Paper 52
Paper 52
Case Study
Abstract— The accurate transmission line parameters are Reinforced (ACSR) according to [4] shows an increase of
important in various power system analyses, while potential around 20% for a temperature rise from 25oC to 75oC.
uncertainty in their values affects the accuracy of control center
applications and compromises the selectivity of the protection Several methods have been recently developed for the
systems. The transmission line parameters are usually calculated calculation of the transmission line parameters, which can be
based on manufacturers data, ignoring environmental factors classified into offline and online methods. In [5] and [6],
(e.g. ambient temperature) which affect the accuracy of the methods for calculating offline the line parameters are
calculated parameters. Thus, the systematic refinement of the described. These methods use the geometry of the tower, the
line parameters can be very beneficial for the situational geometry and type of the conductor, and constant ambient
awareness of the power system operators. In this paper, the conditions. In addition, according to [7], the offline methods
calculation of the positive sequence parameters of a transmission based on lumped parameter model are not accurate for long-
line of the Cyprus power system through real synchronized distance transmission lines. Since the environmental
phasor measurements is presented. The seasonal variation of the conditions vary throughout the year, the line parameters that
transmission line parameters is analyzed by calculating the are calculated through the offline methods might cause serious
parameters during different periods of the year, while the impact discrepancies between the actual and the estimated value of
of the instrument transformers static error is demonstrated in the line parameters.
this real case study.
Based on the aforementioned facts, the development of
Keywords—Instrument transformers, measurement estimation methods, that can obtain line parameters in real-
uncertainty, synchronized phasor measurements, transmission time, is an imperative need. In this attempt, the deployment of
line parameters. synchronized measurement devices, such as Phasor
Measurement Units (PMUs), contributes to the correction of
I. INTRODUCTION any erroneous parameters since PMUs can provide
Transmission line parameters, including resistance, synchronized phasor measurements from both ends of the line
reactance, and susceptance, are used in several critical control [8]. Several methods have been proposed in the literature for
center applications [1]. These parameters are usually taking advantage of online voltage and current measurements
calculated based on the ideal structure of the transmission line, [9]-[14]. The authors in [9] developed a method which uses
ignoring several factors (i.e., weather, soil resistivity, coupling only RMS voltage and power measurements for the estimation
between parallel lines, and joints at the ends of the lines) that of the parameters of a distribution line. Reference [10]
certainly affect the line parameter values. Consequently, any proposed a high accuracy estimation method which calculates
mismatches between the actual and calculated transmission the positive sequence line parameters during normal operation
line parameters directly affect the accuracy of the control by utilizing online voltage and current phasors. This method
center applications, such as the state estimator, power flow detects and removes faulty measurements, minimizes the
analysis and voltage stability analysis. At the same time, the impacts of measurement errors and improves the accuracy of
uncertainty compromises the effectiveness of the protection the estimation. A method for estimating the parameters of a
schemes; for instance, impedance relays require exact long line is proposed in [11]. The method estimates the
knowledge of the line parameters for making a correct parameters by obtaining the ABCD parameters by using
protection zone identification and tripping decision [1], [2]. voltage and current phasors from the two ends of the line.
Reference [12] presents the estimation of the line parameters
It is therefore of great importance to update the using a total least square algorithm. A moving window
transmission line parameters according to the environmental technique is proposed for using voltage, current, active and
conditions, rather than having constant parameters in the reactive power measurements in order to calculate the line
power system models. This is also valid if one considers that parameters of an equivalent pi-model. The line parameters are
the series resistance is dependent on the temperature of the estimated in [13] based on Laplace transform technique by
conductor and typically rises as the conductor temperature utilizing three sets of synchronized voltage and current
increases above a standard temperature (usually at 20oC) [3]. phasors. The authors of [14] proposed a method for estimating
Moreover, series reactance of the Aluminum Conductor Steel the line parameters using phasor measurements provided by
“This work has been supported by the European Union's Horizon 2020 only one PMU. The methodology performs well either for a
research and innovation programme under grant agreement No 739551 single or for multiple lines. However, the magnitude of the
(KIOS CoE) and from the Government of the Republic of Cyprus through measurement noise might affect the performance of the
the Directorate General for European Programmes, Coordination and methodology.
Development.” “This work was also co-funded by the European Regional
Development Fund and the Republic of Cyprus through the Research and
Innovation Foundation (Project: INTEGRATED/0916/0035)”.
-0.50
measurements of Vasilikos power station and Costas Petrou
-1.00
-1.50
substation. It should be noted that the static error of the voltage
-2.00
angle is negligible (as shown in Table I) and was omitted.
More specifically, the synchronized voltage phasor
Time (hours) measurements of each phase from the Vasilikos and Costas
Fig. 3: Calculated resistance with recorded data as they were measured Petrou substation were modified as,
3 567
13.10 = :1 + 9 ) ∠ :8 567 < (12)
Reactance (Ω)
12.95
3 567
12.80 = :1 + 9 ) ∠ :8 567 < (13)
12.65
12.50 where 3 is the modified voltage phasor, 567 and 8 567
are the measured (from PMU) magnitude and angle of the
Time (hours) voltage respectively, and 9 is the static error of the voltage
Fig. 4: Calculated reactance with recorded data as they were measured magnitude. The S and R subscripts refer to sending and
receiving end, respectively.
B. Calculation of line parameters considering PMU
Measurement chain uncertainties In Figs. 6 and 7, the calculated resistance and reactance
including the above static errors are shown, respectively.
Although the procedure for calculating the transmission Based on these two figures, the calculated resistance is very
line parameters through the PMU measurements is simple, the close to the reference value and the deviation from its nominal
quality of the PMU measurements should be always value is minimized considerably. Regarding the reactance of
considered in this procedure. As it is indicated in Fig. 5, the the line, it can be concluded that is not affected by the static
instrument transformers (ITs) and PMU are the two main errors of the voltage transformers as it can be concluded by
components in a PMU measurement chain that might the comparison of Figs. 4 and 7 (calculated reactance before
introduce uncertainties in the PMU measurements. Even and after the consideration of the voltage transformers static
though PMUs can be characterized as high accuracy devices, errors). In this sense, this case study demonstrates through a
the accuracy of their measurements may be low especially real-life example that the voltage transformer static error is
when ITs belong to a low accuracy class [5]. In this sense, the dominant to the calculation of the line resistance and it should
low accuracy of the instrument transformer can deteriorate be always considered to the calculation of the line parameters.
the quality of the PMU measurements and eventually lead to
the calculation of erroneous parameters. 1.30
Resistance (Ω)
1.25
1.20
1.15
1.10
13.20
Reactance (Ω)
resistance, this work was focused on the errors of the voltage 12.30
1.40
variation of the series reactance (Ω) for different weather
1.30
conditions for weekdays and weekends, respectively. Further,
1.20 Figs. 14 and 15 show the variation of the series reactance (Ω)
1.10 for different loading condition in winter and summer,
respectively.
Time (hours)
22 January 19 / Tuesday 22 August 19 / Thursday 12.65
Reactance (Ω)
12.35
Resistance (Ω)
1.40
1.30
1.20 Time (hours)
1.10 22 January 19 / Tuesday 22 August 19 / Thursday
1.00 Fig. 12: Comparison of series reactance between different weather conditions
0.90 for weekdays
12.65
Time (hours)
Reactance (Ω)
1.30
Resistance (Ω)
Time (hours)
1.20
21 January 18 / Sunday 8 July 18 / Sunday
1.10
Fig. 13: Comparison of series reactance between different weather conditions
1.00
for weekends
0.90
12.70
Reactance (Ω)
Time (hours)
22 August 19 / Thursday 8 July 18 / Sunday 12.55
nominal during the day for these cases ranges from 9% to Fig. 15: Comparison of series reactance between different loading conditions
25%. In addition, as shown in Figs. 8 and 9, during the in summer
summer, the value of the series resistance is higher in
The deviation of the calculated series reactance from the depends mainly on the loading conditions and more specific
nominal value during the day, for these cases, ranges between to the current flow of the transmission line.
4% to 6.5%. Based on Figs. 12 and 13, the value of the series
reactance is a bit larger in summer than in winter. Also, as Moreover, it is crucial to include the static error of the
indicated in Figs. 14 and 15, in weekdays around at 2:00-3:00 instrument transformers in the PMU measurements
am, the value of the reactance has a sharp increase for the (especially when the line resistance is calculated). It is
whole year, while this is not the case in the weekends. indicated in this paper that the calculation of the parameters
by using the measurements as they are recorded by the PMUs
However, the value of the reactance is not higher in is compromised. However, the compensation of the static
summer due to the temperature increase but it is dependent on error of the instrument transformers in the PMU
the loading condition of the line, and hence on the current of measurements results in accurate line parameter calculation.
the transmission line (that flows through the line) which is
larger in summer than in winter. Moreover, the current flow in It should be noted that as a part of the future work, the
weekdays increases sharply in the early morning hours, which PMU measurements will be used for the calculation of zero
affects the reactance’s value and as a result shows an increase sequence parameters of the line. This can be done by using
in the corresponding time. PMU measurements from time instants that an asymmetric
disturbance has occurred in the system.
This is verified in Figs. 16 and 17, in which the daily
variation of the reactance is compared to the daily variation of REFERENCES
the current measured by the PMUs. In particular, Fig. 16
[1] Y. Liao and M. Kezunovic, “Online Optimal Transmission Line
shows the reactance and the current on July 8, 2018 (Sunday), Parameter Estimation for Relaying Applications”, IEEE Transactions
and there is no sharp increase during the early morning hours. on Power Delivery, vol. 24, no. 1, pp. 96-102, Jan. 2009.
Further to that, the similarity in the variation of the current and [2] K. Dasgupta and S. A. Soman, “Line parameter estimation using phasor
reactance is obvious. In Fig. 17, the reactance and the current measurements by the total least squares approach,” in Proc. IEEE
on January 22, 2019 is shown. In this day, a sharp increase in Power Energy Soc. General Meeting, pp. 1–5, Jul. 2013.
the value of both reactance and current at around 2:00-3:00 am [3] B. J. Hardy, C. R. Bayliss, “Overhead LineConductor and Technical
can be observed, while their shape is quite similar. Moreover, Specifications”, Transmission and Distribution Electrical
Engineering, Great Britain. 3rd ed. 2007, ch. 18, sec. 18.4, pp. 641.
by comparing the current in winter and summer it is obvious
that the current has higher values in summer ranging between [4] W. Hubbi, Y. Wang and W. Zhang, "Effects of inductance variations
due to temperature on load-flow results," 2013 North American Power
225 and 335 Amperes, while in winter the current ranges Symposium (NAPS), Manhattan, KS, pp. 1-4, 2013.
between 140 and 240 amperes. [5] J. Grainger and W. Stevenson, Power System Analysis. New York:
McGraw-Hill, 1994.
12.65 350
Reactance (Ω)
12.60 315
computer programs,” IEEE Transactions on Power Apparatus System,
12.55 280 vol. PAS- 104, no. 4, pp. 366-370, Feb. 1985.
12.50 245 [7] G. Song, X. Chu, S. Gao, X. Kang, Z. Jiao, and J. Suonan, “Novel
12.45 210
distance protection based on distributed parameter model for long-