Fifth Edition
Volume 4
RETURN TO MAIN
Published by the National Roofing Contractors Association
10255 W. Higgins Road, Suite 600, Rosemont, Ill. 60018-5607
Contents 1013
Manual
Fifth Edition
The NRCA Roofing and Waterproofing Manual—Fifth Edition
Contents 1017
The NRCA Roofing and Waterproofing Manual—Fifth Edition
1018 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MB-12S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Prefabricated Metal Curb) ..............................................................................................1104
MB-13 Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1105
MB-13S Raised Curb Detail for Rooftop Air Handling Units and Ducts
(Job Site Constructed Wood Curb) ...................................................................................1106
MB-14 Skylight, Scuttle, and Smoke Vent ..........................................................................1107
MB-14S Skylight, Scuttle, and Smoke Vent ........................................................................1108
MB-15 Structural Member Through Roof Deck ..................................................................1109
MB-15S Structural Member Through Roof Deck.................................................................1110
MB-16 Sheet Metal Enclosure for Piping Through Roof Deck ................................................1111
MB-16S Sheet Metal Enclosure for Piping Through Roof Deck ..............................................1112
MB-17 Isolated Stack Flashing (Hot or Cold) ......................................................................1113
MB-17S Isolated Stack Flashing (Hot or Cold).....................................................................1114
MB-17A Isolated Stack Flashing (Hot or Cold).....................................................................1115
MB-17AS Isolated Stack Flashing (Hot or Cold)...................................................................1116
MB-18 Plumbing Vent.....................................................................................................1117
MB-18S Plumbing Vent...................................................................................................1118
MB-19 Penetration Pocket ..............................................................................................1119
MB-19S Penetration Pocket ............................................................................................1120
MB-20 Roof Drain..........................................................................................................1121
MB-20S Roof Drain........................................................................................................1122
MB-20A Roof Drain - Alternate Flashing ............................................................................1123
MB-20AS Roof Drain - Alternate Flashing ..........................................................................1124
MB-21 Scupper Through Raised Perimeter Edge ................................................................1125
MB-21S Scupper Through Raised Perimeter Edge ..............................................................1126
MB-22 Gutter ...............................................................................................................1127
MB-22S Gutter..............................................................................................................1128
Thermoplastic Single-ply Roofing
TP-1 Metal Parapet Cap (Coping) and Base Flashing ...........................................................1129
TP-1S Metal Parapet Cap (Coping) and Base Flashing..........................................................1130
TP-2 Raised Perimeter Edge with Metal Flashing (Fascia Cap)...............................................1131
TP-2S Raised Perimeter Edge with Metal Flashing (Fascia Cap) .............................................1132
TP-3 Embedded Edge Metal Flashing (Gravel-stop)...............................................................1133
TP-3S Embedded Edge Metal Flashing (Gravel-stop) .............................................................1134
TP-3A Draining Perimeter Edge........................................................................................1135
TP-3AS Draining Perimeter Edge ......................................................................................1136
TP-3B Joint Detail for Membrane Coated Embedded Edge Metal Flashing (Gravel-stop) .............1137
TP-3C Joint Detail for Membrane Coated Draining Perimeter Edge ........................................1138
TP-4 Surface-mounted Counterflashing for Concrete Walls ...................................................1139
TP-4S Surface-mounted Counterflashing for Concrete Walls .................................................1140
TP-5 Base Flashing for Wall-supported Deck ......................................................................1141
Contents 1019
The NRCA Roofing and Waterproofing Manual—Fifth Edition
1020 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition
Contents 1021
The NRCA Roofing and Waterproofing Manual—Fifth Edition
Steep-slope Roofing
Asphalt Shingles
ASPH-1 Apron Flashing...................................................................................................1266
ASPH-2 Sidewall Flashing ................................................................................................1267
ASPH-3 Backer Flashing .................................................................................................1268
ASPH-3A Backer Flashing ...............................................................................................1269
ASPH-4 Eave and Rake Flashing .......................................................................................1270
ASPH-5 Eave and Rake Flashing with Gutter.......................................................................1271
ASPH-6 Open Valley........................................................................................................1272
ASPH-7 Closed Cut Valley ................................................................................................1273
ASPH-8 Pipe Penetration ................................................................................................1274
Clay and Concrete Tile
TILE-1 Apron Flashing .....................................................................................................1275
TILE-2 Sidewall Flashing ..................................................................................................1276
TILE-3 Backer Flashing....................................................................................................1277
TILE-3A Backer Flashing..................................................................................................1278
TILE-4 Eave Flashing .......................................................................................................1279
TILE-5 Rake Edge Flashing ...............................................................................................1280
TILE-6 Open Valley ..........................................................................................................1281
TILE-7 Two-Piece Pipe Flashing .........................................................................................1282
TILE-7A Pipe Penetration.................................................................................................1283
Slate
SLATE-1 Apron Flashing ..................................................................................................1284
SLATE-2 Sidewall Flashing ...............................................................................................1285
SLATE-3 Backer Flashing.................................................................................................1286
SLATE-3A Backer Flashing...............................................................................................1287
Contents 1023
The NRCA Roofing and Waterproofing Manual—Fifth Edition
1024 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition
Contents 1025
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SPF-based Roofing
SPF-1 Metal Parapet Cap (Coping) ...................................................................................1389
SPF-1S Metal Parapet Cap (Coping) ..................................................................................1390
SPF-2 Perimeter Edge Metal Flashing with Sealant (Foam Stop) ............................................1391
SPF-2S Perimeter Edge Metal Flashing with Sealant (Foam Stop) ..........................................1392
SPF-3 Perimeter Edge Metal Flashing (Foam Stop) .............................................................1393
SPF-3S Perimeter Edge Metal Flashing (Foam Stop) ............................................................1394
SPF-4 Surface-Mount Counterflashing ..............................................................................1395
SPF-4S Surface-Mount Counterflashing .............................................................................1396
SPF-5 Base Flashing for Wall-Supported Deck ....................................................................1397
SPF-5S Base Flashing for Wall-Supported Deck ..................................................................1398
1026 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition
Contents 1027
The NRCA Roofing and Waterproofing Manual—Fifth Edition
Waterproofing
WP-1 Foundation Wall with Hydrostatic Pressure Relief System............................................1454
WP-1S Foundation Wall with Hydrostatic Pressure Relief System ..........................................1455
WP-2 Foundation Wall and Pressure Mat Slab-on-grade ......................................................1456
WP-2S Foundation Wall and Pressure Mat Slab-on-grade ....................................................1457
WP-3 Negative Side Waterproofing ..................................................................................1458
WP-3S Negative Side Waterproofing ................................................................................1459
WP-4 Foundation Wall Brick Ledge...................................................................................1460
WP-4S Foundation Wall Brick Ledge .................................................................................1461
WP-5 Foundation Wall Counterflashing at Grade.................................................................1462
WP-5S Foundation Wall Counterflashing at Grade...............................................................1463
WP-6 Built-In Planter with Weep Drainage .........................................................................1464
WP-6S Built-In Planter with Weep Drainage .......................................................................1465
WP-7 Built-In Planter with Interior Drainage .......................................................................1466
WP-7S Built-In Planter with Interior Drainage .....................................................................1467
WP-8 Foundation Wall Penetration ...................................................................................1468
WP-8S Foundation Wall Penetration .................................................................................1469
WP-9 Plaza Deck Drain - Concrete Wear Surface ...............................................................1470
WP-9S Plaza Deck Drain - Concrete Wear Surface .............................................................1471
WP-10 Plaza Deck Drain - Paver Wear Surface..................................................................1472
WP-10S Plaza Deck Drain - Paver Wear Surface ................................................................1473
1028 Contents
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
CONTINUOUS SHIM
WOOD NAILER
PRIME SURFACE AS
REQUIRED
OPTIONAL: EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT
AP
[10 PRO
0 m X. 4
m] ''
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL BUR-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET MEMBRANE LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1029
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING FEATHERED
AT FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL BUR-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET MEMBRANE LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1030
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
AP
[10 PRO
BELOW BLOCKING
0 m X. 4
m] ''
1'' [25 mm] MIN.
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
FASTENED PER TABLE 1
NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1031
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MULTIPLE-PLY MEMBRANE
BASE FLASHING FEATHERED
AT FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
BELOW BLOCKING
1'' [25 mm] MIN.
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
NOTES : (FASTENED PER TABLE 1)
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1032
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MULTIPLE-PLY
MEMBRANE STRIPPING FLANGE APPROX.
FEATHERED AT FIELD 4'' [100 mm] WIDE
OF ROOF 2" [50 mm]
MIN.
FASTENERS 3'' TO 6'' 2" [50 mm]
[75 TO 150 mm] O.C., MIN.
STAGGERED
BELOW BLOCKING
1'' [25 mm] MIN.
COVERBOARD INSULATION
AND THERMAL
INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
NOTES : (FASTENED PER TABLE 1)
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE
EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE. (SEE BUR-2 FOR THE PREFERRED PERIMETER
CONSTRUCTION.)
2. WHEN USING A GRANULE CAP SHEET AS SURFACING, THE METAL FLANGE AND ASSOCIATED
STRIPPING PLIES CAN BE INSTALLED BENEATH THE CAP SHEET.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1033
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FELT ENVELOPE
(FOR COAL TAR AND
ASPHALT TYPES I AND II)
FASTENERS AT APPROX.
3'' TO 6'' [75 TO 150 mm]
O.C., STAGGERED
MULTIPLE-PLY
MEMBRANE STRIPPING
FEATHERED AT
FIELD OF ROOF
BELOW BLOCKING
1'' [25 mm] MIN.
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
AND THERMAL
INSULATION
ROOF DECK
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE
EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE. (SEE BUR-1 FOR THE PREFERRED PERIMETER
CONSTRUCTION.)
2. WHEN USING A GRANULE CAP SHEET AS SURFACING, THE METAL FLANGE AND ASSOCIATED
STRIPPING PLIES CAN BE INSTALLED BENEATH THE CAP SHEET.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND
SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1034
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SMOOTH CONCRETE
CONCRETE FASTENERS
OPTIONAL : COMPRESSIBLE
ELASTOMETRIC SEALANT OR
TAPE TO SPAN IRREGULARITIES
AP OPTIONAL :
[10 PRO EXTENDED FIELD PLIES
0 m X. 4
m] '' ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF ROOF
CANT
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
BUR-4
2001 NOT DRAWN TO SCALE
1035
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SMOOTH CONCRETE
FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES : CANT
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. COUNTERFLASHING DETAIL MAY BE A TWO-PIECE REGLET AND COUNTERFLASHING (SEE TABLE 2 FOR
ALTERNATE SHEET METAL COUNTERFLASHING).
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
BUR-4S
2001 NOT DRAWN TO SCALE
1036
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
THERMAL INSULATION
ROOF DECK
NOTES : CANT
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1037
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8'' [200 mm]
MIN. HEIGHT) FEATHERED
AT FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1038
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
OPTIONAL :
EXTEND FIELD PLIES
ABOVE HEAD OF CANT
AP
[10 PRO
0 m X. 4
m] ''
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
SUITABLE BASE SHEET
FASTENERS
LIGHTWEIGHT INSULATING
CONCRETE
DECK
NOTES :
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS. (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. ALL PLIES ARE TO BE SOLIDLY MOPPED TO THE BASE SHEET. CARE SHOULD BE USED NOT TO ADHERE
THE BASE SHEET TO THE WALL.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1039
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
VENTED BASE SHEET (DO NOT
ADHERE OR SEAL TO
WALL) FASTENED
APPROX. 8'' [200 mm] O.C.
REMOVABLE SHEET METAL
COUNTERFLASHING
FASTENERS APPROX. 8''
[200 mm] O.C.
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8'' [200 mm]
MIN. HEIGHT) FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
LIGHTWEIGHT INSULATING
CONCRETE
CANT
DECK
NOTES :
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS. (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. ALL PLIES ARE TO BE SOLIDLY MOPPED TO THE BASE SHEET. CARE SHOULD BE USED NOT TO ADHERE
THE BASE SHEET TO THE WALL.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1040
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
OPTIONAL :
EXTENDED BASE FLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL :
AP EXTENDED FIELD PLIES
[10 PRO ABOVE HEAD OF CANT STRIP
0 m X. 4
m] ''
THERMAL INSULATION
CANT
ROOF DECK
FLEXIBLE VAPOR RETARDER WITH
NOTES : COMPRESSIBLE INSULATION
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL
OCCUR BETWEEN THE DECK AND A VERTICAL SURFACE. THE WOOD MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1041
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
OPTIONAL: MEMBRANE
SHEET CLOSURE SECURED
AND ADHERED TO WALL
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF - COVER TOP OF
BASE FLASHING WITH
VAPOR RETARDER
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
FLEXIBLE VAPOR
RETARDER WITH
COMPRESSIBLE
INSULATION
NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL
MOVEMENT WILL OCCUR BETWEEN THE DECK AND A VERTICAL SURFACE. THE WOOD
MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1042
The NRCA Roofing and Waterproofing Manual—Fifth Edition
AP
[10 PRO
0 m X. 4
m] ''
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT
FIELD OF ROOF
CANT
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
BUR-7
2001 NOT DRAWN TO SCALE
1043
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE WEATHERPROOF
MEMBRANE CLOSURE
OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS ARE USED
SHEET METAL EXPANSION
WITH THE METAL CAP
JOINT COVER
COMPRESSIBLE
INSULATION TOP OF CURB TO
DRAIN TO ONE SIDE
OPTIONAL :
EXTENDED BASE FASTENERS APPROX. 8''
FLASHING (NOT [200 mm] O.C.
SHOWN FOR CLARITY)
GASKETED FASTENERS
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
FLASHING HEIGHT
MULTIPLE-PLY MEMBRANE
8'' [200 mm] MIN.
ON LOW SIDE
BASE FLASHING
FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
CANT
COVERBOARD INSULATION
WOOD NAILERS
THERMAL INSULATION
ROOF DECK
BUR-7S
2001 NOT DRAWN TO SCALE
1044
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE
PRE-MANUFACTURED
OPTIONAL : EXPANSION JOINT COVER
EXTENDED
BASE FLASHING
COMPRESSIBLE
INSULATION
GASKETED FASTENERS
FLASHING HEIGHT
8'' [200 mm] MIN.
TOP OF CURB TO
DRAIN TO OUTSIDE
OPTIONAL :
AP EXTENDED FIELD PLIES
[10 PRO ABOVE HEAD OF CANT
0 m X. 4
m] ''
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED
AT FIELD OF ROOF
FLEXIBLE VAPOR
RETARDER TO SERVE AS MULTIPLE-PLY BUILT-UP
INSULATION RETAINER ROOF MEMBRANE
(ATTACHED TO TOP OF
CURB) COVERBOARD INSULATION
CANT
THERMAL INSULATION
WOOD NAILERS ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECURMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1045
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE
COMPRESSIBLE PRE-MANUFACTURED
INSULATION EXPANSION JOINT COVER
OPTIONAL :
EXTENDED BASE TOP OF CURB TO
FLASHING DRAIN OUTSIDE
GASKETED FASTENERS
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
FLASHING HEIGHT
MULTIPLE-PLY MEMBRANE
8'' [200 mm] MIN.
BASE FLASHING
FEATHERED AT FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
WOOD NAILERS
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1046
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
FLASHING HEIGHT
8'' [200 mm] MIN.
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF
WOOD NAILERS
MULTIPLE-PLY BUILT-UP
CANT ROOF MEMBRANE
THERMAL INSULATION
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
BUR-8
2001 NOT DRAWN TO SCALE
1047
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
FLASHING HEIGHT
BASE FLASHING
8'' [200 mm] MIN.
FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
CANT
WOOD NAILERS
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE
ROOF DECK. AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
BUR-8S
2001 NOT DRAWN TO SCALE
1048
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
OPTIONAL :
EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
AP FEATHERED AT FIELD
[10 PRO
0 m X. 4 OF ROOF
m] ''
WOOD CURB
WOOD NAILERS
ROOF DECK
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
CANT
COVERBOARD INSULATION
NOTES : THERMAL INSULATION
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHT-WEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL BUR-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FORM JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
BUR-9
2001 NOT DRAWN TO SCALE
1049
The NRCA Roofing and Waterproofing Manual—Fifth Edition
HEIGHT
WIDTH OF EQUIPMENT OF LEGS
UP TO 24'' [UP TO 600 mm] 24'' [600 mm]
SET BOLTS IN SEALANT 24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
(BY OTHERS) 48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]
SHEET METAL
COVER SET NEOPRENE PAD IN
SEALANT (BY OTHERS)
GASKETED
FASTENERS
FASTENERS
APPROX. 8'' OPTIONAL :
[200 mm] O.C. EXTENDED FIELD PLIES
ABOVE HEAD OF CANT
(NOT SHOWN FOR
CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
CANT
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHT-WEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL BUR-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE SHEET METAL SECTIONS OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
BUR-9S
2001 NOT DRAWN TO SCALE
1050
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
HEIGHT-
SEE TABLE
LE
AB
E ET
SEE DETAIL -S
H
BUR-11 FOR FLASHING IDT
W
OF SUPPORT LEGS
NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL BUR-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED DIRECTLY OVER
COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE ADAPTED FOR OTHER USES,
SUCH AS SIGN SUPPORTS.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
BUR-10
2001 NOT DRAWN TO SCALE
1051
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G., POLYURETHANE)
FOR HEIGHT OF LEGS
SEE TABLE ON BUR-10
DRAWBAND
MULTIPLE MEMBRANE
STRIPPING PLY-
FEATHER PLIES
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
1052
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAWBAND
OR COMPATIBLE SEALANT
AT PENETRATION TO
MEMBRANE JUNCTURE
4'' [100 mm] MINIMUM FLANGE
SET IN COMPATIBLE ROOF
CEMENT OVER FIELD PLIES -
PRIME FLANGE BEFORE
STRIPPING
MULTIPLE-PLY MEMBRANE
STRIPPING PLIES -
FEATHER PLIES
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
1053
The NRCA Roofing and Waterproofing Manual—Fifth Edition
RAISED CURB
WOOD NAILER
SEALING MATERIAL
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING
AP
[10 PRO
0 m X. 4
m] ''
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
ALTERNATE [200 mm] MIN. HEIGHT)
CURB BEARING FEATHERED AT FIELD OF
LOCATION FOR ROOF
HEAVY WEIGHT
LOADING MULTIPLE-PLY BUILT-UP
CONDITIONS WOOD NAILER ROOF MEMBRANE
COVERBOARD INSULATION
1054
The NRCA Roofing and Waterproofing Manual—Fifth Edition
RAISED CURB
SEALING
MATERIAL
GASKETED FASTENERS
WOOD NAILER MINIMUM TWO FASTENERS
PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING
FASTENERS
APPROX. 8''
OPTIONAL: EXTENDED FIELD
[200 mm] O.C.
PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
LOADING CONDITIONS
NOTES :
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1055
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
WOOD CURB
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
SHEET METAL
COUNTERFLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
WOOD
NAILERS
FASTENERS
REMOVABLE
COUNTERFLASHING
BASE FLASHING
WOOD CURB
NOTES :
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1056
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD CURB
SEALING MATERIAL
SHEET METAL
COUNTERFLASHING
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
NOTES :
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1057
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
AP
FASTENERS APPROX.
[10 PRO 8'' [200 mm] O.C.
0 m X. 4
m] ''
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
WOOD NAILERS FEATHERED AT FIELD OF
AND CURB ROOF
MULTIPLE-PLY BUILT-UP
CANT
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTIONS OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
BUR-14
2001 NOT DRAWN TO SCALE
1058
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT AND FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
BUR-14S
2001 NOT DRAWN TO SCALE
1059
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)
INSULATE VOID TO
PREVENT CONDENSATION
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
AP
[10 PRO
0 m X. 4
m] ''
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
CANT
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1060
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WELDED PLATE
SEALED WATERTIGHT
(BY OTHERS)
INSULATE VOID TO
PREVENT CONDENSATION
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
REMOVABLE SHEET
METAL COUNTERFLASHING
OPTIONAL : EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
CANT
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1061
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSULATE VOID
TO PREVENT
CONDENSATION
SHEET METAL OR
FLEX-TUBE COLLAR
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
AP
[10 PRO FASTENERS APPROX. 8''
0 m X. 4
m] '' [200 mm] O.C.
OPTIONAL : EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST PENETRATE THE ROOF.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1062
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
FASTENERS APPROX.
8'' [203 mm] O.C
OPTIONAL : REMOVABLE SHEET
METAL COUNTERFLASHING
SEE NOTE 3
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
COVERBOARD INSULATION
THERMAL INSULATION
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST PENETRATE THE ROOF.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1063
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
COVER TO STACK
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
CANT
1064
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
COVER TO STACK
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
METAL OR
GYPSUM LINER
ROOF DECK
IF REQUIRED
CANT
NOTES :
WOOD NAILERS AND CURB
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE
STACK, AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE
MATERIAL HANDLED BY THE STACK.
3. WHERE THE ISOLATED STACK COVER OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO INTRODUCTIONS FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
1065
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G., POLYURETHANE)
DRAWBAND
MULTIPLE MEMBRANE
STRIPPING PLIES -
FEATHER PLIES
COMPATIBLE ROOF CEMENT
OR COMPATIBLE SEALANT
AT FLASHING TO
MEMBRANE JUNCTURE
OPTIONAL :
METAL LINER
AND INSULATION
IF HOT PIPE
NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE
STACK WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1066
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE
SEALANT (E.G.,
POLYURETHANE)
DRAWBAND
COMPATIBLE ROOF
CEMENT OR
COMPATIBLE
SEALANT AT SHEET METAL
FLASHING TO RAIN COLLAR
MEMBRANE SHEET METAL
JUNCTURE FLASHING MIN. 8''
[200 mm] ABOVE
4'' [100 mm] MIN.
ROOF MEMBRANE
FLANGE SET IN
COMPATIBLE ROOF
MULTIPLE
CEMENT OVER
MEMBRANE
BUILT-UP PLIES -
STRIPPING PLIES -
PRIME FLANGE
FEATHER PLIES
BEFORE STRIPPING
MULTIPLE-PLY
BUILT-UP ROOF
MEMBRANE
OPTIONAL :
METAL LINER COVERBOARD
AND INSULATION INSULATION
IF HOT PIPE
THERMAL
INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE
STACK WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1067
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MULTIPLE MEMBRANE
STRIPPING PLIES FEATHERED
AT FIELD OF ROOF. PRIME
FLANGE BEFORE STRIPPING
APPROX 4''
[100 mm]
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION TO
MEMBRANE JUNCTURE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
SET FLANGE IN COMPATIBLE
ROOF CEMENT
NOTES :
PLUMBING VENT
BUR-18
2001 NOT DRAWN TO SCALE
1068
The NRCA Roofing and Waterproofing Manual—Fifth Edition
COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
SET FLANGE IN
COMPATIBLE ROOF
CEMENT
4'' MIN.
FLANGE MULTIPLE MEMBRANE
[100 mm] STRIPPING PLIES
FEATHERED AT FIELD
OF ROOF. PRIME FLANGE
BEFORE STRIPPING
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
PLUMBING VENT
BUR-18S
2001 NOT DRAWN TO SCALE
1069
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G. POLYURETHANE)
SHEET METAL RAIN
COLLAR OVERLAPPING DRAWBAND
PENETRATION POCKET
COMPATABLE ROOF
APPROX. 1/4''
CEMENT OR COMPATIBLE
[6 mm]
SEALANT AT
CLEARANCE
PENETRATION TO
AT CORNERS
MEMBRANE JUNCTION
MULTIPLE
MEMBRANE 4'' [100 mm] MIN.
STRIPPING FLANGE, SET IN
PLIES FEATHERED COMPATIBLE ROOF
AT FIELD OF CEMENT OVER BUILT-
ROOF UP ROOFING PLIES
PRIME FLANGE BEFORE
STRIPPING
AP
[10 PRO
0 m X. 4
m] ''
POURABLE
SEALANT
NON-SHRINK
GROUT
WEATHERPROOF
SHEET METAL PITCH PAN,
SOLDERED/WELDED
(4'' [100 mm] MIN. HEIGHT)
MULTIPLE-PLY
BUILT-UP ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS BECAUSE THEY
MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL BUR-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
BUR-19
2001 NOT DRAWN TO SCALE
1070
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G. POLYURETHANE)
DRAW BAND
SHEET METAL RAIN
COLLAR OVERLAPPING
POURABLE SEALANT PENETRATION POCKET
COVERBOARD
INSULATION
THERMAL
INSULATION
ROOF DECK
NON-SHRINK GROUT
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS BECAUSE THEY
MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL BUR-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
BUR-19S
2001 NOT DRAWN TO SCALE
1071
The NRCA Roofing and Waterproofing Manual—Fifth Edition
THERMAL
INSULATION
ROOF DECK
TAPERED
INSULATION
CLAMPING RING
DECK CLAMP
DRAIN BOWL
MEMBRANE FIELD
PLIES, METAL FLASHING,
AND STRIPPING PLIES ALL
EXTEND UNDER CLAMPING
RING
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
COMPATIBLE
ROOF CEMENT
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. DO NOT APPLY COAL TAR OR DEAD LEVEL ASPHALT INTO DRAIN SUMP.
3. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
BUR-20
2001 NOT DRAWN TO SCALE
1072
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAIN STRAINER
CLAMPING RING
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE FEATHERED
AT FIELD OF ROOF
COVERBOARD
INSULATION
THERMAL
INSULATION
TAPERED INSULATION
ROOF DECK
DECK CLAMP
DRAIN BOWL
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. DO NOT APPLY COAL TAR OR DEAD LEVEL ASPHALT INTO DRAIN SUMP.
3. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
BUR-20S
2001 NOT DRAWN TO SCALE
1073
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BEAD OF SEALANT
SHEET METAL
CONDUCTOR
HEAD APPROX. 4'' [100 mm]
APPROX. 2'' [50 mm]
ROOF DECK
FELT ENVELOPE
(FOR COAL TAR AND
ASPHALT TYPES I AND II)
WOOD NAILERS
1074
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
FASCIA CAP
FASTEN SCUPPER TO
SHEET METAL SCUPPER
BLOCKING, SET FLANGE
WITH SOLDERED JOINTS
IN COMPATIBLE ROOF
SET IN COMPATIBLE SEALANT
CEMENT, PRIME FLANGE
BEFORE STRIPPING
OPTIONAL : 3/4'' x 3''
[19 mm x 75 mm] MIN.
''L'' SHAPED GRAVEL MULTIPLE-PLY MEMBRANE
GUARD SECURED TO STRIPPING FEATHERED
THE SCUPPER FLANGE, AT FIELD OF ROOF
NOTCHED TO PERMIT
DRAINAGE SUMP AREA IN FRONT OF
SCUPPER TO DRAIN
SEALANT
COVERBOARD
INSULATION
THERMAL INSULATION
MULTIPLE-PLY BUILT-UP
ROOF MEMBRANE
ROOF DECK
FELT ENVELOPE
SHEET METAL (FOR COAL TAR AND
CONDUCTOR ASPHALT TYPES I AND II)
HEAD
EXTEND ONE PLY OR
A SEPARATE MEMBRANE
SHEET TO BELOW
BLOCKING
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND
SECUREMENT OPTIONS FOR SHEET METAL.
1075
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MULTIPLE MEMBRANE
STRIPPING PLIES
FASTENERS
3'' to 6''
[75 to 150 mm] O.C.,
STAGGERED
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS
OPTIONAL: GUTTER
BRACKET SUPPORT
OPTIONAL: STIFFENING
BAR
NOTES :
WOOD NAILERS
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING BUR-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MATERIAL FOR JOINERY AND SECUREMENT OPTIONS.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
BUR-22
2001 NOT DRAWN TO SCALE
1076
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SET FLANGE IN
COMPATIBLE ROOF CEMENT
MULTIPLE MEMBRANE
STRIPPING PLIES
GUTTER SPACER
INSTALLED BETWEEN
GUTTER BRACKETS
SHEET
METAL GUTTER
THE FRONT OF THE GUTTER
SHOULD BE A MINIMUM 1'' [25 mm]
LOWER THAN THE BACK TO
ALLOW FOR OVERFLOW ROOF DECK
NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING BUR-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MATERIAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
BUR-22S
2001 NOT DRAWN TO SCALE
1077
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS CLEAT
FASTENED PER TABLE 1 SHEET METAL PARAPET
CAP SLOPED TO DRAIN
TO ROOF SIDE
GASKETED FASTENERS
CONTINUOUS SHIM
WOOD NAILER
PRIME CONCRETE
AP
PR
[10 O
0 m X. 4
m] ''
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
CANT
SURFACING, THE MULTI-
PLY MEMBRANE BASE
COVERBOARD INSULATION FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
THERMAL INSULATION AND GRANULE-SURFACED
SHEET)
ROOF DECK
MULTIPLE-PLY MODIFIED
NOTES: BITUMEN ROOF MEMBRANE
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL MB-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET FLASHING LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-1
2001 NOT DRAWN TO SCALE
1078
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS SHIM
WOOD NAILER
1''[25 mm] MIN.
GASKETED FASTENERS
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
CANT
COVERBOARD INSULATION
THERMAL INSULATION
NOTES : ROOF DECK
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE ROOF DECK IS SUPPORTED BY THE WALL. DETAIL MB-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET FLASHING LINER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-1S
2001 NOT DRAWN TO SCALE
1079
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
BELOW BLOCKING
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
GASKETED FASTENERS
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
BELOW BLOCKING
COVERBOARD INSULATION
1'' [25 mm] MIN.
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
NOTES : (FASTENED PER TABLE 1)
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1081
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MODIFIED BITUMEN
MEMBRANE STRIPPING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF FLANGE APPROX.
SYSTEMS WITH FACTORY- 4'' [100 mm] WIDE
APPLIED GRANULE
SURFACING, THE
''GRAVEL STOP'' FLANGE
AND MEMBRANE STRIPPING
APPROX. 4''
CAN BE INSTALLED BETWEEN
[100 mm]
THE BASE PLY AND
GRANULE-SURFACED
SHEET)
BELOW BLOCKING
1'' [25mm] MIN.
OPTIONAL: COMPATIBLE
SEALANT AT JUNCTION
OF MEMBRANE AND
EDGE METAL
FASTENERS
3'' to 6''
[75 to 150 mm] O.C.,
STAGGERED
SHEET METAL
''GRAVEL-STOP'' SET
IN COMPATIBLE ROOF
CEMENT PRIME FLANGE
BEFORE STRIPPING
MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE
1082
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.,
STAGGERED
MODIFIED BITUMEN
MEMBRANE STRIPPING
FEATHERED AT FIELD OF
ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE ''GRAVEL
STOP'' FLANGE AND
MEMBRANE STRIPPING
CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE
BELOW BLOCKING
1'' [25mm] MIN.
COVERBOARD
INSULATION
THERMAL INSULATION
ROOF DECK
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE
EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE. (SEE MB-1 FOR THE PREFERRED PERIMETER CONSTRUCTION.)
2. REFER TO SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1083
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SMOOTH CONCRETE
INSTALL APPROPRIATE
SEALANT (E.G.,
POLYURETHANE) AND
TOOL TO FACILITATE
WATER RUN-OFF
CONCRETE FASTENERS
OPTIONAL: COMPRESSIBLE
ELASTOMERIC SEALANT
OR TAPE TO SPAN
IRREGULARITIES
PRIME CONCRETE TO
TOP OF BASE FLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
SEAL TOP OF FLASHING WITH
A COMPATIBLE VERTICAL
GRADE ROOF CEMENT
SHEET METAL
COUNTERFLASHING
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD
OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN.
HEIGHT) FEATHERED AT
FIELD OF ROOF
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD
OF ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
AP SURFACING, THE MULTI-
[10 PRO PLY MEMBRANE BASE
0 m X. 4
m] '' FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
NOTES :
ROOF DECK
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. COUNTERFLASHING DETAIL MAY BE A TWO-PIECE REGLET AND COUNTERFLASHING
(SEE TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING).
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
MB-4
2001 NOT DRAWN TO SCALE
1084
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SMOOTH CONCRETE
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF
OPTIONAL: COMPRESSIBLE
ELASTOMERIC SEALANT OR
TAPE TO SPAN IRREGULARITIES
CONCRETE FASTENERS
SEAL TOP OF FLASHING WITH A
COMPATIBLE VERTICAL GRADE
ROOF CEMENT
SHEET METAL COUNTERFLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8'' [200 mm]
MIN. HEIGHT) FEATHERED AT
FIELD OF ROOF
(FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
NOTES :
ROOF DECK
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. COUNTERFLASHING DETAIL MAY BE A TWO-PIECE REGLET AND COUNTERFLASHING
(SEE TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING).
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
SURFACE-MOUNT COUNTERFLASHING
FOR CONCRETE WALLS
MB-4S
2001 NOT DRAWN TO SCALE
1085
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
PRIME SURFACE AS
REQUIRED
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
AP
ROOF (FOR ROOF
[10 PRO
0 m X. 4 SYSTEMS WITH FACTORY-
m] ''
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1086
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
1087
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
AP FEATHERED AT FIELD OF
[10 PRO ROOF (FOR ROOF
0 m X. 4
m] '' SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
1088
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS APPROX.
8'' [200 mm] O.C.
FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF SYSTEMS
WITH FACTORY-APPLIED
GRANULE SURFACING, THE
MULTI-PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY AND
GRANULE-SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
NOTES :
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. ALL PLIES ARE TO BE SOLIDLY MOPPED TO THE BASE SHEET. CARE SHOULD BE USED NOT TO ADHERE THE BASE
SHEET TO THE WALL.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1089
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
OPTIONAL: MEMBRANE
SHEET CLOSURE SECURED
AND ADHERED TO WALL
OPTIONAL: EXTENDED
BASE FLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL: EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT STRIP
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF - COVER TOP
OF BASE FLASHING WITH
VAPOR RETARDER (FOR ROOF
SYSTEMS WITH FACTORY-
AP APPLIED GRANULE SURFACING,
[10 PRO THE MULTI-PLY MEMBRANE
0 m X. 4
m] '' BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL OCCUR BETWEEN
THE DECK AND A VERTICAL SURFACE. THE WOOD MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1090
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
OPTIONAL : MEMBRANE
SHEET CLOSURE SECURED
AND ADHERED TO WALL
OPTIONAL : EXTENDED
BASE FLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT STRIP (NOT SHOWN
FOR CLARITY)
FLEXIBLE VAPOR RETARDER
WITH COMPRESSIBLE
INSULATION
MULTIPLE-PLY MEMBRANE
BASE FLASHING
(8'' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF - COVER TOP
OF BASE FLASHING WITH
VAPOR RETARDER (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE SURFACING,
THE MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
NOTES :
1. THIS DETAIL SHOULD BE USED WHERE THERE IS ANY POSSIBILITY THAT DIFFERENTIAL MOVEMENT WILL OCCUR BETWEEN
THE DECK AND A VERTICAL SURFACE. THE WOOD MEMBERS SHOULD NOT BE FASTENED TO THE WALL.
2. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1091
The NRCA Roofing and Waterproofing Manual—Fifth Edition
OPTIONAL: EXTENDED
BASE FLASHING
FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
SHEET METAL EXPANSION
COMPRESSIBLE JOINT COVER
INSULATION
FLEXIBLE WEATHERPROOF
MEMBRANE CLOSURE -
OPTIONAL IF DOUBLE LOCK
HEIGHT ON LOW SIDE
MINIMUM FLASHING
METAL CAP
GASKETED FASTENERS
TOP OF CURB TO
DRAIN TO ONE SIDE
OPTIONAL: EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT
MULTIPLE-PLY MEMBRANE
AP BASE FLASHING
[10 PRO FEATHERED AT FIELD
0 m X. 4
m] '' OF ROOF - (FOR
ROOF SYSTEMS WITH
FACTORY-APPLIED
GRANULE SURFACING, THE
MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
CANT
MULTIPLE-PLY MODIFIED
WOOD NAILERS BITUMEN ROOF
MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-7
2001 NOT DRAWN TO SCALE
1092
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
OPTIONAL: EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FLASHING HEIGHT ON LOW SIDE
FEATHERED AT FIELD
FLEXIBLE VAPOR
OF ROOF - (FOR
RETARDER TO
ROOF SYSTEMS WITH
SERVE AS INSULATION
8'' [200 mm] MINIMUM
FACTORY-APPLIED
RETAINER (ATTACHED
GRANULE SURFACING, THE
TO TOP OF CURB)
MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
COMPRESSIBLE
BASE PLY AND GRANULE-
INSULATION
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
CANT
BITUMEN ROOF MEMBRANE
WOOD NAILERS COVERBOARD INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-7S
2001 NOT DRAWN TO SCALE
1093
The NRCA Roofing and Waterproofing Manual—Fifth Edition
OPTIONAL: EXTENDED
BASE FLASHING
FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
PREMANUFACTURED
COMPRESSIBLE EXPANSION JOINT COVER
INSULATION
FLEXIBLE WEATHERPROOF
MEMBRANE CLOSURE
8'' [200 mm] MINIMUM
FLASHING HEIGHT
GASKETED FASTENERS
TOP OF CURB TO
DRAIN TO OUTSIDE
OPTIONAL: EXTENDED
FIELD PLIES ABOVE
HEAD OF CANT
MULTIPLE-PLY MEMBRANE
AP BASE FLASHING
[10 PRO FEATHERED AT FIELD
0 m X. 4
m] '' OF ROOF - (FOR
ROOF SYSTEMS WITH
FACTORY-APPLIED
GRANULE SURFACING, THE
MULTI-PLY MEMBRANE
BASE FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
CANT
MULTIPLE-PLY MODIFIED
WOOD NAILERS BITUMEN ROOF
MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1094
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MULTIPLE-PLY MODIFIED
CANT BITUMEN ROOF
MEMBRANE
WOOD NAILERS COVERBOARD INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1095
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MINIMUM FLASHING
8'' [200 mm]
HEIGHT
GASKETED FASTENERS
OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT
MULTIPLE-PLY MEMBRANE
AP BASE FLASHING
[10 PRO
0 m X. 4 FEATHERED AT FIELD OF
m] ''
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
CANT BASE PLY AND GRANULE-
SURFACED SHEET)
WOOD NAILERS
MULTIPLE-PLY MODIFIED
BITUMEN ROOF
MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-8
2001 NOT DRAWN TO SCALE
1096
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
MINIMUM FLASHING HEIGHT
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
8'' [200 mm]
MULTIPLE-PLY MODIFIED
BITUMEN ROOF
MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-8S
2001 NOT DRAWN TO SCALE
1097
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
OPTIONAL : EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
AP BASE PLY AND GRANULE-
P
[10 ROX SURFACED SHEET)
0m .4
m] ''
MULTIPLE-PLY MODIFIED
WOOD CURB BITUMEN ROOF MEMBRANE
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL MB-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
MB-9
2001 NOT DRAWN TO SCALE
1098
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD
OF ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
WOOD CURB BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
CANT
THERMAL INSULATION
WOOD NAILERS
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL MB-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS ON
VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
MB-9S
2001 NOT DRAWN TO SCALE
1099
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
HEIGHT-
SEE TABLE
LE
AB
E ET
-S
TH
SEE DETAIL ID
W
MB-11 FOR FLASHING
OF SUPPORT LEGS
NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL MB-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED DIRECTLY OVER
COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE ADAPTED FOR OTHER USES,
SUCH AS SIGN SUPPORTS.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-10
2001 NOT DRAWN TO SCALE
1100
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G., POLYURETHANE)
DRAWBAND
OVERLAPPING FLASHING
COLLAR BY 3'' TO 4''
[75 mm TO 100 mm]
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
MODIFIED BITUMEN
MEMBRANE STRIPPING PLY
COVERBOARD INSULATION
1101
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAWBAND
SHEET METAL RAIN COLLAR
OVERLAPPING FLASHING
COLLAR BY 3'' TO 4''
[75 mm TO 100 mm]
SHEET METAL FLASHING
COLLAR MINIMUM OF 8''
APPROPRIATE
[200 mm] ABOVE ROOFING
SEALANT (E.G.,
POLYURETHANE) 1/4'' [6 mm] MINIMUM
CLEARANCE BETWEEN FLASHING
COLLAR AND SUPPORT
1/4'' [6 mm]
FOR HEIGHT OF LEGS
MIN. CLEARANCE
OR COMPATIBLE SEALANT
TO RAIN COLLAR
AT PENETRATION TO
MEMBRANE JUNCTURE
4'' [100 mm] MINIMUM FLANGE
SET IN ROOF COMPATIBLE
CEMENT OVER FIELD PLIES -
PRIME FLANGE BEFORE
STRIPPING (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE FLASHING
COLLAR FLANGE AND MULTI-
PLY MEMBRANE STRIPPING
CAN BE INSTALLED BETWEEN
THE BASE PLY AND GRANULE-
SURFACED SHEET)
1102
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ALTERNATE ROOF (FOR ROOF
CURB BEARING SYSTEMS WITH FACTORY-
LOCATION FOR APPLIED GRANULE
HEAVY WEIGHT SURFACING, THE MULTI-
LOADING PLY MEMBRANE BASE
CONDITIONS WOOD NAILER FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
OPTIONAL : MECHANICAL UNIT, HOOD, ETC. SHEET)
BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND MULTIPLE-PLY MODIFIED
TOP OF CURB
BITUMEN ROOF MEMBRANE
SEALING MATERIAL - MUST
BE CONTINUOUS ON TOP
OF THE CURB COVERBOARD INSULATION
1'' [25 mm] MINIMUM
BELOW TOP OF CURB THERMAL INSULATION
FLASHING RECEIVER
ROOF DECK
WOOD NAILER
NOTES :
FASTENERS
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO
COUNTERFLASHING BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
BASE FLASHING BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
RAISED CURB HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INSULATION INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1103
The NRCA Roofing and Waterproofing Manual—Fifth Edition
RAISED CURB
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
NOTES : LOADING CONDITIONS
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1104
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
WOOD CURB
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
SHEET METAL
COUNTERFLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
WOOD BASE FLASHING (8''
NAILERS [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
CANT ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
ALTERNATE : MECHANICAL UNIT, HOOD, ETC.
BASE OF UNIT EXTENDS 1/2'' MULTIPLE-PLY MODIFIED
[13 mm] MINIMUM BEYOND BITUMEN ROOF MEMBRANE
TOP OF CURB
SEALING MATERIAL - MUST COVERBOARD INSULATION
BE CONTINUOUS ON TOP
OF THE CURB
1'' [25 mm] MINIMUM THERMAL INSULATION
BELOW TOP OF CURB
FLASHING RECEIVER ROOF DECK
WOOD NAILER
FASTENERS
NOTES :
COUNTERFLASHING
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
BASE FLASHING BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
RAISED CURB HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL
INSULATION INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1105
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD CURB
SEALING MATERIAL
SHEET METAL
COUNTERFLASHING
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
NOTES :
1. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND
FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION FOR THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1106
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF. (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
WOOD NAILERS
AND CURB
MULTIPLE-PLY MODIFIED
CANT
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
MB-14
2001 NOT DRAWN TO SCALE
1107
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT AND FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
MB-14S
2001 NOT DRAWN TO SCALE
1108
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)
INSULATE VOID TO
PREVENT CONDENSATION
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING
FASTENERS APPROX.
8'' [200 mm] O.C.
AP
[10 PRO
0 m X. 4
m] ''
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE
INSTALLED BETWEEN THEY
BASE PLY AND GRANULE-
SURFACED SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
WOOD NAILERS AND CURB
THERMAL INSULATION
CANT
NOTES : ROOF DECK
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1109
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WELDED PLATE
SEALED WATERTIGHT
(BY OTHERS)
INSULATE VOID TO
PREVENT CONDENSATION
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
REMOVABLE SHEET
METAL COUNTERFLASHING
OPTIONAL: EXTENDED FIELD
PLIES ABOVE HEAD OF CANT
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
CANT
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, C, BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1110
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSULATE VOID
TO PREVENT
CONDENSATION
SHEET METAL OR
FLEX-TUBE COLLAR
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
OPTIONAL: EXTENDED
FIELD PLIES ABOVE HEAD
OF CANT
AP MULTIPLE-PLY MEMBRANE
[10 PRO BASE FLASHING (8''
0 m X. 4
m] '' [200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
MIN. 4'' [100 mm] PLY MEMBRANE BASE
CLEARANCE FROM PIPE FLASHING CAN BE INSTALLED
TO TOP OF CURB; BETWEEN THE BASE PLY
MIN. 2'' [50 mm] AND GRANULE-SURFACED
BETWEEN PIPES SHEET)
1111
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
FASTENERS APPROX.
8'' [203 mm] O.C
OPTIONAL: REMOVABLE SHEET
METAL COUNTERFLASHING
SEE NOTE 3.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF (FOR ROOF
SYSTEMS WITH FACTORY-
APPLIED GRANULE
SURFACING, THE MULTI-
PLY MEMBRANE BASE
FLASHING CAN BE INSTALLED
BETWEEN THE BASE PLY
AND GRANULE-SURFACED
SHEET)
COVERBOARD INSULATION
OPTIONAL : EXTENDED THERMAL INSULATION
FIELD PLIES ABOVE HEAD OF CANT
(NOT SHOWN FOR CLARITY)
ROOF DECK
CANT
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF GROUPING
PIPING THAT MUST PENETRATE THE ROOF.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1112
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
COVER TO STACK
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
THERMAL INSULATION
1113
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
COVER TO STACK
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
MULTIPLE-PLY MEMBRANE
BASE FLASHING (8''
[200 mm] MIN. HEIGHT)
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
THERMAL INSULATION
METAL OR
GYPSUM LINER ROOF DECK
IF REQUIRED
CANT
NOTES : WOOD NAILERS AND CURB
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE STACK, AND THE NEED
FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE ISOLATED STACK COVER OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1114
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE ELASTOMERIC
ELASTOMERIC SEALANT
DRAWBAND
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
OPTIONAL : THERMAL INSULATION
METAL LINER
AND INSULATION ROOF DECK
IF HOT PIPE
NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE STACK
WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1115
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC
SEALANT
DRAWBAND
COMPATIBLE ROOF
CEMENT OR
COMPATIBLE
SEALANT AT SHEET METAL
FLASHING TO RAIN COLLAR
MEMBRANE SHEET METAL
JUNCTURE FLASHING MIN. 8''
[200 mm] ABOVE
4'' [100 mm] MIN.
ROOF MEMBRANE
FLANGE SET IN
COMPATIBLE ROOF
MULTIPLE-PLY
CEMENT OVER
MEMBRANE
MULTIPLE-PLY
STRIPPING PLIES -
BITUMEN ROOF
FEATHER PLIES
MEMBRANE
BEFORE STRIPPING MULTIPLE-PLY
MODIFIED
BITUMEN ROOF
MEMBRANE
OPTIONAL :
METAL LINER COVERBOARD
AND INSULATION INSULATION
IF HOT PIPE
THERMAL
INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL INSULATION AND METAL LINER AND THE
STACK WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1116
The NRCA Roofing and Waterproofing Manual—Fifth Edition
COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION TO
MEMBRANE JUNCTURE
4'' MIN. FLANGE
[100 mm]
APPROX. 4''
[100 mm]
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
SET FLANGE IN COMPATIBLE
ROOF CEMENT (FOR ROOF
SYSTEMS WITH FACTORY-APPLIED
GRANULE SURFACING, THE
PIPE FLASHING FLANGE
AND MULTI-PLY MEMBRANE
STRIPPING CAN BE
INSTALLED BETWEEN THE
BASE PLY AND GRANULE-
SURFACED SHEET)
COVERBOARD INSULATION
THERMAL INSULATION
NOTES :
ROOF DECK
1. SOFT METAL PIPE FLASHING:
-SHEET LEAD : MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m2 ] OR
-SHEET COPPER: MINIMUM 16 OZ. [5 kg/m2 ]
PRECAUTIONS SHOULD BE TAKEN NOT TO DAMAGE THE SHEET LEAD WHEN USING HEAT-WELDED APPLICATION.
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SEPARATOR SHEET (E.G., ASPHALT-
SATURATED ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT
CONTACT WITH PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
MB-18
2001 NOT DRAWN TO SCALE
1117
The NRCA Roofing and Waterproofing Manual—Fifth Edition
COMPATIBLE ROOF
CEMENT OR COMPATIBLE
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
MODIFIED BITUMEN
MEMBRANE STRIPPING PLY
PRIME FLANGE BEFORE
STRIPPING
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
NOTES : THERMAL INSULATION
PLUMBING VENT
MB-18S
2001 NOT DRAWN TO SCALE
1118
The NRCA Roofing and Waterproofing Manual—Fifth Edition
AP
[10 PRO
0 m X. 4
m] ''
NON-SHRINK
GROUT
WEATHERPROOF
SHEET METAL PITCH PAN,
SOLDERED / WELDED
(4'' [100 mm] MIN. HEIGHT)
COVERBOARD INSULATION
THERMAL INSULATION
ROOF DECK
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS
BECAUSE THEY MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL MB-11 FOR THE PREFERRED
FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
MB-19
2001 NOT DRAWN TO SCALE
1119
The NRCA Roofing and Waterproofing Manual—Fifth Edition
COVERBOARD
INSULATION
THERMAL
INSULATION
ROOF DECK
NON-SHRINK GROUT
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT THE PENETRATIONS
BECAUSE THEY MAY BE A CONSTANT MAINTENANCE PROBLEM. SEE DETAIL MB-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
MB-19S
2001 NOT DRAWN TO SCALE
1120
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAIN STRAINER
COVERBOARD
INSULATION
THERMAL INSULATION
ROOF DECK
TAPERED
INSULATION
CLAMPING RING
DECK CLAMP
DRAIN BOWL
MEMBRANE FIELD
PLIES, METAL FLASHING,
AND STRIPPING PLY ALL
EXTEND UNDER CLAMPING
RING
COMPATIBLE ROOF CEMENT
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
MB-20
2001 NOT DRAWN TO SCALE
1121
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAIN STRAINER
CLAMPING RING
MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE
COVERBOARD
INSULATION
THERMAL
INSULATION
TAPERED INSULATION
ROOF DECK
DECK CLAMP
DRAIN BOWL
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
MB-20S
2001 NOT DRAWN TO SCALE
1122
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ROOF DECK
TAPERED
INSULATION
CLAMPING RING
DECK CLAMP
DRAIN BOWL
MEMBRANE FIELD
PLIES, METAL FLASHING,
AND STRIPPING PLY ALL
EXTEND UNDER CLAMPING
RING
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER,
DRAIN RECEIVER/BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-20A
2001 NOT DRAWN TO SCALE
1123
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAIN STRAINER
CLAMPING RING
COMPATIBLE
ROOF CEMENT
COVERBOARD
INSULATION
THERMAL
INSULATION
TAPERED INSULATION
ROOF DECK
DECK CLAMP
DRAIN BOWL
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER,
DRAIN RECEIVER/BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
MB-20AS
2001 NOT DRAWN TO SCALE
1124
The NRCA Roofing and Waterproofing Manual—Fifth Edition
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1125
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MULTIPLE-PLY MODIFIED
BITUMEN ROOF MEMBRANE
COVERBOARD INSULATION
(SUMP TO DRAIN)
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
EXTEND ONE PLY OR
A SEPARATE MEMBRANE
SHEET TO BELOW
BLOCKING
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1126
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MODIFIED BITUMEN
MEMBRANE STRIPPING
PLY
SET FLANGE IN
COMPATIBLE
ROOF CEMENT
MULTIPLE-PLY
MODIFIED BITUMEN
ROOF MEMBRANE
COVERBOARD OPTION :
INSULATION
THERMAL SHEET METAL EDGE
INSULATION FLASHING - PRIME
FLANGE BEFORE
ROOF DECK STRIPPING (FOR ROOF
SYSTEMS WITH
FACTORY-APPLIED
GRANULE SURFACING,
THE METAL EDGE
FLANGE AND MEMBRANE
STRIPPING CAN BE
INSTALLED BETWEEN
THE BASE PLY AND
GRANULE-SURFACED
SHEET)
FASTENERS 3'' TO 6''
[75 mm TO 150 mm] O.C.
STAGGERED
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS
SHEET METAL GUTTER
THE FRONT OF THE
GUTTER SHOULD BE A
MIN. 1'' [25 mm] LOWER
THAN THE BACK TO
ALLOW FOR OVERFLOW
WOOD OPTIONAL: STIFFENING
NAILERS BAR
EXTEND ONE PLY OR OPTIONAL: GUTTER
A SEPARATE MEMBRANE BRACKET SUPPORT
SHEET TO OVERLAY
METAL CLOSURE
NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING MB-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
MB-22
2001 NOT DRAWN TO SCALE
1127
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MODIFIED BITUMEN
MEMBRANE
STRIPPING PLY
SHEET METAL EDGE SET FLANGE IN
FLASHING - PRIME COMPATIBLE ROOF
FLANGE BEFORE CEMENT
STRIPPING (FOR ROOF
SYSTEMS WITH FASTENERS 3'' TO 6''
FACTORY-APPLIED [75 mm TO 150 mm] O.C.
GRANULE SURFACING, STAGGERED
THE METAL EDGE MULTIPLE-PLY
FLANGE AND MEMBRANE MODIFIED BITUMEN
STRIPPING CAN BE ROOF MEMBRANE
INSTALLED BETWEEN
THE BASE PLY AND
GRANULE-SURFACED
SHEET)
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS ROOF DECK
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING MB-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
MB-22S
2001 NOT DRAWN TO SCALE
1128
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
BELOW BLOCKING
1'' [25 mm] MIN.
WOOD NAILER
FLASHING MEMBRANE
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
CONTINUOUS CLEAT
FASTENED PER TABLE 1
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TP-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-1
2001 NOT DRAWN TO SCALE
1129
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS SHIM
BELOW BLOCKING
1'' [25 mm] MIN.
WOOD NAILER
GASKETED FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
EXTEND MEMBRANE TO
BELOW NAILER AND SECURE
CONTINUOUS CLEAT
COVERBOARD AND
SEAM PLATES AND THERMAL INSULATION
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE PERIMETER
SECUREMENT OPTIONS ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TP-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-1S
2001 NOT DRAWN TO SCALE
1130
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
TP-2
2001 NOT DRAWN TO SCALE
1131
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL FASCIA CAP
GASKETED FASTENERS
FLASHING MEMBRANE
THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
BELOW BLOCKING
1'' [25 mm] MIN.
WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
TP-2S
2001 NOT DRAWN TO SCALE
1132
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT (IF REQUIRED
FOR THE SPECIFIC SYSTEM) 1 1/2'' [38 mm] MIN. FOR
BALLASTED SYSTEMS
ADHERED OR WELDED
FLASHING MEMBRANE
(EXTEND APPROX. 3''
[75 mm] BEYOND FLANGE)
FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.;
STAGGER
THERMOPLASTIC
ROOF MEMBRANE
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER
NOTES : SINGLE-PLY TABLE 1)
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-3
2001 NOT DRAWN TO SCALE
1133
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.,
STAGGER
ADHERED OR WELDED
EXCEED HEIGHT OF BALLAST
BEYOND FLANGE)
1 1/2'' [38 mm] MIN. FOR
THERMOPLASTIC ROOF
MEMBRANE
ROOF DECK
1'' [25 mm] MIN.
CONTINUOUS CLEAT
(FASTENED PER
SINGLE-PLY TABLE 1)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-3S
2001 NOT DRAWN TO SCALE
1134
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS CLEAT
FASTENED PER
TABLE 1.
BELOW BLOCKING
1'' [25 mm] MIN.
ADHERED OR WELDED
FLASHING MEMBRANE
FASTENERS AT APPROX.
3'' to 6'' [75 to 150 mm] O.C.
STAGGER
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
TP-3A
2001 NOT DRAWN TO SCALE
1135
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
FASTENED PER TABLE 1.
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-3AS
2001 NOT DRAWN TO SCALE
1136
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MEMBRANE COATED METAL
FLANGE APPROXIMATELY
3'' [75 mm] MIN. WIDE
APPROXIMATELY 2''
[50 mm] WIDE BOND
BREAKER MATERIAL
(E.G., DUCT TAPE)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. SEE DETAIL TP-3 FOR ADDITIONAL INFORMATION REGARDING EDGE CONSTRUCTION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1137
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLANGE APPROX.
3'' [75 mm]
MIN. WIDE
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. SEE DETAIL TP-3A FOR ADDITIONAL INFORMATION REGARDING EDGE CONSTRUCTION.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-3C
2001 NOT DRAWN TO SCALE
1138
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF
CONCRETE FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS
TP-4
2001 NOT DRAWN TO SCALE
1139
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF
CONCRETE FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS
TP-4S
2001 NOT DRAWN TO SCALE
1140
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-5
2001 NOT DRAWN TO SCALE
1141
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY
AND SECUREMENT OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-5S
2001 NOT DRAWN TO SCALE
1142
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
INSTALL COMPATIBLE
SEALANT BEHIND MEMBRANE
TERMINATION BAR FASTENED
WITH APPROPRIATE
FASTENERS APPROX.
12'' [300 mm] O.C.
REMOVABLE SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
WOOD NAILERS
1. THIS DETAIL ACCOMMODATES INDEPENDENT WALL AND DECK MOVEMENT.
2. OTHER METHODS OF COUNTERFLASHING MAY BE APPLICABLE (SEE TABLE 2).
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-6
2001 NOT DRAWN TO SCALE
1143
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL REGLET
FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
TP-6S
2001 NOT DRAWN TO SCALE
1144
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ON LOW SIDE
GASKETED FASTENERS
FASTENERS APPROX.
8'' [200 mm] O.C.
FLASHING MEMBRANE
THERMOPLASTIC ROOF
TOP OF MEMBRANE
CURB TO DRAIN
TO ONE SIDE
WOOD NAILERS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-7
2001 NOT DRAWN TO SCALE
1145
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
EXPANSION JOINT
FLEXIBLE VAPOR COVER
RETARDER TO SERVE FLEXIBLE
AS INSULATION WEATHERPROOF
RETAINER (ATTACHED MEMBRANE CLOSURE -
TO TOP OF CURB) OPTIONAL IF DOUBLE
LOCK STANDING SEAM
COMPRESSIBLE JOINTS ARE USED WITH
INSULATION THE METAL PARAPET
CAP
TOP OF CURB FASTENERS APPROX.
TO DRAIN TO 8'' [200 mm] O.C.
ONE SIDE
GASKETED FASTENERS
FLASHING MEMBRANE
FASTENERS -
FLASHING HEIGHT
7 FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS. WOOD NAILERS
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-7S
2001 NOT DRAWN TO SCALE
1146
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE VAPOR
RETARDER TO SERVE
AS INSULATION RETAINER PREMANUFACTURED
(ATTACHED TO TOP EXPANSION JOINT
OF CURB) COVER
FLEXIBLE
COMPRESSIBLE WEATHERPROOF
INSULATION MEMBRANE CLOSURE
GASKETED FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT
ON LOW SIDE
FASTENERS APPROX.
8'' [200 mm] O.C.
FLASHING MEMBRANE
TOP OF CURB
TO DRAIN TO
THE OUTSIDE THERMOPLASTIC
ROOF MEMBRANE
WOOD NAILERS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1147
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PREMANUFACTURED
EXPANSION JOINT
COVER
FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE
FASTENERS APPROX.
8'' [200 mm] O.C.
GASKETED FASTENERS
TOP OF CURB
FLASHING MEMBRANE
TO DRAIN TO
(8'' [200 mm] MIN.
THE OUTSIDE
HEIGHT)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE
7 FOR ALTERNATE
PERIMETER
8'' [200 mm] MINIMUM
FLASHING HEIGHT
SECUREMENT OPTIONS
ON LOW SIDE
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1148
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
AREA DIVIDER
COVER
GASKETED
FASTENERS
FLASHING
8'' [200 mm] MINIMUM
FLASHING HEIGHT
MEMBRANE
ON LOW SIDE
SEALANT (IF
REQUIRED FOR
THE SPECIFIC
SYSTEM)
THERMOPLASTIC
ROOF MEMBRANE
WOOD NAILERS
ROOF DECK
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TP-8
2001 NOT DRAWN TO SCALE
1149
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT
FLASHING MEMBRANE
ON LOW SIDE
WOOD NAILERS
ROOF DECK
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
NOTES THERMAL INSULATION
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TP-8S
2001 NOT DRAWN TO SCALE
1150
The NRCA Roofing and Waterproofing Manual—Fifth Edition
HEIGHT
WIDTH OF EQUIPMENT OF LEGS
UP TO 24'' [UP TO 600 mm] 24'' [600 mm] SHEET METAL COVER
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m]
SET NEOPRENE PAD IN
SEALANT (BY OTHERS)
GASKETED FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
WOOD CURB
WOOD NAILERS
THERMOPLASTIC
ROOF DECK ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL TP-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS
ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TP-9
2001 NOT DRAWN TO SCALE
1151
The NRCA Roofing and Waterproofing Manual—Fifth Edition
HEIGHT
WIDTH OF EQUIPMENT OF LEGS SET BOLTS IN SEALANT
UP TO 24'' [UP TO 600 mm] 24'' [600 mm] (BY OTHERS)
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm] SET NEOPRENE PAD IN
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m] SEALANT (BY OTHERS)
GASKETED FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
SEAM PLATES AND
FASTENERS - SEALANT (IF REQUIRED
SEE SINGLE PLY TABLE FOR THE SPECIFIC
7 FOR ALTERNATE SYSTEM)
PERIMETER SECUREMENT
OPTIONS
COVERBOARD AND
ROOF DECK
THERMAL INSULATION
THERMOPLASTIC WOOD NAILERS
ROOF MEMBRANE
WOOD CURB
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL TP-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS
ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TP-9S
2001 NOT DRAWN TO SCALE
1152
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
HEIGHT-
SEE TABLE
LE
B
TA
E
E
S
-
H
T
SEE DETAIL ID
W
TP-11 FOR FLASHING
OF SUPPORT LEGS
NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL TP-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED
DIRECTLY OVER COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE
ADAPTED FOR OTHER USES, SUCH AS SIGN SUPPORTS.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-10
2001 NOT DRAWN TO SCALE
1153
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
OPTIONAL: DRAWBAND
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
TP-11
2001 NOT DRAWN TO SCALE
1154
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
OPTIONAL : DRAWBAND
FOR HEIGHT OF LEGS
SEE TABLE ON TP-10
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
SEALANT (IF REQUIRED
FOR THE SPECIFIC
SYSTEM)
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM
FILL GAPS WITH
INSULATION BOARD
TO PROVIDE EVEN
SUBSTRATE
NOTES :
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-11S
2001 NOT DRAWN TO SCALE
1155
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
OPTIONAL : DRAWBAND
PIPE PENETRATION
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PENETRATIONS TO FACILITATE PROPER FLASHING (SEE TABLE 4).
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-11A
2001 NOT DRAWN TO SCALE
1156
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PIPE PENETRATION
SEALANT
OPTIONAL: DRAWBAND
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING (SEE TABLE 4).
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-11AS
2001 NOT DRAWN TO SCALE
1157
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
RAISED CURB
WOOD NAILER
GASKETED FASTENERS
MIN. TWO FASTENERS
PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
ALTERNATE CURB
BEARING LOCATION
FOR HEAVY-WEIGHT THERMOPLASTIC
LOADING CONDITIONS ROOF MEMBRANE
MECHANICAL UNIT, HOOD, ETC.
COVERBOARD AND
BASE OF UNIT EXTENDS 1/2''
THERMAL INSULATION
[13 mm] MINIMUM BEYOND
TOP OF CURB ROOF DECK
SEALING MATERIAL - MUST
BE CONTINUOUS ON TOP
OF THE CURB
FASTENERS 1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE
TO BE SUPPLIED BY THE CURB MANUFACTURER.
WOOD NAILER 2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
COUNTERFLASHING HAVE BEEN INSTALLED.
INSULATION 3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INFORMATION.
FLASHING MEMBRANE 4. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
RAISED CURB OPTIONS FOR SHEET METAL.
1158
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD NAILER
SEALING MATERIAL
REMOVABLE
SHEET METAL
COUNTERFLASHING
SEAM PLATES AND
FASTENERS - SEE
FLASHING SINGLE PLY TABLE 7
MEMBRANE FOR ALTERNATE
(8'' [200 mm] PERIMETER SECUREMENT
MIN. HEIGHT) OPTIONS
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
LOADING CONDITIONS
NOTES :
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1159
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
WOOD CURB
WOOD
NAILERS
SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
FLASHING RECEIVER
NOTES :
FASTENERS
1. THE MECHANICAL UNITS SHOULD NOT
COUNTERFLASHING BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
FLASHING MEMBRANE 2. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
WOOD CURB OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INFORMATION.
1160
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
REMOVABLE
SHEET METAL
COUNTERFLASHING
WOOD CURB
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
SEALANT (IF
REQUIRED FOR THE
SPECIFIC SYSTEM)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
NOTES :
1. THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1161
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS PER
SIDE
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm]
THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TP-14
2001 NOT DRAWN TO SCALE
1162
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
TP-14S
2001 NOT DRAWN TO SCALE
1163
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSULATE VOID
TO PREVENT
CONDENSATION
WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
AND CURB
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM ALLOWS FOR
MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION IF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR THE SHEET METAL.
TP-15
2001 NOT DRAWN TO SCALE
1164
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSULATE VOID
TO PREVENT
CONDENSATION
WELDED PLATE
SEALED WATERTIGHT
FASTENERS -
(BY OTHERS)
MINIMUM TWO
FASTENERS
WOOD CURB PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
FASTENERS
APPROX. 8'' FLASHING
[200 mm] O.C. MEMBRANE
(8'' [200 mm]
SEALANT MIN. HEIGHT)
(IF REQUIRED
FOR THE THERMOPLASTIC
SPECIFIC ROOF MEMBRANE
SYSTEM)
COVERBOARD
AND THERMAL
INSULATION SEAM PLATES AND
FASTENERS -
ROOF DECK SEE SINGLE PLY
TABLE 7 FOR
ALTERNATE
WOOD NAILERS
PERIMETER
SECUREMENT
OPTIONS
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM ALLOWS FOR
MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION IF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR THE SHEET METAL.
TP-15S
2001 NOT DRAWN TO SCALE
1165
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSULATE VOID TO
PREVENT CONDENSATION
SHEET METAL OR
FLEX-TUBE COLLAR
FLASHING
MINIMUM
HEIGHT
8'' [200 mm]
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
GASKETED FASTENERS
MINIMUM TWO PER SIDE
SHEET METAL
FLASHING RECEIVER
COVERBOARD AND
WOOD NAILERS THERMAL INSULATION
AND CURB
ROOF DECK
THERMOPLASTIC
ROOF MEMBRANE
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL
METHOD OF GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TP-16
2001 NOT DRAWN TO SCALE
1166
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
MINIMUM FLASHING
HEIGHT)
SEALANT (IF REQUIRED
8'' [200 mm]
HEIGHT
ROOF DECK
TP-16S
2001 NOT DRAWN TO SCALE
1167
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
COVER TO STACK
FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE No. 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
WOOD NAILERS COVERBOARD AND
AND CURB THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND STACK, AND THE
NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE SHEET METAL COVER OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TP-17
2001 NOT DRAWN TO SCALE
1168
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC
DRAWBAND OR WELD
SEALANT
COVER TO STACK
FLASHING MEMBRANE
(8'' [200 mm] MIN.
OPTIONAL :
HEIGHT)
REMOVABLE
SHEET METAL
COUNTERFLASHING FASTENERS
SEE NOTE No. 3 MINIMUM TWO
FASTENERS PER SIDE
INSULATE VOID
FOR COLD
STACKS SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECURMENT
OPTIONS
SEALANT (IF REQUIRED
FOR THE SPECIFIC
SYSTEM)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
AND CURB
TP-17S
2001 NOT DRAWN TO SCALE
1169
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MEMBRANE CAP
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. REFER TO THE INTRODUCITON FOR ADDITIONAL INFORMATION.
TP-18
2001 NOT DRAWN TO SCALE
1170
The NRCA Roofing and Waterproofing Manual—Fifth Edition
MEMBRANE CAP
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-18S
2001 NOT DRAWN TO SCALE
1171
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PLUMBING VENT
STACK
SEALANT
DRAWBAND
INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING
PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)
SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
THERMOPLASTIC
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
(PREMANUFACTURED BOOT)
TP-18A
2001 NOT DRAWN TO SCALE
1172
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PLUMBING VENT STACK
SEALANT
DRAWBAND
INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING
PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
ROOF DECK
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
(PREMANUFACTURED BOOT)
TP-18AS
2001 NOT DRAWN TO SCALE
1173
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G., POLYURETHANE)
SHEET METAL RAIN
COLLAR OVERLAPPING DRAW BAND
PENETRATION POCKET
APPROX.
1/4'' [6 mm]
CLEARANCE
AT CORNERS
POURABLE
SEALANT
NON-SHRINK
GROUT
WEATHERPROOF
SOLDERED SHEET METAL OR
MEMBRANE COATED
METAL PITCH PAN
(4'' [100 mm]
MIN. HEIGHT)
COVERBOARD AND
THERMAL INSULATION
BASE MEMBRANE
SECUREMENT AS
REQUIRED FOR
SPECIFIC SYSTEM SEALANT (IF REQUIRED FOR
THE SPECIFIC SYSTEM)
ROOF DECK
THERMOPLASTIC
ROOF MEMBRANE
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TP-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
TP-19
2001 NOT DRAWN TO SCALE
1174
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G., POLYURETHANE)
DRAW BAND
APPROX. 1/4''
[6 mm] CLEARANCE SHEET METAL RAIN
AT CORNERS COLLAR OVERLAPPING
PENETRATION POCKET
COMPATIBLE
SEALANT POURABLE SEALANT
FLASHING
MEMBRANE WEATHERPROOF
SOLDERED SHEET
METAL OR MEMBRANE
COATED METAL PITCH
PAN (4'' [100 mm]
MIN. HEIGHT)
NON-SHRINK GROUT
SEALANT (IF
REQUIRED FOR
THE SPECIFIC 4'' [100 mm]
SYSTEM) MIN. FLANGE
THERMOPLASTIC
ROOF MEMBRANE BASE MEMBRANE
SECUREMENT AS
COVERBOARD AND REQUIRED FOR
THERMAL INSULATION SPECIFIC SYSTEM
ROOF DECK
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TP-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
TP-19S
2001 NOT DRAWN TO SCALE
1175
The NRCA Roofing and Waterproofing Manual—Fifth Edition
COVERBOARD
AND
THERMAL
INSULATION
THERMOPLASTIC
ROOF MEMBRANE
DRAIN STRAINER
ROOF DECK
CLAMPING RING
DECK CLAMP
ROUND CUT IN
THERMOPLASTIC MEMBRANE;
EXTEND APPROX. 1'' [25 mm]
PAST CLAMPING RING
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN
PIPE DIAMETER
DRAIN BOWL
INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE
TAPERED INSULATION
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
TP-20
2001 NOT DRAWN TO SCALE
1176
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAIN STRAINER
CLAMPING RING
THERMOPLASTIC
ROOF MEMBRANE
TAPERED INSULATION
COVERBOARD
AND
THERMAL
INSULATION
ROOF DECK
INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE
DECK CLAMP
DRAIN BOWL
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
TP-20S
2001 NOT DRAWN TO SCALE
1177
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BEAD OF SEALANT
SOLDERED SHEET METAL
]
OR MEMBRANE COATED
0 mm
METAL SCUPPER [10
N.
MI
OPTIONAL: 3/4'' x 3'' 4''
[19 mm x 75 mm] MIN.
''L'' SHAPED GRAVEL
GUARD SECURED AND SEALED
TO THE SCUPPER FLANGE,
NOTCHED TO PERMIT DRAINAGE
SHEET METAL
CONDUCTOR GASKETED FASTENERS
HEAD
SHEET METAL
FASCIA CAP
SUMP TO DRAIN
ADHERED OR WELDED
FLASHING MEMBRANE
(EXTEND APPROX.
3'' [75 mm] BEYOND
SCUPPER)
THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
NOTES :
TP-21
2001 NOT DRAWN TO SCALE
1178
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
FASCIA CAP
SOLDERED SHEET METAL
OR MEMBRANE COATED
METAL SCUPPER
ADHERED OR WELDED
OPTIONAL: 3/4'' x 3'' FLASHING MEMBRANE
[19 mm x 75 mm] MIN. (EXTEND APPROX.
''L'' SHAPED GRAVEL 3'' [75 mm] BEYOND
GUARD SECURED AND SCUPPER)
SEALED TO THE
SCUPPER FLANGE, THERMOPLASTIC
NOTCHED TO PERMIT ROOF MEMBRANE
DRAINAGE
SEALANT (IF REQUIRED
GASKETED
FOR THE SPECIFIC
FASTENERS
SYSTEM)
SHEET
METAL
CONDUCTOR
HEAD
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
EXTEND FIELD SHEET
TO BELOW BLOCKING
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
TP-21S
2001 NOT DRAWN TO SCALE
1179
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SOLDERED
SHEET METAL OR SHEET METAL OR
MEMBRANE COATED MEMBRANE COATED
METAL SCUPPER METAL ''GRAVEL STOP''
SET IN COMPATIBLE SEALANT (AS REQUIRED BY
m m] MANUFACTURER)
OPTIONAL : [1 00
3/4'' x 3'' I N.
4 '' M
[19 mm x 75 mm] SEALANT (IF REQUIRED
MIN. ''L'' SHAPED FOR THE SPECIFIC
GRAVEL GUARD SYSTEM)
SECURED TO THE
SCUPPER FLANGE,
NOTCHED TO
PERMIT DRAINAGE
SHEET METAL
CONDUCTOR
HEAD APPROX.
3'' [75 mm]
THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
TP-21A
2001 NOT DRAWN TO SCALE
1180
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SOLDERED
SHEET METAL OR
MEMBRANE COATED
METAL ''GRAVEL STOP''
(AS REQUIRED BY
MANUFACTURER)
SHEET METAL OR
MEMBRANE COATED
METAL SCUPPER
OPTIONAL :
SEALANT (IF REQUIRED
3/4'' x 3''
FOR THE SPECIFIC
[19 mm x 75 mm]
SYSTEM)
MIN. ''L'' SHAPED
GRAVEL GUARD FLASHING MEMBRANE
SECURED TO THE ADHERED OR WELDED
SCUPPER FLANGE, TO METAL AND FIELD
NOTCHED TO PERMIT MEMBRANE
DRAINAGE
FASTENERS
3'' to 6'' [75 to 150 mm]
O.C., STAGGER
SUMP TO DRAIN
GASKETED
FASTENER
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
THERMOPLASTIC ROOF
MEMBRANE
SHEET METAL
CONDUCTOR HEAD
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
TP-21AS
2001 NOT DRAWN TO SCALE
1181
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
(IF REQUIRED FOR
THE SPECIFIC SYSTEM)
FASTENERS
3'' to 6''
[75 to 150 mm] O.C. OPTION:
STAGGER
SHEET METAL
GUTTER. THE FRONT
OF THE GUTTER
SHOULD BE A MIN.
1'' [25 mm] LOWER
THAN THE BACK TO
ALLOW OVERFLOW
OPTIONAL: GUTTER
BRACKET SUPPORT
WOOD OPTIONAL:
NAILERS STIFFENING BAR
OPTIONAL: CONTINOUS
SEALANT
NOTES:
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TP-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
TP-22
2001 NOT DRAWN TO SCALE
1182
The NRCA Roofing and Waterproofing Manual—Fifth Edition
THERMOPLASTIC ROOF MEMBRANE
FASTENERS AT APPROX.
3'' TO 6'' [75 mm TO 150 mm]
O.C., STAGGER
SEALANT (IF REQUIRED
BY THE SPECIFIC SYSTEM)
SHEET METAL OR
MEMBRANE COATED
METAL EDGE FLASHING
WITH 3'' [75 mm] FLANGE
(AS REQUIRED BY
SPECIFIC SYSTEM)
:
OPTIONAL DRAINAGE
BAR TO RETAIN
BALLAST
ROOF DECK
COVERBOARD AND
THERMAL INSULATION
WOOD NAILERS
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS SHEET METAL GUTTER.
THE FRONT OF THE
OPTIONAL : GUTTER GUTTER SHOULD BE A
BRACKET SUPPORT MINIMUM 1'' [25 mm]
LOWER THAN THE
BACK TO ALLOW
OVERFLOW
NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TP-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
TP-22S
2001 NOT DRAWN TO SCALE
1183
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS APPROX.
12'' [300 mm] O.C. SHEET METAL PARAPET
CAP
EXTEND MEMBRANE
TO BELOW NAILER CONTINUOUS SHIM
AND SECURE
BELOW BLOCKING
GASKETED FASTENERS
1'' [25 mm] MIN.
WOOD NAILER
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
FLASHING MEMBRANE
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
CONTINUOUS CLEAT
FASTENED PER TABLE 1
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TS-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-1
2001 NOT DRAWN TO SCALE
1184
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS SHIM
BELOW BLOCKING
1'' [25 mm] MIN.
WOOD NAILER
GASKETED FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
EXTEND MEMBRANE TO
BELOW NAILER AND SECURE
CONTINUOUS CLEAT
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. EXPANSION
JOINT DETAIL SIMILAR TO DETAIL TP-6 SHOULD BE USED FOR NON-WALL-SUPPORTED DECK.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-1S
2001 NOT DRAWN TO SCALE
1185
The NRCA Roofing and Waterproofing Manual—Fifth Edition
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
BELOW BLOCKING
FASTENERS -
1'' [25 mm] MIN.
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1186
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
BELOW BLOCKING
1'' [25 mm] MIN.
WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1187
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT (IF REQUIRED
FOR THE SPECIFIC SYSTEM)
1 1/2'' [38mm] MIN. FOR
BALLASTED SYSTEMS
1/2'' [13 mm]
MIN. CLEARANCE FLANGE APPROX.
3'' [75 mm] WIDE
2'' [50 mm]
MIN. CLEARANCE APPROX. 3''
[75 mm]
BELOW BLOCKING
1'' [25mm] MIN.
ADHERED
FLASHING MEMBRANE
(EXTEND APPROX. 3''
[75 mm] BEYOND FLANGE)
SHEET METAL
''GRAVEL STOP'' (AS
REQUIRED BY
MANUFACTURER)
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
(FASTENED PER EXTEND FIELD SHEET TO
SINGLE-PLY TABLE 1) BELOW BLOCKING
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-3
2001 NOT DRAWN TO SCALE
1188
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ADHERED FLASHING
EXCEED HEIGHT OF BALLAST
MEMBRANE (EXTEND
APPROX. 3'' [75 mm]
BALLASTED SYSTEMS TO
BEYOND FLANGE)
1 1/2'' [38 mm] MIN. FOR
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
BELOW BLOCKING
ROOF DECK
1'' [25 mm] MIN.
CONTINUOUS CLEAT
(FASTENED PER
SINGLE-PLY TABLE 1)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECURMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-3S
2001 NOT DRAWN TO SCALE
1189
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PERIMETER SHEET
FLANGE APPROX.
METAL FLASHING
3'' [75 mm]
APPROX.
3'' [75 mm]
CONTINUOUS CLEAT
FASTENED PER TABLE 1.
BELOW BLOCKING
1'' [25 mm] MIN.
ADHERED FLASHING
MEMBRANE
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
TS-3A
2001 NOT DRAWN TO SCALE
1190
The NRCA Roofing and Waterproofing Manual—Fifth Edition
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
CONTINUOUS CLEAT
FASTENED PER TABLE 1.
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES
TO BE EMBEDDED OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-3AS
2001 NOT DRAWN TO SCALE
1191
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSTALL APPROPRIATE SEALANT
(E.G., POLYURETHANE) AND
TOOL TO FACILITATE WATER
RUN-OFF
CONCRETE FASTENERS
OPTIONAL :
INSTALL COMPRESSIBLE
ELASTOMERIC SEALANT
OR TAPE TO SPAN IRREGULARITIES
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT OPTIONS
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS
TS-4
2001 NOT DRAWN TO SCALE
1192
The NRCA Roofing and Waterproofing Manual—Fifth Edition
OPTIONAL :
INSTALL COMPRESSIBLE
ELASTOMERIC SEALANT
OR TAPE TO SPAN IRREGULARITIES
CONCRETE FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT OPTIONS
THERMOSET
ROOF MEMBRANE
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
SURFACE-MOUNTED COUNTERFLASHING
FOR CONCRETE WALLS
TS-4S
2001 NOT DRAWN TO SCALE
1193
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE PERIMETER
SECUREMENT OPTIONS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THE JOINTS IN THE SHEET METAL COUNTERFLASHING SHOULD NOT BE SOLDERED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-5
2001 NOT DRAWN TO SCALE
1194
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH SEAM
PLATES AND FASTENERS -
SEE SINGLE PLY
TABLE 7 FOR ALTERNATE
PERIMETER SECUREMENT OPTIONS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THE JOINTS IN THE SHEET METAL COUNTERFLASHING SHOULD NOT BE SOLDERED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-5S
2001 NOT DRAWN TO SCALE
1195
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSTALL COMPATIBLE
SEALANT BEHIND MEMBRANE
FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
WOOD NAILERS
1. THIS DETAIL ACCOMMODATES INDEPENDENT WALL AND DECK MOVEMENT.
2. OTHER METHODS OF COUNTERFLASHING MAY BE APPLICABLE (SEE TABLE 2).
3. THIS DETAIL MAY NOT BE APPLICABLE FOR USE WITH LIGHTWEIGHT FILLS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-6
2001 NOT DRAWN TO SCALE
1196
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
TS-6S
2001 NOT DRAWN TO SCALE
1197
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
FLEXIBLE VAPOR EXPANSION JOINT
RETARDER TO SERVE COVER
AS INSULATION RETAINER FLEXIBLE
(ATTACHED TO TOP WEATHERPROOF
OF CURB) MEMBRANE CLOSURE -
OPTIONAL IF
DOUBLE LOCK
COMPRESSIBLE
STANDING SEAM JOINTS
INSULATION
ARE USED WITH THE
METAL PARAPET CAP
FASTENERS APPROX.
8'' [200 mm] O.C.
8'' [200 mm] MINIMUM
FLASHING HEIGHT
GASKETED FASTENERS
ON LOW SIDE
FLASHING MEMBRANE
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
THERMOSET ROOF
MEMBRANE
TOP OF
CURB TO DRAIN
TO ONE SIDE
WOOD NAILERS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-7
2001 NOT DRAWN TO SCALE
1198
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
FLASHING MEMBRANE
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
8'' [200 mm] MINIMUM
FLASHING HEIGHT
FASTENERS -
ON LOW SIDE
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
TS-7S
2001 NOT DRAWN TO SCALE
1199
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS APPROX.
8'' [200 mm] O.C.
FLASHING MEMBRANE
THERMOSET
ROOF MEMBRANE
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1200
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PREMANUFACTURED
EXPANSION JOINT
COVER
FLEXIBLE
WEATHERPROOF
MEMBRANE CLOSURE
TOP OF CURB
TO DRAIN TO FASTENERS APPROX.
THE OUTSIDE 8'' [200 mm] O.C.
GASKETED FASTENERS
FLASHING MEMBRANE
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
8'' [200 mm] MINIMUM
FLASHING HEIGHT
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
FLEXIBLE VAPOR
RETARDER TO WOOD NAILERS
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB) COMPRESSIBLE
INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1201
The NRCA Roofing and Waterproofing Manual—Fifth Edition
UNREINFORCED
THERMOSET ROOF
MEMBRANE
FASTEN AT
APPROXIMATELY
12'' [300 mm] O.C. ON ONE
SIDE OF EXPANSION JOINT
ONLY TO PERMIT
MOVEMENT
ROOF DECK
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. THIS DETAIL SHOULD ONLY BE USED WITH UNREINFORCED, LOOSE-LAID, BALLASTED SYSTEMS.
2. IF EXPANSION IS GREATER THAN 2'', DETAIL 7A OR 7B ARE PREFERRED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1202
The NRCA Roofing and Waterproofing Manual—Fifth Edition
NOTES :
1. THIS DETAIL SHOULD ONLY BE USED WITH UNREINFORCED, LOOSE-LAID, BALLASTED SYSTEMS.
2. IF EXPANSION IS GREATER THAN 2'', DETAIL 7A OR 7B ARE PREFERRED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1203
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
AREA DIVIDER
COVER
GASKETED
FASTENERS
8'' [200 mm] MINIMUM
FLASHING HEIGHT
FLASHING
MEMBRANE
THERMOSET
ROOF MEMBRANE
REINFORCED MEMBRANE
WOOD NAILERS ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
ROOF DECK
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-8
2001 NOT DRAWN TO SCALE
1204
The NRCA Roofing and Waterproofing Manual—Fifth Edition
REINFORCED MEMBRANE
ATTACHMENT STRIP FLASHING MEMBRANE
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER THERMOSET
SECUREMENT OPTIONS ROOF MEMBRANE
WOOD NAILERS
ROOF DECK
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. AN AREA DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED TO THE ROOF DECK.
AREA DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF THE AREA DIVIDER.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-8S
2001 NOT DRAWN TO SCALE
1205
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
WOOD CURB
WOOD NAILERS
THERMOSET
ROOF MEMBRANE
ROOF DECK
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. THIS DETAIL ALLOWS FOR MEMBRANE MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS
SUPPORT IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE
SPREAD ACROSS TWO OR MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED
OR WHERE THE LOAD CAN BE CONCENTRATED OVER A COLUMN, DETAIL TP-10 MAY BE PREFERRED. A
MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT
OF ROOFING AND FLASHING BETWEEN PARALLEL SUPPORTS. REFER TO THE TABLE ABOVE FOR RECOMMENDATIONS
ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM OF SUPPORTED EQUIPMENT.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS FOR
SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-9
2001 NOT DRAWN TO SCALE
1206
The NRCA Roofing and Waterproofing Manual—Fifth Edition
HEIGHT
WIDTH OF EQUIPMENT OF LEGS
SET BOLTS IN SEALANT
UP TO 24'' [UP TO 600 mm] 24'' [600 mm] (BY OTHERS)
24'' TO 48'' [600 mm TO 1.2 m] 36'' [900 mm]
SET NEOPRENE PAD IN
48'' AND WIDER [1.2 m AND WIDER] 48'' [1.2 m] SEALANT (BY OTHERS)
GASKETED FASTENERS
FLASHING MEMBRANE
REINFORCED MEMBRANE (8'' [200 mm] MIN.
ATTACHMENT STRIP HEIGHT)
WITH SEAM PLATES AND
FASTENERS -
THERMOSET
SEE SINGLE PLY TABLE 7
ROOF MEMBRANE
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
ROOF DECK
TS-9S
2001 NOT DRAWN TO SCALE
1207
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
HEIGHT-
SEE TABLE
LE
AB
E ET
SEE DETAIL -S
TH
TP-11 FOR FLASHING ID
W
OF SUPPORT LEGS
NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL TP-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED
DIRECTLY OVER COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE
ADAPTED FOR OTHER USES, SUCH AS SIGN SUPPORTS.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-10
2001 NOT DRAWN TO SCALE
1208
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
1209
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
FOR HEIGHT OF LEGS
SEE TABLE ON TS-10
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR THE
SPECIFIC SYSTEM
FILL GAPS WITH
INSULATION BOARD
NOTES : TO PROVIDE EVEN
SUBSTRATE
1. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1210
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
RAISED CURB
GASKETED FASTENERS
WOOD NAILER MIN. TWO FASTENERS
PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE
7 FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
ALTERNATE CURB
BEARING LOCATION
FOR HEAVY-WEIGHT THERMOSET
LOADING CONDITIONS ROOF MEMBRANE
FASTENERS NOTES :
WOOD NAILER 1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE
TO BE SUPPLIED BY THE CURB MANUFACTURER.
COUNTERFLASHING
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT
INSULATION BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
FLASHING MEMBRANE 3. REFER TO THE INTRODUCTION FOR ADDITIONAL
INFORMATION.
RAISED CURB 4. REFER TO THE SHEET METAL SECTION OF THE METAL
ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1211
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD NAILER
GASKETED FASTENERS
MIN. TWO FASTENERS
PER SIDE
SEALING MATERIAL
REMOVABLE
RAISED CURB SHEET METAL
COUNTERFLASHING
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SEE SINGLE PLY
TABLE 7 FOR
FLASHING ALTERNATE PERIMETER
MEMBRANE SECUREMENT OPTIONS
(8'' [200 mm]
MIN. HEIGHT)
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
ALTERNATE CURB
BEARING LOCATION
FOR HEAVY WEIGHT
NOTES : LOADING CONDITIONS
1. THE CURBS, TOP WOOD NAILER, AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF MEMBRANE AND FLASHING
HAVE BEEN INSTALLED.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1212
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD CURB
SEALING MATERIAL
WOOD
NAILERS
SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
THERMOSET
MECHANICAL UNIT, HOOD, ETC.
ROOF MEMBRANE
ALTERNATE :
BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND
TOP OF CURB
SEALING MATERIAL - MUST COVERBOARD AND
BE CONTINUOUS ON TOP THERMAL INSULATION
OF THE CURB
ROOF DECK
1'' [25 mm] MINIMUM
BELOW TOP OF CURB
FLASHING RECEIVER
FASTENERS
COUNTERFLASHING
FLASHING MEMBRANE
WOOD CURB
NOTES :
1. THE MECHANICAL UNITS SHOULD NOT BE SET
UNTIL THE ROOF MEMBRANE AND FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1213
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
REMOVABLE
SHEET METAL
COUNTERFLASHING
WOOD CURB
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
NOTES :
1. THE MECHANICAL UNITS SHOULD NOT BE SET
UNTIL THE ROOF MEMBRANE AND FLASHING HAVE BEEN INSTALLED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1214
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MIN. TWO FASTENERS PER
SIDE
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
THERMOSET
ROOF MEMBRANE
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
1. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm],
THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TS-14
2001 NOT DRAWN TO SCALE
1215
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
1. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm],
THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
TS-14S
2001 NOT DRAWN TO SCALE
1216
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSULATE VOID
TO PREVENT
CONDENSATION
WELDED PLATE,
SEALED WATERTIGHT
(BY OTHERS)
FASTENERS -
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
AND CURB
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE AND ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1217
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INSULATE VOID
TO PREVENT
CONDENSATION
WELDED PLATE
SEALED WATERTIGHT
FASTENERS
(BY OTHERS)
MINIMUM TWO
FASTENERS
WOOD CURB PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
FASTENERS
APPROX. 8'' FLASHING
[203 mm] O.C. MEMBRANE
(8'' [200 mm]
MIN. HEIGHT)
THERMOSET
ROOF MEMBRANE
WOOD
NAILERS
REINFORCED MEMBRANE
ATTACHMENT STRIP WITH
SEAM PLATES AND
FASTENERS -
SEE SINGLE PLY TABLE 7
FOR ALTERNATE
PERIMETER SECUREMENT ROOF DECK
OPTIONS
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED SYSTEM
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOF SYSTEM.
2. PENETRATIONS USING H, I, AND C BEAMS/CHANNELS SHOULD BE AVOIDED. SQUARE OR ROUND TUBES ARE PREFERABLE.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1218
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
ENCLOSURE
WITH REMOVABLE TOP
-CROSSBREAK OR
SLOPE FOR DRAINAGE
INSULATE VOID
TO PREVENT
CONDENSATION
SHEET METAL OR
FLEX-TUBE COLLAR
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
OPTIONAL :REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
MIN. 4'' [100 mm] ATTACHMENT STRIP WITH
CLEARANCE FROM SEAM PLATES AND
PIPE TO TOP OF FASTENERS -
CURB - MIN. 2'' SEE SINGLE PLY TABLE 7
[50 mm] BETWEEN FOR ALTERNATE
PIPES PERIMETER SECUREMENT
OPTIONS
SHEET METAL
FLASHING
RECEIVER
THERMOSET
WOOD NAILERS ROOF MEMBRANE
AND CURB
COVERBOARD AND
THERMAL INSULATION
NOTES :
ROOF DECK
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL
METHOD OF GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1219
The NRCA Roofing and Waterproofing Manual—Fifth Edition
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
MINIMUM FLASHING
HEIGHT
FOR ALTERNATE
PERIMETER SECUREMENT
OPTIONS
THERMOSET
ROOF MEMBRANE
WOOD NAILERS
AND CURB THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS
AND AN OPTIONAL METHOD OF GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1220
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
UMBRELLA TO STACK
FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
OPTIONAL : REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE-PLY TABLE 7
FOR ALTERNATE
METAL OR PERIMETER
GYPSUM LINER SECUREMENT OPTIONS
IF REQUIRED
VARIES
THERMOSET
ROOF MEMBRANE
WOOD NAILERS
AND CURB
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE CLEARANCE NECESSARY BETWEEN THE OPTIONAL GYPSUM OR METAL LINER AND THE STACK,
AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL HANDLED BY THE STACK.
3. WHERE THE SHEET METAL COVER OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE
REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
1221
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TEMPERATURE
APPROPRIATE
ELASTOMERIC SEALANT
DRAWBAND OR WELD
UMBRELLA TO STACK
INSULATE VOID FOR
COLD STACKS
FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
REINFORCED MEMBRANE
ATTACHMENT STRIP
WITH SEAM PLATES
AND FASTENERS - SEE
SINGLE-PLY TABLE 7
FOR ALTERNATE
PERIMETER
SECUREMENT OPTIONS
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
AND CURB
1222
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING SEE TABLE 4.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-18
2001 NOT DRAWN TO SCALE
1223
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PIPE PENETRATION
SEALANT
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT)
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
BASE MEMBRANE
ATTACHMENT AS
REQUIRED BY
SPECIFIC SYSTEM
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING SEE TABLE 4.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-18S
2001 NOT DRAWN TO SCALE
1224
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PLUMBING VENT
STACK
SEALANT
DRAWBAND
INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING
PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)
SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
THERMOSET
ROOF MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
(PREMANUFACTURED BOOT)
TS-18A
2001 NOT DRAWN TO SCALE
1225
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
DRAWBAND
INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING
PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm]
MIN. HEIGHT)
BASE MEMBRANE
ATTACHMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
ROOF DECK
COVERBOARD AND
THERMAL INSULATION
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. SEE TABLE 4.
2. NRCA RECOMMENDS FLASHINGS BE 8'' [200 mm] HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
(PREMANUFACTURED BOOT)
TS-18AS
2001 NOT DRAWN TO SCALE
1226
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL RAIN APPROPRIATE SEALANT
COLLAR OVERLAPPING (E.G., POLYURETHANE)
PENETRATION POCKET
DRAW BAND
APPROX.
1/4'' [6 mm] EXTEND 1'' [25 mm]
CLEARANCE MINIMUM INTO PAN
AT CORNERS
4'' [100 mm]
FLASHING MIN. FLANGE
MEMBRANE
BASE MEMBRANE
SECUREMENT AS
REQUIRED FOR
SPECIFIC SYSTEM
POURABLE
SEALANT
NON-SHRINK
GROUT
WEATHERPROOF
SHEET METAL PITCH PAN
SOLDERED/WELDED JOINTS
(4'' [100 mm] MIN. HEIGHT
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
THERMOSET
ROOF MEMBRANE
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TS-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
TS-19
2001 NOT DRAWN TO SCALE
1227
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
(E.G., POLYURETHANE)
DRAW BAND
APPROX. 1/4''
[6 mm] CLEARANCE SHEET METAL RAIN
AT CORNERS COLLAR OVERLAPPING
PENETRATION POCKET
EXTEND 1'' [25 mm]
MINIMUM INTO PAN POURABLE SEALANT
FLASHING
MEMBRANE WEATHERPROOF
SHEET METAL PITCH
PAN WITH SOLDERED/
JOINTS (4'' [100 mm]
MIN. HEIGHT)
NON-SHRINK GROUT
THERMOSET
ROOF MEMBRANE
BASE MEMBRANE
COVERBOARD AND SECUREMENT AS
THERMAL INSULATION REQUIRED FOR
SPECIFIC SYSTEM
ROOF DECK
NOTES :
1. PENETRATION POCKETS ARE NOT THE PREFERRED FLASHING METHOD AT PENETRATIONS BECAUSE THEY MAY BE A
CONSTANT MAINTENANCE PROBLEM. SEE DETAIL TS-11 FOR THE PREFERRED FLASHING METHOD.
2. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PENETRATION POCKET
TS-19S
2001 NOT DRAWN TO SCALE
1228
The NRCA Roofing and Waterproofing Manual—Fifth Edition
COVERBOARD AND
THERMAL INSULATION
THERMOSET
ROOF MEMBRANE
DRAIN STRAINER
ROOF DECK
CLAMPING RING
DECK CLAMP
ROUND CUT IN
THERMOSET MEMBRANE;
EXTEND APPROX. 1'' [25 mm]
PAST CLAMPING RING
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN
PIPE DIAMETER
DRAIN BOWL
INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE
TAPERED INSULATION
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
TS-20
2001 NOT DRAWN TO SCALE
1229
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAIN STRAINER
CLAMPING RING
THERMOSET
ROOF MEMBRANE
TAPERED INSULATION
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
INSTALL COMPATIBLE
SEALANT BETWEEN DRAIN BOWL
FLANGE AND ROOF MEMBRANE
DECK CLAMP
DRAIN BOWL
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
TS-20S
2001 NOT DRAWN TO SCALE
1230
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BEAD OF SEALANT
m m]
OPTIONAL: 3/4'' x 3'' 00
[19 mm x 75 mm] MIN. . [1
M IN
''L'' SHAPED GRAVEL 4''
GUARD SECURED AND
SEALED TO THE SCUPPER
FLANGE, NOTCHED
TO PERMIT DRAINAGE
GASKETED FASTENERS
ADHERED OR WELDED
FLASHING MEMBRANE
(EXTEND APPROX.
3'' [75 mm] BEYOND
SCUPPER)
THERMOPLASTIC ROOF
MEMBRANE
COVERBOARD AND
EXTEND FIELD SHEET THERMAL INSULATION
TO BELOW BLOCKING
ROOF DECK
WOOD NAILERS
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
TS-21
2001 NOT DRAWN TO SCALE
1231
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
FASCIA CAP
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
GASKETED
WOOD NAILERS
FASTENERS
EXTEND FIELD SHEET
TO BELOW BLOCKING
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
TS-21S
2001 NOT DRAWN TO SCALE
1232
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
CONDUCTOR
HEAD
APPROX.
3'' [75 mm]
THERMOSET ROOF
MEMBRANE
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
WOOD NAILERS
TS-21A
2001 NOT DRAWN TO SCALE
1233
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
''GRAVEL STOP''
ADHERED FLASHING
MEMBRANE BONDED TO
METAL AND FIELD
MEMBRANE
OPTIONAL :
3/4'' x 3'' FASTENERS AT APPROX.
[19 mm x 75 mm] 3'' TO 6'' [75 TO 150 mm]
MIN. ''L'' SHAPED O.C., STAGGER
GRAVEL GUARD
SECURED TO THE
SUMP TO DRAIN
SCUPPER FLANGE,
NOTCHED TO PERMIT
DRAINAGE
GASKETED
FASTENER
COVERBOARD AND
THERMAL INSULATION
ROOF DECK
THERMOSET ROOF
MEMBRANE
SHEET METAL
CONDUCTOR HEAD
NOTES :
1. ROOF SURFACES SHOULD BE SLOPED TO DRAIN.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
TS-21AS
2001 NOT DRAWN TO SCALE
1234
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
(IF REQUIRED FOR
THE SPECIFIC SYSTEM)
FASTENERS
3'' to 6''
[75 to 150 mm] O.C.
STAGGER OPTION:
GUTTER SPACERS
INSTALLED BETWEEN
GUTTER BRACKETS
SHEET METAL
GUTTER. THE FRONT
OF THE GUTTER
SHOULD BE A MIN.
1'' [25 mm] LOWER
THAN THE BACK TO
ALLOW OVERFLOW
OPTIONAL : GUTTER
BRACKET SUPPORT
WOOD OPTIONAL:
NAILERS STIFFENING BAR
OPTIONAL: CONTINUOUS
SEALANT
NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TP-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
TS-22
2001 NOT DRAWN TO SCALE
1235
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ROOF
DECK
COVERBOARD
AND THERMAL
INSULATION
NOTES :
1. IN CLIMATES WHERE THE WINTER TEMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF
TIME, NRCA SUGGESTS USING TS-2 AND INTERIOR DRAINS OR SCUPPERS THROUGH THE ROOF EDGE TO
DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY SECURMENT OPTIONS FOR
SHEET METAL.
5. ON BALLASTED SYSTEMS, A DRAINAGE BAR TO RETAIN BALLAST IS REQUIRED.
GUTTER
TS-22S
2001 NOT DRAWN TO SCALE
1236
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD NAILER
CONTINUOUS SHIM
CONTINUOUS CLEAT
FASTENED PER
TABLE 1 EXTENDED BASE FLASHING
GASKETED FASTENERS
EXTENDED BASE FLASHING -
OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS ARE
USED WITH THE METAL
PARAPET CAP
FASTENERS APPROX.
8'' [200 mm] O.C.
1'' [25 mm] MIN.
BELOW BLOCKING
AGGREGATE BALLAST
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)
MULTIPLE-PLY MEMBRANE
BASE FLASHING FEATHERED
AT FIELD OF ROOF
MULTIPLE-PLY BUILT-UP
CANT ROOF MEMBRANE
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL. DETAIL BUR-4
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. IN LIEU OF EXTENDED BASE FLASHING, INSTALL CONTINUOUS SHEET MEMBRANE LINER.
3. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
4. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
6. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1237
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
AGGREGATE BALLAST
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)
NOTES :
1. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURER'S RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/ OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. WHERE THE SHEET METAL ENCLOSURE OVERLAPS THE BASE FLASHING AT LEAST 3'' [75 mm], THE REMOVABLE
SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
5. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
BUR-P-14
2001 NOT DRAWN TO SCALE
1238
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TOP OF FLASHING
CAPPED OR ROLLED
INTO PIPE APPROX.
1'' [25 mm] MIN.
SOFT METAL PIPE
FLASHING (SEE
NOTE 1)
PLUMBING VENT
STACK TO EXTEND A
MINIMUM OF 8''
[200 mm] ABOVE TOP
OF INSULATION
SURFACE
AGGREGATE BALLAST
GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)
ROOF DECK
COMPATIBLE ROOF
CEMENT OR COMPATIBLE EXTRUDED
SEALANT AT PENETRATION POLYSTYRENE
TO MEMBRANE JUNCTURE INSULATION (2''
SET FLANGE IN [50 mm] MIN.)
COMPATIBLE POLYETHYLENE SLIP
ROOF CEMENT SHEET (4 MIL MIN.)
MULTIPLE-PLY BUILT-UP MULTIPLE MEMBRANE
ROOF MEMBRANE STRIPPING PLIES
FEATHERED AT FIELD
NOTES : OF ROOF - PRIME
FLANGE BEFORE
1. SOFT METAL PIPE FLASHING:
- SHEET LEAD: MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m2 ] OR STRIPPING
2
- SHEET COPPER: MINIMUM 16 OZ. [5 kg/m ].
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SLIP SHEET (E.G., ASPHALT-SATURATED
ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT CONTACT WITH
PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
4. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
5. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
6. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
BUR-P-18
2001 NOT DRAWN TO SCALE
1239
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER
AGGREGATE
BALLAST
GEOTEXTILE FABRIC
EXTRUDED
POLYSTYRENE
(2'' [50 mm] MIN.)
MULTIPLE MEMBRANE
STRIPPING PLIES
FEATHERED AT
FIELD OF ROOF
ROOF DECK
DECK CLAMP
DRAIN BOWL
CLAMPING RING
MEMBRANE FIELD PLIES, METAL
FLASHING, AND STRIPPING PLIES COMPATIBLE
ALL EXTEND UNDER CLAMPING RING ROOF CEMENT
30'' [750 mm] SQ. MIN. - 2 1/2 LB. TO 4 LB. MULTIPLE-PLY BUILT-
[12.2 TO 19.5 kg/m 2 ] LEAD OR 16 OZ. UP ROOF MEMBRANE
[4.9 kg/m 2 ] COPPER FLASHING SET ON FINISHED
POLYETHYLENE
ROOF IN COMPATIBLE ROOF CEMENT, PRIME TOP
SLIP SHEET
SURFACE BEFORE STRIPPING
(4 MIL MIN.) CUT
OUTSIDE OF THE
CLAMPING RING
NOTES :
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
4. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
BUR-P-20
2001 NOT DRAWN TO SCALE
1240
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD NAILER
CONTINUOUS SHIM
CONTINUOUS CLEAT
FASTENED PER
TABLE 1
FASTENERS APPROX.
8'' [200 mm] O.C.
1'' [25 mm] MIN.
BELOW BLOCKING
AGGREGATE BALLAST
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)
MODIFIED BITUMEN
MEMBRANE BASE FLASHING
FEATHERED AT FIELD OF
ROOF
MULTIPLE-PLY MODIFIED
CANT BITUMEN ROOF MEMBRANE
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL. DETAIL MB-4
MAY BE USED AS AN EXAMPLE FOR NON-WALL SUPPORTED DECK CONDITION.
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1241
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
AGGREGATE BALLAST
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm] MIN.)
MULTIPLE-PLY MODIFIED
ROOF DECK
BITUMEN ROOF MEMBRANE
NOTES :
1. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURER'S RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/ OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHT, SCUTTLE, OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING
AT LEAST 3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
MB-P-14
2001 NOT DRAWN TO SCALE
1242
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TOP OF FLASHING
CAPPED OR ROLLED
INTO PIPE APPROX.
1'' [25 mm] MIN.
PLUMBING VENT
STACK TO EXTEND A
MINIMUM OF 8''
[200 mm] ABOVE TOP
OF INSULATION
SURFACE
AGGREGATE BALLAST
GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)
4'' MIN. FLANGE
[100 mm]
ROOF DECK
COMPATIBLE ROOF
CEMENT OR COMPATIBLE EXTRUDED
SEALANT AT PENETRATION POLYSTYRENE
TO MEMBRANE JUNCTURE INSULATION (2''
[50 mm] MIN.)
SET FLANGE IN COMPATIBLE
ROOF CEMENT POLYETHYLENE
SLIP SHEET
MULTIPLE-PLY MODIFIED (4 MIL MIN.)
BITUMEN ROOF MEMBRANE
MODIFIED BITUMEN
MEMBRANE STRIPPING
NOTES : PLY - PRIME FLANGE
1. SOFT METAL PIPE FLASHING: BEFORE STRIPPING
2
- SHEET LEAD: MINIMUM OF 2 1/2 LB. PER SQUARE FOOT [12 kg/m ] OR
2
- SHEET COPPER: MINIMUM 16 OZ. [5 kg/m ].
2. IF USING COPPER FLASHING OVER AN IRON OR STEEL PIPE, INSERT A SLIP SHEET (E.G., ASPHALT-
SATURATED ROOFING FELT), WRAPPED AROUND PIPE, TO SEPARATE THE COPPER FLASHING FROM DIRECT
CONTACT WITH PIPE, TO REDUCE GALVANIC ACTION.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
4. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
5. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
6. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
MB-P-18
2001 NOT DRAWN TO SCALE
1243
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER
AGGREGATE
BALLAST
GEOTEXTILE FABRIC
EXTRUDED
POLYSTYRENE
(2'' [50 mm] MIN.)
MODIFIED BITUMEN
MEMBRANE STRIPPING PLY
ROOF DECK
DECK CLAMP
DRAIN BOWL
CLAMPING RING
MEMBRANE FIELD PLIES, METAL COMPATIBLE
FLASHING, AND STRIPPING PLIES ROOF CEMENT
ALL EXTEND UNDER CLAMPING RING MULTIPLE-PLY
30'' [750 mm] SQ. MIN. - 2 1/2 LB. TO 4 LB. MODIFIED BITUMEN
[12.2 TO 19.5 kg/m 2 ] LEAD OR 16 OZ. ROOF MEMBRANE
[4.9 kg/m 2 ] COPPER FLASHING SET ON FINISHED POLYETHYLENE
ROOF IN COMPATIBLE ROOF CEMENT, PRIME TOP SLIP SHEET
SURFACE BEFORE STRIPPING (4 MIL MIN.) CUT
OUTSIDE OF THE
NOTES :
CLAMPING RING
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
4. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
MB-P-20
2001 NOT DRAWN TO SCALE
1244
The NRCA Roofing and Waterproofing Manual—Fifth Edition
EXTEND MEMBRANE TO
BELOW NAILER AND SECURE
FASTENERS APPROX.
12'' [300 mm] O.C.
CONTINUOUS SHIM
WOOD NAILER
CONTINUOUS
CLEAT FASTENED
PER TABLE 1
SHEET METAL
PARAPET CAP
GASKETED FASTENERS
FLASHING MEMBRANE
SLIP SHEET (IF REQUIRED
FOR THE SPECIFIC SYSTEM.)
GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
BELOW BLOCKING
AGGREGATE BALLAST
1'' [25 mm] MIN.
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)
THERMOPLASTIC ROOF
MEMBRANE
SLIP SHEET (IF REQ'D. FOR
THE SPECIFIC SYSTEM)
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. DETAIL TP-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1245
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)
GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
AGGREGATE BALLAST
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)
THERMOPLASTIC ROOF
MEMBRANE
SLIP SHEET (IF REQ'D. FOR
THE SPECIFIC SYSTEM)
ROOF DECK
NOTES :
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHT, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST
3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TP-P-14
2001 NOT DRAWN TO SCALE
1246
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PLUMBING VENT
STACK
SEALANT
OPTIONAL: DRAWBAND
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)
AGGREGATE BALLAST
GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)
SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
EXTRUDED
POLYSTYRENE
INSULATION
(2'' [50 mm] MIN.)
SLIP SHEET
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
BASE MEMBRANE
ATTACHMENT AS REQUIRED
THERMOPLASTIC
FOR SPECIFIC SYSTEM
ROOF MEMBRANE
SLIP SHEET
ROOF DECK
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
TP-P-18
2001 NOT DRAWN TO SCALE
1247
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER
ROOF DECK
AGGREGATE
BALLAST
GEOTEXTILE
FABRIC
EXTRUDED
POLYSTYRENE INSULATION
(2'' [50 mm] MIN.)
THERMOPLASTIC
ROOF MEMBRANE
CLAMPING RING
DECK CLAMP
DRAIN BOWL
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN SLIP SHEET (IF
PIPE DIAMETER REQUIRED FOR THE
SPECIFIC SYSTEM)
INSTALL COMPATIBLE SEALANT
BETWEEN DRAIN BOWL FLANGE SLIP SHEET
AND ROOF MEMBRANE (IF REQUIRED FOR THE
SPECIFIC SYSTEM)
NOTES : CUT OUTSIDE OF THE
CLAMPING RING
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED
HOWEVER, DRAIN RECEIVER/ BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
TP-P-20
2001 NOT DRAWN TO SCALE
1248
The NRCA Roofing and Waterproofing Manual—Fifth Edition
EXTEND MEMBRANE TO
BELOW NAILER AND SECURE
FASTENERS APPROX.
12'' [300 mm] O.C.
CONTINUOUS SHIM
WOOD NAILER
CONTINUOUS
CLEAT FASTENED
PER TABLE 1
SHEET METAL
PARAPET CAP
GASKETED FASTENERS
FLASHING MEMBRANE
GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
BELOW BLOCKING
1'' [25 mm] MIN.
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)
THERMOSET ROOF
MEMBRANE
SLIP SHEET (IF REQ'D. FOR
THE SPECIFIC SYSTEM)
ROOF DECK
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL. DETAIL TS-6
SHOULD BE USED FOR NON-WALL SUPPORTED DECK.
2. OPTION: IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT
OPTIONS FOR SHEET METAL.
5. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
1249
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MINIMUM TWO FASTENERS
PER SIDE
OPTIONAL: REMOVABLE
SHEET METAL
COUNTERFLASHING
SEE NOTE 3
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)
GEOTEXTILE FABRIC
(EXTEND ABOVE BALLAST)
AGGREGATE BALLAST
EXTRUDED POLYSTYRENE
INSULATION (2'' [50 mm]
MIN.)
THERMOSET ROOF
MEMBRANE
NOTES :
1. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
2. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
3. WHERE THE SKYLIGHTC, SCUTTLE OR SMOKE VENT FRAME OVERLAPS THE BASE FLASHING AT LEAST
3'' [75 mm], THE REMOVABLE SHEET METAL COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
TS-P-14
2001 NOT DRAWN TO SCALE
1250
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PLUMBING VENT
STACK
SEALANT
FLASHING MEMBRANE
(8'' [200 mm] MIN.
HEIGHT ABOVE TOP OF
INSULATION SURFACE)
AGGREGATE BALLAST
GEOTEXTILE FABRIC
(EXTEND ABOVE
BALLAST)
SEALANT
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
EXTRUDED
POLYSTYRENE
INSULATION
(2'' [50 mm] MIN.)
SLIP SHEET
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
BASE MEMBRANE
ATTACHMENT AS REQUIRED
THERMOSET
FOR SPECIFIC SYSTEM
ROOF MEMBRANE
SLIP SHEET
ROOF DECK
(IF REQUIRED FOR THE
SPECIFIC SYSTEM)
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING. (SEE TABLE 4.)
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY
BE USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
PLUMBING VENT
TS-P-18
2001 NOT DRAWN TO SCALE
1251
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CUT INSULATION
BOARDS AND FABRIC
TO ALLOW ACCESS
TO DRAIN
DRAIN STRAINER
CONCRETE PAVER OR
GRAVEL RETAINER
ROOF DECK
AGGREGATE
BALLAST
GEOTEXTILE
FABRIC
EXTRUDED
POLYSTYRENE INSULATION
(2'' [50 mm] MIN.)
THERMOSET
ROOF MEMBRANE
CLAMPING RING
DECK CLAMP
DRAIN BOWL
HOLE IN MEMBRANE SHOULD
BE LARGER THAN DRAIN SLIP SHEET (IF
PIPE DIAMETER REQUIRED FOR THE
SPECIFIC SYSTEM)
INSTALL COMPATIBLE SEALANT
BETWEEN DRAIN BOWL FLANGE SLIP SHEET
AND ROOF MEMBRANE (IF REQUIRED FOR THE
SPECIFIC SYSTEM)
NOTES : CUT OUTSIDE OF THE
CLAMPING RING
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED
HOWEVER, DRAIN RECEIVER/ BEARING PLATES ARE APPLICABLE WITH SOME PROJECTS.
2. IN LIEU OF AGGREGATE SURFACING, CONCRETE PAVERS OR CEMENTITIOUS-FACED INSULATION MAY BE
USED. THE MEMBRANE AND SURFACING MANUFACTURERS' RECOMMENDATIONS SHOULD BE CONSULTED.
3. THERMAL INSULATION UNDER THE MEMBRANE SYSTEM MAY BE REQUIRED DEPENDING ON THE DECK TYPE
AND/OR THERMAL REQUIREMENTS.
4. PAVERS, GEOTEXTILE FABRIC, INSULATION AND SLIP SHEET SHALL BE CUT BACK TO ALLOW FOR
THE REMOVAL OF THE DRAIN STRAINER.
5. IN SOME CLIMATES INSULATION AND PAVERS ARE EXTENDED OVER THE DRAIN AND A 1/2'' GALV.
HARDWARE CLOTH STRAINER IS LAID IN THE BOTTOM OF THE BOWL.
6. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
7. REFER TO THE INTRODUCTION FOR ADDITIONAL INFORMATION.
ROOF DRAIN
TS-P-20
2001 NOT DRAWN TO SCALE
1252
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003-H14) COPPER
STEEL
SAME GAUGE
UP TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL
SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL
ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
''A''
''A'' APPROX. 3''
FLANGE
GASKETED FASTENERS ''A''
(APPROX. 18'' O.C.
DEPENDING UPON WIND
ZONE AND LOCAL
CONDITIONS.)
3/4''
3/4'' 3/4''
1253
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003-H14) COPPER
STEEL
UP TO 2
1.02 mm 6.10 kg/m .64 mm .61 mm NOT REQUIRED
75 mm FACE
UP TO 2 SAME GAUGE
.81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL
75 mm FACE
75 mm TO 2 SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
''A''
''A'' APPROX. 75 mm
FLANGE
GASKETED FASTENERS ''A''
1254
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
APPROPRIATE SEALANT
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
1255
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
APPROPRIATE FASTENERS
24'' [600 mm] O.C.
OPTIONAL : SEALANT OR
ELASTOMERIC TAPE
TWO PIECE SURFACE MOUNTED REGLET
AND COUNTERFLASHING
C
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.
OPTIONAL : SEALANT OR
ELASTOMERIC TAPE
1256
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BUILDING PAPER
(IF REQUIRED)
WALL CLADDING
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
1257
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS CLEATS
''
OPTIONAL METAL
/4 FLANGE EXTENSION
.3
ROX
P
AP
''
3 /4
X.
PRO
TYPICAL AP
CLEAT ENGAGEMENT
APPROPRIATE FASTENERS
FASTENED APPROX. 6''
[150 mm] O.C.
. CONTINUOUS CLEAT
M IN
m m] APPROPRIATE FASTENERS
[50 FASTENED APPROX. 6''
2''
[150 mm] O.C.
1258
The NRCA Roofing and Waterproofing Manual—Fifth Edition
2'-
0''
MI [600
NI
MU mm]
M
[ 12
CL 300 m ''
E
MI AR m]
NI AN
MU C
M E 12
[
CL 300 m ''
MI EAR m] 12
'' ]
NI AN
MU C 0 mm NCE
M E 12 [30 ARA UM
[ E IM
CL 300 m '' CL MIN
E
MI AR m]
NI AN
MU C
M E
1259
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SUMPED
ROOF DRAIN
CURBED
PENETRATION
SADDLE
SL
OP
E
SLO
PE
SUMPED
ROOF DRAIN
CANT
CRICKET
NOTES :
1. SADDLES SHOULD BE LOCATED IN VALLEYS ROOF DRAINS AND CRICKETS ON THE HIGH SIDE OF CURBS.
2. LOCATE ROOF DRAINS AT POINTS OF MAXIMUM DECK DEFLECTION / LOW AREAS FOR DRAINAGE.
TABLE 5
2001 NOT DRAWN TO SCALE
1260
The NRCA Roofing and Waterproofing Manual—Fifth Edition
RAISED
PERIMETER EDGE
CURBED
PENETRATION
CRICKET
THROUGH EDGE
SCUPPER
SHEET METAL
CONDUCTOR
HEAD
SL
OP
E
CANT
CRICKET
NOTES :
1. SADDLE SHOULD BE LOCATED BETWEEN THROUGH-EDGE OR WALL SCUPPERS AND CRICKETS ON THE HIGH SIDE OF CURBS.
2. RAISED PERIMETER EDGES WHERE TAPERED CRICKETS ARE USED NECESSITATE THE SPECIFICATION OF RELATIVELY WIDE
(TALL) DIMENSIONAL LUMBER OR THE ERECTION OF FRAMED WALLS.
1261
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT SEALANT
(IF REQUIRED) (IF REQUIRED)
FLASHING FLASHING
MEMBRANE MEMBRANE
REINFORCED REINFORCED
MEMBRANE MEMBRANE
ATTACHMENT ATTACHMENT
STRIP STRIP
SEAM PLATE AND SEAM PLATE AND
FASTENER FASTENER
ROOF MEMBRANE
FIELD SHEET
ROOF MEMBRANE
FIELD SHEET
1262
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
(IF REQUIRED)
SEALANT
(IF REQUIRED)
FLASHING
FLASHING MEMBRANE
MEMBRANE
SEALANT
(IF REQUIRED)
MEMBRANE COATED
METAL FLASHING
FLASHING
MEMBRANE SEALANT
(IF REQUIRED)
BEVELED WOOD
FASTENING STRIP FLASHING
(3/4'' x 2 3/4'' MEMBRANE
[19 mm x 70 mm]
MINIMUM DECAY
RESISTANT TREATED)
FASTENERS AT 12''
FASTENERS AT
[300 mm] O.C. (MIN.)
APPROX. 4''
[100 mm] O.C.
ROOF MEMBRANE
STAGGERED
FIELD SHEET
ROOF MEMBRANE
FIELD SHEET
OPTION 4 : OPTION 5 :
WOOD STRIP MEMBRANE COATED
SECURED TO WALL METAL FLASHING
(THERMOSET ONLY) (THERMOPLASTIC ONLY)
1263
The NRCA Roofing and Waterproofing Manual—Fifth Edition
1
RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL
SAME GAUGE
UP TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL
SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL
ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
''A''
''A'' MIN. 3''
FLANGE
GASKETED FASTENERS ''A''
(APPROX. 18'' O.C.
DEPENDING UPON WIND
ZONE AND LOCAL
CONDITIONS.)
3/4''
3/4'' 3/4''
1264
The NRCA Roofing and Waterproofing Manual—Fifth Edition
1
RECOMMENDED MINIMUM GAUGES FOR FASCIA AND CLEAT
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL
UP TO 2
1.02 mm 6.10 kg/m .64 mm .61 mm NOT REQUIRED
75 mm FACE
UP TO 2 SAME GAUGE
.81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL
75 mm FACE
75 mm TO 2 SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
''A''
''A'' APPROX. 75 mm
FLANGE
GASKETED FASTENERS ''A''
(APPROX. 450 mm O.C.
DEPENDING UPON WIND
ZONE AND LOCAL
CONDITIONS.)
20 mm
20 mm 20 mm
1265
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
APRON FLASHING
WITH HEMMED EDGE
SEALANT
SHEET METAL
COUNTERFLASHING
(SEE NOTE No.1)
RAGGLE
UNDERLAYMENT
TURNED UP WALL
SHEET METAL
STEP FLASHING
SOLDER OR
SEAL CORNERS
ASPHALT
SHINGLES
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT
AND JOINERY OPTIONS FOR SHEET METAL.
APRON FLASHING
ASPH-1
2001 NOT DRAWN TO SCALE
1266
The NRCA Roofing and Waterproofing Manual—Fifth Edition
UNDERLAYMENT
TURNED UP WALL
SIDING TO
COUNTERFLASH
STEPFLASHING
A MIN. 2'' [50 mm]
(SEE NOTE 1)
APPROX. 4'' [100 mm]
SHEET METAL
STEPFLASHING
FOR EACH COURSE
OF SHINGLES
BUILDING PAPER
ASPHALT SHINGLES
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
SIDEWALL FLASHING
ASPH-2
2001 NOT DRAWN TO SCALE
1267
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
COUNTERFLASHING
ASPHALT SHINGLES
STRIPPING PLY
SHEET METAL
BACKER FLASHING
UNDERLAYMENT
SECTION :
SEALANT
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
SHEET METAL
BACKER FLASHING
ASPHALT
SHINGLES
6'' [150 mm] MIN.
SOLDER OR
SEAL CORNERS
UNDERLAYMENT
STRIPPING PLY
ADHERED TO
UNDERLAYMENT
(SEE NOTE 3)
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING PLY IS NOT USED, UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.
BACKER FLASHING
ASPH-3
2001 NOT DRAWN TO SCALE
1268
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHINGLE OVER
STEP FLASHING
SHEET METAL AND UNDER SHEET
BACKER FLASHING METAL BACKER
FLASHING
SHEET METAL
STEP FLASHING
UNDER SHEET
METAL BACKER
FLASHING
NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.
BACKER FLASHING
ASPH-3A
2001 NOT DRAWN TO SCALE
1269
The NRCA Roofing and Waterproofing Manual—Fifth Edition
L-TYPE
EDGE METAL ICE DAM PROTECTION
FLASHING MEMBRANE
EDGE METAL
FLASHING
OPTION :
ALTERNATE :
ASPHALT SHINGLE
STARTER COURSE
ASPH-4
2001 NOT DRAWN TO SCALE
1270
The NRCA Roofing and Waterproofing Manual—Fifth Edition
UNDERLAYMENT
OPTIONAL STRIPPING
PLY
GUTTER
ALTERNATE :
1 PIECE GUTTER
ASPHALT
SHINGLES
''T'' TYPE EDGE
ASPHALT SHINGLE
METAL FLASHING
STARTER COURSE
GUTTER UNDERLAYMENT
NOTES :
1. UNDERLAYMENT CAN BE INSTALLED ON TOP OF OR UNDER THE EAVE EDGE METAL FLASHING DEPENDING
ON CLIMATIC CONDITIONS.
2. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DAPENDING ON CLIMATIC CONDITIONS.
3. THIS DETAIL SHOWS ONE TYPE OF GUTTER SUPPORT. GUTTER SECUREMENT AND SUPPORT OPTIONS VARY ACCORDING
TO REGIONAL PRACTICES AND MANUFACTURERS SPECIFICATIONS.
ASPH-5
2001 NOT DRAWN TO SCALE
1271
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SLOPE
LAP VALLEY
METAL 8''
[200 mm] MIN. AND
SET IN SEALANT
VALLEY METAL
18'' [450 mm]
WIDE MIN.
EXTEND SHINGLES
4'' [100 mm] MIN. OVER VALLEY
VALLEY METAL UNDERLAYMENT
(SEE NOTE 2)
TRIM CORNER
ASPHALT SHINGLES
OF SHINGLES
NOTES:
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. SHINGLES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.
4. FOR CLIPPED VALLEY DETAIL (''ALTERNATE''), HEAVIER WEIGHT SHINGLES MUST BE USED.
OPEN VALLEY
ASPH-6
2001 NOT DRAWN TO SCALE
1272
The NRCA Roofing and Waterproofing Manual—Fifth Edition
EXTEND SHINGLE
12'' [600 mm] MIN. VALLEY UNDERLAYMENT
BEYOND CENTER
OF VALLEY KEEP NAILS 6'' [150 mm]
MIN. FROM CENTER OF
TRIM CORNER VALLEY
OF SHINGLES
ASPHALT SHINGLES
OPTIONAL :
COMPATIBLE
SEALANT
NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. THE CUT SIDE OF THE VALLEY SHOULD BE ON THE SIDE WITH THE GREATEST AREA.
ASPH-7
2001 NOT DRAWN TO SCALE
1273
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PRE-FABRICATED
FLASHING
ASPHALT
SHINGLES
OPTION :
METAL
FLASHING SLEEVE
ASPHALT
SHINGLES
OPTIONAL :
SEALANT UNDER
SHINGLES
PIPE PENETRATION
ASPH-8
2001 NOT DRAWN TO SCALE
1274
The NRCA Roofing and Waterproofing Manual—Fifth Edition
IN LIEU OF LEAD
FLASHING, CHANNEL
FLASHING TO BE
ELEVATED TO
MATCH HEIGHT OF
APRON FLASHING
SHEET METAL ALTERNATE : SOLDER ALL JOINTS
APRON FLASHING
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
SEALANT RAGGLE
SHEET METAL
CHANNEL FLASHING
UNDERLAYMENT
TURNED UP WALL
LEAD WITH
UPTURNED OUTER
EDGE
PANS FILLED WITH
MORTAR OR CLOSURE TILE
UNDER SHEET METAL
APRON FLASHING
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT AND JOINERY
OPTIONS FOR SHEET METAL.
APRON FLASHING
TILE-1
2001 NOT DRAWN TO SCALE
1275
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
SHEET METAL
CHANNEL FLASHING
HALF TILE
TILE
RAGGLE
ROOF DECK
UNDERLAYMENT
TURNED UP WALL
BATTENS
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. METAL CHANNEL FLASHING SHOULD BE CONTINUOUS ALONG LENGTH OF WALL.
3. WIDTH OF METAL CHANNEL FLASHING VARIES DEPENDING UPON TILE LAYOUT.
SIDEWALL FLASHING
TILE-2
2001 NOT DRAWN TO SCALE
1276
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
COUNTERFLASHING
TILE
STRIPPING PLY
EAVE CLOSURE
SHEET METAL
BACKER FLASHING
UNDERLAYMENT
SECTION :
SEALANT
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
METAL BACKER
FLASHING
TILE
STRIPPING PLY
ADHERED TO
UNDERLAYMENT
(SEE NOTE 2)
BATTENS
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING IS NOT USED, UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.
BACKER FLASHING
TILE-3
2001 NOT DRAWN TO SCALE
1277
The NRCA Roofing and Waterproofing Manual—Fifth Edition
EAVE
CLOSURE
BATTENS
SOLDER OR
SEAL CORNER
SHEET METAL
BACKER FLASHING
TILE
HALF TILE
SHEET METAL
CHANNEL FLASHING
NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON WIDTH, SLOPE
AND CLIMATIC CONDITIONS.
BACKER FLASHING
TILE-3A
2001 NOT DRAWN TO SCALE
1278
The NRCA Roofing and Waterproofing Manual—Fifth Edition
OPTION :
WEEP HOLES
EAVE CLOSURE
UNDERLAYMENT
NOTES :
1. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
2. SHIMS SHOULD BE USED WHEN BATTEN LENGTHS ARE GREATER THAN 4'-0'' [1.2 m].
3. SHIMS ALSO MAY BE USED UNDER BATTENS TO ENHANCE DRAINAGE.
EAVE FLASHING
TILE-4
2001 NOT DRAWN TO SCALE
1279
The NRCA Roofing and Waterproofing Manual—Fifth Edition
HALF TILE AT
RAKE
UNDERLAYMENT
RAKE TILE
RAKE TILE
FASTENERS
BATTENS
FASCIA BOARD OR
ROOF DECK BARGE RAFTER
UNDERLAYMENT
NOTES :
1. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
TILE-5
2001 NOT DRAWN TO SCALE
1280
The NRCA Roofing and Waterproofing Manual—Fifth Edition
HEMMED EDGE
BOTH SIDES
METAL CLIP
APPROX. 2''
[50 mm] WIDE
BEND CLIP BACK
OVER TO COVER
FASTENERS,
2 FASTENERS
PER CLIP
ALTERNATE :
CONTINUOUS
STRIPPING PLY
SLOPE
WIDE MIN.
VALLEY UNDERLAYMENT
LAP VALLEY METAL
8'' [200 mm] MIN. AND
SET IN SEALANT
MORTAR FILL
OPENING ALONG
VALLEY CUTS
TILE
EAVE
CLOSURE
NOTES :
BATTENS
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. TILES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.
OPEN VALLEY
TILE-6
2001 NOT DRAWN TO SCALE
1281
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PRIMARY FLASHING
AT TILE - COPPER
OR LEAD
SECONDARY METAL
FLASHING AT
DECK LEVEL
NOTES :
1. ROOF DECK, UNDERLAYMENT, AND BATTENS NOT SHOWN FOR CLARITY.
TILE-7
2001 NOT DRAWN TO SCALE
1282
The NRCA Roofing and Waterproofing Manual—Fifth Edition
EAVE CLOSURE
WHERE TILE IS
SECTION : OMITTED
METAL FLASHING
EXTENDS UPSLOPE
SO A 3'' [75 mm]
LAP IS ACHIEVED
TURNED UP
EDGES OF
METAL FLASHING
UNDERLAYMENT LAPS
OVER UP SLOPE
FLANGE OF FLASHING
METAL FLASHING
EXTENDS DOWNSLOPE
ON TOP OF TILES
APPROX. 6'' [150 mm]
NOTES :
1. ROOF DECK, UNDERLAYMENT, AND BATTENS NOT SHOWN FOR CLARITY.
PIPE PENETRATION
TILE-7A
2001 NOT DRAWN TO SCALE
1283
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
SHEET METAL
COUNTERFLASHING SHEET METAL
(SEE NOTE 1) STEP FLASHING
SOLDER OR
SEAL CORNERS
ALTERNATE :
RAGGLE
UNDERLAYMENT
TURNED UP WALL
SOLDERED ONE
PIECE APRON
FLASHING
CORNERS
SLATE
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
APRON FLASHING
SLATE-1
2001 NOT DRAWN TO SCALE
1284
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SIDING TO
COUNTERFLASH
STEPFLASHING
A MIN. 2'' [50 mm]
(SEE NOTE 1)
UNDERLAYMENT
TURNED UP WALL
4'' [100 mm]
APPROX.
SLATE
SHEET METAL
STEPFLASHING
BUILDING PAPER
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
SIDEWALL FLASHING
SLATE-2
2001 NOT DRAWN TO SCALE
1285
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
SOLDER OR COUNTERFLASHING
SEAL CORNERS SLATE
STRIPPING PLY
SHEET METAL
ALTERNATE : BACKER FLASHING
UNDERLAYMENT
SECTION :
SEALANT
SHEET METAL
COUNTERFLASHING
SHEET METAL
BACKER FLASHING
SLATE
6'' [150 mm] MIN.
SOLDERED ONE
PIECE CORNERS
UNDERLAYMENT
SLATE STARTER
COURSE
STRIPPING PLY
18'' [450 mm] MIN. ADHERED TO
UNDERLAYMENT
(SEE NOTE 3)
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING IS NOT USED UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.
BACKER FLASHING
SLATE-3
2001 NOT DRAWN TO SCALE
1286
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STARTER COURSE
OVER SHEET METAL
BACKER FLASHING
SLATE OVER
SHEET METAL
BACKER FLASHING
SLATE UNDER
SHEET METAL
BACKER FLASHING
SOLDERED ONE
PIECE CORNERS
NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON WIDTH, SLOPE
AND CLIMATIC CONDITIONS.
BACKER FLASHING
SLATE-3A
2001 NOT DRAWN TO SCALE
1287
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRIPPING PLY
EDGE METAL
FLASHING
ALTERNATE : ALTERNATE :
SLATE
UNDERLAYMENT
SLATE STARTER
COURSE
NOTES :
SLATE-4
2001 NOT DRAWN TO SCALE
1288
The NRCA Roofing and Waterproofing Manual—Fifth Edition
UNDERLAYMENT
OPTIONAL STRIPPING
PLY
GUTTER
SLATE ALTERNATE :
UNDERLAYMENT
GUTTER
EAVE CANT WITH
NOTES : OPTIONAL BEVEL
1. UNDERLAYMENT CAN BE INSTALLED ON TOP OF OR UNDER EAVE EDGE METAL FLASHING, DEPENDING ON
CLIMATIC CONDITIONS.
2. UNDERLAYMENT TYPE MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. THIS DETAIL SHOWS ONE TYPE OF GUTTER SUPPORT. GUTTER SECUREMENT AND SUPPORT OPTIONS VARY ACCORDING
TO REGIONAL PRACTICES AND MANUFACTURERS SPECIFICATIONS.
SLATE-5
2001 NOT DRAWN TO SCALE
1289
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS FASTENER
STRIPPING
PLY ON BOTH
SIDES OF
VALLEY METAL
OPTION : ALTERNATE :
SLOPE
EXTEND SLATES VALLEY METAL
4'' [100 mm] MIN. OVER 18'' [450 mm] WIDE MIN.
VALLEY METAL
VALLEY UNDERLAYMENT
NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIDC CONDITIONS.
3. SLATE SHOULD NOT BE FASTENED THROUGH THE VALLEY METAL. USE WIDER SLATE OR WIRE-TIE SYSTEMS.
OPEN VALLEY
SLATE-6
2001 NOT DRAWN TO SCALE
1290
The NRCA Roofing and Waterproofing Manual—Fifth Edition
VALLEY UNDERLAYMENT
VALLEY METAL
SLOPE
18'' [450 mm] WIDE MIN.
WIRE-TIED SLATE
NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. MIN. SLOPE FOR THIS DETAIL IS 8 :12 (34 DEGREES).
CLOSED VALLEY
SLATE-7
2001 NOT DRAWN TO SCALE
1291
The NRCA Roofing and Waterproofing Manual—Fifth Edition
METAL
FLASHING SLEEVE
SLATE
UNDERLAYMENT TO
OVERLAP UPPER FLANGE
OPTIONAL SEALANT
UNDER SLATE
MIN. DOWNSLOPE
FLANGE DIMENSION
TO BE EQUAL TO
FIELD SLATE
EXPOSURE
PIPE PENETRATION
SLATE-8
2001 NOT DRAWN TO SCALE
1292
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
SOLDER OR
SEAL CORNER
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT AND JOINERY
OPTIONS FOR SHEET METAL.
APRON FLASHING
SHK-1
2001 NOT DRAWN TO SCALE
1293
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INTERLAYMENT ON
TOP OF STEP FLASHING
SIDING TO
COUNTERFLASH
STEP FLASHING
A MIN 2'' [50 mm]
(SEE NOTE 1)
APPROX.
4'' MIN.
SHEET METAL
STEP FLASHING
BUILDING PAPER
WOOD SHAKES
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
SIDEWALL FLASHING
SHK-2
2001 NOT DRAWN TO SCALE
1294
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
COUNTERFLASHING
WOOD SHAKES
STRIPPING PLY
SHEET METAL
BACKER FLASHING
OPTIONAL :
UNDERLAYMENT
SEALANT
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
SOLDER OR
SEAL CORNERS SHEET METAL
BACKER FLASHING
WOOD SHAKES
INTERLAYMENT
BACKER FLASHING
SHK-3
2001 NOT DRAWN TO SCALE
1295
The NRCA Roofing and Waterproofing Manual—Fifth Edition
INTERLAYMENT
STARTER SHAKE
OVER SHEET METAL
BACKER FLASHING
SOLDER OR
SEAL CORNERS
SHAKE OVER
STEP FLASHING
SHEET METAL
SHEET METAL STEP FLASHING
BACKER FLASHING
NOTES :
1. UNDERLAYMENT AND STRIPPING PLY NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.
BACKER FLASHING
SHK-3A
2001 NOT DRAWN TO SCALE
1296
The NRCA Roofing and Waterproofing Manual—Fifth Edition
OPTION :
ALTERNATE :
WOOD SHAKES
UNDERLAYMENT
INTERLAYMENT
STARTER
COURSE(S)
SHK-4
2001 NOT DRAWN TO SCALE
1297
The NRCA Roofing and Waterproofing Manual—Fifth Edition
UNDERLAYMENT
OPTIONAL STRIPPING
PLY
GUTTER
WOOD SHAKES
ALTERNATE :
1 PIECE GUTTER
UNDERLAYMENT
INTERLAYMENT
SHK-5
2001 NOT DRAWN TO SCALE
1298
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SLOPE
EXTEND WOOD SHAKES 8'' [200 mm] MIN. AND
4'' [100 mm] MIN. OVER SET IN SEALANT
VALLEY METAL
VALLEY UNDERLAYMENT
(SEE NOTE 2)
NOTES :
WOOD SHAKES
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. SHAKES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.
OPEN VALLEY
SHK-6
2001 NOT DRAWN TO SCALE
1299
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS
KEEP NAILS 8'' [200 mm] STRIPPING
FROM CENTER OF VALLEY PLY ON BOTH
SIDES OF
VALLEY METAL
VALLEY
UNDERLAYMENT
(SEE NOTE 2)
OPTION :
SLOPE
VALLEY METAL
18'' [450 mm] WIDE MIN.
WOOD SHAKES
KEEP SHAKES
APPROX. 1'' [25 mm]
FROM VALLEY RIB
NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. MIN. SLOPE FOR THIS DETAIL IS 8 :12 (34 DEGREES).
CLOSED VALLEY
SHK-7
2001 NOT DRAWN TO SCALE
1300
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PRE-FABRICATED
FLASHING
INTERLAYMENT TO
OVERLAP UPPER
FLANGE
ALTERNATE : INTERLAYMENT
INTERLAYMENT
METAL
SLEEVE FLASHING
OPTIONAL
FASTENERS
MIN. DOWNSLOPE
FLANGE DIMENSION
TO BE EQUAL TO
FIELD SHAKE
EXPOSURE
PIPE PENETRATION
SHK-8
2001 NOT DRAWN TO SCALE
1301
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
APRON FLASHING
WITH HEMMED EDGE
SEALANT
SHEET METAL
COUNTERFLASHING
(SEE NOTE 1)
RAGGLE
UNDERLAYMENT
TURNED UP WALL
SHEET METAL
STEP FLASHING
SOLDER OR
SEAL CORNER
WOOD SHINGLES
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR SECUREMENT AND JOINERY
OPTIONS FOR SHEET METAL.
APRON FLASHING
SHNG-1
2001 NOT DRAWN TO SCALE
1302
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SIDING TO
COUNTERFLASH
STEPFLASHING
A MIN. 2'' [50 mm]
(SEE NOTE 1)
UNDERLAYMENT
TURNED UP WALL
SHEET METAL
STEPFLASHING WOOD SHINGLES
BUILDING PAPER
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
SIDEWALL FLASHING
SHNG-2
2001 NOT DRAWN TO SCALE
1303
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
COUNTERFLASHING
WOOD SHINGLES
STRIPPING PLY
SHEET METAL
BACKER FLASHING
UNDERLAYMENT
SECTION :
SEALANT
SHEET METAL
COUNTERFLASHING
6'' [150 mm] MIN. SHEET METAL
BACKER FLASHING
SOLDER OR WOOD
SEAL CORNERS SHINGLES
UNDERLAYMENT
STARTER COURSE
STRIPPING PLY
ADHERED TO
UNDERLAYMENT
(SEE NOTE 3)
NOTES :
1. ALTERNATE COUNTERFLASHING PROFILES CAN BE USED.
2. IF STRIPPING IS NOT USED, UNDERLAYMENT MUST BE EXTENDED OVER BACKER FLASHING.
3. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE AND CLIMATIC CONDITIONS.
BACKER FLASHING
SHNG-3
2001 NOT DRAWN TO SCALE
1304
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SOLDER OR
SEAL CORNER
SHEET METAL
SHEET STEP FLASHING
METAL
BACKER
FLASHING
NOTES :
1. UNDERLAYMENT AND COUNTERFLASHING NOT SHOWN FOR CLARITY.
2. CRICKETS SHOULD BE CONSIDERED IN LIEU OF BACKER FLASHINGS DEPENDING UPON
WIDTH, SLOPE, AND CLIMATIC CONDITIONS.
SHNG-3A
2001 NOT DRAWN TO SCALE
1305
The NRCA Roofing and Waterproofing Manual—Fifth Edition
L-TYPE
EDGE METAL ICE DAM PROTECTION
FLASHING MEMBRANE
EDGE METAL
FLASHING
OPTION :
ALTERNATE :
WOOD SHINGLES
UNDERLAYMENT
STARTER COURSE
NOTES :
1. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
SHNG-4
2001 NOT DRAWN TO SCALE
1306
The NRCA Roofing and Waterproofing Manual—Fifth Edition
UNDERLAYMENT
OPTIONAL STRIPPING
PLY
GUTTER
ALTERNATE :
1 PIECE GUTTER
WOOD
SHINGLES
WOOD SHINGLE
STARTER COURSE ''T'' TYPE EDGE
METAL FLASHING
GUTTER
UNDERLAYMENT
''L'' TYPE EDGE
METAL FLASHING
NOTES :
1. UNDERLAYMENT CAN BE INSTALLED ON TOP OF OR UNDER THE EAVE EDGE METAL FLASHING DEPENDING
ON CLIMATIC CONDITIONS.
2. UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING IN CLIMATIC CONDITIONS.
3. THIS DETAIL SHOWS ONE TYPE OF GUTTER SUPPORT. GUTTER SECUREMENT AND SUPPORT OPTIONS VARY ACCORDING
TO REGIONAL PRACTICES AND MANUFACTURERS SPECIFICATIONS.
SHNG-5
2001 NOT DRAWN TO SCALE
1307
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ALTERNATE :
SLOPE
VALLEY METAL
18'' [450 mm] WIDE MIN.
EXTEND WOOD SHINGLES
LAP VALLEY METAL
4'' [100 mm] MIN. OVER
8'' [200 mm] MIN. AND
VALLEY METAL
SET IN SEALANT
WOOD SHINGLES
VALLEY UNDERLAYMENT
(SEE NOTE 2)
NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. SHINGLES SHOULD NOT BE FASTENED THROUGH METAL VALLEY.
OPEN VALLEY
SHNG-6
2001 NOT DRAWN TO SCALE
1308
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS
STRIPPING
PLY ON BOTH
SIDES OF VALLEY METAL
VALLEY METAL
18'' [450 mm] WIDE MIN.
SLOPE
SET IN SEALANT
KEEP SHINGLES
VALLEY APPROX. 1'' [25 mm]
UNDERLAYMENT FROM VALLEY RIB
(SEE NOTE 2)
WOOD SHINGLES
NOTES :
1. FIELD UNDERLAYMENT NOT SHOWN FOR CLARITY.
2. VALLEY UNDERLAYMENT TYPE AND NECESSITY MAY VARY DEPENDING ON CLIMATIC CONDITIONS.
3. MINIMUM SLOPE FOR THIS DETAIL IS 8 :12 (34 DEGREES).
CLOSED VALLEY
SHNG-7
2001 NOT DRAWN TO SCALE
1309
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PRE-FABRICATED
BOOT FLASHING
UNDERLAYMENT TO
LAP OVER OR BE
SEALED TO UPPER
FLANGE
METAL
FLASHING SLEEVE
ALTERNATE : UNDERLAYMENT
WOOD SHINGLES
OPTIONAL FASTENERS
MIN. DOWNSLOPE
FLANGE DIMENSION
TO BE EQUAL TO
FIELD SHINGLE
EXPOSURE
PIPE PENETRATION
SHNG-8
2001 NOT DRAWN TO SCALE
1310
The NRCA Roofing and Waterproofing Manual—Fifth Edition
]
0 mm
[15
. 6''
OX
PR
AP
ROOF SIDE
X.
] MA IECE
m P
' [4 H P
12 EAC CA
TH CIA SHEET METAL COVER
E NG FAS
L F PLATE SET IN SEALANT
O
ON EACH SIDE
m m]
[150
. 6''
ROX
P
AP
FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. OVERSIZED HOLES AT GASKETED FASTENERS MAY BE REQUIRED FOR CERTAIN METAL TYPES TO ALLOW FOR MOVEMENT.
3. THE SIDES/EDGES OF THE COVER PLATE CAN BE BENT DOWN SLIGHTLY TO STIFFEN AND HELP SEAT THE COVER PLATE.
SM-1
2001 NOT DRAWN TO SCALE
1311
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
FASCIA CAP
X.
] MA IECE GASKETED FASTENERS
m P
' [4 H P APPROX. 18'' [450 mm] O.C.
12 EAC CA
H IA DEPENDING UPON WIND
N GT ASC ZONE AND LOCAL
LE F F
O CONDITIONS
X.
P RO
AP mm]
[75
3''
ROOF SIDE
SHEET METAL
FASCIA CAP
X.
] MA IECE
m P
' [4 H P
12 EAC CA
TH CIA
E NG FAS
L F
O OVERLAP JOINT SET IN
SEALANT
X.
P RO
AP mm]
[75
3''
FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. OVERSIZED HOLES AT GASKETED FASTENERS MAY BE REQUIRED FOR CERTAIN METAL TYPES TO ALLOW FOR MOVEMENT.
3. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.
SM-2
2001 NOT DRAWN TO SCALE
1312
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
CONCEALED PLATE
SET IN SEALANT
ON EACH SIDE
m m]
[150
. 6''
OX
PR
AP
ROOF SIDE
X.
] MA IECE
m P
' [4 H P
12 EAC CA
TH CIA SHEET METAL
E NG FAS
L F CONCEALED PLATE
O
SET IN SEALANT
ON EACH SIDE
mm]
[1 50
. 6''
ROX
P
AP
FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. OVERSIZED HOLES AT GASKETED FASTENERS MAY BE REQUIRED FOR CERTAIN METAL TYPES TO ALLOW FOR MOVEMENT.
SM-3
2001 NOT DRAWN TO SCALE
1313
The NRCA Roofing and Waterproofing Manual—Fifth Edition
X.
] MA IECE OPTION :
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E
O
X.
] MA IECE
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E SHEET METAL JOINT
O COVER PLATE SET IN
SEALANT ON EACH SIDE
AND FASTENED
APPROPRIATE FASTENERS
] APPROX. 3'' to 6''
0 mm [75 to 150 mm] O.C.
[15 STAGGER PATTERN VARIES
. 6''
OX PER ROOF SYSTEM
PR
AP
FACE SIDE
NOTES :
1. CONTINUOUS CLEAT ON FACE SIDE NOT SHOWN FOR CLARITY.
2. THE SIDES/EDGES OF THE COVER PLATE CAN BE BENT DOWN SLIGHTLY TO STIFFEN AND HELP SEAT THE COVER PLATE.
SM-4
2001 NOT DRAWN TO SCALE
1314
The NRCA Roofing and Waterproofing Manual—Fifth Edition
X.
] MA IECE
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E
O
SHEET METAL SET
IN SEALANT
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
X. STAGGER PATTERN VARIES
P RO
AP mm] PER ROOF SYSTEM
[75
3''
FACE SIDE
NOTES :
1. CONTINUOUS CLEAT AT FACE SIDE NOT SHOWN FOR CLARITY.
2. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.
SM-5
2001 NOT DRAWN TO SCALE
1315
The NRCA Roofing and Waterproofing Manual—Fifth Edition
X. OPTION :
] MA IECE
m P L
' [4 H
12 EAC ETA
H M
N GT DGE
LE F E
O
X.
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F SHEET METAL JOINT
O
COVER PLATE SET IN
SEALANT ON EACH SIDE
AND FASTENED
APPROPRIATE FASTENERS
] APPROX. 3'' to 6''
0 mm [75 to 150 mm] O.C.
[15 STAGGER PATTERN VARIES
. 6''
OX PER ROOF SYSTEM
PR
AP
SM-6
2001 NOT DRAWN TO SCALE
1316
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BEND FLANGE
''L'' TYPE METAL EDGE AT ROOF SIDE
X.
] MA IECE
m P L OPTION :
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O
X.
P RO
AP mm]
[75
3''
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
STAGGER PATTERN VARIES
ROOF SIDE PER ROOF SYSTEM
X.
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O
SHEET METAL SET
IN SEALANT
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
. STAGGER PATTERN VARIES
ROX
P PER ROOF SYSTEM
AP mm]
[75
3''
FACE SIDE
NOTES :
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.
SM-7
2001 NOT DRAWN TO SCALE
1317
The NRCA Roofing and Waterproofing Manual—Fifth Edition
X. OPTION :
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O
X.
] MA IECE
m P L
' [4 H
12 EAC ETA
M
TH E
E NG EDG
L F
O SHEET METAL CONCEALED
PLATE SET IN SEALANT
ON EACH SIDE
]
0 mm APPROPRIATE FASTENERS
[15 APPROX. 3'' to 6''
6''
X. [75 to 150 mm] O.C.
P RO STAGGER PATTERN VARIES
A P
PER ROOF SYSTEM
1318
The NRCA Roofing and Waterproofing Manual—Fifth Edition
X.
P RO
AP ]
5 mm
[ 2
1''
APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[75 to 150 mm] O.C.
ROOF SIDE STAGGER PATTERN VARIES
PER ROOF SYSTEM
APPROX.
1'' to 1.5'' APPROPRIATE FASTENERS
APPROX. 3'' to 6''
[25 to 38 mm] X.
P RO [75 to 150 mm] O.C.
AP ] STAGGER PATTERN VARIES
5 mm
[2 PER ROOF SYSTEM
1''
FACE SIDE
NOTES :
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.
SM-9
NOT DRAWN TO SCALE
2001
1319
The NRCA Roofing and Waterproofing Manual—Fifth Edition
1 2 3
4 5 6
NOTES :
1. DASHED PROFILE REPRESENTS EDGE METAL, COPING CAP, ETC.
2. ALL CLEATS ARE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12' [4 m].
SM-10
2001 NOT DRAWN TO SCALE
1320
The NRCA Roofing and Waterproofing Manual—Fifth Edition
7 8 9
10 11 12
NOTES :
1. DASHED PROFILE REPRESENTS EDGE METAL, COPING CAP, ETC.
2. ALL CLEATS ARE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12' [4 m].
SM-11
2001 NOT DRAWN TO SCALE
1321
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENING TAB
13
FASTENING TAB
14
NOTES :
1. DASHED PROFILE REPRESENTS EDGE METAL, COPING CAP, ETC.
2. ALL CLEATS ARE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12' [4 m].
SM-12
2001 NOT DRAWN TO SCALE
1322
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
APPROPRIATE SEALANT
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
COUNTERFLASHING OPTIONS
SM-13
2001 NOT DRAWN TO SCALE
1323
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
APPROPRIATE FASTENERS
24'' [600 mm] O.C.
OPTIONAL : SEALANT OR
ELASTOMERIC TAPE
OPTIONAL : SEALANT OR
ELASTOMERIC TAPE
COUNTERFLASHING OPTIONS
SM-14
2001 NOT DRAWN TO SCALE
1324
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BUILDING PAPER
(IF REQUIRED)
WALL CLADDING
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
EQUIPMENT FLANGE
OPTIONAL :APPROPRIATE
FASTENERS
APPROX. 12'' [300 mm] O.C.
COUNTERFLASHING OPTIONS
SM-15
2001 NOT DRAWN TO SCALE
1325
The NRCA Roofing and Waterproofing Manual—Fifth Edition
X.
P RO ]
AP mm
0
[15
6''
.
ROX
P
AP m]
[ 7 5m
3''
NOTES : COPING CAP WITH OVERLAP
B
1. CONTINUOUS CLEAT NOT SHOWN FOR CLARITY.
2. REFER TO TABLE SM-19 FOR COPING CAP SECUREMENT OPTIONS.
3. COPING JOINERY IS SIMILAR ON BOTH SIDES.
4. REMOVAL OF UNDERLYING METAL HEM MAY HELP FACILITATE PROPER NESTING.
SM-16
2001 NOT DRAWN TO SCALE
1326
The NRCA Roofing and Waterproofing Manual—Fifth Edition
.
OX
P PR m]
A
0m
[15
6''
COPING CAP WITH CONCEALED PLATE
APPROX. 1/2''
C
[13 mm] GAP SHEET METAL
COPING CAP
SHEET METAL
SET IN SEALANT
X.
P RO
AP ]
0 mm 3/4'' 1/2'' 3/4''
[ 5
2''
SM-17
2001 NOT DRAWN TO SCALE
1327
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL DOUBLE
X. LOCK STANDING SEAM
] MA IECE
m P SHEET METAL
' [4 H P
12 EAC CA COPING CAP
H NG
N GT OPI BUTTON PUNCH TO
LE F C HOLD IN PLACE
O
OPTION :
SHEET METAL
SET IN SEALANT
X. SHEET METAL
] MA IECE DOUBLE ''S'' CLEAT
m P
' [4 H P SET IN SEALANT
12 EAC CA ON EACH SIDE
H NG
N GT OPI
LE F C
O SHEET METAL
SET IN SEALANT
SEALANT
X.
RO
P N.
AP ] MI
m
0m
2'' [5 3/4'' 1/2'' 3/4''
SM-18
2001 NOT DRAWN TO SCALE
1328
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS CLEATS
OPTIONAL METAL
/4''
.3 FLANGE EXTENSION
X
P RO
AP
4''
. 3/
OX
PR
TYPICAL AP
CLEAT ENGAGEMENT
APPROPRIATE FASTENERS
FASTENED APPROX. 6''
[150 mm] O.C.
. CONTINUOUS CLEAT
M IN
mm] APPROPRIATE FASTENERS
[50 FASTENED APPROX. 6''
2''
[150 mm] O.C.
SM-19
2001 NOT DRAWN TO SCALE
1329
The NRCA Roofing and Waterproofing Manual—Fifth Edition
X.
] MA IECE SHEET METAL EXPANSION
m P
' [4 H ER JOINT COVER
12 EAC OV
H C
N GT OINT OVERLAP JOINT WITH
LE N J BEAD OF SEALANT
SIO
PAN SL
EX OP
OF E
GASKETED FASTENERS
AT APPROX. 18'' [450 mm]
O.C. DEPENDING ON WIND
X.
P RO WIND ZONE AND
AP ] LOCAL CONDITIONS
5 mm
[ 7
3''
GASKETED FASTENERS
] AT APPROX. 18'' [450 mm]
mm
50 O.C. DEPENDING ON WIND
6 '' [1 WIND ZONE AND
X.
P RO LOCAL CONDITIONS
AP
SM-20
2001 NOT DRAWN TO SCALE
1330
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
AT APPROX. 18'' [450 mm]
O.C. DEPENDING ON WIND
WIND ZONE AND
X.
P RO LOCAL CONDITIONS
AP ]
0 mm
[ 5
2''
GASKETED FASTENERS
AT APPROX. 18'' [450 mm]
O.C. DEPENDING ON WIND
WIND ZONE AND
LOCAL CONDITIONS
X.
P RO 1'' [25 mm] MIN.
AP ]
0 mm
[ 5
2''
SECTION :
SM-21
2001 NOT DRAWN TO SCALE
1331
The NRCA Roofing and Waterproofing Manual—Fifth Edition
1 2
3 4
5 6
7 8
NOTES :
1. TOPS OF ALL EXPANSION JOINTS MUST SLOPE TO DRAIN.
2. BASE FLASHING, VAPOR RETARDER AND COMPRESSIBLE INSULATION NOT SHOWN FOR CLARITY.
3. FLAT PROFILE EXPANSION JOINTS SHOULD NOT BE SECURED ON BOTH SIDES.
SM-22
2001 NOT DRAWN TO SCALE
1332
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE FASTENERS
VALLEY METAL
NUMBER OF SEALANT
BEADS DEPENDENT
UPON SLOPE AND
CLIMATIC CONDITIONS
CENTER RIB
1'' (25 mm) MIN. HEIGHT
NOTES :
1. THIS DETAIL DEPICTS THE OVERLAP JOINT ONLY.
SM-23
2001 NOT DRAWN TO SCALE
1333
The NRCA Roofing and Waterproofing Manual—Fifth Edition
.
P P ROX
A m]
75 m
3'' [
NOTE :
1. GUTTER PROFILES AND SIZE VARY.
2. APPROPRIATE FASTENERS (E.G. POP-RIVETS) COVERED WITH SEALANT - NOT SHOWN FOR CLARITY.
SOLDER -
SWEAT INTO
SEAM .
P P ROX
A m]
75 m
3'' [
NOTES :
1. GUTTER PROFILES AND SIZE VARY.
2. APPROPRIATE FASTENERS (E.G., POP-RIVETS) SEALED WITH SOLDER - NOT SHOWN FOR CLARITY.
SM-24
2001 NOT DRAWN TO SCALE
1334
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
GUTTER - WELDABLE
METALS ONLY
WELDED JOINT
NOTES :
1. GUTTER PROFILES AND SIZE VARY.
SM-25
2001 NOT DRAWN TO SCALE
1335
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRIVE CLEAT
FLAT LOCK DOUBLE FLAT LOCK
SM-26
2001 NOT DRAWN TO SCALE
1336
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ARCHITECTURAL METAL
ROOF PANEL JOGGLE
CLEAT
''L'' TYPE
SEAM AND PANEL DOWNSLOPE
PROFILES VARY PERIMETER
METAL
FLASHING
PANEL CLIP
MIN. 2
FASTENERS
PER CLIP
E
OP
ALTERNATE :
SL
SLIP SHEET
UNDERLAYMENT
OR ICE DAM
''T'' TYPE PROTECTION
DOWNSLOPE MEMBRANE
PERIMETER
METAL
FLASHING
ROOF AND
WALL PROFILE
OPTIONAL :
INSTALL SEALANT
AT ENDS OF
VERTICAL SEAMS
OPTIONAL :
CONTINUOUS
CLEAT -
SEE TABLE 1
NOTES:
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
A-MTL-1
2001 NOT DRAWN TO SCALE
1337
The NRCA Roofing and Waterproofing Manual—Fifth Edition
E
OP
PANEL
SL
''T'' TYPE SLIP SHEET
DOWNSLOPE
PERIMETER UNDERLAYMENT
METAL OR ICE-DAM
FLASHING PROTECTION
MEMBRANE
OPTIONAL :
OPTIONAL : ICE-DAM
INSTALL SEALANT PROTECTION
AT ENDS OF MEMBRANE
VERTICAL SEAMS OVER ROOF
EDGE
GUTTER
BRACKET
SUPPORT AT
12'' TO 30''
[300 mm TO
750 mm] O.C.
DEPENDING
UPON
CONDITIONS
SHEET
GUTTER METAL GUTTER
SPACER PROFILES MAY
PLACED VARY
BETWEEN
BRACKETS
OPTIONAL :
ROOF AND
STIFFENING BAR
WALL PROFILE
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND REGIONAL PRACTICE
3. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
4. VARIOUS COMBINATIONS OF SUPPORT BRACKETS, SUPPORT BRACKETS AND SPACERS OR SPACER HANGERS CAN BE USED.
1338
The NRCA Roofing and Waterproofing Manual—Fifth Edition
E
ARCHITECTURAL
OP
PANEL CLIP
METAL ROOF
SL
MIN. 2
FASTENERS PANEL
PER CLIP SLIP SHEET
UNDERLAYMENT
OPTIONAL:
OR ICE-DAM
INSTALL SEALANT
PROTECTION
AT ENDS OF
MEMBRANE
VERTICAL SEAMS
GUTTER
SPACER
PLACED
BETWEEN
BRACKETS
JOGGLE CLEAT
OPTIONAL :
DOWNSLOPE
''L'' TYPE
PERIMETER
METAL
FLASHING
SHEET
METAL GUTTER
PROFILES MAY
VARY
OPTIONAL:
STIFFENING BAR ROOF AND
WALL PROFILE
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND REGIONAL PRACTICE
3. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
4. VARIOUS COMBINATIONS OF SUPPORT BRACKETS, SUPPORT BRACKETS AND SPACERS OR SPACER HANGERS CAN BE USED.
1339
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ARCHITECTURAL
METAL ROOF PANEL
OPTION :
PE
O
SL
SLIP SHEET
UNDERLAYMENT
''T'' TYPE RAKE EDGE
METAL
OPTIONAL :
ROOF AND CONTINUOUS CLEAT
WALL PROFILE SEE TABLE 1
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
A-MTL-3
2001 NOT DRAWN TO SCALE
1340
The NRCA Roofing and Waterproofing Manual—Fifth Edition
METAL RAKE
FLASHING
PANEL CLIP
MIN. 2
FASTENERS CLIP
PER CLIP
METAL RAKE
FLASHING
CONTINUOUS CONTINUOUS
CLEAT CLEAT
ALTERNATE : OPTION :
E
OP
SLIP SHEET
UNDERLAYMENT SL
METAL RAKE
FLASHING
CONTINUOUS
CLEAT
ROOF AND
WALL PROFILE
ARCHITECTURAL
METAL ROOF
PANEL
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
A-MTL-3A
2001 NOT DRAWN TO SCALE
1341
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SLO
PE
OPE
SL
SLIP SHEET
SEAM AND PANEL
PROFILES VARY UNDERLAYMENT
ROOF SUBSTRATE
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE PANELS ALONG THE RIDGE IF THE ''Z'' CLOSURE IS FASTENED
THROUGH TO THE ROOF DECK.
A-MTL-4
2001 NOT DRAWN TO SCALE
1342
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
RIDGE CAP
OPTIONAL :
AIR DAM WITH ALTERNATE:
PERFORATED
LOWER FACE OR CONTINUOUS WOOD
GAPS AT ENDS - SHIMMED AS REQUIRED
SOLDER TO PANS TO PASS OVER TOPS
OR SECURE OF SEAMS
UNDER VENT
NON-COMPRESSIBLE
AIR VENT TO MATCH
SEAM HEIGHT
UNDERLAYMENT
NOTES : ROOF SUBSTRATE
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE PANELS ALONG THE RIDGE.
A-MTL-4A
2001 NOT DRAWN TO SCALE
1343
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
HIP CAP
''Z'' CLOSURE
FASTENED AND SET IN
SEALANT, OR SOLDERED
AS MATERIAL PERMITS -
SEAL VERTICAL LEGS
ARCHITECTURAL
METAL ROOF
PANEL
SL
OP
E
E
OP
SL
SLIP SHEET
UNDERLAYMENT
ROOF SUBSTRATE
OPTIONAL: TURN PANEL
PANS UP TO PROVIDE
NOTES : SECONDARY CLOSURE
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE PANELS ALONG THE HIP IF THE ''Z'' CLOSURE IS FASTENED
THROUGH TO THE ROOF DECK.
A-MTL-5
2001 NOT DRAWN TO SCALE
1344
The NRCA Roofing and Waterproofing Manual—Fifth Edition
OPTIONAL :
INSTALL SEALANT
IN ENDS OF VERTICAL
]
SEAMS
5 mm E VALLEY METAL
ARCHITECTURAL [17 ANG
7'' FL H
METAL ROOF PANEL I N. IDT
M W
PE
SL
O
OP
SL
E
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. WHERE ICE FORMATION IS EXPECTED, MINIMUM ROOF SLOPE FOR THIS VALLEY IS 6:12 (27 DEGREES).
3. DIMENSIONS FOR VALLEY METAL WIDTH MAY VARY ACCORDING TO PANEL LENGTHS AND GEOGRAPHIC
CONSIDERATIONS.
A-MTL-6
2001 NOT DRAWN TO SCALE
1345
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PE
O
SL
SL
OP
E
1346
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WALL CONSTRUCTION
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
APPROX.
4'' [100 mm] MIN.
VERTICAL HEIGHT
OPTIONAL: CONTINUOUS
SHEET MEMBRANE LINER
SHEET METAL
ROOF-TO-WALL FLASHING
E
OP
SL
OPE
SL
A-MTL-7
2001 NOT DRAWN TO SCALE
1347
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROXIMATELY 12''
[300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
APPROPRIATE FASTENERS
APPROXIMATELY 24'' [600 mm] O.C.
SL
OP
E
ARCHITECTURAL
METAL ROOF PANEL
SLIP SHEET
UNDERLAYMENT ROOF AND WALL
CONSTRUCTION
SEAM AND PANEL
PROFILES VARY
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE ABUTTING WALL.
2. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
3. THIS DETAIL MAY BE USED WITH ''STARTER'' AND ''END'' PANELS.
4. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION FOR ADDITIONAL COUNTERFLASHING OPTIONS.
A-MTL-8
2001 NOT DRAWN TO SCALE
1348
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
TOOLED TO FACILIATE RUNOFF
APPROPRIATE FASTENERS
APPROXIMATELY 12'' (300mm) O.C.
APPROPRIATE FASTENERS
APPROXIMATELY 24'' (600mm) O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
REMOVABLE SHEET METAL
COUNTERFLASHING
OPTIONAL SEALANT
SHEET METAL
ROOF-TO-WALL FLASHING
''Z'' CLOSURE
FASTENED AND SET
IN SEALANT OR
SOLDERED AS
MATERIAL PERMITS SL
OP
E
ARCHITECTURAL
METAL ROOF PANEL
SLIP SHEET
UNDERLAYMENT
ROOF SUBSTRATE
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE ABUTTING WALL.
2. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
3. THIS DETAIL MAY BE USED WITH ''STARTER'' AND ''END'' PANELS.
4. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION FOR ADDITIONAL COUNTERFLASHING OPTIONS.
5. THIS DETAIL FIXES THE PANEL IF THE ''Z'' CLOSURE IS FASTENED TO
THE ROOF SUBSTRATE.
1349
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TURN PANEL
PANS UP
TO PROVIDE
SECONDARY PE
LO
CLOSURE S
FLEXIBLE VAPOR
RETARDER TO SERVE
AS INSULATION
RETAINER ATTACHED
TO ROOF DECK
SEAM AND
SLIP SHEET PANEL PROFILES
VARY
UNDERLAYMENT
ROOF
SUBSTRATE
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN BOTH DIRECTIONS.
3. THIS DETAIL FIXES THE PANEL IF THE ''Z'' CLOSURE IS FASTENED TO ROOF SUBSTRATE.
4. THE EXPANSION JOINT COVER MUST BE SECURED ON ONE SIDE AND HAVE SUFFICIENT
ENGAGEMENT ON THE OTHER SIDE TO ALLOW FOR EXPANSION AND CONTRACTION OF THE BUILDING.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER OF 1-1/2 TIMES THE WIDTH OF THE DECK OPENING.
1350
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE VAPOR
RETARDER ATTACHED
TO ROOF DECK
OPE
''Z'' CLOSURE SL
FASTENED AND SET IN
SEALANT, OR SOLDERED
AS MATERIAL PERMITS
TURN PANEL
PANS UP
TO PROVIDE
SECONDARY
CLOSURE E
LOP
S
ARCHITECTURAL
METAL ROOF PANEL
UNDERLAYMENT
SLIP SHEET
SEAM AND PANEL
ROOF SUBSTRATE PROFILES VARY
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN BOTH DIRECTIONS.
3. THIS DETAIL FIXES THE PANEL, IF THE ''Z'' CLOSURE IS FASTENED TO ROOF SUBSTRATE.
4. THE EXPANSION JOINT COVER MUST BE SECURED ON ONE SIDE AND HAVE SUFFICIENT
ENGAGEMENT ON THE OTHER SIDE TO ALLOW FOR EXPANSION AND CONTRACTION OF THE BUILDING.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER OF 1-1/2 TIMES THE WIDTH OF THE DECK OPENING.
1351
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE VAPOR
RETARDER WITH
COMPRESSIBLE
INSULATION
WALL CONSTRUCTION
''Z'' CLOSURE
FASTENED AND SET IN E
OP
SEALANT OR SOLDERED SL
AS MATERIAL PERMITS-
SEAL VERTICAL LEGS
ARCHITECTURAL
METAL ROOF PANEL E
PANEL OP
SL
1352
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL
FRAME
LE
AB
SEE DETAIL E ET
A-MTL-12 FOR -S
H
DT
FLASHING OF WI
SUPPORT LEGS
ROUND PIPE
COLUMN
NOTES :
1. DECK SUBSTRATE, UNDERLAYMENT AND SLIP-SHEET NOT SHOWN FOR CLARITY.
A-MTL-11
2001 NOT DRAWN TO SCALE
1353
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WATERTIGHT SHEET
EQUIPMENT SUPPORT METAL RAIN COLLAR
WITH STAINLESS STEEL
STAND/VENT STACK -
DRAWBAND - OVERLAP
SEE NOTE 1 FLASHING COLLAR
3'' [75 mm] MIN.
SEALANT BEAD BETWEEN
PIPE AND FLASHING TOOLED TO
FACILITATE RUNOFF
PREFORMED PENETRATION
FLASHING
GASKETED FASTENERS
SECURE FLASHING COLLAR
FLANGE TO ROOF PANEL
AND NOT TO DECK SO AS
NOT TO FIX PANEL AT
PENETRATION
OPTION :
OPENING IN ROOF DECK
STAINLESS STEEL
ARCHITECTURAL DRAWBAND
METAL ROOF PANEL SET SECUREMENT
RING IN CONTINUOUS
BEAD OF SEALANT
UNDERLAYMENT
SLIP SHEET
SEAM AND PANEL
PROFILES VARY
ROOF SUBSTRATE
NOTES :
1. NRCA RECOMMENDS PENETRATIONS SHOULD NOT INTERFERE WITH PANEL SEAMS OR OCCUR AT
TRANSVERSE SEAMS.
2. CUT HOLE IN ROOF DECK TO ALLOW FOR MOVEMENT.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
4. FOR HOT PIPES, SPECIFIC HIGH-TEMPERATURE BOOTS SHOULD BE USED.
1354
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SOLDERED OR SEALED
SEAM AS MATERIAL
PERMITS
2 BEADS
OF SEALANT
WEATHERPROOF
RIVETS WITH
HEADS SEALED
FASTENERS-SECURE
FLASHING CAP FLASHING COLLAR
FLANGE TO ROOF
PANEL AND NOT TO
METAL FLASHING
DECK SO AS NOT
COLLAR
TO FIX PANEL AT
PENETRATION
ARCHITECTURAL
METAL ROOF PANEL COLLAR FLANGE
BELOW
SOLDERED OR
SEALED SEAM E
OP
AS MATERIAL SL
PERMITS
2 BEADS
OF SEALANT
WEATHERPROOF
RIVETS WITH HEADS
SEALED
SEAM AND PANEL SLIP SHEET
PROFILES VARY UNDERLAYMENT
ROOF SUBSTRATE
NOTES :
1. NRCA RECOMMENDS PENETRATIONS SHOULD NOT INTERFERE WITH PANEL SEAMS OR OCCUR AT
TRANSVERSE SEAMS.
2. CUT HOLE IN ROOF DECK TO ALLOW FOR MOVEMENT.
3. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL
SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
A-MTL-13
2001 NOT DRAWN TO SCALE
1355
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ALTERNATE : COUNTERFLASHING
MIN. HEIGHT
8'' [200 mm]
TURN UP
COUNTER-
FLASHING
WHENEVER
POSSIBLE
SECTION SHOWS
LOCKED SEAMS
OPTIONAL : IN LIEU OF
CRICKET (SEE OVERLAPPED AND
NOTE BELOW) SEALED SEAMS
SEAL ENDS
OF SEAMS
OPTIONAL: CRICKET
(SEE NOTE BELOW)
WITH FLANGES
OVERLAPPED AND
SET IN SEALANT OR
SOLDERED AS
MATERIAL PERMITS
SLIP SHEET
UNDERLAYMENT
ROOF
SUBSTRATE
NOTES :
1. NRCA SUGGESTS THAT DESIGNERS CONSIDER SPECIFYING CRICKETS WHEN THE RAISED CURB IS MORE
THAN 24 INCHES [600 mm] WIDE. WATER DIVERTERS MAY BE USED IN LIEU OF CRICKETS WHEN THE RAISED
CURB IS LESS THAN 24'' [600 mm] WIDE.
2. CURB MOUNTED EQUIPMENT SHOULD BE WEATHERPROOF AND HAVE A WEATHERPROOF INTERLOCK OR SUFFICENT
OVERLAP WITH THE CURB.
3. PROPER STRUCTURAL SUPPORT IS REQUIRED UNDER ALL SIDES OF THE RAISED CURB.
4. ALL METAL JOINTS TO BE SET IN SEALANT OR SOLDERED AS MATERIAL PERMITS.
A-MTL-14
2001 NOT DRAWN TO SCALE
1356
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MIN (2) PER SIDE
2'' [50 mm]
MIN. OVERLAP
COUNTERFLASHING
SECTION :
STRUCTURAL MEMBER
~
PENETRATING ROOF
ASSEMBLY
TEMPERATURE APPROPRIATE
GASKET OR SEALANT TOOLED
TO FACILITATE RUNOFF
STAINLESS STEEL
DRAWBAND
METAL CURB CAP
METAL OR GYPSUM
BOARD LINER FOR
HOT PIPES
~ ~
1357
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ALTERNATE :
JOGGLE CLEAT
SET IN SEALANT
SECTION :
OPTIONAL :
INSTALL SEALANT ARCHITECTURAL
E
OP
LOW-SLOPE ROOF
MEMBRANE BASE
FLASHING
''
''A
E
OP
SL ROOF SUBSTRATE
LOW-SLOPE ROOF
MEMBRANE
NOTES :
1. DIMENSION ''A'' AND PANEL OVERLAP TO BE DETERMINED BY LOW-SLOPE MEMBRANE SYSTEM
REQUIREMENTS, SLOPE OF ROOF AND CLIMATIC CONSIDERATIONS.
2. COMPATIBILITY OF UNDERLAYMENT AND LOW-SLOPE MEMBRANE SHOULD BE CONSIDERED.
3. REFER TO LOW-SLOPE CONSTRUCTION DETAILS FOR SPECIFICS ON MEMBRANE BASE FLASHING.
1358
The NRCA Roofing and Waterproofing Manual—Fifth Edition
TRANSITION
FLASHING
ALTERNATE :
ARCHITECTURAL METAL
ROOF PANEL
E
OPTIONAL : OP UNDERLAYMENT
INSTALL SEALANT
SL
AT ENDS OF CONTINUOUS
VERTICAL SEAMS JOGGLE CLEAT
SET IN SEALANT
SHEET METAL
TRANSITION FLEXIBLE MEMBRANE
FLASHING LINER
UNDERLAYMENT
.
IN SLIP SHEET
m ]M
0m
[15 WOOD BLOCKING
6'' BETWEEN SEAMS
OPTIONAL :
UPTURNED ENDS
''Z'' CLOSURE FASTENED
OPE AND SET IN SEALANT
SL OR SOLDERED AS
MATERIAL PERMITS-
SEAL VERTICAL LEGS
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. THIS METHOD OF FLASHING FIXES THE LOWER ROOF PANELS.
A-MTL-17
2001 NOT DRAWN TO SCALE
1359
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT CONTINUOUS
''C'' CLOSURE
''Z'' CLOSURE
SEALANT
METAL METAL
WALL PANEL WALL PANEL
SECTION : ALTERNATE :
E
OP
SEAMS AND PANEL
SL
PROFILES VARY
ARCHITECTURAL
METAL ROOF PANEL
''T'' TYPE
DOWNSLOPE PERIMETER
METAL FLASHING
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. THIS METHOD OF FLASHING FIXES THE WALL PANELS IF THE ''Z'' CLOSURE IS FASTENED
THROUGH TO THE WALL.
1360
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ARCHITECTURAL
RIB KNUCKLE COVER METAL ROOF
NOTCH AND OVERLAP - PANEL
INSERT OVER PANEL
SEAM - RIVET TO
SEAM AND SEAL SEAMS AND
PANEL PROFILES
VARY
PANEL CLIP
MIN. 2
FASTENERS
E
OP
PER CLIP
SL
APPROPRIATE
SEALANT BOTH
SIDES OF SEAM
SLIP SHEET
UNDERLAYMENT
NOTES :
1. THIS DETAIL IS APPLICABLE WHEN ROOF AND WALL PANEL ARE CONTINUOUS FROM ROOF TO WALL.
2. THIS DESIGN MAY BE SUSCEPTIBLE TO ICE DAMAGE.
3. THIS DETAIL IS APPROPRIATE WHEN THE LOWER PORTION OF THE METAL PANEL IS RELATIVELY SHORT.
4. THIS DETAIL FIXES THE PANEL AT THIS LOCATION.
CONTINUOUS ROOF-TO-WALL
PANEL TRANSITION
A-MTL-19
2001 NOT DRAWN TO SCALE
1361
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL
METAL ROOF PANEL
E
OP
SL
OVERHANG
PANEL 1''
[25 mm] MIN.
PANEL CLIP
GASKETED MIN. 2
FASTENERS FASTENERS
PREFORMED METAL PER CLIP
CLOSURE SET IN
CONTINUOUS SEALANT STRUCTURAL
ON ALL SIDES FRAMING
TO METAL PANEL MEMBERS -
EDGE METAL FLASHING PROFILES AND
SPACING VARY
OPTIONAL :
CONTINUOUS CLEAT WALL
SEE TABLE 1 CONSTRUCTION
NOTES :
1. SPECIFIC FASTENING AND STRUCTURAL REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM
TO SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL FIXES THE PANEL AT THE EAVE.
1362
The NRCA Roofing and Waterproofing Manual—Fifth Edition
JOGGLE CLEAT
FASTENED TO
FRAMING SEALED
TO ''L'' TYPE
METAL FLASHING
STRUCTURAL METAL
ROOF PANEL ALTERNATE:
OPTIONAL :
INSTALL SEALANT
AT ENDS OF
VERTICAL SEAMS PANEL CLIP MIN. 2
FASTENERS PER CLIP
E
OP
SL
NOTES :
1. SPECIFIC FASTENING AND STRUCTURAL REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM
TO SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL CAN ONLY BE USED WHEN FIXED POINT IS NOT AT THE EAVE.
1363
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED
FASTENER
SEALANT TAPE
STRUCTURAL
METAL ROOF PANEL
GASKETED FASTENERS
SECTION :
GASKETED
FASTENERS STRUCTURAL
FRAMING
METAL GUTTER MEMBERS -
STRAP AT EACH PROFILES AND
RIB SPACING VARY
SHEET METAL WALL
GUTTER CONSTRUCTION
OPTIONAL :
FASTENER CONTINUOUS
CLEAT SEE
PREFORMED METAL CLOSURE SET NOTE 6 AND
IN CONTINUOUS SEALANT ON ALL TABLE 1
SIDES TO METAL PANEL
''L'' TYPE
DOWNSLOPE
PERIMETER
NOTES : METAL FLASHING
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. DESIGN GUTTER EXPANSION JOINTS FOR PLACEMENT AT INTERVALS APPROPRIATE TO GUTTER
LENGTH AND TYPE OF METAL.
5. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND
REGIONAL PRACTICES.
6. CONTINUOUS CLEAT MAY NOT BE REQUIRED WHEN GUTTER INSTALLATION SECURES THE FACE OF THE
''L'' TYPE METAL.
S-MTL-2
2001 NOT DRAWN TO SCALE
1364
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED
STRUCTURAL FASTENER
METAL ROOF PANEL FLANGED
GUTTER
SEAM AND PANEL
PROFILES VARY
INSTALL SEALANT
AT ENDS OF
VERTICAL SEAMS
ALTERNATE :
E
OP
SL
PANEL CLIP
MIN. 2 FASTENERS
PER CLIP
S-MTL-2A
2001 NOT DRAWN TO SCALE
1365
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLANGED
GUTTER
STRUCTURAL
METAL ROOF PANEL
INSTALL SEALANT AT
ENDS OF VERTICAL
SEAMS
SEAM AND
PANEL ALTERNATE:
PROFILES
VARY
E
OP
SL
PANEL CLIP
MIN. 2
FASTENERS
PER CLIP
STRUCTURAL FRAMING
MEMBERS - PROFILES
AND SPACING VARY
JOGGLE CLEAT
FASTENED TO FRAMING
GUTTER SPACER AND SEALED TO ''L''
AT 12'' TO 30'' TYPE METAL FLASHING
[300 mm TO 750 mm]
O.C. DEPENDING ON ''L'' TYPE EDGE METAL
CONDITIONS FLASHING
FASTENER OPTIONAL :
CONTINUOUS CLEAT
SEE TABLE 1
SHEET METAL GUTTER
WALL CONSTRUCTION
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. DESIGN GUTTER EXPANSION JOINTS FOR PLACEMENT AT INTERVALS APPROPRIATE TO GUTTER
LENGTH AND TYPE OF METAL.
5. GUTTER PROFILE AND SIZE VARY ACCORDING TO ROOF AREA SIZE, ROOF SLOPE, BUILDING CODE AND
REGIONAL PRACTICES.
S-MTL-2B
2001 NOT DRAWN TO SCALE
1366
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED
FASTENER
SEALANT
STRUCTURAL
METAL ROOF PANEL
SECTION :
E
OP
SL
SEALANT
CONTINUOUS CLEAT
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
S-MTL-3
2001 NOT DRAWN TO SCALE
1367
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL
METAL ROOF PANEL
E
OP
SL
OPTIONAL GASKETED
FASTENER
METAL RAKE
EDGE FLASHING
STRUCTURAL FRAMING
MEMBER - PROFILES RAKE SUPPORT FLASHING
AND SPACING VARY TO BE FORMED OF
HEAVY GAUGE METAL -
ALSO SERVES AS
CONTINUOUS CLEAT
WALL CONSTRUCTION
''Z'' CLOSURE FASTENED
AND SET IN SEALANT
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CODE.
2. REFER TO METAL TABLE 1 FOR PERIMETER EDGE METAL THICKNESS AND CLEAT RECOMMENDATIONS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES
THE PANEL ALONG THE RAKE EDGE.
S-MTL-3A
2001 NOT DRAWN TO SCALE
1368
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
RIDGE CAP
GASKETED
FASTENERS
PREFORMED METAL
CLOSURE - SET IN
SEALANT AND
ATTACHED TO PANEL
SEAL VERTICAL LEGS
PE SLO
PE
SLO
SEAM
AND PANEL
PROFILES VARY STRUCTURAL
FRAMING MEMBER -
PANEL CLIP PROFILES AND
MIN. 2 FASTENERS SPACING VARY
PER CLIP OPTIONAL
STRUCTURAL SEALANT
METAL ROOF PANEL HEAVY GAUGE PANEL
END SUPPORT METAL
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES
THE PANEL ALONG THE RIDGE.
S-MTL-4
2001 NOT DRAWN TO SCALE
1369
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
RIDGE CAP
GASKETED
FASTENERS
OPTIONAL: TURN
PANEL PANS UP AT
RIDGE TO PROVIDE
SECONDARY
CLOSURE
PREFORMED METAL
CLOSURE - SET IN
SLO SEALANT AND
PE
E ATTACHED TO
OP PANEL - SEAL
SL
VERTICAL LEGS
STRUCTURAL
SEAM FRAMING MEMBER -
AND PANEL PROFILES AND
PROFILES VARY SPACING VARY
PANEL CLIP
MIN. 2 FASTENERS
OPTIONAL
PER CLIP
SEALANT
STRUCTURAL
HEAVY GAUGE
METAL ROOF PANEL
PANEL END
SUPPORT METAL
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES
THE PANEL ALONG THE RIDGE.
S-MTL-4A
2001 NOT DRAWN TO SCALE
1370
The NRCA Roofing and Waterproofing Manual—Fifth Edition
NOTCH AT
SEAM
GASKETED
FASTENER
HEAVY GAUGE
PANEL END
SUPPORT METAL
SLOPE
STRUCTURAL
FRAMING MEMBER -
PROFILES AND
SPACING VARY
E
OP
SL
SEAM
AND PANEL
PROFILES VARY
PANEL CLIP
MIN. 2 FASTENERS STRUCTURAL
PER CLIP METAL ROOF
PANEL
PREFORMED METAL
CLOSURE - SET IN OPTIONAL
SEALANT AND SEALANT
ATTACHED TO PANEL -
SEAL VERTICAL LEGS
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
4. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES THE PANELS ALONG THE RIDGE.
S-MTL-5
2001 NOT DRAWN TO SCALE
1371
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
SHEET METAL
RIDGE CAP
RIGID
POLYETHYLENE
VENT
GASKETED
SHEET METAL FASTENERS
CLEAT
SECTION :
PE
SLO
SEAM
AND PANEL
PROFILES VARY
PANEL CLIP
MIN. 2 FASTENERS STRUCTURAL FRAMING
PER CLIP MEMBER - PROFILES
AND SPACING VARY
PREFORMED METAL
STRUCTURAL
CLOSURE - SET IN SEALANT
METAL ROOF
AND ATTACHED TO PANEL -
PANEL
SEAL VERTICAL LEGS
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL WILL WORK FOR TRAPEZOIDAL STRUCTURAL PANELS ALSO.
4. IF THE ''Z'' CLOSURE IS FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES THE PANELS ALONG THE RIDGE.
S-MTL-5A
2001 NOT DRAWN TO SCALE
1372
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
HIP CAP
GASKETED
FASTENERS
SL
OP
E
E
OP
SL
STRUCTURAL
METAL ROOF PANEL
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL FIXES THE PANEL AT THE HIP IF THE CLOSURE IS FASTENED TO THE STRUCTURAL FRAMING MEMBER.
4. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
1373
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SL
OP
E
E
OP
SL
STRUCTURAL
METAL ROOF PANEL
STRUCTURAL FRAMING
PANEL CLIP
MEMBER -PROFILES
MIN. 2 FASTENERS
AND SPACING VARY
PER CLIP
HEAVY GAUGE
PREFORMED METAL
HIP SUPPORT METAL
CLOSURE - SET IN
SEALANT AND SHEET METAL HIP CAP
ATTACHED TO PANEL-
SEAL VERTICAL LEGS
OPTIONAL :CLIP WHEN ''Z'' CLOSURE
IS NOT FASTENED TO HIP SUPPORT METAL.
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. THIS DETAIL FIXES THE PANEL AT THE HIP IF THE ''Z'' CLOSURE IS FASTENED TO THE HIP SUPPORT METAL.
4. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
1374
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL METAL
ROOF PANEL
GASKETED FASTENERS
PE
SLO
SLO
PE
SLOPE
STRUCTURAL FRAMING
MEMBER - PROFILES HEAVY GAUGE VALLEY
AND SPACING VARY LINER SUPPORT METAL
VALLEY METAL SEAM AND PANEL
PROFILES VARY
CENTER RIB (1'' [25 mm] MEMBRANE VALLEY
MIN. HEIGHT) UNDERLAYMENT
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. MINIMUM VALLEY FLANGE WIDTHS FOR SLOPES 2:12 (9 DEGREES) OR LESS.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL FIXES THE PANELS AT THE VALLEY.
5. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
S-MTL-7
2001 NOT DRAWN TO SCALE
1375
The NRCA Roofing and Waterproofing Manual—Fifth Edition
7'' [
175
mm
SEE ]M
IN.
NO 7'' [175 mm] MIN.
TE
2
SEE NOTE 2
SLO
PE
E
OP
SL SLOPE
MEMBRANE VALLEY
VALLEY METAL UNDERLAYMENT
CENTER RIB (1''
[25 mm] MIN. HEIGHT)
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. MINIMUM VALLEY FLANGE WIDTHS FOR SLOPES 2:12 (9°) OR LESS. MINIMUM VALLEY FLANGE
WIDTHS INCREASE AS SLOPES DECREASE.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. PANEL TO VALLEY ENGAGEMANT DETERMINED BY PANEL LENGTH AND TYPE OF MATERIAL.
S-MTL-7A
2001 NOT DRAWN TO SCALE
1376
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WALL CONSTRUCTION
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
PREFORMED
METAL CLOSURE SET
IN SEALANT AND
ATTACHED TO
PANEL - SEAL
E
VERTICAL LEGS OP
SL
SEAM AND PANEL
PROFILES VARY
E
OP
SL
OPTIONAL SEALANT
STRUCTURAL
METAL ROOF OPTIONAL :
PANEL CONTINUOUS SHEET
m m] MEMBRANE LINER
STRUCTURAL FRAMING 00
'' [3
MEMBER - PROFILES AND . 12 L HEAVY GAUGE PANEL
X AL
SPACING VARY P RO O W END STIFFENING
A P T METAL OR
PANEL CLIP STRUCTURAL
MIN. 2 FASTENERS FRAMING MEMBER
PER CLIP
GASKETED
NOTES : FASTENERS
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. IF THE METAL PANELS ARE FASTENED THROUGH THE STRUCTURAL FRAMING, THIS FIXES THE
PANELS ALONG THE UPSLOPE END OF THE ROOF.
3. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
4. THIS DETAIL WILL WORK FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
5. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR ADDITIONAL
COUNTERFLASHING OPTIONS.
S-MTL-8
2001 NOT DRAWN TO SCALE
1377
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
SURFACE
TOOLED TO FACILITATE
MOUNTED
RUN OFF
SHEET METAL
RECEIVER
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C. OPTIONAL
SEALANT
REMOVABLE
E SHEET METAL
OP COUNTERFLASHING
SL
OPTIONAL :
CONTINUOUS SHEET
MEMBRANE LINER
SHEET METAL
ROOF TO WALL
FLASHING
SL
OP
E HEAVY GAUGE
PANEL SUPPORT
METAL
STRUCTURAL
METAL ROOF PANEL
1378
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SURFACE
MOUNTED
SHEET METAL
RECEIVER
OPTIONAL
SEALANT
REMOVABLE
SHEET METAL
APPROPRIATE FASTENERS COUNTERFLASHING
APPROX. 12'' [300 mm] O.C.
OPTIONAL
APPROPRIATE SEALANT
CONTINUOUS
: SHEET
TOOLED TO FACILITATE
MEMBRANE LINER
RUNOFF
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C. SHEET METAL
P E ROOF TO WALL
S LO
FLASHING
HEAVY GAUGE
PANEL SUPPORT
METAL
OPTIONAL SEALANT
SL
OP
E
''Z'' CLOSURE
SET IN SEALANT
AND FASTENED
STRUCTURAL
METAL ROOF PANEL
STRUCTURAL
FRAMING MEMBER -
PROFILES AND
SPACING VARY
NOTES :
1. SPECIFIC FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND BUILDING CODE.
2. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
3. REFER TO SM-13, 14, 15 IN THE SHEET METAL SECTION OF THE ROOFING MANUAL FOR ADDITIONAL
COUNTERFLASHING OPTIONS.
4. THIS DETAIL WORKS FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
FLEXIBLE MEMBRANE
SECTION :
LINER
GASKETED
FASTENERS
E
OP
SL
E
OP
SL
STRUCTURAL
METAL ROOF PANEL
1. SPECIFIC
: FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CONDITIONS.
2. THIS METHOD OF FLASHING FIXES THE PANELS AT THE EXPANSION JOINT IF THE ''Z'' STRIP IS FASTENED
THROUGH TO THE STRUCTURAL FRAMING / PANEL SUPPORT METAL.
3. THIS DETAIL WORKS FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
4. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER 1-1/2 TIMES THE FRAMED OPENING.
EXPANSION JOINT
(THROUGH-PANEL FASTENED)
S-MTL-10
2001 NOT DRAWN TO SCALE
1380
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
SECTION :
FLEXIBLE MEMBRANE
LINER
SHEET METAL
EXPANSION JOINT
COVER
FLEXIBLE FOAM ROD
GASKETED
FASTENER
GASKETED
FASTENER SEALANT
E
SEALANT OP
SL
E
OP
SL
HEAVY GAUGE
PANEL SUPPORT
NOTES :
METAL
1. SPECIFIC
: FASTENING REQUIREMENTS ARE NOT INDICATED, AS THEY VARY FROM SYSTEM TO
SYSTEM DEPENDING UPON PANEL MANUFACTURER'S REQUIREMENTS, WIND ZONE AND LOCAL CONDITIONS.
2. THIS METHOD OF FLASHING FIXES THE PANELS AT THE EXPANSION JOINT IF THE ''Z'' STRIP IS FASTENED
THROUGH TO THE STRUCTURAL FRAMING / PANEL SUPPORT METAL.
3. THIS DETAIL WORKS FOR FLAT PAN, VERTICAL LEG STRUCTURAL PANELS ALSO.
4. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
5. THE FLEXIBLE FOAM ROD SHOULD HAVE A MINIMUM DIAMETER 1-1/2 TIMES THE FRAMED OPENING.
EXPANSION JOINT
S-MTL-10A
2001 NOT DRAWN TO SCALE
1381
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL
FRAME
LE
AB
SEE DETAIL E ET
S-MTL-12 FOR -S
H
DT
FLASHING OF WI
SUPPORT LEGS
ROUND PIPE
COLUMN
NOTES :
1. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
S-MTL-11
2001 NOT DRAWN TO SCALE
1382
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WATERTIGHT SHEET
METAL RAIN COLLAR
WITH STAINLESS STEEL
DRAWBAND - OVERLAP
FLASHING COLLAR
3'' [75 mm] MIN.
EQUIPMENT SUPPORT
STAND/VENT STACK -
SEE NOTE
GASKETED FASTENERS
SECURE FLASHING COLLAR
FLANGE TO ROOF PANEL
OPTION :
SEALANT BEAD
BETWEEN PIPE AND
FLASHING TOOLED TO
FACILITATE RUNOFF
STAINLESS STEEL
STRUCTURAL DRAWBAND
METAL ROOF PANEL
PREFORMED
PENETRATION FLASHING
SET SECUREMENT
RING IN CONTINUOUS
BEAD OF SEALANT
1383
The NRCA Roofing and Waterproofing Manual—Fifth Edition
OPTIONAL :
CRICKET
OVERLAPPED JOINT
WITH TWO BEADS OF
SEALANT OR TAPE
STRUCTURAL
METAL ROOF PANEL 6'' [150 mm]
MIN. OVERLAP
GASKETED
GASKETED
FASTENERS
FASTENER
SEAL END
OF SEAMS OVERLAPPED
JOINT WITH
TWO BEADS
OF SEALANT
SEAM AND
PANEL
PROFILES
VARY
STRUCTURAL
FRAMING
MEMBER -
PROFILES AND
SPACING VARY
6'' [150 mm] MIN.
GASKETED
OVERLAP
FASTENERS
WITH SEALANT
IN SEAMS
NOTES :
1. NRCA SUGGESTS THAT DESIGNERS CONSIDER SPECIFYING CRICKETS WHEN THE RAISED CURB IS MORE THAN
24 INCHES [600 mm] WIDE. WATER DIVERTERS MAY BE USED IN LIEU OF CRICKETS WHEN THE RAISED CURB IS
LESS THAN 24 INCHES [600 mm] WIDE.
2. PROPER STRUCTURAL SUPPORT IS REQUIRED UNDER ALL SIDES OF THE RAISED CURB.
3. THIS DETAIL FIXES THE RAISED CURB TO THE STRUCTURAL METAL PANELS.
4. CURB MOUNTED EQUIPMENT SHOULD BE WEATHERPROOF AND HAVE A WEATHERPROOF INTERLOCK OR
SUFFICIENT OVERLAP WITH THE CURB.
5. INSULATION AND VAPOR RETARDER NOT SHOWN FOR CLARITY.
6. PREMANUFACTURED CURBS ARE AVAILABLE.
S-MTL-13
2001 NOT DRAWN TO SCALE
1384
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GASKETED FASTENERS
MIN (2) PER SIDE
2'' [50 mm]
MIN. OVERLAP
COUNTERFLASHING
SECTION :
STRUCTURAL MEMBER
~
PENETRATING ROOF
ASSEMBLY
TEMPERATURE APPROPRIATE
GASKET OR SEALANT TOOLED
TO FACILITATE RUNOFF
STAINLESS STEEL
DRAWBAND
METAL CURB CAP
METAL OR GYPSUM
BOARD LINER FOR
HOT PIPES
~ ~
1385
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL
SAME GAUGE
1.5'' TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL
SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL
ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
2
CLEAT
NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12 FEET, ALLOW A 1/4'' GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.
1386
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL
UP TO 38 mm 2
.81 mm 4.87 kg/m .64 mm .61 mm NOT REQUIRED
FACE
38 mm TO
1.02 mm 6.10 kg/m 2 .64 mm .61 mm NOT REQUIRED
75 mm FACE
38 mm TO 2 SAME GAUGE
75 mm FACE .81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL
75 mm TO 2 SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
75 mm MIN. 75 mm MIN.
FLANGE FLANGE FASTEN AT APPROX.
''A'' 150 mm O.C. WITH
CORROSION RESISTANT,
BARBED, ANNULAR RING,
OR SCREW SHANK NAIL.
LENGTH TO ACHIEVE
APPROX. 32 mm
PENETRATION INTO
20 mm 20 mm NAILER.
FASTEN NEAR LOWER
''T'' TYPE PROFILE ''L'' TYPE PROFILE BRAKE FOR INCREASED
20 mm UPLIFT RESISTANCE.
2
CLEAT
NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 4 m, ALLOW A 6 mm GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.
1387
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SOME COMMON ARCHITECTURAL AND STRUCTURAL METAL ROOFING PANEL PROFILES AND CLIPS
1388
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BELOW BLOCKING
ALTERNATE :
1'' [25 mm] MIN.
GASKETED FASTENERS
CONTINUOUS SHEET
MEMBRANE CLOSURE.
OPTIONAL IF DOUBLE
LOCK STANDING SEAM
JOINTS ARE USED WITH
THE METAL PARAPET CAP.
CONTINUOUS SHIM
CONTINUOUS CLEAT
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
IF CONCRETE, PRIME
BEFORE APPLYING SPF-
PREPARE AS REQUIRED
ROOF DECK -
NOTES :
PREPARE AS REQUIRED
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-1
2001 NOT DRAWN TO SCALE
1389
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ALTERNATE :
CONTINUOUS SHEET
MEMBRANE CLOSURE.
OPTIONAL IF DOUBLE LOCK
STANDING SEAM JOINTS ARE
USED WITH THE METAL
PARAPET CAP.
GASKETED FASTENERS
CONTINUOUS SHIM
CONTINUOUS CLEAT
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-1S
2001 NOT DRAWN TO SCALE
1390
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS CLEAT
1'' [25 mm] MIN.
BELOW TOP OF WALL
ELASTOMERIC COATING
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. ELASTOMERIC SEALANT TO BE COMPATIBLE WITH COATING.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1391
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ROOF DECK -
PREPARE AS REQUIRED
1'' [25 mm] MIN.
BELOW TOP OF WALL
CONTINUOUS CLEAT
NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. ELASTOMERIC SEALANT TO BE COMPATIBLE WITH COATING.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1392
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS CLEAT
1'' [25 mm] MIN.
BELOW TOP OF WALL
ELASTOMERIC COATING
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1393
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ELASTOMERIC COATING
ROOF DECK -
PREPARE AS REQUIRED
1'' [25 mm] MIN.
BELOW TOP OF WALL
CONTINUOUS CLEAT
NOTES :
1. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
2. THIS DETAIL SHOULD BE USED ONLY WHEN THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1394
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
OPTION :
SMOOTH CONCRETE
EXPOSED SURFACES MUST
BE WEATHERPROOFED
(BY OTHERS)
SHEET METAL
COUNTERFLASHING
COMPRESSIBLE ELASTOMERIC
TAPE TO SPAN
IRREGULARITIES
8'' [200 mm] MIN.
FLASHING HEIGHT
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
PRIME CONCRETE BEFORE
APPLYING SPF
ROOF DECK -
NOTES : PREPARE AS REQUIRED
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SURFACE-MOUNT COUNTERFLASHING
SPF-4
2001 NOT DRAWN TO SCALE
1395
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
SMOOTH CONCRETE -
EXPOSED SURFACES MUST
BE WATERPROOFED
(BY OTHERS)
COMPRESSIBLE ELASTOMERIC
TAPE TO SPAN
IRREGULARITIES
SHEET METAL
COUNTERFLASHING
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
PRIME CONCRETE BEFORE
APPLYING SPF
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SURFACE-MOUNT COUNTERFLASHING
SPF-4S
2001 NOT DRAWN TO SCALE
1396
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1397
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
FOAM STOP
ELASTOMERIC
COATING
ALTERNATE :
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
2. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1398
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
BASE SHEET FASTENERS
LIGHTWEIGHT INSULATING
CONCRETE
VENTED GALVANIZED
NOTES : STEEL DECK
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
OR WHEN REROOFING OVER EXISTING WET-FILL DECKS.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
4. WOOD BLOCKING SHOULD BE SLOTTED FOR VENTING OF WET-FILL DECKS WHERE APPLICABLE.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-5A
2001 NOT DRAWN TO SCALE
1399
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
LIGHTWEIGHT INSULATING
CONCRETE
VENTED GALVANIZED
NOTES : STEEL DECK
1. THIS DETAIL TO BE USED OVER WET-FILL DECKS (E.G., LIGHTWEIGHT INSULATING CONCRETE, POURED GYPSUM)
OR WHEN REROOFING OVER EXISTING WET-FILL DECKS.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE WALL.
3. REFER TO SPF-TABLE 2 FOR ALTERNATE SHEET METAL COUNTERFLASHING TERMINATIONS.
4. WOOD BLOCKING SHOULD BE SLOTTED FOR VENTING OF WET-FILL DECKS WHERE APPLICABLE.
5. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-5AS
2001 NOT DRAWN TO SCALE
1400
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM
STOP
ALTERNATE :
FASTENERS APPROX. 24''
[600 mm] O.C.
FASTENERS APPROX.
8'' [200 mm] O.C.
8'' [200 mm] MIN.
FLASHING HEIGHT
FLEXIBLE VAPOR RETARDER
w/ COMPRESSIBLE
INSULATION
1401
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
WOOD CANT IF NECESSARY
TO BRACE CURB PREPARE
AS REQUIRED
1402
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
FOAM STOP
OPTIONAL IF DOUBLE
LOCK STANDING SEAM 3/4'' 3/4''
[19 mm] [19 mm]
JOINTS ARE USED WITH MIN. MIN.
THE METAL PARAPET OVERHANG OVERHANG
CAP.
FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
COMPRESSIBLE
INSULATION ALTERNATE :
FLASHING HEIGHT
8'' [200 mm] MIN.
GASKETED FASTENERS
TOP OF CURB TO
DRAIN TO ONE SIDE
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
WOOD CANT IF THICKNESS)
NECESSARY TO BRACE
CURB PREPARE AS
REQUIRED ROOF DECK -
PREPARE AS REQUIRED
WOOD NAILER(S) PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-7
2001 NOT DRAWN TO SCALE
1403
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE.
FOAM STOP
OPTONAL IF DOUBLE
LOCK STANDING SEAM 3/4'' 3/4''
[19 mm] [19 mm]
JOINTS ARE USED WITH MIN. MIN.
THE METAL PARAPET OVERHANG OVERHANG
CAP.
FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
ALTERNATE :
COMPRESSIBLE
INSULATION
TOP OF CURB TO
DRAIN TO ONE SIDE
GASKETED FASTENERS
ELASTOMERIC COATING
WOOD CANT IF
NECESSARY TO SPRAY POLYURETHANE
BRACE CURB FOAM (1'' [25 mm] MIN.
PREPARE AS REQUIRED THICKNESS)
WOOD NAILER(S)
ROOF DECK -
PREPARE AS REQUIRED
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-7S
2001 NOT DRAWN TO SCALE
1404
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PREMANUFACTURED
EXPANSION JOINT COVER FOAM STOP
3/4'' 3/4''
FLEXIBLE WATERPROOF [19 mm] [19 mm]
MIN. MIN.
MEMBRANE CLOSURE OVERHANG OVERHANG
FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
COMPRESSIBLE
INSULATION
ALTERNATE :
FLASHING HEIGHT
8'' [200 mm] MIN.
GASKETED FASTENERS
TOP OF CURB TO
DRAIN TO OUTSIDE
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
WOOD CANT IF THICKNESS)
NECESSARY TO
BRACE CURB
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ALLOWS FOR BUILDING MOVEMENT IN MULTIPLE DIRECTIONS.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EXPANSION JOINT.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1405
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
PREMANUFACTURED
EXPANSION JOINT COVER 3/4'' 3/4''
[19 mm] [19 mm]
MIN. MIN.
OVERHANG OVERHANG
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
FLEXIBLE VAPOR
RETARDER TO
SERVE AS INSULATION
RETAINER (ATTACHED
TO TOP OF CURB)
COMPRESSIBLE OPTION :
INSULATION
TOP OF CURB TO
DRAIN TO OUTSIDE
GASKETED FASTENERS
FLASHING HEIGHT
8'' [200 mm] MIN.
ELASTOMERIC COATING
WOOD CANT IF
NECESSARY TO
SPRAY POLYURETHANE
BRACE CURB -
FOAM (1'' [25 mm] MIN.
PREPARE AS REQUIRED
THICKNESS)
WOOD NAILER(S) -
PREPARE AS REQUIRED ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1406
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
3/4''
[19 mm]
MIN.
OVERHANG
ROOF SYSTEM
DIVIDER COVER
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
ALTERNATE :
FLASHING HEIGHT
8'' [200 mm] MIN.
GASKETED FASTENERS
TOP OF CURB TO
DRAIN TO ONE SIDE
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
WOOD NAILER(S) -
PREPARE AS REQUIRED
ROOF DECK -
NOTES :
PREPARE AS REQUIRED
1. A ROOF SYSTEM DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED
TO THE ROOF DECK. ROOF SYSTEM DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. REFER TO APPROPRIATE SECTION OF LOW-SLOPE CONSTRUCTION DETAILS FOR FLASHING REQUIREMENTS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-8
2001 NOT DRAWN TO SCALE
1407
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
3/4'' 3/4''
[19 mm] [19 mm]
MIN. MIN.
OVERHANG OVERHANG
ROOF SYSTEM
DIVIDER COVER
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
ALTERNATE :
GENERIC ROOF
SYSTEM
TOP OF CURB TO
DRAIN TO ONE SIDE
GASKETED FASTENERS
ELASTOMERIC COATING
FLASHING HEIGHT
8'' [200 mm] MIN.
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
NOTES :
1. A ROOF SYSTEM DIVIDER IS A RAISED DOUBLE WOOD MEMBER THAT IS PROPERLY ANCHORED
TO THE ROOF DECK. ROOF SYSTEM DIVIDERS SHOULD NEVER RESTRICT THE FLOW OF WATER.
2. REFER TO APPROPRIATE SECTION OF LOW-SLOPE CONSTRUCTION DETAILS FOR FLASHING REQUIREMENTS.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-8S
2001 NOT DRAWN TO SCALE
1408
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE ALTERNATE:
FLASHING HEIGHT
8'' [200 mm] MIN.
GASKETED FASTENER
EQUIPMENT LEG
NEOPRENE PAD
ELASTOMERIC COATING
SPRAY POLYURETHANE
WOOD NAILER(S) FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
NOTES : PREPARE AS REQUIRED
1. THIS DETAIL ALLOWS FOR ROOF SYSTEM MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS SUPPORT
IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE SPREAD ACROSS TWO OR
MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED OR WHERE THE LOAD CAN BE
CONCENTRATED OVER A COLUMN, DETAIL SPF-10 MAY BE PREFERRED. A MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL
CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT OF ROOFING AND FLASHING BETWEEN PARALLEL
SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM
OF SUPPORTED EQUIPMENT.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EQUIPMENT SUPPORT CURB.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-9
2001 NOT DRAWN TO SCALE
1409
The NRCA Roofing and Waterproofing Manual—Fifth Edition
EQUIPMENT LEG
SET BOLTS IN
SEALANT
NEOPRENE PAD
OR SEALANT
FLEXIBLE WATERPROOF
MEMBRANE CLOSURE
GASKETED FASTENER
PRIME WOOD
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
WOOD NAILER(S) - THICKNESS)
PREPARE AS REQUIRED
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ALLOWS FOR ROOF SYSTEM MAINTENANCE AROUND THE SUPPORTED EQUIPMENT. THE CONTINUOUS SUPPORT
IS PREFERRED IN LIGHTWEIGHT STRUCTURAL SYSTEMS BECAUSE THE EQUIPMENT WEIGHT CAN BE SPREAD ACROSS TWO OR
MORE SUPPORTING MEMBERS. WHERE HEAVY STRUCTURAL SYSTEMS ARE USED OR WHERE THE LOAD CAN BE
CONCENTRATED OVER A COLUMN, DETAIL SPF-10 MAY BE PREFERRED. A MINIMUM OF 2 FEET [600 mm] OF HORIZONTAL
CLEARANCE MUST BE PROVIDED FOR REMOVAL AND REPLACEMENT OF ROOFING AND FLASHING BETWEEN PARALLEL
SUPPORTS. REFER TO TABLE ABOVE FOR RECOMMENDATIONS ON VERTICAL CLEARANCE FROM ROOF SURFACE TO BOTTOM
OF SUPPORTED EQUIPMENT.
2. FLASHING REQUIREMENTS TYPICAL FOR BOTH SIDES OF EQUIPMENT SUPPORT CURB.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-9S
2001 NOT DRAWN TO SCALE
1410
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
HEIGHT-
SEE TABLE
SEE
DETAIL SPF-11
FOR FLASHING
OF SUPPORT LEGS
ROUND
PIPE COLUMN LE
AB
E ET
-S
H
I DT
W
NOTES :
1. THIS DETAIL MAY BE PREFERABLE TO DETAIL SPF-9 WHEN THE CONCENTRATED LOADS CAN BE LOCATED DIRECTLY
OVER COLUMNS OR HEAVY GIRDERS IN THE STRUCTURE OF THE BUILDING. THIS DETAIL CAN BE ADAPTED FOR OTHER
USES, SUCH AS SIGN SUPPORTS.
SPF-10
2001 NOT DRAWN TO SCALE
1411
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
(SEE SPF-10)
SUPPORT COLUMN
ELASTOMERIC COATING
ROOF DECK -
PREPARE AS REQUIRED
1412
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
(SEE SPF-10)
FOR HEIGHT OF LEGS
SEE TABLE ON SPF-10
SUPPORT COLUMN
ELASTOMERIC COATING
ROOF DECK -
PREPARE AS REQUIRED
1413
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WOOD NAILER
FLASHING HEIGHT
SEALING MATERIAL
8'' [200 mm] MIN.
ALTERNATE
CURB BEARING
LOCATION FOR
HEAVY WEIGHT
LOADING SPRAY
CONDITIONS POLYURETHANE FOAM
(1'' [25 mm] MIN.
THICKNESS)
MECHANICAL UNIT, HOOD, ETC.
PRIME METAL
BASE OF UNIT EXTENDS 1/2''
[13 mm] MINIMUM BEYOND
BEFORE APPLYING SPF
TOP OF CURB
ROOF DECK -
SEALING MATERIAL - MUST PREPARE AS REQUIRED
BE CONTINUOUS ON THE
PERIMETER
WOOD NAILER(S) -
1'' [25 mm] MINIMUM BELOW PREPARE AS REQUIRED
TOP OF CURB
1414
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALING MATERIAL
PREFABRICATED METAL
CURB; PRIME BEFORE
APPLYING SPF
PRIME METAL
BEFORE
APPLYING SPF
MIN. FLASHING HEIGHT
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
8'' [200 mm]
MIN. THICKNESS)
ELASTOMERIC
COATING
ALTERNATE
CURB BEARING WOOD NAILER(S) -
LOCATION FOR PREPARE AS REQUIRED
HEAVY WEIGHT
LOADING ROOF DECK -
CONDITIONS PREPARE AS REQUIRED
NOTES :
1. THE CURB, WOOD NAILER AND SEAL STRIP ARE TO BE SUPPLIED BY THE CURB MANUFACTURER.
2. WHEN POSSIBLE, THE MECHANICAL UNITS SHOULD NOT BE SET UNTIL THE ROOF SYSTEM HAS BEEN INSTALLED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1415
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
WOOD CURB -
PREPARE AS REQUIRED SEALING MATERIAL
SHEET METAL
FLASHING RECEIVER
FLASHING HEIGHT
8'' [200 mm] MIN.
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
1416
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
SEALING MATERIAL
SHEET METAL
FLASHING RECEIVER
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FLASHING HEIGHT
8'' [200 mm] MIN.
REMOVABLE
SHEET METAL
COUNTERFLASHING
ELASTOMERIC COATING
SPRAY POLYURETHANE
WOOD CURB - FOAM (1'' [25 mm]
PREPARE AS REQUIRED MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. SELF FLASHING EQUIPMENT DOES NOT REQUIRE COUNTERFLASHING.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1417
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
SKYLIGHT FRAME
WITH WEEP HOLES
FLASHING HEIGHT
8'' [200 mm] MIN.
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
WOOD CURB -
PREPARE AS REQUIRED
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. IF UNIT COUNTERFLASHING EXTENDS 3'' OVER FLASHING, COUNTERFLASHING IS NOT REQUIRED.
2. FOR SCUTTLES, ADDITIONAL WEAR SURFACE SHOULD BE CONSIDERED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-14
2001 NOT DRAWN TO SCALE
1418
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
SKYLIGHT FRAME
WITH WEEP HOLES
GASKETED FASTENERS
MINIMUM TWO
FLASHING HEIGHT
FASTENERS PER SIDE
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
WOOD CURB -
PREPARE AS REQUIRED
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. IF UNIT COUNTERFLASHING EXTENDS 3'' OVER FLASHING, COUNTERFLASHING IS NOT REQUIRED.
2. FOR SCUTTLES, ADDITIONAL WEAR SURFACE SHOULD BE CONSIDERED.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-14S
2001 NOT DRAWN TO SCALE
1419
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
STRUCTURAL MEMBER
ALTERNATE :
INSULATE VOID TO
PREVENT CONDENSATION
FLASHING HEIGHT
8'' [200 mm] MIN.
FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
WOOD DECK -
PREPARE AS REQUIRED
ROOF CURB -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURB CONSTRUCTION
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTURBING THE ROOFING SYSTEM.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1420
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL MEMBER
OPTION :
INSULATE VOID TO
PREVENT CONDENSATION
FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE
SHEET METAL
FLASHING HEIGHT
COUNTERFLASHING
8'' [200 mm] MIN.
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
WOOD CURB -
PREPARE AS REQUIRED
NOTES :
1. THIS DETAIL ILLUSTRATES ONE METHOD OF ELIMINATING PITCH POCKETS. THE CURBED CONSTRUCTION
ALLOWS FOR MOVEMENT IN THE STRUCTURAL MEMBER WITHOUT DISTRUBING THE ROOFING SYSTEM.
2. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1421
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
ENCLOSURE WITH
REMOVABLE TOP
CROSSBREAK OR SLOPE
FOR DRAINAGE
SEALANT
SHEET METAL OR
FLEX-TUBE COLLAR
8'' [200 mm] MIN.
FLASHING
HEIGHT
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-16
2001 NOT DRAWN TO SCALE
1422
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL
ENCLOSURE WITH
REMOVABLE TOP
CROSSBREAK OR SLOPE
FOR DRAINAGE
SEALANT
SHEET METAL OR
FLEX-TUBE COLLAR
SLOPE PIPES AWAY
FROM HOOD
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE SHEET
METAL COUNTERFLASHING
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
NOTES :
1. THIS DETAIL ILLUSTRATES ANOTHER METHOD OF ELIMINATING PITCH POCKETS AND AN OPTIONAL METHOD OF
GROUPING PIPING THAT MUST COME UP ABOVE THE ROOF SURFACE.
2. MANY MANUFACTURERS OFFER PREFABRICATED BOOTS AND OTHER MATERIALS FOR THIS PURPOSE.
SPECIFICS ON THESE PROPRIETARY DESIGNS VARY GREATLY, AND INDIVIDUAL MANUFACTURERS'
SPECIFICATIONS SHOULD BE CONSULTED FOR THEIR USE.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-16S
2001 NOT DRAWN TO SCALE
1423
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL OR
FLEX-TUBE COLLAR
SEALANT
PIPES TO BE 8''
MINIMUM [200 mm]
ABOVE HORIZONTAL
SURFACE OF SPF
ROOF DECK -
PREPRARE AS REQUIRED
SPF-16A
2001 NOT DRAWN TO SCALE
1424
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SHEET METAL OR
FLEX-TUBE COLLAR
SEALANT
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
INSULATE VOID
FOR COLD STACKS
ROOF DECK -
WOOD ENCLOSURE - PREPARE AS REQUIRED
PREPARE AS REQUIRED
SPF-16AS
2001 NOT DRAWN TO SCALE
1425
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
ALTERNATE :
TEMPERATURE
APPROPRIATE
8'' [200 mm] MIN.
ELASTOMERIC SEALANT
FLASHING
HEIGHT
DRAWBAND OR WELD
COVER TO STACK
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
REMOVABLE
SHEET METAL
COUNTERFLASHING
ELASTOMERIC COATING
WOOD CURB -
PREPARE AS REQUIRED
VARIES
SPRAY POLYURETHANE
METAL OR GYPSUM FOAM (1'' [25 mm]
LINER IF REQUIRED MIN. THICKNESS)
ROOF DECK -
NOTES : PREPARE AS REQUIRED
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED.
2. THE METAL LINER, THE CLEARANCE NECESSARY BETWEEN THE LINER AND THE STACK,
AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL
HANDLED BY THE STACK.
3. IF COVER EXTENDS OVER FLASHING 3'', COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-17
2001 NOT DRAWN TO SCALE
1426
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
TEMPERATURE
APPROPRIATE
ELASTOMERIC
SEALANT
DRAWBAND OR
WELD COVER
TO STACK ALTERNATE :
METAL OR GYPSUM
LINER IF REQUIRED
GASKETED FASTENERS
MINIMUM TWO
FASTENERS PER SIDE
FLASHING HEIGHT
8'' [200 mm] MIN.
REMOVABLE
SHEET METAL
COUNTERFLASHING
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
VARIES
NOTES :
WOOD CURB -
1. THIS DETAIL ALLOWS THE OPENING TO BE COMPLETED BEFORE THE STACK IS PLACED. PREPARE AS REQUIRED
2. THE METAL LINER, THE CLEARANCE NECESSARY BETWEEN THE LINER AND THE STACK,
AND THE NEED FOR INSULATION, WILL DEPEND ON THE TEMPERATURE OF THE MATERIAL
HANDLED BY THE STACK.
3. IF COVER EXTENDS OVER FLASHING 3'' [75 mm], COUNTERFLASHING IS NOT REQUIRED.
4. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-17S
2001 NOT DRAWN TO SCALE
1427
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DECK SUPPORTED
PENETRATION
PREPARE PLUMBING
VENT STACK BEFORE
APPLYING SPF AS
REQUIRED
EXTEND ELASTOMERIC
COATING 2'' [50 mm]
ABOVE TERMINATION OF
SPRAY POLYURETHANE
FOAM
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. WHERE DIFFERENTIAL MOVEMENT IS A CONCERN, SEE DETAIL SPF-19.
2. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
SPF-18
2001 NOT DRAWN TO SCALE
1428
The NRCA Roofing and Waterproofing Manual—Fifth Edition
NON-DECK SUPPORTED
PENETRATION
1/4'' [6 mm] MIN.
CLEARANCE BETWEEN SEALANT
RAIN COLLAR AND
DRAWBAND
FLASHING COLLAR
WATERTIGHT SHEET
METAL RAIN COLLAR
OVERLAPPING FLASHING
COLLAR BY RADIUS OF
3'' TO 4'' [75 TO 100 mm]
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
ROOF DECK
NOTES :
1. THIS DETAIL ACCOMMODATES INDEPENDENT DECK AND PENETRATION MOVEMENT.
2. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
SPF-19
2001 NOT DRAWN TO SCALE
1429
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ROOF DECK -
PREPARE AS REQUIRED
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS
V-GROOVE SPF AT CLAMPING
RING AND INSTALL COMPATIBLE
ELASTOMERIC SEALANT
CLAMPING RING
DRAIN STRAINER
DECK CLAMP
DRAIN BOWL
ELASTOMERIC COATING
NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
ROOF DRAIN
SPF-20
2001 NOT DRAWN TO SCALE
1430
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DRAIN STRAINER
ALTERNATE :
V-GROOVE SPF AT CLAMPING
RING AND INSTALL COMPATIBLE
ELASTOMERIC SEALANT
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS
ROOF DECK -
PREPARE AS REQUIRED
CLAMPING RING
DECK CLAMP
DRAIN BOWL
NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
ROOF DRAIN
SPF-20S
2001 NOT DRAWN TO SCALE
1431
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ROOF DECK -
PREPARE AS REQUIRED
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS
DECK CLAMP
DRAIN BOWL
ELASTOMERIC COATING
NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
SPF-20A
2001 NOT DRAWN TO SCALE
1432
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS
ELASTOMERIC COATING
ROOF DECK -
PREPARE AS REQUIRED
DECK CLAMP
DRAIN BOWL
NOTES :
1. TAPER SPF TOWARD DRAIN BOWL TO PROVIDE POSITIVE DRAINAGE.
2. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN RECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
3. WHERE THE SURFACE SKIN IS TRIMMED OR GROUND FLUSH, ADDITIONAL BASE COATING THICKNESS IS REQUIRED.
SPF-20AS
2001 NOT DRAWN TO SCALE
1433
The NRCA Roofing and Waterproofing Manual—Fifth Edition
V-GROOVE SPF AT
LOWER EDGE AND
INSTALL
ELASTOMERIC
SEALANT
ALTERNATE :
PROPERLY PREPARE
METAL FLANGE
BEFORE APPLYING
SPF TO ENHANCE
ADHESION
EXTEND ELASTOMERIC
COATING ONTO SHEET
METAL SCUPPER LINER
2'' [50 mm] MIN.
PAST EDGE OF SPF
SHEET METAL
SCUPPER LINER
PARAPET WALL
ROOF DECK -
PREPARE AS REQUIRED
ELASTOMERIC
COATING
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
1434
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ELASTOMERIC COATING
EXTEND ONTO SHEET
METAL SCUPPER LINER
2'' [50 mm] MIN.
PAST TERMINATION
OF SPF
SEALANT
PROPERLY PREPARE
METAL FLANGE
BEFORE APPLYING
SPF TO ENHANCE
ADHESION
SHEET METAL
SCUPPER LINER
ROOF DECK -
PREPARE AS REQUIRED
1435
The NRCA Roofing and Waterproofing Manual—Fifth Edition
DOUBLE THICKNESS OF
ELASTOMERIC COATING
AT EDGE
ELASTOMERIC COATING
PROPERLY PREPARE
METAL FLANGE BEFORE
ROOF DECK - APPLYING SPF TO
PREPARE AS ENHANCE ADHESION
REQUIRED
V-GROOVE SPF AT
EDGE AND INSTALL
ELASTOMERIC SEALANT
NOTES :
1. IN CLIMATES WHERE THE WINTER TERMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF TIME,
NRCA SUGGESTS USING SPF-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
GUTTER
SPF-22
2001 NOT DRAWN TO SCALE
1436
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GUTTER SPACER
ALTERNATELY
SPACED FROM
BRACKETS
ROOF DECK -
PREPARE AS REQUIRED
SECONDARY PROTECTION
SHEET METAL
GUTTER
GUTTER BRACKET
SUPPORT AT 12'' TO 36''
[300 mm TO 900 mm]
O.C. DEPENDING UPON
CONDITIONS
NOTES :
1. IN CLIMATES WHERE THE WINTER TERMPERATURE REMAINS BELOW FREEZING FOR EXTENDED PERIODS OF TIME,
NRCA SUGGESTS USING SPF-2 AND INTERIOR DRAINS OR THROUGH-CURB SCUPPERS TO DRAIN THE ROOF.
2. GUTTER BRACKETS ARE RECOMMENDED TO BE AT LEAST ONE GAUGE HEAVIER THAN GUTTER STOCK.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
GUTTER
SPF-22S
2001 NOT DRAWN TO SCALE
1437
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOAM STOP
SHEET METAL
COUNTERFLASHING/EAVE
FLASHING
OPTION :
MIN. FLASHING
HEIGHT
8'' [200 mm]
ELASTOMERIC COATING
SPRAY POLYURETHANE
FOAM (1'' [25mm]
MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
SPF-23
2001 NOT DRAWN TO SCALE
1438
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ADHERED FLASHING
MEMBRANE (EXTEND
APPROX. 3'' [75 mm]
BEYOND FLANGE)
FLEECE-BACKED
MEMBRANE
SPRAY POLYURETHANE
FOAM ADHESIVE
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
WOOD NAILERS
EXTEND FIELD SHEET
TO BELOW BLOCKING
CONTINUOUS CLEAT
(FASTENED PER TABLE 1)
NOTES :
1. NRCA SUGGESTS AVOIDING (WHERE POSSIBLE) FLASHING DETAILS THAT REQUIRE RIGID METAL FLANGES TO BE EMBEDDED
OR SANDWICHED INTO THE ROOF MEMBRANE.
2. THIS DETAIL SHOULD BE USED ONLY WHERE THE DECK IS SUPPORTED BY THE OUTSIDE WALL.
3. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
FLEECE-BACKED MEMBRANE
SPRAY POLYURETHANE
FOAM ADHESIVE
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1440
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FASTENERS APPROX.
8'' [200 mm] O.C.
8'' [200 mm] MIN.
FLASHING HEIGHT
FLEXIBLE VAPOR RETARDER
WITH COMPRESSIBLE
INSULATION
FLEECE-BACKED MEMBRANE
SPRAY POLYURETHANE
FOAM ADHESIVE
WOOD NAILER(S) -
PREPARE AS REQUIRED
SPRAY POLYURETHANE
FOAM (1'' [25 mm] MIN.
THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. REFER TO THE SHEET METAL SECTION OF THE METAL ROOFING MANUAL FOR JOINERY AND SECUREMENT OPTIONS
FOR SHEET METAL.
1441
The NRCA Roofing and Waterproofing Manual—Fifth Edition
STRUCTURAL FRAME
SEE SPF-10
SEALANT
FLASHING MEMBRANE
(8'' [200 mm] MIN. HEIGHT)
FLEECE-BACKED MEMBRANE
SPRAY POLYURETHANE
FOAM ADHESIVE
ROOF DECK -
PREPARE AS REQUIRED
1442
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
DRAWBAND
INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING
PREFABRICATED
MEMBRANE FLASHING
(8'' [200 mm] MIN.
HEIGHT)
SPRAY POLYURETHANE
FOAM ADHESIVE
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS)
ROOF DECK -
PREPARE AS REQUIRED
NOTES :
1. VENT STACKS AND OTHER PIPES SHOULD HAVE A MINIMUM OF 12 INCHES [300 mm] OF CLEARANCE ON ALL SIDES
FROM WALLS, CURBS AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
2. NRCA RECOMMENDS FLASHINGS BE 8'' (200 mm) HIGH, HOWEVER, NRCA IS AWARE THAT PRE-MANUFACTURED BOOT
FLASHINGS GENERALLY WILL NOT MEET THE HEIGHT REQUIREMENT.
PLUMBING VENT
(PREMANUFACTURED BOOT)
SPF-18(FB)
2001 NOT DRAWN TO SCALE
1443
The NRCA Roofing and Waterproofing Manual—Fifth Edition
ROOF DECK -
PREPARE AS REQUIRED
SPRAY POLYURETHANE
FOAM (1'' [25 mm]
MIN. THICKNESS
DRAIN STRAINER
CLAMPING RING
DECK CLAMP
ROUND CUT IN
FLEECE-BACKED MEMBRANE
EXTEND APPROX. 1'' [25 mm]
PAST CLAMPING RING
DRAIN BOWL
SPRAY POLYURETHANE
FOAM ADHESIVE
NOTES :
1. THE USE OF A METAL DECK SUMP PAN IS NOT RECOMMENDED. HOWEVER, DRAIN TECEIVER/BEARING PLATES
ARE APPLICABLE WITH SOME PROJECTS.
2. THE DESIGNER SHOULD CONSIDER INSULATING THE DRAIN COMPONENTS BELOW THE DECK TO PREVENT
POTENTIAL CONDENSATION.
3. MEMBRANE SEAMS SHOULD NOT INTERSECT DRAIN CLAMPING RING.
ROOF DRAIN
SPF-20(FB)
2001 NOT DRAWN TO SCALE
1444
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL
SAME GAUGE
UP TO 3'' FACE .032'' 16 oz. 24 ga. 26 ga. AS FASCIA METAL
SAME GAUGE
3'' TO 6'' FACE .040'' 16 oz. 24 ga. 24 ga. AS FASCIA METAL
ONE GAUGE
6'' TO 8'' FACE .050'' 20 oz. 24 ga. 24 ga. HEAVIER THAN
FASCIA METAL
ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ADD BRAKES TO ONE GAUGE
8'' TO 15'' FACE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE STIFFEN OR USE HEAVIER THAN
TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE TWO-PIECE FACE FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
3/4''
2
''A'' TYPE PROFILE CLEAT
NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 12 FEET ALLOW A 1/4'' GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.
1445
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GALVANIZED
EXPOSED FACE ALUMINUM COLD STAINLESS
OR COATED STEEL 2
WITHOUT BRAKES ALLOY ROLLED CLEAT
(G90) (302 AND 304)
''A'' DIMENSION (3003) COPPER
STEEL
UP TO 2
1.02 mm 6.10 kg/m .64 mm .61 mm NOT REQUIRED
75 mm FACE
UP TO 2 SAME GAUGE
.81 mm 4.87 kg/m .64 mm .46 mm AS FASCIA METAL
75 mm FACE
75 mm TO 2
SAME GAUGE
150 mm FACE 1.02 mm 4.87 kg/m .64 mm .61 mm AS FASCIA METAL
1
RECOMMENDED PROFILES AND FASTENING FOR FASCIA AND CLEAT
20 mm
2
''A'' TYPE PROFILE CLEAT
NOTES :
1. CONSIDERATION MUST BE GIVEN TO WIND ZONE AND LOCAL CONDITIONS FOR THE SELECTION OF METAL GAUGE, PROFILE,
AND FASTENING SCHEDULE. SEVERE CONDITIONS OR CODE AND REGULATORY BODIES MAY REQUIRE MORE CONSERVATIVE
DESIGNS. WHEN USING THE ABOVE TABLE, ADDITIONAL ITEMS SHOULD BE CONSIDERED, SUCH AS FASTENING PATTERN.
2. ALL CLEATS SHALL BE CONTINUOUS WITH LENGTHS NOT TO EXCEED 4 m. ALLOW A 6 mm GAP BETWEEN PIECES.
JOINTS IN CLEAT SHOULD NOT COINCIDE WITH JOINTS IN FASCIA METAL.
1446
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
APPROPRIATE SEALANT
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
1447
The NRCA Roofing and Waterproofing Manual—Fifth Edition
APPROPRIATE SEALANT
TOOLED TO FACILITATE
RUNOFF
APPROPRIATE FASTENERS
APPROX. 12'' [300 mm] O.C.
SURFACE MOUNTED
SHEET METAL RECEIVER
APPROPRIATE FASTENERS
24'' [600 mm] O.C.
OPTIONAL: SEALANT OR
ELASTOMERIC TAPE
OPTIONAL: SEALANT OR
ELASTOMERIC TAPE
1448
The NRCA Roofing and Waterproofing Manual—Fifth Edition
BUILDING PAPER
(IF REQUIRED)
WALL CLADDING
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
APPROPRIATE FASTENERS
APPROX. 24'' [600 mm] O.C.
1449
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CONTINUOUS CLEATS
4''
. 3/
OX
PR
TYPICAL AP
CLEAT ENGAGEMENT
APPROPRIATE FASTENERS
FASTENED APPROX. 6''
[150 mm] O.C.
. CONTINUOUS CLEAT
M IN
m] APPROPRIATE FASTENERS
[5 0m
2'' FASTENED APPROX. 6''
[150 mm] O.C.
1450
The NRCA Roofing and Waterproofing Manual—Fifth Edition
2'-
0'
MI ' [600
NI
MU mm
M ]
[ 12
CL 300 ''
MI EAR mm]
NI AN
MU C
M E 12
[
CL 300 ''
MI EAR mm] 12
''
m] CE
NI AN
MU C
0 0 m AN
M E 12 [3 EA R
[
CL 300 '' CL
m
MI EAR m]
NI AN
MU C
M E
1451
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SUMPED
ROOF DRAIN
CURBED
PENETRATION
SL
OP
E
SADDLE CRICKET
SLO
PE
SUMPED
ROOF DRAIN
NOTES :
1. SADDLES SHOULD BE LOCATED IN VALLEYS BETWEEN ROOF DRAINS AND CRICKETS ON THE HIGH SIDE OF CURBS.
2. LOCATE ROOF DRAINS AT POINTS OF MAXIMUM DECK DEFLECTION / LOW AREAS FOR DRAINAGE.
SPF - TABLE 5
2001 NOT DRAWN TO SCALE
1452
The NRCA Roofing and Waterproofing Manual—Fifth Edition
RAISED
PERIMETER EDGE
CURBED
PENETRATION
CRICKET
THROUGH EDGE
SCUPPER
SL
OP
E
SHEET METAL
CONDUCTOR
HEAD
SL
OP
E
CRICKET
NOTES :
1. SADDLE SHOULD BE LOCATED BETWEEN THROUGH-EDGE OR WALL SCUPPERS AND CRICKETS ON THE HIGH SIDE OF CURBS
2. RAISED PERIMETER EDGES WHERE TAPERED CRICKETS ARE USED NECESSITATE THE SPECIFICATION OF RELATIVELY WIDE
(TALL) DIMENSIONAL LUMBER OR THE ERECTION OF FRAMED WALLS.
1453
The NRCA Roofing and Waterproofing Manual—Fifth Edition
GEOCOMPOSITE NON-PRESSURE
OR PROTECTION SLAB-ON GRADE
COURSE
VAPOR
RETARDER
WATERPROOF
MEMBRANE AGGREGATE
UNDERLAYMENT
FOOTING
FILLET - IF
REQUIRED FOR
MEMBRANE TYPE
FILTER FABRIC
PERFORATED DRAIN
PIPE SET IN
AGGREGATE BED
1454
The NRCA Roofing and Waterproofing Manual—Fifth Edition
NON-PRESSURE
CONCRETE
SLAB-ON-GRADE
GEOCOMPOSITE
OR PROTECTION VAPOR RETARDER
COURSE
AGGREGATE
FILLET - IF UNDERLAYMENT
REQUIRED FOR
MEMBRANE TYPE
WATERPROOF
MEMBRANE
FOOTING
PERFORATED DRAIN
PIPE SET IN
AGGREGATE BED
FILTER FABRIC
1455
The NRCA Roofing and Waterproofing Manual—Fifth Edition
WATERSTOP
WATERPROOF (OPTIONAL)
MEMBRANE
PRESSURE MAT
FILLET - IF REQUIRED SLAB
FOR MEMBRANE
TYPE
PROTECTION
COURSE
WORK SLAB
1456
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PROTECTION
COURSE FOUNDATION WALL
WATERPROOF WATERSTOP
MEMBRANE (OPTIONAL)
WORK SLAB
1457
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOUNDATION CRACK
WITH V-SHAPED
GROOVE FILLED WITH
CEMENTITIOUS OR
METALLIC GROUT
CEMENTITIOUS OR
METALLIC GROUT FILLET
CEMENTITIOUS OR
METALLIC WATERPROOFING
WP-3
2001 NOT DRAWN TO SCALE
1458
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOUNDATION CRACK
WITH V-SHAPED
GROOVE FILLED WITH
CEMENTITIOUS OR
METALLIC GROUT
CEMENTITIOUS OR
METALLIC GROUT
FILLET
CONCRETE TOPPING
SLAB
WATERPROOFING
PRESSURE MAT
SLAB-ON-GRADE
CEMENTITIOUS OR METALLIC
WATERPROOFING
WP-3S
2001 NOT DRAWN TO SCALE
1459
The NRCA Roofing and Waterproofing Manual—Fifth Edition
EXTEND
WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
GRADE ABOVE GRADE
NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.
FOUNDATION
WALL
GRADE
EXTEND
WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
ABOVE GRADE
WATERPROOF
MEMBRANE
NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.
WP-4S
2001 NOT DRAWN TO SCALE
1461
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
EXTEND
WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
ABOVE GRADE
GRADE
COUNTERFLASHING
FILTER FABRIC
GEOCOMPOSITE OR
PROTECTION
WATERPROOF
MEMBRANE
NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.
1462
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
COUNTERFLASHING
APPROPRIATE FOR
MASONRY
CONSTRUCTION EXTEND
TYPE WATERPROOF
MEMBRANE
3'' [75 mm] MIN.
GRADE ABOVE GRADE
WATERPROOF
MEMBRANE
GEOCOMPOSITE OR
PROTECTION COURSE
FILTER FABRIC
NOTES :
1. APPLICABLE TO MULTI-PLY SHEET AND LIQUID-APPLIED WATERPROOF MEMBRANES.
1463
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
COUNTERFLASHING
EARTH FILL
FILTER FABRIC
GEOCOMPOSITE OR
PROTECTION COURSE
WATERPROOF
MEMBRANE
FINISHED DECK
WEAR COURSE
GEOCOMPOSITE OR
PROTECTION COURSE
WP-6
2001 NOT DRAWN TO SCALE
1464
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
COUNTERFLASHING -
EXTEND OVER
GEOCOMPOSITE OR
PROTECTION COURSE
GEOCOMPOSITE OR
PROTECTION COURSE
WATERPROOF
MEMBRANE
CONCRETE FILL
PLACED AT BOTTOM STRUCTURAL
OF PLANTER DECK
NOTES :
1. WEEP TUBE SIZE AND SPACING DETERMINED BY PLANTER SIZE AND LOCATION (BY OTHERS).
WP-6S
2001 NOT DRAWN TO SCALE
1465
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
COUNTERFLASHING
EARTH FILL
FILTER FABRIC
GEOCOMPOSITE OR
PROTECTION COURSE
WATERPROOF
MEMBRANE
PLANTER DRAIN
PLANTER WALL
COMPRESSIBLE EXPANSION
STRIP AND BACKER ROD
OPTIONAL
WATERPROOF
MEMBRANE
GEOCOMPOSITE OR
PROTECTION COURSE
WP-7
2001 NOT DRAWN TO SCALE
1466
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT
COUNTERFLASHING -
EXTEND OVER
GEOCOMPOSITE
PROTECTION COURSE
WATERPROOF
MEMBRANE
STRUCTURAL
DECK
WP-7S
2001 NOT DRAWN TO SCALE
1467
The NRCA Roofing and Waterproofing Manual—Fifth Edition
SEALANT BETWEEN
PIPE AND SLEEVE
FOUNDATION WALL AS REQUIRED
WATERPROOF
MEMBRANE PIPE PENETRATION
FILTER FABRIC
GEOCOMPOSITE OR
PROTECTION COURSE
SEALANT BETWEEN
SLEEVE AND WALL
CLAMPING RING
(OPTIONAL)
BACKFILL
PIPE SLEEVE
EXTENDING MIN.
4'' [100 mm] BEYOND
EXTERIOR OF WALL
FILLET IF REQUIRED
FOR MEMBRANE
TYPE
WP-8
2001 NOT DRAWN TO SCALE
1468
The NRCA Roofing and Waterproofing Manual—Fifth Edition
FOUNDATION WALL
WATERPROOF
MEMBRANE
PIPE PENETRATION
PIPE SLEEVE EXTENDING
MIN. 4'' [100 mm] BEYOND
BEYOND EXTERIOR
FACE OF WALL
FILTER FABRIC
GEOCOMPOSITE OR
PROTECTION COURSE
WP-8S
2001 NOT DRAWN TO SCALE
1469
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CAST-IN-PLACE
CONCRETE WEAR
SURFACE
FILTER FABRIC
RIGID INSULATION
GEOCOMPOSITE
DRAINAGE COURSE
(OPTIONAL)
WATERPROOF
MEMBRANE -
EXTEND UNDER
CLAMPING STRAINER
STRUCTURAL DECK
1470
The NRCA Roofing and Waterproofing Manual—Fifth Edition
CAST-IN-PLACE CONCRETE
WEAR SURFACE
FILTER FABRIC
RIGID INSULATION
GEOCOMPOSITE DRAINAGE
COURSE (OPTIONAL)
WATERPROOF MEMBRANE-
EXTEND UNDER CLAMPING
STRAINER
STRUCTURAL DECK
1471
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PRECAST CONCRETE
PAVERS OR STONE -
MARK PAVER OVER
DRAIN TO IDENTIFY
LOCATION
PAVER PEDESTAL
RIGID INSULATION
FILTER FABRIC
GEOCOMPOSITE
DRAINAGE COURSE
(OPTIONAL)
WATERPROOF
MEMBRANE -
EXTEND MEMBRANE
UNDER DRAIN
CLAMPING RING
1472
The NRCA Roofing and Waterproofing Manual—Fifth Edition
PRECAST CONCRETE
PAVERS OR STONE -
MARK PAVER OVER
DRAIN TO IDENTIFY
DRAIN LOCATION
PAVER PEDESTAL
RIGID INSULATION
FILTER FABRIC
GEOCOMPOSITE
DRAINAGE COURSE
(OPTIONAL)
WATERPROOF
MEMBRANE - EXTEND
UNDER DRAIN
CLAMPING RING
STRUCTURAL DECK
1473