Runaway reaction

Validating a less overestimating vent sizing method


Luc VECHOT1, Jean Pierre BIGOT1, Marc KAZMIERCZAK2 and Patricia VICOT2

(1) Centre SPIN, École nationale supérieure des mines de Saint-Étienne, 158 cours Fauriel, 42100 SAINT-
ETIENNE, France, (2) Direction de la Certification, Institut national de l'environnement industriel et des risques
(INERIS), Parc Alata, BP2, 60550 VERNEUIL EN HALATTE, France

Abstract

Simplifying assumptions used in DIERS classical vent sizing methods for gassy systems (mainly
conservation of the initial reactive mass and homogeneous vessel venting) can lead to unrealistically large vent
areas. H. Fauske (2000) proposed to use the same vent area as for pure gas flow venting. It thus leads to a much
smaller vent area. This paper deals about our understanding of Fauske's method bases by introducing the
“balance idea”: when changing from one phase to two-phase venting, decrease of mass inventory in the reactor
could balance venting velocity decrease. Theoretical testing of this idea allowed us to identify types of systems
for which this approach could potentially be not conservative. One is when the reaction kinetics are already rapid
at vent opening and there is therefore not much time for mass to vent before turn-around. Another is when high
quality vent flow occurs (gas with small fraction of liquid) so that vented mass is relatively small, vent flow
velocity at vent being however severely decreased compared to pure gas velocity.

Keywords : vent sizing method ; gassy reaction ; runaway reaction ; gas venting flow

I. Introduction vented mass loss and the venting volume flow rate
decrease into account. The calculation allowed us to
Vent sizing methods were based for a long identify types of systems for which this approach
time on the assumption of one-phase venting could potentially be non conservative.
(vapor/gas). Thanks to the DIERS (Design Institute
for Emergency System Relief), these methods II. Basis of vent sizing for gassy
evolved to the use of simple analytical models (and systems; origin of oversizing
complex computer codes) which take the
occurrence of two-phase flow into account (Leung, The vent sizing method for gassy systems is
Fauske 1987). These methods use data obtained based on two balances: total mass balance and gas
from adiabatic calorimetry. mass balance (Leung 1995).
Nevertheless, because of simplifying assumptions
(mainly conservation of the initial reactive mass dm
= −W = −GA Equation 1
and homogeneous vessel venting), DIERS methods dt
can lead to unrealistically large vent areas. This is
especially the case for untempered systems (gas- dm g •
generating and hybrid systems, peroxide = m m g − Wx i Equation 2
decomposition for example). dt
From large scale experiments, Fauske (2000) Safe vent size is obtained if the pressure rise can be
proposed to use the same vent area as for pure gas stopped when the gas generation rate is maximum.
flow venting. It thus leads to a much smaller vent This leads to consider a pressure rise rate equal to
area. zero. This condition is often called the turn-around :
The objective of this paper is twofold. The first is to
propose our understanding of Fauske's method dP
=0 Equation 3
bases : when changing from one-phase to two- dt
phase venting, decrease of mass inventory in the
reactor could balance the venting velocity decrease. By assuming ideal gas and constant liquid specific
The second objective is to verify whether this volume, recombining equations 1 to 3 leads to the
balance phenomenon can always apply or not. We following expression for the vent area A2ϕ:
tested this approach with a gassy system example
by a computer simulation, which takes both the

1
• v g m g  dT  III. Fauske’s method and balance idea
W 2ϕ v i 2ϕ = A2ϕ (G c v i )2ϕ = v g m m g +  
T  dt 
For gassy systems, Fauske (2000) simply proposed
Equation 4 to install the same vent area as for pure gas flow
Where v i = x i v g + (1 − x i )v l (Agas). Equation 4 neglecting vented gas mass then
becomes:
xi : vent flow quality (gas mass fraction) at inlet
condition  1  • 
vg : gas specific volume in the reactor. Agas =    m0 m g  Equation 7
 Gc gas  
All terms in equation 4 have to be evaluated at  
turn-around. So this equation means that at turn- He verified from large scale data (33 to 2000 liters)
around the volumetric discharge rate is equal to the about peroxide systems (3,5,5-Trimethyl Hexanoyl
sum of: Peroxide, Neat Dicumyl peroxide and t-Butyl
- volumetric gas generation rate Peroxy Benzoate) that this area is safe (Figure 1).
- volumetric expansion rate due to thermal
dilatation. We will subsequently neglect this
term as is generally done.
Equation 4 contains three factors which are not
known. Gc, vi and m at turn-around. In order to
allow for vent sizing even when these important
data are lacking, DIERS methods make the
following safe assumptions:
- All the initial mass is still present in the vessel
at turn-around (Leung, Fauske, 1987)
- Homogeneous two-phase flow with
homogeneous vessel contents occurs at turn-
around (Leung, 1995) or even Bernoulli flow
occurs when void fraction is low (Leung,
Fauske, 1987). Figure 1 : Large scale runaway peroxide
The DIERS vent sizing formula resulting from the decomposition data ; comparison with gas vent
above assumptions is given by: area after Fauske (2000)
1 • Fauske also pointed out (as indicated by
ADIERS = v g m 0 mg calorimetric test) that significant material losses
(Gc vi )HEM hom occurred before reaching turn-around.
Equation 5 So the large scale experiments show that even if
two-phase flow obviously occurs, vent design for
Unfortunately this equation can lead to vent
gas only flow is safe. This method can seem at a
oversizing. For example, in the case of peroxide
first sight non conservative compared to the
decomposition runaway reaction, vent area obtained
classical DIERS method (Equation 5). But
from this vent sizing method can be overestimated
experiments show its efficiency. We tried to give a
by one order of magnitude (Fauske 2000).
theoretical explanation to this idea.
Moreover, experience showed that smaller vent size
If one phase flow actually occurs this method is
can provide good protection against runaway
right. Two phenomena occur concurrently when
reaction.
changing from one-phase flow to two-phase flow:
- vent flow velocity decreases, which tends to
ADIERS  (Gc v i )2ϕ   m0 

=  ask for a vent area increase.
A2ϕ  (Gc vi ) HEM hom  m  - mass vented at turn-around increases, which
 
tends to ask for a vent area decrease.
Equation 6
Validity of Fauske’s proposal (use gas area even
Equation 6 shows that the possible ways for solving when two-phase flow occurs) could result from a
this problem are: a better assessment of (Gc vi )2ϕ balance between these two phenomena. That’s what
we called the “balance idea”. This idea is
and the remaining mass at turn-around m. In fact, mathematically expressed by the vent area needed
these data are not experimentally available. Fauske when two-phase flow occurs being less or equal to
(2000) proposed an interesting way to solve this the vent necessary when one phase flow occurs:
oversizing problem.
A2ϕ ≤ Agas Equation 8

2
Combining equation 4, 8 and 9 the condition for IV.1 Two-phase flow model
balance idea to be correct is the following:

 m   (Gc v i )2ϕ 
We are looking at the (Gc vi )2ϕ (Gc vi ) gas
  ≤  Equation 9 ratio. We show in appendix that this ratio can be
 m0   (Gc v i ) gas 
 approximated by the two-phase to gas critical
This condition means that the vent area decrease velocity ratio : u c 2ϕ u cgas .
effect due to mass loss has to be more or equal to Figure 2 shows experimental data for this latter
the vent area increase effect due to the decrease of
the flow velocity when changing from gas to two- ( ) (
ratio. We also assessed the Gc v i 2ϕ Gc v i gas )
phase flow.
ratio versus αi , using both Leung’s ω-method
(1990) and Tangren et al. method (1949).
IV. Test of balance idea
The shape of the curve in Figure 3 is in accordance
with the experimental data (Figure 2). This justifies
Our aim is now to verify if equation 9 is
the subsequent use of these models.
always valid. Unfortunately not enough large scale
data are available in order to demonstrate it. This
IV.2 Graphical representation of balance
lead us to use simple models in order to identify
idea
cases where balance idea could potentially not
apply. This approach thus allow for qualitative only
study. Conditions of validity
We took gassy reaction data from Etchells et al. As explained in III. , validity of balance idea
(1998). They are described in Table 1. needs equation 9 to be verified for a vessel
equipped with a vent sized for gas flow. Figure 3
can be read as the graphical representation of this
condition.
For a given two-phase flow void fraction at turn-
around αi , m m0 ratio has to lie below the
(Gc vi )2ϕ (Gc vi ) gas curve. On the contrary, if
m m0 ratio lies above the curve, the vented mass is
not sufficient to balance the vent flow velocity
decrease. So vent area assessed by one phase flow
calculation would be undersized.

Effect of mass loss on the balance


Figure 3 also represents two extreme cases: 20%
and 80% of remaining mass in the large scale vessel
at turn-around.
For the unfavourable value of 80%, the curves
show that even a little volume fraction of liquid in
the evacuated flow at turn-around (3% for example)
would lead to balance idea being not verified.
Balance would only occur if void fraction is more
Figure 2 : Two-phase to gas critical velocity ratio than 98%. So sizing the vent by assuming one
vs void fraction (Semenov and Kosterin, 1964) phase flow could be unsafe.

Vessel volume 3.5 m3 Vent opening pressure 14 bars


Vessel
Initial mass inventory 2500 kg Maximum allowable pressure 16 bars
Gas phase volume 3.8 l Maximum pressure rise rate 2263 N/m².s
Sample mass 44.8 g Maximum temperature rise rate 6.95 K/s
Calorimeter
Maximum reactant contents
519 K
temperature in the test cell
Table 1 : Gassy reaction data ; example from Etchells et al. (1998)

3
1

0,9 omega method Tangren et al method

0,8
m/m0 = 80%
0,7  m   (G c v i )2ϕ 

(Gcvi )2ϕ / (Gcvi )gas
  ≤
0,6  m0   (Gc v i ) gas 

0,5

0,4 m/m0 here : balance idea is not OK


0,3

0,2
m/m0 = 20%
0,1
m/m0 here : balance idea is OK
0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
αi

Figure 3 : Ratio (Gvi )2ϕ (Gvi )gas as a function of inlet void fraction by ω-method and Tangren et al
method ; Conditions of validity of the balance idea

On the opposite the 20% remaining mass case primary importance for the balance idea to be
(considered as the favourable case) would balance verified or not.
the fluid velocity decrease whatever the inlet void Another way for illustrating this fact is to plot the
fraction at turn-around. So sizing the vent as for one calculated vent area needed when two-phase flow
phase flow would be a safe method. occurs by means of equations 4, 5 and 7.
This simply means that the value of the ratio of
mass remaining at turn-around to initial mass is of

0,009
Eq. 5 : DIERS 2ϕ hom
0,008
Eq.4 with m/m0 = 100%
0,007

0,006
Vent area (m²)

Eq.4 with m/m0 = 80%

0,005

0,004

0,003

0,002 Eq. 7 : All gas venting

0,001
Eq.4 with m/m0 = 20%
0
0 0,1 0,2 0,3 0,4 αi 0,5 0,6 0,7 0,8 0,9 1

Figure 4 : Vent area as a function of the void fraction for a remaining reactant mass of 20, 80 and 100%

4
1

0,9

0,8
(Gcvi )2ϕ / (Gcvi )gas or m/m0

0,7

0,6

0,5

0,4
∆t=60 sec
0,3

0,2
∆t=120 sec
0,1
∆t=90 sec
0
0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1
αi

Figure 5 : Conditions of validity of the balance idea when the remaining mass is calculated

We consider here the value of the remaining mass - α i is constant (no change in the vent flow gas
as a parameter. (Gc vi )2ϕ is calculated versus inlet volume fraction) during relief.
void fraction by Leung’s ω-method (1990). Figure Let’s express the remaining mass in a vessel
4 shows the influence of the void fraction on the equipped with a vent sized for gas flow ( Agas ):
vent area for remaining reactant masses of 20%,
80% and 100%. m = m0 − Gc Agas ∆t Equation 10
For the 20 % remaining mass case, we can point
that : where ∆t is the delay between vent opening and
• balance idea is valid: gas vent size seems to be turn-around.
a safe one.
• DIERS classical vent sizing method (equation Results
5) is overly conservative.
For the 80% and 100% remaining mass cases, we Figure 5 presents again the
can observe that : (Gc vi )2ϕ (Gc vi )gas ratio calculated by ω-method
• balance idea is not valid: gas vent size seems to versus inlet void fraction. The m m0 ratio,
be unsafe.
• use of DIERS classical vent sizing calculation calculated thanks to equation 10, is also represented
would have been a safer choice. versus inlet void fraction for three values of ∆t :
60, 90 and 120 seconds.
IV.3 Link between m and αi. We can make the following observations:
- For ∆t = 60 seconds, if inlet void fraction in
Up to now, we supposed that vent void fraction the venting flow is larger than 43%, then mass
and mass loss at turn-around are independent loss is not sufficient for balance idea to be
parameters. It is not completely true: the higher the verified.
inlet mean void fraction, the less the mass loss. This - For ∆t = 120 seconds, even inlet void fraction
link can only be calculated if more assumptions are as high as 87% will allow balance idea to be
made. verified. But very high inlet void fractions
(88%<αi<98%) could potentially give rise to
Vented mass model unsafe conditions.
We will now assume that: The kinetics of a gassy reaction are generally
supposed to be the same whether the reactor is
- Gc is constant during relief (calculated by
vented or not. Delay between vent opening and
HEM method at vent opening conditions). turn-around, ∆t is only a function of vent opening
pressure.

5
As a conclusion, it’s possible to identify two cases vc : Specific volume of the vent flow at critical
for which the balance idea could potentially not conditions (m3/kg)
apply: vg : Gas specific volume at vessel conditions
- When the reaction kinetics are already rapid at (m3/kg).
vent opening and there is not much time for vi : Specific volume at inlet conditions (m3/kg)
mass to vent before turn-around. vl : Liquid specific volume (m3/kg).
- When high void fraction vent flow occurs (gas W: Vented mass flow (kg/s)
with small fraction of liquid) so that vented xi : Vent flow gas mass fraction at inlet
mass is relatively small, the vent velocity being condition
however severely decreased. αi : Void fraction at inlet conditions

Discussion about assumptions ∆t : Delay between vent opening and turn-


around (s)
Our assumptions (constant Gc and α i ) can be Subscripts
not realistic, even if they are favourable to balance c: Critical conditions
idea because mass loss is probably overestimated gas : Gas flow
compared to what actually happens in the reactor: HEM : Homogeneous equilibrium model
• actual pressure will decrease when opening the hom : Homogeneous vessel contents
vent and so that the critical mass flux 0: Initial conditions
• actual void fraction will probably be not 2ϕ : Two-phase flow
constant during ∆t . It depends on several REFERENCES:
factors such as the vent opening pressure, the
vent area, etc. Etchells J., Wilday J., “Workbook for chemical
These assumptions however allowed us to reactor relief system sizing”, HSE Books, 1998
qualitatively identify cases for which the balance Fauske H.K., “Properly size vents for non reactive
idea could potentially be unsafe. and reactive chemicals”, Chemical Engineering
Progress, pp 17-29, 2000
V. Conclusion
Leung J.C., Fauske H.K., “Runaway system
characterization and vent sizing based on DIERS
In this work we exposed our understanding of
methodology”, Plant/operation progress, Vol.6,
Fauske's method bases by introducing the “balance
n°2, pp. 77-83, 1987
idea”: when changing from one-phase to two-phase
venting, decrease of mass inventory in the reactor Leung J.C., “A generalized correlation for two-
could balance the venting velocity decrease. phase nonflashing homogeneous choked flow”,
Testing of this idea using simple models allowed us Journal of heat transfer, Vol.112, pp. 528-530,
to identify conditions for which this approach could 1990
potentially be not conservative. One is when the
Leung J.C., “Simplified Vent Sizing Methods
reaction kinetics are already rapid at vent opening
Incorporating Two-Phase Flow” International
and there is not much time for mass to vent before
symposium on runaway reactions and pressure
turn-around. Another is when high quality vent
relief design, 200-236, AICHE, 1995
flow occurs (gas with small fraction of liquid) so
that vented mass is relatively small, the venting Semenov N.I., Kosterin S.I., “Results of studying
velocity being however severely decreased. the speed of sound in moving gas-liquid
We still have to verify if balance idea remains safe systems”, Teploenergetika, Vol.11, n°6, 1964
even under such circumstances. This will be our
next experimental investigations. Tangren & al., “Compressibility effects in two-
phase flow”, Journal of applied physics, Vol.20,
n°7, pp 637-645, 1949
Nomenclature
A: Vent area (m²)
Gc : Critical vent mass flux (kg/m².s)
m: Remaining mass in the vessel at turn- Appendix : u c 2ϕ u cgas as an approximation for
around (kg) (Gc vi )2ϕ (Gc vi )gas
mg : Gas mass (kg)
• From definition of Gc :
mg : Specific gas generation rate (kggas/kg.s)
(Gc vi )2ϕ u c 2ϕ (vi vc )2ϕ
P: Pressure in the vessel (Pa) =
T: Temperature in the vessel (K) (Gc vi )gas u cgas (vi vc )gas
uc : Critical venting velocity (m/s)
Except for very low vent quality, we can write:

6
v g 2ϕ i (T P )2ϕ i
(vi vc )2ϕ ≈ ≈
v g 2ϕ c (T P )2ϕ c
T  T 
The inlet critical ratio     is not so
 P i  P c
different, whether the flow is 2ϕ or gas.
The maximum discrepancy comes from the
pressure ratio ( η ≈ 0.5 for gas ; 0.5 < η < 1 for
2ϕ-flow).
u c 2ϕ u cgas can not differ of (Gc vi )2ϕ (Gc vi ) gas
by more than a factor of two.