CONTENTS
Volume 4
Construction Details 1015

Contents 1013
Manual
Fifth Edition
The NRCA Roofing and Waterproofing Manual—Fifth Edition

Low-slope Membrane Roofing


Built-up Roofing
BUR-1 Metal Parapet Cap Coping (Coping) and Base Flashing...............................................1029
BUR-1S Metal Parapet Cap Coping (Coping) and Base Flashing .............................................1030
BUR-2 Raised Perimeter Edge with Metal Flashing (Fascia Cap) ............................................1031
BUR-2S Raised Perimeter Edge with Metal Flashing (Fascia Cap) ..........................................1032
BUR-3 Embedded Edge Metal Flashing (Gravel-Stop) ............................................................1033
BUR-3S Embedded Edge Metal Flashing (Gravel-Stop) ..........................................................1034
BUR-4 Surface-mount Counterflashing for Concrete Walls....................................................1035
BUR-4S Surface-mount Counterflashing for Concrete Walls..................................................1036
BUR-5 Base Flashing for Wall-supported Deck....................................................................1037
BUR-5S Base Flashing for Wall-supported Deck..................................................................1038
BUR-5A Base Flashing for Vented Base Sheet ....................................................................1039
BUR-5AS Base Flashing for Vented Base Sheet ..................................................................1040
BUR-6 Base Flashing for Non-wall-Supported Deck ..............................................................1041
BUR-6S Base Flashing for Non-wall-supported Deck ............................................................1042
BUR-7 Expansion Joint with Metal Cover ...........................................................................1043
BUR-7S Expansion Joint with Metal Cover..........................................................................1044
BUR-7A Expansion Joint with Pre-manufactured Cover.........................................................1045
BUR-7AS Expansion Joint with Pre-manufactured Cover .......................................................1046
BUR-8 Area Divider in Roof System ..................................................................................1047
BUR-8S Area Divider in Roof System.................................................................................1048
BUR-9 Equipment Support Curb .......................................................................................1049
BUR-9S Equipment Support Curb .....................................................................................1050
BUR-10 Equipment Support Stand....................................................................................1051
BUR-11 Equipment Support Stand and Typical Rain Collar Penetration Detail ..........................1052
BUR-11S Equipment Support Stand and Typical Rain Collar Penetration Detail.........................1053
BUR-12 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1054
BUR-12S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1055
BUR-13 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1056
BUR-13S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1057
BUR-14 Skylight, Scuttle, and Smoke Vent .........................................................................1058
BUR-14S Skylight, Scuttle, and Smoke Vent .......................................................................1059
BUR-15 Structural Member Through Roof Deck .................................................................1060
BUR-15S Structural Member Through Roof Deck ...............................................................1061
BUR-16 Sheet Metal Enclosure for Piping Through Roof Deck...............................................1062
BUR-16S Sheet Metal Enclosure for Piping Through Roof Deck.............................................1063
BUR-17 Isolated Stack Flashing (Hot or Cold) .....................................................................1064

Contents 1017
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BUR-17S Isolated Stack Flashing (Hot or Cold) ...................................................................1065


BUR-17A Isolated Stack Flashing-Sheet Metal (Hot or Cold)..................................................1066
BUR-17AS Isolated Stack Flashing-Sheet Metal (Hot or Cold) ................................................1067
BUR-18 Plumbing Vent ...................................................................................................1068
BUR-18S Plumbing Vent .................................................................................................1069
BUR-19 Penetration Pocket.............................................................................................1070
BUR-19S Penetration Pocket...........................................................................................1071
BUR-20 Roof Drain ........................................................................................................1072
BUR-20S Roof Drain ......................................................................................................1073
BUR-21 Scupper Through Raised Perimeter Edge...............................................................1074
BUR-21S Scupper Through Raised Perimeter Edge .............................................................1075
BUR-22 Gutter ..............................................................................................................1076
BUR-22S Gutter ............................................................................................................1077
Modified Bitumen Roofing
MB-1 Metal Parapet Cap (Coping) and Base Flashing ..........................................................1078
MB-1S Metal Parapet Cap (Coping) and Base Flashing ........................................................1079
MB-2 Raised Perimeter Edge with Metal Flashing (Fascia Cap)..............................................1080
MB-2S Raised Perimeter Edge with Metal Flashing (Fascia Cap)............................................1081
MB-3 Embedded Edge Metal Flashing (Gravel-stop) .............................................................1082
MB-3S Embedded Edge Metal Flashing (Gravel-stop)............................................................1083
MB-4 Surface-mount Counterflashing for Concrete Walls .....................................................1084
MB-4S Surface-mount Counterflashing for Concrete Walls ...................................................1085
MB-5 Base Flashing for Wall-supported Deck .....................................................................1086
MB-5S Base Flashing for Wall-supported Deck ...................................................................1087
MB-5A Base Flashing for Vented Base Sheet .....................................................................1088
MB-5AS Base Flashing for Vented Base Sheet ...................................................................1089
MB-6 Base Flashing for Non-wall-supported Deck ...............................................................1090
MB-6S Base Flashing for Non-wall-supported Deck..............................................................1091
MB-7 Expansion Joint with Metal Cover .............................................................................1092
MB-7S Expansion Joint with Metal Cover ...........................................................................1093
MB-7A Expansion Joint with Premanufactured Cover...........................................................1094
MB-7AS Expansion Joint with Premanufactured Cover .........................................................1095
MB-8 Area Divider in Roof System....................................................................................1096
MB-8S Area Divider in Roof System ..................................................................................1097
MB-9 Equipment Support Curb ........................................................................................1098
MB-9S Equipment Support Curb.......................................................................................1099
MB-10 Equipment Support Stand .....................................................................................1100
MB-11 Equipment Support Stand and Typical Rain Collar Penetration Detail ............................1101
MB-11S Equipment Support Stand and Typical Rain Collar Penetration Detail ..........................1102
MB-12 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1103

1018 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MB-12S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1104
MB-13 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1105
MB-13S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1106
MB-14 Skylight, Scuttle, and Smoke Vent ..........................................................................1107
MB-14S Skylight, Scuttle, and Smoke Vent ........................................................................1108
MB-15 Structural Member Through Roof Deck ..................................................................1109
MB-15S Structural Member Through Roof Deck.................................................................1110
MB-16 Sheet Metal Enclosure for Piping Through Roof Deck ................................................1111
MB-16S Sheet Metal Enclosure for Piping Through Roof Deck ..............................................1112
MB-17 Isolated Stack Flashing (Hot or Cold) ......................................................................1113
MB-17S Isolated Stack Flashing (Hot or Cold).....................................................................1114
MB-17A Isolated Stack Flashing (Hot or Cold).....................................................................1115
MB-17AS Isolated Stack Flashing (Hot or Cold)...................................................................1116
MB-18 Plumbing Vent.....................................................................................................1117
MB-18S Plumbing Vent...................................................................................................1118
MB-19 Penetration Pocket ..............................................................................................1119
MB-19S Penetration Pocket ............................................................................................1120
MB-20 Roof Drain..........................................................................................................1121
MB-20S Roof Drain........................................................................................................1122
MB-20A Roof Drain - Alternate Flashing ............................................................................1123
MB-20AS Roof Drain - Alternate Flashing ..........................................................................1124
MB-21 Scupper Through Raised Perimeter Edge ................................................................1125
MB-21S Scupper Through Raised Perimeter Edge ..............................................................1126
MB-22 Gutter ...............................................................................................................1127
MB-22S Gutter..............................................................................................................1128
Thermoplastic Single-ply Roofing
TP-1 Metal Parapet Cap (Coping) and Base Flashing ...........................................................1129
TP-1S Metal Parapet Cap (Coping) and Base Flashing..........................................................1130
TP-2 Raised Perimeter Edge with Metal Flashing (Fascia Cap)...............................................1131
TP-2S Raised Perimeter Edge with Metal Flashing (Fascia Cap) .............................................1132
TP-3 Embedded Edge Metal Flashing (Gravel-stop)...............................................................1133
TP-3S Embedded Edge Metal Flashing (Gravel-stop) .............................................................1134
TP-3A Draining Perimeter Edge........................................................................................1135
TP-3AS Draining Perimeter Edge ......................................................................................1136
TP-3B Joint Detail for Membrane Coated Embedded Edge Metal Flashing (Gravel-stop) .............1137
TP-3C Joint Detail for Membrane Coated Draining Perimeter Edge ........................................1138
TP-4 Surface-mounted Counterflashing for Concrete Walls ...................................................1139
TP-4S Surface-mounted Counterflashing for Concrete Walls .................................................1140
TP-5 Base Flashing for Wall-supported Deck ......................................................................1141

Contents 1019
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TP-5S Base Flashing for Wall-supported Deck ....................................................................1142


TP-6 Base Flashing for Non-wall-supported Deck.................................................................1143
TP-6S Base Flashing for Non-wall-supported Deck ...............................................................1144
TP-7 Expansion Joint with Metal Cover ..............................................................................1145
TP-7S Expansion Joint with Metal Cover ............................................................................1146
TP-7A Expansion Joint with Premanufactured Cover ............................................................1147
TP-7AS Expansion Joint with Premanufactured Cover ..........................................................1148
TP-8 Area Divider in Roof System .....................................................................................1149
TP-8S Area Divider in Roof System ...................................................................................1150
TP-9 Equipment Support Curb..........................................................................................1151
TP-9S Equipment Support Curb........................................................................................1152
TP-10 Equipment Support Stand ......................................................................................1153
TP-11 Equipment Support Stand Leg (Field Wrap)...............................................................1154
TP-11S Equipment Support Stand Leg (Field Wrap) .............................................................1155
TP-11A Pipe Penetration (Field Wrap) ...............................................................................1156
TP-11AS Equipment Support Stand Leg (Field Wrap) ...........................................................1157
TP-12 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1158
TP-12S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1159
TP-13 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1160
TP-13S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1161
TP-14 Skylight, Scuttle, and Smoke Vent ...........................................................................1162
TP-14S Skylight, Scuttle, and Smoke Vent..........................................................................1163
TP-15 Structural Roof Member Through Roof Deck ............................................................1164
TP-15S Structural Roof Member Through Roof Deck...........................................................1165
TP-16 Sheet Metal Enclosure for Piping Through Roof Deck .................................................1166
TP-16S Sheet Metal Enclosure for Piping Through Roof Deck ...............................................1167
TP-17 Isolated Stack Flashing (Hot or Cold)........................................................................1168
TP-17S Isolated Stack Flashing (Hot or Cold) ......................................................................1169
TP-18 Plumbing Vent (Field Wrap) ....................................................................................1170
TP-18S Plumbing Vent (Field Wrap) ..................................................................................1171
TP-18A Plumbing Vent (Premanufactured Boot)..................................................................1172
TP-18AS Plumbing Vent (Premanufactured Boot) ................................................................1173
TP-19 Penetration Pocket ...............................................................................................1174
TP-19S Penetration Pocket .............................................................................................1175
TP-20 Roof Drain...........................................................................................................1176
TP-20S Roof Drain .........................................................................................................1177
TP-21 Scupper Through Roof Edge ...................................................................................1178
TP-21S Scupper Through Roof Edge .................................................................................1179

1020 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TP-21A Scupper Through Gravel Stop Edge .......................................................................1180


TP-21AS Scupper Through Gravel Stop Edge......................................................................1181
TP-22 Gutter.................................................................................................................1182
TP-22S Gutter...............................................................................................................1183
Thermoset Single-ply Roofing
TS-1 Metal Parapet Cap (Coping) and Base Flashing............................................................1184
TS-1S Metal Parapet Cap (Coping) and Base Flashing..........................................................1185
TS-2 Raised Perimeter Edge with Metal Flashing (Fascia Cap) ...............................................1186
TS-2S Raised Perimeter Edge with Metal Flashing (Fascia Cap) .............................................1187
TS-3 Embedded Edge Metal Flashing (Gravel-stop)...............................................................1188
TS-3S Embedded Edge Metal Flashing (Gravel-stop) .............................................................1189
TS-3A Draining Perimeter Edge........................................................................................1190
TS-3AS Draining Perimeter Edge ......................................................................................1191
TS-4 Surface-Mounted Counterflashing for Concrete Walls ...................................................1192
TS-4S Surface-Mounted Counterflashing for Concrete Walls .................................................1193
TS-5 Base Flashing for Wall-supported Deck ......................................................................1194
TS-5S Base Flashing for Wall-supported Deck ....................................................................1195
TS-6 Base Flashing for Non-wall-supported Deck.................................................................1196
TS-6S Base Flashing for Non-wall-supported Deck ...............................................................1197
TS-7 Expansion Joint with Metal Cover ..............................................................................1198
TS-7S Expansion Joint with Metal Cover ............................................................................1199
TS-7A Expansion Joint with Premanufactured Cover ............................................................1200
TS-7AS Expansion Joint with Premanufactured Cover ..........................................................1201
TS-7B Alternate Expansion Joint for Loose-laid, Ballasted Systems ........................................1202
TS-7BS Alternate Expansion Joint for Loose-laid, Ballasted Systems.......................................1203
TS-8 Area Divider in Roof System .....................................................................................1204
TS-8S Area Divider in Roof System ...................................................................................1205
TS-9 Equipment Support Curb..........................................................................................1206
TS-9S Equipment Support Curb ........................................................................................1207
TS-10 Equipment Support Stand ......................................................................................1208
TS-11 Equipment Support Stand Leg (Field Wrap)...............................................................1209
TS-11S Equipment Support Stand Leg (Field Wrap) .............................................................1210
TS-12 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1211
TS-12S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1212
TS-13 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1213
TS-13S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1214
TS-14 Skylight, Scuttle, and Smoke Vent............................................................................1215
TS-14S Skylight, Scuttle, and Smoke Vent..........................................................................1216

Contents 1021
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TS-15 Structural Member Through Roof Deck....................................................................1217


TS-15S Structural Member Through Roof Deck ..................................................................1218
TS-16 Sheet Metal Enclosure for Piping Through Roof Deck .................................................1219
TS-16S Sheet Metal Enclosure for Piping Through Roof Deck ...............................................1220
TS-17 Isolated Stack Flashing (Hot or Cold) ........................................................................1221
TS-17S Isolated Stack Flashing (Hot or Cold) ......................................................................1222
TS-18 Plumbing Vent (Field Wrap) ....................................................................................1223
TS-18S Plumbing Vent (Field Wrap) ..................................................................................1224
TS-18A Plumbing Vent (Premanufactured Boot)..................................................................1225
TS-18AS Plumbing Vent (Premanufactured Boot) ................................................................1226
TS-19 Penetration Pocket ...............................................................................................1227
TS-19S Penetration Pocket .............................................................................................1228
TS-20 Roof Drain ...........................................................................................................1229
TS-20S Roof Drain .........................................................................................................1230
TS-21 Scupper Through Raised Edge Perimeter .................................................................1231
TS-21S Scupper Through Raised Perimeter Edge ...............................................................1232
TS-21A Scupper Through Gravel-stop Edge ........................................................................1233
TS-21AS Scupper Through Gravel-stop Edge ......................................................................1234
TS-22 Gutter.................................................................................................................1235
TS-22S Gutter ...............................................................................................................1236
Protected Membrane Roofing
BUR-P-1 Metal Parapet Cap (Coping) and Base Flashing ......................................................1237
BUR-P-14 Skylight, Scuttle, and Smoke Vent ......................................................................1238
BUR-P-18 Plumbing Vent ................................................................................................1239
BUR-P-20 Roof Drain .....................................................................................................1240
MB-P-1 Metal Parapet Cap (Coping) and Base Flashing........................................................1241
MB-P-14 Skylight, Scuttle, and Smoke Vent........................................................................1242
MB-P-18 Plumbing Vent ..................................................................................................1243
MB-P-20 Roof Drain .......................................................................................................1244
TP-P-1 Metal Parapet Cap (Coping) and Base Flashing .........................................................1245
TP-P-14 Skylight, Scuttle, and Smoke Vent.........................................................................1246
TP-P-18 Plumbing Vent ...................................................................................................1247
TP-P-20 Roof Drain ........................................................................................................1248
TS-P-1 Metal Parapet Cap (Coping) and Base Flashing .........................................................1249
TS-P-14 Skylight, Scuttle, and Smoke Vent .........................................................................1250
TS-P-18 Plumbing Vent ...................................................................................................1251
TS-P-20 Roof Drain ........................................................................................................1252
Tables
BUR-MB-TABLE 1 Guide for Sheet Metal Fascia Edges for Built-up and
Modified Bitumen Membranes .........................................................................................1253
BUR-MB-TABLE 1 (Metric) Guide for Sheet Metal Fascia Edges for Built-up and
Modified Bitumen Membranes .........................................................................................1254
1022 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TABLE 2.1 Options for Termination of Wall Counterflashing ..................................................1255


TABLE 2.2 Options for Termination of Wall Counterflashing ..................................................1256
TABLE 2.3 Options for Termination of Wall Counterflashing ..................................................1257
TABLE 3 Guide for Sheet Metal Parapet Cap (Coping)..........................................................1258
TABLE 4 Guide for Clearances Between Pipes/Walls/Curbs ................................................1259
TABLE 5 Guide for Crickets and Saddles ............................................................................1260
TABLE 6 Guide for Edge Scuppers with Tapered Saddles ......................................................1261
SINGLE-PLY-TABLE 7.1 Options for Perimeter Base Securement
(Roof-to-wall and Roof-to-curb Intersections) .......................................................................1262
SINGLE-PLY-TABLE 7.2 Options for Perimeter Base Securement
(Roof-to-wall and Roof-to-curb Intersections) .......................................................................1263
SINGLE-PLY-TABLE 1 Guide for Sheet Metal Fascia Edges for Thermoset and
Thermoplastic Membranes..............................................................................................1264
SINGLE-PLY-TABLE 1 (Metric) Guide for Sheet Metal Fascia Edges for Thermoset and
Thermoplastic Membranes..............................................................................................1265

Steep-slope Roofing
Asphalt Shingles
ASPH-1 Apron Flashing...................................................................................................1266
ASPH-2 Sidewall Flashing ................................................................................................1267
ASPH-3 Backer Flashing .................................................................................................1268
ASPH-3A Backer Flashing ...............................................................................................1269
ASPH-4 Eave and Rake Flashing .......................................................................................1270
ASPH-5 Eave and Rake Flashing with Gutter.......................................................................1271
ASPH-6 Open Valley........................................................................................................1272
ASPH-7 Closed Cut Valley ................................................................................................1273
ASPH-8 Pipe Penetration ................................................................................................1274
Clay and Concrete Tile
TILE-1 Apron Flashing .....................................................................................................1275
TILE-2 Sidewall Flashing ..................................................................................................1276
TILE-3 Backer Flashing....................................................................................................1277
TILE-3A Backer Flashing..................................................................................................1278
TILE-4 Eave Flashing .......................................................................................................1279
TILE-5 Rake Edge Flashing ...............................................................................................1280
TILE-6 Open Valley ..........................................................................................................1281
TILE-7 Two-Piece Pipe Flashing .........................................................................................1282
TILE-7A Pipe Penetration.................................................................................................1283
Slate
SLATE-1 Apron Flashing ..................................................................................................1284
SLATE-2 Sidewall Flashing ...............................................................................................1285
SLATE-3 Backer Flashing.................................................................................................1286
SLATE-3A Backer Flashing...............................................................................................1287

Contents 1023
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SLATE-4 Eave and Rake flashing .......................................................................................1288


SLATE-5 Eave and Rake Flashing with Gutter ......................................................................1289
SLATE-6 Open Valley .......................................................................................................1290
SLATE-7 Closed Valley .....................................................................................................1291
SLATE-8 Pipe Penetration................................................................................................1292
Wood Shakes and Shingles
Wood Shakes
SHK-1 Apron Flashing.....................................................................................................1293
SHK-2 Sidewall Flashing ..................................................................................................1294
SHK-3 Backer Flashing ...................................................................................................1295
SHK-3A Backer Flashing .................................................................................................1296
SHK-4 Eave and Rake Flashing .........................................................................................1297
SHK-5 Eave and Rake Flashing with Gutter.........................................................................1298
SHK-6 Open Valley..........................................................................................................1299
SHK-7 Closed Valley .......................................................................................................1300
SHK-8 Pipe Penetration .................................................................................................1301
Wood Shingles
SHNG-1 Apron Flashing ..................................................................................................1302
SHNG-2 Sidewall Flashing................................................................................................1303
SHNG-3 Backer Flashing .................................................................................................1304
SHNG-3A Backer Flashing ...............................................................................................1305
SHNG-4 Eave and Rake Flashing.......................................................................................1306
SHNG-5 Eave and Rake Flashing with Gutter ......................................................................1307
SHNG-6 Open Valley .......................................................................................................1308
SHNG-7 Closed Valley .....................................................................................................1309
SHNG-8 Pipe Penetration ................................................................................................1310

Architectural Metal and Metal Roofing


Sheet Metal
SM-1 Fascia Cap with Cover Plate ....................................................................................1311
SM-2 Fascia Cap with Overlap..........................................................................................1312
SM-3 Fascia Cap with Concealed Plate ..............................................................................1313
SM-4 “A” Type Edge Metal with Cover Plate........................................................................1314
SM-5 “A” Type Edge Metal with Overlap .............................................................................1315
SM-6 “L” Type Edge Metal with Cover Plate ........................................................................1316
SM-7 “L” Type Edge Metal with Overlap .............................................................................1317
SM-8 “L” Type Edge Metal with Concealed Plate..................................................................1318
SM-9 “T” Type Edge Metal with Overlap .............................................................................1319
SM-10 Common Fascia Extension Options .........................................................................1320
SM-11 Common Fascia Extension Options .........................................................................1321
SM-12 Common Fascia Extension Options .........................................................................1322

1024 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SM-13 Counterflashing Options ........................................................................................1323


SM-14 Counterflashing Options ........................................................................................1324
SM-15 Counterflashing Options ........................................................................................1325
SM-16 Coping Cap Options..............................................................................................1326
SM-17 Coping Cap Options..............................................................................................1327
SM-18 Coping Cap Options..............................................................................................1328
SM-19 Coping Cap Securement Options ............................................................................1329
SM-20 Expansion Joint Cover Options ...............................................................................1330
SM-21 Expansion Joint Cover Options ...............................................................................1331
SM-22 Expansion Joint Profile Options ..............................................................................1332
SM-23 Valley Metal with Overlap ......................................................................................1333
SM-24 Gutter Joinery Options..........................................................................................1334
SM-25 Gutter Joinery Options..........................................................................................1335
SM-26 Common Joints and Seams ..................................................................................1336
Architectural Metal Roofing
A-MTL-1 Downslope Perimeter Edge Metal Flashing ............................................................1337
A-MTL-2 Downslope Perimeter with Gutter (“T” Type)...........................................................1338
A-MTL-2A Downslope Perimeter with Gutter (Joggle Cleat)...................................................1339
A-MTL-3 Rake Edge Flashing (“T” Type) ..............................................................................1340
A-MTL-3A Rake Edge Flashing (Cleated).............................................................................1341
A-MTL-4 Non-Venting Ridge Cap Flashing...........................................................................1342
A-MTL-4A Venting Ridge Cap Flashing ...............................................................................1343
A-MTL-5 Hip Cap Flashing ...............................................................................................1344
A-MTL-6 Open Metal Valley ..............................................................................................1345
A-MTL-6A Alternate Open Metal Valley with Side Locks ........................................................1346
A-MTL-7 Roof-to-Wall (Headwall) Transition ........................................................................1347
A-MTL-8 Roof-to-Wall (Sidewall) Transition..........................................................................1348
A-MTL-8A Roof-to-Wall (Sidewall) Transition (“Z” Closure)......................................................1349
A-MTL-9 Expansion Joint - Compact Roof Assembly .............................................................1350
A-MTL-9A Expansion Joint - Non-compact Roof Assembly .....................................................1351
A-MTL-10 Expansion Joint at Roof-to-wall (Headwall) Transition - Non-compact Roof System ......1352
A-MTL-11 Equipment Support Stand .................................................................................1353
A-MTL-12 Equipment Support Stand/Vent Stack Flashing with Preformed Flashing ..................1354
A-MTL-13 Plumbing Vent Flashing ....................................................................................1355
A-MTL-14 Raised Curb for Rooftop Equipment....................................................................1356
A-MTL-15 Counterflashing Options for Raised Curbs............................................................1357
A-MTL-16 Low-Slope Membrane to Metal Roof Transition ....................................................1358
A-MTL-17 Metal Roof to Metal Roof Transition ...................................................................1359
A-MTL-18 Metal Wall to Metal Roof Transition ...................................................................1360
A-MTL-19 Continuous Roof-to-wall Panel Transition..............................................................1361

Contents 1025
The NRCA Roofing and Waterproofing Manual—Fifth Edition

Structural Metal Roofing


S-MTL-1 Downslope Perimeter Edge Metal Flashing ............................................................1362
S-MTL-1A Downslope Perimeter Edge Metal Flashing ..........................................................1363
S-MTL-2 Downslope Flashing with Gutter ...........................................................................1364
S-MTL-2A Downslope Flashing with Gutter .........................................................................1365
S-MTL-2B Downslope Flashing with Gutter .........................................................................1366
S-MTL-3 Rake Edge Flashing - Starter Panel.......................................................................1367
S-MTL-3A Rake Edge Flashing - End Panel..........................................................................1368
S-MTL-4 Ridge Cap Flashing ............................................................................................1369
S-MTL-4A Ridge Cap Flashing ..........................................................................................1370
S-MTL-5 Venting Ridge Cap Flashing .................................................................................1371
S-MTL-5A Venting Ridge Cap Flashing ...............................................................................1372
S-MTL-6 Hip Cap Flashing with Panel End Stiffening Metal ....................................................1373
S-MTL-6A Hip Cap Flashing with Hip Support Metal .............................................................1374
S-MTL-7 Open Valley Metal (Fastened)...............................................................................1375
S-MTL-7A Open Valley Metal (Cleated) ...............................................................................1376
S-MTL-8 Roof-to-Wall (Headwall) Transition ........................................................................1377
S-MTL-9 Roof-to-Wall (Sidewall) Transition - Starter Panel.....................................................1378
S-MTL-9A Roof-to-Wall (Sidewall) Transition - End Panel........................................................1379
S-MTL-10 Expansion Joint (Through-panel Fastened)............................................................1380
S-MTL-10A Expansion Joint .............................................................................................1381
S-MTL-11 Equipment Support Stand .................................................................................1382
S-MTL-12 Equipment Support Stand/Vent Stack Flashing with Preformed Flashing ..................1383
S-MTL-13 Raised Curb For Rooftop Units ..........................................................................1384
S-MTL-14 Counterflashing Options for Raised Curbs............................................................1385
Tables
METAL-TABLE 1 Guide for Sheet Metal Trim and Fascia Edges for Metal Roof Systems ............1386
METAL-TABLE 1 (Metric) Guide for Sheet Metal Trim and Fascia Edges for
Metal Roof Systems .......................................................................................................1387
METAL-TABLE 2 Some Examples of Seam and Clip Profiles ...................................................1388

SPF-based Roofing
SPF-1 Metal Parapet Cap (Coping) ...................................................................................1389
SPF-1S Metal Parapet Cap (Coping) ..................................................................................1390
SPF-2 Perimeter Edge Metal Flashing with Sealant (Foam Stop) ............................................1391
SPF-2S Perimeter Edge Metal Flashing with Sealant (Foam Stop) ..........................................1392
SPF-3 Perimeter Edge Metal Flashing (Foam Stop) .............................................................1393
SPF-3S Perimeter Edge Metal Flashing (Foam Stop) ............................................................1394
SPF-4 Surface-Mount Counterflashing ..............................................................................1395
SPF-4S Surface-Mount Counterflashing .............................................................................1396
SPF-5 Base Flashing for Wall-Supported Deck ....................................................................1397
SPF-5S Base Flashing for Wall-Supported Deck ..................................................................1398
1026 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SPF-5A Base Flashing for Vented Base Sheet.....................................................................1399


SPF-5AS Base Flashing for Vented Base Sheet ...................................................................1400
SPF-6 Base Flashing for Non-wall-supported Deck ..............................................................1401
SPF-6S Base Flashing for Non-wall-supported Deck .............................................................1402
SPF-7 Expansion Joint with Metal Cover ............................................................................1403
SPF-7S Expansion Joint with Metal Cover...........................................................................1404
SPF-7A Expansion Joint with Premanufactured Cover ..........................................................1405
SPF-7AS Expansion Joint with Premanufactured Cover ........................................................1406
SPF-8 Roof System Divider ..............................................................................................1407
SPF-8S Roof System Divider ............................................................................................1408
SPF-9 Equipment Support Curb .......................................................................................1409
SPF-9S Equipment Support Curb ......................................................................................1410
SPF-10 Equipment Support Stand ....................................................................................1411
SPF-11 Equipment Support Stand Support Column .............................................................1412
SPF-11S Equipment Support Stand Support Column............................................................1413
SPF-12 Raised Curb Detail for Rooftop Air Handling Units and Ducts (Prefabricated
Metal Curb) ..................................................................................................................1414
SPF-12S Raised Curb Detail for Rooftop Air Handling Units and Ducts (Prefabricated
Metal Curb) ..................................................................................................................1415
SPF-13 Raised Curb Detail for Rooftop Air Handling Units and Ducts (Job Site Constructed
Wood Curb) ..................................................................................................................1416
SPF-13S Raised Curb Detail for Rooftop Air Handling Units and Ducts (Job Site Constructed
Wood Curb) ..................................................................................................................1417
SPF-14 Skylight, Scuttle and Smoke Vent...........................................................................1418
SPF-14S Skylight, Scuttle and Smoke Vent .........................................................................1419
SPF-15 Structural Member Through Roof Deck ..................................................................1420
SPF-15S Structural Member Through Roof Deck ................................................................1421
SPF-16 Sheet Metal Enclosure for Piping...........................................................................1422
SPF-16S Sheet Metal Enclosure for Piping .........................................................................1423
SPF-16A SPF Enclosure for Piping ....................................................................................1424
SPF-16AS SPF Enclosure for Piping ..................................................................................1425
SPF-17 Isolated Stack Flashing .......................................................................................1426
SPF-17S Isolated Stack Flashing.......................................................................................1427
SPF-18 Deck Supported Penetration.................................................................................1428
SPF-19 Non-Deck Supported Penetration .........................................................................1429
SPF-20 Roof Drain .........................................................................................................1430
SPF-20S Roof Drain .......................................................................................................1431
SPF-20A Alternate Roof Drain ........................................................................................1432
SPF-20AS Alternate Roof Drain........................................................................................1433
SPF-21 Primary Drainage Scupper at Parapet Wall ............................................................1434
SPF-21S Primary Drainage Scupper at Parapet Wall ...........................................................1435
SPF-22 Gutter ...............................................................................................................1436

Contents 1027
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SPF-22S Gutter .............................................................................................................1437


SPF-23 Low-Slope to Steep-Slope Transition .......................................................................1438
SPF-2(FB) Embedded Edge Metal Flashing (Gravel-Stop) .......................................................1439
SPF-5(FB) Base Flashing for Wall-supported Deck ...............................................................1440
SPF-6(FB) Base Flashing for Non-wall-supported Deck..........................................................1441
SPF-11(FB) Equipment Support Stand Leg (Field Wrap)........................................................1442
SPF-18(FB) Plumbing Vent (Premanufactured Boot).............................................................1443
SPF-20(FB) Roof Drain....................................................................................................1444
SPF-TABLE 1 Guide for Sheet Metal Fascia Edges for Spray Polyurethane Foam ......................1445
SPF-TABLE 1 (Metric) Guide for Sheet Metal Fascia Edges for Spray Polyurethane Foam ..........1446
SPF-TABLE 2.1 Options for Termination of Wall Counterflashings ..........................................1447
SPF-TABLE 2.2 Options for Termination of Wall Counterflashings ..........................................1448
SPF-TABLE 2.3 Options for Termination of Wall Counterflashings ..........................................1449
SPF-TABLE 3 Guide for Sheet Metal Parapet Cap (Coping)....................................................1450
SPF-TABLE 4 Guide for Clearances Between Pipes/Walls/Curbs ..........................................1451
SPF-TABLE 5 Guide for Crickets and Saddles......................................................................1452
SPF-TABLE 6 Guide for Edge Scuppers with Tapered Saddles ................................................1453

Waterproofing
WP-1 Foundation Wall with Hydrostatic Pressure Relief System............................................1454
WP-1S Foundation Wall with Hydrostatic Pressure Relief System ..........................................1455
WP-2 Foundation Wall and Pressure Mat Slab-on-grade ......................................................1456
WP-2S Foundation Wall and Pressure Mat Slab-on-grade ....................................................1457
WP-3 Negative Side Waterproofing ..................................................................................1458
WP-3S Negative Side Waterproofing ................................................................................1459
WP-4 Foundation Wall Brick Ledge...................................................................................1460
WP-4S Foundation Wall Brick Ledge .................................................................................1461
WP-5 Foundation Wall Counterflashing at Grade.................................................................1462
WP-5S Foundation Wall Counterflashing at Grade...............................................................1463
WP-6 Built-In Planter with Weep Drainage .........................................................................1464
WP-6S Built-In Planter with Weep Drainage .......................................................................1465
WP-7 Built-In Planter with Interior Drainage .......................................................................1466
WP-7S Built-In Planter with Interior Drainage .....................................................................1467
WP-8 Foundation Wall Penetration ...................................................................................1468
WP-8S Foundation Wall Penetration .................................................................................1469
WP-9 Plaza Deck Drain - Concrete Wear Surface ...............................................................1470
WP-9S Plaza Deck Drain - Concrete Wear Surface .............................................................1471
WP-10 Plaza Deck Drain - Paver Wear Surface..................................................................1472
WP-10S Plaza Deck Drain - Paver Wear Surface ................................................................1473

1028 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL PARAPET


CAP SLOPED TO DRAIN
ROOF SIDE

CONTINUOUS CLEAT EXTENDED BASE FLASHING -


FASTENED PER TABLE 1 OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS
ARE USED WITH THE
METAL PARAPET CAP

GASKETED FASTENERS

CONTINUOUS SHIM

FASTENERS APPROX. 8''


[200 mm] O.C.
1'' [25 mm] MIN.
BELOW BLOCKING

WOOD NAILER

PRIME SURFACE AS
REQUIRED

OPTIONAL: EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT
AP
[10 PRO
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION
CANT
THERMAL INSULATION
ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL BUR-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET MEMBRANE LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING)


AND BASE FLASHING
BUR-1
2001 NOT DRAWN TO SCALE

1029
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL PARAPET


CAP SLOPED TO DRAIN
ROOF SIDE
CONTINUOUS CLEAT CONTINUOUS SHIM
FASTENED PER TABLE 1
WOOD NAILER

EXTENDED BASE FLASHING


OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS
ARE USED WITH THE
METAL PARAPET CAP

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
BELOW BLOCKING
1'' [25 mm] MIN.

CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING FEATHERED
AT FIELD OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL BUR-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET MEMBRANE LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING)


AND BASE FLASHING
BUR-1S
2001 NOT DRAWN TO SCALE

1030
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL FASCIA CAP

GASKETED FASTENERS

FASTEN BASE FLASHING


APPROX. 8'' [200 mm] O.C.

WOOD CANT FASTEN TO


BLOCKING

AP
[10 PRO
BELOW BLOCKING

0 m X. 4
m] ''
1'' [25 mm] MIN.

MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF

EXTEND ONE BASE


FLASHING PLY BELOW
BLOCKING

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD NAILERS

CONTINUOUS CLEAT
FASTENED PER TABLE 1

NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)
BUR-2
2001 NOT DRAWN TO SCALE

1031
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL FASCIA CAP

EXTEND ONE BASE


FLASHING PLY
BELOW BLOCKING

FASTEN BASE FLASHING


APPROX. 8'' [200 mm] O.C.

GASKETED FASTENERS

MULTIPLE-PLY MEMBRANE
BASE FLASHING FEATHERED
AT FIELD OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
BELOW BLOCKING
1'' [25 mm] MIN.

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD CANT FASTEN TO


BLOCKING

WOOD NAILERS

CONTINUOUS CLEAT
NOTES : (FASTENED PER TABLE 1)

1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)
BUR-2S
2001 NOT DRAWN TO SCALE

1032
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MULTIPLE-PLY
MEMBRANE STRIPPING FLANGE APPROX.
FEATHERED AT FIELD 4'' [100 mm] WIDE
OF ROOF 2" [50 mm]
MIN.
FASTENERS 3'' TO 6'' 2" [50 mm]
[75 TO 150 mm] O.C., MIN.
STAGGERED
BELOW BLOCKING
1'' [25 mm] MIN.

SHEET METAL ''GRAVEL-


STOP'' SET IN
COMPATIBLE ROOF
CEMENT - PRIME FLANGE
BEFORE STRIPPING
FELT ENVELOPE
(FOR COAL TAR AND
ASPHALT TYPES I AND II)
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION
AND THERMAL
INSULATION

ROOF DECK

WOOD NAILERS

EXTEND ONE PLY OR A


SEPARATE MEMBRANE
SHEET TO BELOW BLOCKING

CONTINUOUS CLEAT
NOTES : (FASTENED PER TABLE 1)

1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE
EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE. (SEE BUR-2 FOR THE PREFERRED PERIMETER
CONSTRUCTION.)
2. WHEN USING A GRANULE CAP SHEET AS SURFACING, THE METAL FLANGE AND ASSOCIATED
STRIPPING PLIES CAN BE INSTALLED BENEATH THE CAP SHEET.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)
BUR-3
2001 NOT DRAWN TO SCALE

1033
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ''GRAVEL-


STOP'' SET IN
COMPATIBLE ROOF
CEMENT - PRIME FLANGE
BEFORE STRIPPING

FELT ENVELOPE
(FOR COAL TAR AND
ASPHALT TYPES I AND II)

FASTENERS AT APPROX.
3'' TO 6'' [75 TO 150 mm]
O.C., STAGGERED

MULTIPLE-PLY
MEMBRANE STRIPPING
FEATHERED AT
FIELD OF ROOF
BELOW BLOCKING
1'' [25 mm] MIN.

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION
AND THERMAL
INSULATION

ROOF DECK

EXTEND ONE PLY OR A


SEPARATE MEMBRANE
SHEET TO BELOW BLOCKING

CONTINUOUS CLEAT
(FASTENED PER TABLE 1)

NOTES :

1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE
EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE. (SEE BUR-1 FOR THE PREFERRED PERIMETER
CONSTRUCTION.)
2. WHEN USING A GRANULE CAP SHEET AS SURFACING, THE METAL FLANGE AND ASSOCIATED
STRIPPING PLIES CAN BE INSTALLED BENEATH THE CAP SHEET.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND
SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)
BUR-3S
2001 NOT DRAWN TO SCALE

1034
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SMOOTH CONCRETE

INSTALL APPROPRIATE SEALANT


AND (E.G., POLYURETHANE) TOOL
TO FACILITATE WATER RUN-OFF

CONCRETE FASTENERS

SHEET METAL COUNTERFLASHING

OPTIONAL : COMPRESSIBLE
ELASTOMETRIC SEALANT OR
TAPE TO SPAN IRREGULARITIES

SEAL TOP OF FLASHING


WITH A COMPATIBLE
VERTICAL GRADE ROOF CEMENT
FASTENERS APPROX.
8'' [200 mm] O.C.
PRIME CONCRETE TO TOP
OF BASE FLASHING

AP OPTIONAL :
[10 PRO EXTENDED FIELD PLIES
0 m X. 4
m] '' ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF ROOF

CANT

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

NOTES : ROOF DECK


1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. COUNTERFLASHING DETAIL MAY BE A TWO-PIECE REGLET AND COUNTERFLASHING (SEE TABLE 2 FOR
ALTERNATE SHEET METAL COUNTERFLASHING).
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
BUR-4
2001 NOT DRAWN TO SCALE

1035
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SMOOTH CONCRETE

INSTALL APPROPRIATE SEALANT


AND (E.G., POLYURETHANE) TOOL
TO FACILITATE WATER RUN-OFF
OPTIONAL : COMPRESSIBLE
ELASTOMETRIC SEALANT OR
TAPE TO SPAN IRREGULARITIES
CONCRETE FASTENERS

SEAL TOP OF FLASHING WITH A


COMPATIBLE VERTICAL
GRADE ROOF CEMENT
SHEET METAL COUNTERFLASHING

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES : CANT

1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. COUNTERFLASHING DETAIL MAY BE A TWO-PIECE REGLET AND COUNTERFLASHING (SEE TABLE 2 FOR
ALTERNATE SHEET METAL COUNTERFLASHING).
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
BUR-4S
2001 NOT DRAWN TO SCALE

1036
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTER FLASHING
SEAL TOP OF FLASHING
WITH A COMPATIBLE
VERTICAL GRADE ROOF
CEMENT
FASTENERS APPROX. 8''
[200 mm] O.C.
AP
[10 PRO PRIME SURFACE
0 m X. 4
m] '' AS REQUIRED
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVER BOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES : CANT
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


WALL-SUPPORTED DECK
BUR-5
2001 NOT DRAWN TO SCALE

1037
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

REMOVABLE SHEET METAL


COUNTER FLASHING

SEAL TOP OF FLASHING WITH


A COMPATIBLE VERTICAL
GRADE ROOF CEMENT

FASTENERS APPROX. 8''


[200 mm] O.C.

OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)

CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8'' [200 mm]
MIN. HEIGHT) FEATHERED
AT FIELD OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVER BOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


WALL-SUPPORTED DECK
BUR-5S
2001 NOT DRAWN TO SCALE

1038
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTER FLASHING

FASTENERS APPROX. 8''


[200 mm] O.C.
VENTED BASE SHEET (DO NOT
ADHERE OR SEAL TO
WALL) FASTENED APPROX.
8'' [200 mm] O.C.

OPTIONAL :
EXTEND FIELD PLIES
ABOVE HEAD OF CANT

AP
[10 PRO
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
SUITABLE BASE SHEET
FASTENERS
LIGHTWEIGHT INSULATING
CONCRETE

DECK
NOTES :
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS. (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. ALL PLIES ARE TO BE SOLIDLY MOPPED TO THE BASE SHEET. CARE SHOULD BE USED NOT TO ADHERE
THE BASE SHEET TO THE WALL.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


VENTED BASE SHEET
BUR-5A
2001 NOT DRAWN TO SCALE

1039
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS
VENTED BASE SHEET (DO NOT
ADHERE OR SEAL TO
WALL) FASTENED
APPROX. 8'' [200 mm] O.C.
REMOVABLE SHEET METAL
COUNTERFLASHING
FASTENERS APPROX. 8''
[200 mm] O.C.
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8'' [200 mm]
MIN. HEIGHT) FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

SUITABLE BASE SHEET


FASTENERS

LIGHTWEIGHT INSULATING
CONCRETE

CANT

DECK

NOTES :
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS. (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. ALL PLIES ARE TO BE SOLIDLY MOPPED TO THE BASE SHEET. CARE SHOULD BE USED NOT TO ADHERE
THE BASE SHEET TO THE WALL.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


VENTED BASE SHEET
BUR-5AS
2001 NOT DRAWN TO SCALE

1040
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

OPTIONAL : MEMBRANE SHEET


CLOSURE SECURED AND ADHERED
TO WALL

REMOVABLE SHEET METAL


COUNTER FLASHING

OPTIONAL :
EXTENDED BASE FLASHING

FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL :
AP EXTENDED FIELD PLIES
[10 PRO ABOVE HEAD OF CANT STRIP
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE BASE


FLASHING (8'' [200 mm] HEIGHT
MIN.) - FEATHERED AT FIELD OF
ROOF - COVER TOP OF BASE
FLASHING WITH VAPOR RETARDER
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVER BOARD INSULATION

THERMAL INSULATION
CANT
ROOF DECK
FLEXIBLE VAPOR RETARDER WITH
NOTES : COMPRESSIBLE INSULATION
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL
OCCUR BETWEEN THE DECK AND A VERTICAL SURFACE. THE WOOD MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK
BUR-6
2001 NOT DRAWN TO SCALE

1041
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

OPTIONAL: MEMBRANE
SHEET CLOSURE SECURED
AND ADHERED TO WALL

REMOVABLE SHEET METAL


COUNTERFLASHING
OPTIONAL :
EXTENDED BASE FLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
STRIP (NOT SHOWN
FOR CLARITY)

CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF - COVER TOP OF
BASE FLASHING WITH
VAPOR RETARDER
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

FLEXIBLE VAPOR
RETARDER WITH
COMPRESSIBLE
INSULATION
NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL
MOVEMENT WILL OCCUR BETWEEN THE DECK AND A VERTICAL SURFACE. THE WOOD
MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK
BUR-6S
2001 NOT DRAWN TO SCALE

1042
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EXPANSION


JOINT COVER
FLEXIBLE WEATHERPROOF
MEMBRANE CLOSURE.
OPTIONAL IF DOUBLE LOCK TOP OF CURB TO
STANDING SEAM JOINTS ARE DRAIN TO ONE SIDE
USED WITH THE METAL CAP
FASTENERS APPROX. 8''
EXTENDED BASE [200 mm] O.C.
FLASHING
COMPRESSIBLE GASKETED FASTENERS
INSULATION
FLASHING HEIGHT ON
LOW SIDE
8'' [200 mm] MIN.

AP
[10 PRO
0 m X. 4
m] ''

OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT
FIELD OF ROOF

FLEXIBLE MULTIPLE-PLY BUILT-UP


VAPOR RETARDER TO ROOF MEMBRANE
SERVE AS INSULATION
RETAINER (ATTACHED COVERBOARD INSULATION
TO TOP OF CURB)
THERMAL INSULATION
WOOD NAILERS

CANT
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

BUR-7
2001 NOT DRAWN TO SCALE

1043
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE WEATHERPROOF
MEMBRANE CLOSURE
OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS ARE USED
SHEET METAL EXPANSION
WITH THE METAL CAP
JOINT COVER
COMPRESSIBLE
INSULATION TOP OF CURB TO
DRAIN TO ONE SIDE
OPTIONAL :
EXTENDED BASE FASTENERS APPROX. 8''
FLASHING (NOT [200 mm] O.C.
SHOWN FOR CLARITY)

GASKETED FASTENERS
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
FLASHING HEIGHT

MULTIPLE-PLY MEMBRANE
8'' [200 mm] MIN.

ON LOW SIDE

BASE FLASHING
FEATHERED AT
FIELD OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

CANT
COVERBOARD INSULATION
WOOD NAILERS
THERMAL INSULATION

ROOF DECK

FLEXIBLE VAPOR RETARDER


TO SERVE AS INSULATION
RETAINER (ATTACHED TO
TOP OF CURB)
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

BUR-7S
2001 NOT DRAWN TO SCALE

1044
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE
PRE-MANUFACTURED
OPTIONAL : EXPANSION JOINT COVER
EXTENDED
BASE FLASHING

COMPRESSIBLE
INSULATION

GASKETED FASTENERS
FLASHING HEIGHT
8'' [200 mm] MIN.

FASTENERS APPROX. 8''


[200 mm] O.C.

TOP OF CURB TO
DRAIN TO OUTSIDE

OPTIONAL :
AP EXTENDED FIELD PLIES
[10 PRO ABOVE HEAD OF CANT
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED
AT FIELD OF ROOF
FLEXIBLE VAPOR
RETARDER TO SERVE AS MULTIPLE-PLY BUILT-UP
INSULATION RETAINER ROOF MEMBRANE
(ATTACHED TO TOP OF
CURB) COVERBOARD INSULATION
CANT
THERMAL INSULATION
WOOD NAILERS ROOF DECK

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECURMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH


PRE-MANUFACTURED COVER
BUR-7A
2001 NOT DRAWN TO SCALE

1045
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE

COMPRESSIBLE PRE-MANUFACTURED
INSULATION EXPANSION JOINT COVER

OPTIONAL :
EXTENDED BASE TOP OF CURB TO
FLASHING DRAIN OUTSIDE

FASTENERS APPROX. 8''


[200 mm] O.C.

GASKETED FASTENERS
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
FLASHING HEIGHT

MULTIPLE-PLY MEMBRANE
8'' [200 mm] MIN.

BASE FLASHING
FEATHERED AT FIELD OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

ROOF DECK COVERBOARD INSULATION

CANT THERMAL INSULATION

WOOD NAILERS

FLEXIBLE VAPOR RETARDER


TO SERVE AS INSULATION RETAINER
(ATTACHED TO TOP OF CURB)

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH


PRE-MANUFACTURED COVER
BUR-7AS
2001 NOT DRAWN TO SCALE

1046
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL AREA


DIVIDER COVER

GASKETED FASTENERS
FLASHING HEIGHT
8'' [200 mm] MIN.

FASTENERS APPROX. 8''


AP
[200 mm] O.C.
[10 PRO
0 m X. 4
m] ''

OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF
WOOD NAILERS
MULTIPLE-PLY BUILT-UP
CANT ROOF MEMBRANE

ROOF DECK COVERBOARD INSULATION

THERMAL INSULATION

NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

AREA DIVIDER IN ROOF SYSTEM

BUR-8
2001 NOT DRAWN TO SCALE

1047
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL AREA


DIVIDER COVER

FASTENERS APPROX. 8''


[200 mm] O.C.

GASKETED FASTENERS

OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)

MULTIPLE-PLY MEMBRANE
FLASHING HEIGHT

BASE FLASHING
8'' [200 mm] MIN.

FEATHERED AT
FIELD OF ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

CANT

WOOD NAILERS

NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE
ROOF DECK. AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

AREA DIVIDER IN ROOF SYSTEM

BUR-8S
2001 NOT DRAWN TO SCALE

1048
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEIGHT SET BOLTS IN SEALANT


WIDTH OF EQUIPMENT OF LEGS
(BY OTHERS)
UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
SET NEOPRENE PAD IN
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
SEALANT (BY OTHERS)
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.

SHEET METAL COVER

OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
AP FEATHERED AT FIELD
[10 PRO
0 m X. 4 OF ROOF
m] ''

WOOD CURB

WOOD NAILERS

ROOF DECK
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
CANT
COVERBOARD INSULATION
NOTES : THERMAL INSULATION
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHT-WEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL BUR-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FORM JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT CURB

BUR-9
2001 NOT DRAWN TO SCALE

1049
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEIGHT
WIDTH OF EQUIPMENT OF LEGS
UP TO 24'' [UP TO 600 mm] 24'' [600 mm]

SET BOLTS IN SEALANT 24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
(BY OTHERS) 48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]
SHEET METAL
COVER SET NEOPRENE PAD IN
SEALANT (BY OTHERS)
GASKETED
FASTENERS

FASTENERS
APPROX. 8'' OPTIONAL :
[200 mm] O.C. EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR
CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

ROOF DECK COVERBOARD INSULATION


WOOD CURB
THERMAL INSULATION
WOOD NAILERS

CANT
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHT-WEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL BUR-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE SHEET METAL SECTIONS OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT CURB

BUR-9S
2001 NOT DRAWN TO SCALE

1050
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL FRAME

HEIGHT-
SEE TABLE

LE
AB
E ET
SEE DETAIL -S
H
BUR-11 FOR FLASHING IDT
W
OF SUPPORT LEGS

ROUND PIPE COLUMN

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL BUR-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED DIRECTLY OVER
COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE ADAPTED FOR OTHER USES,
SUCH AS SIGN SUPPORTS.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND

BUR-10
2001 NOT DRAWN TO SCALE

1051
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G., POLYURETHANE)
FOR HEIGHT OF LEGS
SEE TABLE ON BUR-10

DRAWBAND

SHEET METAL RAIN COLLAR


OVERLAPPING FLASHING
COLLAR BY 3'' TO 4''
[75 mm TO 100 mm]

MULTIPLE MEMBRANE
STRIPPING PLY-
FEATHER PLIES

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

SHEET METAL FLASHING


COLLAR MINIMUM OF 8''
[200 mm] ABOVE ROOFING
AP
PR
[10 O 1/4'' [6 mm] MINIMUM
0 m X. 4'
m] ' CLEARANCE BETWEEN
FLASHING COLLAR
AND SUPPORT

COMPATIBLE ROOF CEMENT


OR COMPATIBLE SEALANT
AT PENETRATION TO
MEMBRANE JUNCTURE
4'' [100 mm] MINIMUM
FLANGE SET IN
COMPATIBLE ROOF
CEMENT OVER BUILT-UP
PLIES - PRIME FLANGE
BEFORE STRIPPING
COVERBOARD INSULATION
THERMAL INSULATION
1/4'' [6 mm] MIN. CLEARANCE
TO RAIN COLLAR ROOF DECK
FILL GAPS WITH INSULATION
NOTES : BOARD TO PROVIDE
1. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION. EVEN SUBSTRATE

EQUIPMENT SUPPORT STAND AND


TYPICAL RAIN COLLAR PENETRATION
DETAIL BUR-11
2001 NOT DRAWN TO SCALE

1052
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRAWBAND

SHEET METAL RAIN COLLAR


APPROPRIATE OVERLAPPING FLASHING
SEALANT (E.G., COLLAR BY 3'' TO 4''
POLYURETHANE) [75 mm TO 100 mm]
SHEET METAL FLASHING
1/4'' [6 mm] COLLAR MINIMUM OF 8''
MIN. CLEARANCE [200 mm] ABOVE ROOFING
TO RAIN COLLAR 1/4'' [6 mm] MINIMUM
CLEARANCE BETWEEN FLASHING
COLLAR AND SUPPORT
COMPATIBLE ROOF CEMENT
FOR HEIGHT OF LEGS
SEE TABLE ON BUR-10

OR COMPATIBLE SEALANT
AT PENETRATION TO
MEMBRANE JUNCTURE
4'' [100 mm] MINIMUM FLANGE
SET IN COMPATIBLE ROOF
CEMENT OVER FIELD PLIES -
PRIME FLANGE BEFORE
STRIPPING
MULTIPLE-PLY MEMBRANE
STRIPPING PLIES -
FEATHER PLIES

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION
ROOF DECK

FILL GAPS WITH INSULATION


BOARD TO PROVIDE EVEN
SUBSTRATE
NOTES :
1. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND AND


TYPICAL RAIN COLLAR PENETRATION
DETAIL
BUR-11S
2001 NOT DRAWN TO SCALE

1053
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RAISED CURB

WOOD NAILER
SEALING MATERIAL

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING

FASTENERS APPROX. 8''


[200 mm] O.C.

AP
[10 PRO
0 m X. 4
m] ''
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
ALTERNATE [200 mm] MIN. HEIGHT)
CURB BEARING FEATHERED AT FIELD OF
LOCATION FOR ROOF
HEAVY WEIGHT
LOADING MULTIPLE-PLY BUILT-UP
CONDITIONS WOOD NAILER ROOF MEMBRANE

COVERBOARD INSULATION

ALTERNATE : MECHANICAL UNIT, HOOD, ETC. THERMAL INSULATION


BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND ROOF DECK
TOP OF CURB
SEALING MATERIAL - MUST BE
CONTINUOUS ON TOP OF THE CURB

1'' [25 mm] MINIMUM


BELOW TOP OF CURB
FLASHING RECEIVER
NOTES :
WOOD NAILER
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP
FASTENERS ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD
COUNTERFLASHING NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
BASE FLASHING 3. REFER TO THE SHEET METAL SECTION OF THE
RAISED CURB METAL ROOFING MANUAL FOR JOINERY AND
SECUREMENT OPTIONS FOR SHEET METAL.
INSULATION 4. REFER TO INTRODUCTION FOR ADDITIONAL
INFORMATION.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
BUR-12
2001 NOT DRAWN TO SCALE

1054
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RAISED CURB

SEALING
MATERIAL
GASKETED FASTENERS
WOOD NAILER MINIMUM TWO FASTENERS
PER SIDE

REMOVABLE SHEET
METAL COUNTERFLASHING
FASTENERS
APPROX. 8''
OPTIONAL: EXTENDED FIELD
[200 mm] O.C.
PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD NAILERS

ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
LOADING CONDITIONS
NOTES :
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
BUR-12S
2001 NOT DRAWN TO SCALE

1055
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALING MATERIAL

WOOD CURB

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

SHEET METAL
COUNTERFLASHING

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL : EXTENDED FIELD


PLIES ABOVE HEAD OF
CANT
AP
[10 PRO
0 m X. 4
m] ''

WOOD
NAILERS

CANT MULTIPLE-PLY MEMBRANE


BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
ALTERNATE : MECHANICAL UNIT, HOOD, ETC.
BASE OF UNIT EXTENDS 1/2'' MULTIPLE-PLY BUILT-UP
[13 mm] MINIMUM BEYOND ROOF MEMBRANE
TOP OF CURB
SEALING MATERIAL - MUST COVERBOARD INSULATION
BE CONTINUOUS ON TOP
OF THE CURB THERMAL INSULATION
1'' [25 mm] MINIMUM
BELOW TOP OF CURB ROOF DECK
FLASHING RECEIVER

FASTENERS

REMOVABLE
COUNTERFLASHING
BASE FLASHING
WOOD CURB

NOTES :
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
BUR-13
2001 NOT DRAWN TO SCALE

1056
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD CURB
SEALING MATERIAL

SHEET METAL
COUNTERFLASHING

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

CANT THERMAL INSULATION

WOOD ROOF DECK


NAILERS

NOTES :
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
BUR-13S
2001 NOT DRAWN TO SCALE

1057
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE No.1

AP
FASTENERS APPROX.
[10 PRO 8'' [200 mm] O.C.
0 m X. 4
m] ''
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
WOOD NAILERS FEATHERED AT FIELD OF
AND CURB ROOF

MULTIPLE-PLY BUILT-UP
CANT
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK
NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTIONS OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

BUR-14
2001 NOT DRAWN TO SCALE

1058
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL : REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE No.1
OPTIONAL : EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)

CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD NAILERS AND CURB

NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT AND FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

BUR-14S
2001 NOT DRAWN TO SCALE

1059
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)

INSULATE VOID TO
PREVENT CONDENSATION

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE SHEET
METAL COUNTERFLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL : EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

AP
[10 PRO
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

CANT

NOTES : WOOD NAILERS AND CURB

1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

STRUCTURAL MEMBER THROUGH


ROOF DECK
BUR-15
2001 NOT DRAWN TO SCALE

1060
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WELDED PLATE
SEALED WATERTIGHT
(BY OTHERS)

INSULATE VOID TO
PREVENT CONDENSATION

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
REMOVABLE SHEET
METAL COUNTERFLASHING
OPTIONAL : EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD NAILERS AND CURB

CANT

NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

STRUCTURAL MEMBER THROUGH


ROOF DECK
BUR-15S
2001 NOT DRAWN TO SCALE

1061
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ENCLOSURE


WITH REMOVABLE TOP
-CROSSBREAK OR
SLOPE FOR DRAINAGE

INSULATE VOID
TO PREVENT
CONDENSATION

SHEET METAL OR
FLEX-TUBE COLLAR

SLOPE PIPES DOWN AND


AWAY FROM HOOD
OPTIONAL : REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
AP
[10 PRO FASTENERS APPROX. 8''
0 m X. 4
m] '' [200 mm] O.C.

OPTIONAL : EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT

MIN. 4'' [100 mm] MULTIPLE-PLY MEMBRANE


CLEARANCE FROM PIPE BASE FLASHING (8''
TO TOP OF CURB; [200 mm] MIN. HEIGHT)
MIN. 2'' [50 mm] FEATHERED AT FIELD
BETWEEN PIPES OF ROOF
MULTIPLE-PLY BUILT-UP
WOOD NAILERS ROOF MEMBRANE
AND CURB
COVERBOARD INSULATION
CANT THERMAL INSULATION
ROOF DECK

NOTES :

1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST PENETRATE THE ROOF.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK
BUR-16
2001 NOT DRAWN TO SCALE

1062
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ENCLOSURE INSULATE VOID


WITH REMOVABLE TOP TO PREVENT
-CROSSBREAK OR SLOPE CONDENSATION
FOR DRAINAGE
SHEET METAL OR
FLEX-TUBE COLLAR

SLOPE PIPES DOWN AND


AWAY FROM HOOD

MINIMUM 4'' [100 mm]


CLEARANCE FROM PIPE TO
TOP OF CURB; MIN. 2''
2'' [50 mm] BETWEEN PIPES

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
FASTENERS APPROX.
8'' [203 mm] O.C
OPTIONAL : REMOVABLE SHEET
METAL COUNTERFLASHING
SEE NOTE 3
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF

COVERBOARD INSULATION

THERMAL INSULATION

OPTIONAL: EXTENDED ROOF DECK


FIELD PLIES ABOVE HEAD OF
CANT (NOT SHOWN FOR CLARITY) MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
CANT

NOTES :

1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST PENETRATE THE ROOF.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK
BUR-16S
2001 NOT DRAWN TO SCALE

1063
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT

DRAWBAND OR WELD
COVER TO STACK

INSULATE VOID FOR


COLD STACKS

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE 3

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL : EXTENDED FIELD


PLIES ABOVE HEAD OF
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
METAL OR FEATHERED AT FIELD OF
GYPSUM LINER ROOF
IF REQUIRED
MULTIPLE-PLY BUILT-UP
VARIES ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK
CANT

NOTES : WOOD NAILERS


AND CURB
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE
STACK, AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE
MATERIAL HANDLED BY THE STACK.
3. WHERE THE ISOLATED STACK COVER OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
BUR-17
2001 NOT DRAWN TO SCALE

1064
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT

DRAWBAND OR WELD
COVER TO STACK

INSULATE VOID FOR


COLD STACKS

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL : REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE 3

OPTIONAL : EXTENDED FIELD


PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION
METAL OR
GYPSUM LINER
ROOF DECK
IF REQUIRED
CANT
NOTES :
WOOD NAILERS AND CURB
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE
STACK, AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE
MATERIAL HANDLED BY THE STACK.
3. WHERE THE ISOLATED STACK COVER OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO INTRODUCTIONS FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
BUR-17S
2001 NOT DRAWN TO SCALE

1065
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G., POLYURETHANE)
DRAWBAND

SHEET METAL RAIN COLLAR


SHEET METAL FLASHING
MIN. 8'' [200 mm] ABOVE
ROOF MEMBRANE

MULTIPLE MEMBRANE
STRIPPING PLIES -
FEATHER PLIES
COMPATIBLE ROOF CEMENT
OR COMPATIBLE SEALANT
AT FLASHING TO
MEMBRANE JUNCTURE

4'' [100 mm] MIN. FLANGE


SET IN COMPATIBLE ROOF
CEMENT OVER BUILT-UP
PLIES - PRIME FLANGE
BEFORE STRIPPING
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK

OPTIONAL :
METAL LINER
AND INSULATION
IF HOT PIPE

NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE
STACK WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING-SHEET METAL


(HOT OR COLD)
BUR-17A
2001 NOT DRAWN TO SCALE

1066
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE
SEALANT (E.G.,
POLYURETHANE)
DRAWBAND

COMPATIBLE ROOF
CEMENT OR
COMPATIBLE
SEALANT AT SHEET METAL
FLASHING TO RAIN COLLAR
MEMBRANE SHEET METAL
JUNCTURE FLASHING MIN. 8''
[200 mm] ABOVE
4'' [100 mm] MIN.
ROOF MEMBRANE
FLANGE SET IN
COMPATIBLE ROOF
MULTIPLE
CEMENT OVER
MEMBRANE
BUILT-UP PLIES -
STRIPPING PLIES -
PRIME FLANGE
FEATHER PLIES
BEFORE STRIPPING

MULTIPLE-PLY
BUILT-UP ROOF
MEMBRANE

OPTIONAL :
METAL LINER COVERBOARD
AND INSULATION INSULATION
IF HOT PIPE
THERMAL
INSULATION

ROOF DECK

NOTES :

1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE
STACK WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING-SHEET METAL


(HOT OR COLD)
BUR-17AS
2001 NOT DRAWN TO SCALE

1067
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TOP OF FLASHING CAPPED OR


ROLLED INTO PIPE
APPROXIMATELY 1'' [25 mm]

SOFT METAL PIPE FLASHING


SEE NOTE 1
PLUMBING VENT STACK

MULTIPLE MEMBRANE
STRIPPING PLIES FEATHERED
AT FIELD OF ROOF. PRIME
FLANGE BEFORE STRIPPING

4'' MIN. FLANGE


[100 mm]

APPROX 4''
[100 mm]

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION TO
MEMBRANE JUNCTURE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK
SET FLANGE IN COMPATIBLE
ROOF CEMENT
NOTES :

1. SOFT METAL PIPE FLASHING:


-SHEET LEAD : MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m2 ] OR
-SHEET COPPER: MINIMUM 16 OZ. [5 kg/m2]
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SEPARATOR SHEET (E.G., ASPHALT-
SATURATED ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT
CONTACT WITH PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

BUR-18
2001 NOT DRAWN TO SCALE

1068
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TOP OF FLASHING CAPPED


OR ROLLED INTO PIPE
APPROXIMATELY
1'' [25 mm]

PLUMBING VENT STACK

SOFT METAL PIPE


FLASHING
SEE NOTE 1

COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE

SET FLANGE IN
COMPATIBLE ROOF
CEMENT

4'' MIN.
FLANGE MULTIPLE MEMBRANE
[100 mm] STRIPPING PLIES
FEATHERED AT FIELD
OF ROOF. PRIME FLANGE
BEFORE STRIPPING
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :

1. SOFT METAL PIPE FLASHING:


-SHEET LEAD : MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m2 ] OR
-SHEET COPPER: MINIMUM 16 OZ. [5 kg/m2 ]
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SEPARATOR SHEET (E.G., ASPHALT-
SATURATED ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT
CONTACT WITH PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

BUR-18S
2001 NOT DRAWN TO SCALE

1069
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G. POLYURETHANE)
SHEET METAL RAIN
COLLAR OVERLAPPING DRAWBAND
PENETRATION POCKET
COMPATABLE ROOF
APPROX. 1/4''
CEMENT OR COMPATIBLE
[6 mm]
SEALANT AT
CLEARANCE
PENETRATION TO
AT CORNERS
MEMBRANE JUNCTION
MULTIPLE
MEMBRANE 4'' [100 mm] MIN.
STRIPPING FLANGE, SET IN
PLIES FEATHERED COMPATIBLE ROOF
AT FIELD OF CEMENT OVER BUILT-
ROOF UP ROOFING PLIES
PRIME FLANGE BEFORE
STRIPPING

AP
[10 PRO
0 m X. 4
m] ''

POURABLE
SEALANT

NON-SHRINK
GROUT

WEATHERPROOF
SHEET METAL PITCH PAN,
SOLDERED/WELDED
(4'' [100 mm] MIN. HEIGHT)

MULTIPLE-PLY
BUILT-UP ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS BECAUSE THEY
MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL BUR-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

BUR-19
2001 NOT DRAWN TO SCALE

1070
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G. POLYURETHANE)

DRAW BAND
SHEET METAL RAIN
COLLAR OVERLAPPING
POURABLE SEALANT PENETRATION POCKET

4'' [100 mm] MIN.


APPROX. 1/4''
FLANGE, SET IN
[6 mm] CLEARANCE
COMPATIBLE ROOF
AT CORNERS
CEMENT OVER BUILT-UP
ROOFING PLIES, PRIME
WEATHERPROOF FLANGE BEFORE
SHEET METAL PITCH STRIPPING
PAN, SOLDERED/
WELDED MULTIPLE MEMBRANE
(4'' [100 mm] STRIPPING PLIES
MIN. HEIGHT) FEATHERED AT FIELD
OF ROOF
COMPATIBLE ROOF CEMENT
MULTIPLE-PLY
OR COMPATIBLE SEALANT
BUILT-UP ROOF
AT PENETRATION TO
MEMBRANE
MEMBRANE JUNCTURE

COVERBOARD
INSULATION

THERMAL
INSULATION

ROOF DECK

NON-SHRINK GROUT

NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS BECAUSE THEY
MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL BUR-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

BUR-19S
2001 NOT DRAWN TO SCALE

1071
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OPTIONAL : 1''x4'' [25 mm x 100 mm]


30'' [750 mm] SQUARE MINIMUM,
SHEET METAL GRAVEL STOP,
2 1/2 LB. TO 4 LB. [12 TO 20 kg/m2 ]
APPROX. 30'' [750 mm] SQUARE,
LEAD OR 16 OZ. [5 kg/m2 ] SOFT COPPER
SET IN ROOF CEMENT
FLASHING SET ON FINISHED ROOF
MULTIPLE PLY IN COMPATIBLE ROOF CEMENT, PRIME
MEMBRANE TOP SURFACE BEFORE STRIPPING
STRIPPING PLIES
MULTIPLE MEMBRANE STRIPPING PLIES
COVERBOARD FEATHERED AT FIELD OF ROOF
INSULATION
DRAIN STRAINER

THERMAL
INSULATION

ROOF DECK

TAPERED
INSULATION

CLAMPING RING

DECK CLAMP

DRAIN BOWL

MEMBRANE FIELD
PLIES, METAL FLASHING,
AND STRIPPING PLIES ALL
EXTEND UNDER CLAMPING
RING
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COMPATIBLE
ROOF CEMENT
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. DO NOT APPLY COAL TAR OR DEAD LEVEL ASPHALT INTO DRAIN SUMP.
3. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

BUR-20
2001 NOT DRAWN TO SCALE

1072
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRAIN STRAINER

CLAMPING RING

MULTIPLE MEMBRANE STRIPPING PLIES


FEATHERED AT FIELD OF ROOF
30'' [750 mm] SQUARE MINIMUM,
2 1/2 LB. TO 4 LB. [12 TO 20 kg/m2 ]
LEAD OR 16 OZ. [5 kg/m2 ] SOFT COPPER
FLASHING SET ON FINISHED ROOF
IN COMPATIBLE ROOF CEMENT, PRIME
TOP SURFACE BEFORE STRIPPING

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE FEATHERED
AT FIELD OF ROOF

COVERBOARD
INSULATION

THERMAL
INSULATION

TAPERED INSULATION

ROOF DECK

MEMBRANE FIELD PLIES -


METAL FLASHING AND STRIPPING PLIES
ALL EXTEND UNDER CLAMPING RING

DECK CLAMP

DRAIN BOWL

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. DO NOT APPLY COAL TAR OR DEAD LEVEL ASPHALT INTO DRAIN SUMP.
3. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

BUR-20S
2001 NOT DRAWN TO SCALE

1073
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BEAD OF SEALANT

SHEET METAL SCUPPER


WITH SOLDERED JOINTS

OPTIONAL : 3/4'' x 3'' N. GASKETED FASTENERS


MI
[19 mm x 75 mm] MIN. 4'' mm]
0
''L'' SHAPED GRAVEL [10
GUARD SECURED TO THE SHEET METAL
SCUPPER FLANGE, NOTCHED FASCIA CAP
TO PERMIT DRAINAGE

SHEET METAL
CONDUCTOR
HEAD APPROX. 4'' [100 mm]
APPROX. 2'' [50 mm]

SUMP AREA IN FRONT


OF SCUPPER TO DRAIN
MULTIPLE-PLY MEMBRANE
STRIPPING FEATHERED
AT FIELD OF ROOF
FASTEN SCUPPER TO
BLOCKING, SET FLANGE
IN COMPATIBLE ROOF
CEMENT, PRIME FLANGE
BEFORE STRIPPING
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION

ROOF DECK

FELT ENVELOPE
(FOR COAL TAR AND
ASPHALT TYPES I AND II)
WOOD NAILERS

EXTEND ONE PLY OR


A SEPARATE MEMBRANE
NOTES : SHEET TO BELOW BLOCKING

1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.


2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND
SECUREMENT OPTIONS FOR SHEET METAL.

SCUPPER THROUGH RAISED


PERIMETER EDGE
BUR-21
2001 NOT DRAWN TO SCALE

1074
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
FASCIA CAP

FASTEN SCUPPER TO
SHEET METAL SCUPPER
BLOCKING, SET FLANGE
WITH SOLDERED JOINTS
IN COMPATIBLE ROOF
SET IN COMPATIBLE SEALANT
CEMENT, PRIME FLANGE
BEFORE STRIPPING
OPTIONAL : 3/4'' x 3''
[19 mm x 75 mm] MIN.
''L'' SHAPED GRAVEL MULTIPLE-PLY MEMBRANE
GUARD SECURED TO STRIPPING FEATHERED
THE SCUPPER FLANGE, AT FIELD OF ROOF
NOTCHED TO PERMIT
DRAINAGE SUMP AREA IN FRONT OF
SCUPPER TO DRAIN

SEALANT

COVERBOARD
INSULATION
THERMAL INSULATION

MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
ROOF DECK

FELT ENVELOPE
SHEET METAL (FOR COAL TAR AND
CONDUCTOR ASPHALT TYPES I AND II)
HEAD
EXTEND ONE PLY OR
A SEPARATE MEMBRANE
SHEET TO BELOW
BLOCKING

NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND
SECUREMENT OPTIONS FOR SHEET METAL.

SCUPPER THROUGH RAISED


PERIMETER EDGE
BUR-21S
2001 NOT DRAWN TO SCALE

1075
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MULTIPLE MEMBRANE
STRIPPING PLIES

FELT ENVELOPE (FOR


COAL TAR AND ASPHALT
TYPES I AND II) OPTION :

SHEET METAL EDGE


MULTIPLE-PLY FLASHING - SET FLANGE
BUILT-UP IN COMPATIBLE ROOF
ROOF MEMBRANE CEMENT - PRIME FLANGE
BEFORE STRIPPING

FASTENERS
3'' to 6''
[75 to 150 mm] O.C.,
STAGGERED

GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS

SHEET METAL GUTTER


THE FRONT OF THE
GUTTER SHOULD BE A
MINIMUM 1'' [25 mm]
LOWER THAN THE BACK
TO ALLOW FOR
OVERFLOW

OPTIONAL: GUTTER
BRACKET SUPPORT

OPTIONAL: STIFFENING
BAR

EXTEND ONE PLY OR


ROOF DECK A SEPARATE MEMBRANE
SHEET

NOTES :
WOOD NAILERS
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING BUR-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MATERIAL FOR JOINERY AND SECUREMENT OPTIONS.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

BUR-22
2001 NOT DRAWN TO SCALE

1076
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SET FLANGE IN
COMPATIBLE ROOF CEMENT

MULTIPLE MEMBRANE
STRIPPING PLIES

FELT ENVELOPE (FOR


COAL TAR AND ASPHALT
TYPES I AND II) MULTIPLE-PLY
BUILT-UP ROOF
SHEET METAL EDGE MEMBRANE
FLASHING - PRIME FLANGE
BEFORE STRIPPING

GUTTER SPACER
INSTALLED BETWEEN
GUTTER BRACKETS

SHEET
METAL GUTTER
THE FRONT OF THE GUTTER
SHOULD BE A MINIMUM 1'' [25 mm]
LOWER THAN THE BACK TO
ALLOW FOR OVERFLOW ROOF DECK

OPTIONAL : GUTTER WOOD NAILERS


BRACKET SUPPORT
FASTENERS
EXTEND ONE PLY OR A 3'' to 6''
SEPARATE MEMBRANE SHEET [75 to 150 mm] O.C.,
STAGGERED

NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING BUR-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MATERIAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

BUR-22S
2001 NOT DRAWN TO SCALE

1077
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTINUOUS CLEAT
FASTENED PER TABLE 1 SHEET METAL PARAPET
CAP SLOPED TO DRAIN
TO ROOF SIDE

EXTENDED BASE FLASHING-


BELOW BLOCKING

OPTIONAL IF DOUBLE LOCK


1'' [25 mm] MIN.

STANDING SEAM JOINTS ARE


USED WITH THE METAL
PARAPET CAP

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.

CONTINUOUS SHIM

WOOD NAILER

PRIME CONCRETE
AP
PR
[10 O
0 m X. 4
m] ''

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF
CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
CANT
SURFACING, THE MULTI-
PLY MEMBRANE BASE
COVERBOARD INSULATION FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
THERMAL INSULATION AND GRANULE-SURFACED
SHEET)
ROOF DECK
MULTIPLE-PLY MODIFIED
NOTES: BITUMEN ROOF MEMBRANE

1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL MB-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET FLASHING LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING)


AND BASE FLASHING

MB-1
2001 NOT DRAWN TO SCALE

1078
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EXTENDED BASE FLASHING -


SHEET METAL PARAPET OPTIONAL IF DOUBLE LOCK
CAP SLOPED TO DRAIN STANDING SEAM JOINTS
TO ROOF SIDE ARE USED WITH THE METAL
PARAPET CAP
BELOW BLOCKING

CONTINUOUS SHIM
WOOD NAILER
1''[25 mm] MIN.

GASKETED FASTENERS

FASTENERS APPROX. 8"


[200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN
THE BASE PLY AND
GRANULE-SURFACED
SHEET)
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
CANT

COVERBOARD INSULATION

THERMAL INSULATION
NOTES : ROOF DECK
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL MB-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET FLASHING LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING)


AND BASE FLASHING

MB-1S
2001 NOT DRAWN TO SCALE

1079
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL FASCIA CAP

GASKETED FASTENERS

FASTEN BASE FLASHING


APPROX. 8''
[200 mm] O.C.

WOOD CANT FASTEN TO


BLOCKING

MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
BELOW BLOCKING

OF ROOF. (FOR ROOF


1'' [25 mm] MIN.

SYSTEMS WITH FACTORY-


APPLIED GRANULE
SURFACING, THE MULTI-
AP PLY MEMBRANE BASE
P
[10 ROX FLASHING CAN BE
0 m . 4''
m] INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

EXTEND ONE BASE


FLASHING PLY BELOW
BLOCKING

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD NAILERS

CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)

2001 NOT DRAWN TO SCALE MB-2


1080
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL FASCIA CAP

EXTEND ONE BASE


FLASHING PLY
BELOW BLOCKING

FASTEN BASE FLASHING


APPROX. 8'' [200 mm] O.C.

GASKETED FASTENERS

MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
BELOW BLOCKING

COVERBOARD INSULATION
1'' [25 mm] MIN.

THERMAL INSULATION

ROOF DECK

WOOD CANT FASTEN TO


BLOCKING

WOOD NAILERS

CONTINUOUS CLEAT
NOTES : (FASTENED PER TABLE 1)

1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)
MB-2S
2001 NOT DRAWN TO SCALE

1081
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MODIFIED BITUMEN
MEMBRANE STRIPPING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF FLANGE APPROX.
SYSTEMS WITH FACTORY- 4'' [100 mm] WIDE
APPLIED GRANULE
SURFACING, THE
''GRAVEL STOP'' FLANGE
AND MEMBRANE STRIPPING
APPROX. 4''
CAN BE INSTALLED BETWEEN
[100 mm]
THE BASE PLY AND
GRANULE-SURFACED
SHEET)
BELOW BLOCKING
1'' [25mm] MIN.

OPTIONAL: COMPATIBLE
SEALANT AT JUNCTION
OF MEMBRANE AND
EDGE METAL

FASTENERS
3'' to 6''
[75 to 150 mm] O.C.,
STAGGERED

SHEET METAL
''GRAVEL-STOP'' SET
IN COMPATIBLE ROOF
CEMENT PRIME FLANGE
BEFORE STRIPPING

MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE

CONTINUOUS CLEAT COVERBOARD


(FASTENED PER INSULATION
TABLE 1)
THERMAL INSULATION
EXTEND ONE PLY OR A
SEPARATE MEMBRANE ROOF DECK
SHEET TO BELOW
BLOCKING WOOD NAILERS
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE
EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE. (SEE MB-2 FOR THE PREFERRED PERIMETER CONSTRUCTION.)
2. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)
MB-3
2001 NOT DRAWN TO SCALE

1082
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ''GRAVEL-


STOP'' SET IN COMPATIBLE
ROOF CEMENT - PRIME
FLANGE BEFORE STRIPPING OPTIONAL: COMPATIBLE
SEALANT AT JUNCTION
OF MEMBRANE AND
EDGE METAL

FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.,
STAGGERED

MODIFIED BITUMEN
MEMBRANE STRIPPING
FEATHERED AT FIELD OF
ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE ''GRAVEL
STOP'' FLANGE AND
MEMBRANE STRIPPING
CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)

MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE
BELOW BLOCKING
1'' [25mm] MIN.

COVERBOARD
INSULATION

THERMAL INSULATION

ROOF DECK

EXTEND ONE PLY OR A


SEPARATE MEMBRANE
SHEET TO BELOW
BLOCKING

CONTINUOUS CLEAT
(FASTENED PER TABLE 1)

NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE
EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE. (SEE MB-1 FOR THE PREFERRED PERIMETER CONSTRUCTION.)
2. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)
MB-3S
2001 NOT DRAWN TO SCALE

1083
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SMOOTH CONCRETE
INSTALL APPROPRIATE
SEALANT (E.G.,
POLYURETHANE) AND
TOOL TO FACILITATE
WATER RUN-OFF
CONCRETE FASTENERS
OPTIONAL: COMPRESSIBLE
ELASTOMERIC SEALANT
OR TAPE TO SPAN
IRREGULARITIES
PRIME CONCRETE TO
TOP OF BASE FLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
SEAL TOP OF FLASHING WITH
A COMPATIBLE VERTICAL
GRADE ROOF CEMENT
SHEET METAL
COUNTERFLASHING
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD
OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN.
HEIGHT) FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
AP SURFACING, THE MULTI-
[10 PRO PLY MEMBRANE BASE
0 m X. 4
m] '' FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
NOTES :
ROOF DECK
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. COUNTERFLASHING DETAIL MAY BE A TWO-PIECE REGLET AND COUNTERFLASHING
(SEE TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING).
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
MB-4
2001 NOT DRAWN TO SCALE

1084
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SMOOTH CONCRETE
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF

OPTIONAL: COMPRESSIBLE
ELASTOMERIC SEALANT OR
TAPE TO SPAN IRREGULARITIES
CONCRETE FASTENERS
SEAL TOP OF FLASHING WITH A
COMPATIBLE VERTICAL GRADE
ROOF CEMENT
SHEET METAL COUNTERFLASHING

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8'' [200 mm]
MIN. HEIGHT) FEATHERED AT
FIELD OF ROOF
(FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

CANT

THERMAL INSULATION
NOTES :
ROOF DECK
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. COUNTERFLASHING DETAIL MAY BE A TWO-PIECE REGLET AND COUNTERFLASHING
(SEE TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING).
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
MB-4S
2001 NOT DRAWN TO SCALE

1085
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

SEAL TOP OF FLASHING


WITH A COMPATIBLE
VERTICLE GRADE
ROOF CEMENT

PRIME SURFACE AS
REQUIRED

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF
CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
AP
ROOF (FOR ROOF
[10 PRO
0 m X. 4 SYSTEMS WITH FACTORY-
m] ''
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

CANT THERMAL INSULATION

ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR WALL-


SUPPORTED DECK
MB-5
2001 NOT DRAWN TO SCALE

1086
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

REMOVABLE SHEET METAL


COUNTERFLASHING

SEAL TOP OF FLASHING


WITH A COMPATIBLE
VERTICAL GRADE ROOF
CEMENT
FASTENERS APPROX.
8'' [200 mm] O.C.
PRIME SURFACE AS
REQUIRED
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF
CANT
CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR WALL-


SUPPORTED DECK
MB-5S
2001 NOT DRAWN TO SCALE

1087
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

VENTED BASE SHEET (DO NOT


ADHERE OR SEAL TO WALL)
FASTENED APPROX. 8''
[200 mm] O.C.

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL : EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
AP FEATHERED AT FIELD OF
[10 PRO ROOF (FOR ROOF
0 m X. 4
m] '' SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

SUITABLE BASE SHEET


FASTENERS
LIGHTWEIGHT INSULATING
CONCRETE
CANT DECK
NOTES :
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. ALL PLIES ARE TO BE SOLIDLY MOPPED TO THE BASE SHEET. CARE SHOULD BE USED NOT TO ADHERE
THE BASE SHEET TO THE WALL.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR VENTED


BASE SHEET
MB-5A
2001 NOT DRAWN TO SCALE

1088
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET


FASTENERS

FASTENERS APPROX.
8'' [200 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING

VENTED BASE SHEET (DO NOT


ADHERE OR SEAL TO WALL)
FASTENED APPROX. 8''
[200 mm] O.C.

FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT

CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF SYSTEMS
WITH FACTORY-APPLIED
GRANULE SURFACING, THE
MULTI-PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY AND
GRANULE-SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

SUITABLE BASE SHEET


FASTENERS
LIGHTWEIGHT INSULATING
CONCRETE
DECK

NOTES :
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. ALL PLIES ARE TO BE SOLIDLY MOPPED TO THE BASE SHEET. CARE SHOULD BE USED NOT TO ADHERE THE BASE
SHEET TO THE WALL.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR VENTED


BASE SHEET
MB-5AS
2001 NOT DRAWN TO SCALE

1089
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS

SHEET METAL REGLET

OPTIONAL: MEMBRANE
SHEET CLOSURE SECURED
AND ADHERED TO WALL

OPTIONAL: EXTENDED
BASE FLASHING

REMOVABLE SHEET METAL


COUNTERFLASHING

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT STRIP

FLEXIBLE VAPOR RETARDER


WITH COMPRESSIBLE
INSULATION

MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF - COVER TOP
OF BASE FLASHING WITH
VAPOR RETARDER (FOR ROOF
SYSTEMS WITH FACTORY-
AP APPLIED GRANULE SURFACING,
[10 PRO THE MULTI-PLY MEMBRANE
0 m X. 4
m] '' BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL OCCUR BETWEEN
THE DECK AND A VERTICAL SURFACE. THE WOOD MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK
MB-6
2001 NOT DRAWN TO SCALE

1090
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

OPTIONAL : MEMBRANE
SHEET CLOSURE SECURED
AND ADHERED TO WALL

REMOVABLE SHEET METAL


COUNTERFLASHING

OPTIONAL : EXTENDED
BASE FLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT STRIP (NOT SHOWN
FOR CLARITY)
FLEXIBLE VAPOR RETARDER
WITH COMPRESSIBLE
INSULATION

MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF - COVER TOP
OF BASE FLASHING WITH
VAPOR RETARDER (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE SURFACING,
THE MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION

CANT ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL OCCUR BETWEEN
THE DECK AND A VERTICAL SURFACE. THE WOOD MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK
MB-6S
2001 NOT DRAWN TO SCALE

1091
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OPTIONAL: EXTENDED
BASE FLASHING

FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
SHEET METAL EXPANSION
COMPRESSIBLE JOINT COVER
INSULATION
FLEXIBLE WEATHERPROOF
MEMBRANE CLOSURE -
OPTIONAL IF DOUBLE LOCK
HEIGHT ON LOW SIDE
MINIMUM FLASHING

STANDING SEAM JOINTS


ARE USED WITH THE
8'' [200 mm]

METAL CAP

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.

TOP OF CURB TO
DRAIN TO ONE SIDE
OPTIONAL: EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT

MULTIPLE-PLY MEMBRANE
AP BASE FLASHING
[10 PRO FEATHERED AT FIELD
0 m X. 4
m] '' OF ROOF - (FOR
ROOF SYSTEMS WITH
FACTORY-APPLIED
GRANULE SURFACING, THE
MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

CANT
MULTIPLE-PLY MODIFIED
WOOD NAILERS BITUMEN ROOF
MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

MB-7
2001 NOT DRAWN TO SCALE

1092
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EXPANSION FLEXIBLE WEATHERPROOF


JOINT COVER MEMBRANE CLOSURE
OPTIONAL IF DOUBLE LOCK
TOP OF CURB TO STANDING SEAM JOINTS
DRAIN TO ONE SIDE ARE USED WITH THE
METAL CAP
OPTIONAL: EXTENDED FASTENERS APPROX. 8''
BASE FLASHING [200 mm] O.C.

GASKETED FASTENERS
OPTIONAL: EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FLASHING HEIGHT ON LOW SIDE

FEATHERED AT FIELD
FLEXIBLE VAPOR
OF ROOF - (FOR
RETARDER TO
ROOF SYSTEMS WITH
SERVE AS INSULATION
8'' [200 mm] MINIMUM

FACTORY-APPLIED
RETAINER (ATTACHED
GRANULE SURFACING, THE
TO TOP OF CURB)
MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
COMPRESSIBLE
BASE PLY AND GRANULE-
INSULATION
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
CANT
BITUMEN ROOF MEMBRANE
WOOD NAILERS COVERBOARD INSULATION

ROOF DECK THERMAL INSULATION

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

MB-7S
2001 NOT DRAWN TO SCALE

1093
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OPTIONAL: EXTENDED
BASE FLASHING

FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
PREMANUFACTURED
COMPRESSIBLE EXPANSION JOINT COVER
INSULATION
FLEXIBLE WEATHERPROOF
MEMBRANE CLOSURE
8'' [200 mm] MINIMUM
FLASHING HEIGHT

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.

TOP OF CURB TO
DRAIN TO OUTSIDE
OPTIONAL: EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT

MULTIPLE-PLY MEMBRANE
AP BASE FLASHING
[10 PRO FEATHERED AT FIELD
0 m X. 4
m] '' OF ROOF - (FOR
ROOF SYSTEMS WITH
FACTORY-APPLIED
GRANULE SURFACING, THE
MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

CANT
MULTIPLE-PLY MODIFIED
WOOD NAILERS BITUMEN ROOF
MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
MB-7A
2001 NOT DRAWN TO SCALE

1094
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PREMANUFACTURED FLEXIBLE WEATHERPROOF


EXPANSION JOINT COVER MEMBRANE CLOSURE

FLEXIBLE VAPOR TOP OF CURB TO


RETARDER TO DRAIN TO OUTSIDE
SERVE AS INSULATION FASTENERS APPROX. 8''
RETAINER (ATTACHED [200 mm] O.C.
TO TOP OF CURB)
GASKETED FASTENERS
OPTIONAL: EXTENDED
BASE FLASHING OPTIONAL: EXTENDED
FIELD PLIES ABOVE
COMPRESSIBLE HEAD OF CANT
INSULATION
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF - (FOR
ROOF SYSTEMS WITH
FACTORY-APPLIED
8'' [200 mm] MINIMUM
FLASHING HEIGHT

GRANULE SURFACING, THE


MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
CANT BITUMEN ROOF
MEMBRANE
WOOD NAILERS COVERBOARD INSULATION

ROOF DECK THERMAL INSULATION

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
MB-7AS
2001 NOT DRAWN TO SCALE

1095
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MINIMUM FLASHING
8'' [200 mm]

HEIGHT

SHEET METAL AREA


DIVIDER COVER

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.

OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT

MULTIPLE-PLY MEMBRANE
AP BASE FLASHING
[10 PRO
0 m X. 4 FEATHERED AT FIELD OF
m] ''
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
CANT BASE PLY AND GRANULE-
SURFACED SHEET)
WOOD NAILERS

MULTIPLE-PLY MODIFIED
BITUMEN ROOF
MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

AREA DIVIDER IN ROOF SYSTEM

MB-8
2001 NOT DRAWN TO SCALE

1096
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL AREA


DIVIDER COVER

FASTENERS APPROX. 8''


[200 mm] O.C.

GASKETED FASTENERS

OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
MINIMUM FLASHING HEIGHT

APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
8'' [200 mm]

BASE PLY AND GRANULE-


SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF
MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

AREA DIVIDER IN ROOF SYSTEM

MB-8S
2001 NOT DRAWN TO SCALE

1097
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

SHEET METAL COVER

SET BOLTS IN SEALANT


(BY OTHERS)

SET NEOPRENE PAD IN


SEALANT (BY OTHERS)

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.

OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
AP BASE PLY AND GRANULE-
P
[10 ROX SURFACED SHEET)
0m .4
m] ''

MULTIPLE-PLY MODIFIED
WOOD CURB BITUMEN ROOF MEMBRANE

CANT COVERBOARD INSULATION


WOOD NAILERS
THERMAL INSULATION
ROOF DECK

NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL MB-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

EQUIPMENT SUPPORT CURB

MB-9
2001 NOT DRAWN TO SCALE

1098
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m] SET BOLTS IN SEALANT
(BY OTHERS)
SET NEOPRENE PAD IN
SEALANT (BY OTHERS)
SHEET METAL COVER

GASKETED FASTENERS

FASTENERS APPROX. 8''


[200 mm] O.C.
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
WOOD CURB BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
WOOD NAILERS
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL MB-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EQUIPMENT SUPPORT CURB

MB-9S
2001 NOT DRAWN TO SCALE

1099
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL FRAME

HEIGHT-
SEE TABLE

LE
AB
E ET
-S
TH
SEE DETAIL ID
W
MB-11 FOR FLASHING
OF SUPPORT LEGS

ROUND PIPE COLUMN

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL MB-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED DIRECTLY OVER
COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE ADAPTED FOR OTHER USES,
SUCH AS SIGN SUPPORTS.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND

MB-10
2001 NOT DRAWN TO SCALE

1100
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G., POLYURETHANE)

DRAWBAND

SHEET METAL RAIN COLLAR


FOR HEIGHT OF LEGS
SEE TABLE ON MB-10

OVERLAPPING FLASHING
COLLAR BY 3'' TO 4''
[75 mm TO 100 mm]

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

MODIFIED BITUMEN
MEMBRANE STRIPPING PLY

SHEET METAL FLASHING


COLLAR MINIMUM OF 8''
[200 mm] ABOVE ROOFING

1/4'' [6 mm] MINIMUM


CLEARANCE BETWEEN
FLASHING COLLAR
AND SUPPORT
AP COMPATIBLE ROOF CEMENT
[10 PRO OR COMPATIBLE SEALANT
0 m X. 4
m] '' AT PENETRATION TO
MEMBRANE JUNCTURE
4'' [100 mm] MINIMUM FLANGE
SET IN COMPATIBLE ROOF
CEMENT OVER FIELD PLIES
PRIME FLANGE BEFORE
STRIPPING (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE FLASHING
COLLAR FLANGE AND MULTI-
PLY MEMBRANE STRIPPING
CAN BE INSTALLED BETWEEN
THE BASE PLY AND GRANULE-
SURFACED SHEET)

COVERBOARD INSULATION

1/4'' [6 mm] MIN. CLEARANCE THERMAL INSULATION


TO RAIN COLLAR ROOF DECK

FILL GAPS WITH INSULATION


NOTES : BOARD TO PROVIDE
EVEN SUBSTRATE
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND AND TYPICAL


RAIN COLLAR PENETRATION DETAIL
MB-11
2001 NOT DRAWN TO SCALE

1101
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRAWBAND
SHEET METAL RAIN COLLAR
OVERLAPPING FLASHING
COLLAR BY 3'' TO 4''
[75 mm TO 100 mm]
SHEET METAL FLASHING
COLLAR MINIMUM OF 8''
APPROPRIATE
[200 mm] ABOVE ROOFING
SEALANT (E.G.,
POLYURETHANE) 1/4'' [6 mm] MINIMUM
CLEARANCE BETWEEN FLASHING
COLLAR AND SUPPORT
1/4'' [6 mm]
FOR HEIGHT OF LEGS

COMPATIBLE ROOF CEMENT


SEE TABLE ON MB-10

MIN. CLEARANCE
OR COMPATIBLE SEALANT
TO RAIN COLLAR
AT PENETRATION TO
MEMBRANE JUNCTURE
4'' [100 mm] MINIMUM FLANGE
SET IN ROOF COMPATIBLE
CEMENT OVER FIELD PLIES -
PRIME FLANGE BEFORE
STRIPPING (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE FLASHING
COLLAR FLANGE AND MULTI-
PLY MEMBRANE STRIPPING
CAN BE INSTALLED BETWEEN
THE BASE PLY AND GRANULE-
SURFACED SHEET)

MODIFIED BITUMEN MEMBRANE


STRIPPING PLY
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
FILL GAPS WITH INSULATION
NOTES : BOARD TO PROVIDE EVEN
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION. SUBSTRATE

EQUIPMENT SUPPORT STAND AND TYPICAL


RAIN COLLAR PENETRATION DETAIL
MB-11S
2001 NOT DRAWN TO SCALE

1102
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RAISED CURB SEALING MATERIAL


WOOD NAILER
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING

FASTENERS APPROX. 8''


[200 mm] O.C.

OPTIONAL: EXTENDED FIELD


AP
[10 PRO PLIES ABOVE HEAD OF CANT
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ALTERNATE ROOF (FOR ROOF
CURB BEARING SYSTEMS WITH FACTORY-
LOCATION FOR APPLIED GRANULE
HEAVY WEIGHT SURFACING, THE MULTI-
LOADING PLY MEMBRANE BASE
CONDITIONS WOOD NAILER FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
OPTIONAL : MECHANICAL UNIT, HOOD, ETC. SHEET)
BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND MULTIPLE-PLY MODIFIED
TOP OF CURB
BITUMEN ROOF MEMBRANE
SEALING MATERIAL - MUST
BE CONTINUOUS ON TOP
OF THE CURB COVERBOARD INSULATION
1'' [25 mm] MINIMUM
BELOW TOP OF CURB THERMAL INSULATION
FLASHING RECEIVER
ROOF DECK
WOOD NAILER
NOTES :
FASTENERS
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO
COUNTERFLASHING BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
BASE FLASHING BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
RAISED CURB HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INSULATION INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
MB-12
2001 NOT DRAWN TO SCALE

1103
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RAISED CURB

SEALING GASKETED FASTENERS


MATERIAL MINIMUM TWO FASTENERS
PER SIDE
WOOD NAILER
REMOVABLE SHEET
METAL COUNTERFLASHING

OPTIONAL : EXTENDED FIELD


PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
FASTENERS
APPROX. 8''
MULTIPLE-PLY MEMBRANE
[200 mm] O.C.
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD NAILERS

ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
NOTES : LOADING CONDITIONS
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
MB-12S
2001 NOT DRAWN TO SCALE

1104
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALING MATERIAL

WOOD CURB

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

SHEET METAL
COUNTERFLASHING

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED FIELD


AP PLIES ABOVE HEAD OF CANT
[10 PRO
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
WOOD BASE FLASHING (8''
NAILERS [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
CANT ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
ALTERNATE : MECHANICAL UNIT, HOOD, ETC.
BASE OF UNIT EXTENDS 1/2'' MULTIPLE-PLY MODIFIED
[13 mm] MINIMUM BEYOND BITUMEN ROOF MEMBRANE
TOP OF CURB
SEALING MATERIAL - MUST COVERBOARD INSULATION
BE CONTINUOUS ON TOP
OF THE CURB
1'' [25 mm] MINIMUM THERMAL INSULATION
BELOW TOP OF CURB
FLASHING RECEIVER ROOF DECK

WOOD NAILER

FASTENERS
NOTES :
COUNTERFLASHING
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
BASE FLASHING BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
RAISED CURB HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL
INSULATION INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
MB-13
2001 NOT DRAWN TO SCALE

1105
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD CURB
SEALING MATERIAL

SHEET METAL
COUNTERFLASHING

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

CANT COVERBOARD INSULATION

WOOD THERMAL INSULATION


NAILERS
ROOF DECK

NOTES :
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION FOR THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
MB-13S
2001 NOT DRAWN TO SCALE

1106
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE No.1

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED FIELD


AP
[10 PRO PLIES ABOVE HEAD OF CANT
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
WOOD NAILERS
AND CURB
MULTIPLE-PLY MODIFIED
CANT
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK
NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

MB-14
2001 NOT DRAWN TO SCALE

1107
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE No.1
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT

CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

ROOF DECK

WOOD NAILERS AND CURB

NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT AND FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

MB-14S
2001 NOT DRAWN TO SCALE

1108
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)

INSULATE VOID TO
PREVENT CONDENSATION

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE SHEET
METAL COUNTERFLASHING

FASTENERS APPROX.
8'' [200 mm] O.C.

EXTENDED FIELD PLIES


ABOVE HEAD OF CANT

AP
[10 PRO
0 m X. 4
m] ''

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THEY
BASE PLY AND GRANULE-
SURFACED SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION
WOOD NAILERS AND CURB
THERMAL INSULATION
CANT
NOTES : ROOF DECK

1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

STRUCTURAL MEMBER THROUGH


ROOF DECK
MB-15
2001 NOT DRAWN TO SCALE

1109
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WELDED PLATE
SEALED WATERTIGHT
(BY OTHERS)
INSULATE VOID TO
PREVENT CONDENSATION
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
REMOVABLE SHEET
METAL COUNTERFLASHING
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION

WOOD NAILERS AND CURB ROOF DECK

CANT

NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

STRUCTURAL MEMBER THROUGH


ROOF DECK
MB-15S
2001 NOT DRAWN TO SCALE

1110
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ENCLOSURE


WITH REMOVABLE TOP
-CROSSBREAK OR
SLOPE FOR DRAINAGE

INSULATE VOID
TO PREVENT
CONDENSATION

SHEET METAL OR
FLEX-TUBE COLLAR

SLOPE PIPES DOWN AND


AWAY FROM HOOD
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

FASTENERS APPROX. 8''


[200 mm] O.C.

OPTIONAL: EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT

AP MULTIPLE-PLY MEMBRANE
[10 PRO BASE FLASHING (8''
0 m X. 4
m] '' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
MIN. 4'' [100 mm] PLY MEMBRANE BASE
CLEARANCE FROM PIPE FLASHING CAN BE INSTALLED
TO TOP OF CURB; BETWEEN THE BASE PLY
MIN. 2'' [50 mm] AND GRANULE-SURFACED
BETWEEN PIPES SHEET)

WOOD NAILERS MULTIPLE-PLY MODIFIED


AND CURB BITUMEN ROOF MEMBRANE
CANT COVERBOARD INSULATION
THERMAL INSULATION
NOTES : ROOF DECK
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF GROUPING
PIPING THAT MUST PENETRATE THE ROOF.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK
MB-16
2001 NOT DRAWN TO SCALE

1111
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ENCLOSURE


WITH REMOVABLE TOP
-CROSSBREAK OR SLOPE
FOR DRAINAGE

INSULATE VOID SHEET METAL OR


TO PREVENT FLEX-TUBE COLLAR
CONDENSATION

SLOPE PIPES DOWN AND


AWAY FROM HOOD

MINIMUM 4'' [100 mm]


CLEARANCE FROM PIPE TO
TOP OF CURB; MIN. 2''
2'' [50 mm] BETWEEN PIPES

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
FASTENERS APPROX.
8'' [203 mm] O.C
OPTIONAL: REMOVABLE SHEET
METAL COUNTERFLASHING
SEE NOTE 3.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)

COVERBOARD INSULATION
OPTIONAL : EXTENDED THERMAL INSULATION
FIELD PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
ROOF DECK
CANT
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF GROUPING
PIPING THAT MUST PENETRATE THE ROOF.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK
MB-16S
2001 NOT DRAWN TO SCALE

1112
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT

DRAWBAND OR WELD
COVER TO STACK

INSULATE VOID FOR


COLD STACKS

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE SHEET METAL


COUNTERFLASHING
SEE NOTE 3

FASTENERS APPROX.
8'' [200 mm] O.C.

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
METAL OR [200 mm] MIN. HEIGHT)
GYPSUM LINER FEATHERED AT FIELD OF
IF REQUIRED ROOF
MULTIPLE-PLY MODIFIED
VARIES BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION

THERMAL INSULATION

WOOD NAILERS ROOF DECK


AND CURB
CANT
NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE STACK, AND THE NEED FOR
INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE ISOLATED STACK COVER OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
MB-17
2001 NOT DRAWN TO SCALE

1113
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT

DRAWBAND OR WELD
COVER TO STACK

INSULATE VOID FOR


COLD STACKS

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

FASTENERS APPROX.
8'' [200 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING
SEE NOTE 3

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION

THERMAL INSULATION
METAL OR
GYPSUM LINER ROOF DECK
IF REQUIRED
CANT
NOTES : WOOD NAILERS AND CURB
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE STACK, AND THE NEED
FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE ISOLATED STACK COVER OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
MB-17S
2001 NOT DRAWN TO SCALE

1114
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE ELASTOMERIC
ELASTOMERIC SEALANT
DRAWBAND

SHEET METAL RAIN COLLAR


SHEET METAL FLASHING
MIN. 8'' [200 mm] ABOVE
ROOF MEMBRANE
MULTIPLE MEMBRANE
STRIPPING PLIES -
FEATHER PLIES
COMPATIBLE ROOF CEMENT
OR COMPATIBLE SEALANT
AT FLASHING TO
MEMBRANE JUNCTURE
4'' [100 mm] MIN. FLANGE
SET IN COMPATIBLE ROOF
CEMENT OVER MODIFIED
BITUMEN ROOF
MEMBRANE - PRIME
FLANGE BEFORE
STRIPPING

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION
OPTIONAL : THERMAL INSULATION
METAL LINER
AND INSULATION ROOF DECK
IF HOT PIPE

NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE STACK
WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
MB-17A
2001 NOT DRAWN TO SCALE

1115
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC
SEALANT
DRAWBAND

COMPATIBLE ROOF
CEMENT OR
COMPATIBLE
SEALANT AT SHEET METAL
FLASHING TO RAIN COLLAR
MEMBRANE SHEET METAL
JUNCTURE FLASHING MIN. 8''
[200 mm] ABOVE
4'' [100 mm] MIN.
ROOF MEMBRANE
FLANGE SET IN
COMPATIBLE ROOF
MULTIPLE-PLY
CEMENT OVER
MEMBRANE
MULTIPLE-PLY
STRIPPING PLIES -
BITUMEN ROOF
FEATHER PLIES
MEMBRANE
BEFORE STRIPPING MULTIPLE-PLY
MODIFIED
BITUMEN ROOF
MEMBRANE

OPTIONAL :
METAL LINER COVERBOARD
AND INSULATION INSULATION
IF HOT PIPE
THERMAL
INSULATION

ROOF DECK

NOTES :

1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE
STACK WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
MB-17AS
2001 NOT DRAWN TO SCALE

1116
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TOP OF FLASHING CAPPED OR


ROLLED INTO PIPE
APPROXIMATELY 1'' [25 mm]
SOFT METAL PIPE FLASHING
SEE NOTE No. 1
PLUMBING VENT STACK

MODIFIED BITUMEN MEMBRANE


STRIPPING PLY - PRIME FLANGE
BEFORE STRIPPING

COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION TO
MEMBRANE JUNCTURE
4'' MIN. FLANGE
[100 mm]
APPROX. 4''
[100 mm]

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
SET FLANGE IN COMPATIBLE
ROOF CEMENT (FOR ROOF
SYSTEMS WITH FACTORY-APPLIED
GRANULE SURFACING, THE
PIPE FLASHING FLANGE
AND MULTI-PLY MEMBRANE
STRIPPING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
COVERBOARD INSULATION
THERMAL INSULATION
NOTES :
ROOF DECK
1. SOFT METAL PIPE FLASHING:
-SHEET LEAD : MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m2 ] OR
-SHEET COPPER: MINIMUM 16 OZ. [5 kg/m2 ]
PRECAUTIONS SHOULD BE TAKEN NOT TO DAMAGE THE SHEET LEAD WHEN USING HEAT-WELDED APPLICATION.
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SEPARATOR SHEET (E.G., ASPHALT-
SATURATED ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT
CONTACT WITH PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

MB-18
2001 NOT DRAWN TO SCALE

1117
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TOP OF FLASHING CAPPED


OR ROLLED INTO PIPE
APPROXIMATELY
1'' [25 mm]

PLUMBING VENT STACK

SOFT METAL PIPE


FLASHING
SEE NOTE No. 1

COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE

SET FLANGE IN COMPATIBLE


ROOF CEMENT
(FOR ROOF SYSTEMS WITH
FACTORY-APPLIED
4'' MIN. GRANULE SURFACING, THE
FLANGE PIPE FLASHING FLANGE
[100 mm] AND MULTI-PLY MEMBRANE
STRIPPING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

MODIFIED BITUMEN
MEMBRANE STRIPPING PLY
PRIME FLANGE BEFORE
STRIPPING
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
NOTES : THERMAL INSULATION

1. SOFT METAL PIPE FLASHING: ROOF DECK


2
-SHEET LEAD : MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m ] OR
-SHEET COPPER: MINIMUM 16 OZ. [5 kg/m2]
PRECAUTIONS SHOULD BE TAKEN NOT TO DAMAGE THE SHEET LEAD WHEN USING HEAT-WELDED APPLICATION.
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SEPARATOR SHEET (E.G., ASPHALT-
SATURATED ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT
CONTACT WITH PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

MB-18S
2001 NOT DRAWN TO SCALE

1118
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL RAIN APPROPRIATE SEALANT


COLLAR OVERLAPPING (E.G. POLYURETHANE)
PENETRATION POCKET DRAWBAND
APPROX. 1/4'' 4'' [100 mm] MIN. FLANGE
[6 mm] SET IN COMPATIBLE ROOF
CLEARANCE CEMENT OVER FIELD
AT CORNERS PLIES, PRIME FLANGE
MODIFIED BEFORE STRIPPING
(FOR ROOF SYSTEMS WITH
BITUMEN
FACTORY-APPLIED
MEMBRANE
GRANULE SURFACING, THE
STRIPPING
PIPE FLASHING FLANGE
PLY
AND MULTI-PLY MEMBRANE
POURABLE STRIPPING CAN BE
SEALANT INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)

AP
[10 PRO
0 m X. 4
m] ''

NON-SHRINK
GROUT

WEATHERPROOF
SHEET METAL PITCH PAN,
SOLDERED / WELDED
(4'' [100 mm] MIN. HEIGHT)

COMPATIBLE ROOF CEMENT


OR COMPATIBLE SEALANT
AT PENETRATION TO
MEMBRANE JUNCTURE

COVERBOARD INSULATION
THERMAL INSULATION

ROOF DECK

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS
BECAUSE THEY MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL MB-11 FOR THE PREFERRED
FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

MB-19
2001 NOT DRAWN TO SCALE

1119
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL RAIN


COLLAR OVERLAPPING
APPROPRIATE SEALANT PENETRATION POCKET
(E.G. POLYURETHANE)
4'' [100 mm] MIN. FLANGE,
DRAW BAND SET IN COMPATIBLE ROOF
CEMENT OVER FIELD PLIES,
PRIME FLANGE BEFORE
APPROX. 1/4''
STRIPPING
[6 mm] CLEARANCE
(FOR ROOF SYSTEMS WITH
AT CORNERS
FACTORY-APPLIED
GRANULE SURFACING, THE
POURABLE SEALANT PIPE FLASHING FLANGE
AND MULTI-PLY MEMBRANE
STRIPPING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
WEATHERPROOF
SHEET METAL PITCH PAN,
SOLDERED / WELDED MODIFIED BITUMEN
(4'' [100 mm] MIN. HEIGHT) MEMBRANE STRIPPING PLY

COMPATIBLE ROOF CEMENT MULTIPLE-PLY


OR COMPATIBLE SEALANT MODIFIED BITUMEN
AT PENETRATION TO ROOF MEMBRANE
MEMBRANE JUNCTURE

COVERBOARD
INSULATION

THERMAL
INSULATION

ROOF DECK

NON-SHRINK GROUT

NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS
BECAUSE THEY MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL MB-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

MB-19S
2001 NOT DRAWN TO SCALE

1120
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OPTIONAL 1''x4'' [25 mm x 100mm]


SHEET METAL GRAVEL STOP, APPROX. 30'' [750 mm] SQUARE MINIMUM,
30'' [750 mm] SQUARE, SET IN 2 1/2 LB. [12 kg/m2] LEAD OR
ROOF CEMENT 16 oz. [5 kg/m2] SOFT COPPER
FLASHING SET ON FINISHED ROOF
MODIFIED BITUMEN MEMBRANE IN COMPATIBLE ROOF CEMENT. PRIME
STRIPPING PLY TOP SURFACE BEFORE STRIPPING

DRAIN STRAINER

COVERBOARD
INSULATION

THERMAL INSULATION
ROOF DECK
TAPERED
INSULATION
CLAMPING RING

DECK CLAMP
DRAIN BOWL
MEMBRANE FIELD
PLIES, METAL FLASHING,
AND STRIPPING PLY ALL
EXTEND UNDER CLAMPING
RING
COMPATIBLE ROOF CEMENT

MULTIPLE-PLY MODIFIED BITUMEN ROOF MEMBRANE

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

MB-20
2001 NOT DRAWN TO SCALE

1121
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRAIN STRAINER

CLAMPING RING

30'' [750 mm] SQUARE MINIMUM,


2 1/2 LB. [12 kg/m2] LEAD OR
2
16 oz. [5 kg/m ] SOFT COPPER
FLASHING SET ON FINISHED ROOF
IN COMPATIBLE ROOF CEMENT. PRIME TOP
SURFACE BEFORE STRIPPING

MODIFIED BITUMEN MEMBRANE


STRIPPING PLY

MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE

COVERBOARD
INSULATION

THERMAL
INSULATION

TAPERED INSULATION

ROOF DECK

DECK CLAMP

MEMBRANE FIELD PLIES,


METAL FLASHING AND STRIPPING PLY
ALL EXTEND UNDER CLAMPING RING

DRAIN BOWL

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

MB-20S
2001 NOT DRAWN TO SCALE

1122
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MODIFIED BITUMEN ROOF


MEMBRANE CAP SHEET
COVERBOARD INSULATION
MODIFIED BITUMEN MEMBRANE
STRIPPING PLY
THERMAL INSULATION
30'' [750 mm] SQUARE MINIMUM,
2 1/2 LB. TO 4 LB. [12 TO 20 kg/m2]
LEAD OR 16 OZ. [5 kg/m2] SOFT COPPER
FLASHING SET IN COMPATIBLE ROOF
CEMENT PRIME TOP SURFACE BEFORE
STRIPPING
DRAIN STRAINER

ROOF DECK

TAPERED
INSULATION

CLAMPING RING

DECK CLAMP

DRAIN BOWL

MEMBRANE FIELD
PLIES, METAL FLASHING,
AND STRIPPING PLY ALL
EXTEND UNDER CLAMPING
RING

COMPATIBLE ROOF CEMENT

MODIFIED BITUMEN ROOF MEMBRANE BASE PLY

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER,
DRAIN RECEIVER/BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN - ALTERNATE FLASHING

MB-20A
2001 NOT DRAWN TO SCALE

1123
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRAIN STRAINER

CLAMPING RING

MODIFIED BITUMEN ROOF


MEMBRANE CAP SHEET
MODIFIED BITUMEN MEMBRANE
STRIPPING PLY

30'' [750 mm] SQUARE MINIMUM,


2 1/2 LB. TO 4 LB. [12 TO 20 kg/m2 ]
LEAD OR 16 OZ. [5 kg/m2] SOFT COPPER
FLASHING SET IN COMPATIBLE ROOF
CEMENT PRIME TOP SURFACE BEFORE
STRIPPING

COMPATIBLE
ROOF CEMENT

MODIFIED BITUMEN ROOF


MEMBRANE BASE PLY

COVERBOARD
INSULATION

THERMAL
INSULATION

TAPERED INSULATION
ROOF DECK
DECK CLAMP

MEMBRANE FIELD PLIES,


METAL FLASHING AND STRIPPING PLY
ALL EXTEND UNDER CLAMPING RING

DRAIN BOWL

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER,
DRAIN RECEIVER/BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN - ALTERNATE FLASHING

MB-20AS
2001 NOT DRAWN TO SCALE

1124
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL SCUPPER


WITH SOLDERED JOINTS
SET IN COMPATIBLE N.
MI
SEALANT 4'' mm]
0 BEAD OF SEALANT
[10
OPTIONAL: 3/4'' x 3''
[19 mm x 75 mm] MIN. SHEET METAL FASCIA CAP
''L'' SHAPED GRAVEL
GUARD SECURED TO THE GASKETED FASTENERS
SCUPPER FLANGE, NOTCHED
TO PERMIT DRAINAGE APPROX. 4'' [100 mm]
SHEET METAL
APPROX. 2'' [50 mm]
CONDUCTOR
HEAD

SUMP AREA IN FRONT


OF SCUPPER TO DRAIN
MULTIPLE-PLY MEMBRANE
STRIPPING (FOR ROOF SYSTEMS
WITH FACTORY-APPLIED
GRANULE SURFACING, THE
SCUPPER FLANGE AND MULTI-
PLY MEMBRANE STRIPPING
CAN BE INSTALLED BETWEEN
THE BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
FASTEN SCUPPER TO
BLOCKING, SET FLANGE IN
COMPATIBLE ROOF CEMENT
PRIME FLANGE BEFORE
EXTEND ONE PLY OR STRIPPING
A SEPARATE MEMBRANE COVERBOARD INSULATION
SHEET TO BELOW
BLOCKING THERMAL INSULATION
ROOF DECK
WOOD NAILERS

NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SCUPPER THROUGH RAISED PERIMETER


EDGE
MB-21
2001 NOT DRAWN TO SCALE

1125
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL FASCIA CAP


SHEET METAL SCUPPER
WITH SOLDERED JOINTS FASTEN SCUPPER TO
BLOCKING, SET FLANGE IN
COMPATIBLE ROOF CEMENT
PRIME FLANGE BEFORE
OPTIONAL: 3/4'' x 3'' STRIPPING
[19 mm x 75 mm] MIN.
''L'' SHAPED GRAVEL MULTIPLE-PLY MEMBRANE
GUARD SECURED TO STRIPPING (FOR ROOF SYSTEMS
THE SCUPPER FLANGE, WITH FACTORY-APPLIED
NOTCHED TO PERMIT GRANULE SURFACING, THE
DRAINAGE SCUPPER FLANGE AND MULTI-
PLY MEMBRANE STRIPPING
SEALANT CAN BE INSTALLED BETWEEN
THE BASE PLY AND GRANULE-
SHEET METAL SURFACED SHEET)
CONDUCTOR
SUMP AREA
HEAD
IN FRONT OF
SCUPPER TO
DRAIN

MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE

COVERBOARD INSULATION
(SUMP TO DRAIN)
THERMAL INSULATION
ROOF DECK

WOOD NAILERS
EXTEND ONE PLY OR
A SEPARATE MEMBRANE
SHEET TO BELOW
BLOCKING

NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SCUPPER THROUGH RAISED PERIMETER


EDGE
MB-21S
2001 NOT DRAWN TO SCALE

1126
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MODIFIED BITUMEN
MEMBRANE STRIPPING
PLY
SET FLANGE IN
COMPATIBLE
ROOF CEMENT
MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE

COVERBOARD OPTION :
INSULATION
THERMAL SHEET METAL EDGE
INSULATION FLASHING - PRIME
FLANGE BEFORE
ROOF DECK STRIPPING (FOR ROOF
SYSTEMS WITH
FACTORY-APPLIED
GRANULE SURFACING,
THE METAL EDGE
FLANGE AND MEMBRANE
STRIPPING CAN BE
INSTALLED BETWEEN
THE BASE PLY AND
GRANULE-SURFACED
SHEET)
FASTENERS 3'' TO 6''
[75 mm TO 150 mm] O.C.
STAGGERED
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS
SHEET METAL GUTTER
THE FRONT OF THE
GUTTER SHOULD BE A
MIN. 1'' [25 mm] LOWER
THAN THE BACK TO
ALLOW FOR OVERFLOW
WOOD OPTIONAL: STIFFENING
NAILERS BAR
EXTEND ONE PLY OR OPTIONAL: GUTTER
A SEPARATE MEMBRANE BRACKET SUPPORT
SHEET TO OVERLAY
METAL CLOSURE

NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING MB-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

MB-22
2001 NOT DRAWN TO SCALE

1127
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MODIFIED BITUMEN
MEMBRANE
STRIPPING PLY
SHEET METAL EDGE SET FLANGE IN
FLASHING - PRIME COMPATIBLE ROOF
FLANGE BEFORE CEMENT
STRIPPING (FOR ROOF
SYSTEMS WITH FASTENERS 3'' TO 6''
FACTORY-APPLIED [75 mm TO 150 mm] O.C.
GRANULE SURFACING, STAGGERED
THE METAL EDGE MULTIPLE-PLY
FLANGE AND MEMBRANE MODIFIED BITUMEN
STRIPPING CAN BE ROOF MEMBRANE
INSTALLED BETWEEN
THE BASE PLY AND
GRANULE-SURFACED
SHEET)

GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS ROOF DECK

SHEET METAL GUTTER THERMAL


THE FRONT OF THE INSULATION
GUTTER SHOULD BE A COVERBOARD
MIN. 1'' [25 mm] LOWER INSULATION
THAN THE BACK TO
ALLOW FOR OVERFLOW WOOD
NAILERS
OPTIONAL: GUTTER
EXTEND ONE PLY
BRACKET SUPPORT
OR A SEPARATE
MEMBRANE SHEET
TO OVERLAY
NOTES : METAL CLOSURE

1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING MB-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

MB-22S
2001 NOT DRAWN TO SCALE

1128
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS APPROX. SHEET METAL PARAPET


12'' [300 mm] O.C. CAP

EXTEND MEMBRANE CONTINUOUS SHIM


TO BELOW NAILER
AND SECURE

GASKETED FASTENERS
BELOW BLOCKING
1'' [25 mm] MIN.

WOOD NAILER

SEAM PLATES AND


FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE PERIMETER
SECUREMENT OPTIONS

SEALANT (IF REQUIRED


FOR THE SPECIFIC SYSTEM)

FLASHING MEMBRANE

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

CONTINUOUS CLEAT
FASTENED PER TABLE 1
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TP-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING) AND


BASE FLASHING

TP-1
2001 NOT DRAWN TO SCALE

1129
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL PARAPET


CAP

FASTENERS APPROX. 12''


[300 mm] O.C.

CONTINUOUS SHIM
BELOW BLOCKING
1'' [25 mm] MIN.

WOOD NAILER

GASKETED FASTENERS

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

EXTEND MEMBRANE TO
BELOW NAILER AND SECURE

CONTINUOUS CLEAT

SEALANT (IF REQUIRED


FOR THE SPECIFIC SYSTEM)
THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
SEAM PLATES AND THERMAL INSULATION
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE PERIMETER
SECUREMENT OPTIONS ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TP-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING) AND


BASE FLASHING

TP-1S
2001 NOT DRAWN TO SCALE

1130
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS

SHEET METAL FASCIA CAP

WOOD CANT FASTENED


TO WOOD NAILERS
FLASHING MEMBRANE

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)
BELOW BLOCKING
1'' [25 mm] MIN.

THERMOPLASTIC ROOF
MEMBRANE

SEAM PLATES AND


FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

CONTINUOUS CLEAT
(FASTENED PER TABLE 1)

NOTES :
1. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)

TP-2
2001 NOT DRAWN TO SCALE

1131
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL FASCIA CAP

GASKETED FASTENERS

WOOD CANT FASTENED TO


WOOD NAILERS

FLASHING MEMBRANE

SEAM PLATES AND


FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

THERMOPLASTIC ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
BELOW BLOCKING
1'' [25 mm] MIN.

WOOD NAILERS

EXTEND MEMBRANE BELOW


WOOD BLOCKING

CONTINUOUS CLEAT
(FASTENED PER TABLE 1)

NOTES :
1. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)

TP-2S
2001 NOT DRAWN TO SCALE

1132
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT (IF REQUIRED
FOR THE SPECIFIC SYSTEM) 1 1/2'' [38 mm] MIN. FOR
BALLASTED SYSTEMS

1/2'' [13 mm]


MIN. CLEARANCE FLANGE APPROX.
3'' [75 mm] WIDE
2'' [50 mm]
MIN. CLEARANCE APPROX. 3''
[75 mm]
BELOW BLOCKING
1'' [25mm] MIN.

ADHERED OR WELDED
FLASHING MEMBRANE
(EXTEND APPROX. 3''
[75 mm] BEYOND FLANGE)

FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.;
STAGGER

SHEET METAL OR MEMBRANE


COATED METAL ''GRAVEL
STOP'' (AS REQUIRED BY
MANUFACTURER)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND THERMAL


INSULATION

ROOF DECK
WOOD NAILERS

EXTEND FIELD SHEET TO


BELOW BLOCKING

CONTINUOUS CLEAT
(FASTENED PER
NOTES : SINGLE-PLY TABLE 1)

1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)

TP-3
2001 NOT DRAWN TO SCALE

1133
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL OR MEMBRANE


COATED METAL ''GRAVEL STOP''
(AS REQUIRED BY
MANUFACTURER)
SEALANT (IF REQUIRED FOR
THE SPECIFIC SYSTEM)

FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.,
STAGGER

ADHERED OR WELDED
EXCEED HEIGHT OF BALLAST

FLASHING MEMBRANE (EXTEND


APPROX. 3'' [75 mm]
BALLASTED SYSTEMS TO

BEYOND FLANGE)
1 1/2'' [38 mm] MIN. FOR

SEALANT (IF REQUIRED BY


THE SPECIFIC SYSTEM)

THERMOPLASTIC ROOF
MEMBRANE

COVERBOARD AND THERMAL


INSULATION
BELOW BLOCKING

ROOF DECK
1'' [25 mm] MIN.

EXTEND FIELD SHEET TO


BELOW BLOCKING

CONTINUOUS CLEAT
(FASTENED PER
SINGLE-PLY TABLE 1)

NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)

TP-3S
2001 NOT DRAWN TO SCALE

1134
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT (IF REQUIRED


FOR THE SPECIFIC SYSTEM)
FLANGE APPROX.
PERIMETER SHEET METAL 3'' [75 mm]
OR MEMBRANE COATED APPROX.
METAL FLASHING 3'' [75 mm]

CONTINUOUS CLEAT
FASTENED PER
TABLE 1.
BELOW BLOCKING
1'' [25 mm] MIN.

ADHERED OR WELDED
FLASHING MEMBRANE

FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.
STAGGER

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

EXTEND FIELD SHEET

OPTIONAL : WOOD NAILER


AND SHEET METAL
NOTES : CLOSURE
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

DRAINING PERIMETER EDGE

TP-3A
2001 NOT DRAWN TO SCALE

1135
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT (IF REQUIRED FOR THE


SPECIFIC SYSTEM)

PERIMETER SHEET METAL OR


MEMBRANE COATED METAL FLASHING

FASTENERS AT APPROX. 3'' to 6''


[75 to 150 mm] O.C., STAGGER

ADHERED OR WELDED FLASHING


MEMBRANE (EXTEND APPROX. 3''
[75 mm] BEYOND FLANGE)

SEALANT (IF REQUIRED FOR THE


SPECIFIC SYSTEM)

THERMOPLASTIC ROOF MEMBRANE


BELOW BLOCKING
1'' [25 mm] MIN.

COVERBOARD AND THERMAL INSULATION

ROOF DECK

EXTEND FIELD SHEET

WOOD NAILERS

OPTIONAL: WOOD NAILER AND


SHEET METAL CLOSURE

CONTINUOUS CLEAT
FASTENED PER TABLE 1.

NOTES :

1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

DRAINING PERIMETER EDGE

TP-3AS
2001 NOT DRAWN TO SCALE

1136
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MEMBRANE COATED METAL

FASTENERS AT APPROX. 3''


to 6'' [75 to 150 mm] O.C.;
STAGGER

4'' [100 mm] WIDE FLASHING


MEMBRANE WELDED TO
MEMBRANE COATED METAL
EDGE

4'' [100 mm]

FLANGE APPROXIMATELY
3'' [75 mm] MIN. WIDE

1 1/2'' [38 mm] MIN.


FOR BALLASTED SYSTEMS TO
EXCEED HEIGHT OF BALLAST

MEMBRANE JOINT COVER


INSTALLED PER
MANUFACTURERS
RECOMMENDATIONS

1/4'' [6 mm] GAP BETWEEN


ADJACENT PIECES OF
MEMBRANE COATED METAL

APPROXIMATELY 2''
[50 mm] WIDE BOND
BREAKER MATERIAL
(E.G., DUCT TAPE)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. SEE DETAIL TP-3 FOR ADDITIONAL INFORMATION REGARDING EDGE CONSTRUCTION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

JOINT DETAIL FOR MEMBRANE COATED


EMBEDDED EDGE METAL FLASHING
(GRAVEL-STOP)
TP-3B
2001 NOT DRAWN TO SCALE

1137
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MEMBRANE COATED METAL

FASTENERS AT APPROX. 3'' to 6''


[75 to 150 mm] O.C.; STAGGER

4'' [100 mm] WIDE FLASHING


MEMBRANE WELDED TO MEMBRANE
COATED METAL EDGE

4'' [100 mm]

FLANGE APPROX.
3'' [75 mm]
MIN. WIDE

MEMBRANE JOINT COVER


INSTALLED PER MANUFACTURERS
RECOMMENDATIONS

1/4'' [6 mm] GAP BETWEEN


ADJACENT PIECES OF MEMBRANE
COATED METAL

APPROXIMATELY 2'' [50 mm]


WIDE BOND BREAKER MATERIAL
(E.G., DUCT TAPE)

NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. SEE DETAIL TP-3A FOR ADDITIONAL INFORMATION REGARDING EDGE CONSTRUCTION.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

JOINT DETAIL FOR MEMBRANE COATED


DRAINING PERIMETER EDGE

TP-3C
2001 NOT DRAWN TO SCALE

1138
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF

CONCRETE FASTENERS

SHEET METAL COUNTERFLASHING


(SEE TABLE 2)

OPTIONAL: INSTALL COMPRESSIBLE


ELASTOMERIC SEALANT OR TAPE
TO SPAN IRREGULARITIES

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

SEALANT (IF REQUIRED FOR THE


SPECIFIC SYSTEM)

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS

TP-4
2001 NOT DRAWN TO SCALE

1139
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF

OPTIONAL: INSTALL COMPRESSIBLE


ELASTOMERIC SEALANT OR TAPE
TO SPAN IRREGULARITIES

CONCRETE FASTENERS

TERMINATION BAR FASTENED WITH


APPROPRIATE FASTENERS APPROX.
12'' [300 mm] O.C.

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE

SHEET METAL COUNTERFLASHING


(SEE TABLE 2)

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

SEALANT (IF REQUIRED FOR THE


SPECIFIC SYSTEM)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS

TP-4S
2001 NOT DRAWN TO SCALE

1140
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

NOTES : ROOF DECK

1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR WALL-SUPPORTED


DECK

TP-5
2001 NOT DRAWN TO SCALE

1141
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

REMOVABLE SHEET METAL


COUNTERFLASHING

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR WALL-SUPPORTED


DECK

TP-5S
2001 NOT DRAWN TO SCALE

1142
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

INSTALL COMPATIBLE
SEALANT BEHIND MEMBRANE
TERMINATION BAR FASTENED
WITH APPROPRIATE
FASTENERS APPROX.
12'' [300 mm] O.C.
REMOVABLE SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

FLEXIBLE FOAM ROD


MINIMUM DIAMETER 1 1/2
TIMES WIDTH OF OPENING

FLEXIBLE VAPOR RETARDER


WITH COMPRESSIBLE
INSULATION
SEAM PLATES AND
FATENERS - SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

THERMOPLASTIC ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
NOTES :
WOOD NAILERS
1. THIS DETAIL ACCOMMODATES INDEPENDENT WALL AND DECK MOVEMENT.
2. OTHER METHODS OF COUNTERFLASHING MAY BE APPLICABLE (SEE TABLE 2).
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK

TP-6
2001 NOT DRAWN TO SCALE

1143
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL REGLET

FASTENERS

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT

FLEXIBLE FOAM ROD; MINIMUM


DIAMETER 1 1/2 TIMES WIDTH
OF OPENING

SEAM PLATES AND


FASTENERS - SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

FLEXIBLE VAPOR RETARDER


WITH COMPRESSIBLE
INSULATION
NOTES :
1. THIS DETAIL ACCOMMODATES INDEPENDENT WALL AND DECK MOVEMENT.
2. OTHER METHODS OF COUNTERFLASHING MAY BE APPLICABLE (SEE TABLE 2).
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK

TP-6S
2001 NOT DRAWN TO SCALE

1144
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EXPANSION


JOINT COVER
FLEXIBLE VAPOR
RETARDER TO SERVE FLEXIBLE
AS INSULATION RETAINER WEATHERPROOF
(ATTACHED TO TOP MEMBRANE CLOSURE -
OF CURB) OPTIONAL IF DOUBLE
LOCK STANDING SEAM
COMPRESSIBLE JOINTS ARE USED
INSULATION
WITH THE METAL
PARAPET CAP
FLASHING HEIGHT
8'' [200 mm] MINIMUM

ON LOW SIDE

GASKETED FASTENERS

FASTENERS APPROX.
8'' [200 mm] O.C.

FLASHING MEMBRANE

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

SEAM PLATES AND


FASTENERS - SEE
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOPLASTIC ROOF
TOP OF MEMBRANE
CURB TO DRAIN
TO ONE SIDE

WOOD NAILERS

COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

TP-7
2001 NOT DRAWN TO SCALE

1145
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
EXPANSION JOINT
FLEXIBLE VAPOR COVER
RETARDER TO SERVE FLEXIBLE
AS INSULATION WEATHERPROOF
RETAINER (ATTACHED MEMBRANE CLOSURE -
TO TOP OF CURB) OPTIONAL IF DOUBLE
LOCK STANDING SEAM
COMPRESSIBLE JOINTS ARE USED WITH
INSULATION THE METAL PARAPET
CAP
TOP OF CURB FASTENERS APPROX.
TO DRAIN TO 8'' [200 mm] O.C.
ONE SIDE
GASKETED FASTENERS

FLASHING MEMBRANE

SEAM PLATES AND


8'' [200 mm] MINIMUM

FASTENERS -
FLASHING HEIGHT

SEE SINGLE PLY TABLE


ON LOW SIDE

7 FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

THERMOPLASTIC ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS. WOOD NAILERS
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

TP-7S
2001 NOT DRAWN TO SCALE

1146
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE VAPOR
RETARDER TO SERVE
AS INSULATION RETAINER PREMANUFACTURED
(ATTACHED TO TOP EXPANSION JOINT
OF CURB) COVER

FLEXIBLE
COMPRESSIBLE WEATHERPROOF
INSULATION MEMBRANE CLOSURE

GASKETED FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT
ON LOW SIDE

FASTENERS APPROX.
8'' [200 mm] O.C.

FLASHING MEMBRANE

SEALANT (IF REQUIRED


FOR BY THE SPECIFIC
SYSTEM)
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE
7 FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

TOP OF CURB
TO DRAIN TO
THE OUTSIDE THERMOPLASTIC
ROOF MEMBRANE
WOOD NAILERS

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :

1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.


2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
TP-7A
2001 NOT DRAWN TO SCALE

1147
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PREMANUFACTURED
EXPANSION JOINT
COVER
FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE

FASTENERS APPROX.
8'' [200 mm] O.C.
GASKETED FASTENERS

TOP OF CURB
FLASHING MEMBRANE
TO DRAIN TO
(8'' [200 mm] MIN.
THE OUTSIDE
HEIGHT)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE
7 FOR ALTERNATE
PERIMETER
8'' [200 mm] MINIMUM
FLASHING HEIGHT

SECUREMENT OPTIONS
ON LOW SIDE

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

FLEXIBLE VAPOR WOOD NAILERS


RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED COMPRESSIBLE
TO TOP OF CURB) INSULATION

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
TP-7AS
2001 NOT DRAWN TO SCALE

1148
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
AREA DIVIDER
COVER

GASKETED
FASTENERS

FLASHING
8'' [200 mm] MINIMUM
FLASHING HEIGHT

MEMBRANE
ON LOW SIDE

SEALANT (IF
REQUIRED FOR
THE SPECIFIC
SYSTEM)

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE
7 FOR ALTERNATE
PERIMETER
SECUREMENT
OPTIONS

THERMOPLASTIC
ROOF MEMBRANE

WOOD NAILERS

ROOF DECK

COVERBOARD AND
THERMAL INSULATION

NOTES :

1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

AREA DIVIDER IN ROOF SYSTEM

TP-8
2001 NOT DRAWN TO SCALE

1149
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEAM PLATES AND


FASTENERS -
SEE SINGLE PLY TABLE
SHEET METAL AREA
7 FOR ALTERNATE
DIVIDER COVER
PERIMETER SECUREMENT
OPTIONS

GASKETED FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT

FLASHING MEMBRANE
ON LOW SIDE

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

WOOD NAILERS

ROOF DECK

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
NOTES THERMAL INSULATION

1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

AREA DIVIDER IN ROOF SYSTEM

TP-8S
2001 NOT DRAWN TO SCALE

1150
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEIGHT
WIDTH OF EQUIPMENT OF LEGS
UP TO 24'' [UP TO 600 mm] 24'' [600 mm] SHEET METAL COVER
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]
SET NEOPRENE PAD IN
SEALANT (BY OTHERS)

SET BOLTS IN SEALANT


(BY OTHERS)

GASKETED FASTENERS

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE
7 FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS

WOOD CURB

WOOD NAILERS
THERMOPLASTIC
ROOF DECK ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL TP-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS
ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

EQUIPMENT SUPPORT CURB

TP-9
2001 NOT DRAWN TO SCALE

1151
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEIGHT
WIDTH OF EQUIPMENT OF LEGS SET BOLTS IN SEALANT
UP TO 24'' [UP TO 600 mm] 24'' [600 mm] (BY OTHERS)
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm] SET NEOPRENE PAD IN
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m] SEALANT (BY OTHERS)

SHEET METAL COVER

GASKETED FASTENERS

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
SEAM PLATES AND
FASTENERS - SEALANT (IF REQUIRED
SEE SINGLE PLY TABLE FOR THE SPECIFIC
7 FOR ALTERNATE SYSTEM)
PERIMETER SECUREMENT
OPTIONS

COVERBOARD AND
ROOF DECK
THERMAL INSULATION
THERMOPLASTIC WOOD NAILERS
ROOF MEMBRANE
WOOD CURB
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL TP-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS
ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

EQUIPMENT SUPPORT CURB

TP-9S
2001 NOT DRAWN TO SCALE

1152
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL FRAME

HEIGHT-
SEE TABLE

LE
B
TA
E
E
S
-
H
T
SEE DETAIL ID
W
TP-11 FOR FLASHING
OF SUPPORT LEGS

ROUND PIPE COLUMN

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL TP-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED
DIRECTLY OVER COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE
ADAPTED FOR OTHER USES, SUCH AS SIGN SUPPORTS.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND

TP-10
2001 NOT DRAWN TO SCALE

1153
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOR HEIGHT OF LEGS


SEE TABLE ON TP-10

SEALANT

OPTIONAL: DRAWBAND

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

FILL GAPS WITH


INSULATION BOARD
NOTES : TO PROVIDE EVEN
SUBSTRATE
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND LEG


(FIELD WRAP)

TP-11
2001 NOT DRAWN TO SCALE

1154
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

OPTIONAL : DRAWBAND
FOR HEIGHT OF LEGS
SEE TABLE ON TP-10

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
SEALANT (IF REQUIRED
FOR THE SPECIFIC
SYSTEM)
COVERBOARD AND
THERMAL INSULATION

ROOF DECK
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM
FILL GAPS WITH
INSULATION BOARD
TO PROVIDE EVEN
SUBSTRATE
NOTES :
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND LEG


(FIELD WRAP)

TP-11S
2001 NOT DRAWN TO SCALE

1155
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

OPTIONAL : DRAWBAND

PIPE PENETRATION

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PENETRATIONS TO FACILITATE PROPER FLASHING (SEE TABLE 4).
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PIPE PENETRATION (FIELD WRAP)

TP-11A
2001 NOT DRAWN TO SCALE

1156
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PIPE PENETRATION

SEALANT

OPTIONAL: DRAWBAND

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING (SEE TABLE 4).
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND LEG


(FIELD WRAP)

TP-11AS
2001 NOT DRAWN TO SCALE

1157
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL

RAISED CURB

WOOD NAILER

GASKETED FASTENERS
MIN. TWO FASTENERS
PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

ALTERNATE CURB
BEARING LOCATION
FOR HEAVY-WEIGHT THERMOPLASTIC
LOADING CONDITIONS ROOF MEMBRANE
MECHANICAL UNIT, HOOD, ETC.
COVERBOARD AND
BASE OF UNIT EXTENDS 1/2''
THERMAL INSULATION
[13 mm] MINIMUM BEYOND
TOP OF CURB ROOF DECK
SEALING MATERIAL - MUST
BE CONTINUOUS ON TOP
OF THE CURB

1'' [25 mm] MINIMUM


BELOW TOP OF CURB NOTES :

FASTENERS 1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE
TO BE SUPPLIED BY THE CURB MANUFACTURER.
WOOD NAILER 2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
COUNTERFLASHING HAVE BEEN INSTALLED.
INSULATION 3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INFORMATION.
FLASHING MEMBRANE 4. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
RAISED CURB OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
TP-12
2001 NOT DRAWN TO SCALE

1158
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD NAILER
SEALING MATERIAL

RAISED CURB GASKETED FASTENERS


MIN. TWO FASTENERS
PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING
SEAM PLATES AND
FASTENERS - SEE
FLASHING SINGLE PLY TABLE 7
MEMBRANE FOR ALTERNATE
(8'' [200 mm] PERIMETER SECUREMENT
MIN. HEIGHT) OPTIONS
THERMOPLASTIC
ROOF MEMBRANE

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
LOADING CONDITIONS

NOTES :
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
TP-12S
2001 NOT DRAWN TO SCALE

1159
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALING MATERIAL
WOOD CURB

WOOD
NAILERS

SHEET METAL
COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOPLASTIC
ROOF MEMBRANE

ALTERNATE: MECHANICAL UNIT, HOOD, ETC. COVERBOARD AND


THERMAL INSULATION
BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND
TOP OF CURB ROOF DECK
SEALING MATERIAL - MUST
BE CONTINUOUS ON TOP
OF THE CURB

1'' [25 mm] MINIMUM


BELOW TOP OF CURB

FLASHING RECEIVER
NOTES :
FASTENERS
1. THE MECHANICAL UNITS SHOULD NOT
COUNTERFLASHING BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
FLASHING MEMBRANE 2. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
WOOD CURB OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INFORMATION.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
TP-13
2001 NOT DRAWN TO SCALE

1160
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALING MATERIAL

REMOVABLE
SHEET METAL
COUNTERFLASHING

WOOD CURB

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

SEALANT (IF
REQUIRED FOR THE
SPECIFIC SYSTEM)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

NOTES :
1. THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
TP-13S
2001 NOT DRAWN TO SCALE

1161
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO FASTENERS PER
SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS AND CURB

NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm]
THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

TP-14
2001 NOT DRAWN TO SCALE

1162
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)
THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

WOOD NAILERS AND CURB


NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm]
THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

TP-14S
2001 NOT DRAWN TO SCALE

1163
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INSULATE VOID
TO PREVENT
CONDENSATION

WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION

ROOF DECK
WOOD NAILERS
AND CURB

NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM ALLOWS FOR
MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION IF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR THE SHEET METAL.

STRUCTURAL ROOF MEMBER THROUGH


ROOF DECK

TP-15
2001 NOT DRAWN TO SCALE

1164
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INSULATE VOID
TO PREVENT
CONDENSATION
WELDED PLATE
SEALED WATERTIGHT
FASTENERS -
(BY OTHERS)
MINIMUM TWO
FASTENERS
WOOD CURB PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING
FASTENERS
APPROX. 8'' FLASHING
[200 mm] O.C. MEMBRANE
(8'' [200 mm]
SEALANT MIN. HEIGHT)
(IF REQUIRED
FOR THE THERMOPLASTIC
SPECIFIC ROOF MEMBRANE
SYSTEM)

COVERBOARD
AND THERMAL
INSULATION SEAM PLATES AND
FASTENERS -
ROOF DECK SEE SINGLE PLY
TABLE 7 FOR
ALTERNATE
WOOD NAILERS
PERIMETER
SECUREMENT
OPTIONS

NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM ALLOWS FOR
MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION IF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR THE SHEET METAL.

STRUCTURAL ROOF MEMBER THROUGH


ROOF DECK

TP-15S
2001 NOT DRAWN TO SCALE

1165
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ENCLOSURE


WITH REMOVABLE TOP
-CROSSBREAK OR
SLOPE FOR DRAINAGE

INSULATE VOID TO
PREVENT CONDENSATION

SHEET METAL OR
FLEX-TUBE COLLAR
FLASHING
MINIMUM

HEIGHT
8'' [200 mm]

SLOPE PIPES DOWN AND


AWAY FROM HOOD

OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

GASKETED FASTENERS
MINIMUM TWO PER SIDE

SEAM PLATES AND


MIN. 4'' [100 mm]
FASTENERS - SEE
CLEARANCE FROM
SINGLE PLY TABLE 7
PIPE TO TOP OF
FOR ALTERNATE
CURB; MIN. 2''
PERIMETER SECUREMENT
[50 mm] BETWEEN
OPTIONS
PIPES

SHEET METAL
FLASHING RECEIVER
COVERBOARD AND
WOOD NAILERS THERMAL INSULATION
AND CURB
ROOF DECK
THERMOPLASTIC
ROOF MEMBRANE
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL
METHOD OF GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK

TP-16
2001 NOT DRAWN TO SCALE

1166
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SLOPE PIPES DOWN SEALANT


AND AWAY FROM HOOD
SHEET METAL OR
INSULATE VOID TO FLEX-TUBE COLLAR
PREVENT CONDENSATION SHEET METAL FLASHING
RECEIVER
SHEET METAL ENCLOSURE
WITH REMOVABLE TOP - MIN. 4'' [100 mm]
CROSSBREAK OR CLEARANCE FROM PIPE
SLOPE FOR DRAINAGE TO TOP OF CURB;
MIN. 2'' [50 mm]
BETWEEN PIPES

GASKETED FASTENERS
MINIMUM TWO PER SIDE

OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
MINIMUM FLASHING

HEIGHT)
SEALANT (IF REQUIRED
8'' [200 mm]

HEIGHT

FOR THE SPECIFIC


SYSTEM)
THERMOPLASTIC
ROOF MEMBRANE

ROOF DECK

SEAM PLATES AND COVERBOARD AND


FASTENERS - SEE SINGLE PLY THERMAL INSULATION
TABLE 7 FOR ALTERNATE PERIMETER
WOOD NAILERS
SECUREMENT OPTIONS
AND CURB
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL
METHOD OF GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK

TP-16S
2001 NOT DRAWN TO SCALE

1167
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT

DRAWBAND OR WELD
COVER TO STACK

INSULATE VOID FOR


COLD STACKS

FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE No. 3

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

SEAM PLATES AND


METAL OR
FASTENERS - SEE
GYPSUM LINER
SINGLE PLY TABLE 7 FOR
IF REQUIRED
ALTERNATE PERIMETER
VARIES SECUREMENT OPTIONS

THERMOPLASTIC
ROOF MEMBRANE
WOOD NAILERS COVERBOARD AND
AND CURB THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND STACK, AND THE
NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE SHEET METAL COVER OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)

TP-17
2001 NOT DRAWN TO SCALE

1168
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC
DRAWBAND OR WELD
SEALANT
COVER TO STACK

FLASHING MEMBRANE
(8'' [200 mm] MIN.
OPTIONAL :
HEIGHT)
REMOVABLE
SHEET METAL
COUNTERFLASHING FASTENERS
SEE NOTE No. 3 MINIMUM TWO
FASTENERS PER SIDE
INSULATE VOID
FOR COLD
STACKS SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECURMENT
OPTIONS
SEALANT (IF REQUIRED
FOR THE SPECIFIC
SYSTEM)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS
AND CURB

NOTES : METAL OR GYPSUM


LINER IF REQUIRED
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND STACK, AND THE
NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE SHEET METAL COVER OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)

TP-17S
2001 NOT DRAWN TO SCALE

1169
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MEMBRANE CAP

PLUMBING VENT STACK

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :

1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. REFER TO THE INTRODUCITON FOR ADDITIONAL INFORMATION.

PLUMBING VENT (FIELD WRAP)

TP-18
2001 NOT DRAWN TO SCALE

1170
The NRCA Roofing and Waterproofing Manual—Fifth Edition

MEMBRANE CAP

PLUMBING VENT STACK

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

NOTES :

1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT (FIELD WRAP)

TP-18S
2001 NOT DRAWN TO SCALE

1171
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLUMBING VENT
STACK

SEALANT

DRAWBAND

INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING

PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)

SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

THERMOPLASTIC
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT
(PREMANUFACTURED BOOT)
TP-18A
2001 NOT DRAWN TO SCALE

1172
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PLUMBING VENT STACK

SEALANT

DRAWBAND

INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING

PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

SEALANT (IF THERMOPLASTIC


REQUIRED FOR THE ROOF MEMBRANE
SPECIFIC SYSTEM)

ROOF DECK

COVERBOARD AND
THERMAL INSULATION

NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT
(PREMANUFACTURED BOOT)
TP-18AS
2001 NOT DRAWN TO SCALE

1173
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G., POLYURETHANE)
SHEET METAL RAIN
COLLAR OVERLAPPING DRAW BAND
PENETRATION POCKET

APPROX.
1/4'' [6 mm]
CLEARANCE
AT CORNERS

FLASHING COMPATIBLE SEALANT


MEMBRANE

4'' [100 mm]


MIN. FLANGE

POURABLE
SEALANT

NON-SHRINK
GROUT

WEATHERPROOF
SOLDERED SHEET METAL OR
MEMBRANE COATED
METAL PITCH PAN
(4'' [100 mm]
MIN. HEIGHT)

COVERBOARD AND
THERMAL INSULATION

BASE MEMBRANE
SECUREMENT AS
REQUIRED FOR
SPECIFIC SYSTEM SEALANT (IF REQUIRED FOR
THE SPECIFIC SYSTEM)
ROOF DECK
THERMOPLASTIC
ROOF MEMBRANE
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TP-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

TP-19
2001 NOT DRAWN TO SCALE

1174
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G., POLYURETHANE)

DRAW BAND

APPROX. 1/4''
[6 mm] CLEARANCE SHEET METAL RAIN
AT CORNERS COLLAR OVERLAPPING
PENETRATION POCKET
COMPATIBLE
SEALANT POURABLE SEALANT

FLASHING
MEMBRANE WEATHERPROOF
SOLDERED SHEET
METAL OR MEMBRANE
COATED METAL PITCH
PAN (4'' [100 mm]
MIN. HEIGHT)

NON-SHRINK GROUT
SEALANT (IF
REQUIRED FOR
THE SPECIFIC 4'' [100 mm]
SYSTEM) MIN. FLANGE

THERMOPLASTIC
ROOF MEMBRANE BASE MEMBRANE
SECUREMENT AS
COVERBOARD AND REQUIRED FOR
THERMAL INSULATION SPECIFIC SYSTEM

ROOF DECK

NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TP-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

TP-19S
2001 NOT DRAWN TO SCALE

1175
The NRCA Roofing and Waterproofing Manual—Fifth Edition

COVERBOARD
AND
THERMAL
INSULATION

THERMOPLASTIC
ROOF MEMBRANE

DRAIN STRAINER

ROOF DECK

CLAMPING RING

DECK CLAMP

ROUND CUT IN
THERMOPLASTIC MEMBRANE;
EXTEND APPROX. 1'' [25 mm]
PAST CLAMPING RING
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN
PIPE DIAMETER

DRAIN BOWL

INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE
TAPERED INSULATION
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

TP-20
2001 NOT DRAWN TO SCALE

1176
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRAIN STRAINER

CLAMPING RING

THERMOPLASTIC
ROOF MEMBRANE

TAPERED INSULATION

COVERBOARD
AND
THERMAL
INSULATION

ROOF DECK

INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE

DECK CLAMP

DRAIN BOWL

HOLE IN MEMBRANE SHOULD BE LARGER THAN


DRAIN PIPE DIAMETER

ROUND CUT IN THERMOPLASTIC MEMBRANE;


EXTEND APPROX. 1'' [25 mm] PAST CLAMPING RING

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

TP-20S
2001 NOT DRAWN TO SCALE

1177
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BEAD OF SEALANT
SOLDERED SHEET METAL
]
OR MEMBRANE COATED
0 mm
METAL SCUPPER [10
N.
MI
OPTIONAL: 3/4'' x 3'' 4''
[19 mm x 75 mm] MIN.
''L'' SHAPED GRAVEL
GUARD SECURED AND SEALED
TO THE SCUPPER FLANGE,
NOTCHED TO PERMIT DRAINAGE

SHEET METAL
CONDUCTOR GASKETED FASTENERS
HEAD
SHEET METAL
FASCIA CAP

SUMP TO DRAIN

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

ADHERED OR WELDED
FLASHING MEMBRANE
(EXTEND APPROX.
3'' [75 mm] BEYOND
SCUPPER)

THERMOPLASTIC ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

WOOD NAILERS

EXTEND FIELD SHEET


TO BELOW BLOCKING

NOTES :

1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.


3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SCUPPER THROUGH ROOF EDGE

TP-21
2001 NOT DRAWN TO SCALE

1178
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
FASCIA CAP
SOLDERED SHEET METAL
OR MEMBRANE COATED
METAL SCUPPER
ADHERED OR WELDED
OPTIONAL: 3/4'' x 3'' FLASHING MEMBRANE
[19 mm x 75 mm] MIN. (EXTEND APPROX.
''L'' SHAPED GRAVEL 3'' [75 mm] BEYOND
GUARD SECURED AND SCUPPER)
SEALED TO THE
SCUPPER FLANGE, THERMOPLASTIC
NOTCHED TO PERMIT ROOF MEMBRANE
DRAINAGE
SEALANT (IF REQUIRED
GASKETED
FOR THE SPECIFIC
FASTENERS
SYSTEM)
SHEET
METAL
CONDUCTOR
HEAD

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS
EXTEND FIELD SHEET
TO BELOW BLOCKING

NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

SCUPPER THROUGH ROOF EDGE

TP-21S
2001 NOT DRAWN TO SCALE

1179
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SOLDERED
SHEET METAL OR SHEET METAL OR
MEMBRANE COATED MEMBRANE COATED
METAL SCUPPER METAL ''GRAVEL STOP''
SET IN COMPATIBLE SEALANT (AS REQUIRED BY
m m] MANUFACTURER)
OPTIONAL : [1 00
3/4'' x 3'' I N.
4 '' M
[19 mm x 75 mm] SEALANT (IF REQUIRED
MIN. ''L'' SHAPED FOR THE SPECIFIC
GRAVEL GUARD SYSTEM)
SECURED TO THE
SCUPPER FLANGE,
NOTCHED TO
PERMIT DRAINAGE

SHEET METAL
CONDUCTOR
HEAD APPROX.
3'' [75 mm]

SUMP AREA IN FRONT


OF SCUPPER TO DRAIN

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)
FLASHING MEMBRANE
ADHERED OR WELDED
TO METAL AND
FIELD MEMBRANE
FASTENERS
3'' to 6'' [75 to 150 mm]
O.C., STAGGER

THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK

WOOD NAILERS

NOTES : EXTEND FIELD SHEET


TO BELOW BLOCKING
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

SCUPPER THROUGH GRAVEL STOP EDGE

TP-21A
2001 NOT DRAWN TO SCALE

1180
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SOLDERED
SHEET METAL OR
MEMBRANE COATED
METAL ''GRAVEL STOP''
(AS REQUIRED BY
MANUFACTURER)

SHEET METAL OR
MEMBRANE COATED
METAL SCUPPER
OPTIONAL :
SEALANT (IF REQUIRED
3/4'' x 3''
FOR THE SPECIFIC
[19 mm x 75 mm]
SYSTEM)
MIN. ''L'' SHAPED
GRAVEL GUARD FLASHING MEMBRANE
SECURED TO THE ADHERED OR WELDED
SCUPPER FLANGE, TO METAL AND FIELD
NOTCHED TO PERMIT MEMBRANE
DRAINAGE
FASTENERS
3'' to 6'' [75 to 150 mm]
O.C., STAGGER
SUMP TO DRAIN
GASKETED
FASTENER

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

THERMOPLASTIC ROOF
MEMBRANE

EXTEND FIELD SHEET


TO BELOW BLOCKING

SHEET METAL
CONDUCTOR HEAD
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

SCUPPER THROUGH GRAVEL-STOP EDGE

TP-21AS
2001 NOT DRAWN TO SCALE

1181
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT
(IF REQUIRED FOR
THE SPECIFIC SYSTEM)

FASTENERS
3'' to 6''
[75 to 150 mm] O.C. OPTION:
STAGGER

THERMOPLASTIC FLASHING MEMBRANE


ROOF MEMBRANE SHEET METAL OR
MEMBRANE COATED
ROOF METAL EDGE
DECK FLASHING WITH 3''
[75 mm] FLANGE
(AS REQ'D FOR
SPECIFIC SYSTEM)
1/2
MI
'' :
OPTIONAL DRAINAGE
N. BAR TO RETAIN
2'' BALLAST
MI
N.
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS

SHEET METAL
GUTTER. THE FRONT
OF THE GUTTER
SHOULD BE A MIN.
1'' [25 mm] LOWER
THAN THE BACK TO
ALLOW OVERFLOW
OPTIONAL: GUTTER
BRACKET SUPPORT

WOOD OPTIONAL:
NAILERS STIFFENING BAR

OPTIONAL: CONTINOUS
SEALANT

NOTES:
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TP-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

TP-22
2001 NOT DRAWN TO SCALE

1182
The NRCA Roofing and Waterproofing Manual—Fifth Edition
THERMOPLASTIC ROOF MEMBRANE

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)
FLASHING MEMBRANE

FASTENERS AT APPROX.
3'' TO 6'' [75 mm TO 150 mm]
O.C., STAGGER
SEALANT (IF REQUIRED
BY THE SPECIFIC SYSTEM)
SHEET METAL OR
MEMBRANE COATED
METAL EDGE FLASHING
WITH 3'' [75 mm] FLANGE
(AS REQUIRED BY
SPECIFIC SYSTEM)
:
OPTIONAL DRAINAGE
BAR TO RETAIN
BALLAST

ROOF DECK

COVERBOARD AND
THERMAL INSULATION

WOOD NAILERS

EXTEND FIELD SHEET


OR A SEPARATE
MEMBRANE SHEET

GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS SHEET METAL GUTTER.
THE FRONT OF THE
OPTIONAL : GUTTER GUTTER SHOULD BE A
BRACKET SUPPORT MINIMUM 1'' [25 mm]
LOWER THAN THE
BACK TO ALLOW
OVERFLOW
NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TP-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

TP-22S
2001 NOT DRAWN TO SCALE

1183
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS APPROX.
12'' [300 mm] O.C. SHEET METAL PARAPET
CAP
EXTEND MEMBRANE
TO BELOW NAILER CONTINUOUS SHIM
AND SECURE
BELOW BLOCKING

GASKETED FASTENERS
1'' [25 mm] MIN.

WOOD NAILER

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

FLASHING MEMBRANE

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK
CONTINUOUS CLEAT
FASTENED PER TABLE 1
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TS-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING) AND


BASE FLASHING

TS-1
2001 NOT DRAWN TO SCALE

1184
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL PARAPET


CAP

FASTENERS APPROX. 12''


[300 mm] O.C.

CONTINUOUS SHIM
BELOW BLOCKING
1'' [25 mm] MIN.

WOOD NAILER

GASKETED FASTENERS

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

EXTEND MEMBRANE TO
BELOW NAILER AND SECURE

CONTINUOUS CLEAT

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TP-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING) AND


BASE FLASHING

TS-1S
2001 NOT DRAWN TO SCALE

1185
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD CANT FASTENED


TO WOOD NAILERS
GASKETED FASTENERS

SHEET METAL FASCIA CAP

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
BELOW BLOCKING

FASTENERS -
1'' [25 mm] MIN.

SEE SINGLE PLY TABLE 7


FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

CONTINUOUS CLEAT
(FASTENED PER TABLE 1)

NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)
TS-2
2001 NOT DRAWN TO SCALE

1186
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL FASCIA CAP

GASKETED FASTENERS

WOOD CANT FASTENED TO


WOOD NAILERS

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
BELOW BLOCKING
1'' [25 mm] MIN.

WOOD NAILERS

EXTEND MEMBRANE BELOW


WOOD BLOCKING

CONTINUOUS CLEAT
(FASTENED PER TABLE 1)

NOTES :
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED PERIMETER EDGE WITH


METAL FLASHING (FASCIA CAP)
TS-2S
2001 NOT DRAWN TO SCALE

1187
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT (IF REQUIRED
FOR THE SPECIFIC SYSTEM)
1 1/2'' [38mm] MIN. FOR
BALLASTED SYSTEMS
1/2'' [13 mm]
MIN. CLEARANCE FLANGE APPROX.
3'' [75 mm] WIDE
2'' [50 mm]
MIN. CLEARANCE APPROX. 3''
[75 mm]
BELOW BLOCKING
1'' [25mm] MIN.

ADHERED
FLASHING MEMBRANE
(EXTEND APPROX. 3''
[75 mm] BEYOND FLANGE)

FASTENERS 3'' to 6''


[75 to 150 mm] O.C.;
STAGGER

SHEET METAL
''GRAVEL STOP'' (AS
REQUIRED BY
MANUFACTURER)

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER EXTEND FIELD SHEET TO
SINGLE-PLY TABLE 1) BELOW BLOCKING

NOTES :

1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)

TS-3
2001 NOT DRAWN TO SCALE

1188
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL ''GRAVEL STOP''

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)
FASTENERS 3'' to 6''
[75 to 150 mm] O.C.,
STAGGER

ADHERED FLASHING
EXCEED HEIGHT OF BALLAST

MEMBRANE (EXTEND
APPROX. 3'' [75 mm]
BALLASTED SYSTEMS TO

BEYOND FLANGE)
1 1/2'' [38 mm] MIN. FOR

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION
BELOW BLOCKING

ROOF DECK
1'' [25 mm] MIN.

EXTEND FIELD SHEET TO


BELOW BLOCKING

CONTINUOUS CLEAT
(FASTENED PER
SINGLE-PLY TABLE 1)

NOTES :

1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECURMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)

TS-3S
2001 NOT DRAWN TO SCALE

1189
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT (IF REQUIRED


FOR THE SPECIFIC SYSTEM)

PERIMETER SHEET
FLANGE APPROX.
METAL FLASHING
3'' [75 mm]
APPROX.
3'' [75 mm]
CONTINUOUS CLEAT
FASTENED PER TABLE 1.
BELOW BLOCKING
1'' [25 mm] MIN.

ADHERED FLASHING
MEMBRANE

FASTENERS 3'' to 6''


[75 to 150 mm] O.C.
STAGGER

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

EXTEND FIELD SHEET

OPTIONAL : WOOD NAILER


AND SHEET METAL
NOTES : CLOSURE
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

DRAINING PERIMETER EDGE

TS-3A
2001 NOT DRAWN TO SCALE

1190
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT (IF REQUIRED FOR THE


SPECIFIC SYSTEM)

PERIMETER SHEET METAL FLASHING

FASTENERS 3'' to 6'' [75 to 150 mm]


O.C., STAGGER

ADHERED FLASHING MEMBRANE

SEALANT (IF REQUIRED FOR THE


SPECIFIC SYSTEM)

THERMOSET ROOF MEMBRANE


BELOW BLOCKING
1'' [25 mm] MIN.

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

EXTEND FIELD SHEET

WOOD NAILERS

OPTIONAL: WOOD NAILER AND


SHEET METAL CLOSURE

CONTINUOUS CLEAT
FASTENED PER TABLE 1.

NOTES :

1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

DRAINING PERIMETER EDGE

TS-3AS
2001 NOT DRAWN TO SCALE

1191
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF
CONCRETE FASTENERS

SHEET METAL COUNTERFLASHING


(SEE TABLE 2)

OPTIONAL :
INSTALL COMPRESSIBLE
ELASTOMERIC SEALANT
OR TAPE TO SPAN IRREGULARITIES

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT OPTIONS

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS

TS-4
2001 NOT DRAWN TO SCALE

1192
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INSTALL APPROPRIATE SEALANT


(E.G., POLYURETHANE) AND TOOL
TO FACILITATE WATER RUN-OFF

OPTIONAL :
INSTALL COMPRESSIBLE
ELASTOMERIC SEALANT
OR TAPE TO SPAN IRREGULARITIES

CONCRETE FASTENERS

TERMINATION BAR FASTENED WITH


APPROPRIATE FASTENERS APPROX.
12'' [300 mm] O.C.

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE

SHEET METAL COUNTERFLASHING


(SEE TABLE 2)

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT OPTIONS

THERMOSET
ROOF MEMBRANE

COVER BOARD AND


THERMAL INSULATION

ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS

TS-4S
2001 NOT DRAWN TO SCALE

1193
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

REMOVABLE SHEET METAL


COUNTERFLASHING

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

INSTALL SEALANT BEHIND


MEMBRANE

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

THERMOSET ROOF MEMBRANE

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE PERIMETER
SECUREMENT OPTIONS

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
NOTES :
1. THE JOINTS IN THE SHEET METAL COUNTERFLASHING SHOULD NOT BE SOLDERED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR WALL-


SUPPORTED DECK

TS-5
2001 NOT DRAWN TO SCALE

1194
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

INSTALL SEALANT BEHIND


MEMBRANE

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENER
APPROX. 12'' [300 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT OPTIONS

THERMOSET ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
NOTES :
1. THE JOINTS IN THE SHEET METAL COUNTERFLASHING SHOULD NOT BE SOLDERED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR WALL -


SUPPORTED DECK

TS-5S
2001 NOT DRAWN TO SCALE

1195
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INSTALL COMPATIBLE
SEALANT BEHIND MEMBRANE

SHEET METAL REGLET

FASTENERS

TERMINATION BAR FASTENED


WITH APPROPRIATE
FASTENERS APPROX.
12'' [300 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

FLEXIBLE FOAM ROD;


MINIMUM DIAMETER 1 1/2
TIMES WIDTH OF OPENING

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

THERMOSET ROOF
MEMBRANE

FLEXIBLE VAPOR RETARDER


WITH COMPRESSIBLE
INSULATION

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
NOTES :
WOOD NAILERS
1. THIS DETAIL ACCOMMODATES INDEPENDENT WALL AND DECK MOVEMENT.
2. OTHER METHODS OF COUNTERFLASHING MAY BE APPLICABLE (SEE TABLE 2).
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK

TS-6
2001 NOT DRAWN TO SCALE

1196
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

FASTENERS

INSTALL COMPATIBLE SEALANT


BEHIND MEMBRANE

TERMINATION BAR FASTENED


WITH APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT

FLEXIBLE FOAM ROD - MINIMUM


DIAMETER 1 1/2 TIMES WIDTH
OF OPENING
SEAM PLATES AND FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

FLEXIBLE VAPOR RETARDER


WITH COMPRESSIBLE
NOTES : INSULATION
1. THIS DETAIL ACCOMMODATES INDEPENDENT WALL AND DECK MOVEMENT.
2. OTHER METHODS OF COUNTERFLASHING MAY BE APPLICABLE (SEE TABLE 2).
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

BASE FLASHING FOR


NON-WALL-SUPPORTED DECK

TS-6S
2001 NOT DRAWN TO SCALE

1197
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
FLEXIBLE VAPOR EXPANSION JOINT
RETARDER TO SERVE COVER
AS INSULATION RETAINER FLEXIBLE
(ATTACHED TO TOP WEATHERPROOF
OF CURB) MEMBRANE CLOSURE -
OPTIONAL IF
DOUBLE LOCK
COMPRESSIBLE
STANDING SEAM JOINTS
INSULATION
ARE USED WITH THE
METAL PARAPET CAP
FASTENERS APPROX.
8'' [200 mm] O.C.
8'' [200 mm] MINIMUM
FLASHING HEIGHT

GASKETED FASTENERS
ON LOW SIDE

FLASHING MEMBRANE

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS

THERMOSET ROOF
MEMBRANE

TOP OF
CURB TO DRAIN
TO ONE SIDE
WOOD NAILERS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

TS-7
2001 NOT DRAWN TO SCALE

1198
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE VAPOR SHEET METAL


RETARDER TO SERVE EXPANSION JOINT
AS INSULATION COVER
RETAINER (ATTACHED FLEXIBLE
TO TOP OF CURB) WEATHERPROOF
MEMBRANE CLOSURE -
COMPRESSIBLE OPTIONAL IF
INSULATION DOUBLE LOCK
STANDING SEAM JOINTS
ARE USED WITH THE
TOP OF CURB
METAL PARAPET CAP
TO DRAIN TO
ONE SIDE FASTENERS APPROX.
8'' [200 mm] O.C.

GASKETED FASTENERS

FLASHING MEMBRANE

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
8'' [200 mm] MINIMUM
FLASHING HEIGHT

FASTENERS -
ON LOW SIDE

SEE SINGLE PLY TABLE 7


FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES : WOOD NAILERS


1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH METAL COVER

TS-7S
2001 NOT DRAWN TO SCALE

1199
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE VAPOR PREMANUFACTURED


RETARDER TO SERVE EXPANSION JOINT
AS INSULATION RETAINER COVER
(ATTACHED TO TOP
OF CURB) FLEXIBLE
WEATHERPROOF
COMPRESSIBLE MEMBRANE CLOSURE
INSULATION
GASKETED FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT

FASTENERS APPROX.
8'' [200 mm] O.C.

FLASHING MEMBRANE

THERMOSET
ROOF MEMBRANE

TOP OF CURB REINFORCED MEMBRANE


TO DRAIN TO ATTACHMENT STRIP WITH
THE OUTSIDE SEAM PLATES AND
FASTENERS -
WOOD NAILERS SEE SINGLE PLY TABLE 7
FOR ALTERNATE
COVERBOARD AND PERIMETER SECUREMENT
THERMAL INSULATION OPTIONS

ROOF DECK

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
TS-7A
2001 NOT DRAWN TO SCALE

1200
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PREMANUFACTURED
EXPANSION JOINT
COVER

FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE
TOP OF CURB
TO DRAIN TO FASTENERS APPROX.
THE OUTSIDE 8'' [200 mm] O.C.

GASKETED FASTENERS

FLASHING MEMBRANE

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
8'' [200 mm] MINIMUM
FLASHING HEIGHT

FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
FLEXIBLE VAPOR
RETARDER TO WOOD NAILERS
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB) COMPRESSIBLE
INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
TS-7AS
2001 NOT DRAWN TO SCALE

1201
The NRCA Roofing and Waterproofing Manual—Fifth Edition

UNREINFORCED
THERMOSET ROOF
MEMBRANE

FASTEN AT
APPROXIMATELY
12'' [300 mm] O.C. ON ONE
SIDE OF EXPANSION JOINT
ONLY TO PERMIT
MOVEMENT

4'' [100 mm]


MINIMUM 2'' [50 mm]
MAXIMUM

SHEET METAL PLATE :


MINIMUM ONE GAUGE
HEAVIER THAN GAUGE
OF METAL DECK OR
MIN. 22 GAUGE FOR
OTHER DECK TYPES
(HEM EDGES)

ROOF DECK

COVERBOARD AND
THERMAL INSULATION

NOTES :
1. THIS DETAIL SHOULD ONLY BE USED WITH UNREINFORCED, LOOSE-LAID, BALLASTED SYSTEMS.
2. IF EXPANSION IS GREATER THAN 2'', DETAIL 7A OR 7B ARE PREFERRED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ALTERNATE EXPANSION JOINT FOR


LOOSE-LAID, BALLASTED SYSTEMS
TS-7B
2001 NOT DRAWN TO SCALE

1202
The NRCA Roofing and Waterproofing Manual—Fifth Edition

COVERBOARD AND UNREINFORCED


THERMAL INSULATION THERMOSET ROOF
4'' [100 mm] MEMBRANE
MINIMUM

2'' [50 mm] ROOF DECK


MAXIMUM
CUTOUT SHOWN FOR
CLARITY - INSULATION
BOARDS ARE NOT
KERFED

FASTEN AT SHEET METAL PLATE -


APPROXIMATELY MINIMUM ONE GAUGE
12'' [300 mm] O.C. ON HEAVIER THAN GAUGE
ONE SIDE OF EXPANSION OF METAL DECK OR
JOINT ONLY TO MIN. 22 GA. FOR
PERMIT MOVEMENT OTHER DECK TYPES
(HEM EDGES)

NOTES :
1. THIS DETAIL SHOULD ONLY BE USED WITH UNREINFORCED, LOOSE-LAID, BALLASTED SYSTEMS.
2. IF EXPANSION IS GREATER THAN 2'', DETAIL 7A OR 7B ARE PREFERRED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ALTERNATE EXPANSION JOINT FOR


LOOSE-LAID, BALLASTED SYSTEMS
TS-7BS
2001 NOT DRAWN TO SCALE

1203
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
AREA DIVIDER
COVER

GASKETED
FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT

FLASHING
MEMBRANE

THERMOSET
ROOF MEMBRANE

REINFORCED MEMBRANE
WOOD NAILERS ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
ROOF DECK
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
COVERBOARD AND
THERMAL INSULATION

NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

AREA DIVIDER IN ROOF SYSTEM

TS-8
2001 NOT DRAWN TO SCALE

1204
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL AREA


DIVIDER COVER
GASKETED
FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT

REINFORCED MEMBRANE
ATTACHMENT STRIP FLASHING MEMBRANE
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER THERMOSET
SECUREMENT OPTIONS ROOF MEMBRANE

WOOD NAILERS

ROOF DECK

COVERBOARD AND
THERMAL INSULATION
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

AREA DIVIDER IN ROOF SYSTEM

TS-8S
2001 NOT DRAWN TO SCALE

1205
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WIDTH OF EQUIPMENT HEIGHT


OF LEGS
UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
SHEET METAL COVER
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]
SET NEOPRENE PAD IN
SEALANT (BY OTHERS)

SET BOLTS IN SEALANT


(BY OTHERS)

GASKETED FASTENERS

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS

WOOD CURB

WOOD NAILERS
THERMOSET
ROOF MEMBRANE
ROOF DECK

COVERBOARD AND
THERMAL INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL TP-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS
ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT CURB

TS-9
2001 NOT DRAWN TO SCALE

1206
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEIGHT
WIDTH OF EQUIPMENT OF LEGS
SET BOLTS IN SEALANT
UP TO 24'' [UP TO 600 mm] 24'' [600 mm] (BY OTHERS)
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
SET NEOPRENE PAD IN
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m] SEALANT (BY OTHERS)

SHEET METAL COVER

GASKETED FASTENERS

FLASHING MEMBRANE
REINFORCED MEMBRANE (8'' [200 mm] MIN.
ATTACHMENT STRIP HEIGHT)
WITH SEAM PLATES AND
FASTENERS -
THERMOSET
SEE SINGLE PLY TABLE 7
ROOF MEMBRANE
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

ROOF DECK

COVERBOARD AND WOOD NAILERS


THERMAL INSULATION
WOOD CURB
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL TP-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS
ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT CURB

TS-9S
2001 NOT DRAWN TO SCALE

1207
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL FRAME

HEIGHT-
SEE TABLE

LE
AB
E ET
SEE DETAIL -S
TH
TP-11 FOR FLASHING ID
W
OF SUPPORT LEGS

ROUND PIPE COLUMN

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL TP-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED
DIRECTLY OVER COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE
ADAPTED FOR OTHER USES, SUCH AS SIGN SUPPORTS.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND

TS-10
2001 NOT DRAWN TO SCALE

1208
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOR HEIGHT OF LEGS


SEE TABLE ON TS-10

SEALANT

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

FILL GAPS WITH


INSULATION BOARD
NOTES : TO PROVIDE EVEN
SUBSTRATE
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND LEG


(FIELD WRAP)
TS-11
2001 NOT DRAWN TO SCALE

1209
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
FOR HEIGHT OF LEGS
SEE TABLE ON TS-10

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM
FILL GAPS WITH
INSULATION BOARD
NOTES : TO PROVIDE EVEN
SUBSTRATE
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

EQUIPMENT SUPPORT STAND LEG


(FIELD WRAP)
TS-11S
2001 NOT DRAWN TO SCALE

1210
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALING MATERIAL

RAISED CURB
GASKETED FASTENERS
WOOD NAILER MIN. TWO FASTENERS
PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE
7 FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS

ALTERNATE CURB
BEARING LOCATION
FOR HEAVY-WEIGHT THERMOSET
LOADING CONDITIONS ROOF MEMBRANE

MECHANICAL UNIT, HOOD, ETC.


BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND
TOP OF CURB
COVERBOARD AND
SEALING MATERIAL - MUST THERMAL INSULATION
BE CONTINUOUS ON TOP
OF THE CURB ROOF DECK

1'' [25 mm] MINIMUM


BELOW TOP OF CURB

FASTENERS NOTES :
WOOD NAILER 1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE
TO BE SUPPLIED BY THE CURB MANUFACTURER.
COUNTERFLASHING
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
INSULATION BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
FLASHING MEMBRANE 3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INFORMATION.
RAISED CURB 4. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
TS-12
2001 NOT DRAWN TO SCALE

1211
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD NAILER

GASKETED FASTENERS
MIN. TWO FASTENERS
PER SIDE
SEALING MATERIAL
REMOVABLE
RAISED CURB SHEET METAL
COUNTERFLASHING

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SEE SINGLE PLY
TABLE 7 FOR
FLASHING ALTERNATE PERIMETER
MEMBRANE SECUREMENT OPTIONS
(8'' [200 mm]
MIN. HEIGHT)

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
NOTES : LOADING CONDITIONS

1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
TS-12S
2001 NOT DRAWN TO SCALE

1212
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD CURB
SEALING MATERIAL
WOOD
NAILERS

SHEET METAL
COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET
MECHANICAL UNIT, HOOD, ETC.
ROOF MEMBRANE
ALTERNATE :
BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND
TOP OF CURB
SEALING MATERIAL - MUST COVERBOARD AND
BE CONTINUOUS ON TOP THERMAL INSULATION
OF THE CURB
ROOF DECK
1'' [25 mm] MINIMUM
BELOW TOP OF CURB
FLASHING RECEIVER
FASTENERS

COUNTERFLASHING

FLASHING MEMBRANE

WOOD CURB

NOTES :
1. THE MECHANICAL UNITS SHOULD NOT BE SET
UNTIL THE ROOF MEMBRANE AND FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
TS-13
2001 NOT DRAWN TO SCALE

1213
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALING MATERIAL

REMOVABLE
SHEET METAL
COUNTERFLASHING

WOOD CURB

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

NOTES :
1. THE MECHANICAL UNITS SHOULD NOT BE SET
UNTIL THE ROOF MEMBRANE AND FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
TS-13S
2001 NOT DRAWN TO SCALE

1214
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MIN. TWO FASTENERS PER
SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

THERMOSET
ROOF MEMBRANE

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

NOTES : WOOD NAILERS AND CURB

1. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm],
THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

TS-14
2001 NOT DRAWN TO SCALE

1215
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS MIN.


TWO FASTENERS PER
SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

WOOD NAILERS AND CURB


NOTES :

1. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm],
THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

TS-14S
2001 NOT DRAWN TO SCALE

1216
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INSULATE VOID
TO PREVENT
CONDENSATION

WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)

FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS
AND CURB

NOTES :

1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE AND ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

STRUCTURAL MEMBER THROUGH


ROOF DECK
TS-15
2001 NOT DRAWN TO SCALE

1217
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INSULATE VOID
TO PREVENT
CONDENSATION
WELDED PLATE
SEALED WATERTIGHT
FASTENERS
(BY OTHERS)
MINIMUM TWO
FASTENERS
WOOD CURB PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING
FASTENERS
APPROX. 8'' FLASHING
[203 mm] O.C. MEMBRANE
(8'' [200 mm]
MIN. HEIGHT)

THERMOSET
ROOF MEMBRANE

WOOD
NAILERS

REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT ROOF DECK
OPTIONS
COVERBOARD AND
THERMAL INSULATION

NOTES :

1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

STRUCTURAL MEMBER THROUGH


ROOF DECK
TS-15S
2001 NOT DRAWN TO SCALE

1218
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
ENCLOSURE
WITH REMOVABLE TOP
-CROSSBREAK OR
SLOPE FOR DRAINAGE
INSULATE VOID
TO PREVENT
CONDENSATION

SHEET METAL OR
FLEX-TUBE COLLAR

SLOPE PIPES DOWN AND


AWAY FROM HOOD

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

OPTIONAL :REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
MIN. 4'' [100 mm] ATTACHMENT STRIP WITH
CLEARANCE FROM SEAM PLATES AND
PIPE TO TOP OF FASTENERS -
CURB - MIN. 2'' SEE SINGLE PLY TABLE 7
[50 mm] BETWEEN FOR ALTERNATE
PIPES PERIMETER SECUREMENT
OPTIONS
SHEET METAL
FLASHING
RECEIVER
THERMOSET
WOOD NAILERS ROOF MEMBRANE
AND CURB
COVERBOARD AND
THERMAL INSULATION
NOTES :
ROOF DECK
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL
METHOD OF GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK
TS-16
2001 NOT DRAWN TO SCALE

1219
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT MIN. 4'' [100 mm]


CLEARANCE FROM
SLOPE PIPES DOWN PIPE TO TOP OF
AND AWAY FROM HOOD CURB; MIN. 2''
[50 mm] BETWEEN
INSULATE VOID PIPES
TO PREVENT
SHEET METAL OR
CONDENSATION
FLEX-TUBE COLLAR
SHEET METAL ENCLOSURE SHEET METAL FLASHING
WITH REMOVABLE TOP RECEIVER
- CROSSBREAK OR
SLOPE FOR DRAINAGE GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
MINIMUM FLASHING

AND FASTENERS - SEE


SINGLE PLY TABLE 7
8'' [200 mm]

HEIGHT

FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS

THERMOSET
ROOF MEMBRANE
WOOD NAILERS
AND CURB THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS
AND AN OPTIONAL METHOD OF GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING


THROUGH ROOF DECK
TS-16S
2001 NOT DRAWN TO SCALE

1220
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT

DRAWBAND OR WELD
UMBRELLA TO STACK

INSULATE VOID FOR


COLD STACKS

FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

OPTIONAL : REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE-PLY TABLE 7
FOR ALTERNATE
METAL OR PERIMETER
GYPSUM LINER SECUREMENT OPTIONS
IF REQUIRED

VARIES

THERMOSET
ROOF MEMBRANE

WOOD NAILERS
AND CURB

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE STACK,
AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE SHEET METAL COVER OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
TS-17
2001 NOT DRAWN TO SCALE

1221
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
UMBRELLA TO STACK
INSULATE VOID FOR
COLD STACKS
FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE-PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
AND CURB

NOTES : METAL OR GYPSUM


LINER IF REQUIRED
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE STACK,
AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE SHEET METAL COVER OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

ISOLATED STACK FLASHING


(HOT OR COLD)
TS-17S
2001 NOT DRAWN TO SCALE

1222
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

PLUMBING VENT STACK

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

NOTES :

1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING SEE TABLE 4.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT (FIELD WRAP)

TS-18
2001 NOT DRAWN TO SCALE

1223
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PIPE PENETRATION

SEALANT

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION
ROOF DECK

BASE MEMBRANE
ATTACHMENT AS
REQUIRED BY
SPECIFIC SYSTEM

NOTES :

1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING SEE TABLE 4.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT (FIELD WRAP)

TS-18S
2001 NOT DRAWN TO SCALE

1224
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLUMBING VENT
STACK

SEALANT

DRAWBAND

INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING

PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)

SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

THERMOSET
ROOF MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT
(PREMANUFACTURED BOOT)
TS-18A
2001 NOT DRAWN TO SCALE

1225
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLUMBING VENT STACK

SEALANT

DRAWBAND

INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING

PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)

BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

SEALANT (IF THERMOPLASTIC


REQUIRED FOR THE ROOF MEMBRANE
SPECIFIC SYSTEM)

ROOF DECK

COVERBOARD AND
THERMAL INSULATION
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT
(PREMANUFACTURED BOOT)
TS-18AS
2001 NOT DRAWN TO SCALE

1226
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL RAIN APPROPRIATE SEALANT
COLLAR OVERLAPPING (E.G., POLYURETHANE)
PENETRATION POCKET
DRAW BAND
APPROX.
1/4'' [6 mm] EXTEND 1'' [25 mm]
CLEARANCE MINIMUM INTO PAN
AT CORNERS
4'' [100 mm]
FLASHING MIN. FLANGE
MEMBRANE

BASE MEMBRANE
SECUREMENT AS
REQUIRED FOR
SPECIFIC SYSTEM

POURABLE
SEALANT

NON-SHRINK
GROUT

WEATHERPROOF
SHEET METAL PITCH PAN
SOLDERED/WELDED JOINTS
(4'' [100 mm] MIN. HEIGHT

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

THERMOSET
ROOF MEMBRANE

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TS-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

TS-19
2001 NOT DRAWN TO SCALE

1227
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
(E.G., POLYURETHANE)

DRAW BAND

APPROX. 1/4''
[6 mm] CLEARANCE SHEET METAL RAIN
AT CORNERS COLLAR OVERLAPPING
PENETRATION POCKET
EXTEND 1'' [25 mm]
MINIMUM INTO PAN POURABLE SEALANT

FLASHING
MEMBRANE WEATHERPROOF
SHEET METAL PITCH
PAN WITH SOLDERED/
JOINTS (4'' [100 mm]
MIN. HEIGHT)

NON-SHRINK GROUT

SEALANT (IF 4'' [100 mm]


REQUIRED FOR MIN. FLANGE
THE SPECIFIC
SYSTEM)

THERMOSET
ROOF MEMBRANE
BASE MEMBRANE
COVERBOARD AND SECUREMENT AS
THERMAL INSULATION REQUIRED FOR
SPECIFIC SYSTEM
ROOF DECK

NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TS-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PENETRATION POCKET

TS-19S
2001 NOT DRAWN TO SCALE

1228
The NRCA Roofing and Waterproofing Manual—Fifth Edition

COVERBOARD AND
THERMAL INSULATION

THERMOSET
ROOF MEMBRANE
DRAIN STRAINER

ROOF DECK

CLAMPING RING

DECK CLAMP

ROUND CUT IN
THERMOSET MEMBRANE;
EXTEND APPROX. 1'' [25 mm]
PAST CLAMPING RING
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN
PIPE DIAMETER

DRAIN BOWL

INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE

TAPERED INSULATION

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

TS-20
2001 NOT DRAWN TO SCALE

1229
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRAIN STRAINER

CLAMPING RING

THERMOSET
ROOF MEMBRANE

TAPERED INSULATION

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE

DECK CLAMP

DRAIN BOWL

HOLE IN MEMBRANE SHOULD BE LARGER THAN


DRAIN PIPE DIAMETER

ROUND CUT IN THERMOSET MEMBRANE;


EXTEND APPROX. 1'' [25 mm] PAST CLAMPING RING

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

TS-20S
2001 NOT DRAWN TO SCALE

1230
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BEAD OF SEALANT

SHEET METAL SCUPPER


WITH SOLDERED JOINTS

m m]
OPTIONAL: 3/4'' x 3'' 00
[19 mm x 75 mm] MIN. . [1
M IN
''L'' SHAPED GRAVEL 4''
GUARD SECURED AND
SEALED TO THE SCUPPER
FLANGE, NOTCHED
TO PERMIT DRAINAGE
GASKETED FASTENERS

SHEET METAL SHEET METAL


CONDUCTOR FASCIA CAP
HEAD
SUMP TO DRAIN

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

ADHERED OR WELDED
FLASHING MEMBRANE
(EXTEND APPROX.
3'' [75 mm] BEYOND
SCUPPER)

THERMOPLASTIC ROOF
MEMBRANE

COVERBOARD AND
EXTEND FIELD SHEET THERMAL INSULATION
TO BELOW BLOCKING

ROOF DECK
WOOD NAILERS

NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

SCUPPER THROUGH RAISED


EDGE PERIMETER

TS-21
2001 NOT DRAWN TO SCALE

1231
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
FASCIA CAP

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SHEET METAL SCUPPER SYSTEM)
WITH SOLDERED JOINTS
ADHERED OR WELDED
OPTIONAL: 3/4'' x 3'' FLASHING MEMBRANE
[19 mm x 75 mm] MIN. (EXTEND APPROX.
''L'' SHAPED GRAVEL 3'' [75 mm] BEYOND
GUARD SECURED AND SCUPPER)
SEALED TO THE SCUPPER
FLANGE, NOTCHED THERMOPLASTIC
TO PERMIT DRAINAGE ROOF MEMBRANE
SEALANT (IF REQUIRED
FOR THE SPECIFIC
SYSTEM)

SHEET METAL SUMP TO DRAIN


CONDUCTOR
HEAD

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
GASKETED
WOOD NAILERS
FASTENERS
EXTEND FIELD SHEET
TO BELOW BLOCKING

NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

SCUPPER THROUGH RAISED


PERIMETER EDGE

TS-21S
2001 NOT DRAWN TO SCALE

1232
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SOLDERED SHEET SHEET METAL


METAL SCUPPER SET ''GRAVEL STOP''
IN COMPATIBLE SEALANT
OPTIONAL: SEALANT (IF REQUIRED
3/4'' x 3'' m]
0 0m FOR THE SPECIFIC
[19 mm x 75 mm] N . [1 SYSTEM)
MI
MIN. ''L'' SHAPED 4''
GRAVEL GUARD
SECURED TO THE
SCUPPER FLANGE,
NOTCHED TO
PERMIT DRAINAGE

SHEET METAL
CONDUCTOR
HEAD
APPROX.
3'' [75 mm]

SUMP AREA IN FRONT


OF SCUPPER TO DRAIN

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)
ADHERED FLASHING
MEMBRANE BONDED
TO METAL AND
FIELD MEMBRANE
FASTENERS AT APPROX.
3'' TO 6'' [75 TO
150 mm] O.C., STAGGER

THERMOSET ROOF
MEMBRANE

COVERBOARD AND
THERMAL INSULATION

ROOF DECK

WOOD NAILERS

NOTES : EXTEND FIELD SHEET


1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN. TO BELOW BLOCKING
2. REFER TO THE INTRODUCTION FOR ADDITTIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

SCUPPER THROUGH GRAVEL-STOP EDGE

TS-21A
2001 NOT DRAWN TO SCALE

1233
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
''GRAVEL STOP''

SHEET METAL SCUPPER

SEALANT (IF REQUIRED


FOR THE SPECIFIC
SYSTEM)

ADHERED FLASHING
MEMBRANE BONDED TO
METAL AND FIELD
MEMBRANE
OPTIONAL :
3/4'' x 3'' FASTENERS AT APPROX.
[19 mm x 75 mm] 3'' TO 6'' [75 TO 150 mm]
MIN. ''L'' SHAPED O.C., STAGGER
GRAVEL GUARD
SECURED TO THE
SUMP TO DRAIN
SCUPPER FLANGE,
NOTCHED TO PERMIT
DRAINAGE

GASKETED
FASTENER

COVERBOARD AND
THERMAL INSULATION

ROOF DECK
THERMOSET ROOF
MEMBRANE

EXTEND FIELD SHEET


TO BELOW BLOCKING

SHEET METAL
CONDUCTOR HEAD

NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

SCUPPER THROUGH GRAVEL-STOP EDGE

TS-21AS
2001 NOT DRAWN TO SCALE

1234
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT
(IF REQUIRED FOR
THE SPECIFIC SYSTEM)

FASTENERS
3'' to 6''
[75 to 150 mm] O.C.
STAGGER OPTION:

THERMOSET FLASHING MEMBRANE


ROOF MEMBRANE
SHEET METAL EDGE
ROOF FLASHING WITH 3''
DECK [75 mm] FLANGE

GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS

SHEET METAL
GUTTER. THE FRONT
OF THE GUTTER
SHOULD BE A MIN.
1'' [25 mm] LOWER
THAN THE BACK TO
ALLOW OVERFLOW
OPTIONAL : GUTTER
BRACKET SUPPORT

WOOD OPTIONAL:
NAILERS STIFFENING BAR

OPTIONAL: CONTINUOUS
SEALANT

NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TP-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

TS-22
2001 NOT DRAWN TO SCALE

1235
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EDGE SEALANT (IF REQUIRED FOR THE


FLASHING WITH 3'' [75 mm] SPECIFIC SYSTEM)
FLANGE - OPTIONAL :
DRAINAGE BAR TO FLASHING MEMBRANE
RETAIN BALLAST
FASTENERS AT APPROX. 3'' TO
6'' [75 TO 150 mm] O.C.,
STAGGER
GUTTER SPACERS
THERMOSET ROOF MEMBRANE
INSTALLED BETWEEN
GUTTER BRACKETS SEALANT (IF REQUIRED FOR THE
SPECIFIC SYSTEM)

ROOF
DECK

COVERBOARD
AND THERMAL
INSULATION

OPTIONAL: GUTTER WOOD


BRACKET SUPPORT NAILERS

SHEET METAL GUTTER


THE FRONT OF THE GUTTER
SHOULD BE A MINIMUM 1''
[25 mm] LOWER THAN THE
BACK TO ALLOW OVERFLOW

EXTEND FIELD SHEET OR A SEPARATE


MEMBRANE SHEET

NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TS-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO
DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY SECURMENT OPTIONS FOR
SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.

GUTTER

TS-22S
2001 NOT DRAWN TO SCALE

1236
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD NAILER
CONTINUOUS SHIM
CONTINUOUS CLEAT
FASTENED PER
TABLE 1 EXTENDED BASE FLASHING

SHEET METAL PARAPET CAP


SLOPED TO DRAIN TO
ROOF SIDE

GASKETED FASTENERS
EXTENDED BASE FLASHING -
OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS ARE
USED WITH THE METAL
PARAPET CAP

FASTENERS APPROX.
8'' [200 mm] O.C.
1'' [25 mm] MIN.
BELOW BLOCKING

GEOTEXTILE FABRIC (EXTEND


ABOVE BALLAST)

AGGREGATE BALLAST

PRIME SURFACE AS REQUIRED

POLYETHYLENE SLIP SHEET


(4 MIL MIN.)

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)

MULTIPLE-PLY MEMBRANE
BASE FLASHING FEATHERED
AT FIELD OF ROOF

MULTIPLE-PLY BUILT-UP
CANT ROOF MEMBRANE
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL. DETAIL BUR-4
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET MEMBRANE LINER.
3. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
4. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
6. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING)


AND BASE FLASHING
BUR-P-1
2001 NOT DRAWN TO SCALE

1237
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE No. 3

FASTENERS APPROX. 8''


[200 mm] O.C.

GEOTEXTILE FABRIC (EXTEND


ABOVE BALLAST)

AGGREGATE BALLAST

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)

POLYETHYLENE SLIP SHEET


(4 MIL MIN.)

MULTIPLE-PLY MEMBRANE BASE


FLASHING (8'' [200 mm] MIN.
WOOD CURB
HEIGHT ABOVE TOP OF
CANT INSULATION SHEET) FEATHERED
AT FIELD OF ROOF
ROOF DECK
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE

NOTES :
1. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURER'S RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/ OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

BUR-P-14
2001 NOT DRAWN TO SCALE

1238
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TOP OF FLASHING
CAPPED OR ROLLED
INTO PIPE APPROX.
1'' [25 mm] MIN.
SOFT METAL PIPE
FLASHING (SEE
NOTE 1)

PLUMBING VENT
STACK TO EXTEND A
MINIMUM OF 8''
[200 mm] ABOVE TOP
OF INSULATION
SURFACE
AGGREGATE BALLAST
GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)

4'' MIN. FLANGE


[100 mm]

ROOF DECK

COMPATIBLE ROOF
CEMENT OR COMPATIBLE EXTRUDED
SEALANT AT PENETRATION POLYSTYRENE
TO MEMBRANE JUNCTURE INSULATION (2''
SET FLANGE IN [50 mm] MIN.)
COMPATIBLE POLYETHYLENE SLIP
ROOF CEMENT SHEET (4 MIL MIN.)
MULTIPLE-PLY BUILT-UP MULTIPLE MEMBRANE
ROOF MEMBRANE STRIPPING PLIES
FEATHERED AT FIELD
NOTES : OF ROOF - PRIME
FLANGE BEFORE
1. SOFT METAL PIPE FLASHING:
- SHEET LEAD: MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m2 ] OR STRIPPING
2
- SHEET COPPER: MINIMUM 16 OZ. [5 kg/m ].
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SLIP SHEET (E.G., ASPHALT-SATURATED
ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT CONTACT WITH
PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
4. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
5. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
6. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

BUR-P-18
2001 NOT DRAWN TO SCALE

1239
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER

3'-0'' ± (900 mm) MIN.

AGGREGATE
BALLAST
GEOTEXTILE FABRIC
EXTRUDED
POLYSTYRENE
(2'' [50 mm] MIN.)
MULTIPLE MEMBRANE
STRIPPING PLIES
FEATHERED AT
FIELD OF ROOF
ROOF DECK
DECK CLAMP
DRAIN BOWL
CLAMPING RING
MEMBRANE FIELD PLIES, METAL
FLASHING, AND STRIPPING PLIES COMPATIBLE
ALL EXTEND UNDER CLAMPING RING ROOF CEMENT
30'' [750 mm] SQ. MIN. - 2 1/2 LB. TO 4 LB. MULTIPLE-PLY BUILT-
[12.2 TO 19.5 kg/m 2 ] LEAD OR 16 OZ. UP ROOF MEMBRANE
[4.9 kg/m 2 ] COPPER FLASHING SET ON FINISHED
POLYETHYLENE
ROOF IN COMPATIBLE ROOF CEMENT, PRIME TOP
SLIP SHEET
SURFACE BEFORE STRIPPING
(4 MIL MIN.) CUT
OUTSIDE OF THE
CLAMPING RING
NOTES :
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
4. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

BUR-P-20
2001 NOT DRAWN TO SCALE

1240
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD NAILER
CONTINUOUS SHIM
CONTINUOUS CLEAT
FASTENED PER
TABLE 1

SHEET METAL PARAPET CAP


GASKETED FASTENERS
EXTENDED BASE FLASHING -
OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS ARE
USED WITH THE METAL
PARAPET CAP

FASTENERS APPROX.
8'' [200 mm] O.C.
1'' [25 mm] MIN.
BELOW BLOCKING

GEOTEXTILE FABRIC (EXTEND


ABOVE BALLAST)

AGGREGATE BALLAST

PRIME SURFACE AS REQUIRED

POLYETHYLENE SLIP SHEET


(4 MIL MIN.)

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)

MODIFIED BITUMEN
MEMBRANE BASE FLASHING
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY MODIFIED
CANT BITUMEN ROOF MEMBRANE
ROOF DECK

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL. DETAIL MB-4
MAY BE USED AS AN EXAMPLE FOR NON-WALL SUPPORTED DECK CONDITION.
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING)


AND BASE FLASHING
MB-P-1
2001 NOT DRAWN TO SCALE

1241
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE

OPTIONAL: REMOVABLE SHEET


METAL COUNTERFLASHING
SEE NOTE No. 3

FASTENERS APPROX. 8''


[200 mm] O.C.

GEOTEXTILE FABRIC (EXTEND


ABOVE BALLAST)

AGGREGATE BALLAST

OPTIONAL: EXTENDED FIELD


PLIES ABOVE HEAD OF CANT

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)

POLYETHYLENE SLIP SHEET


(4 MIL MIN.)

MODIFIED BITUMEN MEMBRANE


BASE FLASHING (8'' [200 mm]
WOOD CURB
MIN. HEIGHT ABOVE TOP OF
CANT INSULATION SURFACE)

MULTIPLE-PLY MODIFIED
ROOF DECK
BITUMEN ROOF MEMBRANE

NOTES :
1. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURER'S RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/ OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

MB-P-14
2001 NOT DRAWN TO SCALE

1242
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TOP OF FLASHING
CAPPED OR ROLLED
INTO PIPE APPROX.
1'' [25 mm] MIN.

SOFT METAL PIPE


FLASHING (SEE
NOTE No. 1)

PLUMBING VENT
STACK TO EXTEND A
MINIMUM OF 8''
[200 mm] ABOVE TOP
OF INSULATION
SURFACE
AGGREGATE BALLAST

GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)
4'' MIN. FLANGE
[100 mm]

ROOF DECK

COMPATIBLE ROOF
CEMENT OR COMPATIBLE EXTRUDED
SEALANT AT PENETRATION POLYSTYRENE
TO MEMBRANE JUNCTURE INSULATION (2''
[50 mm] MIN.)
SET FLANGE IN COMPATIBLE
ROOF CEMENT POLYETHYLENE
SLIP SHEET
MULTIPLE-PLY MODIFIED (4 MIL MIN.)
BITUMEN ROOF MEMBRANE
MODIFIED BITUMEN
MEMBRANE STRIPPING
NOTES : PLY - PRIME FLANGE
1. SOFT METAL PIPE FLASHING: BEFORE STRIPPING
2
- SHEET LEAD: MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m ] OR
2
- SHEET COPPER: MINIMUM 16 OZ. [5 kg/m ].
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SLIP SHEET (E.G., ASPHALT-
SATURATED ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT
CONTACT WITH PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
4. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
5. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
6. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

MB-P-18
2001 NOT DRAWN TO SCALE

1243
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER

3'-0'' +- (900 mm) MIN.

AGGREGATE
BALLAST
GEOTEXTILE FABRIC

EXTRUDED
POLYSTYRENE
(2'' [50 mm] MIN.)

MODIFIED BITUMEN
MEMBRANE STRIPPING PLY

ROOF DECK

DECK CLAMP

DRAIN BOWL
CLAMPING RING
MEMBRANE FIELD PLIES, METAL COMPATIBLE
FLASHING, AND STRIPPING PLIES ROOF CEMENT
ALL EXTEND UNDER CLAMPING RING MULTIPLE-PLY
30'' [750 mm] SQ. MIN. - 2 1/2 LB. TO 4 LB. MODIFIED BITUMEN
[12.2 TO 19.5 kg/m 2 ] LEAD OR 16 OZ. ROOF MEMBRANE
[4.9 kg/m 2 ] COPPER FLASHING SET ON FINISHED POLYETHYLENE
ROOF IN COMPATIBLE ROOF CEMENT, PRIME TOP SLIP SHEET
SURFACE BEFORE STRIPPING (4 MIL MIN.) CUT
OUTSIDE OF THE
NOTES :
CLAMPING RING
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
4. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

MB-P-20
2001 NOT DRAWN TO SCALE

1244
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EXTEND MEMBRANE TO
BELOW NAILER AND SECURE
FASTENERS APPROX.
12'' [300 mm] O.C.

CONTINUOUS SHIM
WOOD NAILER
CONTINUOUS
CLEAT FASTENED
PER TABLE 1

SHEET METAL
PARAPET CAP
GASKETED FASTENERS

FLASHING MEMBRANE
SLIP SHEET (IF REQUIRED
FOR THE SPECIFIC SYSTEM.)
GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
BELOW BLOCKING

AGGREGATE BALLAST
1'' [25 mm] MIN.

SEAM PLATES AND


FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)
THERMOPLASTIC ROOF
MEMBRANE
SLIP SHEET (IF REQ'D. FOR
THE SPECIFIC SYSTEM)
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. DETAIL TP-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING) AND


BASE FLASHING
TP-P-1
2001 NOT DRAWN TO SCALE

1245
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)

GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
AGGREGATE BALLAST

SLIP SHEET (IF REQUIRED


FOR THE SPECIFIC SYSTEM)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)
THERMOPLASTIC ROOF
MEMBRANE
SLIP SHEET (IF REQ'D. FOR
THE SPECIFIC SYSTEM)
ROOF DECK

NOTES :
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST
3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

TP-P-14
2001 NOT DRAWN TO SCALE

1246
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLUMBING VENT
STACK

SEALANT

OPTIONAL: DRAWBAND
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)

AGGREGATE BALLAST

GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)

SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)

EXTRUDED
POLYSTYRENE
INSULATION
(2'' [50 mm] MIN.)
SLIP SHEET
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
BASE MEMBRANE
ATTACHMENT AS REQUIRED
THERMOPLASTIC
FOR SPECIFIC SYSTEM
ROOF MEMBRANE
SLIP SHEET
ROOF DECK
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)

NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

TP-P-18
2001 NOT DRAWN TO SCALE

1247
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER

3'-0'' +- (900 mm) MIN.

ROOF DECK
AGGREGATE
BALLAST
GEOTEXTILE
FABRIC
EXTRUDED
POLYSTYRENE INSULATION
(2'' [50 mm] MIN.)
THERMOPLASTIC
ROOF MEMBRANE

CLAMPING RING
DECK CLAMP
DRAIN BOWL
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN SLIP SHEET (IF
PIPE DIAMETER REQUIRED FOR THE
SPECIFIC SYSTEM)
INSTALL COMPATIBLE SEALANT
BETWEEN DRAIN BOWL FLANGE SLIP SHEET
AND ROOF MEMBRANE (IF REQUIRED FOR THE
SPECIFIC SYSTEM)
NOTES : CUT OUTSIDE OF THE
CLAMPING RING
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED
HOWEVER, DRAIN RECEIVER/ BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

TP-P-20
2001 NOT DRAWN TO SCALE

1248
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EXTEND MEMBRANE TO
BELOW NAILER AND SECURE
FASTENERS APPROX.
12'' [300 mm] O.C.

CONTINUOUS SHIM
WOOD NAILER
CONTINUOUS
CLEAT FASTENED
PER TABLE 1

SHEET METAL
PARAPET CAP
GASKETED FASTENERS

FLASHING MEMBRANE
GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
BELOW BLOCKING
1'' [25 mm] MIN.

SLIP SHEET (IF REQUIRED


FOR THE SPECIFIC SYSTEM)
AGGREGATE BALLAST
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)
THERMOSET ROOF
MEMBRANE
SLIP SHEET (IF REQ'D. FOR
THE SPECIFIC SYSTEM)
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. DETAIL TS-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

METAL PARAPET CAP (COPING) AND


BASE FLASHING
TS-P-1
2001 NOT DRAWN TO SCALE

1249
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)

GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
AGGREGATE BALLAST

SLIP SHEET (IF REQUIRED


FOR THE SPECIFIC SYSTEM.)
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7 FOR
ALTERNATE PERIMETER
SECUREMENT OPTIONS

EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)

THERMOSET ROOF
MEMBRANE

SLIP SHEET (IF REQ'D. FOR


THE SPECIFIC SYSTEM)
ROOF DECK

NOTES :
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHTC, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST
3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

SKYLIGHT, SCUTTLE, AND SMOKE VENT

TS-P-14
2001 NOT DRAWN TO SCALE

1250
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLUMBING VENT
STACK

SEALANT

FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)

AGGREGATE BALLAST

GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)

SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)

EXTRUDED
POLYSTYRENE
INSULATION
(2'' [50 mm] MIN.)
SLIP SHEET
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
BASE MEMBRANE
ATTACHMENT AS REQUIRED
THERMOSET
FOR SPECIFIC SYSTEM
ROOF MEMBRANE
SLIP SHEET
ROOF DECK
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)

NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

PLUMBING VENT

TS-P-18
2001 NOT DRAWN TO SCALE

1251
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER

3'-0'' +- (900 mm) MIN.

ROOF DECK
AGGREGATE
BALLAST
GEOTEXTILE
FABRIC
EXTRUDED
POLYSTYRENE INSULATION
(2'' [50 mm] MIN.)
THERMOSET
ROOF MEMBRANE

CLAMPING RING
DECK CLAMP
DRAIN BOWL
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN SLIP SHEET (IF
PIPE DIAMETER REQUIRED FOR THE
SPECIFIC SYSTEM)
INSTALL COMPATIBLE SEALANT
BETWEEN DRAIN BOWL FLANGE SLIP SHEET
AND ROOF MEMBRANE (IF REQUIRED FOR THE
SPECIFIC SYSTEM)
NOTES : CUT OUTSIDE OF THE
CLAMPING RING
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED
HOWEVER, DRAIN RECEIVER/ BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.

ROOF DRAIN

TS-P-20
2001 NOT DRAWN TO SCALE

1252
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT 1

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003-H14) COPPER
STEEL

UP TO 3'' FACE .040'' 20 oz. 24 ga. 24 ga. NOT REQUIRED

SAME GAUGE
UP TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL

SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL

ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

1'' UP TO 1 1/2'' FASTEN APPROX. 3'' TO 6'' O.C. STAGGERED, WITH


CORROSION RESISTANT, BARBED, ANNULAR RING
OR SCREW SHANK NAIL. LENGTH TO ACHIEVE
3-1/2'' APPROX. 1 1/4'' PENETRATION INTO NAILER.

''A''
''A'' APPROX. 3''
FLANGE
GASKETED FASTENERS ''A''
(APPROX. 18'' O.C.
DEPENDING UPON WIND
ZONE AND LOCAL
CONDITIONS.)
3/4''
3/4'' 3/4''

FASCIA CAP PROFILE ''A'' TYPE PROFILE ''L'' TYPE PROFILE


FASTEN AT APPROX.
6'' O.C. WITH CORROSION
RESISTANT, BARBED,
NOTES : ANNULAR RING, OR
SCREW SHANK NAIL.
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL LENGTH TO ACHIEVE
CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE, AND APPROX. 1 1/4''
3'' PENETRATION INTO
FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND NAILER.
REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE DESIGNS.
WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE FASTEN NEAR LOWER
CONSIDERED, SUCH AS FASTENING PATTERN. BRAKE FOR INCREASED
3/4'' UPLIFT RESISTANCE.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED
12 FEET ALLOW A 1/4'' GAP BETWEEN PIECES. JOINTS IN CLEAT 2
CLEAT
SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL FASCIA EDGES


FOR BUILT-UP AND MODIFIED BITUMEN
MEMBRANES
BUR/MB - TABLE 1
2001 NOT DRAWN TO SCALE

1253
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT 1

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003-H14) COPPER
STEEL

UP TO 2
1.02 mm 6.10 kg/m .64 mm .61 mm NOT REQUIRED
75 mm FACE
UP TO 2 SAME GAUGE
.81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL
75 mm FACE

75 mm TO 2 SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL

150 mm TO ONE GAUGE


2 HEAVIER THAN
200 mm FACE 1.27 mm 6.10 kg/m .64 mm .61 mm
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
200 mm TO STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
375 mm FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

25 mm UP TO 40 mm FASTEN APPROX. 75 mm TO 150 mm O.C.


STAGGERED, WITH CORROSION RESISTANT,
BARBED, ANNULAR RING OR SCREW SHANK
90 mm NAIL. LENGTH TO ACHIEVE APPROX. 32 mm
PENETRATION INTO NAILER.

''A''
''A'' APPROX. 75 mm
FLANGE
GASKETED FASTENERS ''A''

(APPROX. 450 mm O.C.


DEPENDING UPON WIND
ZONE AND LOCAL
CONDITIONS.)
20 mm
20 mm 20 mm

FASCIA CAP PROFILE ''A'' TYPE PROFILE ''L'' TYPE PROFILE


FASTEN AT APPROX.
150 mm O.C. WITH
CORROSION RESISTANT,
BARBED, ANNULAR RING,
NOTES : OR SCREW SHANK NAIL.
LENGTH TO ACHIEVE
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL APPROX. 32 mm
75 mm PENETRATION INTO
CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE, AND
NAILER.
FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND
REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE DESIGNS. FASTEN NEAR LOWER
WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE BRAKE FOR INCREASED
CONSIDERED, SUCH AS FASTENING PATTERN. 20 mm UPLIFT RESISTANCE.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED
2
4 m. ALLOW A 6 mm GAP BETWEEN PIECES. JOINTS IN CLEAT CLEAT
SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL FASCIA EDGES


FOR BUILT-UP AND MODIFIED BITUMEN
MEMBRANES
BUR/MB - TABLE 1 (METRIC)
2001 NOT DRAWN TO SCALE

1254
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

OPTIONAL: 2'' [50 mm] WIDE


CLIP APPROX. 30'' [750 mm]
O.C. - 2 FASTENERS
PER CLIP

MEMBRANE BASE FLASHING

THROUGH-WALL REGLET AND COUNTERFLASHING


A
LEAD WEDGE AT APPROX.
24'' [600 mm] O.C.

APPROPRIATE SEALANT

FRICTION FIT SHEET METAL


REGLET INSERT IN RAGGLE
JOINT

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

OPTIONAL: 2'' [50 mm] WIDE


CLIP APPROX. 30'' [750 mm]
O.C. - 2 FASTENERS
PER CLIP

MEMBRANE BASE FLASHING

INSERT REGLET AND COUNTERFLASHING


B

OPTIONS FOR TERMINATION OF WALL


COUNTERFLASHING
TABLE 2.1
2001 NOT DRAWN TO SCALE

1255
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
APPROPRIATE FASTENERS
24'' [600 mm] O.C.

3'' [75 mm] LAP AT JOINTS

REMOVABLE SHEET METAL


COUNTERFLASHING

OPTIONAL: 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

MEMBRANE BASE FLASHING

OPTIONAL : SEALANT OR
ELASTOMERIC TAPE
TWO PIECE SURFACE MOUNTED REGLET
AND COUNTERFLASHING
C
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

ONE-PIECE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINT

OPTIONAL: 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

MEMBRANE BASE FLASHING

OPTIONAL : SEALANT OR
ELASTOMERIC TAPE

ONE-PIECE SURFACE MOUNTED COUNTERFLASHING


D

OPTIONS FOR TERMINATION OF WALL


COUNTERFLASHINGS
TABLE 2.2
2001 NOT DRAWN TO SCALE

1256
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BUILDING PAPER
(IF REQUIRED)
WALL CLADDING

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

SHEET METAL REGLET

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

MEMBRANE BASE FLASHING

OPTIONAL: 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

EMBEDDED REGLET AND COUNTERFLASHING


E

OPTIONS FOR TERMINATION OF WALL


COUNTERFLASHING
TABLE 2.3
2001 NOT DRAWN TO SCALE

1257
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTINUOUS CLEATS

''
OPTIONAL METAL
/4 FLANGE EXTENSION
.3
ROX
P
AP

''
3 /4
X.
PRO
TYPICAL AP
CLEAT ENGAGEMENT

APPROPRIATE FASTENERS
FASTENED APPROX. 6''
[150 mm] O.C.

CONTINUOUS CLEATS EACH SIDE


A
OPTIONAL METAL FLANGE
EXTENSION

. CONTINUOUS CLEAT
M IN
m m] APPROPRIATE FASTENERS
[50 FASTENED APPROX. 6''
2''
[150 mm] O.C.

2'' [50 mm] WIDE ISOLATED


3/4

CLIPS WITH APPROPRIATE


'' M

FASTENERS APPROX. 12''


IN.

COPING CAP [300 mm] O.C. DEPENDING


HEMMED EDGE
ON WIND ZONE AND
LOCAL CLIMATES
TYPICAL
CLIP ENGAGEMENT

CONTINUOUS CLEAT AND ISOLATED CLIPS


B
OPTIONAL METAL FLANGE
CONTINUOUS EXTENSION
CLEAT
GASKETED FASTENERS
AT APPROX. 18''
APPROPRIATE [450 mm] O.C. DEPENDING
FASTENERS ON WIND ZONE AND
FASTENED LOCAL CONDITIONS
APPROX. 6''
[150 mm] O.C.

CONTINUOUS CLEAT AND GASKETED FASTENERS


C

GUIDE FOR SHEET METAL PARAPET


CAP (COPING)
TABLE 3
2001 NOT DRAWN TO SCALE

1258
The NRCA Roofing and Waterproofing Manual—Fifth Edition

2'-
0''
MI [600
NI
MU mm]
M

[ 12
CL 300 m ''
E
MI AR m]
NI AN
MU C
M E 12
[
CL 300 m ''
MI EAR m] 12
'' ]
NI AN
MU C 0 mm NCE
M E 12 [30 ARA UM
[ E IM
CL 300 m '' CL MIN
E
MI AR m]
NI AN
MU C
M E

GUIDE FOR CLEARANCES BETWEEN


PIPES/WALLS/CURBES
TABLE 4
2001 NOT DRAWN TO SCALE

1259
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SUMPED
ROOF DRAIN

CURBED
PENETRATION

SADDLE

SL
OP
E

SLO
PE

SUMPED
ROOF DRAIN

CANT

CRICKET

NOTES :
1. SADDLES SHOULD BE LOCATED IN VALLEYS ROOF DRAINS AND CRICKETS ON THE HIGH SIDE OF CURBS.
2. LOCATE ROOF DRAINS AT POINTS OF MAXIMUM DECK DEFLECTION / LOW AREAS FOR DRAINAGE.

GUIDE FOR CRICKETS AND SADDLES

TABLE 5
2001 NOT DRAWN TO SCALE

1260
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RAISED
PERIMETER EDGE

CURBED
PENETRATION

CRICKET

THROUGH EDGE
SCUPPER

SHEET METAL
CONDUCTOR
HEAD

SL
OP
E

CANT

CRICKET

NOTES :
1. SADDLE SHOULD BE LOCATED BETWEEN THROUGH-EDGE OR WALL SCUPPERS AND CRICKETS ON THE HIGH SIDE OF CURBS.
2. RAISED PERIMETER EDGES WHERE TAPERED CRICKETS ARE USED NECESSITATE THE SPECIFICATION OF RELATIVELY WIDE
(TALL) DIMENSIONAL LUMBER OR THE ERECTION OF FRAMED WALLS.

GUIDE FOR EDGE SCUPPERS WITH


TAPERED SADDLES
TABLE 6
2001 NOT DRAWN TO SCALE

1261
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT SEALANT
(IF REQUIRED) (IF REQUIRED)

FLASHING FLASHING
MEMBRANE MEMBRANE

FASTENING STRIP FASTENING STRIP


(BAR) AND (BAR) AND
FASTENERS FASTENERS

ROOF MEMBRANE ROOF MEMBRANE


FIELD SHEET FIELD SHEET

OPTION 1-A : OPTION 1-B :


FASTENING STRIP FASTENING STRIP
SECURED TO WALL SECURED TO DECK

REINFORCED REINFORCED
MEMBRANE MEMBRANE
ATTACHMENT ATTACHMENT
STRIP STRIP
SEAM PLATE AND SEAM PLATE AND
FASTENER FASTENER

ROOF MEMBRANE
FIELD SHEET

ROOF MEMBRANE
FIELD SHEET

OPTION 2-A : OPTION 2-B :


ATTACHMENT STRIP ATTACHMENT STRIP
SECURED TO WALL SECURED TO DECK

OPTIONS FOR PERIMETER BASE


SECUREMENT (ROOF-TO-WALL AND
ROOF-TO-CURB INTERSECTIONS)
SINGLE-PLY TABLE 7.1
2001 NOT DRAWN TO SCALE

1262
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT
(IF REQUIRED)
SEALANT
(IF REQUIRED)
FLASHING
FLASHING MEMBRANE
MEMBRANE

SEAM PLATE SEAM PLATE


AND FASTENER AND FASTENER

ROOF MEMBRANE ROOF MEMBRANE


FIELD SHEET FIELD SHEET

OPTION 3-A : OPTION 3-B :


SEAM PLATES AND SEAM PLATES AND
FASTENERS TO WALL FASTENERS TO DECK
(REINFORCED MEMBRANE) (REINFORCED MEMBRANE)

SEALANT
(IF REQUIRED)
MEMBRANE COATED
METAL FLASHING
FLASHING
MEMBRANE SEALANT
(IF REQUIRED)
BEVELED WOOD
FASTENING STRIP FLASHING
(3/4'' x 2 3/4'' MEMBRANE
[19 mm x 70 mm]
MINIMUM DECAY
RESISTANT TREATED)

FASTENERS AT 12''
FASTENERS AT
[300 mm] O.C. (MIN.)
APPROX. 4''
[100 mm] O.C.
ROOF MEMBRANE
STAGGERED
FIELD SHEET
ROOF MEMBRANE
FIELD SHEET
OPTION 4 : OPTION 5 :
WOOD STRIP MEMBRANE COATED
SECURED TO WALL METAL FLASHING
(THERMOSET ONLY) (THERMOPLASTIC ONLY)

OPTIONS FOR PERIMETER BASE


SECUREMENT (ROOF-TO-WALL AND
ROOF-TO-CURB INTERSECTIONS)
SINGLE-PLY TABLE 7.2
2001 NOT DRAWN TO SCALE

1263
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1
RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL

UP TO 3'' FACE .040'' 20 oz. 24 ga. 24 ga. NOT REQUIRED

SAME GAUGE
UP TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL

SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL

ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

1'' UP TO 2'' FASTEN APPROX. 3'' TO 6'' O.C. STAGGERED, WITH


CORROSION RESISTANT, BARBED, ANNULAR RING
OR SCREW SHANK NAIL. LENGTH TO ACHIEVE
3-1/2'' APPROX. 1 1/4'' PENETRATION INTO NAILER.

''A''
''A'' MIN. 3''
FLANGE
GASKETED FASTENERS ''A''
(APPROX. 18'' O.C.
DEPENDING UPON WIND
ZONE AND LOCAL
CONDITIONS.)
3/4''
3/4'' 3/4''

FASCIA CAP PROFILE ''A'' TYPE PROFILE ''L'' TYPE PROFILE


FASTEN AT APPROX.
6'' O.C. WITH CORROSION
RESISTANT, BARBED,
ANNULAR RING, OR
NOTES : SCREW SHANK NAIL.
LENGTH TO ACHIEVE
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL APPROX. 1 1/4''
3'' PENETRATION INTO
CONDITIONS IN REGARDS TO THE SELECTION OF METAL GAUGE,
NAILER.
PROFILE AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE
AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE FASTEN NEAR LOWER
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BRAKE FOR INCREASED
BE CONSIDERED, SUCH AS FASTENING PATTERN. 3/4'' UPLIFT RESISTANCE.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED
2
12 FEET. ALLOW A 1/4'' GAP BETWEEN PIECES. JOINTS IN CLEAT CLEAT
SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL FASCIA EDGES


FOR THERMOSET AND THERMOPLASTIC
MEMBRANES
SINGLE-PLY - TABLE 1
2001 NOT DRAWN TO SCALE

1264
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1
RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL

UP TO 2
1.02 mm 6.10 kg/m .64 mm .61 mm NOT REQUIRED
75 mm FACE
UP TO 2 SAME GAUGE
.81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL
75 mm FACE

75 mm TO 2 SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL

150 mm TO ONE GAUGE


2
1.27 mm 6.10 kg/m .64 mm .61 mm HEAVIER THAN
200 mm FACE FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
200 mm TO STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
375 mm FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

25 mm UP TO 50 mm FASTEN APPROX. 75 mm TO 150 mm O.C.


STAGGERED, WITH CORROSION RESISTANT,
BARBED, ANNULAR RING OR SCREW SHANK
90 mm NAIL. LENGTH TO ACHIEVE APPROX. 32 mm
PENETRATION INTO NAILER.

''A''
''A'' APPROX. 75 mm
FLANGE
GASKETED FASTENERS ''A''
(APPROX. 450 mm O.C.
DEPENDING UPON WIND
ZONE AND LOCAL
CONDITIONS.)
20 mm
20 mm 20 mm

FASCIA CAP PROFILE ''A'' TYPE PROFILE ''L'' TYPE PROFILE


FASTEN AT APPROX.
150 mm O.C. WITH
CORROSION RESISTANT,
BARBED, ANNULAR RING,
OR SCREW SHANK NAIL.
NOTES : LENGTH TO ACHIEVE
APPROX. 32 mm
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL 75 mm PENETRATION INTO
CONDITIONS IN REGARD TO THE SELECTION OF METAL GAUGE, NAILER.
PROFILE, AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE
AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE FASTEN NEAR LOWER
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BRAKE FOR INCREASED
BE CONSIDERED, SUCH AS FASTENING PATTERN. 20 mm UPLIFT RESISTANCE.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED
4 m. ALLOW A 6 mm GAP BETWEEN PIECES. JOINTS IN CLEAT 2
CLEAT
SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL FASCIA EDGES


FOR THERMOSET AND THERMOPLASTIC
MEMBRANES
SINGLE-PLY - TABLE 1 (METRIC)
2001 NOT DRAWN TO SCALE

1265
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
APRON FLASHING
WITH HEMMED EDGE

SEALANT

SHEET METAL
COUNTERFLASHING
(SEE NOTE No.1)

RAGGLE

UNDERLAYMENT
TURNED UP WALL

SHEET METAL
STEP FLASHING

SOLDER OR
SEAL CORNERS

ASPHALT
SHINGLES

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT
AND JOINERY OPTIONS FOR SHEET METAL.

APRON FLASHING

ASPH-1
2001 NOT DRAWN TO SCALE

1266
The NRCA Roofing and Waterproofing Manual—Fifth Edition

UNDERLAYMENT
TURNED UP WALL
SIDING TO
COUNTERFLASH
STEPFLASHING
A MIN. 2'' [50 mm]
(SEE NOTE 1)
APPROX. 4'' [100 mm]

SHEET METAL
STEPFLASHING
FOR EACH COURSE
OF SHINGLES

BUILDING PAPER

ASPHALT SHINGLES

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.

SIDEWALL FLASHING

ASPH-2
2001 NOT DRAWN TO SCALE

1267
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
COUNTERFLASHING
ASPHALT SHINGLES
STRIPPING PLY

SHEET METAL
BACKER FLASHING

UNDERLAYMENT
SECTION :

SEALANT

SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)

SHEET METAL
BACKER FLASHING

ASPHALT
SHINGLES
6'' [150 mm] MIN.

SOLDER OR
SEAL CORNERS

UNDERLAYMENT

STRIPPING PLY
ADHERED TO
UNDERLAYMENT
(SEE NOTE 3)

18'' [450 mm] MIN.

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING PLY IS NOT USED, UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.

BACKER FLASHING

ASPH-3
2001 NOT DRAWN TO SCALE

1268
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OPTIONAL: SEALANT HIGH NAIL FIRST SHINGLE


UNDER TABS AT FIRST OVER SHEET METAL
COURSE BEHIND BACKER FLASHING
PENETRATION
SHINGLES OVER
SHEET METAL
BACKER FLASHING

SHINGLE OVER
STEP FLASHING
SHEET METAL AND UNDER SHEET
BACKER FLASHING METAL BACKER
FLASHING

SHEET METAL
STEP FLASHING
UNDER SHEET
METAL BACKER
FLASHING

NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.

BACKER FLASHING

ASPH-3A
2001 NOT DRAWN TO SCALE

1269
The NRCA Roofing and Waterproofing Manual—Fifth Edition

L-TYPE
EDGE METAL ICE DAM PROTECTION
FLASHING MEMBRANE
EDGE METAL
FLASHING

OPTION :

ALTERNATE :

ASPHALT SHINGLES UNDERLAYMENT OR


ICE DAM PROTECTION
MEMBRANE

ASPHALT SHINGLE
STARTER COURSE

''T'' TYPE METAL


EDGE FLASHING

''T'' TYPE METAL


NOTES : EDGE FLASHING

1. NOT ALL SHINGLES ARE SHOWN FOR CLARITY.


2. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.

EAVE AND RAKE FLASHING

ASPH-4
2001 NOT DRAWN TO SCALE

1270
The NRCA Roofing and Waterproofing Manual—Fifth Edition

UNDERLAYMENT

OPTIONAL STRIPPING
PLY

GUTTER

ALTERNATE :
1 PIECE GUTTER

ASPHALT
SHINGLES
''T'' TYPE EDGE
ASPHALT SHINGLE
METAL FLASHING
STARTER COURSE

GUTTER UNDERLAYMENT

''L'' TYPE EDGE


METAL FLASHING

NOTES :
1. UNDERLAYMENT CAN BE INSTALLED ON TOP OF OR UNDER THE EAVE EDGE METAL FLASHING DEPENDING
ON CLIMATIC CONDITIONS.
2. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DAPENDING ON CLIMATIC CONDITIONS.
3. THIS DETAIL SHOWS ONE TYPE OF GUTTER SUPPORT. GUTTER SECUREMENT AND SUPPORT OPTIONS VARY ACCORDING
TO REGIONAL PRACTICES AND MANUFACTURERS SPECIFICATIONS.

EAVE AND RAKE FLASHING WITH GUTTER

ASPH-5
2001 NOT DRAWN TO SCALE

1271
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEMMED EDGE CONTINUOUS


BOTH SIDES STRIPPING
PLY ON BOTH
METAL CLIP SIDES OF
APPROX. 2'' VALLEY METAL
[50 mm] WIDE

BEND CLIP BACK


OVER TO COVER
FASTENERS,
2 FASTENERS
PER CLIP OPTION:
ALTERNATE :

SLOPE
LAP VALLEY
METAL 8''
[200 mm] MIN. AND
SET IN SEALANT

VALLEY METAL
18'' [450 mm]
WIDE MIN.
EXTEND SHINGLES
4'' [100 mm] MIN. OVER VALLEY
VALLEY METAL UNDERLAYMENT
(SEE NOTE 2)

TRIM CORNER
ASPHALT SHINGLES
OF SHINGLES

NOTES:
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. SHINGLES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.
4. FOR CLIPPED VALLEY DETAIL (''ALTERNATE''), HEAVIER WEIGHT SHINGLES MUST BE USED.

OPEN VALLEY

ASPH-6
2001 NOT DRAWN TO SCALE

1272
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EXTEND SHINGLE
12'' [600 mm] MIN. VALLEY UNDERLAYMENT
BEYOND CENTER
OF VALLEY KEEP NAILS 6'' [150 mm]
MIN. FROM CENTER OF
TRIM CORNER VALLEY
OF SHINGLES
ASPHALT SHINGLES
OPTIONAL :
COMPATIBLE
SEALANT

NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. THE CUT SIDE OF THE VALLEY SHOULD BE ON THE SIDE WITH THE GREATEST AREA.

CLOSED CUT VALLEY

ASPH-7
2001 NOT DRAWN TO SCALE

1273
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PRE-FABRICATED
FLASHING

ASPHALT
SHINGLES

OPTION :

METAL
FLASHING SLEEVE

ASPHALT
SHINGLES

MIN. 4'' [100 mm]


UPSLOPE

MIN. 4'' [100 mm]


OPTIONAL
DOWNSLOPE
FASTENERS

OPTIONAL :
SEALANT UNDER
SHINGLES

PIPE PENETRATION

ASPH-8
2001 NOT DRAWN TO SCALE

1274
The NRCA Roofing and Waterproofing Manual—Fifth Edition

IN LIEU OF LEAD
FLASHING, CHANNEL
FLASHING TO BE
ELEVATED TO
MATCH HEIGHT OF
APRON FLASHING
SHEET METAL ALTERNATE : SOLDER ALL JOINTS
APRON FLASHING

SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)

SEALANT RAGGLE

SHEET METAL
CHANNEL FLASHING

UNDERLAYMENT
TURNED UP WALL

LEAD WITH
UPTURNED OUTER
EDGE
PANS FILLED WITH
MORTAR OR CLOSURE TILE
UNDER SHEET METAL
APRON FLASHING

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT AND JOINERY
OPTIONS FOR SHEET METAL.

APRON FLASHING

TILE-1
2001 NOT DRAWN TO SCALE

1275
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)

SHEET METAL
CHANNEL FLASHING

HALF TILE

TILE

RAGGLE

ROOF DECK

UNDERLAYMENT
TURNED UP WALL

BATTENS

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. METAL CHANNEL FLASHING SHOULD BE CONTINUOUS ALONG LENGTH OF WALL.
3. WIDTH OF METAL CHANNEL FLASHING VARIES DEPENDING UPON TILE LAYOUT.

SIDEWALL FLASHING

TILE-2
2001 NOT DRAWN TO SCALE

1276
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
COUNTERFLASHING
TILE
STRIPPING PLY

EAVE CLOSURE
SHEET METAL
BACKER FLASHING
UNDERLAYMENT
SECTION :

SEALANT
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)

METAL BACKER
FLASHING
TILE

6'' [150 mm] MIN.


SOLDER OR
SEAL CORNER

18'' [450 mm] MIN.

STRIPPING PLY
ADHERED TO
UNDERLAYMENT
(SEE NOTE 2)
BATTENS

SHEET METAL EAVE CLOSURE


CHANNEL
FLASHING SHEET METAL
BACKER FLASHING
UNDERLAYMENT

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING IS NOT USED, UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.

BACKER FLASHING

TILE-3
2001 NOT DRAWN TO SCALE

1277
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EAVE
CLOSURE

BATTENS

SOLDER OR
SEAL CORNER

SHEET METAL
BACKER FLASHING

TILE

HALF TILE

SHEET METAL
CHANNEL FLASHING

NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON WIDTH, SLOPE
AND CLIMATIC CONDITIONS.

BACKER FLASHING

TILE-3A
2001 NOT DRAWN TO SCALE

1278
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ICE DAM PROTECTION


MEMBRANE
EDGE METAL
FLASHING

OPTION :

1'' x 2'' NOMINAL


[25 x 50 mm]
4' LONG [1.2 m]
WOOD BATTENS
WITH 1/2'' [13 mm]
MIN. GAPS

WEEP HOLES

EAVE CLOSURE

UNDERLAYMENT

''L'' TYPE EDGE METAL


FLASHING

NOTES :
1. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
2. SHIMS SHOULD BE USED WHEN BATTEN LENGTHS ARE GREATER THAN 4'-0'' [1.2 m].
3. SHIMS ALSO MAY BE USED UNDER BATTENS TO ENHANCE DRAINAGE.

EAVE FLASHING

TILE-4
2001 NOT DRAWN TO SCALE

1279
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HALF TILE AT
RAKE

UNDERLAYMENT

SECTION : BATTENS NOT SHOWN FOR CLARITY

RAKE TILE

RAKE TILE
FASTENERS

BATTENS

FASCIA BOARD OR
ROOF DECK BARGE RAFTER

UNDERLAYMENT

NOTES :
1. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.

RAKE EDGE FLASHING

TILE-5
2001 NOT DRAWN TO SCALE

1280
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEMMED EDGE
BOTH SIDES
METAL CLIP
APPROX. 2''
[50 mm] WIDE
BEND CLIP BACK
OVER TO COVER
FASTENERS,
2 FASTENERS
PER CLIP
ALTERNATE :

CONTINUOUS
STRIPPING PLY

EXTEND TILE 4''


[100 mm] MIN. OVER
VALLEY METAL VALLEY METAL
18'' [450 mm]

SLOPE
WIDE MIN.

VALLEY UNDERLAYMENT
LAP VALLEY METAL
8'' [200 mm] MIN. AND
SET IN SEALANT
MORTAR FILL
OPENING ALONG
VALLEY CUTS

TILE

EAVE
CLOSURE
NOTES :
BATTENS
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. TILES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.

OPEN VALLEY

TILE-6
2001 NOT DRAWN TO SCALE

1281
The NRCA Roofing and Waterproofing Manual—Fifth Edition

UNDERLAYMENT TO TILE TO OVERLAP


OVERLAP UPSLOPE UPPER FLANGE
FLANGE OF SECONDARY OF PRIMARY FLASHING
FLASHING

PRIMARY FLASHING
AT TILE - COPPER
OR LEAD

SECONDARY METAL
FLASHING AT
DECK LEVEL

NOTES :
1. ROOF DECK, UNDERLAYMENT, AND BATTENS NOT SHOWN FOR CLARITY.

TWO-PIECE PIPE FLASHING

TILE-7
2001 NOT DRAWN TO SCALE

1282
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EAVE CLOSURE
WHERE TILE IS
SECTION : OMITTED

METAL FLASHING
EXTENDS UPSLOPE
SO A 3'' [75 mm]
LAP IS ACHIEVED

TURNED UP
EDGES OF
METAL FLASHING

UNDERLAYMENT LAPS
OVER UP SLOPE
FLANGE OF FLASHING

METAL FLASHING
EXTENDS DOWNSLOPE
ON TOP OF TILES
APPROX. 6'' [150 mm]

NOTES :
1. ROOF DECK, UNDERLAYMENT, AND BATTENS NOT SHOWN FOR CLARITY.

PIPE PENETRATION

TILE-7A
2001 NOT DRAWN TO SCALE

1283
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL APRON


FLASHING WITH
HEMMED EDGE

SEALANT

SHEET METAL
COUNTERFLASHING SHEET METAL
(SEE NOTE 1) STEP FLASHING

SOLDER OR
SEAL CORNERS
ALTERNATE :

RAGGLE

UNDERLAYMENT
TURNED UP WALL

SOLDERED ONE
PIECE APRON
FLASHING
CORNERS

SLATE

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.

APRON FLASHING

SLATE-1
2001 NOT DRAWN TO SCALE

1284
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SIDING TO
COUNTERFLASH
STEPFLASHING
A MIN. 2'' [50 mm]
(SEE NOTE 1)
UNDERLAYMENT
TURNED UP WALL
4'' [100 mm]
APPROX.

SLATE
SHEET METAL
STEPFLASHING
BUILDING PAPER

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.

SIDEWALL FLASHING

SLATE-2
2001 NOT DRAWN TO SCALE

1285
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
SOLDER OR COUNTERFLASHING
SEAL CORNERS SLATE
STRIPPING PLY

SHEET METAL
ALTERNATE : BACKER FLASHING
UNDERLAYMENT
SECTION :

SEALANT
SHEET METAL
COUNTERFLASHING

SHEET METAL
BACKER FLASHING
SLATE
6'' [150 mm] MIN.

SOLDERED ONE
PIECE CORNERS

UNDERLAYMENT
SLATE STARTER
COURSE

STRIPPING PLY
18'' [450 mm] MIN. ADHERED TO
UNDERLAYMENT
(SEE NOTE 3)

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING IS NOT USED UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.

BACKER FLASHING

SLATE-3
2001 NOT DRAWN TO SCALE

1286
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STARTER COURSE
OVER SHEET METAL
BACKER FLASHING

SLATE OVER
SHEET METAL
BACKER FLASHING

SLATE UNDER
SHEET METAL
BACKER FLASHING

SOLDERED ONE
PIECE CORNERS

SHEET METAL SLATE OVER


BACKER FLASHING SHEET METAL
STEP FLASHING

NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON WIDTH, SLOPE
AND CLIMATIC CONDITIONS.

BACKER FLASHING

SLATE-3A
2001 NOT DRAWN TO SCALE

1287
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EAVE CANT ABOVE ICE DAM PROTECTION


EDGE METAL FLASHING MEMBRANE TURNED
DOWN FASCIA

STRIPPING PLY

EDGE METAL
FLASHING

ALTERNATE : ALTERNATE :

SLATE

UNDERLAYMENT

SLATE STARTER
COURSE

''T'' TYPE EDGE


METAL FLASHING
''T'' TYPE
EDGE METAL
EAVE CANT

NOTES :

1. UNDERLAYMENT TYPE MAY VARY DEPENDING ON CLIMATIC CONDITIONS.

EAVE AND RAKE FLASHING

SLATE-4
2001 NOT DRAWN TO SCALE

1288
The NRCA Roofing and Waterproofing Manual—Fifth Edition

UNDERLAYMENT

OPTIONAL STRIPPING
PLY

GUTTER

SLATE ALTERNATE :

UNDERLAYMENT

''T'' TYPE EDGE


''L'' TYPE EDGE METAL FLASHING
METAL FLASHING

GUTTER
EAVE CANT WITH
NOTES : OPTIONAL BEVEL
1. UNDERLAYMENT CAN BE INSTALLED ON TOP OF OR UNDER EAVE EDGE METAL FLASHING, DEPENDING ON
CLIMATIC CONDITIONS.
2. UNDERLAYMENT TYPE MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. THIS DETAIL SHOWS ONE TYPE OF GUTTER SUPPORT. GUTTER SECUREMENT AND SUPPORT OPTIONS VARY ACCORDING
TO REGIONAL PRACTICES AND MANUFACTURERS SPECIFICATIONS.

EAVE AND RAKE FLASHING WITH GUTTER

SLATE-5
2001 NOT DRAWN TO SCALE

1289
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTINUOUS FASTENER
STRIPPING
PLY ON BOTH
SIDES OF
VALLEY METAL

OPTION : ALTERNATE :

SLOPE
EXTEND SLATES VALLEY METAL
4'' [100 mm] MIN. OVER 18'' [450 mm] WIDE MIN.
VALLEY METAL

LAP VALLEY METAL


SLATE 8'' [200 mm] MIN. AND
SET IN SEALANT

VALLEY UNDERLAYMENT

METAL CLIP (APPROX. 2''


[50 mm] WIDE) BEND
CLIP BACK OVER TO
COVER FASTENERS. MIN. 2
FASTENERS PER CLIP

NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIDC CONDITIONS.
3. SLATE SHOULD NOT BE FASTENED THROUGH THE VALLEY METAL. USE WIDER SLATE OR WIRE-TIE SYSTEMS.

OPEN VALLEY

SLATE-6
2001 NOT DRAWN TO SCALE

1290
The NRCA Roofing and Waterproofing Manual—Fifth Edition

VALLEY UNDERLAYMENT

VALLEY METAL

SLOPE
18'' [450 mm] WIDE MIN.
WIRE-TIED SLATE

LAP VALLEY METAL


8'' [200 mm] MIN. AND
SET IN SEALANT
SLATE

KEEP NAILS 8'' [200 mm]


FROM CENTER OF VALLEY

NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. MIN. SLOPE FOR THIS DETAIL IS 8 :12 (34 DEGREES).

CLOSED VALLEY

SLATE-7
2001 NOT DRAWN TO SCALE

1291
The NRCA Roofing and Waterproofing Manual—Fifth Edition

METAL
FLASHING SLEEVE

SLATE

UNDERLAYMENT TO
OVERLAP UPPER FLANGE

OPTIONAL SEALANT
UNDER SLATE

MIN. DOWNSLOPE
FLANGE DIMENSION
TO BE EQUAL TO
FIELD SLATE
EXPOSURE

4'' [100 mm]


MIN. TYP.

PIPE PENETRATION

SLATE-8
2001 NOT DRAWN TO SCALE

1292
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RAGGLE SHEET METAL


STEP FLASHING
SEALANT

SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)

SHEET METAL APRON


FLASHING WITH HEMMED EDGE WOOD SHAKES

SOLDER OR
SEAL CORNER
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT AND JOINERY
OPTIONS FOR SHEET METAL.

APRON FLASHING

SHK-1
2001 NOT DRAWN TO SCALE

1293
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INTERLAYMENT ON
TOP OF STEP FLASHING

SIDING TO
COUNTERFLASH
STEP FLASHING
A MIN 2'' [50 mm]
(SEE NOTE 1)

APPROX.
4'' MIN.

SHEET METAL
STEP FLASHING

BUILDING PAPER

WOOD SHAKES

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.

SIDEWALL FLASHING

SHK-2
2001 NOT DRAWN TO SCALE

1294
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
COUNTERFLASHING
WOOD SHAKES
STRIPPING PLY

SHEET METAL
BACKER FLASHING

OPTIONAL :
UNDERLAYMENT

SECTION: INTERPLY NOT SHOWN FOR CLARITY

SEALANT

SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
SOLDER OR
SEAL CORNERS SHEET METAL
BACKER FLASHING

WOOD SHAKES

INTERLAYMENT

18'' [450 mm] MIN. STARTER COURSE

NOTES : STRIPPING PLY


1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED. (SEE NOTE 3)
2. UNDERLAYMENT NOT SHOWN FOR CLARITY.
3. IF STRIPPING PLY IS NOT USED, INTERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
4. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.

BACKER FLASHING

SHK-3
2001 NOT DRAWN TO SCALE

1295
The NRCA Roofing and Waterproofing Manual—Fifth Edition

INTERLAYMENT

STARTER SHAKE
OVER SHEET METAL
BACKER FLASHING

SHAKE UNDER SHEET


METAL BACKER
FLASHING

SOLDER OR
SEAL CORNERS

SHAKE OVER
STEP FLASHING

SHEET METAL
SHEET METAL STEP FLASHING
BACKER FLASHING

NOTES :
1. UNDERLAYMENT AND STRIPPING PLY NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.

BACKER FLASHING

SHK-3A
2001 NOT DRAWN TO SCALE

1296
The NRCA Roofing and Waterproofing Manual—Fifth Edition

L-TYPE ICE DAM PROTECTION


EDGE METAL MEMBRANE
FLASHING
EDGE METAL
FLASHING

OPTION :

ALTERNATE :
WOOD SHAKES

UNDERLAYMENT

INTERLAYMENT

STARTER
COURSE(S)

''T'' TYPE METAL


EDGE FLASHING

NOTES : ''T'' TYPE METAL


EDGE FLASHING
1. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.

EAVE AND RAKE FLASHING

SHK-4
2001 NOT DRAWN TO SCALE

1297
The NRCA Roofing and Waterproofing Manual—Fifth Edition

UNDERLAYMENT
OPTIONAL STRIPPING
PLY

GUTTER

WOOD SHAKES

ALTERNATE :
1 PIECE GUTTER

UNDERLAYMENT

INTERLAYMENT

GUTTER ''T'' TYPE EDGE


METAL FLASHING

''L'' TYPE EDGE


METAL FLASHING
STARTER COURSE
NOTES :
1. UNDERLAYMENT CAN BE INSTALLED ON TOP OF OR UNDER EAVE EDGE METAL FLASHING, DEPENDING ON
CLIMATIC CONDITIONS.
2. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. THIS DETAIL SHOWS ONE TYPE OF GUTTER SUPPORT. GUTTER SECUREMENT AND SUPPORT OPTIONS VARY ACCORDING
TO REGIONAL PRACTICES AND MANUFACTURERS SPECIFICATIONS.

EAVE AND RAKE FLASHING WITH GUTTER

SHK-5
2001 NOT DRAWN TO SCALE

1298
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEMMED EDGE CONTINUOUS


BOTH SIDES STRIPPING
PLY ON BOTH
METAL CLIP SIDES OF
APPROX. 2'' VALLEY METAL
[50 mm] WIDE

BEND CLIP BACK


OVER TO COVER
FASTENERS,
2 FASTENERS
PER CLIP OPTION :

ALTERNATE : VALLEY METAL


18'' [450 mm] WIDE MIN.

LAP VALLEY METAL

SLOPE
EXTEND WOOD SHAKES 8'' [200 mm] MIN. AND
4'' [100 mm] MIN. OVER SET IN SEALANT
VALLEY METAL
VALLEY UNDERLAYMENT
(SEE NOTE 2)

NOTES :
WOOD SHAKES
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. SHAKES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.

OPEN VALLEY

SHK-6
2001 NOT DRAWN TO SCALE

1299
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS
KEEP NAILS 8'' [200 mm] STRIPPING
FROM CENTER OF VALLEY PLY ON BOTH
SIDES OF
VALLEY METAL
VALLEY
UNDERLAYMENT
(SEE NOTE 2)
OPTION :

SLOPE
VALLEY METAL
18'' [450 mm] WIDE MIN.

LAP VALLEY METAL


8'' [200 mm] MIN. AND SET INTERLAYMENT
IN SEALANT

WOOD SHAKES
KEEP SHAKES
APPROX. 1'' [25 mm]
FROM VALLEY RIB

NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. MIN. SLOPE FOR THIS DETAIL IS 8 :12 (34 DEGREES).

CLOSED VALLEY

SHK-7
2001 NOT DRAWN TO SCALE

1300
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PRE-FABRICATED
FLASHING

INTERLAYMENT TO
OVERLAP UPPER
FLANGE

ALTERNATE : INTERLAYMENT

INTERLAYMENT

METAL
SLEEVE FLASHING

OPTIONAL
FASTENERS

MIN. DOWNSLOPE
FLANGE DIMENSION
TO BE EQUAL TO
FIELD SHAKE
EXPOSURE

PIPE PENETRATION

SHK-8
2001 NOT DRAWN TO SCALE

1301
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
APRON FLASHING
WITH HEMMED EDGE

SEALANT

SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)

RAGGLE

UNDERLAYMENT
TURNED UP WALL

SHEET METAL
STEP FLASHING

SOLDER OR
SEAL CORNER

WOOD SHINGLES

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT AND JOINERY
OPTIONS FOR SHEET METAL.

APRON FLASHING

SHNG-1
2001 NOT DRAWN TO SCALE

1302
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SIDING TO
COUNTERFLASH
STEPFLASHING
A MIN. 2'' [50 mm]
(SEE NOTE 1)
UNDERLAYMENT
TURNED UP WALL

APPROX. 1'' [25 mm]


APPROX. 4'' [100 mm]

SHEET METAL
STEPFLASHING WOOD SHINGLES

BUILDING PAPER

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.

SIDEWALL FLASHING

SHNG-2
2001 NOT DRAWN TO SCALE

1303
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
COUNTERFLASHING
WOOD SHINGLES
STRIPPING PLY

SHEET METAL
BACKER FLASHING

UNDERLAYMENT

SECTION :

SEALANT
SHEET METAL
COUNTERFLASHING
6'' [150 mm] MIN. SHEET METAL
BACKER FLASHING
SOLDER OR WOOD
SEAL CORNERS SHINGLES

UNDERLAYMENT

STARTER COURSE

STRIPPING PLY
ADHERED TO
UNDERLAYMENT
(SEE NOTE 3)

18'' [450 mm] MIN.

NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING IS NOT USED, UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.

BACKER FLASHING

SHNG-3
2001 NOT DRAWN TO SCALE

1304
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD SHINGLE STARTER


COURSE OVER SHEET
METAL BACKER FLASHING

WOOD SHINGLE OVER


SHEET METAL
BACKER FLASHING

WOOD SHINGLE UNDER


SHEET METAL
BACKER FLASHING AND
OVER STEP FLASHING

SOLDER OR
SEAL CORNER

SHEET METAL
SHEET STEP FLASHING
METAL
BACKER
FLASHING

NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE, AND CLIMATIC CONDITIONS.

PLAN VIEW AT CORNER

SHNG-3A
2001 NOT DRAWN TO SCALE

1305
The NRCA Roofing and Waterproofing Manual—Fifth Edition

L-TYPE
EDGE METAL ICE DAM PROTECTION
FLASHING MEMBRANE
EDGE METAL
FLASHING

OPTION :

ALTERNATE :

WOOD SHINGLES
UNDERLAYMENT

STARTER COURSE

''T'' TYPE METAL


EDGE FLASHING ''T'' TYPE METAL
EDGE FLASHING

NOTES :
1. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.

EAVE AND RAKE FLASHING

SHNG-4
2001 NOT DRAWN TO SCALE

1306
The NRCA Roofing and Waterproofing Manual—Fifth Edition

UNDERLAYMENT

OPTIONAL STRIPPING
PLY

GUTTER

ALTERNATE :
1 PIECE GUTTER

WOOD
SHINGLES
WOOD SHINGLE
STARTER COURSE ''T'' TYPE EDGE
METAL FLASHING
GUTTER
UNDERLAYMENT
''L'' TYPE EDGE
METAL FLASHING

NOTES :
1. UNDERLAYMENT CAN BE INSTALLED ON TOP OF OR UNDER THE EAVE EDGE METAL FLASHING DEPENDING
ON CLIMATIC CONDITIONS.
2. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING IN CLIMATIC CONDITIONS.
3. THIS DETAIL SHOWS ONE TYPE OF GUTTER SUPPORT. GUTTER SECUREMENT AND SUPPORT OPTIONS VARY ACCORDING
TO REGIONAL PRACTICES AND MANUFACTURERS SPECIFICATIONS.

EAVE AND RAKE FLASHING WITH GUTTER

SHNG-5
2001 NOT DRAWN TO SCALE

1307
The NRCA Roofing and Waterproofing Manual—Fifth Edition

HEMMED EDGE CONTINUOUS


BOTH SIDES STRIPPING
PLY ON BOTH
METAL CLIP SIDES OF
APPROX. 2'' VALLEY METAL
[50 mm] WIDE
BEND CLIP BACK
OVER TO COVER
FASTENERS,
2 FASTENERS
PER CLIP OPTION :

ALTERNATE :

SLOPE
VALLEY METAL
18'' [450 mm] WIDE MIN.
EXTEND WOOD SHINGLES
LAP VALLEY METAL
4'' [100 mm] MIN. OVER
8'' [200 mm] MIN. AND
VALLEY METAL
SET IN SEALANT
WOOD SHINGLES
VALLEY UNDERLAYMENT
(SEE NOTE 2)

NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. SHINGLES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.

OPEN VALLEY

SHNG-6
2001 NOT DRAWN TO SCALE

1308
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTINUOUS
STRIPPING
PLY ON BOTH
SIDES OF VALLEY METAL
VALLEY METAL
18'' [450 mm] WIDE MIN.

OPTION : LAP VALLEY METAL


8'' [200 mm] MIN. AND

SLOPE
SET IN SEALANT

KEEP SHINGLES
VALLEY APPROX. 1'' [25 mm]
UNDERLAYMENT FROM VALLEY RIB
(SEE NOTE 2)

KEEP NAILS 8'' [200 mm]


FROM CENTER OF VALLEY

WOOD SHINGLES

NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. MINIMUM SLOPE FOR THIS DETAIL IS 8 :12 (34 DEGREES).

CLOSED VALLEY

SHNG-7
2001 NOT DRAWN TO SCALE

1309
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PRE-FABRICATED
BOOT FLASHING

UNDERLAYMENT TO
LAP OVER OR BE
SEALED TO UPPER
FLANGE

METAL
FLASHING SLEEVE

ALTERNATE : UNDERLAYMENT
WOOD SHINGLES

OPTIONAL FASTENERS

MIN. DOWNSLOPE
FLANGE DIMENSION
TO BE EQUAL TO
FIELD SHINGLE
EXPOSURE

PIPE PENETRATION

SHNG-8
2001 NOT DRAWN TO SCALE

1310
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROX. 1/2'' SHEET METAL


[13 mm] GAP FASCIA CAP
GASKETED FASTENERS
X. APPROX. 18'' [450 mm] O.C.
] MA IECE
m P DEPENDING UPON WIND
' [4 H P
12 EAC CA ZONE AND LOCAL
TH CIA CONDITIONS
E NG FAS
L F
O

SHEET METAL COVER


PLATE SET IN SEALANT
ON EACH SIDE

]
0 mm
[15
. 6''
OX
PR
AP

ROOF SIDE

APPROX. 1/2'' SHEET METAL


[13 mm] GAP FASCIA CAP

X.
] MA IECE
m P
' [4 H P
12 EAC CA
TH CIA SHEET METAL COVER
E NG FAS
L F PLATE SET IN SEALANT
O
ON EACH SIDE

m m]
[150
. 6''
ROX
P
AP

FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. OVERSIZED HOLES AT GASKETED FASTENERS MAY BE REQUIRED FOR CERTAIN METAL TYPES TO ALLOW FOR MOVEMENT.
3. THE SIDES/EDGES OF THE COVER PLATE CAN BE BENT DOWN SLIGHTLY TO STIFFEN AND HELP SEAT THE COVER PLATE.

FASCIA CAP WITH COVER PLATE

SM-1
2001 NOT DRAWN TO SCALE

1311
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
FASCIA CAP
X.
] MA IECE GASKETED FASTENERS
m P
' [4 H P APPROX. 18'' [450 mm] O.C.
12 EAC CA
H IA DEPENDING UPON WIND
N GT ASC ZONE AND LOCAL
LE F F
O CONDITIONS

OVERLAP JOINT SET IN


SEALANT

X.
P RO
AP mm]
[75
3''

ROOF SIDE
SHEET METAL
FASCIA CAP
X.
] MA IECE
m P
' [4 H P
12 EAC CA
TH CIA
E NG FAS
L F
O OVERLAP JOINT SET IN
SEALANT

X.
P RO
AP mm]
[75
3''

FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. OVERSIZED HOLES AT GASKETED FASTENERS MAY BE REQUIRED FOR CERTAIN METAL TYPES TO ALLOW FOR MOVEMENT.
3. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

FASCIA CAP WITH OVERLAP

SM-2
2001 NOT DRAWN TO SCALE

1312
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROX. 1/2'' SHEET METAL


[13 mm] GAP FASCIA CAP
GASKETED FASTENERS
X.
] MA IECE APPROX. 18'' [450 mm] O.C.
m P DEPENDING UPON WIND
' [4 H P
12 EAC CA ZONE AND LOCAL
TH CIA CONDITIONS
E NG FAS
L F
O

SHEET METAL
CONCEALED PLATE
SET IN SEALANT
ON EACH SIDE

m m]
[150
. 6''
OX
PR
AP

ROOF SIDE

APPROX. 1/2'' SHEET METAL


[13 mm] GAP FASCIA CAP

X.
] MA IECE
m P
' [4 H P
12 EAC CA
TH CIA SHEET METAL
E NG FAS
L F CONCEALED PLATE
O
SET IN SEALANT
ON EACH SIDE

mm]
[1 50
. 6''
ROX
P
AP

FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. OVERSIZED HOLES AT GASKETED FASTENERS MAY BE REQUIRED FOR CERTAIN METAL TYPES TO ALLOW FOR MOVEMENT.

FASCIA CAP WITH CONCEALED PLATE

SM-3
2001 NOT DRAWN TO SCALE

1313
The NRCA Roofing and Waterproofing Manual—Fifth Edition

''A'' TYPE EDGE METAL BEND FLANGE


AT ROOF SIDE
APPROX. 1/2''
[13 mm] GAP

X.
] MA IECE OPTION :
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E
O

SHEET METAL JOINT


m ]
COVER PLATE SET IN
0m
[15 SEALANT ON EACH SIDE
. 6'' AND FASTENED
OX
PR
AP
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
STAGGER PATTERN VARIES
ROOF SIDE PER ROOF SYSTEM

APPROX. 1/2'' ''A'' TYPE EDGE METAL


[13 mm] GAP

X.
] MA IECE
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E SHEET METAL JOINT
O COVER PLATE SET IN
SEALANT ON EACH SIDE
AND FASTENED

APPROPRIATE FASTENERS
] APPROX. 3'' to 6''
0 mm [75 to 150 mm] O.C.
[15 STAGGER PATTERN VARIES
. 6''
OX PER ROOF SYSTEM
PR
AP

FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. THE SIDES/EDGES OF THE COVER PLATE CAN BE BENT DOWN SLIGHTLY TO STIFFEN AND HELP SEAT THE COVER PLATE.

''A'' TYPE EDGE METAL WITH COVER PLATE

SM-4
2001 NOT DRAWN TO SCALE

1314
The NRCA Roofing and Waterproofing Manual—Fifth Edition

''A'' TYPE METAL EDGE BEND FLANGE


AT ROOF SIDE
X.
] MA IECE
m P L
' [4 H
12 EAC ETA
H M OPTION :
N GT DGE
LE F E
O

SHEET METAL SET


IN SEALANT
X.
P RO
AP mm]
[75
3''
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
STAGGER PATTERN VARIES
PER ROOF SYSTEM
ROOF SIDE
''A'' TYPE METAL EDGE

X.
] MA IECE
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E
O
SHEET METAL SET
IN SEALANT

APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
X. STAGGER PATTERN VARIES
P RO
AP mm] PER ROOF SYSTEM
[75
3''

FACE SIDE
NOTES :
1. CONTINUOUS CLEAT AT FACE SIDE NOT SHOWN FOR CLARITY.
2. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

''A'' TYPE EDGE METAL WITH OVERLAP

SM-5
2001 NOT DRAWN TO SCALE

1315
The NRCA Roofing and Waterproofing Manual—Fifth Edition

''L'' TYPE METAL EDGE BEND FLANGE


AT ROOF SIDE
APPROX. 1/2''
[13 mm] GAP

X. OPTION :
] MA IECE
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E
O

SHEET METAL JOINT


] COVER PLATE SET IN
0 mm SEALANT ON EACH SIDE
[15 AND FASTENED
. 6''
OX
PR
AP
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
STAGGER PATTERN VARIES
PER ROOF SYSTEM
ROOF SIDE

APPROX. 1/2'' ''L'' TYPE METAL EDGE


[13 mm] GAP

X.
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F SHEET METAL JOINT
O
COVER PLATE SET IN
SEALANT ON EACH SIDE
AND FASTENED

APPROPRIATE FASTENERS
] APPROX. 3'' to 6''
0 mm [75 to 150 mm] O.C.
[15 STAGGER PATTERN VARIES
. 6''
OX PER ROOF SYSTEM
PR
AP

NOTES : FACE SIDE


1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. THE SIDES/EDGES OF THE COVER PLATE CAN BE BENT DOWN SLIGHTLY TO STIFFEN AND HELP SEAT THE COVER PLATE.

''L'' TYPE EDGE METAL WITH COVER PLATE

SM-6
2001 NOT DRAWN TO SCALE

1316
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BEND FLANGE
''L'' TYPE METAL EDGE AT ROOF SIDE

X.
] MA IECE
m P L OPTION :
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O

SHEET METAL SET


IN SEALANT

X.
P RO
AP mm]
[75
3''
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
STAGGER PATTERN VARIES
ROOF SIDE PER ROOF SYSTEM

''L'' TYPE METAL EDGE

X.
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O
SHEET METAL SET
IN SEALANT

APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
. STAGGER PATTERN VARIES
ROX
P PER ROOF SYSTEM
AP mm]
[75
3''

FACE SIDE
NOTES :
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

''L'' TYPE EDGE METAL WITH OVERLAP

SM-7
2001 NOT DRAWN TO SCALE

1317
The NRCA Roofing and Waterproofing Manual—Fifth Edition

''L'' TYPE METAL EDGE BEND FLANGE


AT ROOF SIDE
APPROX. 1/2''
[13 mm] GAP

X. OPTION :
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O

SHEET METAL CONCEALED


PLATE SET IN SEALANT
m m] ON EACH SIDE
[1 50
6''
X.
P RO
AP
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
STAGGER PATTERN VARIES
ROOF SIDE PER ROOF SYSTEM

APPROX. 1/2'' ''L'' TYPE METAL EDGE


[13 mm] GAP

X.
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O SHEET METAL CONCEALED
PLATE SET IN SEALANT
ON EACH SIDE

]
0 mm APPROPRIATE FASTENERS
[15 APPROX. 3'' to 6''
6''
X. [75 to 150 mm] O.C.
P RO STAGGER PATTERN VARIES
A P
PER ROOF SYSTEM

NOTES : FACE SIDE


1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.

''L'' TYPE EDGE METAL WITH


CONCEALED PLATE
SM-8
2001 NOT DRAWN TO SCALE

1318
The NRCA Roofing and Waterproofing Manual—Fifth Edition

''T'' TYPE METAL EDGE APPROX.


1'' to 1.5''
[25 to 38 mm]
X.
] MA IECE
m P L BEND FLANGE
' [4 H
12 EAC ETA AT ROOF SIDE
H M
N GT DGE
LE F E
O
OPTION :

SHEET METAL SET


IN SEALANT

X.
P RO
AP ]
5 mm
[ 2
1''

APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
ROOF SIDE STAGGER PATTERN VARIES
PER ROOF SYSTEM

''T'' TYPE METAL EDGE


X.
] MA IECE
m P L SHEET METAL SET
' [4 H
12 EAC ETA IN SEALANT
H M
N GT DGE
LE F E
O

APPROX.
1'' to 1.5'' APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[25 to 38 mm] X.
P RO [75 to 150 mm] O.C.
AP ] STAGGER PATTERN VARIES
5 mm
[2 PER ROOF SYSTEM
1''

FACE SIDE
NOTES :
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

''T'' TYPE EDGE METAL WITH OVERLAP

SM-9
NOT DRAWN TO SCALE
2001
1319
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1 2 3

4 5 6

NOTES :
1. DASHED PROFILE REPRESENTS EDGE METAL, COPING CAP, ETC.
2. ALL CLEATS ARE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12' [4 m].

COMMON FASCIA EXTENSION OPTIONS

SM-10
2001 NOT DRAWN TO SCALE

1320
The NRCA Roofing and Waterproofing Manual—Fifth Edition

7 8 9

INTERMITTENT INTERMITTENT INTERMITTENT


CLIP CLIP CLIP

10 11 12

NOTES :
1. DASHED PROFILE REPRESENTS EDGE METAL, COPING CAP, ETC.
2. ALL CLEATS ARE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12' [4 m].

COMMON FASCIA EXTENSION OPTIONS

SM-11
2001 NOT DRAWN TO SCALE

1321
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DASHED PROFILE REPRESENTS


EDGE METAL, COPING CAP, ETC.

FASTENING TAB

13

DASHED PROFILE REPRESENTS


EDGE METAL, COPING CAP, ETC.

FASTENING TAB

14

NOTES :
1. DASHED PROFILE REPRESENTS EDGE METAL, COPING CAP, ETC.
2. ALL CLEATS ARE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12' [4 m].

COMMON FASCIA EXTENSION OPTIONS

SM-12
2001 NOT DRAWN TO SCALE

1322
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

OPTIONAL : 2'' [50 mm] WIDE


CLIP APPROX. 30'' [750 mm]
O.C. - 2 FASTENERS
PER CLIP

THROUGH-WALL REGLET AND COUNTERFLASHING


WITH OVERLAP JOINT
A
LEAD WEDGE AT APPROX.
24'' [600 mm] O.C.

APPROPRIATE SEALANT

FRICTION FIT SHEET METAL


REGLET INSERT IN RAGGLE
JOINT

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

OPTIONAL : 2'' [50 mm] WIDE


CLIP APPROX. 30'' [750 mm]
O.C. - 2 FASTENERS
PER CLIP

INSERT REGLET AND COUNTERFLASHING


WITH OVERLAP JOINT
B

COUNTERFLASHING OPTIONS

SM-13
2001 NOT DRAWN TO SCALE

1323
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
APPROPRIATE FASTENERS
24'' [600 mm] O.C.

3'' [75 mm] LAP AT JOINTS

REMOVABLE SHEET METAL


COUNTERFLASHING

OPTIONAL : 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

OPTIONAL : SEALANT OR
ELASTOMERIC TAPE

TWO PIECE SURFACE MOUNTED REGLET AND


COUNTERFLASHING WITH OVERLAP JOINT
C
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

ONE-PIECE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINT

OPTIONAL : 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

OPTIONAL : SEALANT OR
ELASTOMERIC TAPE

ONE-PIECE SURFACE MOUNTED COUNTERFLASHING


WITH OVERLAP JOINT
D

COUNTERFLASHING OPTIONS

SM-14
2001 NOT DRAWN TO SCALE

1324
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BUILDING PAPER
(IF REQUIRED)
WALL CLADDING

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

SHEET METAL REGLET

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

OPTIONAL : 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP
REGLET BEHIND CLADDING AND COUNTERFLASHING
WITH OVERLAP JOINT
E
OPTIONAL FASTENER
LOCATION

EQUIPMENT FLANGE

OPTIONAL :APPROPRIATE
FASTENERS
APPROX. 12'' [300 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINT

CURB COUNTERFLASHING (SKIRT FLASHING)


F

COUNTERFLASHING OPTIONS

SM-15
2001 NOT DRAWN TO SCALE

1325
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROX. 1/2'' SHEET METAL JOINT COVER


[13 mm] GAP SET IN SEALANT ON
EACH SIDE
X.
] MA IECE SHEET METAL
m P
' [4 H P COPING CAP
12 EAC CA
H NG
N GT OPI
LE F C
O

X.
P RO ]
AP mm
0
[15
6''

COPING CAP WITH COVER PLATE


A
SHEET METAL SET
X. IN SEALANT ON
] MA IECE EACH SIDE
m P
' [4 H P
12 EAC CA SHEET METAL
H NG
N GT OPI COPING CAP
LE F C
O

.
ROX
P
AP m]
[ 7 5m
3''
NOTES : COPING CAP WITH OVERLAP
B
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REFER TO TABLE SM-19 FOR COPING CAP SECUREMENT OPTIONS.
3. COPING JOINERY IS SIMILAR ON BOTH SIDES.
4. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

COPING CAP OPTIONS

SM-16
2001 NOT DRAWN TO SCALE

1326
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROX. 1/2'' SHEET METAL CONCEALED


[13 mm] GAP PLATE SET IN SEALANT
ON EACH SIDE
X.
] MA IECE SHEET METAL
m P
' [4 H P COPING CAP
12 EAC CA
H NG
N GT OPI
LE F C
O

.
OX
P PR m]
A
0m
[15
6''
COPING CAP WITH CONCEALED PLATE
APPROX. 1/2''
C
[13 mm] GAP SHEET METAL
COPING CAP

X. SHEET METAL DRIVE CLEAT


] MA IECE
m P BEND DOWN EACH FACE
' [4 H P
12 EAC CA
H NG
N GT OPI
LE F C
O

SHEET METAL
SET IN SEALANT

X.
P RO
AP ]
0 mm 3/4'' 1/2'' 3/4''
[ 5
2''

NOTES : COPING CAP WITH DRIVE CLEAT


D
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REFER TO TABLE SM-19 FOR COPING CAP SECUREMENT OPTIONS.
3. COPING JOINERY IS SIMILAR ON BOTH SIDES.
4. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

COPING CAP OPTIONS

SM-17
2001 NOT DRAWN TO SCALE

1327
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL DOUBLE
X. LOCK STANDING SEAM
] MA IECE
m P SHEET METAL
' [4 H P
12 EAC CA COPING CAP
H NG
N GT OPI BUTTON PUNCH TO
LE F C HOLD IN PLACE
O

1'' [25 mm] MIN.

OPTION :

SHEET METAL
SET IN SEALANT

X. 1'' [25 mm] MIN.


P RO
AP mm]
[50
2'' SECTION :

COPING CAP WITH DOUBLE LOCK STANDING SEAM


E
APPROX. 1/2'' SHEET METAL
[13 mm] GAP COPING CAP

X. SHEET METAL
] MA IECE DOUBLE ''S'' CLEAT
m P
' [4 H P SET IN SEALANT
12 EAC CA ON EACH SIDE
H NG
N GT OPI
LE F C
O SHEET METAL
SET IN SEALANT

SEALANT
X.
RO
P N.
AP ] MI
m
0m
2'' [5 3/4'' 1/2'' 3/4''

COPING CAP WITH DOUBLE ''S'' CLEAT


NOTES : F
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REFER TO TABLE SM-19 FOR COPING CAP SECUREMENT OPTIONS.
3. COPING JOINERY IS SIMILAR ON BOTH SIDES.
4. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

COPING CAP OPTIONS

SM-18
2001 NOT DRAWN TO SCALE

1328
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTINUOUS CLEATS

OPTIONAL METAL
/4''
.3 FLANGE EXTENSION
X
P RO
AP

4''
. 3/
OX
PR
TYPICAL AP
CLEAT ENGAGEMENT

APPROPRIATE FASTENERS
FASTENED APPROX. 6''
[150 mm] O.C.

CONTINUOUS CLEATS EACH SIDE


A
OPTIONAL METAL FLANGE
EXTENSION

. CONTINUOUS CLEAT
M IN
mm] APPROPRIATE FASTENERS
[50 FASTENED APPROX. 6''
2''
[150 mm] O.C.

2'' [50 mm] WIDE ISOLATED


3/4

CLIPS WITH APPROPRIATE


'' M

FASTENERS APPROX. 12''


IN.

COPING CAP [300 mm] O.C. DEPENDING


HEMMED EDGE
ON WIND ZONE AND
LOCAL CLIMATES
TYPICAL
CLIP ENGAGEMENT

CONTINUOUS CLEAT AND ISOLATED CLIPS


B
OPTIONAL METAL FLANGE
CONTINUOUS EXTENSION
CLEAT
GASKETED FASTENERS
AT APPROX. 18''
APPROPRIATE [450 mm] O.C. DEPENDING
FASTENERS ON WIND ZONE AND
FASTENED LOCAL CONDITIONS
APPROX. 6''
[150 mm] O.C.

CONTINUOUS CLEAT AND GASKETED FASTENERS


C

COPING CAP SECUREMENT OPTIONS

SM-19
2001 NOT DRAWN TO SCALE

1329
The NRCA Roofing and Waterproofing Manual—Fifth Edition

X.
] MA IECE SHEET METAL EXPANSION
m P
' [4 H ER JOINT COVER
12 EAC OV
H C
N GT OINT OVERLAP JOINT WITH
LE N J BEAD OF SEALANT
SIO
PAN SL
EX OP
OF E

GASKETED FASTENERS
AT APPROX. 18'' [450 mm]
O.C. DEPENDING ON WIND
X.
P RO WIND ZONE AND
AP ] LOCAL CONDITIONS
5 mm
[ 7
3''

CONTINUOUS SHEET METAL


''T'' TYPE CLEAT

EXPANSION JOINT COVER WITH OVERLAP


A
APPROX. 1/2''
[13 mm] JOINT
SHEET METAL EXPANSION
JOINT COVER
X.
] MA IECE
m P
' [4 H ER
12 EAC OV SHEET METAL COVER
H C
N GT OINT PLATE SET IN SEALANT
LE N J ON EACH SIDE
IO
NS
PA
EX SL
OF OP
E

GASKETED FASTENERS
] AT APPROX. 18'' [450 mm]
mm
50 O.C. DEPENDING ON WIND
6 '' [1 WIND ZONE AND
X.
P RO LOCAL CONDITIONS
AP

CONTINUOUS SHEET METAL


''T'' TYPE CLEAT

EXPANSION JOINT COVER WITH COVER PLATE


NOTES : B
1. BASE FLASHING, VAPOR RETARDER AND COMPRESSIBLE INSULATION ARE NOT SHOWN FOR CLARITY.
2. SEE SM-22 FOR ADDITIONAL METAL PROFILES.

EXPANSION JOINT COVER OPTIONS

SM-20
2001 NOT DRAWN TO SCALE

1330
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROX. 1/2'' SHEET METAL EXPANSION


[13 mm] GAP JOINT COVER
X. BUTTON PUNCH
] MA IECE TO HOLD IN PLACE
m P
' [4 H ER
12 EAC OV 1'' [25 mm] MIN.
C
TH T
E NG JOIN
L N
N SIO SL
OP
OPTION :
A E
EXP SHEET METAL DRIVE CLEAT
OF BEND DOWN EACH FACE
CONTINUOUS SHEET METAL
''T'' TYPE CLEAT

GASKETED FASTENERS
AT APPROX. 18'' [450 mm]
O.C. DEPENDING ON WIND
WIND ZONE AND
X.
P RO LOCAL CONDITIONS
AP ]
0 mm
[ 5
2''

3/4'' 1/2'' 3/4''

EXPANSION JOINT COVER WITH DRIVE CLEAT


C
SHEET METAL EXPANSION
. JOINT COVER
M AX CE
m] PIE R
' [4 H E SHEET METAL DOUBLE
12 EAC OV
H T C LOCK STANDING SEAM
T
NG OIN
LE N J
SL
SIO OP
PAN E
EX
OF CONTINUOUS SHEET METAL
''T'' TYPE CLEAT

GASKETED FASTENERS
AT APPROX. 18'' [450 mm]
O.C. DEPENDING ON WIND
WIND ZONE AND
LOCAL CONDITIONS

X.
P RO 1'' [25 mm] MIN.
AP ]
0 mm
[ 5
2''
SECTION :

EXPANSION JOINT COVER WITH STANDING SEAM


NOTES :
D
1. BASE FLASHING, VAPOR RETARDER AND COMPRESSIBLE INSULATION ARE NOT SHOWN FOR CLARITY.
2. SEE SM-22 FOR ADDITIONAL METAL PROFILES.
3. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.

EXPANSION JOINT COVER OPTIONS

SM-21
2001 NOT DRAWN TO SCALE

1331
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1 2

3 4

5 6

7 8
NOTES :
1. TOPS OF ALL EXPANSION JOINTS MUST SLOPE TO DRAIN.
2. BASE FLASHING, VAPOR RETARDER AND COMPRESSIBLE INSULATION NOT SHOWN FOR CLARITY.
3. FLAT PROFILE EXPANSION JOINTS SHOULD NOT BE SECURED ON BOTH SIDES.

EXPANSION JOINT PROFILE OPTIONS

SM-22
2001 NOT DRAWN TO SCALE

1332
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE FASTENERS

VALLEY METAL

NUMBER OF SEALANT
BEADS DEPENDENT
UPON SLOPE AND
CLIMATIC CONDITIONS

8'' [200 mm] MIN.


OVERLAP OF VALLEY
METAL AT JOINTS

CENTER RIB
1'' (25 mm) MIN. HEIGHT

NOTES :
1. THIS DETAIL DEPICTS THE OVERLAP JOINT ONLY.

VALLEY METAL WITH OVERLAP

SM-23
2001 NOT DRAWN TO SCALE

1333
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OVERLAP JOINT SHEET METAL GUTTER


SET IN SEALANT

.
P P ROX
A m]
75 m
3'' [
NOTE :
1. GUTTER PROFILES AND SIZE VARY.
2. APPROPRIATE FASTENERS (E.G. POP-RIVETS) COVERED WITH SEALANT - NOT SHOWN FOR CLARITY.

GUTTER WITH OVERLAP JOINT AND SEALANT


1
SOLDERED OVERLAP SHEET METAL GUTTER -
JOINT SOLDERABLE METALS
ONLY

SOLDER -
SWEAT INTO
SEAM .
P P ROX
A m]
75 m
3'' [
NOTES :
1. GUTTER PROFILES AND SIZE VARY.
2. APPROPRIATE FASTENERS (E.G., POP-RIVETS) SEALED WITH SOLDER - NOT SHOWN FOR CLARITY.

GUTTER WITH OVERLAP JOINT AND SOLDER


2

GUTTER JOINERY OPTIONS

SM-24
2001 NOT DRAWN TO SCALE

1334
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
GUTTER - WELDABLE
METALS ONLY

WELDED JOINT

NOTES :
1. GUTTER PROFILES AND SIZE VARY.

GUTTER WITH BUTT JOINT - WELDED


3
SHEET METAL
GUTTER

SPLICE PLATE JOINT


NOTES : SET IN SEALANT

1. GUTTER PROFILES AND SIZE VARY.


2. APPROPRIATE FASTENERS (E.G., POP-RIVETS) COVERED WITH SEALANT - NOT SHOWN FOR CLARITY.

GUTTER WITH SPLICE PLATE


4

GUTTER JOINERY OPTIONS

SM-25
2001 NOT DRAWN TO SCALE

1335
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DRIVE CLEAT
FLAT LOCK DOUBLE FLAT LOCK

''S'' CLEAT DOUBLE ''S'' CLEAT LAP SEAM

MECHANICALLY CONCEALED PLATE COVER PLATE


FASTENED SEAM SEAM SEAM

BUTT JOINT OVERLAP STANDING DOUBLE LOCK


(WELDED) SEAM STANDING SEAM

SINGLE LOCK CAPPED STANDING PITTSBURGH LOCK


STANDING SEAM SEAM

COMMON JOINTS AND SEAMS

SM-26
2001 NOT DRAWN TO SCALE

1336
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ARCHITECTURAL METAL
ROOF PANEL JOGGLE
CLEAT
''L'' TYPE
SEAM AND PANEL DOWNSLOPE
PROFILES VARY PERIMETER
METAL
FLASHING
PANEL CLIP
MIN. 2
FASTENERS
PER CLIP

E
OP
ALTERNATE :

SL
SLIP SHEET
UNDERLAYMENT
OR ICE DAM
''T'' TYPE PROTECTION
DOWNSLOPE MEMBRANE
PERIMETER
METAL
FLASHING

ROOF AND
WALL PROFILE
OPTIONAL :
INSTALL SEALANT
AT ENDS OF
VERTICAL SEAMS

OPTIONAL :
CONTINUOUS
CLEAT -
SEE TABLE 1

NOTES:
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.

DOWNSLOPE PERIMETER EDGE METAL


FLASHING

A-MTL-1
2001 NOT DRAWN TO SCALE

1337
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEAM AND PANEL


PROFILES VARY

PANEL CLIP ALTERNATE:


MIN. 2
FASTENERS
PER CLIP ARCHITECTURAL
METAL ROOF

E
OP
PANEL

SL
''T'' TYPE SLIP SHEET
DOWNSLOPE
PERIMETER UNDERLAYMENT
METAL OR ICE-DAM
FLASHING PROTECTION
MEMBRANE
OPTIONAL :
OPTIONAL : ICE-DAM
INSTALL SEALANT PROTECTION
AT ENDS OF MEMBRANE
VERTICAL SEAMS OVER ROOF
EDGE
GUTTER
BRACKET
SUPPORT AT
12'' TO 30''
[300 mm TO
750 mm] O.C.
DEPENDING
UPON
CONDITIONS

SHEET
GUTTER METAL GUTTER
SPACER PROFILES MAY
PLACED VARY
BETWEEN
BRACKETS

OPTIONAL :
ROOF AND
STIFFENING BAR
WALL PROFILE

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND REGIONAL PRACTICE
3. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
4. VARIOUS COMBINATIONS OF SUPPORT BRACKETS, SUPPORT BRACKETS AND SPACERS OR SPACER HANGERS CAN BE USED.

DOWNSLOPE PERIMETER WITH GUTTER


(''T'' TYPE)
A-MTL-2
2001 NOT DRAWN TO SCALE

1338
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEAM AND PANEL


PROFILES VARY

E
ARCHITECTURAL

OP
PANEL CLIP
METAL ROOF

SL
MIN. 2
FASTENERS PANEL
PER CLIP SLIP SHEET
UNDERLAYMENT
OPTIONAL:
OR ICE-DAM
INSTALL SEALANT
PROTECTION
AT ENDS OF
MEMBRANE
VERTICAL SEAMS

GUTTER
SPACER
PLACED
BETWEEN
BRACKETS

JOGGLE CLEAT

OPTIONAL :
DOWNSLOPE
''L'' TYPE
PERIMETER
METAL
FLASHING

SHEET
METAL GUTTER
PROFILES MAY
VARY

OPTIONAL:
STIFFENING BAR ROOF AND
WALL PROFILE

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND REGIONAL PRACTICE
3. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
4. VARIOUS COMBINATIONS OF SUPPORT BRACKETS, SUPPORT BRACKETS AND SPACERS OR SPACER HANGERS CAN BE USED.

DOWNSLOPE PERIMETER WITH GUTTER


(JOGGLE CLEAT)
A-MTL-2A
2001 NOT DRAWN TO SCALE

1339
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEAM AND PANEL


PROFILES VARY

ARCHITECTURAL
METAL ROOF PANEL

OPTION :

PE
O
SL

SLIP SHEET

UNDERLAYMENT
''T'' TYPE RAKE EDGE
METAL

OPTIONAL :
ROOF AND CONTINUOUS CLEAT
WALL PROFILE SEE TABLE 1

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.

RAKE EDGE FLASHING (''T'' TYPE)

A-MTL-3
2001 NOT DRAWN TO SCALE

1340
The NRCA Roofing and Waterproofing Manual—Fifth Edition

METAL RAKE
FLASHING

PANEL CLIP
MIN. 2
FASTENERS CLIP
PER CLIP

METAL RAKE
FLASHING

CONTINUOUS CONTINUOUS
CLEAT CLEAT
ALTERNATE : OPTION :

SEAM AND PANEL


PROFILES VARY

E
OP
SLIP SHEET

UNDERLAYMENT SL

METAL RAKE
FLASHING

CONTINUOUS
CLEAT
ROOF AND
WALL PROFILE
ARCHITECTURAL
METAL ROOF
PANEL

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.

RAKE EDGE FLASHING (CLEATED)

A-MTL-3A
2001 NOT DRAWN TO SCALE

1341
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ARCHITECTURAL SHEET METAL


METAL ROOF PANEL RIDGE CAP

''Z'' CLOSURE FASTENED


AND SET IN SEALANT OR
SOLDERED AS MATERIAL
PERMITS - SEAL
VERTICAL LEGS

OPTIONAL : TURN PANEL


PANS UP AT RIDGE TO
PROVIDE SECONDARY
CLOSURE

SLO
PE

OPE
SL

SLIP SHEET
SEAM AND PANEL
PROFILES VARY UNDERLAYMENT

ROOF SUBSTRATE

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE PANELS ALONG THE RIDGE IF THE ''Z'' CLOSURE IS FASTENED
THROUGH TO THE ROOF DECK.

NON-VENTING RIDGE CAP FLASHING

A-MTL-4
2001 NOT DRAWN TO SCALE

1342
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
RIDGE CAP

''T'' TYPE CLEAT

OPTIONAL :
AIR DAM WITH ALTERNATE:
PERFORATED
LOWER FACE OR CONTINUOUS WOOD
GAPS AT ENDS - SHIMMED AS REQUIRED
SOLDER TO PANS TO PASS OVER TOPS
OR SECURE OF SEAMS
UNDER VENT
NON-COMPRESSIBLE
AIR VENT TO MATCH
SEAM HEIGHT

TURN PANEL PANS


UP AT RIDGE TO
PROVIDE SECONDARY
CLOSURE
ARCHITECTURAL
METAL ROOF PANEL
SEAM AND PANEL
PROFILES VARY SLIP SHEET

UNDERLAYMENT
NOTES : ROOF SUBSTRATE
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE PANELS ALONG THE RIDGE.

VENTING RIDGE CAP FLASHING

A-MTL-4A
2001 NOT DRAWN TO SCALE

1343
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
HIP CAP

''Z'' CLOSURE
FASTENED AND SET IN
SEALANT, OR SOLDERED
AS MATERIAL PERMITS -
SEAL VERTICAL LEGS

ARCHITECTURAL
METAL ROOF
PANEL

SL
OP
E

E
OP
SL

SEAMS AND PANEL


PROFILES VARY

SLIP SHEET

UNDERLAYMENT

ROOF SUBSTRATE
OPTIONAL: TURN PANEL
PANS UP TO PROVIDE
NOTES : SECONDARY CLOSURE
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE PANELS ALONG THE HIP IF THE ''Z'' CLOSURE IS FASTENED
THROUGH TO THE ROOF DECK.

HIP CAP FLASHING

A-MTL-5
2001 NOT DRAWN TO SCALE

1344
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OPTIONAL :
INSTALL SEALANT
IN ENDS OF VERTICAL
]
SEAMS
5 mm E VALLEY METAL
ARCHITECTURAL [17 ANG
7'' FL H
METAL ROOF PANEL I N. IDT
M W

LOCK PANEL PANS TO


ENGAGE VALLEY METAL

PE
SL

O
OP

SL
E

1'' [25 mm]


MIN.

SEAM AND PANEL


PROFILES VARY
VALLEY CLIP MIN. 2
FASTENERS PER CLIP UNDERLAYMENT OR
(APPROX. 2'' [50mm] WIDE) ICE-DAM PROTECTION
BEND CLIP BACK OVER MEMBRANE
TO COVER FASTENERS
CENTER RIB (1''
SLIP SHEET [25 mm] MIN.
HEIGHT)
ROOF SUBSTRATE

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. WHERE ICE FORMATION IS EXPECTED, MINIMUM ROOF SLOPE FOR THIS VALLEY IS 6:12 (27 DEGREES).
3. DIMENSIONS FOR VALLEY METAL WIDTH MAY VARY ACCORDING TO PANEL LENGTHS AND GEOGRAPHIC
CONSIDERATIONS.

OPEN METAL VALLEY

A-MTL-6
2001 NOT DRAWN TO SCALE

1345
The NRCA Roofing and Waterproofing Manual—Fifth Edition

5'' [125 mm]


MIN. FLANGE WIDTH
ARCHITECTURAL
METAL ROOF PANEL
VALLEY METAL
OPTIONAL :
SOLDERED JOGGLE INSTALL SEALANT IN
CLEAT IN LIEU OF ENDS OF VERTICAL
CONTINUOUS LOCK SEAMS
ALTERNATE :
LOCK PANEL PANS TO
ENGAGE VALLEY METAL

PE
O
SL
SL
OP
E

SEAM AND PANEL


PROFILES VARY

VALLEY CLIP MIN. 2 4'' [100 mm] MIN.


FASTENERS PER CLIP PANEL OVERLAP ONTO
(APPROX. 2'' [50 mm] VALLEY METAL FLANGE
WIDE) BEND CLIP BACK
UNDERLAYMENT OR
OVER TO COVER FASTENERS
ICE-DAM PROTECTION
CONTINUOUS LOCK MEMBRANE

SLIP SHEET CENTER RIB (1''


[25 mm] MIN.
ROOF SUBSTRATE HEIGHT)
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. MINIMUM SLOPE RECOMMENDED FOR USE OF THIS VALLEY CONSTRUCTION IS 3:12 (14 DEGREES).
3. DIMENSIONS FOR VALLEY METAL WIDTH MAY VARY ACCORDING TO PANEL LENGTHS AND GEOGRAPHIC
CONSIDERATIONS.

ALTERNATE OPEN METAL VALLEY


WITH SIDE LOCKS
A-MTL-6A
2001 NOT DRAWN TO SCALE

1346
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WALL CONSTRUCTION

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

APPROX.
4'' [100 mm] MIN.
VERTICAL HEIGHT

OPTIONAL: CONTINUOUS
SHEET MEMBRANE LINER

SHEET METAL
ROOF-TO-WALL FLASHING
E
OP
SL

OPE
SL

SEAM AND PANEL OPTIONAL: TURN PANEL PANS


PROFILES VARY UP AT HEADWALL TO PROVIDE
SECONDARY CLOSURE
ARCHITECTURAL
METAL ROOF PANEL
''Z'' CLOSURE FASTENED AND
SLIP SHEET SET IN SEALANT OR
SOLDERED AS MATERIAL
UNDERLAYMENT PERMITS- SEAL VERTICAL LEGS
PANEL CLIP MIN. [2]
ROOF SUBSTRATE
FASTENERS PER CLIP
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE PANELS ALONG THE UPSLOPE END OF THE ROOF DECK
IF THE ''Z'' CLOSURE IS FASTENED THROUGH TO THE DECK.
3. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION FOR ADDITIONAL COUNTERFLASHING OPTIONS.

ROOF-TO-WALL (HEADWALL) TRANSITION

A-MTL-7
2001 NOT DRAWN TO SCALE

1347
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROXIMATELY 12''
[300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER

REMOVABLE SHEET METAL


COUNTERFLASHING
OPTIONAL SEALANT

APPROPRIATE FASTENERS
APPROXIMATELY 24'' [600 mm] O.C.

WALL PANEL CLIP


MIN. 2 FASTENERS

4'' [100 mm]


APPROX.
PER CLIP

SL
OP
E

ARCHITECTURAL
METAL ROOF PANEL

SLIP SHEET
UNDERLAYMENT ROOF AND WALL
CONSTRUCTION
SEAM AND PANEL
PROFILES VARY

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE ABUTTING WALL.
2. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
3. THIS DETAIL MAY BE USED WITH ''STARTER'' AND ''END'' PANELS.
4. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION FOR ADDITIONAL COUNTERFLASHING OPTIONS.

ROOF-TO-WALL (SIDEWALL) TRANSITION

A-MTL-8
2001 NOT DRAWN TO SCALE

1348
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
TOOLED TO FACILIATE RUNOFF
APPROPRIATE FASTENERS
APPROXIMATELY 12'' (300mm) O.C.
APPROPRIATE FASTENERS
APPROXIMATELY 24'' (600mm) O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
REMOVABLE SHEET METAL
COUNTERFLASHING

OPTIONAL SEALANT

SHEET METAL
ROOF-TO-WALL FLASHING

''Z'' CLOSURE
FASTENED AND SET
IN SEALANT OR
SOLDERED AS
MATERIAL PERMITS SL
OP
E

ARCHITECTURAL
METAL ROOF PANEL

SLIP SHEET
UNDERLAYMENT

SEAM AND PANEL


PROFILES VARY

ROOF SUBSTRATE

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE ABUTTING WALL.
2. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
3. THIS DETAIL MAY BE USED WITH ''STARTER'' AND ''END'' PANELS.
4. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION FOR ADDITIONAL COUNTERFLASHING OPTIONS.
5. THIS DETAIL FIXES THE PANEL IF THE ''Z'' CLOSURE IS FASTENED TO
THE ROOF SUBSTRATE.

ROOF-TO-WALL (SIDEWALL) TRANSITION


(''Z'' CLOSURE)
A-MTL-8A
2001 NOT DRAWN TO SCALE

1349
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EXPANSION


JOINT COVER SHEET METAL EXPANSION
JOINT COVER WITH
CENTER RIB
FLEXIBLE
MEMBRANE LINER ALTERNATE :

FLEXIBLE FOAM ROD


PE
COMPRESSIBLE LO
INSULATION S ARCHITECTURAL
METAL ROOF
''Z'' CLOSURE PANEL
FASTENED AND SET IN
SEALANT, OR SOLDERED
AS MATERIAL PERMITS

TURN PANEL
PANS UP
TO PROVIDE
SECONDARY PE
LO
CLOSURE S

FLEXIBLE VAPOR
RETARDER TO SERVE
AS INSULATION
RETAINER ATTACHED
TO ROOF DECK
SEAM AND
SLIP SHEET PANEL PROFILES
VARY
UNDERLAYMENT
ROOF
SUBSTRATE

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN BOTH DIRECTIONS.
3. THIS DETAIL FIXES THE PANEL IF THE ''Z'' CLOSURE IS FASTENED TO ROOF SUBSTRATE.
4. THE EXPANSION JOINT COVER MUST BE SECURED ON ONE SIDE AND HAVE SUFFICIENT
ENGAGEMENT ON THE OTHER SIDE TO ALLOW FOR EXPANSION AND CONTRACTION OF THE BUILDING.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER OF 1-1/2 TIMES THE WIDTH OF THE DECK OPENING.

EXPANSION JOINT - COMPACT


ROOF ASSEMBLY
A-MTL-9
2001 NOT DRAWN TO SCALE

1350
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EXPANSION


JOINT COVER

FLEXIBLE SHEET METAL EXPANSION


MEMBRANE LINER JOINT COVER WITH CENTER RIB
ALTERNATE :
FLEXIBLE FOAM ROD

FLEXIBLE VAPOR
RETARDER ATTACHED
TO ROOF DECK
OPE
''Z'' CLOSURE SL
FASTENED AND SET IN
SEALANT, OR SOLDERED
AS MATERIAL PERMITS

TURN PANEL
PANS UP
TO PROVIDE
SECONDARY
CLOSURE E
LOP
S

ARCHITECTURAL
METAL ROOF PANEL

UNDERLAYMENT

SLIP SHEET
SEAM AND PANEL
ROOF SUBSTRATE PROFILES VARY

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN BOTH DIRECTIONS.
3. THIS DETAIL FIXES THE PANEL, IF THE ''Z'' CLOSURE IS FASTENED TO ROOF SUBSTRATE.
4. THE EXPANSION JOINT COVER MUST BE SECURED ON ONE SIDE AND HAVE SUFFICIENT
ENGAGEMENT ON THE OTHER SIDE TO ALLOW FOR EXPANSION AND CONTRACTION OF THE BUILDING.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER OF 1-1/2 TIMES THE WIDTH OF THE DECK OPENING.

EXPANSION JOINT - NON-COMPACT


ROOF ASSEMBLY
A-MTL-9A
2001 NOT DRAWN TO SCALE

1351
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE VAPOR
RETARDER WITH
COMPRESSIBLE
INSULATION

WALL CONSTRUCTION

FASTENERS APPROX. 24'' [600 mm] O.C.

SHEET METAL REGLET

REMOVABLE SHEET METAL OPTION: COMPACT ROOF SYSTEM


COUNTERFLASHING

APPROX. 4'' [100 mm] MIN.


VERTICAL HEIGHT

SHEET METAL ROOF TO WALL


FLASHING WITH SUFFICIENT
ENGAGEMENT TO ACCOMMODATE
EXPANSION AND CONTRACTION

''Z'' CLOSURE
FASTENED AND SET IN E
OP
SEALANT OR SOLDERED SL
AS MATERIAL PERMITS-
SEAL VERTICAL LEGS

ARCHITECTURAL
METAL ROOF PANEL E
PANEL OP
SL

SLIP SHEET OPTIONAL :


FLEXIBLE FOAM ROD
SEAM AND PANEL
MIN. DIA.1-1/2 TIMES
PROFILES VARY
WIDTH OF OPENING
PANEL CLIP MIN.
2 FASTENERS FLEXIBLE SHEET
PER CLIP MEMBRANE FLASHING
OPTIONAL :TURN
UNDERLAYMENT
PANEL PANS UP AT
ROOF SUBSTRATE HEADWALL TO PROVIDE
SECONDARY CLOSURE
NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS DIFFERENTIAL MOVEMENT BETWEEN THE ROOF DECK AND A
VERTICAL WALL.
2. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO SYSTEM DEPENDING
UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
3. THIS METHOD OF FLASHING CAN FIX THE PANELS ALONG THE UPSLOPE END OF THE ROOF DECK IF THE ''Z''
CLOSURE IS FASTENED THROUGH TO THE DECK.
4. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION FOR ADDITIONAL COUNTERFLASHING OPTIONS.

EXPANSION JOINT AT ROOF-TO-WALL


(HEADWALL) TRANSITION
- NON-COMPACT ROOF SYSTEM
A-MTL-10
2001 NOT DRAWN TO SCALE

1352
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL
FRAME

12'' [300 mm]


MIN.
E
OP
SL

LE
AB
SEE DETAIL E ET
A-MTL-12 FOR -S
H
DT
FLASHING OF WI
SUPPORT LEGS

SEAM AND PANEL


PROFILES VARY

ROUND PIPE
COLUMN

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

NOTES :
1. DECK SUBSTRATE, UNDERLAYMENT AND SLIP-SHEET NOT SHOWN FOR CLARITY.

EQUIPMENT SUPPORT STAND

A-MTL-11
2001 NOT DRAWN TO SCALE

1353
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WATERTIGHT SHEET
EQUIPMENT SUPPORT METAL RAIN COLLAR
WITH STAINLESS STEEL
STAND/VENT STACK -
DRAWBAND - OVERLAP
SEE NOTE 1 FLASHING COLLAR
3'' [75 mm] MIN.
SEALANT BEAD BETWEEN
PIPE AND FLASHING TOOLED TO
FACILITATE RUNOFF

PREFORMED PENETRATION
FLASHING

GASKETED FASTENERS
SECURE FLASHING COLLAR
FLANGE TO ROOF PANEL
AND NOT TO DECK SO AS
NOT TO FIX PANEL AT
PENETRATION
OPTION :
OPENING IN ROOF DECK

STAINLESS STEEL
ARCHITECTURAL DRAWBAND
METAL ROOF PANEL SET SECUREMENT
RING IN CONTINUOUS
BEAD OF SEALANT

UNDERLAYMENT
SLIP SHEET
SEAM AND PANEL
PROFILES VARY
ROOF SUBSTRATE
NOTES :
1. NRCA RECOMMENDS PENETRATIONS SHOULD NOT INTERFERE WITH PANEL SEAMS OR OCCUR AT
TRANSVERSE SEAMS.
2. CUT HOLE IN ROOF DECK TO ALLOW FOR MOVEMENT.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
4. FOR HOT PIPES, SPECIFIC HIGH-TEMPERATURE BOOTS SHOULD BE USED.

EQUIPMENT SUPPORT STAND/VENT STACK


FLASHING WITH PREFORMED FLASHING
A-MTL-12
2001 NOT DRAWN TO SCALE

1354
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SOLDERED OR SEALED
SEAM AS MATERIAL
PERMITS

2 BEADS
OF SEALANT

WEATHERPROOF
RIVETS WITH
HEADS SEALED

OPTION : UNDERLAYMENT AND SLIP SHEET NOT SHOWN FOR CLARITY

FASTENERS-SECURE
FLASHING CAP FLASHING COLLAR
FLANGE TO ROOF
PANEL AND NOT TO
METAL FLASHING
DECK SO AS NOT
COLLAR
TO FIX PANEL AT
PENETRATION
ARCHITECTURAL
METAL ROOF PANEL COLLAR FLANGE
BELOW
SOLDERED OR
SEALED SEAM E
OP
AS MATERIAL SL
PERMITS

2 BEADS
OF SEALANT

WEATHERPROOF
RIVETS WITH HEADS
SEALED
SEAM AND PANEL SLIP SHEET
PROFILES VARY UNDERLAYMENT
ROOF SUBSTRATE

NOTES :
1. NRCA RECOMMENDS PENETRATIONS SHOULD NOT INTERFERE WITH PANEL SEAMS OR OCCUR AT
TRANSVERSE SEAMS.
2. CUT HOLE IN ROOF DECK TO ALLOW FOR MOVEMENT.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

PLUMBING VENT FLASHING

A-MTL-13
2001 NOT DRAWN TO SCALE

1355
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ALTERNATE : COUNTERFLASHING

MIN. HEIGHT
8'' [200 mm]
TURN UP
COUNTER-
FLASHING
WHENEVER
POSSIBLE
SECTION SHOWS
LOCKED SEAMS
OPTIONAL : IN LIEU OF
CRICKET (SEE OVERLAPPED AND
NOTE BELOW) SEALED SEAMS

IF JOINT IS OVERLAPPED SEAM AND PANEL


BUT NOT LOCKED, MIN. 2 PROFILES VARY
BEADS OF SEALANT
PLACED BETWEEN
UPSLOPE FLASHING
FLANGE AND TOP
SIDE OF PANEL

SEAL ENDS
OF SEAMS

OPTIONAL: CRICKET
(SEE NOTE BELOW)
WITH FLANGES
OVERLAPPED AND
SET IN SEALANT OR
SOLDERED AS
MATERIAL PERMITS

6'' [150 mm]


MIN. OVERLAP

SLIP SHEET

UNDERLAYMENT

ROOF
SUBSTRATE

6'' [150 mm] MIN. OVERLAP SHEET METAL CURB


FLASHING
ARCHITECTURAL METAL ROOF PANEL

NOTES :
1. NRCA SUGGESTS THAT DESIGNERS CONSIDER SPECIFYING CRICKETS WHEN THE RAISED CURB IS MORE
THAN 24 INCHES [600 mm] WIDE. WATER DIVERTERS MAY BE USED IN LIEU OF CRICKETS WHEN THE RAISED
CURB IS LESS THAN 24'' [600 mm] WIDE.
2. CURB MOUNTED EQUIPMENT SHOULD BE WEATHERPROOF AND HAVE A WEATHERPROOF INTERLOCK OR SUFFICENT
OVERLAP WITH THE CURB.
3. PROPER STRUCTURAL SUPPORT IS REQUIRED UNDER ALL SIDES OF THE RAISED CURB.
4. ALL METAL JOINTS TO BE SET IN SEALANT OR SOLDERED AS MATERIAL PERMITS.

RAISED CURB FOR ROOFTOP EQUIPMENT

A-MTL-14
2001 NOT DRAWN TO SCALE

1356
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MIN (2) PER SIDE
2'' [50 mm]
MIN. OVERLAP

COUNTERFLASHING

SECTION :

STRUCTURAL MEMBER
~
PENETRATING ROOF
ASSEMBLY

PLATE WELDED WATERTIGHT -


INSTALLED AFTER CURB
FLASHINGS
~ ~

WELDED COUNTERFLASHING FOR STRUCTURAL MEMBER THROUGH ROOF


1

TEMPERATURE APPROPRIATE
GASKET OR SEALANT TOOLED
TO FACILITATE RUNOFF

STAINLESS STEEL
DRAWBAND
METAL CURB CAP

METAL OR GYPSUM
BOARD LINER FOR
HOT PIPES

INSULATE VOID FOR


COLD STACKS TO LIMIT ~
CONDENSATION

~ ~

ISOLATED STACK FLASHING FOR HOT OR COLD PIPE PENETRATIONS


2

COUNTERFLASHING OPTIONS FOR


RAISED CURBS
A-MTL-15
2001 NOT DRAWN TO SCALE

1357
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FUTURE COUNTERFLASHING 1'' [25 mm] MIN.


SECURED ONLY TO JOGGLE
CLEAT EXTENSION

ALTERNATE :
JOGGLE CLEAT
SET IN SEALANT
SECTION :

SEAM AND PANEL


PROFILES VARY

OPTIONAL :
INSTALL SEALANT ARCHITECTURAL
E
OP

AT ENDS OF METAL ROOF


SL

VERTICAL SEAMS PANEL


SLIP SHEET
UNDERLAYMENT

LOW-SLOPE ROOF
MEMBRANE BASE
FLASHING
''
''A

E
OP
SL ROOF SUBSTRATE

LOW-SLOPE ROOF
MEMBRANE

NOTES :
1. DIMENSION ''A'' AND PANEL OVERLAP TO BE DETERMINED BY LOW-SLOPE MEMBRANE SYSTEM
REQUIREMENTS, SLOPE OF ROOF AND CLIMATIC CONSIDERATIONS.
2. COMPATIBILITY OF UNDERLAYMENT AND LOW-SLOPE MEMBRANE SHOULD BE CONSIDERED.
3. REFER TO LOW-SLOPE CONSTRUCTION DETAILS FOR SPECIFICS ON MEMBRANE BASE FLASHING.

LOW-SLOPE MEMBRANE TO METAL


ROOF TRANSITION
A-MTL-16
2001 NOT DRAWN TO SCALE

1358
The NRCA Roofing and Waterproofing Manual—Fifth Edition

TRANSITION
FLASHING

ALTERNATE :
ARCHITECTURAL METAL
ROOF PANEL

SEAM AND PANEL


PROFILES VARY SLIP SHEET

E
OPTIONAL : OP UNDERLAYMENT
INSTALL SEALANT
SL

AT ENDS OF CONTINUOUS
VERTICAL SEAMS JOGGLE CLEAT
SET IN SEALANT
SHEET METAL
TRANSITION FLEXIBLE MEMBRANE
FLASHING LINER

UNDERLAYMENT
.
IN SLIP SHEET
m ]M
0m
[15 WOOD BLOCKING
6'' BETWEEN SEAMS

OPTIONAL :
UPTURNED ENDS
''Z'' CLOSURE FASTENED
OPE AND SET IN SEALANT
SL OR SOLDERED AS
MATERIAL PERMITS-
SEAL VERTICAL LEGS

METAL ROOF PANEL

SEAM AND ROOF SUBSTRATE


PANEL PROFILES
VARY

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE LOWER ROOF PANELS.

METAL ROOF TO METAL ROOF TRANSITION

A-MTL-17
2001 NOT DRAWN TO SCALE

1359
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT CONTINUOUS
''C'' CLOSURE
''Z'' CLOSURE
SEALANT

METAL METAL
WALL PANEL WALL PANEL

SECTION : ALTERNATE :

E
OP
SEAMS AND PANEL
SL
PROFILES VARY

ARCHITECTURAL
METAL ROOF PANEL

OPTIONAL : INSTALL SLIP SHEET


SEALANT AT ENDS
OF VERTICAL SEAMS
UNDERLAYMENT

''T'' TYPE
DOWNSLOPE PERIMETER
METAL FLASHING

ROOF AND WALL


PROFILE

''Z'' CLOSURE FASTENED


AND SET IN SEALANT
OR SOLDERED AS
MATERIAL PERMITS-
SEAL VERTICAL LEGS

METAL WALL PANELS

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. THIS METHOD OF FLASHING FIXES THE WALL PANELS IF THE ''Z'' CLOSURE IS FASTENED
THROUGH TO THE WALL.

METAL WALL TO METAL ROOF


TRANSITION
A-MTL-18
2001 NOT DRAWN TO SCALE

1360
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ARCHITECTURAL
RIB KNUCKLE COVER METAL ROOF
NOTCH AND OVERLAP - PANEL
INSERT OVER PANEL
SEAM - RIVET TO
SEAM AND SEAL SEAMS AND
PANEL PROFILES
VARY

PANEL CLIP
MIN. 2
FASTENERS

E
OP
PER CLIP

SL

APPROPRIATE
SEALANT BOTH
SIDES OF SEAM

SLIP SHEET

UNDERLAYMENT

WALL PANEL CLIP


MIN. 2 FASTENERS
PER CLIP ROOF AND WALL
PROFILE

NOTES :
1. THIS DETAIL IS APPLICABLE WHEN ROOF AND WALL PANEL ARE CONTINUOUS FROM ROOF TO WALL.
2. THIS DESIGN MAY BE SUSCEPTIBLE TO ICE DAMAGE.
3. THIS DETAIL IS APPROPRIATE WHEN THE LOWER PORTION OF THE METAL PANEL IS RELATIVELY SHORT.
4. THIS DETAIL FIXES THE PANEL AT THIS LOCATION.

CONTINUOUS ROOF-TO-WALL
PANEL TRANSITION
A-MTL-19
2001 NOT DRAWN TO SCALE

1361
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL
METAL ROOF PANEL

METAL PANEL END


CLOSURES FASTENED
TO PANELS

SEAM AND PANEL


PROFILES VARY

ALTERNATE WALL CONSTRUCTION

E
OP
SL

OVERHANG
PANEL 1''
[25 mm] MIN.
PANEL CLIP
GASKETED MIN. 2
FASTENERS FASTENERS
PREFORMED METAL PER CLIP
CLOSURE SET IN
CONTINUOUS SEALANT STRUCTURAL
ON ALL SIDES FRAMING
TO METAL PANEL MEMBERS -
EDGE METAL FLASHING PROFILES AND
SPACING VARY
OPTIONAL :
CONTINUOUS CLEAT WALL
SEE TABLE 1 CONSTRUCTION
NOTES :
1. SPECIFIC FASTENING AND STRUCTURAL REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM
TO SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL FIXES THE PANEL AT THE EAVE.

DOWNSLOPE PERIMETER EDGE


METAL FLASHING
S-MTL-1
2001 NOT DRAWN TO SCALE

1362
The NRCA Roofing and Waterproofing Manual—Fifth Edition

JOGGLE CLEAT
FASTENED TO
FRAMING SEALED
TO ''L'' TYPE
METAL FLASHING

STRUCTURAL METAL
ROOF PANEL ALTERNATE:

OPTIONAL :
INSTALL SEALANT
AT ENDS OF
VERTICAL SEAMS PANEL CLIP MIN. 2
FASTENERS PER CLIP

E
OP
SL

SEAM AND PANEL STRUCTURAL


PROFILES VARY FRAMING MEMBERS -
PROFILES AND
SPACING VARY

''T'' TYPE DOWNSLOPE WALL CONSTRUCTION


PERIMETER METAL FLASHING
OPTIONAL: CONTINUOUS
CLEAT SEE TABLE 1

NOTES :
1. SPECIFIC FASTENING AND STRUCTURAL REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM
TO SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL CAN ONLY BE USED WHEN FIXED POINT IS NOT AT THE EAVE.

DOWNSLOPE PERIMETER EDGE


METAL FLASHING
S-MTL-1A
2001 NOT DRAWN TO SCALE

1363
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED
FASTENER
SEALANT TAPE

STRUCTURAL
METAL ROOF PANEL

GASKETED FASTENERS

SEAM AND PANEL


PROFILES VARY

SECTION :

PANEL CLIP MIN


2 FASTENERS
E PER CLIP
OP
SL

GASKETED
FASTENERS STRUCTURAL
FRAMING
METAL GUTTER MEMBERS -
STRAP AT EACH PROFILES AND
RIB SPACING VARY
SHEET METAL WALL
GUTTER CONSTRUCTION
OPTIONAL :
FASTENER CONTINUOUS
CLEAT SEE
PREFORMED METAL CLOSURE SET NOTE 6 AND
IN CONTINUOUS SEALANT ON ALL TABLE 1
SIDES TO METAL PANEL
''L'' TYPE
DOWNSLOPE
PERIMETER
NOTES : METAL FLASHING
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. DESIGN GUTTER EXPANSION JOINTS FOR PLACEMENT AT INTERVALS APPROPRIATE TO GUTTER
LENGTH AND TYPE OF METAL.
5. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND
REGIONAL PRACTICES.
6. CONTINUOUS CLEAT MAY NOT BE REQUIRED WHEN GUTTER INSTALLATION SECURES THE FACE OF THE
''L'' TYPE METAL.

DOWNSLOPE FLASHING WITH GUTTER

S-MTL-2
2001 NOT DRAWN TO SCALE

1364
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED
STRUCTURAL FASTENER
METAL ROOF PANEL FLANGED
GUTTER
SEAM AND PANEL
PROFILES VARY

INSTALL SEALANT
AT ENDS OF
VERTICAL SEAMS

ALTERNATE :
E
OP
SL

PANEL CLIP
MIN. 2 FASTENERS
PER CLIP

GUTTER SPACER STRUCTURAL


PLACED BETWEEN FRAMING MEMBERS -
BRACKETS PROFILES AND
SPACING VARY
GUTTER BRACKET
SUPPORT AT 12'' TO 30'' WALL
[300 mm TO 750 mm] O.C. CONSTRUCTION
DEPENDING UPON CONDITIONS
OPTIONAL :
SHEET METAL GUTTER CONTINUOUS CLEAT
SEE TABLE 1
EDGE METAL
FLASHING
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. DESIGN GUTTER EXPANSION JOINTS FOR PLACEMENT AT INTERVALS APPROPRIATE TO GUTTER
LENGTH AND TYPE OF METAL.
5. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND
REGIONAL PRACTICES.

DOWNSLOPE FLASHING WITH GUTTER

S-MTL-2A
2001 NOT DRAWN TO SCALE

1365
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLANGED
GUTTER

STRUCTURAL
METAL ROOF PANEL

INSTALL SEALANT AT
ENDS OF VERTICAL
SEAMS

SEAM AND
PANEL ALTERNATE:
PROFILES
VARY
E
OP
SL

PANEL CLIP
MIN. 2
FASTENERS
PER CLIP

STRUCTURAL FRAMING
MEMBERS - PROFILES
AND SPACING VARY
JOGGLE CLEAT
FASTENED TO FRAMING
GUTTER SPACER AND SEALED TO ''L''
AT 12'' TO 30'' TYPE METAL FLASHING
[300 mm TO 750 mm]
O.C. DEPENDING ON ''L'' TYPE EDGE METAL
CONDITIONS FLASHING

FASTENER OPTIONAL :
CONTINUOUS CLEAT
SEE TABLE 1
SHEET METAL GUTTER
WALL CONSTRUCTION
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. DESIGN GUTTER EXPANSION JOINTS FOR PLACEMENT AT INTERVALS APPROPRIATE TO GUTTER
LENGTH AND TYPE OF METAL.
5. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND
REGIONAL PRACTICES.

DOWNSLOPE FLASHING WITH GUTTER

S-MTL-2B
2001 NOT DRAWN TO SCALE

1366
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED
FASTENER
SEALANT

STRUCTURAL
METAL ROOF PANEL

SEAM AND PANEL


PROFILES VARY

SECTION :

E
OP
SL

SEALANT

METAL RAKE EDGE


FLASHING
STRUCTURAL FRAMING
MEMBER - PROFILES AND
SPACING VARY PANEL CLIP MIN. 2
FASTENERS PER CLIP

WALL CONSTRUCTION RAKE SUPPORT FLASHING


TO BE FORMED OF
HEAVY GAUGE METAL

CONTINUOUS CLEAT

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.

RAKE EDGE FLASHING - STARTER PANEL

S-MTL-3
2001 NOT DRAWN TO SCALE

1367
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL
METAL ROOF PANEL

SEAM AND PANEL


PROFILES VARY SECTION :

E
OP
SL

OPTIONAL GASKETED
FASTENER

METAL RAKE
EDGE FLASHING
STRUCTURAL FRAMING
MEMBER - PROFILES RAKE SUPPORT FLASHING
AND SPACING VARY TO BE FORMED OF
HEAVY GAUGE METAL -
ALSO SERVES AS
CONTINUOUS CLEAT
WALL CONSTRUCTION
''Z'' CLOSURE FASTENED
AND SET IN SEALANT
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES
THE PANEL ALONG THE RAKE EDGE.

RAKE EDGE FLASHING - END PANEL

S-MTL-3A
2001 NOT DRAWN TO SCALE

1368
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
RIDGE CAP

GASKETED
FASTENERS

PREFORMED METAL
CLOSURE - SET IN
SEALANT AND
ATTACHED TO PANEL
SEAL VERTICAL LEGS

PE SLO
PE
SLO

SEAM
AND PANEL
PROFILES VARY STRUCTURAL
FRAMING MEMBER -
PANEL CLIP PROFILES AND
MIN. 2 FASTENERS SPACING VARY
PER CLIP OPTIONAL
STRUCTURAL SEALANT
METAL ROOF PANEL HEAVY GAUGE PANEL
END SUPPORT METAL

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES
THE PANEL ALONG THE RIDGE.

RIDGE CAP FLASHING

S-MTL-4
2001 NOT DRAWN TO SCALE

1369
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
RIDGE CAP

GASKETED
FASTENERS

OPTIONAL: TURN
PANEL PANS UP AT
RIDGE TO PROVIDE
SECONDARY
CLOSURE

PREFORMED METAL
CLOSURE - SET IN
SLO SEALANT AND
PE
E ATTACHED TO
OP PANEL - SEAL
SL
VERTICAL LEGS

STRUCTURAL
SEAM FRAMING MEMBER -
AND PANEL PROFILES AND
PROFILES VARY SPACING VARY

PANEL CLIP
MIN. 2 FASTENERS
OPTIONAL
PER CLIP
SEALANT
STRUCTURAL
HEAVY GAUGE
METAL ROOF PANEL
PANEL END
SUPPORT METAL

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES
THE PANEL ALONG THE RIDGE.

RIDGE CAP FLASHING

S-MTL-4A
2001 NOT DRAWN TO SCALE

1370
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL SECTION :


RIDGE CAP GASKETED
FASTENER
PANEL END HEAVY GAUGE
SUPPORT PERFORATED
METAL
HEAVY GAUGE SHEET METAL
PERFORATED RIDGE CAP
METAL

NOTCH AT
SEAM

GASKETED
FASTENER

HEAVY GAUGE
PANEL END
SUPPORT METAL
SLOPE

STRUCTURAL
FRAMING MEMBER -
PROFILES AND
SPACING VARY

E
OP
SL

SEAM
AND PANEL
PROFILES VARY

PANEL CLIP
MIN. 2 FASTENERS STRUCTURAL
PER CLIP METAL ROOF
PANEL
PREFORMED METAL
CLOSURE - SET IN OPTIONAL
SEALANT AND SEALANT
ATTACHED TO PANEL -
SEAL VERTICAL LEGS

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
4. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES THE PANELS ALONG THE RIDGE.

VENTING RIDGE CAP FLASHING

S-MTL-5
2001 NOT DRAWN TO SCALE

1371
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS

SHEET METAL
RIDGE CAP

RIGID
POLYETHYLENE
VENT
GASKETED
SHEET METAL FASTENERS
CLEAT
SECTION :

PE
SLO

SEAM
AND PANEL
PROFILES VARY

PANEL CLIP
MIN. 2 FASTENERS STRUCTURAL FRAMING
PER CLIP MEMBER - PROFILES
AND SPACING VARY
PREFORMED METAL
STRUCTURAL
CLOSURE - SET IN SEALANT
METAL ROOF
AND ATTACHED TO PANEL -
PANEL
SEAL VERTICAL LEGS

HEAVY GAUGE PANEL OPTIONAL


END SUPPORT METAL SEALANT

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL WILL WORK FOR TRAPEZOIDAL STRUCTURAL PANELS ALSO.
4. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES THE PANELS ALONG THE RIDGE.

VENTING RIDGE CAP FLASHING

S-MTL-5A
2001 NOT DRAWN TO SCALE

1372
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
HIP CAP

GASKETED
FASTENERS

SL
OP
E

E
OP
SL

SEAM AND PANEL


PROFILES VARY

STRUCTURAL
METAL ROOF PANEL

PANEL CLIP STRUCTURAL FRAMING


MIN. 2 FASTENERS MEMBER - PROFILES
PER CLIP AND SPACING VARY
HEAVY GAUGE PANEL
PREFORMED METAL END STIFFENING METAL
CLOSURE - SET IN
SEALANT AND OPTIONAL SEALANT
ATTACHED TO PANEL -
SEAL VERTICAL LEGS

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL FIXES THE PANEL AT THE HIP IF THE CLOSURE IS FASTENED TO THE STRUCTURAL FRAMING MEMBER.
4. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.

HIP CAP FLASHING WITH PANEL END


STIFFENING METAL
S-MTL-6
2001 NOT DRAWN TO SCALE

1373
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SL
OP
E

E
OP
SL

SEAM AND PANEL


PROFILES VARY

STRUCTURAL
METAL ROOF PANEL
STRUCTURAL FRAMING
PANEL CLIP
MEMBER -PROFILES
MIN. 2 FASTENERS
AND SPACING VARY
PER CLIP
HEAVY GAUGE
PREFORMED METAL
HIP SUPPORT METAL
CLOSURE - SET IN
SEALANT AND SHEET METAL HIP CAP
ATTACHED TO PANEL-
SEAL VERTICAL LEGS
OPTIONAL :CLIP WHEN ''Z'' CLOSURE
IS NOT FASTENED TO HIP SUPPORT METAL.

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL FIXES THE PANEL AT THE HIP IF THE ''Z'' CLOSURE IS FASTENED TO THE HIP SUPPORT METAL.
4. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.

HIP CAP FLASHING WITH HIP


SUPPORT METAL
S-MTL-6A
2001 NOT DRAWN TO SCALE

1374
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PREFORMED FOAM PREFORMED METAL


CLOSURE SET IN CLOSURE SET IN
CONTINUOUS SEALANT/ CONTINUOUS SEALANT/
TAPE-SEAL ALL SIDES TAPE-SEAL ALL SIDES
TO METAL PANEL TO METAL PANEL
10''
[250
mm
MIN ]
. 10'' [250 mm]
MIN.

STRUCTURAL METAL
ROOF PANEL

GASKETED FASTENERS

PE
SLO

SLO
PE

SLOPE

STRUCTURAL FRAMING
MEMBER - PROFILES HEAVY GAUGE VALLEY
AND SPACING VARY LINER SUPPORT METAL
VALLEY METAL SEAM AND PANEL
PROFILES VARY
CENTER RIB (1'' [25 mm] MEMBRANE VALLEY
MIN. HEIGHT) UNDERLAYMENT
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. MINIMUM VALLEY FLANGE WIDTHS FOR SLOPES 2:12 (9 DEGREES) OR LESS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL FIXES THE PANELS AT THE VALLEY.
5. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.

OPEN VALLEY METAL (FASTENED)

S-MTL-7
2001 NOT DRAWN TO SCALE

1375
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL METAL INSTALL SEALANT


ROOF PANEL IN ENDS OF
VERTICAL SEAMS

7'' [
175
mm
SEE ]M
IN.
NO 7'' [175 mm] MIN.
TE
2
SEE NOTE 2

SLO
PE

E
OP
SL SLOPE

STRUCTURAL SEAM AND PANEL


FRAMING MEMBER - PROFILES VARY
PROFILES AND
SPACING VARY METAL CLIP APPROX.
2'' [50 mm] WIDE
HEAVY GAUGE VALLEY BEND CLIP OVER
LINER SUPPORT METAL FASTENERS

MEMBRANE VALLEY
VALLEY METAL UNDERLAYMENT
CENTER RIB (1''
[25 mm] MIN. HEIGHT)
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. MINIMUM VALLEY FLANGE WIDTHS FOR SLOPES 2:12 (9°) OR LESS. MINIMUM VALLEY FLANGE
WIDTHS INCREASE AS SLOPES DECREASE.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. PANEL TO VALLEY ENGAGEMANT DETERMINED BY PANEL LENGTH AND TYPE OF MATERIAL.

OPEN VALLEY METAL (CLEATED)

S-MTL-7A
2001 NOT DRAWN TO SCALE

1376
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WALL CONSTRUCTION

SHEET METAL REGLET

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING

APPROX. 4'' [100 mm] MIN.


VERTICAL HEIGHT

SHEET METAL ROOF


TO WALL FLASHING

PREFORMED
METAL CLOSURE SET
IN SEALANT AND
ATTACHED TO
PANEL - SEAL
E
VERTICAL LEGS OP
SL
SEAM AND PANEL
PROFILES VARY

E
OP
SL

OPTIONAL SEALANT
STRUCTURAL
METAL ROOF OPTIONAL :
PANEL CONTINUOUS SHEET
m m] MEMBRANE LINER
STRUCTURAL FRAMING 00
'' [3
MEMBER - PROFILES AND . 12 L HEAVY GAUGE PANEL
X AL
SPACING VARY P RO O W END STIFFENING
A P T METAL OR
PANEL CLIP STRUCTURAL
MIN. 2 FASTENERS FRAMING MEMBER
PER CLIP
GASKETED
NOTES : FASTENERS
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. IF THE METAL PANELS ARE FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES THE
PANELS ALONG THE UPSLOPE END OF THE ROOF.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
5. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR ADDITIONAL
COUNTERFLASHING OPTIONS.

ROOF-TO-WALL (HEADWALL) TRANSITION

S-MTL-8
2001 NOT DRAWN TO SCALE

1377
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE FASTENERS ALTERNATE :


APPROX. 12'' [300 mm] O.C.

APPROPRIATE SEALANT
SURFACE
TOOLED TO FACILITATE
MOUNTED
RUN OFF
SHEET METAL
RECEIVER
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C. OPTIONAL
SEALANT

REMOVABLE
E SHEET METAL
OP COUNTERFLASHING
SL

OPTIONAL :
CONTINUOUS SHEET
MEMBRANE LINER

SHEET METAL
ROOF TO WALL
FLASHING
SL
OP
E HEAVY GAUGE
PANEL SUPPORT
METAL

STRUCTURAL
METAL ROOF PANEL

SEAM AND PANEL


PROFILES VARY

PANEL CLIP MIN. 2


FASTENERS PER
CLIP
STRUCTURAL FRAMING
MEMBER - PROFILES
AND SPACING VARY
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR ADDITIONAL
COUNTERFLASHING OPTIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.

ROOF-TO-WALL (SIDEWALL) TRANSITION -


STARTER PANEL
S-MTL-9
2001 NOT DRAWN TO SCALE

1378
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SURFACE
MOUNTED
SHEET METAL
RECEIVER

OPTIONAL
SEALANT

REMOVABLE
SHEET METAL
APPROPRIATE FASTENERS COUNTERFLASHING
APPROX. 12'' [300 mm] O.C.
OPTIONAL
APPROPRIATE SEALANT
CONTINUOUS
: SHEET
TOOLED TO FACILITATE
MEMBRANE LINER
RUNOFF
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C. SHEET METAL
P E ROOF TO WALL
S LO
FLASHING
HEAVY GAUGE
PANEL SUPPORT
METAL
OPTIONAL SEALANT
SL
OP
E
''Z'' CLOSURE
SET IN SEALANT
AND FASTENED

STRUCTURAL
METAL ROOF PANEL

SEAM AND PANEL


PROFILES VARY

PANEL CLIP MIN. 2


FASTENERS PER
CLIP

STRUCTURAL
FRAMING MEMBER -
PROFILES AND
SPACING VARY

NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION OF THE ROOFING MANUAL FOR ADDITIONAL
COUNTERFLASHING OPTIONS.
4. THIS DETAIL WORKS FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.

ROOF-TO-WALL (SIDEWALL) TRANSITION -


END PANEL
S-MTL-9A
2001
NOT DRAWN TO SCALE
1379
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EXPANSION


JOINT COVER

FLEXIBLE MEMBRANE
SECTION :
LINER

FLEXIBLE FOAM ROD

GASKETED
FASTENERS

E
OP
SL
E
OP
SL

STRUCTURAL
METAL ROOF PANEL

COMPRESSIBLE ''Z'' CLOSURE SET IN


INSULATION SEALANT AND
FASTENED
FLEXIBLE VAPOR
RETARDER TO SERVE PANEL CLIP - MIN. 2
AS INSULATION FASTENERS PER
RETAINER ATTACHED CLIP
TO ROOF DECK, BOTH
SIDES HEAVY GAUGE
PANEL SUPPORT
NOTES : METAL

1. SPECIFIC
: FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CONDITIONS.
2. THIS METHOD OF FLASHING FIXES THE PANELS AT THE EXPANSION JOINT IF THE ''Z'' STRIP IS FASTENED
THROUGH TO THE STRUCTURAL FRAMING / PANEL SUPPORT METAL.
3. THIS DETAIL WORKS FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
4. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER 1-1/2 TIMES THE FRAMED OPENING.

EXPANSION JOINT
(THROUGH-PANEL FASTENED)
S-MTL-10
2001 NOT DRAWN TO SCALE

1380
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

SECTION :
FLEXIBLE MEMBRANE
LINER
SHEET METAL
EXPANSION JOINT
COVER
FLEXIBLE FOAM ROD
GASKETED
FASTENER
GASKETED
FASTENER SEALANT
E
SEALANT OP
SL

E
OP
SL

COMPRESSIBLE ''Z'' CLOSURE SET IN


INSULATION OPTIONAL SEALANT
AND FASTENED
FLEXIBLE VAPOR
STRUCTURAL METAL
RETARDER TO SERVE
ROOF PANEL
AS INSULATION
RETAINER ATTACHED PANEL CLIP - MIN. 2
TO PANEL SUPPORT FASTENERS PER
BOTH SIDES CLIP

HEAVY GAUGE
PANEL SUPPORT
NOTES :
METAL
1. SPECIFIC
: FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CONDITIONS.
2. THIS METHOD OF FLASHING FIXES THE PANELS AT THE EXPANSION JOINT IF THE ''Z'' STRIP IS FASTENED
THROUGH TO THE STRUCTURAL FRAMING / PANEL SUPPORT METAL.
3. THIS DETAIL WORKS FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
4. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER 1-1/2 TIMES THE FRAMED OPENING.

EXPANSION JOINT

S-MTL-10A
2001 NOT DRAWN TO SCALE

1381
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL
FRAME

12'' [300 mm]


MIN.
E
OP
SL

LE
AB
SEE DETAIL E ET
S-MTL-12 FOR -S
H
DT
FLASHING OF WI
SUPPORT LEGS

SEAM AND PANEL


PROFILES VARY

ROUND PIPE
COLUMN

WIDTH OF EQUIPMENT HEIGHT OF LEGS

UP TO 24'' [UP TO 600 mm] 24'' [600 mm]

24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]

48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

NOTES :
1. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.

EQUIPMENT SUPPORT STAND

S-MTL-11
2001 NOT DRAWN TO SCALE

1382
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WATERTIGHT SHEET
METAL RAIN COLLAR
WITH STAINLESS STEEL
DRAWBAND - OVERLAP
FLASHING COLLAR
3'' [75 mm] MIN.

EQUIPMENT SUPPORT
STAND/VENT STACK -
SEE NOTE

GASKETED FASTENERS
SECURE FLASHING COLLAR
FLANGE TO ROOF PANEL
OPTION :
SEALANT BEAD
BETWEEN PIPE AND
FLASHING TOOLED TO
FACILITATE RUNOFF
STAINLESS STEEL
STRUCTURAL DRAWBAND
METAL ROOF PANEL
PREFORMED
PENETRATION FLASHING
SET SECUREMENT
RING IN CONTINUOUS
BEAD OF SEALANT

SEAM AND PANEL


PROFILES VARY
NOTES :
1. NRCA RECOMMENDS PENETRATIONS SHOULD NOT INTERFERE WITH PANEL SEAMS OR OCCUR AT
TRANSVERSE SEAMS.
2. IF FIELD PANELS OVERLAP AT THE PENETRATION, ATTACHMENT OF THE DOWNSLOPE PANEL, ALONG ITS
UPSLOPE END, MAY BE NECESSARY.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
4. FOR HOT PIPES, SPECIFIC HIGH-TEMPERATURE BOOTS SHOULD BE USED.

EQUIPMENT SUPPORT STAND/VENT STACK


FLASHING WITH PREFORMED FLASHING
S-MTL-12
2001 NOT DRAWN TO SCALE

1383
The NRCA Roofing and Waterproofing Manual—Fifth Edition

OPTIONAL :
CRICKET

ONE-PIECE WELDED HEAVY


GAUGE METAL CURB WELDED HEAVY GAUGE METAL
TO METAL FLANGE WITH COMPRESSION PLATES
OPTIONAL CRICKET
SEE NOTE No.1 SECTION :

OVERLAPPED JOINT
WITH TWO BEADS OF
SEALANT OR TAPE
STRUCTURAL
METAL ROOF PANEL 6'' [150 mm]
MIN. OVERLAP
GASKETED
GASKETED
FASTENERS
FASTENER
SEAL END
OF SEAMS OVERLAPPED
JOINT WITH
TWO BEADS
OF SEALANT

SEAM AND
PANEL
PROFILES
VARY

STRUCTURAL
FRAMING
MEMBER -
PROFILES AND
SPACING VARY
6'' [150 mm] MIN.
GASKETED
OVERLAP
FASTENERS
WITH SEALANT
IN SEAMS

NOTES :
1. NRCA SUGGESTS THAT DESIGNERS CONSIDER SPECIFYING CRICKETS WHEN THE RAISED CURB IS MORE THAN
24 INCHES [600 mm] WIDE. WATER DIVERTERS MAY BE USED IN LIEU OF CRICKETS WHEN THE RAISED CURB IS
LESS THAN 24 INCHES [600 mm] WIDE.
2. PROPER STRUCTURAL SUPPORT IS REQUIRED UNDER ALL SIDES OF THE RAISED CURB.
3. THIS DETAIL FIXES THE RAISED CURB TO THE STRUCTURAL METAL PANELS.
4. CURB MOUNTED EQUIPMENT SHOULD BE WEATHERPROOF AND HAVE A WEATHERPROOF INTERLOCK OR
SUFFICIENT OVERLAP WITH THE CURB.
5. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
6. PREMANUFACTURED CURBS ARE AVAILABLE.

RAISED CURB FOR ROOFTOP UNITS

S-MTL-13
2001 NOT DRAWN TO SCALE

1384
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GASKETED FASTENERS
MIN (2) PER SIDE
2'' [50 mm]
MIN. OVERLAP

COUNTERFLASHING

SECTION :

STRUCTURAL MEMBER
~
PENETRATING ROOF
ASSEMBLY

PLATE WELDED WATERTIGHT -


INSTALLED AFTER CURB
FLASHINGS
~ ~

WELDED COUNTERFLASHING FOR STRUCTURAL


MEMBER THROUGH ROOF
1

TEMPERATURE APPROPRIATE
GASKET OR SEALANT TOOLED
TO FACILITATE RUNOFF

STAINLESS STEEL
DRAWBAND
METAL CURB CAP

METAL OR GYPSUM
BOARD LINER FOR
HOT PIPES

INSULATE VOID FOR


COLD STACKS TO LIMIT ~
CONDENSATION

~ ~

ISOLATED STACK FLASHING FOR HOT OR COLD


PIPE PENETRATIONS
2

COUNTERFLASHING OPTIONS FOR


RAISED CURBS
S-MTL-14
2001 NOT DRAWN TO SCALE

1385
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT 1

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL

UP TO 1.5'' FACE .032'' 16 oz. 24 ga. 24 ga. NOT REQUIRED

1.5'' to 3'' face .040'' 20 oz. 24 ga. 24 ga. NOT REQUIRED

SAME GAUGE
1.5'' TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL

SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL

ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

FASTEN AT APPROX. 3'' TO 6'' O.C. STAGGERED, WITH


CORROSION RESISTANT, BARBED, ANNULAR RING
OR SCREW SHANK NAIL. LENGTH TO ACHIEVE
APPROX. APPROX. 1 1/4'' PENETRATION INTO NAILER.
1'' - 1-1/2''

3'' MIN. 3'' MIN.


FLANGE ''A'' FLANGE FASTEN AT APPROX.
''A'' 6'' O.C. WITH CORROSION
RESISTANT, BARBED,
ANNULAR RING, OR
SCREW SHANK NAIL.
LENGTH TO ACHIEVE
APPROX. 1 1/4''
PENETRATION INTO
3/4'' 3/4'' NAILER.
FASTEN NEAR LOWER
''T'' TYPE PROFILE ''L'' TYPE PROFILE BRAKE FOR INCREASED
3/4'' UPLIFT RESISTANCE.

2
CLEAT

NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12 FEET, ALLOW A 1/4'' GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL TRIM AND FASCIA


EDGES FOR METAL ROOF SYSTEMS
METAL - TABLE 1
2001 NOT DRAWN TO SCALE

1386
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT 1

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL
UP TO 38 mm 2
.81 mm 4.87 kg/m .64 mm .61 mm NOT REQUIRED
FACE
38 mm TO
1.02 mm 6.10 kg/m 2 .64 mm .61 mm NOT REQUIRED
75 mm FACE
38 mm TO 2 SAME GAUGE
75 mm FACE .81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL

75 mm TO 2 SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL

150 mm TO ONE GAUGE


2
1.27 mm 6.10 kg/m .64 mm .61 mm HEAVIER THAN
200 mm FACE FASCIA METAL
200 mm TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
375 mm FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

FASTEN AT APPROX. 75 mm TO 150 mm O.C. STAGGERED, WITH


CORROSION RESISTANT, BARBED, ANNULAR RING
.
APPRO3X8 mm OR SCREW SHANK NAIL. LENGTH TO ACHIEVE
25 mm TO APPROX. 1 1/4'' PENETRATION INTO NAILER.

75 mm MIN. 75 mm MIN.
FLANGE FLANGE FASTEN AT APPROX.
''A'' 150 mm O.C. WITH
CORROSION RESISTANT,
BARBED, ANNULAR RING,
OR SCREW SHANK NAIL.
LENGTH TO ACHIEVE
APPROX. 32 mm
PENETRATION INTO
20 mm 20 mm NAILER.
FASTEN NEAR LOWER
''T'' TYPE PROFILE ''L'' TYPE PROFILE BRAKE FOR INCREASED
20 mm UPLIFT RESISTANCE.

2
CLEAT

NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 4 m, ALLOW A 6 mm GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL TRIM AND FASCIA


EDGES FOR METAL ROOF SYSTEMS
METAL - TABLE 1 (METRIC)
2001 NOT DRAWN TO SCALE

1387
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SOME COMMON ARCHITECTURAL AND STRUCTURAL METAL ROOFING PANEL PROFILES AND CLIPS

ARCHITECTURAL PANEL ARCHITECTURAL PANEL

1. DOUBLE-LOCK STANDING SEAM 2. TRADITIONAL BATTEN

ARCHITECTURAL PANEL ARCHITECTURAL PANEL

3. SNAP-ON BATTEN CAP 4. MECHANICALLY-SEAMED


WITH CLIP SINGLE LOCK
ARCHITECTURAL PANEL ARCHITECTURAL PANEL

5. SNAP-LOCK SEAM 6. SNAP-CAP SEAM

ARCHITECTURAL PANEL ARCHITECTURAL PANEL

7. T-SEAM 8. INTEGRAL SEAM No. 2

STRUCTURAL PANEL STRUCTURAL PANEL

10. RAISED MECHANICALLY-


9. TRAPEZOIDAL SEAM SEAMED PANEL

SOME EXAMPLES OF SEAM AND


CLIP PROFILES
METAL - TABLE 2
2001 NOT DRAWN TO SCALE

1388
The NRCA Roofing and Waterproofing Manual—Fifth Edition

3/4'' [18 mm] MIN.


OVERHANG

BELOW BLOCKING

ALTERNATE :
1'' [25 mm] MIN.

SHEET METAL PARAPET


CAP

GASKETED FASTENERS

CONTINUOUS SHEET
MEMBRANE CLOSURE.
OPTIONAL IF DOUBLE
LOCK STANDING SEAM
JOINTS ARE USED WITH
THE METAL PARAPET CAP.

CONTINUOUS SHIM

8'' [200 mm] MIN.


FLASHING HEIGHT

CONTINUOUS CLEAT

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

IF CONCRETE, PRIME
BEFORE APPLYING SPF-
PREPARE AS REQUIRED
ROOF DECK -
NOTES :
PREPARE AS REQUIRED
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

METAL PARAPET CAP (COPING)

SPF-1
2001 NOT DRAWN TO SCALE

1389
The NRCA Roofing and Waterproofing Manual—Fifth Edition

3/4'' [18 mm] MIN.


OVERHANG
BELOW BLOCKING
1'' [25 mm] MIN.

ALTERNATE :

CONTINUOUS SHEET
MEMBRANE CLOSURE.
OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS ARE
USED WITH THE METAL
PARAPET CAP.

GASKETED FASTENERS

CONTINUOUS SHIM

SHEET METAL PARAPET CAP

CONTINUOUS CLEAT

8'' [200 mm] MIN.


FLASHING HEIGHT

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

IF CONCRETE, PRIME BEFORE


APPLYING SPF

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

METAL PARAPET CAP (COPING)

SPF-1S
2001 NOT DRAWN TO SCALE

1390
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1'' [25 mm] MIN. THICKNESS


OF SPF ABOVE METAL FLANGE

FASTENERS 3'' TO 6'' V-GROOVE SPF AT EDGE AND


[75 TO 150 mm] O.C., INSTALL ELASTOMERIC SEALANT
STAGGERED

PROPERLY PREPARE METAL DOUBLE THICKNESS OF


FLANGE BEFORE APPLYING SPF ELASTOMERIC COATING 12''
TO ENHANCE ADHESION [300 mm] FROM PERIMETER

SHEET METAL EDGE FLASHING


(FOAM STOP) APPROX. 4''
[100 mm] WIDE FLANGE

CONTINUOUS CLEAT
1'' [25 mm] MIN.
BELOW TOP OF WALL

ELASTOMERIC COATING

SPRAY POLYURETHANE FOAM


(1'' [25 mm] MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. ELASTOMERIC SEALANT TO BE COMPATIBLE WITH COATING.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

PERIMETER EDGE METAL


FLASHING WITH SEALANT (FOAM STOP)
SPF-2
2001 NOT DRAWN TO SCALE

1391
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1'' [25 mm] MIN. THICKNESS


DOUBLE THICKNESS OF OF SPF ABOVE METAL FLANGE
ELASTOMERIC COATING 12''
[300 mm] FROM PERIMETER

V-GROOVE SPF ELASTOMERIC COATING


AT EDGE AND INSTALL
ELASTOMERIC SEALANT

1'' MIN. 1'' MIN.


[25 mm] [25 mm]
SPRAY POLYURETHANE FOAM
(1'' [25 mm] MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED
1'' [25 mm] MIN.
BELOW TOP OF WALL

FASTENERS 3'' TO 6''


[75 TO 150 mm] O.C.,
STAGGERED

PROPERLY PREPARE METAL


FLANGE BEFORE APPLYING SPF
TO ENHANCE ADHESION

SHEET METAL EDGE FLASHING


(FOAM STOP) APPROX. 4''
[100 mm] WIDE FLANGE

CONTINUOUS CLEAT
NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. ELASTOMERIC SEALANT TO BE COMPATIBLE WITH COATING.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

PERIMETER EDGE METAL


FLASHING WITH SEALANT (FOAM STOP)
SPF-2S
2001 NOT DRAWN TO SCALE

1392
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1'' [25 mm] MIN. THICKNESS


OF SPF ABOVE METAL FLANGE

FASTENERS 3'' TO 6''


[75 TO 150 mm] O.C.,
STAGGERED

PROPERLY PREPARE METAL


FLANGE BEFORE APPLYING SPF
TO ENHANCE ADHESION

SHEET METAL EDGE FLASHING


(FOAM STOP) APPROX. 4''
[100 mm] WIDE FLANGE

CONTINUOUS CLEAT
1'' [25 mm] MIN.
BELOW TOP OF WALL

ELASTOMERIC COATING

SPRAY POLYURETHANE FOAM


(1'' [25 mm] MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

PERIMETER EDGE METAL FLASHING


(FOAM STOP)
SPF-3
2001 NOT DRAWN TO SCALE

1393
The NRCA Roofing and Waterproofing Manual—Fifth Edition

1'' [25 mm] MIN. THICKNESS


OF SPF ABOVE METAL FLANGE

FASTENERS 3'' TO 6''


[75 TO 150 mm] O.C.,
STAGGERED

PROPERLY PREPARE METAL


FLANGE BEFORE APPLYING SPF
TO ENHANCE ADHESION

SHEET METAL EDGE FLASHING


(FOAM STOP) APPROX. 4''
[100 mm] WIDE FLANGE

ELASTOMERIC COATING

SPRAY POLYURETHANE FOAM


(1'' [25 mm] MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED
1'' [25 mm] MIN.
BELOW TOP OF WALL

CONTINUOUS CLEAT

NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

PERIMETER EDGE METAL FLASHING


(FOAM STOP)
SPF-3S
2001 NOT DRAWN TO SCALE

1394
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

OPTION :

SMOOTH CONCRETE
EXPOSED SURFACES MUST
BE WEATHERPROOFED
(BY OTHERS)

INSTALL APPROPRIATE (E.G.,


POLYURETHANE) SEALANT
AND TOOL TO FACILITATE
WATER RUN-OFF
CONCRETE FASTENERS

SHEET METAL
COUNTERFLASHING

COMPRESSIBLE ELASTOMERIC
TAPE TO SPAN
IRREGULARITIES
8'' [200 mm] MIN.
FLASHING HEIGHT

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
PRIME CONCRETE BEFORE
APPLYING SPF
ROOF DECK -
NOTES : PREPARE AS REQUIRED

1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

SURFACE-MOUNT COUNTERFLASHING

SPF-4
2001 NOT DRAWN TO SCALE

1395
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

SMOOTH CONCRETE -
EXPOSED SURFACES MUST
BE WATERPROOFED
(BY OTHERS)

INSTALL APPROPRIATE (E.G.,


POLYURETHANE) SEALANT
AND TOOL TO FACILITATE
WATER RUN-OFF
CONCRETE FASTENERS

COMPRESSIBLE ELASTOMERIC
TAPE TO SPAN
IRREGULARITIES

8'' [200 mm] MIN.


FLASHING HEIGHT

SHEET METAL
COUNTERFLASHING

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
PRIME CONCRETE BEFORE
APPLYING SPF
ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

SURFACE-MOUNT COUNTERFLASHING

SPF-4S
2001 NOT DRAWN TO SCALE

1396
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

FASTENERS APPROX. 24''


[600 mm] O.C.

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

8'' [200 mm] MIN.


FLASHING HEIGHT

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR WALL-SUPPORTED


DECK
SPF-5
2001 NOT DRAWN TO SCALE

1397
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT
FOAM STOP

ELASTOMERIC
COATING

ALTERNATE :

SHEET METAL REGLET

FASTENERS APPROX. 24''


[600 mm] O.C.

REMOVABLE SHEET METAL


COUNTERFLASHING

8'' [200 mm] MIN.


FLASHING HEIGHT

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR WALL-SUPPORTED


DECK
SPF-5S
2001 NOT DRAWN TO SCALE

1398
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

FASTENERS APPROX. 24''


[600 mm] O.C.

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

VENTED BASE SHEET (DO


NOT ADHERE TO WALL)
FASTENED APPROX. 8''
[200 mm] O.C.

8'' [200 mm] MIN.


FLASHING HEIGHT

1'' [25 mm] MIN. THICKNESS


OF SPF ABOVE CANT
ELASTOMERIC COATING

DECAY RESISTANT CANT

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
BASE SHEET FASTENERS

LIGHTWEIGHT INSULATING
CONCRETE
VENTED GALVANIZED
NOTES : STEEL DECK
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
OR WHEN REROOFING OVER EXISTING WET-FILL DECKS.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
4. WOOD BLOCKING SHOULD BE SLOTTED FOR VENTING OF WET-FILL DECKS WHERE APPLICABLE.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR VENTED BASE SHEET

SPF-5A
2001 NOT DRAWN TO SCALE

1399
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

FASTENERS APPROX. 24''


[600 mm] O.C.
SHEET METAL REGLET

ALTERNATE :

REMOVABLE SHEET METAL


COUNTERFLASHING

8'' [200 mm] MIN.


FLASHING HEIGHT

VENTED BASE SHEET (DO


NOT ADHERE TO WALL)
FASTENED APPROX. 8''
[200 mm] O.C.
1'' [25 mm] MIN. THICKNESS
OF SPF ABOVE CANT
ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

BASE SHEET FASTENERS


DECAY RESISTANT CANT

LIGHTWEIGHT INSULATING
CONCRETE
VENTED GALVANIZED
NOTES : STEEL DECK
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
OR WHEN REROOFING OVER EXISTING WET-FILL DECKS.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
4. WOOD BLOCKING SHOULD BE SLOTTED FOR VENTING OF WET-FILL DECKS WHERE APPLICABLE.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR VENTED BASE SHEET

SPF-5AS
2001 NOT DRAWN TO SCALE

1400
The NRCA Roofing and Waterproofing Manual—Fifth Edition

3/4'' [19 mm] MIN.


OVERHANG

FOAM
STOP

ALTERNATE :
FASTENERS APPROX. 24''
[600 mm] O.C.

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

MEMBRANE SHEET CLOSURE


SECURED AND ADHERED TO
WALL

FASTENERS APPROX.
8'' [200 mm] O.C.
8'' [200 mm] MIN.
FLASHING HEIGHT
FLEXIBLE VAPOR RETARDER
w/ COMPRESSIBLE
INSULATION

1'' [25 mm] MIN. THICKNESS


OF SPF ABOVE CANT
ELASTOMERIC COATING

WOOD CANT IF NECESSARY


TO BRACE CURB - PREPARE
AS REQUIRED
WOOD NAILER(S) -
PREPARE AS REQUIRED
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
NOTES : PREPARE AS REQUIRED
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL
OCCUR BETWEEN THE DECK AND A VERTICAL SURFACE, SUCH AS AT A PENTHOUSE WALL. THE WOOD
MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR NON-WALL-


SUPPORTED DECK
SPF-6
2001 NOT DRAWN TO SCALE

1401
The NRCA Roofing and Waterproofing Manual—Fifth Edition

3/4'' [19 mm] MIN.


OVERLAP

FOAM STOP

ALTERNATE :

SHEET METAL REGLET

FASTENERS APPROX. 24''


[600 mm] O.C.

MEMBRANE SHEET CLOSURE


SECURED AND ADHERED TO
WALL

REMOVABLE SHEET METAL


COUNTERFLASHING
8'' [200 mm] MIN.
FLASHING HEIGHT
1'' [25 mm] MIN. THICKNESS
OF SPF ABOVE CANT

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
WOOD CANT IF NECESSARY
TO BRACE CURB PREPARE
AS REQUIRED

ROOF DECK PREPARE -


AS REQUIRED

WOOD NAILER(S) PREPARE -


AS REQUIRED

FLEXIBLE VAPOR RETARDER


w/ COMPRESSIBLE
INSULATION
NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL
OCCUR BETWEEN THE DECK AND A VERTICAL SURFACE, SUCH AS AT A PENTHOUSE WALL. THE WOOD
MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR NON-WALL-


SUPPORTED DECK
SPF-6S
2001 NOT DRAWN TO SCALE

1402
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
FOAM STOP
OPTIONAL IF DOUBLE
LOCK STANDING SEAM 3/4'' 3/4''
[19 mm] [19 mm]
JOINTS ARE USED WITH MIN. MIN.
THE METAL PARAPET OVERHANG OVERHANG
CAP.

FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)

COMPRESSIBLE
INSULATION ALTERNATE :
FLASHING HEIGHT
8'' [200 mm] MIN.

SHEET METAL EXPANSION


JOINT COVER

GASKETED FASTENERS

TOP OF CURB TO
DRAIN TO ONE SIDE

ELASTOMERIC COATING

1'' [25 mm] MIN.


THICKNESS OF SPF
OVER CANT

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
WOOD CANT IF THICKNESS)
NECESSARY TO BRACE
CURB PREPARE AS
REQUIRED ROOF DECK -
PREPARE AS REQUIRED
WOOD NAILER(S) PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EXPANSION JOINT WITH METAL COVER

SPF-7
2001 NOT DRAWN TO SCALE

1403
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FLEXIBLE WATERPROOF
MEMBRANE CLOSURE.
FOAM STOP
OPTONAL IF DOUBLE
LOCK STANDING SEAM 3/4'' 3/4''
[19 mm] [19 mm]
JOINTS ARE USED WITH MIN. MIN.
THE METAL PARAPET OVERHANG OVERHANG
CAP.

FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
ALTERNATE :
COMPRESSIBLE
INSULATION

SHEET METAL EXPANSION


JOINT COVER
FLASHING HEIGHT
8'' [200 mm] MIN.

TOP OF CURB TO
DRAIN TO ONE SIDE

GASKETED FASTENERS

ELASTOMERIC COATING

1'' [25 mm] MIN.


THICKNESS OF SPF
ABOVE CANT

WOOD CANT IF
NECESSARY TO SPRAY POLYURETHANE
BRACE CURB FOAM (1'' [25 mm] MIN.
PREPARE AS REQUIRED THICKNESS)

WOOD NAILER(S)
ROOF DECK -
PREPARE AS REQUIRED
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EXPANSION JOINT WITH METAL COVER

SPF-7S
2001 NOT DRAWN TO SCALE

1404
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PREMANUFACTURED
EXPANSION JOINT COVER FOAM STOP
3/4'' 3/4''
FLEXIBLE WATERPROOF [19 mm] [19 mm]
MIN. MIN.
MEMBRANE CLOSURE OVERHANG OVERHANG

FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)

COMPRESSIBLE
INSULATION
ALTERNATE :
FLASHING HEIGHT
8'' [200 mm] MIN.

GASKETED FASTENERS

TOP OF CURB TO
DRAIN TO OUTSIDE

ELASTOMERIC COATING

1'' [25 mm] MIN.


THICKNESS OF SPF
OVER CANT

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
WOOD CANT IF THICKNESS)
NECESSARY TO
BRACE CURB
PREPARE AS REQUIRED

WOOD NAILER(S) ROOF DECK -


PREPARE AS REQUIRED PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
SPF-7A
2001 NOT DRAWN TO SCALE

1405
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP
PREMANUFACTURED
EXPANSION JOINT COVER 3/4'' 3/4''
[19 mm] [19 mm]
MIN. MIN.
OVERHANG OVERHANG
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE

FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)

COMPRESSIBLE OPTION :
INSULATION

TOP OF CURB TO
DRAIN TO OUTSIDE

GASKETED FASTENERS
FLASHING HEIGHT
8'' [200 mm] MIN.

ELASTOMERIC COATING

1'' [25 mm] MIN.


THICKNESS OF SPF
ABOVE CANT

WOOD CANT IF
NECESSARY TO
SPRAY POLYURETHANE
BRACE CURB -
FOAM (1'' [25 mm] MIN.
PREPARE AS REQUIRED
THICKNESS)
WOOD NAILER(S) -
PREPARE AS REQUIRED ROOF DECK -
PREPARE AS REQUIRED

NOTES :

1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.


2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EXPANSION JOINT WITH


PREMANUFACTURED COVER
SPF-7AS
2001 NOT DRAWN TO SCALE

1406
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP
3/4''
[19 mm]
MIN.
OVERHANG

ROOF SYSTEM
DIVIDER COVER

FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
ALTERNATE :
FLASHING HEIGHT
8'' [200 mm] MIN.

GASKETED FASTENERS

TOP OF CURB TO
DRAIN TO ONE SIDE

ELASTOMERIC COATING

1'' [25 mm] MIN.


THICKNESS OF SPF
OVER CANT

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
WOOD NAILER(S) -
PREPARE AS REQUIRED

ROOF DECK -
NOTES :
PREPARE AS REQUIRED

1. A ROOF SYSTEM DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED
TO THE ROOF DECK. ROOF SYSTEM DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. REFER TO APPROPRIATE SECTION OF LOW-SLOPE CONSTRUCTION DETAILS FOR FLASHING REQUIREMENTS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

ROOF SYSTEM DIVIDER

SPF-8
2001 NOT DRAWN TO SCALE

1407
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP
3/4'' 3/4''
[19 mm] [19 mm]
MIN. MIN.
OVERHANG OVERHANG

ROOF SYSTEM
DIVIDER COVER

FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
ALTERNATE :
GENERIC ROOF
SYSTEM

TOP OF CURB TO
DRAIN TO ONE SIDE

GASKETED FASTENERS

ELASTOMERIC COATING
FLASHING HEIGHT
8'' [200 mm] MIN.

1'' [25 mm] MIN.


THICKNESS OF SPF
ABOVE CANT

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

WOOD NAILER(S) - ROOF DECK -


PREPARE AS REQUIRED PREPARE AS REQUIRED

NOTES :
1. A ROOF SYSTEM DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED
TO THE ROOF DECK. ROOF SYSTEM DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. REFER TO APPROPRIATE SECTION OF LOW-SLOPE CONSTRUCTION DETAILS FOR FLASHING REQUIREMENTS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

ROOF SYSTEM DIVIDER

SPF-8S
2001 NOT DRAWN TO SCALE

1408
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WIDTH OF EQUIPMENT HEIGHT OF LEGS


FOAM STOP
UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
3/4'' 3/4''
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm] [18 mm] [18 mm]
MIN. MIN.
OVERHANG OVERHANG
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

SHEET METAL COVER

FLEXIBLE WATERPROOF
MEMBRANE CLOSURE ALTERNATE:
FLASHING HEIGHT
8'' [200 mm] MIN.

GASKETED FASTENER

EQUIPMENT LEG

NEOPRENE PAD

SET BOLTS IN SEALANT

ELASTOMERIC COATING

1'' [25 mm] MIN.


THICKNESS OF SPF
OVER BLOCKING

SPRAY POLYURETHANE
WOOD NAILER(S) FOAM (1'' [25 mm] MIN.
THICKNESS)

ROOF DECK -
NOTES : PREPARE AS REQUIRED

1. THIS DETAIL ALLOWS FOR ROOF SYSTEM MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS SUPPORT
IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE SPREAD ACROSS TWO OR
MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED OR WHERE THE LOAD CAN BE
CONCENTRATED OVER A COLUMN, DETAIL SPF-10 MAY BE PREFERRED. A MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL
CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT OF ROOFING AND FLASHING BETWEEN PARALLEL
SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM
OF SUPPORTED EQUIPMENT.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EQUIPMENT SUPPORT CURB.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EQUIPMENT SUPPORT CURB

SPF-9
2001 NOT DRAWN TO SCALE

1409
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]

24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]

48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

EQUIPMENT LEG
SET BOLTS IN
SEALANT

NEOPRENE PAD
OR SEALANT
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
GASKETED FASTENER

SHEET METAL COVER


FLASHING HEIGHT
8'' [200 mm] MIN.

PRIME WOOD

ELASTOMERIC COATING

1'' [25 mm] MIN.


THICKNESS OF SPF
ABOVE CANT

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
WOOD NAILER(S) - THICKNESS)
PREPARE AS REQUIRED
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ALLOWS FOR ROOF SYSTEM MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS SUPPORT
IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE SPREAD ACROSS TWO OR
MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED OR WHERE THE LOAD CAN BE
CONCENTRATED OVER A COLUMN, DETAIL SPF-10 MAY BE PREFERRED. A MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL
CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT OF ROOFING AND FLASHING BETWEEN PARALLEL
SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM
OF SUPPORTED EQUIPMENT.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EQUIPMENT SUPPORT CURB.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EQUIPMENT SUPPORT CURB

SPF-9S
2001 NOT DRAWN TO SCALE

1410
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL FRAME

HEIGHT-
SEE TABLE

SEE
DETAIL SPF-11
FOR FLASHING
OF SUPPORT LEGS

ROUND
PIPE COLUMN LE
AB
E ET
-S
H
I DT
W

WIDTH OF EQUIPMENT HEIGHT OF LEGS


UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]

NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL SPF-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED DIRECTLY
OVER COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE ADAPTED FOR OTHER
USES, SUCH AS SIGN SUPPORTS.

EQUIPMENT SUPPORT STAND

SPF-10
2001 NOT DRAWN TO SCALE

1411
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOR HEIGHT OF LEGS


SEE TABLE ON SPF-10

STRUCTURAL FRAME
(SEE SPF-10)

SUPPORT COLUMN

PRIME SUPPORT COLUMN


BEFORE APPLYING SPF

8'' [200 mm] MIN.


FLASHING HEIGHT

ELASTOMERIC COATING

FILL GAPS WITH SPF

SPRAY POLYURETHANE FOAM


(1'' [25 mm] MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

EQUIPMENT SUPPORT STAND


SUPPORT COLUMN
SPF-11
2001 NOT DRAWN TO SCALE

1412
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL FRAME
(SEE SPF-10)
FOR HEIGHT OF LEGS
SEE TABLE ON SPF-10

SUPPORT COLUMN

8'' [200 mm] MIN.


FLASHING HEIGHT

ELASTOMERIC COATING

FILL GAPS WITH SPF

SPRAY POLYURETHANE FOAM


(1'' [25 mm] MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

EQUIPMENT SUPPORT STAND


SUPPORT COLUMN
SPF-11S
2001 NOT DRAWN TO SCALE

1413
The NRCA Roofing and Waterproofing Manual—Fifth Edition

WOOD NAILER

FLASHING HEIGHT
SEALING MATERIAL
8'' [200 mm] MIN.

PREFABRICATED METAL CURB;


PRIME BEFORE APPLYING SPF

SHEET METAL REMOVABLE


COUNTERFLASHING
ELASTOMERIC
COATING

ALTERNATE
CURB BEARING
LOCATION FOR
HEAVY WEIGHT
LOADING SPRAY
CONDITIONS POLYURETHANE FOAM
(1'' [25 mm] MIN.
THICKNESS)
MECHANICAL UNIT, HOOD, ETC.
PRIME METAL
BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND
BEFORE APPLYING SPF
TOP OF CURB
ROOF DECK -
SEALING MATERIAL - MUST PREPARE AS REQUIRED
BE CONTINUOUS ON THE
PERIMETER
WOOD NAILER(S) -
1'' [25 mm] MINIMUM BELOW PREPARE AS REQUIRED
TOP OF CURB

WOOD NAILER FOAM STOP

SHEET METAL REMOVABLE NOTES :


COUNTERFLASHING
1. THE CURB, WOOD NAILER AND SEAL STRIP
ELASTOMERIC COATING ARE TO BE SUPPLIED BY THE CURB
MANUFACTURER.
SPRAY POLYURETHANE FOAM 2. WHEN POSSIBLE, THE MECHANICAL UNITS
SHOULD NOT BE SET UNTIL THE ROOF
PREFABRICATED METAL CURB SYSTEM HAS BEEN INSTALLED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
SPF-12
2001 NOT DRAWN TO SCALE

1414
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALING MATERIAL

PREFABRICATED METAL
CURB; PRIME BEFORE
APPLYING SPF

WOOD NAILER REMOVABLE


SHEET METAL
COUNTERFLASHING

PRIME METAL
BEFORE
APPLYING SPF
MIN. FLASHING HEIGHT

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
8'' [200 mm]

MIN. THICKNESS)

ELASTOMERIC
COATING

ALTERNATE
CURB BEARING WOOD NAILER(S) -
LOCATION FOR PREPARE AS REQUIRED
HEAVY WEIGHT
LOADING ROOF DECK -
CONDITIONS PREPARE AS REQUIRED

NOTES :
1. THE CURB, WOOD NAILER AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF SYSTEM HAS BEEN INSTALLED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS
(PREFABRICATED METAL CURB)
SPF-12S
2001 NOT DRAWN TO SCALE

1415
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

WOOD CURB -
PREPARE AS REQUIRED SEALING MATERIAL

SHEET METAL
FLASHING RECEIVER
FLASHING HEIGHT
8'' [200 mm] MIN.

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

NOTES : ROOF DECK -


PREPARE AS REQUIRED
1. SELF FLASHING EQUIPMENT DOES NOT REQUIRE COUNTERFLASHING.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
SPF-13
2001 NOT DRAWN TO SCALE

1416
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

SEALING MATERIAL

SHEET METAL
FLASHING RECEIVER

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FLASHING HEIGHT
8'' [200 mm] MIN.

REMOVABLE
SHEET METAL
COUNTERFLASHING

ELASTOMERIC COATING

SPRAY POLYURETHANE
WOOD CURB - FOAM (1'' [25 mm]
PREPARE AS REQUIRED MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. SELF FLASHING EQUIPMENT DOES NOT REQUIRE COUNTERFLASHING.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

RAISED CURB DETAIL FOR ROOFTOP AIR


HANDLING UNITS AND DUCTS (JOB SITE
CONSTRUCTED WOOD CURB)
SPF-13S
2001 NOT DRAWN TO SCALE

1417
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

DOUBLE DOME SKYLIGHT


(BY OTHERS)

SKYLIGHT FRAME
WITH WEEP HOLES
FLASHING HEIGHT
8'' [200 mm] MIN.

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

WOOD CURB -
PREPARE AS REQUIRED

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. IF UNIT COUNTERFLASHING EXTENDS 3'' OVER FLASHING, COUNTERFLASHING IS NOT REQUIRED.
2. FOR SCUTTLES, ADDITIONAL WEAR SURFACE SHOULD BE CONSIDERED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

SKYLIGHT, SCUTTLE AND SMOKE VENT

SPF-14
2001 NOT DRAWN TO SCALE

1418
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

DOUBLE DOME SKYLIGHT


(BY OTHERS)

SKYLIGHT FRAME
WITH WEEP HOLES

GASKETED FASTENERS
MINIMUM TWO

FLASHING HEIGHT
FASTENERS PER SIDE

8'' [200 mm] MIN.


REMOVABLE
SHEET METAL
COUNTERFLASHING

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

WOOD CURB -
PREPARE AS REQUIRED

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. IF UNIT COUNTERFLASHING EXTENDS 3'' OVER FLASHING, COUNTERFLASHING IS NOT REQUIRED.
2. FOR SCUTTLES, ADDITIONAL WEAR SURFACE SHOULD BE CONSIDERED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

SKYLIGHT, SCUTTLE AND SMOKE VENT

SPF-14S
2001 NOT DRAWN TO SCALE

1419
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP
STRUCTURAL MEMBER

METAL PLATE WELDED


TO STRUCTURAL
MEMBER; SEALED
WATERTIGHT

ALTERNATE :
INSULATE VOID TO
PREVENT CONDENSATION
FLASHING HEIGHT
8'' [200 mm] MIN.

FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

WOOD DECK -
PREPARE AS REQUIRED

ROOF CURB -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURB CONSTRUCTION
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOFING SYSTEM.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

STRUCTURAL MEMBER THROUGH


ROOF DECK
SPF-15
2001 NOT DRAWN TO SCALE

1420
The NRCA Roofing and Waterproofing Manual—Fifth Edition

STRUCTURAL MEMBER

METAL PLATE WELDED


TO STRUCTURAL FOAM STOP
MEMBER; SEALED
WATERTIGHT

OPTION :

INSULATE VOID TO
PREVENT CONDENSATION

FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE
SHEET METAL
FLASHING HEIGHT

COUNTERFLASHING
8'' [200 mm] MIN.

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

WOOD CURB -
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED CONSTRUCTION
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTRUBING THE ROOFING SYSTEM.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

STRUCTURAL MEMBER THROUGH


ROOF DECK
SPF-15S
2001 NOT DRAWN TO SCALE

1421
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
ENCLOSURE WITH
REMOVABLE TOP
CROSSBREAK OR SLOPE
FOR DRAINAGE

SEALANT

SHEET METAL OR
FLEX-TUBE COLLAR
8'' [200 mm] MIN.
FLASHING
HEIGHT

SLOPE PIPES AWAY


FROM HOOD

SHEET METAL FLASHING


RECEIVER
REMOVABLE SHEET
METAL COUNTERFLASHING

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

INSULATE VOID TO ELASTOMERIC COATING


PREVENT CONDENSATION SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MINIMUM 4'' [100 mm] MIN. THICKNESS)
CLEARANCE FROM PIPE
TO TOP OF CURB;
MINIMUM 2'' [50 mm]
BETWEEN PIPES
ROOF DECK -
PREPARE AS REQUIRED
WOOD CURB -
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING

SPF-16
2001 NOT DRAWN TO SCALE

1422
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL
ENCLOSURE WITH
REMOVABLE TOP
CROSSBREAK OR SLOPE
FOR DRAINAGE

SEALANT

SHEET METAL OR
FLEX-TUBE COLLAR
SLOPE PIPES AWAY
FROM HOOD

MINIMUM 4'' [100 mm]


CLEARANCE FROM PIPE
TO TOP OF CURB;
MINIMUM 2'' [50 mm]
BETWEEN PIPES
SHEET METAL FLASHING
RECEIVER
FLASHING HEIGHT
8'' [200 mm] MIN.

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

INSULATE VOID FOR


COLD STACKS
ROOF DECK -
WOOD CURB - PREPARE AS REQUIRED
PREPARE AS REQUIRED

NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

SHEET METAL ENCLOSURE FOR PIPING

SPF-16S
2001 NOT DRAWN TO SCALE

1423
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL OR
FLEX-TUBE COLLAR
SEALANT

SLOPE PIPES AWAY


FROM ENCLOSURE -
MINIMUM 2'' [50 mm]
BETWEEN PIPES

PIPES TO BE 8''
MINIMUM [200 mm]
ABOVE HORIZONTAL
SURFACE OF SPF

INSULATE VOID FOR ELASTOMERIC COATING


COLD STACKS SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
WOOD ENCLOSURE -
PREPRARE AS REQUIRED

ROOF DECK -
PREPRARE AS REQUIRED

SPF ENCLOSURE FOR PIPING

SPF-16A
2001 NOT DRAWN TO SCALE

1424
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL OR
FLEX-TUBE COLLAR
SEALANT

SLOPE PIPES AWAY


FROM ENCLOSURE -
MINIMUM 2'' [50 mm]
BETWEEN PIPES

PIPES TO BE 8'' MINIMUM


[200 mm] ABOVE
HORIZONTAL SURFACE
OF SPF

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

INSULATE VOID
FOR COLD STACKS
ROOF DECK -
WOOD ENCLOSURE - PREPARE AS REQUIRED
PREPARE AS REQUIRED

SPF ENCLOSURE FOR PIPING

SPF-16AS
2001 NOT DRAWN TO SCALE

1425
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

ALTERNATE :

TEMPERATURE
APPROPRIATE
8'' [200 mm] MIN.

ELASTOMERIC SEALANT
FLASHING
HEIGHT

DRAWBAND OR WELD
COVER TO STACK

INSULATE VOID FOR


COLD STACK

SHEET METAL COVER

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE

REMOVABLE
SHEET METAL
COUNTERFLASHING

ELASTOMERIC COATING

WOOD CURB -
PREPARE AS REQUIRED
VARIES
SPRAY POLYURETHANE
METAL OR GYPSUM FOAM (1'' [25 mm]
LINER IF REQUIRED MIN. THICKNESS)

ROOF DECK -
NOTES : PREPARE AS REQUIRED
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE METAL LINER, THE CLEARANCE NECESSARY BETWEEN THE LINER AND THE STACK,
AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL
HANDLED BY THE STACK.
3. IF COVER EXTENDS OVER FLASHING 3'', COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

ISOLATED STACK FLASHING

SPF-17
2001 NOT DRAWN TO SCALE

1426
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP
TEMPERATURE
APPROPRIATE
ELASTOMERIC
SEALANT

DRAWBAND OR
WELD COVER
TO STACK ALTERNATE :
METAL OR GYPSUM
LINER IF REQUIRED

INSULATE VOID FOR


COLD STACKS

SHEET METAL COVER

GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FLASHING HEIGHT
8'' [200 mm] MIN.

REMOVABLE
SHEET METAL
COUNTERFLASHING

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
VARIES
NOTES :
WOOD CURB -
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED. PREPARE AS REQUIRED
2. THE METAL LINER, THE CLEARANCE NECESSARY BETWEEN THE LINER AND THE STACK,
AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL
HANDLED BY THE STACK.
3. IF COVER EXTENDS OVER FLASHING 3'' [75 mm], COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

ISOLATED STACK FLASHING

SPF-17S
2001 NOT DRAWN TO SCALE

1427
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DECK SUPPORTED
PENETRATION

PREPARE PLUMBING
VENT STACK BEFORE
APPLYING SPF AS
REQUIRED

EXTEND ELASTOMERIC
COATING 2'' [50 mm]
ABOVE TERMINATION OF
SPRAY POLYURETHANE
FOAM

8'' [200 mm] MIN.


FLASHING HEIGHT

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. WHERE DIFFERENTIAL MOVEMENT IS A CONCERN, SEE DETAIL SPF-19.
2. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

DECK SUPPORTED PENETRATION

SPF-18
2001 NOT DRAWN TO SCALE

1428
The NRCA Roofing and Waterproofing Manual—Fifth Edition

NON-DECK SUPPORTED
PENETRATION
1/4'' [6 mm] MIN.
CLEARANCE BETWEEN SEALANT
RAIN COLLAR AND
DRAWBAND
FLASHING COLLAR

WATERTIGHT SHEET
METAL RAIN COLLAR
OVERLAPPING FLASHING
COLLAR BY RADIUS OF
3'' TO 4'' [75 TO 100 mm]

SHEET METAL FLASHING


COLLAR; PRIME BEFORE
APPLYING SPF

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

ROOF DECK

NOTES :
1. THIS DETAIL ACCOMMODATES INDEPENDENT DECK AND PENETRATION MOVEMENT.
2. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

NON-DECK SUPPORTED PENETRATION

SPF-19
2001 NOT DRAWN TO SCALE

1429
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ROOF DECK -
PREPARE AS REQUIRED

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS
V-GROOVE SPF AT CLAMPING
RING AND INSTALL COMPATIBLE
ELASTOMERIC SEALANT

CLAMPING RING

DRAIN STRAINER

DECK CLAMP

DRAIN BOWL

INSTALL SEALANT UNDER


CLAMPING RING BEFORE
SECURING TO BOWL

ELASTOMERIC COATING

NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.

ROOF DRAIN

SPF-20
2001 NOT DRAWN TO SCALE

1430
The NRCA Roofing and Waterproofing Manual—Fifth Edition

30'' (750 mm) SQUARE MINIMUM,


2-1/2 LB. TO 4 LB. (12 to 20 kg/m 2)
LEAD OR 16oz. (5 kg/m 2)
COPPER FLASHING SET ON ROOF
SUBSTRATE IN COMPATIBLE
ROOF CEMENT, PREPARE TOP
SURFACE AS REQUIRED.

DRAIN STRAINER
ALTERNATE :
V-GROOVE SPF AT CLAMPING
RING AND INSTALL COMPATIBLE
ELASTOMERIC SEALANT

ELASTOMERIC COATING; DOUBLE


THICKNESS AT DRAIN

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS

ROOF DECK -
PREPARE AS REQUIRED

INSTALL SEALANT UNDER


CLAMPING RING BEFORE
SECURING TO BOWL

CLAMPING RING

DECK CLAMP

DRAIN BOWL

NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.

ROOF DRAIN

SPF-20S
2001 NOT DRAWN TO SCALE

1431
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ROOF DECK -
PREPARE AS REQUIRED

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS

DECK CLAMP

DRAIN BOWL

APPLY SPF INTO


DRAIN BOWL - PREPARE AS
REQUIRED TO ENHANCE
ADHESION

AFFIX DRAIN STRAINER


TO ELASTOMERIC COATING
WITH DABS OF COMPATIBLE
SEALANT

ELASTOMERIC COATING

NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.

ALTERNATE ROOF DRAIN

SPF-20A
2001 NOT DRAWN TO SCALE

1432
The NRCA Roofing and Waterproofing Manual—Fifth Edition

AFFIX DRAIN STRAINER


TO ELASTOMERIC COATING
WITH DABS OF COMPATIBLE
SEALANT

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS

ELASTOMERIC COATING

ROOF DECK -
PREPARE AS REQUIRED

APPLY SPF INTO


DRAIN BOWL - PREPARE AS
REQUIRED TO ENHANCE
ADHESION

DECK CLAMP

DRAIN BOWL

NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.

ALTERNATE ROOF DRAIN

SPF-20AS
2001 NOT DRAWN TO SCALE

1433
The NRCA Roofing and Waterproofing Manual—Fifth Edition

V-GROOVE SPF AT
LOWER EDGE AND
INSTALL
ELASTOMERIC
SEALANT

ALTERNATE :

SEE DETAIL SPF-7 OR


SPF-7A FOR PARAPET
TERMINATIONS

PROPERLY PREPARE
METAL FLANGE
BEFORE APPLYING
SPF TO ENHANCE
ADHESION

EXTEND ELASTOMERIC
COATING ONTO SHEET
METAL SCUPPER LINER
2'' [50 mm] MIN.
PAST EDGE OF SPF

SHEET METAL
SCUPPER LINER

PARAPET WALL

ROOF DECK -
PREPARE AS REQUIRED

ELASTOMERIC
COATING

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

PRIMARY DRAINAGE SCUPPER


AT PARAPET WALL
SPF-21
2001 NOT DRAWN TO SCALE

1434
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ELASTOMERIC COATING
EXTEND ONTO SHEET
METAL SCUPPER LINER
2'' [50 mm] MIN.
PAST TERMINATION
OF SPF

SEALANT

PROPERLY PREPARE
METAL FLANGE
BEFORE APPLYING
SPF TO ENHANCE
ADHESION

SHEET METAL
SCUPPER LINER

1'' [25 mm] MINIMUM


THICKNESS OF SPF
ABOVE METAL
FLANGE

ROOF DECK -
PREPARE AS REQUIRED

PRIMARY DRAINAGE SCUPPER


AT PARAPET WALL
SPF-21S
2001 NOT DRAWN TO SCALE

1435
The NRCA Roofing and Waterproofing Manual—Fifth Edition

DOUBLE THICKNESS OF
ELASTOMERIC COATING
AT EDGE

ELASTOMERIC COATING

SHEET METAL EDGE


FLASHING APPROX. 4''
[100 mm] WIDE FLANGE;
FASTEN AT APPROX. 3''
TO 6'' [75 TO 150 mm] O.C.
STAGGERED CONTINUOUS SHEET
WOOD NAILER METAL CLOSURE
FASTENED APPROX.
SPRAY ALTERNATE : 18'' [450 mm] O.C.
POLYURETHANE
FOAM (1'' [25 mm] 1'' [25 mm] MINIMUM
MIN. THICKNESS) THICKNESS OF SPF
ABOVE METAL FLANGE

PROPERLY PREPARE
METAL FLANGE BEFORE
ROOF DECK - APPLYING SPF TO
PREPARE AS ENHANCE ADHESION
REQUIRED
V-GROOVE SPF AT
EDGE AND INSTALL
ELASTOMERIC SEALANT

OPTIONAL : GUTTER BRACKET


SEALANT SUPPORT

SECONDARY GUTTER SPACER


PROTECTION ALTERNATELY
SPACED FROM
SHEET METAL GUTTER BRACKETS

NOTES :
1. IN CLIMATES WHERE THE WINTER TERMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF TIME,
NRCA SUGGESTS USING SPF-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

GUTTER

SPF-22
2001 NOT DRAWN TO SCALE

1436
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL EDGE


FLASHING APPROX. 4''
[100 mm] WIDE FLANGE;
FASTEN AT APPROX. 3''
TO 6'' [75 TO 150 mm] O.C.
STAGGERED
DOUBLE THICKNESS OF
PROPERLY PREPARE
ELASTOMERIC COATING
METAL FLANGE BEFORE
12'' [300 mm] FROM
APPLYING SPF TO
PERIMETER
ENHANCE ADHESION

1'' [25 mm] MINIMUM ELASTOMERIC COATING


THICKNESS OF SPF
SPRAY POLYURETHANE
ABOVE METAL FLANGE
FOAM (1'' [25 mm]
MIN. THICKNESS)
V-GROOVE SPF AT
EDGE AND INSTALL
ELASTOMERIC SEALANT

GUTTER SPACER
ALTERNATELY
SPACED FROM
BRACKETS

ROOF DECK -
PREPARE AS REQUIRED

SECONDARY PROTECTION

SHEET METAL
GUTTER

GUTTER BRACKET
SUPPORT AT 12'' TO 36''
[300 mm TO 900 mm]
O.C. DEPENDING UPON
CONDITIONS

NOTES :
1. IN CLIMATES WHERE THE WINTER TERMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF TIME,
NRCA SUGGESTS USING SPF-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

GUTTER

SPF-22S
2001 NOT DRAWN TO SCALE

1437
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOAM STOP

STEEP SLOPE ROOF


COVERING NOT SHOWN

SHEET METAL
COUNTERFLASHING/EAVE
FLASHING

OPTION :
MIN. FLASHING
HEIGHT
8'' [200 mm]

ELASTOMERIC COATING

SPRAY POLYURETHANE
FOAM (1'' [25mm]
MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED
NOTES :

1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

LOW-SLOPE TO STEEP-SLOPE TRANSITION

SPF-23
2001 NOT DRAWN TO SCALE

1438
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM) APPROX. 3'' [75 mm]

FASTENERS AT APPROX. 3''


FLANGE APPROX. 4''
TO 6'' [75 TO 150 mm] O.C.
[100 mm] MIN. WIDE
STAGGERED

1/2'' [13 mm]


MIN. CLEARANCE
SHEET METAL
''GRAVEL STOP''

2'' [50 mm]


MIN. CLEARANCE
BELOW BLOCKING
1'' [25mm] MIN.

ADHERED FLASHING
MEMBRANE (EXTEND
APPROX. 3'' [75 mm]
BEYOND FLANGE)

FLEECE-BACKED
MEMBRANE

SPRAY POLYURETHANE
FOAM ADHESIVE

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

WOOD NAILERS
EXTEND FIELD SHEET
TO BELOW BLOCKING
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE EMBEDDED
OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

EMBEDDED EDGE METAL FLASHING


(GRAVEL-STOP)
SPF-2(FB)
2001
NOT DRAWN TO SCALE
1439
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS APPROX. 24''


[600 mm] O.C.

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

8'' [200 mm] MIN.


FLASHING HEIGHT

FLEECE-BACKED MEMBRANE

SPRAY POLYURETHANE
FOAM ADHESIVE

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR WALL-SUPPORTED


DECK
SPF-5(FB)
2001 NOT DRAWN TO SCALE

1440
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FASTENERS APPROX. 24''


[600 mm] O.C.

SHEET METAL REGLET

REMOVABLE SHEET METAL


COUNTERFLASHING

MEMBRANE SHEET CLOSURE


SECURED AND ADHERED TO
WALL

FASTENERS APPROX.
8'' [200 mm] O.C.
8'' [200 mm] MIN.
FLASHING HEIGHT
FLEXIBLE VAPOR RETARDER
WITH COMPRESSIBLE
INSULATION
FLEECE-BACKED MEMBRANE

SPRAY POLYURETHANE
FOAM ADHESIVE

WOOD CANT IF NECESSARY


TO BRACE CURB

WOOD NAILER(S) -
PREPARE AS REQUIRED

SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.

BASE FLASHING FOR NON-WALL-


SUPPORTED DECK
SPF-6(FB)
2001 NOT DRAWN TO SCALE

1441
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOR HEIGHT OF LEGS


SEE TABLE ON SPF-10

STRUCTURAL FRAME
SEE SPF-10

SEALANT

SEALANT (IF REQUIRED FOR


THE SPECIFIC SYSTEM)

FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)

FLEECE-BACKED MEMBRANE

SPRAY POLYURETHANE
FOAM ADHESIVE

FILL GAPS WITH SPF

SPRAY POLYURETHANE FOAM


(1'' [25 mm] MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

EQUIPMENT SUPPORT STAND LEG


(FIELD WRAP)
SPF-11(FB)
2001 NOT DRAWN TO SCALE

1442
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLUMBING VENT STACK

SEALANT

DRAWBAND

INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING

PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm] MIN.
HEIGHT)

SEALANT (IF REQUIRED


BY THE SPECIFIC
SYSTEM)
FLEECE-BACKED
MEMBRANE

SPRAY POLYURETHANE
FOAM ADHESIVE

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)

ROOF DECK -
PREPARE AS REQUIRED

NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
2. NRCA RECOMMENDS FLASHINGS BE 8'' (200 mm) HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.

PLUMBING VENT
(PREMANUFACTURED BOOT)
SPF-18(FB)
2001 NOT DRAWN TO SCALE

1443
The NRCA Roofing and Waterproofing Manual—Fifth Edition

ROOF DECK -
PREPARE AS REQUIRED

SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS
DRAIN STRAINER

CLAMPING RING

DECK CLAMP

ROUND CUT IN
FLEECE-BACKED MEMBRANE
EXTEND APPROX. 1'' [25 mm]
PAST CLAMPING RING

HOLE IN MEMBRANE SHOULD


BE LARGER THAN DRAIN
PIPE DIAMETER

DRAIN BOWL

REMOVE FLEECE FROM BACK OF


MEMBRANE UNDER CLAMPING RING

INSTALL SEALANT BETWEEN


DRAIN BOWL AND MEMBRANE

SPRAY POLYURETHANE
FOAM ADHESIVE

NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN TECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.

ROOF DRAIN

SPF-20(FB)
2001 NOT DRAWN TO SCALE

1444
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT 1

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL

UP TO 3'' FACE .040'' 20 oz. 24 ga. 24 ga. NOT REQUIRED

SAME GAUGE
UP TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL

SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL

ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

3/4'' MIN. FASTEN APPROX. 3'' TO 6'' O.C. STAGGERED, WITH


CORROSION RESISTANT, BARBED, ANNULAR RING
OR SCREW SHANK NAIL. LENGTH TO ACHIEVE
APPROX. 1 1/4'' PENETRATION INTO NAILER. FASTEN AT APPROX.
6'' O.C. WITH CORROSION
RESISTANT, BARBED,
ANNULAR RING, OR
SCREW SHANK NAIL.
LENGTH TO ACHIEVE
APPROX. 1 1/4''
''A'' APPROX. 4'' 3'' PENETRATION INTO
FLANGE NAILER.
FASTEN NEAR LOWER
BRAKE FOR INCREASED
3/4'' UPLIFT RESISTANCE.

3/4''

2
''A'' TYPE PROFILE CLEAT

NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12 FEET ALLOW A 1/4'' GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL FASCIA EDGES


FOR SPRAY POLYURETHANE FOAM
SPF - TABLE 1
2001 NOT DRAWN TO SCALE

1445
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT 1

GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL

UP TO 2
1.02 mm 6.10 kg/m .64 mm .61 mm NOT REQUIRED
75 mm FACE
UP TO 2 SAME GAUGE
.81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL
75 mm FACE

75 mm TO 2
SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL

150 mm TO ONE GAUGE


2 HEAVIER THAN
200 mm FACE 1.27 mm 6.10 kg/m .64 mm .61 mm
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
200 mm TO STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
375 mm FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL

1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT

20 mm MIN. FASTEN APPROX. 75 mm TO 150 mm O.C. STAGGERED, WITH


CORROSION RESISTANT, BARBED, ANNULAR RING
OR SCREW SHANK NAIL. LENGTH TO ACHIEVE
APPROX. 1 1/4'' PENETRATION INTO NAILER. FASTEN AT APPROX.
150 mm O.C. WITH
CORROSION RESISTANT,
BARBED, ANNULAR RING,
OR SCREW SHANK NAIL.
LENGTH TO ACHIEVE
APPROX. 32 mm
''A'' APPROX. 100 mm 75 mm PENETRATION INTO
FLANGE NAILER.
FASTEN NEAR LOWER
BRAKE FOR INCREASED
20 mm UPLIFT RESISTANCE.

20 mm

2
''A'' TYPE PROFILE CLEAT

NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 4 m. ALLOW A 6 mm GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.

GUIDE FOR SHEET METAL FASCIA EDGES


FOR SPRAY POLYURETHANE FOAM

SPF - TABLE 1 (METRIC)


2001 NOT DRAWN TO SCALE

1446
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SHEET METAL REGLET

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

OPTIONAL: 2'' [50 mm] WIDE


CLIP APPROX. 30'' [750 mm]
O.C. - 2 FASTENERS
PER CLIP
SPF ROOF SYSTEM

THROUGH-WALL REGLET AND COUNTERFLASHING


A

LEAD WEDGE AT APPROX.


24'' [600 mm] O.C.

APPROPRIATE SEALANT

FRICTION FIT SHEET METAL


REGLET INSERT IN RAGGLE
JOINT

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

OPTIONAL: 2'' [50 mm] WIDE


CLIP APPROX. 30'' [750 mm]
O.C. - 2 FASTENERS
PER CLIP

SPF ROOF SYSTEM

INSERT REGLET AND COUNTERFLASHING


B

OPTIONS FOR TERMINATION OF WALL


COUNTERFLASHINGS
SPF -TABLE 2.1
2001 NOT DRAWN TO SCALE

1447
The NRCA Roofing and Waterproofing Manual—Fifth Edition

APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
APPROPRIATE FASTENERS
24'' [600 mm] O.C.

3'' [75 mm] LAP AT JOINTS

REMOVABLE SHEET METAL


COUNTERFLASHING

OPTIONAL: 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

SPF ROOF SYSTEM

OPTIONAL: SEALANT OR
ELASTOMERIC TAPE

TWO PIECE SURFACE MOUNTED REGLET AND


COUNTERFLASHING
C
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.

ONE-PIECE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINT

OPTIONAL: 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

SPF ROOF SYSTEM

OPTIONAL: SEALANT OR
ELASTOMERIC TAPE

ONE-PIECE SURFACE MOUNTED COUNTERFLASHING


D

OPTIONS FOR TERMINATION OF WALL


COUNTERFLASHINGS
SPF -TABLE 2.2
2001 NOT DRAWN TO SCALE

1448
The NRCA Roofing and Waterproofing Manual—Fifth Edition

BUILDING PAPER
(IF REQUIRED)
WALL CLADDING

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

SHEET METAL REGLET

APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.

3'' [75 mm] LAP WITH BEAD


OF SEALANT

REMOVABLE SHEET METAL


COUNTERFLASHING

3'' [75 mm] LAP AT JOINTS

SPF ROOF SYSTEM

OPTIONAL: 2'' [50 mm]


WIDE CLIP APPROX.
30'' [750 mm] O.C. -
2 FASTENERS PER CLIP

EMBEDDED REGLET AND COUNTERFLASHING


E

OPTIONS FOR TERMINATION OF WALL


COUNTERFLASHING
SPF - TABLE 2.3
2001 NOT DRAWN TO SCALE

1449
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTINUOUS CLEATS

' OPTIONAL METAL


3/4' FLANGE EXTENSION
OX.
PR
AP

4''
. 3/
OX
PR
TYPICAL AP
CLEAT ENGAGEMENT

APPROPRIATE FASTENERS
FASTENED APPROX. 6''
[150 mm] O.C.

CONTINUOUS CLEATS EACH SIDE


A
OPTIONAL METAL FLANGE
EXTENSION

. CONTINUOUS CLEAT
M IN
m] APPROPRIATE FASTENERS
[5 0m
2'' FASTENED APPROX. 6''
[150 mm] O.C.

2'' [50 mm] WIDE ISOLATED


3/4

CLIPS WITH APPROPRIATE


'' M

FASTENERS APPROX. 12''


IN.

COPING CAP [300 mm] O.C. DEPENDING


HEMMED EDGE
ON WIND ZONE AND
LOCAL CLIMATES
TYPICAL
CLIP ENGAGEMENT

CONTINUOUS CLEAT AND ISOLATED CLIPS


B
OPTIONAL METAL FLANGE
CONTINUOUS EXTENSION
CLEAT
GASKETED FASTENERS
AT APPROX. 18''
APPROPRIATE [450 mm] O.C. DEPENDING
FASTENERS ON WIND ZONE AND
FASTENED LOCAL CONDITIONS
APPROX. 6''
[150 mm] O.C.

CONTINUOUS CLEAT AND GASKETED FASTENERS


C

GUIDE FOR SHEET METAL PARAPET CAP


(COPING)
SPF - TABLE 3
2001 NOT DRAWN TO SCALE

1450
The NRCA Roofing and Waterproofing Manual—Fifth Edition

2'-
0'
MI ' [600
NI
MU mm
M ]

[ 12
CL 300 ''
MI EAR mm]
NI AN
MU C
M E 12
[
CL 300 ''
MI EAR mm] 12
''
m] CE
NI AN
MU C
0 0 m AN
M E 12 [3 EA R
[
CL 300 '' CL
m
MI EAR m]
NI AN
MU C
M E

GUIDE FOR CLEARANCES BETWEEN


PIPES / WALLS / CURBES
SPF - TABLE 4
2001 NOT DRAWN TO SCALE

1451
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SUMPED
ROOF DRAIN

CURBED
PENETRATION

SL
OP
E

SADDLE CRICKET

SLO
PE

SUMPED
ROOF DRAIN

NOTES :
1. SADDLES SHOULD BE LOCATED IN VALLEYS BETWEEN ROOF DRAINS AND CRICKETS ON THE HIGH SIDE OF CURBS.
2. LOCATE ROOF DRAINS AT POINTS OF MAXIMUM DECK DEFLECTION / LOW AREAS FOR DRAINAGE.

GUIDE FOR CRICKETS AND SADDLES

SPF - TABLE 5
2001 NOT DRAWN TO SCALE

1452
The NRCA Roofing and Waterproofing Manual—Fifth Edition

RAISED
PERIMETER EDGE

CURBED
PENETRATION

CRICKET

THROUGH EDGE
SCUPPER
SL
OP
E

SHEET METAL
CONDUCTOR
HEAD

SL
OP
E

CRICKET

NOTES :
1. SADDLE SHOULD BE LOCATED BETWEEN THROUGH-EDGE OR WALL SCUPPERS AND CRICKETS ON THE HIGH SIDE OF CURBS
2. RAISED PERIMETER EDGES WHERE TAPERED CRICKETS ARE USED NECESSITATE THE SPECIFICATION OF RELATIVELY WIDE
(TALL) DIMENSIONAL LUMBER OR THE ERECTION OF FRAMED WALLS.

GUIDE FOR EDGE SCUPPERS WITH


TAPERED SADDLES
SPF - TABLE 6
2001 NOT DRAWN TO SCALE

1453
The NRCA Roofing and Waterproofing Manual—Fifth Edition

GEOCOMPOSITE NON-PRESSURE
OR PROTECTION SLAB-ON GRADE
COURSE
VAPOR
RETARDER
WATERPROOF
MEMBRANE AGGREGATE
UNDERLAYMENT

FOOTING

FILLET - IF
REQUIRED FOR
MEMBRANE TYPE
FILTER FABRIC

PERFORATED DRAIN
PIPE SET IN
AGGREGATE BED

FOUNDATION WALL WITH HYDROSTATIC


PRESSURE RELIEF SYSTEM
WP-1
2001 NOT DRAWN TO SCALE

1454
The NRCA Roofing and Waterproofing Manual—Fifth Edition

NON-PRESSURE
CONCRETE
SLAB-ON-GRADE

GEOCOMPOSITE
OR PROTECTION VAPOR RETARDER
COURSE
AGGREGATE
FILLET - IF UNDERLAYMENT
REQUIRED FOR
MEMBRANE TYPE

WATERPROOF
MEMBRANE

FOOTING
PERFORATED DRAIN
PIPE SET IN
AGGREGATE BED

FILTER FABRIC

FOUNDATION WALL WITH HYDROSTATIC


PRESSURE RELIEF SYSTEM
WP-1S
2001 NOT DRAWN TO SCALE

1455
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PROTECTION COURSE FOUNDATION


WALL

WATERSTOP
WATERPROOF (OPTIONAL)
MEMBRANE

PRESSURE MAT
FILLET - IF REQUIRED SLAB
FOR MEMBRANE
TYPE

PROTECTION
COURSE

WORK SLAB

ALTERNATE SLAB EDGE FLASHING

FOUNDATION WALL AND PRESSURE MAT


SLAB-ON-GRADE
WP-2
2001 NOT DRAWN TO SCALE

1456
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PROTECTION
COURSE FOUNDATION WALL

WATERPROOF WATERSTOP
MEMBRANE (OPTIONAL)

FILLET - IF PRESSURE MAT SLAB


REQUIRED FOR
MEMBRANE TYPE
PROTECTION COURSE

WORK SLAB

ALTERNATE SLAB EDGE FLASHING

FOUNDATION WALL AND PRESSURE MAT


SLAB-ON-GRADE
WP-2S
2001 NOT DRAWN TO SCALE

1457
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTROL JOINT WITH


WATERPROOFING CAST-IN-PLACE RECESS
FILLED WITH
CEMENTITIOUS OR
METALLIC GROUT
CONCRETE
TOPPING SLAB

FOUNDATION CRACK
WITH V-SHAPED
GROOVE FILLED WITH
CEMENTITIOUS OR
METALLIC GROUT

CEMENTITIOUS OR
METALLIC GROUT FILLET

PRESSURE MAT SLAB-


ON-GRADE

CEMENTITIOUS OR
METALLIC WATERPROOFING

ALTERNATE CORNER DETAIL ALTERNATE CORNER DETAIL FOR


CRYSTALLINE WATERPROOFING

NEGATIVE SIDE WATERPROOFING

WP-3
2001 NOT DRAWN TO SCALE

1458
The NRCA Roofing and Waterproofing Manual—Fifth Edition

CONTROL JOINT WITH


WITH CAST-IN-PLACE
RECESS FILLED WITH
CEMENTITIOUS OR
METALLIC GROUT

FOUNDATION CRACK
WITH V-SHAPED
GROOVE FILLED WITH
CEMENTITIOUS OR
METALLIC GROUT

CEMENTITIOUS OR
METALLIC GROUT
FILLET

CONCRETE TOPPING
SLAB
WATERPROOFING

PRESSURE MAT
SLAB-ON-GRADE

CEMENTITIOUS OR METALLIC
WATERPROOFING

ALTERNATE CORNER DETAIL ALTERNATE CORNER DETAIL FOR


CRYSTALLINE WATERPROOFING

NEGATIVE SIDE WATERPROOFING

WP-3S
2001 NOT DRAWN TO SCALE

1459
The NRCA Roofing and Waterproofing Manual—Fifth Edition

EXTEND
WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
GRADE ABOVE GRADE

FILTER FABRIC FOUNDATION


WALL
GEOCOMPOSITE
OR PROTECTION
FILLET - IF
COURSE
REQUIRED FOR
MEMBRANE TYPE
WATERPROOF
MEMBRANE

NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.

FOUNDATION WALL BRICK LEDGE

2001 NOT DRAWN TO SCALE


WP-4
1460
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOUNDATION
WALL

GRADE
EXTEND
WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
ABOVE GRADE

FILTER FABRIC FILLET - IF


REQUIRED FOR
GEOCOMPOSITE OR MEMBRANE TYPE
PROTECTION
COURSE

WATERPROOF
MEMBRANE

NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.

FOUNDATION WALL BRICK LEDGE

WP-4S
2001 NOT DRAWN TO SCALE

1461
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

EXTEND
WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
ABOVE GRADE

GRADE

COUNTERFLASHING

FILTER FABRIC

GEOCOMPOSITE OR
PROTECTION

WATERPROOF
MEMBRANE

NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.

FOUNDATION WALL COUNTERFLASHING


AT GRADE
WP-5
2001 NOT DRAWN TO SCALE

1462
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

COUNTERFLASHING
APPROPRIATE FOR
MASONRY
CONSTRUCTION EXTEND
TYPE WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
GRADE ABOVE GRADE

WATERPROOF
MEMBRANE

GEOCOMPOSITE OR
PROTECTION COURSE

FILTER FABRIC

NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.

FOUNDATION WALL COUNTERFLASHING


AT GRADE
WP-5S
2001 NOT DRAWN TO SCALE

1463
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

COUNTERFLASHING

EARTH FILL

FILTER FABRIC

GEOCOMPOSITE OR
PROTECTION COURSE

WATERPROOF
MEMBRANE

CONCRETE FILL WEEP TUBE


PLACED AT BOTTOM (SEE BELOW).
OF PLANTER EXTEND 1/2''
[13 mm] PAST
FACE OF
COMPRESSIBLE
MASONRY.
EXPANSION STRIP AND
BACKER ROD OPTIONAL

FINISHED DECK
WEAR COURSE

GEOCOMPOSITE OR
PROTECTION COURSE

WEEP TUBE FLANGE


STRIPPED INTO
WATERPROOF
MEMBRANE
NOTES :
1. WEEP TUBE SIZE AND SPACING DETERMINED BY PLANTER SIZE AND LOCATION (BY OTHERS).

BUILT-IN PLANTER WITH WEEP DRAINAGE

WP-6
2001 NOT DRAWN TO SCALE

1464
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT
COUNTERFLASHING -
EXTEND OVER
GEOCOMPOSITE OR
PROTECTION COURSE

EARTH FILL - MIN. PLANTER WALL


OF 3'' [75 mm]
BELOW TOP OF
WATERPROOF
WEEP TUBE (SEE
MEMBRANE
BELOW). EXTEND 1/2''
FILTER FABRIC [13 mm] PAST FACE
OF MASONRY
GEOCOMPOSITE OR
PROTECTION COURSE
SEALANT AROUND
WATERPROOF TUBE
MEMBRANE
COMPRESSIBLE
EXPANSION STRIP
WITH SEALANT AND
BACKER ROD
OPTIONAL
FINISHED DECK
WEAR COURSE

GEOCOMPOSITE OR
PROTECTION COURSE

WATERPROOF
MEMBRANE
CONCRETE FILL
PLACED AT BOTTOM STRUCTURAL
OF PLANTER DECK

GEOCOMPOSITE OR PLANTER WALL


PROTECTION COURSE
FLANGE SOLDERED
TO TUBE
WEEP TUBE FLANGE
STRIPPED INTO 1/2'' [13 mm] MIN.
WATERPROOF DIAMETER WEEP
MEMBRANE TUBE
WATERPROOF
PLANTER BOX MEMBRANE
CONCRETE FILL

NOTES :
1. WEEP TUBE SIZE AND SPACING DETERMINED BY PLANTER SIZE AND LOCATION (BY OTHERS).

BUILT-IN PLANTER WITH WEEP DRAINAGE

WP-6S
2001 NOT DRAWN TO SCALE

1465
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

COUNTERFLASHING

EARTH FILL

FILTER FABRIC

GEOCOMPOSITE OR
PROTECTION COURSE

WATERPROOF
MEMBRANE

PLANTER DRAIN

PLANTER WALL

COMPRESSIBLE EXPANSION
STRIP AND BACKER ROD
OPTIONAL

WATERPROOF
MEMBRANE

FINISHED DECK WEAR SURFACE

GEOCOMPOSITE OR
PROTECTION COURSE

BUILT-IN PLANTER WITH INTERIOR DRAINAGE

WP-7
2001 NOT DRAWN TO SCALE

1466
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT

COUNTERFLASHING -
EXTEND OVER
GEOCOMPOSITE
PROTECTION COURSE

EARTH FILL - MIN. OF


3'' [75 mm] BELOW TOP
OF WATERPROOF
PLANTER WALL
MEMBRANE
COMPRESSIBLE
FILTER FABRIC EXPANSION
STRIP AND
GEOCOMPOSITE OR BACKER ROD
PROTECTION COURSE OPTIONAL

WATERPROOF FINISHED DECK


MEMBRANE WEAR COURSE

EARTH FILL GEOCOMPOSITE


OR PROTECTION
PLANTER COURSE
DRAIN

WATERPROOF
MEMBRANE

STRUCTURAL
DECK

BUILT-IN PLANTER WITH INTERIOR DRAINAGE

WP-7S
2001 NOT DRAWN TO SCALE

1467
The NRCA Roofing and Waterproofing Manual—Fifth Edition

SEALANT BETWEEN
PIPE AND SLEEVE
FOUNDATION WALL AS REQUIRED

WATERPROOF
MEMBRANE PIPE PENETRATION

FILTER FABRIC

GEOCOMPOSITE OR
PROTECTION COURSE

SEALANT BETWEEN
SLEEVE AND WALL

CLAMPING RING
(OPTIONAL)

BACKFILL

PIPE SLEEVE
EXTENDING MIN.
4'' [100 mm] BEYOND
EXTERIOR OF WALL

FILLET IF REQUIRED
FOR MEMBRANE
TYPE

FOUNDATION WALL PENETRATION

WP-8
2001 NOT DRAWN TO SCALE

1468
The NRCA Roofing and Waterproofing Manual—Fifth Edition

FOUNDATION WALL
WATERPROOF
MEMBRANE

FILLET IF REQUIRED FOR


MEMBRANE TYPE SEALANT BETWEEN
SLEEVE AND WALL
CLAMPING RING
(OPTIONAL) SEALANT BETWEEN
PIPE AND SLEEVE
AS REQUIRED

PIPE PENETRATION
PIPE SLEEVE EXTENDING
MIN. 4'' [100 mm] BEYOND
BEYOND EXTERIOR
FACE OF WALL

FILTER FABRIC

GEOCOMPOSITE OR
PROTECTION COURSE

FOUNDATION WALL PENETRATION

WP-8S
2001 NOT DRAWN TO SCALE

1469
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLAZA DECK DRAIN

CAST-IN-PLACE
CONCRETE WEAR
SURFACE

FILTER FABRIC

RIGID INSULATION

GEOCOMPOSITE
DRAINAGE COURSE
(OPTIONAL)
WATERPROOF
MEMBRANE -
EXTEND UNDER
CLAMPING STRAINER

STRUCTURAL DECK

PLAZA DECK DRAIN - CONCRETE


WEAR SURFACE
WP-9
2001 NOT DRAWN TO SCALE

1470
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PLAZA DECK DRAIN

CAST-IN-PLACE CONCRETE
WEAR SURFACE

FILTER FABRIC

RIGID INSULATION

GEOCOMPOSITE DRAINAGE
COURSE (OPTIONAL)

WATERPROOF MEMBRANE-
EXTEND UNDER CLAMPING
STRAINER

STRUCTURAL DECK

PLAZA DECK DRAIN - CONCRETE


WEAR SURFACE
WP-9S
2001 NOT DRAWN TO SCALE

1471
The NRCA Roofing and Waterproofing Manual—Fifth Edition

PRECAST CONCRETE
PAVERS OR STONE -
MARK PAVER OVER
DRAIN TO IDENTIFY
LOCATION

PAVER PEDESTAL

LARGE SUMP DRAIN


WITH SEDIMENT BUCKET

RIGID INSULATION

FILTER FABRIC

GEOCOMPOSITE
DRAINAGE COURSE
(OPTIONAL)

WATERPROOF
MEMBRANE -
EXTEND MEMBRANE
UNDER DRAIN
CLAMPING RING

PLAZA DECK DRAIN - PAVER


WEAR SURFACE
WP-10
2001 NOT DRAWN TO SCALE

1472
The NRCA Roofing and Waterproofing Manual—Fifth Edition

LARGE SUMP DRAIN


WITH SEDIMENT BUCKET

PRECAST CONCRETE
PAVERS OR STONE -
MARK PAVER OVER
DRAIN TO IDENTIFY
DRAIN LOCATION

PAVER PEDESTAL

RIGID INSULATION

FILTER FABRIC

GEOCOMPOSITE
DRAINAGE COURSE
(OPTIONAL)

WATERPROOF
MEMBRANE - EXTEND
UNDER DRAIN
CLAMPING RING

STRUCTURAL DECK

PLAZA DECK DRAIN - PAVER


WEAR SURFACE
WP-10S
2001 NOT DRAWN TO SCALE

1473