Parallel 2
LOAD No. of MPP Trackers 2
CAN
PEC recommends that 5% Voltage drop is allowed in No. of Strings per MPPT 1+1
PV IN BATTERY GEN GRID
HM
any circuit installation , therefor 4mm² PV Cable is
acceptable AC Output Data
Rated AC Output and UPS Power (W) 5000W
BATTERY PROTECTION Max. AC Output Power (W) 5500W
IMAX = (PMAXINV / VBATT) x 125% Peak Power (Off-Grid) 2 times of rated power, 10 S
IMAX = 5000W / 51.2V = 97.656 A x 125% AC Output Rated Current (A) 21.7A
IMAX = 122.07 A Max. AC Current (A) 25A
Use: 125AT DC MCCB Max. Continuous AC Passthrough (A) 35A
2-35mm² Battery Cable Power Factor 0.8 leading to 0.8 lagging
Output Frequency and Voltage 50/60Hz; 220/230/240 VAC
www.niceaye.com www.niceaye.com
INVERTER AC PROTECTION Grid Type Single Phase
1055.0W 1055.0W
2218.8kWh
232.6V 59.8Hz
2218.8kWh
232.6V 59.8Hz IMAX = (PMAXINV / VAC) x 125% Current Harmonic Distortion THD <3% (Linear load <1.5%)
5.00A 0.90PF 5.00A 0.90PF
1 SINGLE LINE DIAGRAM 2 Circuit Protection and 3 5kW Hybrid Inverter (DEYE) 4 500W Solar Panel (Trina)
E 1 E 1 E 1 E 1
Voltage Drop Calculation Specifications Specifications
C. THE REQUIREMENTS OF THE LOCAL POWER COMPANY. 2. MODULES CONFORM TO AND ARE LISTED TO UL
1703. CT LIMITER
2. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY
SOLAR INVERTER
LICENSED ELECTRICAL PRACTITIONER. 3. CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE SERVICE ENTRANCE
LISTED AS SUNLIGHT RESISTANT AS PER PEC.
3. ALL EQUIPMENT, DEVICES, MATERIALS AND INSTALLATION METHODS SHALL BE APPLICABLE TO THE
DESIGN , INTENT/ PURPOSE/ FUNCTION, LOCATION, SITE/ AREA CONDITION, AND WEATHER. 4. CONDUCTORS EXPOSED TO WET LOCATION GROUNDING
SHALL BE SUITABLE FOR USE ON WET LOCATION
www.niceaye.com
4. THE CONTRACTOR / IN-CHARGE OF INSTALLATION SHALL VERIFY AND ORIENT THE ACTUAL LOCATION AS PER PEC. LIFEPO4 BATTERY
1055.0W
OF THE UNITS TO BE INSTALLED. 2218.8kWh
232.6 V 59.8Hz
5.00A 0.90PF
DIGITAL WATT-METER
5. NEW REC METER SHALL BE INSTALLED NEAR THE
5. EXPOSED CONDUIT RUNS SHALL BE INSTALLED PARALLEL TO OR PERPENDICULAR WITH THE NEW BI-DIRECTIONAL METER.
BUILDING LINE, DIAGONAL RUN SHALL NOT BE ACCEPTED, ALL BOXES AND CONDUITS SHALL BE
RIGIDLY SUPPORTED BY HANGER RODS, ANGLE BARS, U-BOLTS AND METAL CONDUIT CLAMPS. USE 6. TAPPING POINT OF REC METER LOAD SIDE AC/DC SURGE PROTECTIVE DEVICE SOLAR PANEL
OF G.I WIRE HANGER IS NOT ACCEPTABLE. CONDUIT SUPPORT SHALL BE EVERY 1500MM MAXIMUM CONDUCTORS SHALL BE AT THE LOAD VISIBLE, A
INTERVAL. USE OF NON-METALLIC FLEXIBLE CONDUIT IS PROHIBITED. SERVICE DISCONNECT DEVICE SHALL BE
INSTALLED BEFORE SERVICE EQUIPMENT, REC AC/ DC CIRCUIT BREAKER
6. ALL RACEWAYS, SPLICE BOXES, AND/OR WIRE GUTTERS SHALL BE GAUGE #16, G.I SHEET, PAINTED METERS LOAD SIDE CONDUCTORS SHOULD BE NEGATIVE/ NEUTRAL WIRE (L2)
FINISH WITH MATCHING TOUCH-UP COATING. SHORT AS POSSIBLE.
MANUAL TRANSFER SWITCH POSITIVE/ LIVE WIRE (L1)
7. ALL DEVICES AND NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT SHALL BE 7. THE LINE SIDE CONDUCTORS OF THE REC METER
PROPERLY GROUNDED TO THE BOX BY MEANS OF TERMINAL LUGS IN ACCORDANCE WITH THE BETWEEN THE GRID-TIE INVERTER SHALL BE GROUNDING WIRE
PROVISION IN THE ARTICLE 2.50 "GROUNDING AND BONDING" PHILIPPINE ELECTRICAL CODE, VOLUME ENCLOSED IN AN EXPOSED RIGID METALLIC AC/ DC MOLDED CASE COMM. CABLE/ RS485
1, 2017 EDITION. CONDUIT OR INTERMEDIATE METALLIC CONDUIT. CIRCUIT BREAKER
CT WIRE
8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF THE APPROVED TYPE FOR LOCATION AND 8. WARNING SHOULD BE MOUNTED ON OR
PURPOSE. ADJACENT TO THE VISIBLE DISCONNECTION
9. EXACT LOCATION AND RATING OF ALL EQUIPMENT TO BE SUPPLIED BY OTHER TRADES SHALL BE
DEVICE AND SHALL BE READ PROMINENTLY.
5 LEGENDS 6 SITE LOCATION
COORDINATED WITH THEIR RESPECTIVE TRADE DRAWINGS / PLANS PRIOR TO IMPLEMENTATION.
E 1 E 1