Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Measurement Log / BA100 33/.

600kV,8MVA Furnace Transfomer-5


V3.14.3 Sl.No : MEHI-20425/2
AGSI

IEC 60156:95
Sample Number FTR_5_AFTER FILTRATION

TEST START 4/4/2024 10:26 AM

Test 1 76.3 kV
Test 2 74.4 kV
Test 3 84.3 kV
Test 4 83.6 kV
Test 5 60.3 kV
Test 6 67.4 kV

TEST END 4/4/2024 10:23 AM all values (rms)

Mean 76.7 kV
Std.Dev. 10.5 kV

Stop, Temperature 30 °C
Test Frequency 60 Hz

Test Setup: Stirrer used during Test

100 kV
90 kV
80 kV
72.7 kV
70 kV
60 kV
50 kV
40 kV
30 kV
20 kV
10 kV

1 2 3 4 5 6

printed with BA Report Engine / b2 electronic