Catalogue (RCA2000, Surgetec) - en
Catalogue (RCA2000, Surgetec) - en
kr
RCA 2000
CONTENTS
10.5 pt
- 345kV Surge Arrester Failure - - 154kV Surge Arrester Failure - - 23kV Surge Arrester Failure -
① Gapless type surge arrester generates low leakage current during operation
② Total leakage current(It) is the vector composition of capacitive(Ic) and resistive current(Ir)
· Capacitive current(Ic) is the majority of leakage current (It, 0.2~3mA), and it maintains
a constant value until reaching the lifespan.
· The resistive current(Ir) is surge arrester failure factor and a low value at the beginning,
but increases as deteriorated (10〜600㎂).
① Cause of deterioration
· Aging deterioration by overvoltage from lightning or surge and continuous operating
voltage stress.
② Deterioration process
· As resistive current increases, temperature rises, and the increased temperature
deteriorates the arrester.
③ Result of deterioration
· Thermal runaway occurs if heat dissipation is exceeded to the limit due to temperature rise.
· Surge arrester explosion accident due to thermal runaway, and blackout caused by
a ground fault between the power line and ground.
Total leakage-
Overvoltage current
Aging Thermal
Tempera-
Operating deterioration Capacitive current ture↑ runaway
voltage (constancy)
Resistive current↑
Deterioration
03ㅣ RCA2000
World-class high accuracy diagnostic equipment for Surge arrester
· When harmonics included in the system voltage are introduced, a large error occurs
in the harmonics measurement generated by the surge arrester.
Total
Fundamental
Harmonic 3
Harmonic 5
Harmonic 7
50µA 200µA
Harmonic 9
It =∑ancos(nωt) +∑ bnsin(nωt)
du
It = Ic + Ir = C dt + kuα
n=1 n=1
leakage Condition
current diagnosis
Analysis
· Resistive leakage current is 10µA to 600µA peak in the normal operating condition(20℃).
· Resistive leakage current limit of the arrester manufacturers is typically 100µA to 500µA.
· Condition diagnosis by identifying change trends through periodic resistive leakage current
measurement.
On-site diagnosis
05ㅣ RCA2000
World-class high accuracy diagnostic equipment for Surge arrester
· fundamental harmonic(60Hz)
Total leakage current (It)
· harmonics(3rd · 5th · 7th · 9th)
· fundamental harmonic(60Hz)
Leakage Capacitive current (Ic)
· harmonics(3rd · 5th · 7th · 9th)
current
Measurement measuring
item · fundamental harmonic(60Hz)
Resistive current(Ir) · harmonics(3rd · 5th · 7th · 9th)
· Peak value
Measuring
Minimum 0.03[mA] ~ maximum 10[mA]
range
Processing
Octa Core (2.8[GHz]+2.4[Ghz]+1.7[Ghz])
speed
Micro
Processor
Memory 128[GB], RAM : 6[GB]
Condition
Normal, Caution, Defect
Data judgment
Administration
Diagnostic Draw up, Save
reports