ELECTRICAL SYMBOLS : GENERAL NOTES :

OVERHEAD SERVICE ENTRANCE: 230 V,


2
2-36 WATTS, 230 VOLTS, 60Hz, FLUORESCENT LIGHTING FIXTURE, 1Ø, 2W, 60Hz., A.C. WITH 32mmØ TYPE "F"
BOX TYPE CONDULET, WEATHERHEAD

1
1-30 WATTS, 230 VOLTS, 60Hz, FLUORESCENT LIGHTING FIXTURE,
BOX TYPE 2 - 14mm² THWN + 1-8.0mm²
"DP" THW (G) in 32mmØ RSC
WF WALL FAN, 65 WATTS, 230V, 60Hz

S FC WALL FAN CONTROL SWITCH

S SINGLE POLE WALL SWITCH M 8.0mm² THW GROUND WIRE


in 15mmØ C - CLAMPED TO
S² 2 SINGLE POLE WALL SWITCHES IN ONE SWITCH PLATE COPPER-CLAD GROUNDING
ROD
S ³W THREE WAY SWITCH

DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE, 15A, 250VOLTS


"WP" DENOTES WEATHERPROOF OUTLET
1800 mm

GROUND FLOOR LEVEL

3100 mm (MIN.)
CONCEALED OR EMBEDDED CONDUIT RUN
FINISHED GRADE LEVEL
UNDERGROUND OR UNDERFLOOR CONDUIT RUN
1800 mm

GROUNDING SYSTEM
CIRCUIT HOMERUN
16mmØ X 2400mm LENGTH
BUILDING LINE

DISTRIBUTION PANELBOARD COPPERCLAD GROUNDING


ROD
M ELECTRIC SERVICE METER

ELECTRIC SERVICE ENTRANCE

PUSH BUTTON, 10A, 230 VOLTS


1500mm ABOVE FINISHED GRADE LINE ELECTRICAL RISER DIAGRAM
B VIBRATING BELL OUTLET, 230mm DIAMETER, 230V, 60Hz
TO BE INSTALLED @ 300mm BELOW CEILING LINE

GROUNDING SYSTEM

SCHEDULE OF LOADS AND COMPUTATIONS :


DISTRIBUTION PANELBOARD " DP "

SCHEDULE OF LIGHTING FIXTURES AND LAMPS : BRANCH CKT. BREAKER SIZE OF HOMERUN
CKT. VA PER
LOAD DESCRIPTION VOLTS
NO. CKT. ( WIRES IN CONDUIT )
INSTALLATION/ AF P AT
SYMBOLS D E S C R I P T I O N
MOUNTING
1 LIGHT OUTLETS 1320 230 50 2 15 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) in 20mmØ PVC

ONE (1)-36W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE SURFACED CEILING
1 2 LIGHT OUTLETS 1440 230 50 2 15 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) in 20mmØ PVC
MOUNTED
3 LIGHT OUTLETS 1440 230 50 2 15 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) in 20mmØ PVC
SURFACED CEILING
2 TWO (2)-36W, 230V, 60Hz AC, FLUORESCENT LIGHTING FIXTURE , BOX TYPE
MOUNTED 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) in 20mmØ PVC
4 WALL FANS 1000 230 50 2 20
NOTE: ALL FLUORESCENT LIGHTING FIXTURES SHALL BE EQUIPPED WITH A HIGH POWER FACTOR, PRE-HEAT 5 CONVENIENCE OUTLETS 980 230 50 2 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) in 20mmØ PVC
WITH STARTER AND THERMALLY PROTECTED BALLAST, COMPLETE WITH ALL NECESSARY ACCESSORIES,
WIRED AND READY FOR USE. 6 CONVENIENCE OUTLETS 980 230 50 2 20 2 - 3.5mm² THHN + 1 - 3.5mm² THHN (G) in 20mmØ PVC

7 SPARE 1500 230 50 2 30

8 SPARE 1500 230 50 2 30

TOTAL 12160 MACB : 100AF, 2P, 240V, 60AT, 18kAIC

12160 (0.85) = 44.94 AMPERES


I L @ 85% D.F. =
230 USE : 2 - 14mm² THW + 1 - 8.0mm² THW (G) in 32mmØ RSC

VARIOUS DPWH
(SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET) PROPOSED PROJECTS ELECTRICAL SYMBOLS, GENERAL NOTES, BOD
SCHEDULE OF LIGHTING FIXTURES AND LAMPS, 16
NOTE : STANDARD ONE-STOREY SCHEDULE OF LOADS AND COMPUTATION, EE-2
GILBERTO S. REYES RAUL C. ASIS ROGELIO L. SINGSON 16
SCHOOL BUILDING ELECTRICAL RISER DIAGRAM
OIC, BUILDING DIVISION DIRECTOR IV, BOD UNDERSECRETARY SECRETARY
( 5-CLASSROOM )