2
Pressure Dependent Valve Sizing and Operation
GPM
Pressure Dependent Flow Cv
Coefficient-Valve Sizing P
• 1 Cv = 1 gallon of 60 DegF water passing through a
fully open control valve with a pressure drop of 1 psi.
• Sizing is typically done using a PD of 3-5 PSI
• Manual balancing can not maintain a constant PD and
causes overflow and low delta T.
3
Pressure Dependent Valve Authority
Should =.4 or greater
Pressure Differential Sensor
10 psi
4 A=4/10=0.40
p = 4 psi p = 2 psi
p = 4 psi
Flow/Heat output %
gpm = 0 to 100
A=4/20=0.20
20 psi
p = 4 psi p = 12 psi
p = 4 psi
gpm = 0 to 100
2
30 psi
p = 4 psi p = 22 psi
p = 4 psi
gpm = 0 to 100 A=4/30=0.13
1
40 psi
p = 4 psi p = 4 psi p = 32 psi
gpm = 0 to 100
VFD-Pump Overflow
Overflow
Bypass Line
A=4/40=0.10
Chiller 1 Signal
Chiller 2 Accumulative Waste
4
Pressure Independent Control Valve
Mechanically Regulated
Operational theory-VENTURI = DYNAMIC BALANCING
Replaces control valve and balance valve
Water passes through
regulator, disc, and ball
Pressure Drops
Ports sense
pressure drop and
transfer it below
regulator
Low pressure pulls regulator
down, against the spring
force
5
Electronic Pressure Independent Valve
Flow Meter (True Flow) Regulating
Flow Sensor
Actuator
Valve
6
Electronic Pressure Independent Valve
Delta T Management and BTU Meter
7
Typical Chilled Water Design
Tons 24
GPM
T
8
Typical Chilled Water System
42˚ 54˚
Chiller
VFD Pump
Part Load Condition (45%) 200 tons
Chiller #1 Load = 90% 90% Load
Chiller #2 Load = 0%
Loop Flow = 360 GPM
Chiller ΔT = 12˚F VFD Pump Chiller
200 tons
9
Typical Chilled Water System
Water ∆T decreases by
< 2 degrees F. = flow 180 Ton Load (45%)
CHWS CHWR
increases by 15%
42˚ 52.4˚
Chiller
VFD Pump
Part Load Condition (45%) 200 tons
Chiller #1 Load = 45% 45% Load
Chiller #2 Load = 45%
Loop Flow = 414 GPM
Chiller ΔT = 10.4˚F VFD Pump
Chiller
200 tons
45% Load
Pump Affinity Law =
Pump HP = (414/360)3 = 52% increase! 414 GPM Loop Flow
10
Design
Causes of Low Delta T
11
Hayden Library Case Study, 2010/2011
Correction CHW Low Delta T
12
Hayden Library Case Study
• Over pumping
13
Independent Study
MIT Chilled Water System
Peak Load 26,000 Tons
15
Design
Not the Solution
Deny or Choke Valve, will not allow a coil to run
as designed. This application will negate proper de-
humidification and comfort.
16
Case Study Setup
• 5 Energy Valves
• Chilled Water is designed to run through a coil at a designed
temperature drop to supply air conditioned cooling air and to
de-humidify. i.e. Water delta T=12 degrees F.
17
Energy Valve
Hayden Library
Actuator
Magnetic
Flow sensor
Temperature Sensors
Valve (for supply & return water)
18
New Definitions
• Waste Zone
– Range beyond the “Power Saturation Point.”
19
Power Saturation & Waste Zone
20
Hours Delta T Manager Active
Summer 2011
21
Library Whole Building Results
22
Case Study Findings
23
Hayden Library Saving Calculations
24
Energy Valve
Technical Summary
• Maximize coil performance
• Monitor and calculate savings at the coil level
• Documented commissioning of coil
• 13 month data archive
• Delta T management function
25
Energy Valve Operation
26
Pressure Independent and Delta T Manager
Pump Savings in Large Tech Company in NC
♦ Pressure Independent
♦ Pressure Dependent
27
Knowledge is Power
Process Order
1. Benchmarking
2. Data Acquisition
3. Analysis
4. Optimization
28
Data Analysis
Analyzing the Power Curve
`
29
Thank You