PROPOSED BUNGALOW For Building Permit

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

..\Desktop\334899313_531721435697983_5969940162874563083_n.

png
DISTRICT/ MUNICIPACILITY/CITY
TABLE OF CONTENTS
ARCHITECTURAL LAND USE AND ZONING

A1 PERSPECTIVE
VICINITY MAP
SITE DEVELOPMENT PLAN

A2 FLOOR PLAN
ROOF PLAN

A3 FRONT ELEVATION
RIGHT SIDE ELEVATION LINE AND GRADE
REAR ELEVATION
LEFT SIDE ELEVATION

A4 SECTIONS
SCHEDULE OF DOORS & WINDOWS

STRUCTURAL

1 PERSPECTIVE
S1 FOUNDATION PLAN ARCHITECTURAL
WALL FOOTING DETAIL

1
COLUMN FOOTING DETAIL

2
A -01 S C A L E NTS

3
6000
3350
FENCE DETAIL PLAN
2650 700
FENCE DETAIL ELEVATION
300 1150
1200
1000
1200
1150 S2 R.C. BEAM DETAIL
RAFTER DETAIL
THIS SITE ROOF FRAMING PLAN

S3 GENERAL NOTES
MONSERRAT SLAB DETAIL STRUCTURAL
BRGY. YUKOS, NAGCARLAN, LAGUNA

A
RD
- LILIW
CA RLAN ELECTRICAL
NAG
430
E1 LEGENDS
LIRIO ST.

3000
SCHEDULE OF LOADS
LIGHTING LAYOUT
N POWER LAYOUT
SINGLE LINE RISER DIAGRAM
.
VICTORIA ST
LEDESMA ST.

3400

6050

B
GENERAL NOTES ELECTRICAL

900
W E
6680

425

650
PLUMBING

3050
MONSERRAT
RD

600
P1 WASTE WATER LAYOUT
725

WATERLINE LAYOUT
RIZAL-NAGCARLAN

2000
LIRIO ST.

PLUMBING NOTES

900
1200

LEGENDS

C
425
P2 MISCELLANEOUS DETAIL SANITARY
925

1075 1000
2275 FIRE PROTECTION
2650
T. 1000
CALAUAN-NAGCARLAN RD RIA S 8000 FP1 GROUND FLOOR FIRE PROTECTION
M. DO
LAYOUT
MUNICIPAL HALL
NAGCARLAN

MECHANICAL

2 VICINITY MAP 3 SITE DEVELOPMENT PLAN


A -01 S C A L E NTS A -01 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

A-01
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
A B C A B C
6050 6050
3000 3050 3000 3050
900 650 600 900 900 650 600 900

1000

1000
700

700
D-2
1 1

1075

1075
1150

1150
D-3
3350

3350
1200

1200
W2

2275

2275
2400
D-1 1950
1
A -04
1000

1000
6000

8000

6000

8000
600
300

300
2 2
D-1
1200

1200
W2
2650

2650

2650

2650
1150

1150
W1

3 3

1000

1000
425 2000 425 425 2000 425

430 3400 725 1200 925 430 3400 725 1200 925

2 6680 6680

A -04

1 GROUND FLOOR PLAN 2 ROOF PLAN


A -02 S C A L E NTS A -02 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

A-02
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
A B C 3 2 1
6050 8000

3000 3050 1000 2650 2275 1075 1000


630 850 1850 300 3050
APEX APEX
ELEV. @ 4.35m ELEV. @ 4.35m

550

550
600

600
FCL FCL
ELEV. @ 3.2m ELEV. @ 3.2m
3000

3000
1500

1500
FFL FFL
ELEV. @ 0.600m ELEV. @ 0.600m
600

600
NGL NGL
ELEV. @ 0.00m ELEV. @ 0.00m

1 FRONT ELEVATION 2 RIGHT SIDE ELEVATION


A -03 S C A L E NTS A -03 S C A L E NTS

C B A 1 2 3
6050 6000

1000 573 2700 1875 700 1150 1200 1000 300 1200 1150

APEX APEX
ELEV. @ 4.35m ELEV. @ 4.35m
550

550
600

600
FCL FCL
ELEV. @ 3.2m ELEV. @ 3.2m
3000

3000
1500
FFL FFL
ELEV. @ 0.600m ELEV. @ 0.600m
600

600

NGL NGL
ELEV. @ 0.00m ELEV. @ 0.00m

3 LEFT SIDE ELEVATION 4 REAR ELEVATION


A -03 S C A L E NTS A -03 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

A-03
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
A B C
6050

3000 3050

630 850 1850 300 3050 700 800 600


APEX
ELEV. @ 4.35m

550
600
FCL
ELEV. @ 3.2m

2100

2100
2100
3000
D-2 FLASH DOOR D-1 FLASH DOOR D-3 PVC DOOR
FFL NO.OF SETS: 1 SET NO.OF SETS: 2 SETS NO.OF SETS: 1 SET
ELEV. @ 0.600m LOCATION: BACK DOOR KITCHEN LOCATION: BEDROOMS LOCATION: T&B
600

NGL
ELEV. @ 0.00m

1 SECTION 1 3 SCHEDULES OF DOORS


A -04 S C A L E NTS A -04 S C A L E NTS

3 2 1
8000

1000 2650 2275 1075 1000


2000
1000 1000
APEX 1200
ELEV. @ 4.35m
550
600

FCL

1200

2500
ELEV. @ 3.2m
3000

900
W2 W1
1500

ALUMINUM POWDER
FFL COATED BLACK
ELEV. @ 0.600m SLIDING WINDOW
LOCATION: BEDROOMS
600

NGL
ELEV. @ 0.00m

2 SECTION 2 4 SCHEDULES OF WINDOWS


A -04 S C A L E NTS
A -04 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

A-04
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
4-12 mm Ø & 2-10 mm Ø 4-12 mm Ø & 2-10 mm Ø
4-12 mm Ø & 2-10 mm Ø RSB VERT. BARS
RSB VERT. BARS RSB VERT. BARS
W/10mm Ø LATERAL TIES, W/10mm Ø LATERAL TIES,
W/10mm Ø LATERAL TIES, 1 @50m, 6 @100, 6@150 REST AT 200 OC
1 @50m, 6 @100, 6@150 REST AT 200 OC 1 @50m, 6 @100, 6@150 REST AT 200 OC

5-Ø12mm dia RSB 5-Ø12mm dia RSB 5-Ø12mm dia RSB


SPACED AS SHOWNED SPACED AS SHOWNED SPACED AS SHOWNED
BOTH WAYS BOTH WAYS BOTH WAYS

N.G.L. N.G.L.
1000 1000
N.G.L.
300 200
1000
200 800.00

800.00

800.00

1000
150
1000
200
250.00
1000
250.00
300

250.00

PLAN ELEVATION PLAN ELEVATION


PLAN ELEVATION F1-C1 F1-C2 1000
1000
F1-C1 1000

A B C 2 COLUMN FOOTING DETAIL


S -01 S C A L E NTS
6050
DRYWALL 3" x 2" x 1.5
3000 3050 GPURLINS FRAME W/
1/2" THK FICEM BOARD

F1C1 F1C1 F1C1 3-10mmø


LONGITUDINAL BARS

CHB
1

4"
VERT./HOR. 10mm
BARS EVERY 3
FTB FTB LAYERS OF CHB 4" THK CONCRETE
4-10mm Ø RSB VERT. BARS HOLLOW BLOCKS
100mmø TRANSVERSE W/9mm Ø LATERAL TIES
CONCRETE PLASTER
BARS @ 0.40M O.C. 4-10mm Ø RSB VERT. BARS

CHB
SLAB ON FILL

4"
W/9mm Ø LATERAL TIES
ELEV. .60m +-
FTB
3350

3350
FTB

3-10mmø CONCRETE DESIGN CONCRETE DESIGN


LONGITUDINAL BARS 3000 PSI 3000 PSI

F1C1 F1C1 PLAN SECTION WALL FOOTING 200mm


WF WIDE, 2-Ø10mm
6000

6000

300

HOR. BAR W/
Ø10mm STIRRUPS
2
3 WF DETAIL HOS. SPACED @
400mm OC

S -01 S C A L E NTS COMPACTED


GRAVEL BEDDING
WALL FOOTING 200mm 50mm THK
FTB

FTB

WIDE, 2-Ø10mm 5-Ø10mm dia RSB


2650

2650

HOR. BAR W/ SPACED AS SHOWNED


Ø10mm STIRRUPS BOTH WAYS

F1C1 F1C1 F1C1 HOS. SPACED @


400mm OC FF1 FF1
3
FTB FTB CONCRETE DESIGN
3000 PSI

100mm THK CONCRETE SLAB ON


FFTB1 CONCRETE DESIGN
3000 PSI
FILL W/ 8mmØ REBARS @450mmO.C. COMPACTED
GRAVEL BEDDING
ON 50mm THK WELL-COMPACTED 50mm THK

3000 3050
BASECOURSE, 95% MDD
FC1 4-10 mm Ø RSB VERT. BARS
COMPACTED
GRAVEL BEDDING
6050 W/9mm Ø LATERAL TIES
FC1 50mm THK

4000
5 FENCE DETAIL ELEVATION
1 FOUNDATION PLAN 4 FENCE DETAIL PLAN S -01 S C A L E NTS
S -01 S C A L E NTS S -01 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

S-01
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
V A R I E S
@ MID SPAN
200mm L/4 EXTRA TOP BARS @ L/4
SUPPORTS

A B C
400mm

6050

3000 3050

@SUPPORT STIFFENER @MIDSPAN @SUPPORT


BOTTOM BARS
L/2

10mmØ BARS STIRRUPS


@ SUPPORT @ SUPPORT

1000
SPACED @ 1 @ 50mm,
2''x4''x1/4'' Chanel Bar Rafter
3 @ 100mm,4 @ 150mm, 1
REST @ 200mm
RB-01 RB-01

1075
1 R.C. BEAM DETAIL
S -02 S C A L E NTS

RB-01

RB-01
3350

2275
R.C . COLUMNS SCHEDULE
REINFORCEMENTS TIE BARS EQUAL EQUAL EQUAL

6000

8000
COLUMNS SIZE
VERT. BARS SIZE SPACING FROM
MARK (B x D)
OF BOTTOM OF SUPPORT 2
NUMBER OF BARS TIES OF SPAN (mm)
C1 200 X 300 4-12Ø & 2-10Ø 1-Ø10 1@50,6@100,6@150 REST @200 O.C.

RB-01

RB-01
C2 200 X 300 4-12Ø & 2-10Ø 1-Ø10 1@50,6@100,6@150 REST @200 O.C.

2650

2650
FC 200 X 300 4-10Ø 1-Ø9 1@50,6@100,6@150 REST @200 O.C.


°

R.C . FOOTING SCHEDULE


REINFORCEMENTS
SIZE DEPTH
MARK (L x W x D) OF INSIDE GUTTER 3
HOR. BARS RB-01 RB-01
FOOTING

1000
NUMBER OF BARS 50x75x1.2mm CEE PURLINS

FOOTINGS 1
RAFTER 1 - 2x4x4 CHANNEL BAR

F1 1000 x 1000 x 300 1200 5-Ø12 @ BOTHWAYS 2''x3''x1.5mm C-Purlins


FF1 800 x 800 x 300 1200 5-Ø12 @ BOTHWAYS 2 RAFTER DETAIL
S -02 S C A L E NTS

R.C . BEAM SCHEDULE


REINFORCEMENTS WEB
MARK SIZE BARS
(W x D) SUPPORT MIDSPAN SPACING FROM FACE OF
EACH SIZE
TOP BOTTOM TOP BOTTOM FACE SUPPORT OF SPAN (mm)

BEAMS

FTBM 200 X 300 4-Ø12 2-Ø12 2-Ø12 4-Ø12 Ø10 1@50,6@100,6@150 REST @250 O.C.

RB-01 200 X 300 2-Ø12 2-Ø12 2-Ø12 2-Ø12 Ø10 1@50,6@100,6@150 REST @250 O.C.
430 3400 725 1200 925

FFTB-01 200 X 300 2-Ø10 2-Ø10 2-Ø10 2-Ø10 Ø10 1@50,6@100,6@150 REST @400 O.C. 6680

3 ROOF FRAMING PLAN


S -02 S C A L E NTS
ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

S-02
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
GENERAL NOTES: 7.2 WHERE LOOSE/SOFT MATERIAL IS ENCOUNTERED AT DEPTH OF FOOTING/FOUNDATION
1.0 GENERAL : INDICATED, EXCAVATE TO FIRM LAYER AND REPLACE LOOSE/SOFT MATERIALS UNDERNEATH
THE FOOTING WITHIN THE FOOTING AREA PLUS ½ DEPTH OF SOIL MATERIAL ON ALL SIDES WITH
SELECTED BACKFILL. COMPACT SELECTED BACKFILL TO 95% MAXIMUM DRY DENSITY (ASTM
1.1 ALL DIMENSIONS ARE SHOWN IN MILLIMETERS, ELEVATIONS ARE IN METERS, UNLESS D1557).
NOTED OTHERWISE. 7.3 ALL COLUMN FOOTINGS SHALL REST ON 100mm THK COMPACTED GRAVEL BASE COURSE,
1.2 THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE, AND UNLESS OTHERWISE STATED.
4.2.1 UNLESS OTHERWISE SPECIFIED ON PLANS, ALL REINFORCING BARS SHALL BE
SHALL NOTIFY THE ENGINEER OF DISCREPANCIES BETWEEN ACTUAL BOTTOM BARS
DEFORMED WITH A MINIMU YIELD STRENGTH, fy = 275 MPa (40,000 PSI). 7.4 FILL/BACKFILL SHALL BE PLACED IN 20mm LAYERS AND EACH LAYER SHALL BE TOP BARS
CONDITIONS AND INFORMATION SHOWN ON THE DRAWINGS BEFORE PROCEEDING WITH THE
FOR DIAMETER 12 AND 16 AND fy = 228MPa (33,000 PSI). COMPACTED TO 95% MAXIMUM DRY DENSITY BEFORE SUBSEQUENT LAYERS ARE TO BE LAID.
WORK. THIS SHALL INCLUDE THE LOCATION AND DIMENSIONS OF GROOVES, REGLETS,
SLEEVES, CURBS, OPENINGS, EMBEDDED OR ATTACHED ITEMS, ETC. REFER TO ARCHITECTURAL, FOR DIAMETER 10 AND BELOW. SECTION
MECHANICAL, AND ELECTRICAL AND PLUMBING ALL FIGURED DIMENSIONS SHALL TAKE 4.2.2 ALL REINFORCING BARS SHALL BE CLEANED OF RUST, GREASE OR OTHER MATERIALS
PRECEDENCE OVER SCALE SHOWN ON PLANS, DRAWINGS. WHICH TEND TO IMPAIR BOND. LENGTH (SHORT SPAN)
1.3 SECTIONS OR DETAILS, SPECIFIC NOTES AND DETAILS ON DRAWINGS SHALL TAKE 4.2.3 ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED BEFORE BAR ANCHORAGE
STANDARD HOOK LAP SPLICE (m)
UNIT
MIN. LAP SPLICE LENGTH L/4 L/2 L/4
(m) OF COL REINF.
PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. POURING CONCRETE OR APPLYING MORTAR OR GROUT. DIAMETER LENGTH TENSION BAR COMP. BAR WEIGHT INDIVIDUAL BARS
(mm) (m) (Kg/m)
1.4 THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE 4.2.4 LAPPED SPLICES SHALL BE STAGGERED WHERE POSSIBLE. 90° 180° 135° TOP BAR OTHERS TOP BAR OTHERS W/ TIES W/ SPIRAL
FINISHED STRUCTURES. THEY DO NOT INDICATE THE METHOD OF CONTRUCTION UNLESS 4.2.5 UNLESS INDICATED OTHERWISE, SPLICING OF REINFORCEMENT SHALL BE IN 10 0.50 0.15 0.13 0.10 0.42 0.30 0.42 0.30 0.617 0.30 0.30
SO STATED. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MEASURES TO PROTECT THE ACCORDANCE WITH ACI- 318-2002.
12 0.50 0.20 0.15 0.12 0.42 0.30 0.42 0.30 0.889 0.30 0.30
STRUCTURES, ADJACENT PROPERTIES, WORKMEN AND OTHER PERSONS DURING ALL PHASES 4.2.6 UNLESS SHOWN OTHERWISE ON PLANS, SPLICES SHALL BE AS FOLLOWS :
OF CONSTRUCTION. 16 0.60 0.25 0.18 0.14 0.73 0.52 0.87 0.62 1.580 0.52 0.47
A.BEAMS AND FOOTING TIE BEAMS : TOP AND BOTTOM BARS SHALL NOT BE SPLICED
1.5 THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE OWNER AND/OR THE ENGINEER 20 0.60 0.30 0.20 0.20 0.91 0.65 1.10 0.78 2.469 0.65 0.58
WITHIN THE COLUMN OR WITHIN A DISTANCE OF TWICE THE MEMBER DEPTH FROM
OF ANY CONDITION WHICH IN HIS OPINION MIGHT ENDANGER THE STABILITY OF THE STRUCTURES THE FACE OF THE COLUMN: AT LEAST TWO EXTRA STIRRUP- IES SHALL BE 25 0.68 0.40 0.28 0.26 1.15 0.82 1.40 1.00 3.858 0.80 0.73
OR CAUSE DISTRESS IN THE STRUCTURES. PROVIDED AT ALL SPLICES. THE SPLICE LENGTH SHALL NOT BE LESS THAN THE 28 0.86 0.48 0.38 1.45 1.03 1.53 1.09 4.840 0.90 0.82
1.6 CONSTRUCTION MATERIALS SHALL NOT BE STORED ON POURED FLOORS. IT IS THE LENGTH IN ITEM 4.2.9 BELOW. 32 1.12 0.56 0.43 1.90 1.35 1.74 1.24 6.327 1.03 0.93
GENERAL CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT THE SUB-CONTRACTORS ARE

LENGTH (LONGER SPAN)


B. COLUMNS : SPLICES WHEN PERMITTED SHALL BE MADE WITHIN THE CENTER HALF 36 1.43 0.61 0.48 2.40 1.70 2.00 1.40 8.00 1.20 1.05
INFORMED AND DO NOT VIOLATE THIS IMPORTANT REQUIREMENT.
OF COLUMN HEIGHT AND LAP SPLICE SHALL NOT BE LESS THAN 40 BAR
1.7 THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION BRACINGS AND SHORINGS COLUMN/WALL

FOR ALL THE STRUCTURAL MEMBERS AS REQUIRED FOR STRUCTURE STABILITY DURING ALL
DIAMETERS. THE USED OF APPROVED MECHANICAL DEVICES MAY BE PERMITTED NOTES: FACE ANCHORAGE
LENGTH
PROVIDED THAT NOT MORE THAN ALTERNATE BARS ARE SPLICED AT ANY LEVEL 1. ACI SECTION 12.4 STATES THAT DEVELOPMENT LENGTH OF INDIVIDUAL BARS WITHIN A
PHASES OF CONSTRUCTION. AND THE MINIMUM VERTICAL DISTANCE BETWEEN TWO ADJACENT BAR SPLICES BUNDLE, IN TENSION OR COMPRESSION, SHALL BE THAT FOR THE INDIVIDUAL BAR,
1.8 THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE PROPER SHALL BE 600mm. INCREASED 20% FOR THREE BAR BUNDLE, AND 33% FOR FOUR BAR BUNDLE. 180°
ALIGNMENT OF THE STRUCTURE DURING AND AFTER THE INSTALLATION OF ALL STRUCTURAL 2.FOR COLUMNS, AT ANY LEVEL NO MORE THAN ALTERNATE BARS SHOULD BE SPLICED. NOT HOOK
C.CMU WALLS : VERTICAL BARS SHALL BE SPLICED AT THE TOP OF WALL FOOTING
AND FINISHED MATERIALS. MORE THAN 33% OF THE BARS SHALL BE SPLICED WITHIN THE REQUIRED LAP LENGTH.
OR TIE BEAM AND AT THE BOTTOM OF RC LINTEL BEAM OR BEAMS. SPLICE 3.TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 300mm DEPTH OF CONCRETE CAST
1.9 WORKS UNLESS OTHERWISE SHOWN ON DRAWINGS. 135°
LENGTHS SHALL BE 600mm MIN. BELOW THE REINFORCEMENT. HOOK 90°
4. AS MUCH AS POSSIBLE, SPLICES SUBJECTED TO TENSILE STRESSES ARE DISCOURAGE, THESE
4.2.7 UNLESS INDICATED OTHERWISE ALL BEAMS TERMINATING AT THE COLUMN SHALL HOOK
2.0 STANDARDS AND REFERENCE SHOULD BE AVOIDED OR PROVIDED WITH STANDARD HOOKS.
HAVE TOP AND BOTTOM BARS EXTENDING TO THE FAR FACE OF THE COLUMN, TERMINATING IN A
THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND CONSTRUCTION OF THE STANDARD 90° HOOK LENGTH OF ANCHORAGE NOT LESS THAN 600mm.
PROJECT. 4.2.8 SHOP DRAWINGS FOR BENDING AND CUTTING OF REINFORCEMENT SHALL BE
SUBMITTED FOR APPROVAL TO THE ENGINEER PRIOR TO FABRICATION.
DETAIL
2.1 AMERICAN CONCRETE INSTITUTE (ACI PUBLICATIONS) ; 12mm THK. COMPRESSIBLE JOINT
AC1 318-2002 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE 4.2.9 SPLICE LENGTH OF REINFORCING BARS SHALL BE AS SHOWN IN THE TABLE BELOW. FILLER W/ SEALANT
(TYP.)
DOWELS
ACI 315-80 MANUAL OF STANDARD PRACTICE FOR DETAILS AND DETAILING OF 6t_OR
4.3 STRUCTURAL STEEL/ ANCHOR BOLTS/ BOLTS/ WELDS & WELDMENTS 450 MIN
CONCRETE REINFORCEMENT.
STIFFENER/ BOND BEAM
2.2 AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC PUBLICATION) : 4.3.1 ALL STRUCTURAL STEEL SHALL HAVE A MINIMUM YIELD STRENGTH, Fy = 248 MPa (36
MANUAL OF STEEL CONSTRUCTION, NINTH EDITION. KSI) AND SHALL CONFORM TO ASTM A 36 SPECIFICATIONS. CASE 1
4.3.2 ALL STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH

2.3
“ALLOWABLE STRESS DESIGN” (ASD)
AMERICAN WELDING SOCIETY (AWS) PUBLICATION D.1.1-2000.
THE AISC SPECIFICATIONS (9TH EDITION) AND CODE OF STANDARD PRACTICE AS AMENDED
150
PROVIDE 90° HOOK WHERE
t EXCEEDS 50mm BOTTOM OF BEAM S-2 PLAN VIEW
TO DATE.
2.4 AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM) 4.3.3 ALL COLD FORMED STEEL SHALL HAVE A MINIMUM STRENGTH, FY = 230 MPa (33 KSI)
2.5 NATIONAL STRUCTURAL CODE OF THE PHILIPPINES (NSCP) VOL. 1, SIXTH EDITION 2010. 4.3.4 NO STEEL SHALL BE FABRICATED OR ERECTED UNTIL SHOP DRAWINGSHAVE BEEN
10mmø AS SHOWN HORIZONTAL BARS
2.6 ASSOCIATION OF STRUCTURAL ENGINEERS OF THE PHILIPPINES (ASEP) HANDBOOK OF APPROVED BY THE STRUCTURAL ENGINEER. 10mmø @ 400mm O.C.
STRUCTURAL STEEL SHAPES AND SECTIONS, 1987 4.3.5 ALL SHOP AND FIELD WELDING SHALL BE IN ACCORDANCE WITH AWS D.1.1-2000 AND VERTICAL BARS
BOTTOM BARS
100 TOP BARS
2.7 UNIFORM BUILDING CODE (UBC), VOL. 2 1997 EDITION PERFORMED BY QUALIFIED WELDERS. CASE 3
4.3.6 UNLESS INDICATED OTHERWISE, WELDING ELECTRODES SHALL BE E70XX, MINIMUM
THICKNESS OF WELD SHALL BE 3mm.
FINISH FLOOR LINE SECTION
3.0 BASIC DESIGN LOADS
4.3.7 UNLESS OTHERWISE INDICATED ALL ANCHOR BOLTS SHALL CONFORM TO ASTM A307 DOWELS LENGTH (SHORT SPAN)
3.1 DESIGN LOADS (DL) : SPECIFICATIONS. CASE 2
3.1.1 CONCRETE 24.00 Kn/m
DEPRESSED BEAM/SLAB AND SLAB EDGE DETAILS L/4 L/2 L/4
4.3.8 BOLTS FOR MEMBER CONNECTIONS SHALL BE HIGH STRENGTH BOLTS, CONFORMING TYPICAL CHB WALL ELEVATION
3.1.2 STEEL 77.00 Kn/m TO ASTM A325 FRICTION TYPE WITH WASHERS.
150 100
3.1.3 SOIL 18.00 kPa 4.4 CONCRETE MASONRY UNITS (CMU)
R.C. WALL BOT. OF STIFFENER/BOND BEAM

3.1.4 CEILING 0.20 kPa 4.4.1 CMU USED IN THESE WORKS SHALL HAVE A MINIMUM ULTIMATE COMPRESSIVE BEAM
CHB WALL 16mmø VERT. BARS
STRENGTH @28 DAYS. @ 200mm O.C.
3.1.5 FLOOR FINISH 1.20 kPa 12mm THK. PLASTER
4.4.2 ALL CELLS SHALL BE SOLIDLY FILLED WITH GROUT. CONCRETE SHALL HAVE A 10mmø HOR. BARS 10mmø HOR. BARS COMPRESSIBLE
3.1.6 ROOFING (CLAYTILES), PURLINS & INSULATION 1.00 kPa MINIMUM COMPRESSIVE STRENGTH OF 13.80MPa (2000 PSI) @ 28 DAYS. @ 400mm O.C. @ 300mm O.C. JOINT FILLER W/

<1000
SEALANT
3.1.7 100mm THK. CHB WALL 2.11 kPa 4.4.3 UNLESS INDICATED OTHERWISE, CMU REINFORCEMENT SHALL BE 10mmø HORIZONTAL (TYP.) 100 CHB WALL

L/4
<1000 <3000
BARS @ 600 AND 10mmø VERTICAL BARS @ 600. 16mmø VERT. BARS 16mmø VERT. BARS
3.1.8 150mm THK. CHB WALL 2.73 kPa @ 400mm O.C. @ 200mm O.C.

h
4.4.4 ALL WALLS SHALL BE CONSTRUCTED IN CONVENTIONAL RUNNIG BOND UNLESS

h/2
3.2 LIVE LOADS (LL) : NOTED OTHERWISE. DECK SLAB DECK SLAB
3.2.1 RESIDENTIAL 1.90 kPa 4.4.5 GROUT MASONRY IN 2.4M MAXIMUM LIFTS. REINFORCING SHALL BE SECURED AGAINST 1-ø16 VERT. BAR

3.2.2 ROOF 0.60 kPa DISPLACEMENT PRIOR TO GROUTING BY WIRE POSITIONERS AT INTERVALS NOT SECTION B

h
EXCEEDING 200 BAR DIAMETERS NOR 3M.
3.2.3 BALCONY 2.90 kPa R.C. EDGE BEAM R.C. EDGE BEAM
4.4.6 IF WORK IS STOPPED ONE (1) HOUR OR LONGER, PROVIDE HORIZONTAL FFL
3.2.4 STORAGE (@ ATTIC) 1.90 kPa CONSTRUCTION JOINTS BY STOPPING THE GROUT 50mm BELOW THE TOP OF THE BLOCK.

L/2
NOTE: DOWELS
3.2.5 STORAGE (@ SECOND FLOOR) 4.80 kPa (UNLESS OTHERWISE

3.2.6 THEATRE 2.90 kPa 5.0 CONSTRUCTION JOINTS :


CASE 1 NOTED ON PLANS) CASE 2
SECTION A
3.2.7 HALLWAY 3.80 kPa 5.1 CONSTRUCTION JOINTS NOT INDICATED ON PLANS SHALL BE MADE SO AS TO LEAST IMPAIR
3.3 WIND LOAD (WL) THE STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT TO APPROVAL OF THE ENGINEER. TYPICAL DETAIL OF PARAPET TOP BARS TOP BARS
THE WIND LOAD ON STRUCTURE AND BUILDING SHALL BE CALCULATED, BASED ON 5.2 UNLESS SHOWN OTHERWISE, SLAB ON GRADE SHALL HAVE CONTROL JINTS @ 6.00M
MAXIMUM CENTER TO CENTER. 250
NATIONAL STRUCTURAL CODE OF THE PHILIPPINES, CONSIDERING BASIC WIND SPEED (3
ø 10mm TIES/
SECOND GUST SPEED) EQUALS TO 41.70 M/SEC. NOTE:
STIRRUPS @ 200mm

L/4
UNLESS OTHERWISE NOTED IN THE PLAN, PROVIDE
O.C.
BASIC WIND SPEED, V = 200 Km/HOUR 6.0 NOTES ON BEAMS AND GIRDERS FRAMING STIFFENER COLUMNS & STIFFENER BEAMS BOT. BARS BOT. BARS
NOT MORE THAN 3.0M APART.

100
OCCUPANCY CATEGORY = IV 6.1 UNLESS OTHERWISE NOTED IN PLANS OR SPECIFICATIONS, CAMBER ALL BEAMS AND OPENING
IMPORTANCE FACTOR,lw = 1.0 GIRDERS AT LEAST 0.006M FOR EVERY 4.50M OF SPAN EXCEPT CANTILEVERS FOR WHICH THE CLEAR SPAN
12mmø MAIN BARS
CAMBERS SHALL BE AS NOTED IN THE PLANS OR AS ORDERED BY THE DESIGNERS. BUT IN TOTAL LENGTH
EXPOSURE CATEGORY =B
h < 3000

NO CASE LESS THAN .019M FOR EVERY 3.00M OF FREE SPAN.


300 ø 10mm TIES/
VELOCITY PRESSURE AT HEIGHT 'Z', qz = 47.3x10-6.Kz.KzT.V2.lw
6.2 IF THERE ARE TWO OR MORE LAYERS OF REINFORCING BARS, USE SEPARATORS OF SIZE STIRRUPS @ 200mm
THIS VELOCITY PRESSURE SHALL BE USED ALONG WITH FORCE COEFFICIENTS TO NOT LESS THAN 25mm BARS SPACED ABOUT 1.00M ON CENTER AND PLACED DIAGONALLY. IN O.C.
REINF. CONCRETE LINTEL S-1 PLAN VIEW
h < 3000

WALL BASE

150-200
CALCULATE WIND LOAD ON SPECIFIC STRUCTURE. NO CASE SHALL THERE BE LESS TWO (2) SEPARATORS BETWEEN LAYERS OF BARS.
3.4 SEISMIC LOAD, E 6.3 WHEN A BEAM CROSSES A GIRDER, REST BEAM BARS ON TOP OF GIRDER BARS.
BEAM IN CHB WALLS
REINFORCING BARS SHALL BE ASYMMETRICAL ABOUT THE CENTER LINE WHENEVER
POSSIBLE. UPPER LAYER SHALL BE PLACED DIRECTLY ABOVE THOSE IN THE BOTTOM LAYER. t < 3000 t < 3000 4-ø12mm MAIN BARS
4.0 MATERIALS SPACING OF BARS IN LAYER SHALL NOT BE LESS THAN 0.025M NOR ONE BAR DIAMETER.
4.1 NORMAL WEIGHT CONCRETE: 6.4 GENERALLY, NO SPLICE SHALL BE PERMITTED ON BEAM AT POINT WHERE CRITICAL OF COLUMN
4.1.1 CONCRETE USED IN THIS WORK SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH @ BENDING STRESSES OCCUR. WELDED SPLICES SHALL DEVELOP IN TENSION ATLEAST 125% OF
28 DAYS AS FOLLOWS: THE SPECIFIED STRENGTH OF THE BAR, NOT MORE THAN 50% OF THE BARS AT ANY ONE TYPICAL DETAIL STIFFENER BEAMS/COLUMNS
COLUMNS & BEAMS fc' = 21MPa (3,000 PSI) SECTION SHALL BE ALLOWED TO BE SPLICED THEREIN.
FOUNDATION, & SLABS, & SLAB ON GRADE fc' = 17.5MPa (2,500 PSI)
4.1.2 ALL CONCRETE SHALL BE DEPOSITED, VIBRATED AND CURED IN ACCORDANCE WITH
6.5 FOR BARS TERMINATIONS OF TOP BARS AT SUPPORT AND MIDSPAN BARS, CUT-OFF ONLY
TWO BARS AT EVERY 0.3M INTERVAL (UNLESS REQUIRED IN SPECIFICATIONS, OR NOTED 25mm-75mm 1 SLAB DETAIL
ACI STANDARD 318-95
4.1.3 MINIMUM CONCRETE COVER FOR REINFORCING BARS SHALL BE AS FOLLOWS:
OTHERWISE.) NOTE:
1. REINF. TO BE SAME BAR SIZE AND SPACING AS S -03 S C A L E NTS
ADJACENT REINF. BARS ON SLABS. TOP BARS
A.FOOTINGS & BOT. OF FOOTING TIE BEAM = 75mm (CAST AGAINST EARTH) 2-10mmø TYP. 2. FOR CLOSURE SLABS AT OPENINGS AND BLOCKS STIRRUPS @ 100mm
7.0 FOUNDATIONS 250mmø OUT, REBARS TO BE THE SAME SIZE, AND 2/3 THE
MAX. BOTTOM BARS MAX. SPACING
25mm-75mm

B.BEAMS AND COLUMNS = 25mm (TO STIRRUPS AND TIES) 7.1 FOOTING WERE DESIGNED USING AN ASSUMED ALLOWABLE SOIL BEARING CAPACITY OF
SPACING OF BARS AS ADJACENT SLABS.

C.SLABS AND WALLS = 20mm (CAST AGAINST FORMS) 144KPa (3000 PSF) AT DEPTHS INDICATED IN THE DRAWING BASED FROM THE GEOTECHNICAL
4.1.4 BEFORE CONCRETE IS POURED, CHECK WITH ALL TRADES TO ENSURE PROPER REPORT AS SUBMITTED BY GEOTESTING (INTERNATIONAL) IN.
PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, ETC. RELATIVE TO THE WORK.4.2 TYPICAL SPLICE DETAILS FOR BEAMS
REINFORCING BARS :
TYPICAL PIPE SLEEVE OPENING FOR SLABS FRAMING INTO COLUMN

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

S-03
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
LEGEND LOAD SCHEDULE - MAIN DISTRIBUTION PANEL
CIRCUIT BREAKER RATING
CKT VA PER PVC
RMS LOAD DESCRIPTON AMPERE SERVICE WIRE GROUND WIRE
NO. AT AF POLE V TYPE CKT Dia. IN INCH
KAIC
1 15 50 2 230 5 BO LIGHTING OUTLET, 45@40VA 1560 6.78 2 X 3.5mm2THHN 1 X 3.5mm2THHN 1/2
2 20 50 2 230 5 BO CONVENIENCE OUTLET, 18@250VA 4500 19.57 2 X 3.5mm2THHN 1 X 3.5mm2THHN 1/2
3 30 50 2 230 5 BO REFRIGERATOR 1000 2 X 3.5mm2THHN 1 X 3.5mm2THHN 1/2
S1
4 30 50 2 230 5 BO RANGE 2000 8.70 2 X 3.5mm2THHN 1 X 3.5mm2THHN 1/2
Sab
5 30 50 2 230 5 BO AIRCON 6000 26.10 2 X 3.5mm2THHN 1 X 3.5mm2THHN 1/2
Sabc
USE: 60AT, BO, 60AF, 10KAIC, 2 POLE MAIN CIRCUIT BREAKER
2 x 5.5mm2THHN SERVICE WIRE & 1-3.5mm2THHN GROUND WIRE
1 LOAD SCHEDULE
E -01 S C A L E NTS

GENERAL NOTES :
ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH ALL THE
PROVISIONS OF PHILIPPINE ELECTRICAL CODE, PART I, AND ALL THE REGULATIONS
OF THE LOCAL AUTHORITY AND THE UTILITY COMPANY, WHICH ARE HEREBY MADE
S1 PART OF THESE SPECIFICATIONS.
S1 RESPECTIVE KIND.
ALL MATERIALS SHALL BE NEW AND SHALL CONFORM WITH THE STANDARDS OF
THE UNDERWRITTER'S LABORATORY OR TO THE BUREAU OF PRODUCT.
4
Crkt REF ALL MATERIALS WHERE NOT SPECIFIED SHALL BE THE BEST OF THEIR STANDARDS.
S1
3
Crkt
1. ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE

S
ab
M PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE,
THE LAWS AND ORDINANCES OF THE LOCAL CODE ENFORCING AUTHORITIES
AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY.
2. THE CONTRACTOR SHALL SECURE ALL PERMITS AND PAY ALL FEES REQUIRED
FOR THE WORK AND SHALL FURNISH THE OWNER THROUGH THE ENGINEERS.
FINAL CERTIFICATES OF ELECTRICAL INSPECTION AND APPROVAL FROM
PROPER GOVERNMENT AUTHORITIES FOR COMPLETE WORK.
S1
3. ALL MATERIALS TO BE USED SHALL BE NEW AND INSTALLED IN APPLICATIONS
4 FOR WHICH THEY ARE INTENDED.
Crkt
4. ALL METALLIC CONDUITS, CABINETS AND EQUIPMENTS SHALL BE PROPERLY
S abc GROUNDED AND BONDED BY MEANS OF COPPER STRAPS AND BONDING
BUSHING. CONNECTION TO GROUND ROD SHALL BE EXPOSED READILY
ACCESIBLE FOR INSPECTION.
2 5. LIGHTING BRANCH CIRCUITS WITHOUT DESIGNATION SHALL BE 2-WIRE, 3.5
Crkt sq.mm TW, 1-3.5 sq.mm GROUND WIRE IN 15mm (INTERNAL DIAMETER)
CONDUIT UNLESS NOTED OTHERWISE.
1 6. BOXES SHALL BE MADE OF CODE GAGE SEEL WITH ZINC CHROMATE
Crkt PROTECTION.
7. MOUNTING HEIGHTS FOR SWITCHES AND CONVENIENCE OUTLETS SHALL BE
1.40M. AND 0.30M RESPECTIVELY, UNLESS OTHERWISE NOTED.
8. ALL RECEPTACLE OUTLETS SHALL BE PROPERLY GROUNDED TO THE BOX BY
MEANS OF GROUNDING LUGS.
9. FOR SWITCH BOXES WITH MORE THAN (4) WIRES ENTERING THEM USE
4 SINGLE LINE RISER DIAGRAM 10.
1OOmm. X 100MM. SQUARE BOX WITH ONE (1) GANG ADAPTER RING.
PULLBOXES SHALL BE PROVIDED BY THE CONTRACTOR WHENEVER NECESSARY
E -01 S C A L E NTS TO FACILITATE WIRE PULLING EVEN IF THESE ARE NOT INDICATED ON THE
PLANS.
11. THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR THE EXACT
LOCATION OF MOTORS AND CONTROLS.
12. ALL PIPE CHASE OPENINGS BETWEEN FLOORS SHALL BE CONCRETED TO CLOSE
THE OPENINGS AFTER INSTALLATION OF CONDUITS.
13. ALL RISERS FOR POWER AND AUXILIARY SHALL BE IN EE PIPE CHASE ONLY
UNLESS OTHERWISE NOTED.
14. THE CONTRACTOR SHALL PERFORM THE APPLICATION OF ELECTRICAL POWER
AND TELEPHONE CONNECTION INCLUDING PREPARATION OF ALL NECESSARY
PLANS, SHOP DRAWINGS, FORM AND RELATED DOCUMENTS, PAYMENT OF ALL
REQUIRED FEES AND CHARGES AND COORDINATION WITH OTHER
AUTHORITIES OR PERSON INVOLVED IN THE PROCEDURE.

GROUND FLOOR GROUND FLOOR

2 LIGHTING LAYOUT 3 POWER LAYOUT


E-01 S C A L E NTS E-01 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

E-01
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
SHO/

KS
LAV
F 1. ALL PLUMBING WORKS HEREIN SHALL ON
HB FORM WITH THE LATEST PROVISION OF
KS
CB
LAV THE PHILIPPINE PLUMBING CODE & THE
WC FD
LOCAL AUTHORITIES CONCERNED.
WC

2. USE PVC PIPE FOR THE WATER SUPPLY


LINE.
KS

KS
3. INSTALLATION AND TESTING SHALL BE
CB
CO
DONE UNDER THE DIRECT SUPERVISION OF
A DULY REGISTERED SANITARY ENGINEER
OR MASTER PLUMBER.
HB
4. MAINTAIN A SLOPE OF 2% FOR SEWER LINE
CB & 1% FOR DRAINAGE LINE
5. ALL MATERIALS SHALL BE NEW AND
APPROVED TYPE.

6. CLEAN OUT SHALL BE SUPPLIED EVERY 45°


SEPTIC
VAULT .BEND.

7. ALL DRAIN SHALL BE VENTED


INDIVIDUALLY.

8. ALL PIPING SHALL BE AS MUCH AS


POSSIBLE CONCEALED.

9. ANY REVISIONS OR RELOCATION SHALL BE


FROM UPON THE APPROVAL OF THE ENGINEER.
WATER
SOURCE

GROUND FLOOR GROUND FLOOR

1 WATERLINE LAYOUT 2 WASTE WATER LAYOUT


P-01 S C A L E NTS P-01 S C A L E NTS

500
500 LEGENDS & SYMBOLS :
400 100 300 100

100 300 100 ST SEPTIC TANK PT PRESSURE TANK


50 50
F FAUCET CWL COLWATER LINE
LAV LAVATORY DFPR DOWN FEED PIPE RISER
PERFORATED STEEL PLATE KS KITCHEN SINK UFPR UP FEED PIPE RISER
100

AV ANGLE VALVE CB CATCH BASIN


CO CLEAN OUT SS SOIL STACK
INLET OUTLET 4" THK CHB FD FLOOR DRAIN VSTR VENTILATION STACK THRU ROOF
400
400

INLET OUTLET SHO SHOWER LT LAUNDRY TUB


300
500

GV GATE VALVE SPDR STORM PIPE DRAIN RISER


100mm uPVC PIPE CV CHECK VALVE WMD WASHING MACHINE DRAIN
HB HOSE BIBB RD ROOF DRAIN
BP
100

WC WATER CLOSET BOOSTER PUMP


100

100mm R.C. SLAB W/ 6-12mm


BARS B.W.

3 AREA DRAIN/ CATCH BASIN DETAIL


P -01 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

P-01
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
GASKETED ABS CLEAN OUT PLUG

POLISHED BRASS COVER HOUSING (ADJUSTABLE) ADJUSTABLE


SURFACE FINISHING SQUARE DRAINER

FINISHED FLOOR LINE FLASHING CLAMP

CONCRETE SLAB

3200 PVC CONNECTION TO


SUIT DRAIN & P-TRAP
150 1000 150 1000 150 1000 150 ADAPTER OUTLET (CAULKED OR THREADED) SIZE

200 600 200 100 600 100 100 600 100 PVC TRAP

1/4 BEND OR T-Y CONNECTION


150
200

OUTLET
DETAIL OF SHOWER/FLOOR DRAIN

2 FLOOR CLEAN OUT DETAIL 3 P-TRAP DETAIL


INLET

P -02 S C A L E NTS P -02 S C A L E NTS


MH MH MH
1300
1000
600

ø12 BARS
@ 150mm O.C. (E.W.)
ø12 BARS
@ 150mm O.C. (E.W.)
200
150

Ø1/2"HOSE BIBB(BALL VALVE)

ø12 DIAGONAL BARS


PLAN EVERY CORNER

Ø1/2"PVC. PIPE
100

CLAM

AIR SPACE AIR SPACE AIR SPACE


ø150 pvc pipe

HOSE Ø1/2"HOSE BIBB


1250
1500
1300

DIGESTIVE LEACHING LEACHING CLAM


ø12 HORIZONTAL BAR EVERY 3 LAYERS OF CHB

150mm THK. CHB PLASTERED FIN. 150mm THK. CHB PLASTERED FIN.
ø12 VERTICAL BAR @600mm O.C. ø12 VERTICAL
BAR @600mm
HOSE
O.C.
150mm THK. CHB PLASTERED FIN. Ø1/2"GSP. PIPE
(ABOVE GROUND)

ø12 BARS @600mm O.C. CONCRETE


FINISH FLOOR LEVEL

SECTION
HDPE PN-10 PIPE (UNDER GROUND)

1 SEPTIC TANK DETAIL


P -02 S C A L E NTS
4 HOSE BIBB DETAIL
P -02 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

P-02
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA
LEGEND

EXIT
EXIT
FIRE EXTINGUISHER

ESCAPE ROUTE
EXIT

EXIT

EXIT

GROUND FLOOR

1 FIRE PROTECTION LAYOUT


FP -01 S C A L E NTS

ARCHITECT / ENGINEER: PROJECT TITLE : OWNER : WRITTEN DIMENSIONS ON THESE DRAWINGS SHEET CONTENT : REVISIONS : SHEET NO. :
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTORS SHALL VERIFY AND

PROPOSED BUNGALOW RESPONSIBLE FOR ALL DIMENSIONS AND


CONDITIONS ON THE JOB. THE DESIGNER MUST

FP-01
BE NOTIFIED IMMEDIATELY OF ANY VARIATIONS
FROM THE DIMENSIONS AND CONDITIONS SHOWN

REG. NO. VALIDITY TIN NO. RESIDENTIAL NICOLAI BRYAN T. CARINGAL BY THESE DRAWINGS.
AS SHOWN
ANY DISCREPANCY ON ALL DRAWINGS AND
SPECIFICATIONS SHALL BE SUBJECT FOR
LOCATION: VERIFICATION.
PTR NO. PLACE ISS. DATE ISS. MONSERRAT BRGY. YUKOS NAGCARLAN, LAGUNA