TEST SHEET FOR MF-VRLA BATTERY SET

Site Name_________________________________ Site ID_________________SSA____________________


Capacity______________ Discharge Current_____________Date ______________ Set (A/B) ______________

S.No. TEST Status(cleared/not


cleared)
1 Check the installation in a clean proper ventilated and dry location
2 Visual examination check
2.1 Check alignment and levelling of battery set
2.2 Check cracks of battery container and finish paint of stand
2.3 Polarity sign writings
2.4 Check of fuse rating and link on positive lead
3 CAPACITY TEST (Fill the table given bellow):- Result(Pass /Fail)
Check the capacity of battery set (Test discharge) [Taken after freshening charge at C-10 rate i.e.1/10 th of
rated capacity applying temperature Correction to 27 C] 0

Measure and record the voltage of cells hourly up to 8 hours then after every 30 minutes
Record the room temperature hourly.
Record the discharge current and load current hourly.
End of discharge: stop the test discharge at 1.85xN (N= no. of cells) terminal volts or any cell voltage
reaches to 1.74 volt.

Time No On 1 2 3 4 5 6 7 8 8.5 9 9.5 10


Cell no Load Load
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Total
voltage
current
Temp.

(Blue ink signature of veirdor Rep.) (Blue ink signature of veirdor Rep.)
Name_______________________ Name_______________________
Designation___________________ Designation___________________
Mob. No._____________________ Mob. No._____________________