Basic wind speed Vb = 47 m/s - Fig 1 or Annex A, IS 875-3, 2015 Class of the structure = i - Table 1, IS 875-3, 2015 All general buildings and structures Mean Probable Design Life in Years = 50 - Table 1, IS 875-3, 2015 Risk Coefficient k1 = 1 - Table 1, IS 875-3, 2015 Terrain Category = Terrain Category 1 - Cl. 6.3.2, IS 875-3, 2015 Terrain & Height Multiplier k2 = 1.05 Topography factor k3 = 1 - Cl. 6.3.3, IS 875-3, 2015 Does the site falls in cyclonic region = No - Cl. 6.3.4, IS 875-3, 2015 (60 Km from all the east cost region and Gujarat cost) Imporatnace of the structure (for k4) = Industrial structures Importance Factor for Cyclonic Region. k4 = 1 - Cl. 6.3.4, IS 875-3, 2015 Design wind speed Vz = k1 k2 k3 k4 Vb - Cl. 6.3, IS 875-3, 2015 Vz = 49.35 m/s Wind directionality factor Kd = 0.9 - Cl. 7.2.1, IS 875-3, 2015 Trubutory Area = 42*1.5 = 63 m2 Area averaging factor K a = 0.85 - Cl. 7.2.2, IS 875-3, 2015 Combination factor Kc = 1 Kd Ka Kc = 0.765 Design wind pressure pd = Kd Ka Kc 0.6 Vz2 = 1.118 kN/m2
Hourly mean wind speed factor, k2,i = 𝑧 0.0706
0.1423 𝑙𝑛 𝑧0,𝑖 𝑧0.𝑖 z0,i = 0.002 - Cl. 6.3.2, IS 875-3, 2015 k2,i = 0.7815 Design hourly mean wind speed, V̅z,d = k1 k2,i k3 k4 Vb - Cl. 6.4, IS 875-3, 2015 = 36.733 m/s Diameter to decide the criticazl flow = 6/ V̅d = 0.1633 m
Wind Load on Open Frames - X Direction
Solidity ratio of the frame Φ = 0.23
For ciruclar profiles Φe = 0.088 - Fig 6, IS 875-3, 2015 Frame spacing ratio = 0.8
Flat Members Circular Members
Force coefficient 1.77 Wind Critical Flow D V̅ d < 6 m2/s Sheilding factor 0.83 Force coefficient 1.20 Pressure first frame 1.979 kN/m2 Sheilding factor 0.96 Pressure other frame 1.642 kN/m2 Pressure first frame 1.341 kN/m2 Pressure other frame 1.294 kN/m2 Forces on individual members Size / Member force in first Member force in other S. No Profile Type Dia frame, kN/m frames, kN/m 1 0.2 Flat 0.396 0.328
For ciruclar profiles Φe = 0.2 - Fig 6, IS 875-3, 2015 Frame spacing ratio = 1
Flat Members Circular Members
Force coefficient 1.80 Wind Critical Flow D V̅ d < 6 m2/s Sheilding factor 0.75 Force coefficient 1.15 Pressure - first frame 2.012 kN/m2 Sheilding factor 0.90 2 Pressure other frame 1.509 kN/m Pressure - first frame 1.286 kN/m2 Pressure other frame 1.157 kN/m2 Forces on individual members Size / Member force in first Member force in other S. No Profile Type Dia frame, kN/m frames, kN/m 1 0.2 Flat 0.402 0.302 2 0.1 Circular 0.129 0.116 3 Flat 0.000 0.000 4 Flat 0.000 0.000
Wind load on equipment or utlities
Height, Span, No of Supports, Force - S.No Description Cf m m Effective Span factor KN,m 1 Cable Tray 1.2 0.15 1.15 1 0.231 2 Potable water pipe 1.2 1 0.000 3 Fire fighting pipe 1.2 1 0.000 4 Conceyor belt 1.1 1 0.000