT VTC
GAUGES 3 NUMBERS.

MADE CHKD APPD CLIENT: Intern usa DRAWING NO. DATE PAGE
BY BY BY Technical Group Pte Ltd 133-HR-CS- 04-JUNE- 8 OF
AB NVK AKS BOILER NO: PH0331/0332 31072 REV.1 2008 31
OPTIONS
INSTRUMENT SPECIFICATION SHEET- 133

AIR FILTER + GAUGE


MAKE - SHAVO NORGREN/FISHER SANMAR
,,
AIRLOCK --- REQUIRED
VALVE DATA
CV MINIMUM\ CV MAXIMUM --- VTC
CV NORMAL \ SELECTED CV --VTC
VALVE \ ACTUATOR MODEL - VTC
CHARACTERISTICS --- LINEAR
MAKE --- FISHER SANMAR/ MIL

NOTES-:
1) BUTT WELD DETAILS WILL BE FURNISHED DURING VALVE DRAWING APPROVAL STAGE
BY MECHANICAL ENGINEERING.
2) CONTROL VALVE SHALL BE SUPPLIED WITH ALL ACCESSORIES DULY FITTED, TUBED
USING SS TUBE & DOUBLE COMPRESSION SS FITTINGS.
3) CONTROL VALVE TO BE SUPPLIED WITH LO-dB PLATES, EXPANDERS/ REDUCERS.
4) DIFFERENTIAL PRESSURE DISTRIBUTION ACROSS CONTROL VALVE & LO-DB PLATES TO
BE DECIDED BY CONTROL VALVE VENDOR.
5) VTC - VENDOR TO CONFIRM.

MADE CHKD APPD CLIENT: Internusa DRAWING NO. DATE PAGE