Check the adequacy of the continuous composite profiled deck slab with
spans of 3.5 m. The cross section of the profiled sheeting is shown in Fig.
A1. The slab is propped at the centre during construction stage. [ ap = 1.15,
M20 concrete is used]
15 tp= 0.86
40
Plastic neutral axis
Centroidal axis ep= 33
e = 30
138 bo = 162
13
300
Fig. A1 Cross-section of composite slab
Version II 24 - 8
COMPOSITE FLOORS - II
k = 0.0530 N/mm2
The profiled deck sheet is propped at the centre as shown in Fig. A2. Assume
the top flanges of the supporting steel beams are at least 0.15 m wide and the
width of the prop is neglected.
3500 150 70
e 1710 mm
2
Version II 24 - 9
COMPOSITE FLOORS - II
3.2 Factored moments and vertical shears: (See table – 7 and table – 8 of
chapter titled Composite Beams – II)
Moments:
wu , DL wu , LL 2 3.25 2.25
Sagging moment e 1.71
2
12 10 12 10
1.45 kNm / m
wu , DL wu , LL 2 3.25 2.25
Hogging moment e 1.71
2
10 9 10 9
A Prop B C
40 1710 1710 40
Fig.A2 Profiled sheeting during construction
Vertical shear:
Version II 24 - 10
COMPOSITE FLOORS - II
Design moment = Mpa / ap = 4.92/1.15 = 4.27 kN-m/m > 1.68 kN-m/m
Design shear = Vpa / ap = 49.2/1.15 = 42.8 kN/m > 5.64 kN/m
Version II 24 - 11
COMPOSITE FLOORS - II
The design ultimate loading = (wu, DL + wu, LL) = 3.25 + 6.75 = 10.0 kN/m2
Ap f yp 0.28
Ncf 1185 289 kN / m
ap 1.15
So, from equation (2) of a previous chapter, the depth of the stress block is
Ncf 289
x 40.1 mm
b( f ck )cu 1 7.2
Version II 24 - 12
COMPOSITE FLOORS - II
The area Ap is
174
0.009
162 120
and
The basic shear strength is Rd = 0.30 N/mm2, so from equation (20) of
previous chapter
162
Vv .Rd 120 0.3 1.48 ( 1.2 0.36 ) 45 kN / m
300
Vv.Rd > Vsd, hence composite slab is OK in shear.
Version II 24 - 13
COMPOSITE FLOORS - II
The design vertical shear is 28.3 kN/m, so composite slab is safe against
longitudinal shear. Note partial safety factor for shear studs is taken as 1.25.
4.6.2 Deflection