Project: Brigade BrookfieldTechpark

Client Brigade

Consultant LCS

Subject: : Design of Domestic Monoblock / submersible Pumps - Zone B


Date : 23/01/2017; 30/12/2016

1 hp = 746 W = 0.746 KW 0.746 KW


Terrace Rain water Filter feed Flushing water supply booster
Filter Feed Pump STP Flushing water lift pumps
pumps pumps

RWS-01 RWS-02
Sl No: Description / Specification UG Sump-01 UG Sump-02 TO OHT (STP-1&2) Booster pump
(Monoblock) (Submersible)

LOCATION/Building name B1 & B2 B3 & B4 B1&B2 B3 B1-STP - OHT B3-STP - OHT B1


1 Total Head in "M" 30 30 30 30 40 40 40
(Static Head+Residual Head+Friction Loss)
2 Q= Capacity of water in Ltrs 260000 260000 250000 250000 35000 30000 35000

3 Assumed hours of operation 12 12 12 12 4 4 4

4 Total Flow in LPS (Roundoff) 7 7 6 6 3 3 3

5 Pump Capacity in HP 4.31 4.31 3.69 3.69 2.46 2.46 2.46

(HP=WQH/75*Efficiency {Assumed 65% of Efficiency}

Considered Capacity of pump in HP 5 5 4 4 3 3 3

No of Pumps (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s)

Type of pumps Monoblock Monoblock Monoblock Submersible Monoblock Monoblock Monoblock

Total Working Load in KW 3.73 3.73 2.98 2.98 2.24 2.24 2.24

4 4 4 3.7 2.2 2.2

PIPE DIA CALCULATION

Q = Cum/Sec 0.007 0.007 0.006 0.006 0.003 0.003 0.003

Dia of Pipe = A*V { Area of pipe & Velocity ie., velocity


considered 1.5 & A = ╥ d²/4 }
Dia of Pipe in M 0.08 0.08 0.07 0.07 0.05 0.05 0.05
Dia of Pipe in MM 77 77 71 71 50 50 50
Available Dia / Designed dia of Pipe in mm 80 80 80 80 65 65 65

TRC Engineering (I) pvt ltd


Flushing water supply booster External Rain water harvesting sumps
De watering lift pumps (Submersible type)
pumps Submersible pump (Zone-B)

UG Sump UG Sump STP -01 (Pump STP -02 (Pump Storm water lift Storm water lift Storm water lift Storm water lift
Booster pump Sump-01
pump room-01 pump room-02 room) room) pump-01 pump-02 pump-03 pump-04

B3 B1 B3 B1 B3 Combined Basement South


40 20 20 20 20 20 20 20 20 30

30000 2000 2000 2000 2000 40000 40000 35000 35000 100000

4 1 1 1 1 2.5 2.5 2 2 8

3 1 1 1 1 5 5 5 5 4

2.46 0.41 0.41 0.41 0.41 2.05 2.05 2.05 2.05 2.46

3 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

(1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s) (1w+1s)

Monoblock Submersible Submersible Submersible Submersible Submersible Submersible Submersible Submersible Submersible

2.24 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37

3 3 3 3 5.5 5.5 5.5 5

0.003 0.001 0.001 0.001 0.001 0.005 0.005 0.005 0.005 0.004

0.05 0.03 0.03 0.03 0.03 0.07 0.07 0.07 0.07 0.06

50 29 29 29 29 65 65 65 65 58
65 32 32 32 32 50 65 65 65 65

TRC Engineering (I) pvt ltd


External Rain water harvesting sumps
Irrigation Pumps Monoblock
Submersible pump (Zone-B)

Sump-02 STP-01 STP-02

North B1 B3
30 30 30

100000 80000 80000

8 12 12

4 2 2

2.46 1.23 1.23

0.5 1.5 1.5

(1w+1s) (1w+1s) (1w+1s)

Submersible Monoblock Monoblock

0.37 1.12 1.12

0.004 0.002 0.002

0.06 0.04 0.04

58 41 41
65 50 50

TRC Engineering (I) pvt ltd


Project:

Client

Consultant

Subject: : Design of Hydropneumatic pumps - Zone B


Date : 23/01/2017; 30/12/2016

1 hp = 746 W = 0.746 KW 0.746 KW 0.746 KW


Sl No: Description / Specification Domestic water ditribution pumps Flushing ater ditribution booster pump
B1 & B2 B3 & B4 B1 & B2 B3
1 Total Head in "M" 40 40 15 15
(Static Head+Residual Head+Friction Loss)
2 Q= Capacity of water in Ltrs 260000 260000 30000 260000

3 Total No of Fixture Units in Nos 825 Lpm 825 Lpm 714 Lpm 588 Lpm

Lower than above FU (Flow in Lpm) 800 682.4 800 682.4 700 606 500 472.9

Higher than above FU (Flow in Lpm) 900 739 900 739 800 682.4 600 549.3

Flow required for Total No of Fixture Units in Nos FU from Table-32,


4 697 lpm 697 lpm 617 lpm 540 lpm
SP:35(S&T)-1987
Hydro pneumatic system for domestic water stand-by 100% 100% 100% 100%
50% (ie. 1 working & 1 stand by) = 697 lpm each
5 Total Flow in LPS (Roundoff) 11.62 11.62 10.28 9.00
6 Designed for 50% of LPS 5.81 5.81 5.14 4.50

7 Pump Capacity in HP 9.53 9.53 3.16 2.77

(HP=WQH/75*Efficiency {Assumed 65% of Efficiency}

8 Considered Capacity of pump in HP 10 10 4 3

No of Pumps (2w+1s) (2w+1s) (2w+1s) (2w+1s)

9 Total Working Load in KW 7.46 7.46 2.98 2.24

7.5 7.5 3 3

PIPE DIA CALCULATION

Q = Cum/Sec 0.0116 0.0116 0.0103 0.0090

Dia of Pipe = A*V { Area of pipe & Velocity ie., velocity considered 1.5 & A
= ╥ d²/4 }
Dia of Pipe in M 0.10 0.10 0.09 0.09
Dia of Pipe in MM 99 99 93 87
Available Dia of Pipe in mm 100 100 100 100

TRC Engineering (I) pvt ltd