Professional Documents
Culture Documents
Parameter List: Protection and Power Management, PPM-3
Parameter List: Protection and Power Management, PPM-3
• Alarm list
• Parameter list
2. Alarm list
2.1 Reverse power protection..................................................................................................................................................................................................... 9
2.1.1 Reverse power protection...............................................................................................................................................................................................9
2.2 Over-current protection....................................................................................................................................................................................................... 10
2.2.1 Over-current protection................................................................................................................................................................................................. 10
2.3 Generator voltage protection............................................................................................................................................................................................14
2.3.1 Generator voltage protection...................................................................................................................................................................................... 14
2.4 Generator frequency protection...................................................................................................................................................................................... 16
2.4.1 Generator frequency protection.................................................................................................................................................................................16
2.5 Busbar voltage protection.................................................................................................................................................................................................. 18
2.5.1 Busbar voltage protection............................................................................................................................................................................................ 18
2.6 Busbar frequency protection............................................................................................................................................................................................ 20
2.6.1 Busbar frequency protection....................................................................................................................................................................................... 20
2.7 Overload protection............................................................................................................................................................................................................... 23
2.7.1 Overload protection........................................................................................................................................................................................................ 23
2.8 Current unbalance protection.......................................................................................................................................................................................... 25
2.8.1 Current unbalance protection..................................................................................................................................................................................... 25
2.9 Voltage asymmetry protection......................................................................................................................................................................................... 26
2.9.1 Voltage asymmetry protection.................................................................................................................................................................................... 26
2.10 Reactive power import (loss of excitation)............................................................................................................................................................. 26
2.10.1 Reactive power import (loss of excitation)..........................................................................................................................................................26
2.11 Reactive power export (over-excitation).................................................................................................................................................................. 27
2.11.1 Reactive power export (over-excitation).............................................................................................................................................................. 27
2.12 Busbar unbalance voltage protection....................................................................................................................................................................... 27
2.12.1 Busbar unbalance voltage protection................................................................................................................................................................... 27
2.13 Non Essential Load trip..................................................................................................................................................................................................... 27
2.13.1 Non Essential Load trip.............................................................................................................................................................................................. 27
2.14 Max. parallel time protection.......................................................................................................................................................................................... 30
2.14.1 Max. parallel time protection.................................................................................................................................................................................... 30
2.15 Breaker external trip alarm.............................................................................................................................................................................................. 30
2.15.1 Breaker external trip alarm........................................................................................................................................................................................30
2.16 Synchronisation and breaker alarms.........................................................................................................................................................................31
2.16.1 Synchronisation and breaker alarms.................................................................................................................................................................... 31
2.17 Regulation alarms................................................................................................................................................................................................................ 33
2.17.1 Regulation alarms......................................................................................................................................................................................................... 33
3. Parameter list
3.1 Synchronisation....................................................................................................................................................................................................................... 80
3.1.1 Synchronisation................................................................................................................................................................................................................ 80
3.2 Regulation................................................................................................................................................................................................................................... 81
3.2.1 Regulation...........................................................................................................................................................................................................................81
3.3 Digital output setup................................................................................................................................................................................................................86
3.3.1 Digital output setup......................................................................................................................................................................................................... 86
3.4 Pulse width modulation....................................................................................................................................................................................................... 89
3.4.1 Pulse width modulation................................................................................................................................................................................................. 89
3.5 Load reduction..........................................................................................................................................................................................................................90
3.5.1 Load reduction.................................................................................................................................................................................................................. 90
3.6 Analogue output limits......................................................................................................................................................................................................... 90
3.6.1 Analogue output limits................................................................................................................................................................................................... 90
3.7 Transducer outputs................................................................................................................................................................................................................ 91
3.7.1 Transducer outputs......................................................................................................................................................................................................... 91
3.8 Regulator output selection.................................................................................................................................................................................................95
3.8.1 Regulator output selection........................................................................................................................................................................................... 95
3.9 System...........................................................................................................................................................................................................................................96
Throughout this document, a number of warnings and notes with helpful user information will be presented. To ensure that these are
noticed, they will be highlighted as follows in order to separate them from the general text.
Warnings
DANGER!
Warnings indicate a potentially dangerous situation, which could result in death, personal injury or damaged equipment, if
certain guidelines are not followed.
Notes
INFO
Notes provide general information, which will be helpful for the reader to bear in mind.
DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the
engine/generator controlled by the Multi-line 2 unit, the company responsible for the installation or the operation of the set must be
contacted.
DANGER!
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF does not
take responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document.
If there is a discrepancy, the English version prevails.
Installing and operating the Multi-line 2 unit may imply work with dangerous currents and voltages. Therefore, the installation should
only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment.
DANGER!
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury
or death.
Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and
connected, these precautions are no longer necessary.
The Multi-line 2 unit is delivered from factory with certain factory settings. These are based on average values and are not
necessarily the correct settings for matching the engine/generator set in question. Precautions must be taken to check the settings
before running the engine/generator set.
This document is a complete parameter list including all parameters, which means that some of the option parameters included may
not be accessible in the system in question.
The document includes a complete standard alarm list and a complete standard parameter list for setup. Therefore, this document is
to be used for reference, when information about specific alarms and parameters is needed.
DANGER!
Please make sure to read this document before starting to work with the Multi-line 2 unit and the genset to be controlled.
Failure to do this could result in human injury or damage to the equipment.
This Parameter List is mainly intended for the person responsible for the unit parameter setup. In most cases, this would be a panel
builder designer. Naturally, other users might also find useful information here.
This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the
top of a new page.
INFO
In the following, these abbreviations are used:
G: Generator
This chapter includes a complete alarm list, including all possible options. Therefore, this chapter is to be used for reference when
specific information about the individual parameters is needed for the unit setup.
The alarm set point is adjusted in the set point menu. The setting is a percentage
Set point:
of the nominal values.
The timer setting is the time that must expire from the alarm level is reached until
Delay:
the alarm occurs.
Fail class: When the alarm occurs, the unit will react depending on the selected fail class.
INFO
Small differences due to the character of the parameters may exist between the individual tables.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
G/SG/SC – -110.0 %
1001 Set point - 8.0 %
P> 1 0.0 %
G/SG/SC - 0.1 s
1002 Delay 5.0 s
P> 1 300.0 s
Not used
G/SG/SC - Relay
1003 Option- Not used The alarm and fail class are activated
P> 1 output A Designer’s
dependent when the reverse power has been
Reference
Not used continuously above the programmed
G/SG/SC - Relay Handbook
1004 Option- Not used value during the programmed delay.
P> 1 output B
dependent
G/SG/SC - OFF
1005 Enable ON
P> 1 ON
G/SG/SC - Trip GB
1006 Fail class F1…F7
P> 1 (F3)
G/SG/SC - -110.0 %
1011 Set point - 15.0 %
P> 2 0.0 %
G/SG/SC - 0.1 s
1012 Delay 2.0 s
P> 2 300.0 s
Not used
G/SG/SC - Relay
1013 Option- Not used The alarm and fail class are activated
P> 2 output A Designer’s
dependent when the reverse power has been
Reference
Not used continuously above the programmed
G/SG/SC - Relay Handbook
1014 Option- Not used value during the programmed delay.
P> 2 output B
dependent
G/SG/SC - OFF
1015 Enable ON
P> 2 ON
G/SG/SC - Trip GB
1016 Fail class F1…F7
P> 2 (F3)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
G/SG/SC/B
50 %
1031 A Set point 100 %
200 %
I> 1
G/SG/SC/B
0.1 s
1032 A Delay 20.0 s
999.9 s
I> 1
G/SG/SC/B
OFF
1035 A Enable ON
ON
I> 1
G/SG/SC/B
Warning
1036 A Fail class F1…F7
(F2)
I> 1
G/SG/SC/B
50 %
1041 A Set point 110 %
200 %
I> 2
G/SG/SC/B
0.1 s
1042 A Delay 60.0 s
999.9 s
I> 2
G/SG/SC/B
OFF
1045 A Enable ON
ON
I> 2
G/SG/SC/B
Trip GB
1046 A Fail class F1…F7
(F3)
I> 2
G/SG/SC/B
50 %
1051 A Set point 130 %
200 %
I> 3
G/SG/SC/B
0.1 s
1052 A Delay 30.0 s
999.9 s
I> 3
G/SG/SC/B
OFF
1055 A Enable ON
ON
I> 3
G/SG/SC/B
Trip GB
1056 A Fail class F1…F7
(F3)
I> 3
G/SG/SC/B
50 %
1061 A Set point 150 %
200 %
I> 4
G/SG/SC/B
0.1 s
1062 A Delay 10.0 s
999.9 s
I> 4
G/SG/SC/B
OFF
1065 A Enable ON
ON
I> 4
G/SG/SC/B
Trip GB
1066 A Fail class F1…F7
(F3)
I> 4
P>ship-to- 0.1 s
1071 Delay 5.0 s
ship 120.0 s
Not used
P>ship-to- Option- Designer’s
1072 Relay A Option-
ship dependent Reference
dependent
Handbook
Not used
P>ship-to- Option-
1073 Relay B Option-
ship dependent
dependent
@50 %
Voltage dep. Set point 50 %
1101 110 % nom
I> I1 200 %
voltage
@60 %
Voltage dep. Set point 50 %
1102 125 % nom
I> I2 200 %
voltage
@90 %
Voltage dep. Set point 50 %
1105 170 % nom
I> I5 200 %
voltage
@100 %
Voltage dep. Set point 50 %
1106 200 % nom
I> I6 200 %
voltage
Not used
Voltage dep.
1112 Relay A Option- Not used
I> The alarm and fail class are
dependent
activated when the overcurrent has
Designer’s
Not used been continuously above the
Voltage dep. Reference
1113 Relay B Option- Not used programmed value during the
I> Handbook
dependent programmed delay. Values are set
in parameters 1101-1106.
Voltage dep. OFF
1114 Activate OFF
I> ON
G/SG/SC/B
80 %
1131 A Set point 200 %
350 %
I>> 1
G/SG/SC/B
0.0 s
1132 A Delay 0.0 s
3.0 s
I>> 1
G/SG/SC/B
OFF
1135 A Enable OFF
ON
I>> 1
G/SG/SC/B
Trip GB
1136 A Fail class F1…F7
(F3)
I>> 1
G/SG/SC/B
80 %
1141 A Set point 300 %
350 %
I>> 2
G/SG/SC/B
0.0 s
1142 A Delay 0.0 s
3.0 s
I>> 2
G/SG/SC/B
OFF
1145 A Enable OFF
ON
I>> 2
G/SG/SC/B
Trip GB
1146 A Fail class F1…F7
(F3)
I>> 2
Min. Factory
No. Setting Notes Ref. Description
Max. setting
G/SG/SC 80 %
1151 Set point 105 %
U> 1 120 %
G/SG/SC 0.1 s
1152 Timer 5.0 s
U> 1 100.0 s
Not used
G/SG/SC
1153 Relay A Option- Not used The alarm and fail class are activated when
U> 1 Designer’s
dependent the voltage has been continuously above
Reference
Not used the programmed value during the
G/SG/SC Handbook
1154 Relay B Option- Not used programmed delay.
U> 1
dependent
G/SG/SC OFF
1155 Enable ON
U> 1 ON
G/SG/SC Warning
1156 Fail class F1…F7
U> 1 (F2)
G/SG/SC 80 %
1161 Set point 115 %
U> 2 120 %
G/SG/SC 0.1 s
1162 Timer 1.0 s
U> 2 100.0 s
Not used
G/SG/SC
1163 Relay A Option- Not used The alarm and fail class are activated when
U> 2 Designer’s
dependent the voltage has been continuously above
Reference
Not used the programmed value during the
G/SG/SC Handbook
1164 Relay B Option- Not used programmed delay.
U> 2
dependent
G/SG/SC OFF
1165 Enable ON
U> 2 ON
G/SG/SC Block
1166 Fail class F1…F7
U> 2 (F1)
G/SG/SC 50 %
1171 Set point 95 %
U< 1 100 %
G/SG/SC 0.1 s
1172 Timer 5.0 s
U< 1 100.0 s
Not used
G/SG/SC
1173 Relay A Option- Not used The alarm and fail class are activated when
U< 1 Designer’s
dependent the voltage has been continuously under
Reference
Not used the programmed value during the
G/SG/SC Handbook
1174 Relay B Option- Not used programmed delay.
U< 1
dependent
G/SG/SC OFF
1175 Enable ON
U< 1 ON
G/SG/SC Warning
1176 Fail class F1…F7
U< 1 (F2)
G/SG/SC 50 %
1181 Set point 80 %
U< 2 100 %
G/SG/SC 0.1 s
1182 Timer 3.0 s
U< 2 100.0 s
Not used
G/SG/SC
1183 Relay A Option- Not used The alarm and fail class are activated when
U< 2 Designer’s
dependent the voltage has been continuously under
Reference
Not used the programmed value during the
G/SG/SC Handbook
1184 Relay B Option- Not used programmed delay.
U< 2
dependent
G/SG/SC OFF
1185 Enable ON
U< 2 ON
G/SG/SC Block
1186 Fail class F1…F7
U< 2 (F1)
G/SG/SC 50 %
1191 Set point 70 %
U< 3 100 %
G/SG/SC 0.1 s
1192 Timer 1.0 s
U< 3 100.0 s
Not used
G/SG/SC
1193 Relay A Option- Not used The alarm and fail class are activated when
U< 3 Designer’s
dependent the voltage has been continuously under
Reference
Not used the programmed value during the
G/SG/SC Handbook
1194 Relay B Option- Not used programmed delay.
U< 3
dependent
G/SG/SC OFF
1195 Enable OFF
U< 3 ON
G/SG/SC Block
1196 Fail class F1…F7
U< 3 (F1)
INFO
Frequency settings relate to the nominal frequency setting.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
G/SG/SC 80 %
1211 Set point 105 %
f> 1 120 %
G/SG/SC 0.2 s
1212 Timer 5.0 s
f> 1 100.0 s
G/SG/SC Not used The alarm and fail class are activated when the
1213 Relay A Not used Designer’s
f> 1 Option- dep. frequency has been continuously above the
Reference
G/SG/SC Not used programmed value during the programmed
1214 Relay B Not used Handbook
f> 1 Option- dep. delay.
G/SG/SC OFF
1215 Enable ON
f> 1 ON
G/SG/SC Warning
1216 Fail class F1…F7
f> 1 (F2)
G/SG/SC 80 %
1221 Set point 107 %
f> 2 120 %
G/SG/SC 0.2 s
1222 Timer 3.0 s
f> 2 100.0 s
G/SG/SC Not used The alarm and fail class are activated when the
1223 Relay A Not used Designer’s
f> 2 Option- dep. frequency has been continuously above the
Reference
G/SG/SC Not used programmed value during the programmed
1224 Relay B Not used Handbook
f> 2 Option- dep. delay.
G/SG/SC OFF
1225 Enable ON
f> 2 ON
G/SG/SC Block
1226 Fail class F1…F7
f> 2 (F1)
G/SG/SC 80 %
1231 Set point 110 %
f> 3 120 %
G/SG/SC 0.2 s
1232 Timer 1.0 s
f> 3 100.0 s
G/SG/SC Not used The alarm and fail class are activated when the
1233 Relay A Not used Designer’s
f> 3 Option- dep. frequency has been continuously above the
Reference
G/SG/SC Not used programmed value during the programmed
1234 Relay B Not used Handbook
f> 3 Option- dep. delay.
G/SG/SC OFF
1235 Enable OFF
f> 3 ON
G/SG/SC Block
1236 Fail class F1…F7
f> 3 (F1)
G/SG/SC 80 %
1241 Set point 95 %
f< 1 100 %
G/SG/SC 0.2 s
1242 Timer 5.0 s
f< 1 100.0 s
G/SG/SC Not used The alarm and fail class are activated when the
1243 Relay A Not used Designer’s
f< 1 Option- dep. frequency has been continuously under the
Reference
G/SG/SC Not used programmed value during the programmed
1244 Relay B Not used Handbook
f< 1 Option- dep. delay.
G/SG/SC OFF
1245 Enable ON
f< 1 ON
G/SG/SC Warning
1246 Fail class F1…F7
f< 1 (F2)
G/SG/SC 80 %
1251 Set point 93 %
f< 2 100 %
G/SG/SC 0.2 s
1252 Timer 3.0 s
f< 2 100.0 s
G/SG/SC Not used The alarm and fail class are activated when the
1253 Relay A Not used Designer’s
f< 2 Option- dep. frequency has been continuously under the
Reference
G/SG/SC Not used programmed value during the programmed
1254 Relay B Not used Handbook
f< 2 Option- dep. delay.
G/SG/SC OFF
1255 Enable ON
f< 2 ON
G/SG/SC Block
1256 Fail class F1…F7
f< 2 (F1)
G/SG/SC 80 %
1261 Set point 90 %
f< 3 100 %
G/SG/SC 0.2 s
1262 Timer 1.0 s
f< 3 100.0 s
G/SG/SC Not used The alarm and fail class are activated when the
1263 Relay A Not used Designer’s
f< 3 Option- dep. frequency has been continuously under the
Reference
G/SG/SC Not used programmed value during the programmed
1264 Relay B Not used Handbook
f< 3 Option- dep. delay.
G/SG/SC OFF
1265 Enable OFF
f< 3 ON
G/SG/SC Block
1266 Fail class F1…F7
f< 3 (F1)
INFO
Voltage settings relate to the nominal voltage setting.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
90 %
1271 BB U> 1 Set point 110 %
150 %
0.00 s
1272 BB U> 1 Timer 5.00 s
99.99 s
Not used The alarm and fail class are activated when the
1273 BB U> 1 Relay A Not used Designer’s
Option- dep. voltage has been continuously above the
Reference
Not used programmed value during the programmed
1274 BB U> 1 Relay B Not used Handbook
Option- dep. delay.
OFF
1275 BB U> 1 Enable ON
ON
Warning
1276 BB U> 1 Fail class F1…F7
(F2)
90 %
1281 BB U> 2 Set point 120 %
150 %
0.00 s
1282 BB U> 2 Timer 3.00 s
99.99 s
Not used The alarm and fail class are activated when the
1283 BB U> 2 Relay A Not used Designer’s
Option- dep. voltage has been continuously above the
Reference
Not used programmed value during the programmed
1284 BB U> 2 Relay B Not used Handbook
Option- dep. delay.
OFF
1285 BB U> 2 Enable ON
ON
Trip GB
1286 BB U> 2 Fail class F1…F7
(F3)
90 %
1291 BB U> 3 Set point 130 %
150 %
0.00 s
1292 BB U> 3 Timer 1.00 s
99.99 s
Not used The alarm and fail class are activated when the
1293 BB U> 3 Relay A Not used Designer’s
Option- dep. voltage has been continuously above the
Reference
Not used programmed value during the programmed
1294 BB U> 3 Relay B Not used Handbook
Option- dep. delay.
OFF
1295 BB U> 3 Enable OFF
ON
Trip GB
1296 BB U> 3 Fail class F1…F7
(F3)
50 %
1301 BB U< 1 Set point 95 %
100 %
0.00 s
1302 BB U< 1 Timer 5.00 s
99.99 s
Not used The alarm and fail class are activated when the
1303 BB U< 1 Relay A Not used Designer’s
Option- dep. voltage has been continuously under the
Reference
Not used programmed value during the programmed
1304 BB U< 1 Relay B Not used Handbook
Option- dep. delay.
OFF
1305 BB U< 1 Enable ON
ON
Warning
1306 BB U< 1 Fail class F1…F7
(F2)
50 %
1311 BB U< 2 Set point 80 %
100 %
0.00 s
1312 BB U< 2 Timer 3.00 s
99.99 s
Not used The alarm and fail class are activated when the
1313 BB U< 2 Relay A Not used Designer’s
Option- dep. voltage has been continuously under the
Reference
Not used programmed value during the programmed
1314 BB U< 2 Relay B Not used Handbook
Option- dep. delay.
OFF
1315 BB U< 2 Enable ON
ON
Trip GB
1316 BB U< 2 Fail class F1…F7
(F3)
50 %
1321 BB U< 3 Set point 70 %
100 %
0.00 s
1322 BB U< 3 Timer 2.00 s
99.99 s
Not used The alarm and fail class are activated when the
1323 BB U< 3 Relay A Not used Designer’s
Option- dep. voltage has been continuously under the
Reference
Not used programmed value during the programmed
1324 BB U< 3 Relay B Not used Handbook
Option- dep. delay.
OFF
1325 BB U< 3 Enable OFF
ON
Trip GB
1326 BB U< 3 Fail class F1…F7
(F3)
50 %
1331 BB U< 4 Set point 60 %
100 %
0.00 s
1332 BB U< 4 Timer 1.00 s
99.99 s
Not used The alarm and fail class are activated when the
1333 BB U< 4 Relay A Not used Designer’s
Option- dep. voltage has been continuously under the
Reference
Not used programmed value during the programmed
1334 BB U< 4 Relay B Not used Handbook
Option- dep. delay.
OFF
1335 BB U< 4 Enable OFF
ON
Trip GB
1336 BB U< 4 Fail class F1…F7
(F3)
INFO
Frequency settings relate to the nominal frequency setting.
100 %
1351 BB f> 1 Set point 105 %
130 %
0.00 s
1352 BB f> 1 Timer 5.00 s
99.99 s
Not used
1353 BB f> 1 Relay A Not used Designer’s The alarm and fail class are activated when the
Option-dep.
Reference frequency has been continuously above the
Not used Handbook programmed value during the programmed delay.
1354 BB f> 1 Relay B Not used
Option-dep.
OFF
1355 BB f> 1 Enable ON
ON
Warning
1356 BB f> 1 Fail class F1…F7
(F2)
100 %
1361 BB f> 2 Set point 110 %
130 %
0.00 s
1362 BB f> 2 Timer 8.00 s
99.99 s
Not used
1363 BB f> 2 Relay A Not used Designer’s The alarm and fail class are activated when the
Option-dep.
Reference frequency has been continuously above the
Not used Handbook programmed value during the programmed delay.
1364 BB f> 2 Relay B Not used
Option-dep.
OFF
1365 BB f> 2 Enable ON
ON
Trip GB
1366 BB f> 2 Fail class F1…F7
(F3)
100 %
1371 BB f> 3 Set point 120 %
130 %
0.00 s
1372 BB f> 3 Timer 6.00 s
99.99 s
Not used
1373 BB f> 3 Relay A Not used Designer’s The alarm and fail class are activated when the
Option-dep.
Reference frequency has been continuously above the
Not used Handbook programmed value during the programmed delay.
1374 BB f> 3 Relay B Not used
Option-dep.
OFF
1375 BB f> 3 Enable OFF
ON
Trip GB
1376 BB f> 3 Fail class F1…F7
(F3)
80 %
1381 BB f< 1 Set point 96 %
100 %
0.00 s
1382 BB f< 1 Timer 5.00 s
99.99 s
Not used
1383 BB f< 1 Relay A Not used Designer’s The alarm and fail class are activated when the
Option-dep.
Reference frequency has been continuously under the
Not used Handbook programmed value during the programmed delay.
1384 BB f< 1 Relay B Not used
Option-dep.
OFF
1385 BB f< 1 Enable ON
ON
Warning
1386 BB f< 1 Fail class F1…F7
(F2)
80 %
1391 BB f< 2 Set point 93 %
100 %
0.00 s
1392 BB f< 2 Timer 10.00 s
99.99 s
Not used
1393 BB f< 2 Relay A Not used Designer’s The alarm and fail class are activated when the
Option-dep.
Reference frequency has been continuously under the
Not used Handbook programmed value during the programmed delay.
1394 BB f< 2 Relay B Not used
Option-dep.
OFF
1395 BB f< 2 Enable ON
ON
Trip GB
1396 BB f< 2 Fail class F1…F7
(F3)
80 %
1401 BB f< 3 Set point 92 %
100 %
0.00 s
1402 BB f< 3 Timer 8.00 s
99.99 s
Not used
1403 BB f< 3 Relay A Not used Designer’s The alarm and fail class are activated when the
Option-dep.
Reference frequency has been continuously under the
Not used Handbook programmed value during the programmed delay.
1404 BB f< 3 Relay B Not used
Option-dep.
OFF
1405 BB f< 3 Enable OFF
ON
Trip GB
1406 BB f< 3 Fail class F1…F7
(F3)
80 %
1411 BB f< 4 Set point 90 %
100 %
0.00 s
1412 BB f< 4 Timer 6.00 s
99.99 s
Not used
1413 BB f< 4 Relay A Not used Designer’s The alarm and fail class are activated when the
Option-dep.
Reference frequency has been continuously under the
Not used Handbook programmed value during the programmed delay.
1414 BB f< 4 Relay B Not used
Option-dep.
OFF
1415 BB f< 4 Enable OFF
ON
Trip GB
1416 BB f< 4 Fail class F1…F7
(F3)
INFO
Settings relate to nominal power.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
G/SG/SC/ -200 %
1451 Set point 95 %
BA P> 1 200 %
G/SG/SC/ 0.1 s
1452 Timer 30.0 s
BA P> 1 100.0 s
The alarm and fail class are activated when the
G/SG/SC/ R0 R0 power has been continuously above the
1453 Relay A Designer’s
BA P> 1 Option-dep. (none) programmed value during the programmed delay.
Reference
G/SG/SC/ R0 R0 If negative values are chosen the high alarm must
1454 Relay B Handbook
BA P> 1 Option-dep. (none) be deactivated. The deactivating is only available
from the USW.
G/SG/SC/ OFF
1455 Enable ON
BA P> 1 ON
G/SG/SC/ Warning
1456 Fail class F1…F7
BA P> 1 (F2)
G/SG/SC/ -200 %
1461 Set point 110 %
BA P> 2 200 %
G/SG/SC/ 0.1 s
1462 Timer 30.0 s
BA P> 2 100.0 s
The alarm and fail class are activated when the
G/SG/SC/ R0 R0 power has been continuously above the
1463 Relay A Designer’s
BA P> 2 Option-dep. (none) programmed value during the programmed delay.
Reference
G/SG/SC/ R0 R0 If negative values are chosen the high alarm must
1464 Relay B Handbook
BA P> 2 Option-dep. (none) be deactivated. The deactivating is only available
from the USW.
G/SG/SC/ OFF
1465 Enable ON
BA P> 2 ON
G/SG/SC/ Trip GB
1466 Fail class F1…F7
BA P> 2 (F3)
G/SG/SC/ -200 %
1471 Set point 120 %
BA P> 3 200 %
G/SG/SC/ 0.1 s
1472 Timer 10.0 s
BA P> 3 100.0 s
The alarm and fail class are activated when the
G/SG/SC/ R0 R0 power has been continuously above the
1473 Relay A Designer’s
BA P> 3 Option-dep. (none) programmed value during the programmed delay.
Reference
G/SG/SC/ R0 R0 If negative values are chosen the high alarm must
1474 Relay B Handbook
BA P> 3 Option-dep. (none) be deactivated. The deactivating is only available
from the USW.
G/SG/SC/ OFF
1475 Enable OFF
BA P> 3 ON
G/SG/SC/ Trip GB
1476 Fail class F1…F7
BA P> 3 (F3)
G/SG/SC/ -200 %
1481 Set point 130 %
BA P> 4 200 %
G/SG/SC/ 0.1 s
1482 Timer 5.0 s
BA P> 4 100.0 s
The alarm and fail class are activated when the
G/SG/SC/ R0 R0 power has been continuously above the
1483 Relay A Designer’s
BA P> 4 Option-dep. (none) programmed value during the programmed delay.
Reference
G/SG/SC/ R0 R0 If negative values are chosen the high alarm must
1484 Relay B Handbook
BA P> 4 Option-dep. (none) be deactivated. The deactivating is only available
from the USW.
G/SG/SC/ OFF
1485 Enable OFF
BA P> 4 ON
G/SG/SC/ Trip GB
1486 Fail class F1…F7
BA P> 4 (F3)
G/SG/SC/ -200 %
1491 Set point 150 %
BA P> 5 200 %
G/SG/SC/ 0.1 s
1492 Timer 1.0 s
BA P> 5 100.0 s
The alarm and fail class are activated when the
G/SG/SC/ R0 R0 power has been continuously above the
1493 Relay A Designer’s
BA P> 5 Option-dep. (none) programmed value during the programmed delay.
Reference
G/SG/SC/ R0 R0 If negative values are chosen the high alarm must
1494 Relay B Handbook
BA P> 5 Option-dep. (none) be deactivated. The deactivating is only available
from the USW.
G/SG/SC/ OFF
1495 Enable OFF
BA P> 5 ON
G/SG/SC/ Trip GB
1496 Fail class F1…F7
BA P> 5 (F3)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
1500 G Unbalance I
G Unbalance 0.00 %
1501 Set point 30 %
I 100.00 %
G Unbalance 0.1 s
1502 Timer 10.0 s
I 100.0 s
G Unbalance OFF
1505 Enable ON
I ON
G Unbalance Warning
1506 Fail class F1…F7
I (F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
1510 G Unbalance U
G Unbalance 0.00 %
1511 Set point 10 %
U 50.00 %
G Unbalance 0.1 s
1512 Timer 10.0 s
U 100.0 s
G Unbalance Warning
1516 Fail class F1…F7
U (F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
0.00 %
1521 G/SG–Q> Set point 50 %
150.00 %
0.1 s
1522 G/SG–Q> Timer 10.0 s
100.0 s
OFF
1525 G/SG–Q> Enable OFF
ON
Warning
1526 G/SG–Q> Fail class F1…F7
(F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
0.00 %
1531 G/SG Q> Set point 75 %
100.00 %
0.1 s
1532 G/SG Q> Timer 10.0 s
100.0 s
OFF
1535 G/SG Q> Enable OFF
ON
Warning
1536 G/SG Q> Fail class F1…F7
(F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
1620 BB Unbalance U
BB Unbalance 0.00 %
1621 Set point 10 %
U 50.00 %
BB Unbalance 0.1 s
1622 Timer 10.0 s
U 100.0 s
BB Unbalance OFF
1625 Enable ON
U ON
BB Unbalance Warning
1626 Fail class F1…F7
U (F2)
INFO
Setting values relate to the nominal setting.
50 %
1801 NEL 1 I> Set point 100 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to overcurrent.
1802 NEL 1 I> Timer 5.0 s Reference
100.0 s This function activates NEL group 1.
Handbook
OFF
1803 NEL 1 I> Enable OFF
ON
50 %
1811 NEL 2 I> Set point 100 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to overcurrent.
1812 NEL 2 I> Timer 8.0 s Reference
100.0 s This function activates NEL group 2.
Handbook
OFF
1813 NEL 2 I> Enable OFF
ON
50 %
1821 NEL 3 I> Set point 100 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to overcurrent.
1822 NEL 3 I> Timer 10.0 s Reference
100.0 s This function activates NEL group 3.
Handbook
OFF
1823 NEL 3 I> Enable OFF
ON
70 %
1831 NEL 1 Bus f< Set point 95 %
100 %
Designer’s Trip of Non Essential Load due to low
0.1 s
1832 NEL 1 Bus f< Timer 5.0 s Reference frequency. This function activates NEL group
100.0 s
Handbook 1.
OFF
1833 NEL 1 Bus f< Enable OFF
ON
70 %
1841 NEL 2 Bus f< Set point 95 %
100 %
Designer’s Trip of Non Essential Load due to low
0.1 s
1842 NEL 2 Bus f< Timer 8.0 s Reference frequency. This function activates NEL group
100.0 s
Handbook 2.
OFF
1843 NEL 2 Bus f< Enable OFF
ON
70 %
1851 NEL 3 Bus f< Set point 95 %
100 %
Designer’s Trip of Non Essential Load due to low
0.1 s
1852 NEL 3 Bus f< Timer 10.0 s Reference frequency. This function activates NEL group
100.0 s
Handbook 3.
OFF
1853 NEL 3 Bus f< Enable OFF
ON
10 %
1861 NEL 1 P> Set point 100 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to overload.
1862 NEL 1 P> Timer 5.0 s Reference
999.0 s This function activates NEL group 1.
Handbook
OFF
1863 NEL 1 P> Enable OFF
ON
10 %
1871 NEL 2 P> Set point 100 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to overload.
1872 NEL 2 P> Timer 8.0 s Reference
999.0 s This function activates NEL group 2.
Handbook
OFF
1873 NEL 2 P> Enable OFF
ON
10 %
1881 NEL 3 P> Set point 100 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to overload.
1882 NEL 3 P> Timer 10.0 s Reference
999.0 s This function activates NEL group 3.
Handbook
OFF
1883 NEL 3 P> Enable OFF
ON
10 %
1891 NEL 1 P>> Set point 110 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to high
1892 NEL 1 P>> Timer 1.0 s Reference
999.0 s overload. This function activates NEL group 1.
Handbook
OFF
1893 NEL 1 P>> Enable OFF
ON
10 %
1901 NEL 2 P>> Set point 110 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to high
1902 NEL 2 P>> Timer 1.0 s Reference
999.0 s overload. This function activates NEL group 2.
Handbook
OFF
1903 NEL 2 P>> Enable OFF
ON
10 %
1911 NEL 3 P>> Set point 110 %
200 %
Designer’s
0.1 s Trip of Non Essential Load due to high
1912 NEL 3 P>> Timer 1.0 s Reference
999.0 s overload. This function activates NEL group 3.
Handbook
OFF
1913 NEL 3 P>> Enable OFF
ON
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Min. Factory
No. Setting Notes Ref. Description
Max. setting
GB/BTB 3.0 s
2131 Delay 120.0 s
sync failure 300.0 s
GB/BTB Warning
2135 Fail class F1…F7
sync failure (F2)
SGB/SCB/T
3.0 s
2141 B sync Delay 120.0 s
300.0 s
failure
SGB/SCB/T
Relay Not used
2142 B sync Not used
output A Option-dep.
failure SGB: Shaft generator breaker
SCB: Shore connection breaker
SGB/SCB/T Designer’s
Relay Not used TB: Tie breaker (emergency generator)
2143 B sync Not used Reference
output B Option-dep. The controller has unsuccessfully tried to
failure Handbook
synchronise the generator to the busbar
SGB/SCB/T within the time delay.
OFF
2144 B sync Enable OFF
ON
failure
SGB/SCB/T
Warning
2145 B sync Fail class F1…F7
(F2)
failure
GB/BTB 1.0 s
2161 Delay 2.0 s
open fail 5.0 s
GB/BTB Warning
2165 Fail class F1…F7
open fail (F2)
GB/BTB 1.0 s
2171 Delay 2.0 s
close fail 5.0 s
GB/BTB Warning
2175 Fail class F1…F7
close fail (F2)
SGB/SCB/T 1.0 s
2201 Delay 2.0 s
B open fail 5.0 s
SGB/SCB/T Warning
2205 Fail class F1…F7
B open fail (F2)
SGB/SCB/T 1.0 s
2211 Delay 2.0 s
B close fail 5.0 s
SGB/SCB/T Warning
2215 Fail class F1…F7
B close fail (F2)
SGB/SCB/T 1.0 s
2221 Delay 1.0 s
B pos fail 5.0 s
SGB/SCB/T Warning
2225 Fail class F1…F7
B pos fail (F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Gov. reg 1%
2561 Deadband 30 %
fail 100 %
Deload 0.0 s
2631 Delay 10.0 s
error 60.0 s
Not used
Deload Relay output
2632 Option- Not used
error A
dependent
Designer’s
Not used The alarm is activated, if the generator
Deload Relay output Reference
2633 Option- Not used fails to de-load within the time delay.
error B Handbook
dependent
Deload OFF
2634 Enable ON
error ON
Deload Warning
2635 Fail class F1…F7
error (F2)
AVR reg. 1%
2681 Deadband 30 %
failure 100 %
Min. Factory
No. Setting Notes Ref. Description
Max. setting
0.0 s
3011 Dig. input 24 Delay 1.0 s
100.0 s
Warning
3015 Dig. input 24 Fail class F1…F7
(F2)
N/O
3016 Dig. input 24 N/X N/O
N/C
0.0 s
3021 Dig. input 25 Delay 1.0 s
100.0 s
Warning
3025 Dig. input 25 Fail class F1…F7
(F2)
N/O
3026 Dig. input 25 N/X N/O
N/C
0.0 s
3131 Dig. input 43 Delay 1.0 s
100.0 s
Warning
3135 Dig. input 43 Fail class F1…F7
(F2)
N/O
3136 Dig. input 43 N/X N/O
N/C
0.0 s
3141 Dig. input 44 Delay 1.0 s
100.0 s
Warning
3145 Dig. input 44 Fail class F1…F7
(F2)
N/O
3146 Dig. input 44 N/X N/O
N/C
0.0 s
3151 Dig. input 45 Delay 1.0 s
100.0 s
Warning
3155 Dig. input 45 Fail class F1…F7
(F2)
N/O
3156 Dig. input 45 N/X N/O
N/C
0.0 s
3161 Dig. input 46 Delay 1.0 s
100.0 s
Warning
3165 Dig. input 46 Fail class F1…F7
(F2)
N/O
3166 Dig. input 46 N/X N/O
N/C
0.0 s
3171 Dig. input 47 Delay 1.0 s
100.0 s
Warning
3175 Dig. input 47 Fail class F1…F7
(F2)
N/O
3176 Dig. input 47 N/X N/O
N/C
0.0 s
3181 Dig. input 48 Delay 1.0 s
100.0 s
Warning
3185 Dig. input 48 Fail class F1…F7
(F2)
N/O
3186 Dig. input 48 N/X N/O
N/C
0.0 s
3191 Dig. input 49 Delay 1.0 s
100.0 s
Warning
3195 Dig. input 49 Fail class F1…F7
(F2)
N/O
3196 Dig. input 49 N/X N/O
N/C
0.0 s
3201 Dig. input 50 Delay 1.0 s
100.0 s
Warning
3205 Dig. input 50 Fail class F1…F7
(F2)
N/O
3206 Dig. input 50 N/X N/O
N/C
0.0 s
3211 Dig. input 51 Delay 1.0 s
100.0 s
Warning
3215 Dig. input 51 Fail class F1…F7
(F2)
N/O
3216 Dig. input 51 N/X N/O
N/C
0.0 s
3221 Dig. input 52 Delay 1.0 s
100.0 s
Warning
3225 Dig. input 52 Fail class F1…F7
(F2)
N/O
3226 Dig. input 52 N/X N/O
N/C
0.0 s
3231 Dig. input 53 Delay 1.0 s
100.0 s
Warning
3235 Dig. input 53 Fail class F1…F7
(F2)
N/O
3236 Dig. input 53 N/X N/O
N/C
0.0 s
3241 Dig. input 54 Delay 1.0 s
100.0 s
Warning
3245 Dig. input 54 Fail class F1…F7
(F2)
N/O
3246 Dig. input 54 N/X N/O
N/C
0.0 s
3251 Dig. input 55 Delay 1.0 s
100.0 s
Warning
3255 Dig. input 55 Fail class F1…F7
(F2)
N/O
3256 Dig. input 55 N/X N/O
N/C
0.0 s
3331 Dig. input 91 Delay 1.0 s
100.0 s
Relay output R0 R0
3332 Dig. input 91
A Option-dep. (none)
Warning
3335 Dig. input 91 Fail class F1…F7
(F2)
N/O
3336 Dig. input 91 N/X N/O
N/C
0.0 s
3341 Dig. input 92 Delay 1.0 s
100.0 s
Relay output R0 R0
3342 Dig. input 92
A Option-dep. (none)
Warning
3345 Dig. input 92 Fail class F1…F7
(F2)
N/O
3346 Dig. input 92 N/X N/O
N/C
0.0 s
3351 Dig. input 93 Delay 1.0 s
100.0 s
Relay output R0 R0
3352 Dig. input 93
A Option-dep. (none)
Warning
3355 Dig. input 93 Fail class F1…F7
(F2)
N/O
3356 Dig. input 93 N/X N/O
N/C
0.0 s
3361 Dig. input 94 Delay 1.0 s
100.0 s
Relay output R0 R0
3362 Dig. input 94
A Option-dep. (none)
Warning
3365 Dig. input 94 Fail class F1…F7
(F2)
N/O
3366 Dig. input 94 N/X N/O
N/C
0.0 s
3371 Dig. input 95 Delay 1.0 s
100.0 s
Relay output R0 R0
3372 Dig. input 95
A Option-dep. (none)
Warning
3375 Dig. input 95 Fail class F1…F7
(F2)
N/O
3376 Dig. input 95 N/X N/O
N/C
0.0 s
3381 Dig. input 96 Delay 1.0 s
100.0 s
Relay output R0 R0
3382 Dig. input 96
A Option-dep. (none)
Warning
3385 Dig. input 96 Fail class F1…F7
(F2)
N/O
3386 Dig. input 96 N/X N/O
N/C
0.0 s
3391 Dig. input 97 Delay 1.0 s
100.0 s
Relay output R0 R0
3392 Dig. input 97
A Option-dep. (none)
Warning
3395 Dig. input 97 Fail class F1…F7
(F2)
N/O
3396 Dig. input 97 N/X N/O
N/C
OFF
3401 Wire fail 102 Enable OFF
ON
Dig. input Relay output Not used The input is configurable and can have
3403 Not used Designer’s
102 A Option-dep. different functions in different units.
Reference
Dig. input Relay output Not used (Only available if multi-input 102 is
3404 Not used Handbook
102 B Option-dep. configured to ‘digital’).
OFF
3411 Wire fail 105 Enable OFF
ON
Dig. input Relay output Not used The input is configurable and can have
3413 Not used Designer’s
105 A Option-dep. different functions in different units.
Reference
Dig. input Relay output Not used (Only available if multi-input 105 is
3414 Not used Handbook
105 B Option-dep. configured to ‘digital’).
OFF
3421 Wire fail 108 Enable OFF
ON
Dig. input Relay output Not used The input is configurable and can have
3423 Not used Designer’s
108 A Option-dep. different functions in different units.
Reference
Dig. input Relay output Not used (Only available if multi-input 108 is
3424 Not used Handbook
108 B Option-dep. configured to ‘digital’).
0.0 s
3491 Emer. stop Delay 0.0 s
100.0 s
Shutdow
3495 Emer. stop Fail class F1…F7 n
(F5)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
4 mA
4001 4-20 mA 91.1 Set point 10 mA
20 mA
0.0 s
4002 4-20 mA 91.1 Delay 120.0 s
600.0 s
R0 R0
4003 4-20 mA 91.1 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4004 4-20 mA 91.1 Relay B
Option-dep. (none)
OFF
4005 4-20 mA 91.1 Enable OFF
ON
Warning
4006 4-20 mA 91.1 Fail class F1…F7
(F2)
4 mA
4011 4-20 mA 91.2 Set point 10 mA
20 mA
0.0 s
4012 4-20 mA 91.2 Delay 120.0 s
600.0 s
R0 R0
4013 4-20 mA 91.2 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4014 4-20 mA 91.2 Relay B
Option-dep. (none)
OFF
4015 4-20 mA 91.2 Enable OFF
ON
Warning
4016 4-20 mA 91.2 Fail class F1…F7
(F2)
R0 R0
4021 W. fail ana 91 Relay A
Option-dep. (none)
Warning
4024 W. fail ana 91 Fail class F1…F7
(F2)
4 mA
4031 4-20 mA 93.1 Set point 10 mA
20 mA
0.0 s
4032 4-20 mA 93.1 Delay 120.0 s
600.0 s
R0 R0
4033 4-20 mA 93.1 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4034 4-20 mA 93.1 Relay B
Option-dep. (none)
OFF
4035 4-20 mA 93.1 Enable OFF
ON
Warning
4036 4-20 mA 93.1 Fail class F1…F7
(F2)
4 mA
4041 4-20 mA 93.2 Set point 10 mA
20 mA
0.0 s
4042 4-20 mA 93.2 Delay 120.0 s
600.0 s
R0 R0
4043 4-20 mA 93.2 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4044 4-20 mA 93.2 Relay B
Option-dep. (none)
OFF
4045 4-20 mA 93.2 Enable OFF
ON
Warning
4046 4-20 mA 93.2 Fail class F1…F7
(F2)
R0 R0
4051 W. fail ana 93 Relay A
Option-dep. (none)
Warning
4054 W. fail ana 93 Fail class F1…F7
(F2)
4 mA
4061 4-20 mA 95.1 Set point 10 mA
20 mA
0.0 s
4062 4-20 mA 95.1 Delay 120.0 s
600.0 s
R0 R0
4063 4-20 mA 95.1 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4064 4-20 mA 95.1 Relay B
Option-dep. (none)
OFF
4065 4-20 mA 95.1 Enable OFF
ON
Warning
4066 4-20 mA 95.1 Fail class F1…F7
(F2)
4 mA
4071 4-20 mA 95.2 Set point 10 mA
20 mA
0.0 s
4072 4-20 mA 95.2 Delay 120.0 s
600.0 s
R0 R0
4073 4-20 mA 95.2 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4074 4-20 mA 95.2 Relay B
Option-dep. (none)
OFF
4075 4-20 mA 95.2 Enable OFF
ON
Warning
4076 4-20 mA 95.2 Fail class F1…F7
(F2)
R0 R0
4081 W. fail ana 95 Relay A
Option-dep. (none)
Warning
4084 W. fail ana 95 Fail class F1…F7
(F2)
4 mA
4091 4-20 mA 97.1 Set point 10 mA
20 mA
0.0 s
4092 4-20 mA 97.1 Delay 120.0 s
600.0 s
R0 R0
4093 4-20 mA 97.1 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4094 4-20 mA 97.1 Relay B
Option-dep. (none)
OFF
4095 4-20 mA 97.1 Enable OFF
ON
Warning
4096 4-20 mA 97.1 Fail class F1…F7
(F2)
4 mA
4101 4-20 mA 97.2 Set point 10 mA
20 mA
0.0 s
4102 4-20 mA 97.2 Delay 120.0 s
600.0 s
R0 R0
4103 4-20 mA 97.2 Relay A
Option-dep. (none) Option:
Configurable analogue input.
R0 R0 4 x 4-20 mA inputs (M15.6)
4104 4-20 mA 97.2 Relay B
Option-dep. (none)
OFF
4105 4-20 mA 97.2 Enable OFF
ON
Warning
4106 4-20 mA 97.2 Fail class F1…F7
(F2)
R0 R0
4111 W. fail ana 97 Relay A
Option-dep. (none)
Warning
4114 W. fail ana 97 Fail class F1…F7
(F2)
INFO
The available menus for multi-input no. 102 depend on the input type configured in the PC utility software (menu 10980).
Min. Factory
No. Setting Notes Ref. Description
Max. setting
4-20 mA 4 mA
4121 Set point 10 mA
102.1 20 mA
4-20 mA 0.0 s
4122 Delay 120.0 s
102.1 999.0 s
4-20 mA OFF
4125 Enable OFF
102.1 ON
4-20 mA Warning
4126 Fail class F1…F7
102.1 (F2)
4-20 mA 4 mA
4131 Set point 10 mA
102.2 20 mA
4-20 mA 0.0 s
4132 Delay 120.0 s
102.2 999.0 s
4-20 mA OFF
4135 Enable OFF
102.2 ON
4-20 mA Warning
4136 Fail class F1…F7
102.2 (F2)
4140 V DC 102.1
0.0 V DC
4141 V DC 102.1 Set point 20.0 V DC
40.0 V DC
0.0 s
4142 V DC 102.1 Delay 10.0 s
999.0 s
OFF
4145 V DC 102.1 Enable OFF
ON
Warning
4146 V DC 102.1 Fail class F1…F7
(F2)
4150 V DC 102.2
0.0 V DC
4151 V DC 102.2 Set point 20.0 V DC
40.0 V DC
0.0 s
4152 V DC 102.2 Delay 10.0 s
999.0 s
OFF
4155 V DC 102.2 Enable OFF
ON
Warning
4156 V DC 102.2 Fail class F1…F7
(F2)
-49
4161 PT 102.1 Set point 80
482
0.0 s
4162 PT 102.1 Delay 5.0 s
999.0 s
Warning
4166 PT 102.1 Fail class F1…F7
(F2)
-49
4171 PT 102.2 Set point 80
482
0.0 s
4172 PT 102.2 Delay 5.0 s
999.0 s
Warning
4176 PT 102.2 Fail class F1…F7
(F2)
RMI oil 0
4181 Set point 4
102.1 145
RMI oil Relay Not used The multi-input 102 has been configured
4183 Not used Designer’s as RMI oil pressure.
102.1 output A Option-dep.
Reference Oil pressure set point can be in Bar or
RMI oil Relay Not used Handbook PSI, dependent on the unit selection
4184 Not used
102.1 output B Option-dep. (setting 10970).
RMI oil OFF
4185 Enable OFF
102.1 ON
RMI oil 0
4191 Set point 5
102.2 145
RMI oil Relay Not used The multi-input 102 has been configured
4193 Not used Designer’s as RMI oil pressure.
102.2 output A Option-dep.
Reference Oil pressure set point can be in Bar or
RMI oil Relay Not used Handbook PSI, dependent on the unit selection
4194 Not used
102.2 output B Option-dep. (setting 10970).
RMI oil OFF
4195 Enable OFF
102.2 ON
RMI water Relay Not used The multi-input 102 has been configured
4203 Not used Designer’s as RMI water temperature.
102.1 output A Option-dep.
Reference Water temperature set point can be in
RMI water Relay Not used Handbook deg. C or Fahrenheit, dependent on the
4204 Not used
102.1 output B Option-dep. unit selection (setting 10970).
RMI water OFF
4205 Enable OFF
102.1 ON
RMI water Relay Not used The multi-input 102 has been configured
4213 Not used Designer’s as RMI water temperature.
102.2 output A Option-dep.
Reference Water temperature set point can be in
RMI water Relay Not used Handbook deg. C or Fahrenheit, dependent on the
4214 Not used
102.2 output B Option-dep. unit selection (setting 10970).
RMI water OFF
4215 Enable OFF
102.2 ON
RMI fuel 0%
4221 Set point 10 %
102.1 100 %
RMI fuel 0%
4231 Set point 10 %
102.2 100 %
Warning
4244 W. fail 102 Fail class F1…F7
(F2)
INFO
The available menus for multi-input no. 105 depend on the input type configured in the PC utility software (menu 10990).
4-20 mA 4 mA
4251 Set point 10 mA
105.1 20 mA
4-20 mA 0.0 s
4252 Delay 120.0 s
105.1 999.0 s
4-20 mA OFF
4255 Enable OFF
105.1 ON
4-20 mA Warning
4256 Fail class F1…F7
105.1 (F2)
4-20 mA 4 mA
4261 Set point 10 mA
105.2 20 mA
4-20 mA 0.0 s
4262 Delay 120.0 s
105.2 999.0 s
4-20 mA OFF
4265 Enable OFF
105.2 ON
4-20 mA Warning
4266 Fail class F1…F7
105.2 (F2)
4270V DC 105.1
0.0 V DC
4271 V DC 105.1 Set point 20.0 V DC
40.0 V DC
0.0 s
4272 V DC 105.1 Delay 10.0 s
999.0 s
OFF
4275 V DC 105.1 Enable OFF
ON
Warning
4276 V DC 105.1 Fail class F1…F7
(F2)
4280V DC 105.2
0.0 V DC
4281 V DC 105.2 Set point 20.0 V DC
40.0 V DC
0.0 s
4282 V DC 105.2 Delay 10.0 s
999.0 s
OFF
4285 V DC 105.2 Enable OFF
ON
Warning
4286 V DC 105.2 Fail class F1…F7
(F2)
-49
4291 PT 105.1 Set point 80
482
0.0 s
4292 PT 105.1 Delay 5.0 s
999.0 s
Warning
4296 PT 105.1 Fail class F1…F7
(F2)
-49
4301 PT 105.2 Set point 80
482
0.0 s
4302 PT 105.2 Delay 5.0 s
999.0 s
Warning
4306 PT 105.2 Fail class F1…F7
(F2)
RMI oil 0
4311 Set point 4
105.1 145
RMI oil Relay Not used The multi-input 105 has been configured
4313 Not used Designer’s as RMI oil pressure.
105.1 output A Option-dep.
Reference Oil pressure set point can be in Bar or
RMI oil Relay Not used Handbook PSI, dependent on the unit selection
4314 Not used
105.1 output B Option-dep. (setting 10970).
RMI oil OFF
4315 Enable OFF
105.1 ON
RMI oil 0
4321 Set point 5
105.2 145
RMI oil Relay Not used The multi-input 105 has been configured
4323 Not used Designer’s as RMI oil pressure.
105.2 output A Option-dep.
Reference Oil pressure set point can be in Bar or
RMI oil Relay Not used Handbook PSI, dependent on the unit selection
4324 Not used
105.2 output B Option-dep. (setting 10970).
RMI oil OFF
4325 Enable OFF
105.2 ON
RMI water Relay Not used The multi-input 105 has been configured
4333 Not used Designer’s as RMI water temperature.
105.1 output A Option-dep.
Reference Water temperature set point can be in
RMI water Relay Not used Handbook deg. C or Fahrenheit, dependent on the
4334 Not used
105.1 output B Option-dep. unit selection (setting 10970).
RMI water OFF
4335 Enable OFF
105.1 ON
RMI water Relay Not used The multi-input 105 has been configured
4343 Not used Designer’s as RMI water temperature.
105.2 output A Option-dep.
Reference Water temperature set point can be in
RMI water Relay Not used Handbook deg. C or Fahrenheit, dependent on the
4344 Not used
105.2 output B Option-dep. unit selection (setting 10970).
RMI water OFF
4345 Enable OFF
105.2 ON
RMI fuel 0%
4351 Set point 10 %
105.1 100 %
RMI fuel 0%
4361 Set point 10 %
105.2 100 %
Warning
4374 W. fail 105 Fail class F1…F7
(F2)
INFO
The available menus for multi-input no. 108 depend on the input type configured in the PC utility software (menu 11000).
Min. Factory
No. Setting Notes Ref. Description
Max. setting
4-20 mA 4 mA
4381 Set point 10 mA
108.1 20 mA
4-20 mA 0.0 s
4382 Delay 120.0 s
108.1 999.0 s
4-20 mA OFF
4385 Enable OFF
108.1 ON
4-20 mA Warning
4386 Fail class F1…F7
108.1 (F2)
4-20 mA 4 mA
4391 Set point 10 mA
108.2 20 mA
4-20 mA 0.0 s
4392 Delay 120.0 s
108.2 999.0 s
4-20 mA OFF
4395 Enable OFF
108.2 ON
4-20 mA Warning
4396 Fail class F1…F7
108.2 (F2)
4400 V DC 108.1
0.0 V DC
4401 V DC 108.1 Set point 20.0 V DC
40.0 V DC
0.0 s
4402 V DC 108.1 Delay 10.0 s
999.0 s
OFF
4405 V DC 108.1 Enable OFF
ON
Warning
4406 V DC 108.1 Fail class F1…F7
(F2)
4410 V DC 108.2
0.0 V DC
4411 V DC 108.2 Set point 20.0 V DC
40.0 V DC
0.0 s
4412 V DC 108.2 Delay 10.0 s
999.0 s
OFF
4415 V DC 108.2 Enable OFF
ON
Warning
4416 V DC 108.2 Fail class F1…F7
(F2)
-49
4421 PT 108.1 Set point 80
482
0.0 s
4422 PT 108.1 Delay 5.0 s
999.0 s
Warning
4426 PT 108.1 Fail class F1…F7
(F2)
-49
4431 PT 108.2 Set point 80
482
0.0 s
4432 PT 108.2 Delay 5.0 s
999.0 s
Warning
4436 PT 108.2 Fail class F1…F7
(F2)
RMI oil 0
4441 Set point 4
108.1 145
RMI oil Relay Not used The multi-input 108 has been configured
4443 Not used Designer’s as RMI oil pressure.
108.1 output A Option-dep.
Reference Oil pressure set point can be in Bar or
RMI oil Relay Not used Handbook PSI, dependent on the unit selection
4444 Not used
108.1 output B Option-dep. (setting 10970).
RMI oil OFF
4445 Enable OFF
108.1 ON
RMI oil 0
4451 Set point 5
108.2 145
RMI oil Relay Not used The multi-input 108 has been configured
4453 Not used Designer’s as RMI oil pressure.
108.2 output A Option-dep.
Reference Oil pressure set point can be in Bar or
RMI oil Relay Not used Handbook PSI, dependent on the unit selection
4454 Not used
108.2 output B Option-dep. (setting 10970).
RMI oil OFF
4455 Enable OFF
108.2 ON
RMI water Relay Not used The multi-input 108 has been configured
4463 Not used Designer’s as RMI water temperature.
108.1 output A Option-dep.
Reference Water temperature set point can be in
RMI water Relay Not used Handbook deg. C or Fahrenheit, dependent on the
4464 Not used
108.1 output B Option-dep. unit selection (setting 10970).
RMI water OFF
4465 Enable OFF
108.1 ON
RMI water Relay Not used The multi-input 108 has been configured
4473 Not used Designer’s as RMI water temperature.
108.2 output A Option-dep.
Reference Water temperature set point can be in
RMI water Relay Not used Handbook deg. C or Fahrenheit, dependent on the
4474 Not used
108.2 output B Option-dep. unit selection (setting 10970).
RMI water OFF
4475 Enable OFF
108.2 ON
RMI fuel 0%
4481 Set point 10 %
108.1 100 %
RMI fuel 0%
4491 Set point 10 %
108.2 100 %
Warning
4504 W. fail 108 Fail class F1…F7
(F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
4510 Overspeed 1
100 %
4511 Overspeed 1 Set point 110 %
150 %
0.0 s
4512 Overspeed 1 Delay 5.0 s
100.0 s
OFF
4515 Overspeed 1 Enable ON
ON
Warning
4516 Overspeed 1 Fail class F1…F7
(F2)
4520 Overspeed 2
100 %
4521 Overspeed 2 Set point 120 %
150 %
0.0 s
4522 Overspeed 2 Delay 1.0 s
100.0 s
OFF
4525 Overspeed 2 Enable ON
ON
Shutdown
4526 Overspeed 2 Fail class F1…F7
(F5)
1 RPM
4531 Crank failure Set point 50 RPM
400 RPM
0.0 s
4532 Crank failure Delay 2.0 s
20.0 s
OFF
4535 Crank failure Enable OFF
ON
Warning
4536 Crank failure Fail class F1…F7
(F2)
0.0 s
4541 Run feedb. fail Delay 2.0 s
20.0 s
Warning
4545 Run feedb. fail Fail class F1…F7
(F2)
1.0 s
4561 Hz/V failure Delay 30.0 s
99.0 s
Block
4565 Hz/V failure Fail class F1…F7
(F1)
10.0 s
4581 Stop failure Delay 30.0 s
120.0 s
Shutdown
4585 Stop failure Fail class F1…F7
(F5)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
4 mA
4801 4-20 mA 127.1 Set point 10 mA
20 mA
0.0 s
4802 4-20 mA 127.1 Delay 120.0 s
600.0 s
R0 R0
4803 4-20 mA 127.1 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4804 4-20 mA 127.1 Relay B
Option-dep. (none)
OFF
4805 4-20 mA 127.1 Enable OFF
ON
Warning
4806 4-20 mA 127.1 Fail class F1…F7
(F2)
4 mA
4811 4-20 mA 127.2 Set point 10 mA
20 mA
0.0 s
4812 4-20 mA 127.2 Delay 120.0 s
600.0 s
R0 R0
4813 4-20 mA 127.2 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4814 4-20 mA 127.2 Relay B
Option-dep. (none)
OFF
4815 4-20 mA 127.2 Enable OFF
ON
Warning
4816 4-20 mA 127.2 Fail class F1…F7
(F2)
R0 R0
4821 W. fail ana 127 Relay A
Option-dep. (none)
Warning
4824 W. fail ana 127 Fail class F1…F7
(F2)
4 mA
4831 4-20 mA 129.1 Set point 10 mA
20 mA
0.0 s
4832 4-20 mA 129.1 Delay 120.0 s
600.0 s
R0 R0
4833 4-20 mA 129.1 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4834 4-20 mA 129.1 Relay B
Option-dep. (none)
OFF
4835 4-20 mA 129.1 Enable OFF
ON
Warning
4836 4-20 mA 129.1 Fail class F1…F7
(F2)
4 mA
4841 4-20 mA 129.2 Set point 10 mA
20 mA
0.0 s
4842 4-20 mA 129.2 Delay 120.0 s
600.0 s
R0 R0
4843 4-20 mA 129.2 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4844 4-20 mA 129.2 Relay B
Option-dep. (none)
OFF
4845 4-20 mA 129.2 Enable OFF
ON
Warning
4846 4-20 mA 129.2 Fail class F1…F7
(F2)
R0 R0
4851 W. fail ana 129 Relay A
Option-dep. (none)
Warning
4854 W. fail ana 129 Fail class F1…F7
(F2)
4 mA
4861 4-20 mA 131.1 Set point 10 mA
20 mA
0.0 s
4862 4-20 mA 131.1 Delay 120.0 s
600.0 s
R0 R0
4863 4-20 mA 131.1 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4864 4-20 mA 131.1 Relay B
Option-dep. (none)
OFF
4865 4-20 mA 131.1 Enable OFF
ON
Warning
4866 4-20 mA 131.1 Fail class F1…F7
(F2)
4 mA
4871 4-20 mA 131.2 Set point 10 mA
20 mA
0.0 s
4872 4-20 mA 131.2 Delay 120.0 s
600.0 s
R0 R0
4873 4-20 mA 131.2 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4874 4-20 mA 131.2 Relay B
Option-dep. (none)
OFF
4875 4-20 mA 131.2 Enable OFF
ON
Warning
4876 4-20 mA 131.2 Fail class F1…F7
(F2)
R0 R0
4881 W. fail ana 131 Relay A
Option-dep. (none)
Warning
4884 W. fail ana 131 Fail class F1…F7
(F2)
4 mA
4891 4-20 mA 133.1 Set point 10 mA
20 mA
0.0 s
4892 4-20 mA 133.1 Delay 120.0 s
600.0 s
R0 R0
4893 4-20 mA 133.1 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4894 4-20 mA 133.1 Relay B
Option-dep. (none)
OFF
4895 4-20 mA 133.1 Enable OFF
ON
Warning
4896 4-20 mA 133.1 Fail class F1…F7
(F2)
4 mA
4901 4-20 mA 133.2 Set point 10 mA
20 mA
0.0 s
4902 4-20 mA 133.2 Delay 120.0 s
600.0 s
R0 R0
4903 4-20 mA 133.2 Relay A Option:
Option-dep. (none)
4 x 4-20 mA inputs Configurable analogue input.
R0 R0 (M15.8)
4904 4-20 mA 133.2 Relay B
Option-dep. (none)
OFF
4905 4-20 mA 133.2 Enable OFF
ON
Warning
4906 4-20 mA 133.2 Fail class F1…F7
(F2)
R0 R0
4911 W. fail ana 133 Relay A
Option-dep. (none)
Warning
4914 W. fail ana 133 Fail class F1…F7
(F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Manual
Int. comm. CAN fail.
7532 No mode Manual
ID mode
change
Min. Factory
No. Setting Notes Ref. Description
Max. setting
0.0 s
7571 EI comm. error Timer 0.0 s
100.0 s
Warning
7575 EI comm. error Fail class F1…F7
(F2)
0.0 s
7581 EIC warning Timer 0.0 s
100.0 s
Not used
7582 EIC warning Relay A Not used
Option-dep. Option: J1939 and MTU ADEC/
MDEC (H5)
Not used
7583 EIC warning Relay B Not used Cummins Modbus
Option-dep.
(H6)
OFF J1939 (H7)
7584 EIC warning Enable ON
ON
Warning
7585 EIC warning Fail class F1…F7
(F2)
0.0 s
7591 EIC shutdown Timer 0.0 s
100.0 s
Not used
7592 EIC shutdown Relay A Not used
Option-dep. Option: J1939 and MTU ADEC/
MDEC (H5)
Not used
7593 EIC shutdown Relay B Not used Cummins Modbus
Option-dep.
(H6)
OFF J1939 (H7)
7594 EIC shutdown Enable ON
ON
Warning
7595 EIC shutdown Fail class F1…F7
(F2)
0%
7601 EIC overspeed Set point 107 %
400 %
0.0 s
7602 EIC overspeed Timer 2.0 s
100.0 s
Warning
7606 EIC overspeed Fail class F1…F7
(F2)
-40 deg
7611 EIC coolant t. 1 Set point 100 deg
210 deg
0.0 s
7612 EIC coolant t. 1 Timer 5.0 s
100.0 s
Warning
7616 EIC coolant t. 1 Fail class F1…F7
(F2)
-40 deg
7621 EIC coolant t. 2 Set point 110 deg
210 deg
0.0 s
7622 EIC coolant t. 2 Timer 5.0 s
100.0 s
Warning
7626 EIC coolant t. 2 Fail class F1…F7
(F2)
0 bar
7631 EIC oil press. 1 Set point 2 bar
10 bar
0.0 s
7632 EIC oil press. 1 Timer 5.0 s
100.0 s
Warning
7636 EIC oil press. 1 Fail class F1…F7
(F2)
0 bar
7641 EIC oil press. 2 Set point 1 bar
10 bar
0.0 s
7642 EIC oil press. 2 Timer 5.0 s
100.0 s
Warning
7646 EIC oil press. 2 Fail class F1…F7
(F2)
0 deg.
7651 EIC oil temp. 1 Set point 40 deg.
300 deg
0.0 s
7652 EIC oil temp. 1 Timer 5.0 s
100.0 s
Warning
7656 EIC oil temp. 1 Fail class F1…F7
(F2)
0 deg.
7661 EIC oil temp. 2 Set point 40 deg.
300 deg
0.0 s
7662 EIC oil temp. 2 Timer 5.0 s
100.0 s
Warning
7666 EIC oil temp. 2 Fail class F1…F7
(F2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Min. Factory
No. Setting Notes Ref. Description
Max. setting
INFO
The alarms based on external I/O modules can only be configured using the PC utility software.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
-20000
Ext. Ain 1.1 Set point 10
20000
2.0 s
Ext. Ain 1.1 Delay 10.0 s
600.0 s
Warning
Ext. Ain 1.1 Fail class F1…F7 Option:
(F2)
External I/O modules
R0 R0 (H8.x)
Ext. Ain 1.1 Relay A
Option-dep. (none)
R0 R0
Ext. Ain 1.1 Relay B
Option-dep. (none)
OFF
Ext. Ain 1.1 Enable OFF
ON
-20000
Ext. Ain 1.2 Set point 10
20000
2.0 s
Ext. Ain 1.2 Delay 10.0 s
600.0 s
Warning
Ext. Ain 1.2 Fail class F1…F7 Option:
(F2)
External I/O modules
R0 R0 (H8.x)
Ext. Ain 1.2 Relay A
Option-dep. (none)
R0 R0
Ext. Ain 1.2 Relay B
Option-dep. (none)
OFF
Ext. Ain 1.2 Enable OFF
ON
INFO
Same order for settings 12030-12230.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
2.0 s
Ext. dig. in 1 Delay 10.0 s
600.0 s
Warning
Ext. dig. in 1 Fail class F1…F7
(F2)
Option:
R0 R0
Ext. dig. in 1 Relay A External I/O modules
Option-dep. (none)
(H8.x)
R0 R0
Ext. dig. in 1 Relay B
Option-dep. (none)
OFF
Ext. dig. in 1 Enable OFF
ON
INFO
Same order for settings 12550-12690.
The parameter list contains settings for regulators and other non-alarm related settings.
3.1 Synchronisation
3.1.1 Synchronisation
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Dynamic 0.0 Hz
2021 dfMax. 0.2 Hz
sync. 0.5 Hz
Dynamic -0.5 Hz
2022 dfMin. 0.0 Hz
sync. 0.3 Hz
Sync t.
Dynamic 40 ms EG/SG/SC
2025 TB/SGB/SCB 50 ms
sync. 300 ms /BTB only
/BTB
0.00 Hz
2031 Static sync. dfMax. 0.10 Hz
0.50 Hz
2%
2032 Static sync. dUMax 5% Designer’s Setting 2030 is only available if
10 %
Reference ‘Static sync.’ Is chosen in setting
Close 0.1 deg Handbook 2001
2033 Static sync. 10.0 deg
window 20.0 deg
0.1 s
2034 Static sync. Delay 1.0 s
99.0 s
0.00
2041 f sync f Kp 0.50
60.00
PID controller for dynamic sync.
0.00 s Option E1, E2, This setting is only available if
2042 f sync f Ti 5.00 s
60.00 s EF2, EF4, EF5 “analogue” or “PWM” or “EIC” is
selected in setting 2780.
0.00 s
2043 f sync f Td 0.00 s
2.00 s
Designer’s
0 This setting is only available if
2051 f sync Kp 10 Reference
100 “relay” is selected in setting 2780.
Handbook
0.00
2061 Phase sync Phase Kp 0.50
60.00
PID controller for static sync.
Designer’s
0.00 s This setting is only available if
2062 Phase sync Phase Ti 5.00 s Reference
60.00 s “analogue” or “PWM” or “EIC” is
Handbook
selected in setting 2780.
0.00 s
2063 Phase sync Phase Td 0.00 s
2.00 s
Designer’s
0 This setting is only available if
2071 Phase Kp 10 Reference
100 “relay” is selected in setting 2780.
Handbook
0.0 Hz
2101 Sync PTH dfMax 0.3 Hz
0.5 Hz
-0.5 Hz
2102 Sync PTH dfMin 0.0 Hz Designer’s
0.3 Hz
Reference
2% Handbook
2103 Sync PTH dUMax 5%
30 %
P ramp 2%
2104 Sync PTH 100 %
down 100 %
Sync. 0.0 Hz
2111 dfMax. 3.0 Hz Designer’s Settings are accepted limits for
Blackout 0.5 Hz
Reference closing of the breaker, referring to
Sync. 2% Handbook nominal frequency and voltage.
2112 dUMax 5%
Blackout 10 %
3.2 Regulation
3.2.1 Regulation
Min. Factory
No. Setting Notes Ref. Description
Max. setting
0.00
2511 f control f Kp 0.50
60.00
Designer’s PID controller for frequency control
0.00 s
2512 f control f Ti 5.00 s Reference This menu is only available if
60.00 s
Handbook ‘analogue’ is chosen in menu 2781.
0.00 s
2513 f control f Td 0.00 s
2.00 s
0.00
2531 P control P Kp 0.50
60.00
Designer’s PID controller for power control
0.00 s
2532 P control P Ti 5.00 s Reference This menu is only available if
60.00 s
Handbook ‘analogue’ is chosen in menu 2781.
0.00 s
2533 P control P Td 0.00 s
2.00 s
0.00
2541 P LS control P LS Kp 0.50
60.00
PID controller for load sharing
Designer’s
0.00 s control
2542 P LS control P LS Ti 5.00 s Reference
60.00 s This menu is only available if
handbook
‘analogue’ is chosen in menu 2781.
0.00 s
2543 P LS control P LS Td 0.00 s
2.00 s
Analogue 0%
2551 Offset 50 % Designer’s PID controller for power control
GOV 100 %
Reference This menu is only available if
Analogue 0% Handbook ‘analogue’ is chosen in menu 2781.
2552 Set point 1 %/s
GOV 100 %
f control 0.20 %
2571 Deadband 2% Designer’s
relay 10.00 % This menu is only available if ‘relay’
Reference
f control 0 is chosen in menu 2781.
2572 Kp 10 Handbook
relay 100
P control 0.20 %
2581 Deadband 1% Designer’s
relay 10.00 % This menu is only available if ‘relay’
Reference
P control 0 is chosen in menu 2781.
2582 Kp 10 Handbook
relay 100
LS ctrl. 0.20 %
2591 f deadband 1%
relay 10.00 %
LS ctrl. 0
2592 LS Kp 10 Designer’s
relay 100 This menu is only available if ‘relay’
Reference
LS ctrl. 0.20 % is chosen in menu 2781.
2593 P deadband 2% Handbook
relay 10.00 %
LS ctrl. 0%
2594 P weight 15 %
relay 100 %
Relay GOV ON 10 ms
2601 500 ms
control time 6500 ms
Not used
Relay Decrease
2604 Option- Not used
control relay
dependent
0.00
2641 U control U Kp 0.50
60.00
PID controller for voltage control
Option:
0.00 s This menu is only available if
2642 U control U Ti 5.00 s AVR control
60.00 s analogue output is chosen in menu
(D1/D2)
2782.
0.00 s
2643 U control U Td 0.00 s
2.00 s
0.0 %
2691 U control U DB 2.0 % Option: PI controller for voltage control
10.0 %
AVR control This menu is only available if ‘relay’
0.0 (D1/D2) is chosen in menu 2782.
2692 U control U Kp 2.0
100.0
Relay R0
2724 U decrease R0
control Option-dep.
0s
2741 Delay reg. Delay 0s
9900 s
Not used
Relay output Delay regulation is the waiting time
2742 Delay reg. Option- Not used
A Designer’s before synchronising after the
dependent
Reference engine has started. It is used if the
Not used Handbook engine needs to stabilise after start
Relay output
2743 Delay reg. Option- Not used before attempting to synchronise.
B
dependent
OFF
2744 Delay reg. Enable OFF
ON
10 %
2951 Base load Power set 90 % Designer’s Setting and enabling of base load
120 %
Reference running. Note: Base load is only
OFF Handbook possible in semi-auto mode.
2952 Base load Enable OFF
ON
P Loadsh. 2.0 %
2961 Set point 15.0 %
fail 30.0 %
P Loadsh. 0.0 s
2962 Timer 30.0 s
fail 999.0 s
The alarm and fail class are
P Loadsh. Relay output Not used activated when the difference in
2963 Not used Designer’s
fail A Option-dep. “Power load share” between
Reference
P Loadsh. Relay output Not used generators has been continuously
2964 Not used Handbook
fail B Option-dep. above the programmed value
during the programmed delay.
P Loadsh. OFF
2965 Enable ON
fail ON
P Loadsh. Warning
2966 Fail class F1…F7
fail (F2)
Q Loadsh. 2.0 %
2971 Set point 15.0 %
fail 30.0 %
Q Loadsh. 0.0 s
2972 Timer 30.0 s The alarm and fail class are
fail 999.0 s
activated when the difference in
Q Loadsh. Relay output Not used “Reactive power load share”
2973 Not used Designer’s
fail A Option-dep. between generators has been
Reference
Q Loadsh. Relay output Not used continuously above the
2974 Not used Handbook
fail B Option-dep. programmed value during the
programmed delay. "Set point" is a
Q Loadsh. OFF percentage of P nominal.
2975 Enable ON
fail ON
Q Loadsh. Warning
2976 Fail class F1…F7
fail (F2)
Fixed PF 0.60
2981 Set point 0.80 Designer’s
set 1.00
Reference
Fixed PF Inductive Handbook
2982 Set point Inductive
set Capacitive
Min. Factory
No. Setting Notes Ref. Description
Max. setting
5000 Relay 05
5010 Relay 08
5020 Relay 11
5050 Relay 20
5060 Relay 21
5110 Relay 57
5120 Relay 59
5130 Relay 61
5140 Relay 63
5150 Relay 65
5160 Relay 67
5170 Relay 69
5180 Relay 71
5190 Relay 90
Alarm
5191 Relay 90 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #6
- Limit
0.0 s (M14.6)
5192 Relay 90 OFF delay 5.0 s - Horn
999.9 s
5200 Relay 92
Alarm
5201 Relay 92 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #6
- Limit
1.0 s (M14.6)
5202 Relay 92 OFF delay 5.0 s - Horn
999.9 s
5210 Relay 94
Alarm
5211 Relay 94 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #6
- Limit
2.0 s (M14.6)
5212 Relay 94 OFF delay 5.0 s - Horn
999.9 s
5220 Relay 96
Alarm
5221 Relay 96 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #6
- Limit
3.0 s (M14.6)
5222 Relay 96 OFF delay 5.0 s - Horn
999.9 s
Alarm
5231 Relay 126 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #8
- Limit
4.0 s (M14.8)
5232 Relay 126 OFF delay 5.0 s - Horn
999.9 s
Alarm
5241 Relay 128 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #8
- Limit
5.0 s (M14.8)
5242 Relay 128 OFF delay 5.0 s - Horn
999.9 s
Alarm
5251 Relay 130 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #8
- Limit
6.0 s (M14.8)
5252 Relay 130 OFF delay 5.0 s - Horn
999.9 s
Alarm
5261 Relay 132 Function Limit Alarm Function selections:
Option:
Horn - Alarm
4 x relay output, slot #8
- Limit
7.0 s (M14.8)
5262 Relay 132 OFF delay 5.0 s - Horn
999.9 s
5271 Transistor 20 T20 Relay kWh Relay The transistor outputs on terminals
21 and 22 can be configured as relay
outputs or pulse signals. If ‘Relay’ is
Designer’s Reference selected, the relays 20 and 21 will be
5272 Transistor 21 T21 Relay kvarh Relay Handbook available.
If set to ‘relay’, external relays are
needed due to limited current output.
Max. 10 mA.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
0.0 %
5721 Min. 10.0 % This is the minimum output level of the PWM signal.
50.0 %
0.0 % This is the initial output level, which is the level where the
5722 Init. value 35.0 %
100.0 % Option: PWM signal will start the regulation.
Governor PWM
50.0 % EF5
5723 Max. 90.0 % This is the maximum output level of the PWM signal.
100.0 %
OFF
5724 Enable OFF Enables or disables the PWM control.
ON
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Min. Factory
No. Setting Notes Ref. Description
Max. setting
-25/0 mA
5781 AOut 66 limits Min. -20/0 mA
10 mA Option: Min. range and factory setting value is
10 mA 2 x analogue outputs (E1/E2) option- dependent.
5782 AOut 66 limits Max. 20 mA
25 mA
-25/0 mA
5791 AOut 71 limits Min. -20/0 mA
10 mA Option: Min. range and factory setting value is
10 mA 2 x analogue outputs (E1/E2) option- dependent.
5792 AOut 71 limits Max. 20 mA
25 mA
0 mA
5801 AOut 91 limits Min. 0 mA
10 mA Option: Min. range and factory setting value is
10 mA 2 x analogue outputs (F1) option- dependent.
5802 AOut 91 limits Max. 20 mA
25 mA
0 mA
5811 AOut 95 limits Min. 0 mA
10 mA Option: Min. range and factory setting value is
10 mA 2 x analogue outputs (F1) option- dependent.
5812 AOut 95 limits Max. 20 mA
25 mA
Min. Factory
No. Setting Notes Ref. Description
Max. setting
5820 P output 1
R0 R0
5821 P output 1 Output A
Option-dep. (none)
R0 R0
5822 P output 1 Output B
Option-dep. (none)
Disabled Option:
5823 P output 1 Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0 kW
5824 P output 1 Max. value 500 kW
20000 kW
-9999 kW
5825 P output 1 Min. value 0 kW
20000 kW
5830 P output 2
R0 R0
5831 P output 2 Output A
Option-dep. (none)
R0 R0
5832 P output 2 Output B
Option-dep. (none)
Disabled Option:
5833 P output 2 Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0 kW
5834 P output 2 Max. value 500 kW
20000 kW
-9999 kW
5835 P output 2 Min. value 0 kW
20000 kW
5840 P output 3
R0 R0
5841 P output 3 Output A
Option-dep. (none)
R0 R0
5842 P output 3 Output B
Option-dep. (none)
Disabled Option:
5843 P output 3 Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0 kW
5844 P output 3 Max. value 500 kW
20000 kW
-9999 kW
5845 P output 3 Min. value 0 kW
20000 kW
5850 S output
R0 R0
5851 S output Output A
Option-dep. (none)
R0 R0
5852 S output Output B
Option-dep. (none)
Disabled Option:
5853 S output Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0 kVA
5854 S output Max. value 600 kVA
20000 kVA
-9999 kVA
5855 S output Min. value 0 kVA
20000 kVA
5860 Q output
R0 R0
5861 Q output Output A
Option-dep. (none)
R0 R0
5862 Q output Output B
Option-dep. (none)
Disabled Option:
5863 Q output Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0 kvar
5864 Q output Max. value 400 kvar
16000 kvar
-9999 kvar
5865 Q output Min. value 0 kvar
20000 kvar
5870 PF output
R0 R0
5871 PF output Output A
Option-dep. (none)
R0 R0
5872 PF output Output B
Option-dep. (none)
Disabled Option:
Positive value means inductive.
5873 PF output Type 0-20 mA Disabled Analogue outputs
Negative value means capacitive.
4-20 mA (E2 or F1 or EF2)
0.50
5874 PF output Max. value 0.80
0.99
-0.99
5875 PF output Min. value -0.80
-0.50
5880 f output
R0 R0
5881 F output Output A
Option-dep. (none)
R0 R0
5882 F output Output B
Option-dep. (none)
Disabled Option:
5883 F output Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0.0 Hz
5884 F output Max. value 55.0 Hz
70.0 Hz
0.0 Hz
5885 F output Min. value 45.0 Hz
70.0 Hz
5890 U output
R0 R0
5891 U output Output A
Option-dep. (none)
R0 R0
5892 U output Output B
Option-dep. (none)
Disabled Option:
The voltage output represents L1-L2
5893 U output Type 0-20 mA Disabled Analogue outputs
voltage.
4-20 mA (E2 or F1 or EF2)
0V
5894 U output Max. value 500 V
28000 V
0V
5895 U output Min. value 0V
28000 V
5900 I output
R0 R0
5901 I output Output A
Option-dep. (none)
R0 R0
5902 I output Output B
Option-dep. (none)
Disabled Option:
The current output represents L1
5903 I output Type 0-20 mA Disabled Analogue outputs
current.
4-20 mA (E2 or F1 or EF2)
0A
5904 I output Max. value 1000 A
9000 A
0A
5905 I output Min. value 0A
9000 A
5910 U BB output
R0 R0
5911 U BB output Output A
Option-dep. (none)
R0 R0
5912 U BB output Output B
Option-dep. (none)
Disabled Option:
The voltage output represents L1-L2
5913 U BB output Type 0-20 mA Disabled Analogue outputs
voltage.
4-20 mA (E2 or F1 or EF2)
0V
5914 U BB output Max. value 500 V
28000 V
0V
5915 U BB output Min. value 0V
28000 V
5920 f BB output
R0 R0
5921 F BB output Output A
Option-dep. (none)
R0 R0
5922 F BB output Output B
Option-dep. (none)
Disabled Option:
5923 F BB output Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0.0 Hz
5924 F BB output Max. value 55.0 Hz
70.0 Hz
0.0 Hz
5925 F BB output Min. value 45.0 Hz
70.0 Hz
R0 R0
5931 Multi-input 102 Output A
Option-dep. (none)
R0 R0
5932 Multi-input 102 Output B
Option-dep. (none)
Disabled Option:
5933 Multi-input 102 Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0
5934 Multi-input 102 Max. value 500
28000
0
5935 Multi-input 102 Min. value 0
28000
R0 R0
5941 Multi-input 105 Output A
Option-dep. (none)
R0 R0
5942 Multi-input 105 Output B
Option-dep. (none)
Disabled Option:
5943 Multi-input 105 Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0
5944 Multi-input 105 Max. value 500
28000
0
5945 Multi-input 105 Min. value 0
28000
R0 R0
5951 Multi-input 108 Output A
Option-dep. (none)
R0 R0
5952 Multi-input 108 Output B
Option-dep. (none)
Disabled Option:
5953 Multi-input 108 Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0
5954 Multi-input 108 Max. value 500
28000
0
5955 Multi-input 108 Min. value 0
28000
R0 R0
5961 P total consumed Output A
Option-dep. (none)
R0 R0
5962 P total consumed Output B
Option-dep. (none)
Disabled Option:
5963 P total consumed Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0 kW
5964 P total consumed Max. value 500 kW
20000 kW
-9999 kW
5965 P total consumed Min. value 0 kW
20000 kW
R0 R0
5971 P total available Output A
Option-dep. (none)
R0 R0
5972 P total available Output B
Option-dep. (none)
Disabled Option:
5973 P total available Type 0-20 mA Disabled Analogue outputs
4-20 mA (E2 or F1 or EF2)
0 kW
5974 P total available Max. value 500 kW
20000 kW
-9999 kW
5975 P total available Min. value 0 kW
20000 kW
INFO
These menus are used to select which analogue output to use for governor/ AVR (option D) control.
Factory
No. Setting Available settings Notes Ref. Description
setting
Disabled Option:
5981 Governor output Output A AO66 Option-dependent Analogue governor output
AO71 (E1/EF)
Disabled Option:
5991 AVR output Output A AO66 Option-dependent Analogue AVR output (E1/EF
AO71 and D1)
INFO
These menus include parameters for the system setup.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
48.0 Hz
6001 Nom. settings Frequency 50.0 Hz
62.0 Hz
10 kW
6002 Nom. settings Power 1000 kW
20000 kW
0A
6003 Nom. settings Current 1804 A Designer’s
9000 A
Reference
100 V Handbook
6004 Nom. settings Voltage 400 V
25000 V
100 RPM
6005 Nom. settings RPM 1500 RPM
4000 RPM
1
6006 Nom. settings Set 1
4
Nom. settings 10 kW
6012 Power 500 kW
2 20000 kW
Designer’s
Nom. settings 0A
6013 Current 902 A Reference
2 9000 A
Handbook
Nom. settings 100 V
6014 Voltage 400 V
2 25000 V
100 V
6041 G transformer U primary 400 V
25000 V
1A
6044 G transformer I secondary 5A
5A
6080 Language
2001 Depends on
6091 Date and time Year
2100 version
1 Depends on
6092 Date and time Month
12 version
0 Depends on
6095 Date and time Hour
23 version
0 Depends on
6096 Date and time Minute
59 version
6100 Counters
0 hr
6101 Counters Running hour 0 hr
999 hr
Start
6106 Counters
attempts
Not used
Service timer
6115 Output A Option- Not used
1
dependent
Not used
Service timer Relay output
6125 Option- Not used
2 A
dependent
0.0 s
6161 Run status Delay 5.0 s
300.0 s
Not used
Relay output
6162 Run status Option- Not used
A Designer’s
dependent If a relay output is used, the relay
Reference
Not used in question must be set to ‘limit’.
Relay output Handbook
6163 Run status Option- Not used
B
dependent
OFF
6164 Run status Enable OFF
ON
6180 Starter
0.0 s
6181 Starter Start prepare 5.0 s
600.0 s
0.0 s
6182 Starter Ext. prepare 0.0 s
600.0 s
Menus 6185 and 6186 relate to
Start ON 1.0 s using oil pressure as running
6183 Starter 5.0 s Designer’s
time 180.0 s feedback.
Reference
Start OFF 1.0 s If menu 6186 is set to 0.0, the oil
6184 Starter 5.0 s Handbook
time 99.0 s pressure running feedback is
disregarded.
Multi-input 102 Multi-input
6185 Starter Input type
Multi-input 108 102
0.0 bar
6186 Starter Set point 0.0 bar
300.0 bar
Designer’s
1
6191 Start attempts Set point 3 Reference Number of start attempts.
10
Handbook
Shutdown 1
6201 Attempts 7
override 10
Shutdown override turns all
Designer’s
Shutdown Cooling 0.0 s shutdowns into warnings. Only
6202 240.0 s Reference
override down 9900.0 s exception is overspeed and
Handbook
emergency stop.
Shutdown OFF
6203 Enable OFF
override ON
6210 STOP
Cooling 1.0 s
6211 STOP 240.0 s
down 9900.0 s The extended stop timer starts
Extended 2.0 s when the running feedback
6212 STOP 5.0 s Designer’s disappears. During the delay
stop 3200.0 s
Reference time it is not possible to start the
Multi-input 102 Multi-input Handbook engine. Menus 6213 and 6214
6213 STOP Type
M-Logic 102 are used for temperature-
0 dec. dependent cooling down.
6214 STOP Set point 0 dec.
482 dec.
6220 Hz/V OK
0.0 s
6231 GB control Close delay 2.0 s Designer’s Menu 6212 is for compact
30.0 s
Reference breakers (need to charge spring
0.0 s Handbook before closing).
6232 GB control Load time 0.0 s
30.0 s
Option G3
Load share 1V Adjustment of the analogue load
6381 Set point 4V Analogue load
out 5V sharing line max. value.
sharing
No mode
change/
SWBD ret. No mode
6911 Mode Semi auto
mode change
mode/
Auto
Min. Factory
No. Setting Notes Ref. Description
Max. setting
7040 Test
1%
7041 Test Set point 80 %
100 %
0.0 min.
7042 Test Delay 5.0 min.
999.0 min.
Semi-auto
7043 Return mode Auto
Auto
Simple
7044 Test type Load Simple
Full
Min. Factory
No. Setting Notes Ref. Description
Max. setting
OFF
7501 Comm. control Power OFF
ON
OFF
7502 Comm. control Frequency OFF These settings must be ON if commands are
ON
Option: to be sent over the Modbus communication.
OFF Modbus (H2) This will overrule external and internal
7503 Comm. control Voltage OFF
ON or Profibus settings.
(H3) Voltage, power factor and reactive power
OFF
7504 Comm. control PF OFF control requires AVR control (option D1).
ON
Reactive OFF
7505 Comm. control OFF
power ON
Option:
Ext. 1 Modbus (H2)
7511 ID 1
communication 247 or Profibus
(H3) The mode ASCII is used for modem
communication (ASCII: 7 data bit, RTU: 8
Ext. 9600 Option:
7512 Baud rate 9600 data bit)
communication 19200 Modbus (H2)
Min. Factory
No. Setting Notes Ref. Description
Max. setting
1
7531 Int. comm. ID ID 1 Designer’s Reference Handbook
16
Min. Factory
No. Setting Notes Ref. Description
Max. setting
OFF
Option:
Engine QSX15 The setting affects the displayed data, but
7561 Engine I/F OFF Cummins
type QSK23/45/60/78 not the Modbus data (option H2).
Modbus (H6)
QST30
OFF
DDEC
EMR
JDEC
Iveco
Perkins
Caterpillar MTU MDEC is only available in option H5.
Volvo Penta EMS Please choose MDEC 2000/4000 M.303,
Engine Volvo Penta EMS 2 when M.201 or M.304 is required.
7561 Engine I/F OFF
type Scania EMS Option: Menu 7562 is only available when MTU
Scania EMS S6 J1939/ MTU ADEC is selected as engine type.
MDEC 2000/4000 ADEC/ MTU Menu 7563 is for enabling the EIC
M.302 MDEC commands transmission.
MDEC 2000/4000 (H5) Menu 7564: When set to “on”, up to 19 extra
M.303 J1939 views (of 3 lines) are added to the 15 original
MTU ADEC (H7) V1 views (of 3 lines). These extra views are
Cummins displaying all the present engine com. values
Generic J1939 broadcasted on this CAN communication
CANopen 1 when this function is set on “on”.
7562 Node ID 6
ID 128
EIC On
7563 Enable On
controls Off
EIC Auto On
7564 Enable Off
view Off
Min. Factory
No. Setting Notes Ref. Description
Max. setting
KL320x
7951 Module 1
config
OFF
CAN I/F
7971 Type AOP-2 OFF
H8.2
Beckhoff
This menu is only activated if option H8.6 is
50 k activated.
CAN I/F Option:
7972 Baud 125 k 125 k After changing type, the parameter list in the
H8.2 External I/O
250 k PC USW must be uploaded again.
modules (H8)
CAN I/F Menu 7974 is for reestablishing
7973 ID 1 to 64 1 communication after a fault/disconnection.
H8.2
CAN I/F NO
7974 Reset NO
H8.2 YES
OFF
CAN I/F
7981 Type AOP-2 OFF
H8.8
Beckhoff
This menu is only activated if option H8.8 is
50 k activated.
CAN I/F Option:
7982 Baud 125 k 125 k After changing type, the parameter list in the
H8.8 External I/O
250 k PC USW must be uploaded again.
modules (H8)
CAN I/F Menu 7984 is for reestablishing
7983 ID 1 to 64 1 communication after a fault/disconnection.
H8.8
CAN I/F NO
7984 Reset NO
H8.8 YES
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Load-dep. 0.0 s
8004 Delay 10.0 s
start 990.0 s
Priorities available:
- Manual
Designer’s
Priority Manual - Delayed prio. shift
8031 Priority Manual Reference
select. Fuel optimisation - Dynamic
Handbook
- Running hours
- Fuel optimisation
1
8081 Priority 1 ID 1
16
1
8082 Priority 2 ID 2
16
1
8091 Priority 6 ID 6
16
1
8092 Priority 7 ID 7
16
1
8096 Priority 11 ID 11
16
1
8101 Priority 12 ID 12
16
1
8102 Priority 13 ID 13
16 Menu 8086 is only available if
Designer’s “Manual” is selected in menu 8031.
1
8103 Priority 14 ID 14 Reference Menu 8086 resets itself to OFF
16
Handbook automatically once the new settings
1 have been transmitted.
8104 Priority 15 ID 15
16
1
8105 Priority 16 ID 16
16
Running 1 hrs
8111 Set timer 175 hrs
hours 20000 hrs
Designer’s
Running Absolute The priority selection 8031 has been
8112 Type Absolute Reference
hours Relative selected as running hours.
Handbook
Running OFF
8113 Reset OFF
hours ON
Fuel 30 %
8171 Set point 80 %
optimise 100 %
0 kVA
8201 HC 1 Req. value 500 kVA
9999 kVA
0 kVA
8211 HC 2 Req. value 500 kVA
9999 kVA
Avail. Power 10 kW
8221 Set point 1000 kW
1 20000 kW
Avail. Power 10 kW
8231 Set point 1000 kW
2 20000 kW
Load-dep. 0.0 s
8304 Delay 10.0 s
start 2 990.0 s
0 kVA
8321 HC 3 Req. value 500 kVA
9999 kVA
0 kVA
8331 HC 4 Req. value 500 kVA
9999 kVA
10.0 s
8341 HC 1 Delay 180.0 s
600.0 s
Not used
8342 HC 1 Output A Option- Not used
dependent Designer’s
Reference
Not used Handbook
8343 HC 1 Output B Option- Not used
dependent
OFF
8344 HC 1 Enable OFF
ON
10.0 s
8351 HC 2 Delay 180.0 s
600.0 s
Not used
8352 HC 2 Output A Option- Not used
dependent Designer’s
Reference
Not used Handbook
8353 HC 2 Output B Option- Not used
dependent
OFF
8354 HC 2 Enable OFF
ON
10.0 s
8361 HC 3 Delay 180.0 s
600.0 s
Not used
8362 HC 3 Output A Option- Not used
dependent Designer’s
Reference
Not used Handbook
8363 HC 3 Output B Option- Not used
dependent
OFF
8364 HC 3 Enable OFF
ON
10.0 s
8371 HC 4 Delay 180.0 s
600.0 s
Not used
8372 HC 4 Output A Option- Not used
dependent Designer’s
Reference
Not used Handbook
8373 HC 4 Output B Option- Not used
dependent
OFF
8374 HC 4 Enable OFF
ON
Ld. start/ kW
8881 S1 kW Designer’s
stop kVA Selection of the base for the load-
Reference
Ld. start/ Percentage Percentag dependent start/stop.
8882 S2 Handbook
stop Value e
Designer’s
Blackout OFF Only for SG (shaft), SC (shore) and
8891 Auto close OFF Reference
func. ON BTB (bus tie breaker) unit.
Handbook
Blackout OFF
8892 I>> Start OFF
func. ON, 1 attempt
Secured OFF
8921 Enable OFF
mode ON
Analogue 102
HC 1 var Analogue
8931 Input Option-
load 102
dependent
Designer’s
This setting only appears if “Variable
HC 1 var 0 mA Reference
8934 Min Limit 0 mA load” is selected in setting 8203
load 10 mA Handbook
HC 1 var 10 mA
8935 Max Limit 20 mA
load 20 mA
Analogue 102
HC 2 var Analogue
8941 Input Option-
load 102
dependent
Designer’s
This setting only appears if “Variable
HC 2 var 0 mA Reference
8944 Min Limit 0 mA load” is selected in setting 8213
load 10 mA Handbook
HC 2 var 10 mA
8945 Max Limit 20 mA
load 20 mA
Max. no. DG 1
8951 Setting 1 16
run 16
Information about the actual software downloaded to the unit. Check this before contacting DEIF regarding service and support
matters.
The service port can be set up to use the ASCII communication. The ASCII communication is used when the utility software is
connected through a modem.
INFO
Selection ‘0’ must be used for cable connection between the PPM and the PC.
Selection ‘1’ must be used for modem connection between the PPM and the PC.
Information about the software version in the engine I/F PCB placed in slot #8.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
9100 Application
DANGER!
The unit will return to factory settings if the parameter is changed.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
911x Password
User 0
9116 Setting 2000
password 32000
It is recommended to change the password
Designer’s
Service YYYYY 0 levels of the user, service and master password,
9117 2001 Reference
password setting 32000 if access to parameter settings must be
Handbook
restricted.
Master XXXXX 0
9118 2002
password setting 32000
The service menu can only be entered using the ‘JUMP’ push-button. This menu is used in service situations.
In the alarm selection you can see all the alarm timers and their remaining time if they are counting.
The input and output selections show the present status of the inputs and outputs, for example mode inputs, relay outputs and load
sharing lines.
9122 N/A
9130 AC config
The backlight intensity of the display unit can be adjusted by using this parameter.
Backlight dim
9150 Sets the light intensity for the display
Press UP or DOWN
Min. Factory
No. Setting Notes Ref. Description
Max. setting
By using this setting, an application, which is available in one unit, can be transmitted to all other PPM-3 units connected to the
internal CAN bus line.
Min. Factory
No. Setting Notes Description
Max. setting
Off
ENABLE Broadcast + Off To broadcast an application to other PPM-3 units, the
Activate application number to be transmitted must be selected.
9190 Appl. Broadcast
Afterwards, the enable function can be chosen to either
Application 1 broadcast or broadcast and activate the application.
APPL. Appl. 1
Application 4
INFO
GSM settings are only accessible in the utility software.
0
GSM Pin code Function 1933 Designer’s Reference Handbook
9999
0
10330 Telephone 1 Function 12345678903 Designer’s Reference Handbook
99999999999
INFO
Telephone nos. 2-5 settings 10340-10370 are equal to setting 10330.
3.18 Passwords
3.18.1 Passwords
INFO
Password settings are only accessible in the utility software.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Selections are:
- None
None
10390 Passw. Lang. page None Designer’s Reference Handbook - Master
Customer
- Service
- Customer
Selections are:
- None
None
10400 Passw. Log page None Designer’s Reference Handbook - Master
Customer
- Service
- Customer
Selections are:
- None
None
10410 Passw. Control page None Designer’s Reference Handbook - Master
Customer
- Service
- Customer
INFO
RMI 102 settings are only accessible in the utility software.
Selections are:
- Sensor type 1
Sensor type 1
10460 RMI 1 type Sensor type 1 Designer’s Reference Handbook - Sensor type 2
Configurable
- Sensor type 3
- Configurable
0 Ohm
10470 RMI 1 inp. Setp. 1 10 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10480 RMI 1 outp. Setp. 1 40 Designer’s Reference Handbook Configurable RMI curve
482
0 Ohm
10490 RMI 1 inp. Setp. 2 44.9 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10500 RMI 1 outp. Setp. 2 50 Designer’s Reference Handbook Configurable RMI curve
482
0 Ohm
10510 RMI 1 inp. Setp. 3 81 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10520 RMI 1 outp. Setp. 3 60 Designer’s Reference Handbook Configurable RMI curve
482
0 Ohm
10530 RMI 1 inp. Setp. 4 134.7 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10540 RMI 1 outp. Setp. 4 80 Designer’s Reference Handbook Configurable RMI curve
482
0 Ohm
10550 RMI 1 inp. Setp. 5 184 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10560 RMI 1 outp. Setp. 5 100 Designer’s Reference Handbook Configurable RMI curve
482
0 Ohm
10570 RMI 1 inp. Setp. 6 200 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10580 RMI 1 outp. Setp. 6 110 Designer’s Reference Handbook Configurable RMI curve
482
0 Ohm
10590 RMI 1 inp. Setp. 7 210 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10600 RMI 1 outp. Setp. 7 115 Designer’s Reference Handbook Configurable RMI curve
482
0 Ohm
10610 RMI 1 inp. Setp. 8 220 Ohm Designer’s Reference Handbook Configurable RMI curve
480 Ohm
-49
10620 RMI 1 outp. Setp. 8 120 Designer’s Reference Handbook Configurable RMI curve
482
INFO
RMI 105 settings are only accessible in the utility software.
INFO
Settings 10630-10790 equal the settings for RMI 102 (10460-10620).
INFO
RMI 108 settings are only accessible in the utility software.
INFO
Settings 10800-10960 equal the settings for RMI 102 (10460-10620).
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Bar/Celsius
10970 Engineering units Bar/Celsius
Psi/Fahrenheit
Possible selections:
4-20 mA
4-20 mA 0-40 V DC
10980 Multi-inp. conf. 102 0-40 V DC
Binary Pt100
Pt1000
RMI oil pressure
Possible selections:
4-20 mA
0-40 V DC
Pt100
4-20 mA
10990 Multi-inp. conf. 105 0-40 V DC Pt1000
Binary
RMI oil pressure
RMI water temp.
RMI fuel level
Binary
Possible selections:
4-20 mA
0-40 V DC
Pt100
4-20 mA
11000 Multi-inp. conf. 108 0-40 V DC Pt1000
Binary
RMI oil pressure
RMI water temp.
RMI fuel level
Binary
INFO
External digital output settings are only accessible in the utility software.
Min. Factory
No. Setting Notes Ref. Description
Max. setting
Alarm
Siren
12790 Ext. dig. out 1 Function Alarm
Horn Option:
Limit External I/O modules (H8)
0.0 s
Ext. dig. out 1 OFF delay 5.0 s
999.9 s
INFO
The same applies to settings 12800-12940.
INFO
External module status is only accessible in the utility software.
Min.
No. Setting Notes Ref. Description
Max.
INFO
The same applies to settings 12951-12983 (external modules 1 to 33).