OTDR Report (1550 nm (9 µm))

General Information
Filename: Fiber1_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:32:06 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.1
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2299 km Average loss: 0.196 dB/km Injection level: 12.7 dB
Span loss: 0.830 dB Average splice loss: ---
Span ORL: 27.96 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.211 dB/km A-B average loss: 3.441 dB/km
a 1.9999 12.228 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.560 dB
A 3.9999 11.855 A-B ORL: 47.31 dB Maximum reflectance: -54.5 dB
B 6.0001 4.972
b 8.0001 6.822

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -28.6 0.000
Section 4.2299 0.830 0.196 0.830
Reflective 2 4.2299 --- -54.4 0.830

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber1_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:32:13 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.1
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2298 km Average loss: 0.331 dB/km Injection level: 14.2 dB
Span loss: 1.400 dB Average splice loss: ---
Span ORL: 27.53 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.378 dB/km A-B average loss: 6.427 dB/km
a 1.9999 13.484 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.685 dB
A 3.9999 12.855 A-B ORL: 45.34 dB Maximum reflectance: -54.0 dB
B 6.0001 0.000
b 8.0001 6.444

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.8 0.000
Section 4.2298 1.400 0.331 1.400
Reflective 2 4.2298 --- -54.0 1.400

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber2_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:39:05 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.2
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2308 km Average loss: 0.195 dB/km Injection level: 12.6 dB
Span loss: 0.826 dB Average splice loss: ---
Span ORL: 26.94 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.028 dB/km A-B average loss: 5.977 dB/km
a 1.9999 12.134 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.600 dB
A 3.9999 11.955 A-B ORL: 47.46 dB Maximum reflectance: -53.8 dB
B 6.0001 0.000
b 8.0001 5.470

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.4 0.000
Section 4.2308 0.826 0.195 0.826
Reflective 2 4.2308 --- -53.8 0.826

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber2_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:39:13 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.2
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2307 km Average loss: 0.338 dB/km Injection level: 14.2 dB
Span loss: 1.428 dB Average splice loss: ---
Span ORL: 27.26 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.122 dB/km A-B average loss: 3.120 dB/km
a 1.9999 13.472 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.478 dB
A 3.9999 13.052 A-B ORL: 45.83 dB Maximum reflectance: -54.2 dB
B 6.0001 6.811
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.4 0.000
Section 4.2307 1.428 0.338 1.428
Reflective 2 4.2307 --- -54.2 1.428

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber3_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:39:52 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.3
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2305 km Average loss: 0.198 dB/km Injection level: 12.7 dB
Span loss: 0.839 dB Average splice loss: ---
Span ORL: 27.03 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.893 dB/km A-B average loss: 5.870 dB/km
a 1.9999 12.256 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.607 dB
A 3.9999 11.742 A-B ORL: 45.65 dB Maximum reflectance: -49.6 dB
B 6.0001 0.000
b 8.0001 4.712

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.5 0.000
Section 4.2305 0.839 0.198 0.839
Reflective 2 4.2305 --- -49.6 0.839

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber3_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:39:59 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.3
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2304 km Average loss: 0.336 dB/km Injection level: 14.1 dB
Span loss: 1.421 dB Average splice loss: ---
Span ORL: 27.22 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.333 dB/km A-B average loss: 5.774 dB/km
a 1.9999 13.502 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.669 dB
A 3.9999 12.738 A-B ORL: 44.85 dB Maximum reflectance: -51.9 dB
B 6.0001 1.188
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.4 0.000
Section 4.2304 1.421 0.336 1.421
Reflective 2 4.2304 --- -51.9 1.421

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber4_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:40:47 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.4
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2305 km Average loss: 0.197 dB/km Injection level: 12.6 dB
Span loss: 0.833 dB Average splice loss: ---
Span ORL: 26.92 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.079 dB/km A-B average loss: 5.875 dB/km
a 1.9999 12.064 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.675 dB
A 3.9999 11.751 A-B ORL: 45.09 dB Maximum reflectance: -48.1 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.4 0.000
Section 4.2305 0.833 0.197 0.833
Reflective 2 4.2305 --- -48.1 0.833

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber4_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:40:54 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.4
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2304 km Average loss: 0.335 dB/km Injection level: 14.1 dB
Span loss: 1.418 dB Average splice loss: ---
Span ORL: 27.13 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.574 dB/km A-B average loss: 4.293 dB/km
a 1.9999 13.456 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.465 dB
A 3.9999 12.618 A-B ORL: 45.15 dB Maximum reflectance: -54.5 dB
B 6.0001 4.030
b 8.0001 2.490

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.4 0.000
Section 4.2304 1.418 0.335 1.418
Reflective 2 4.2304 --- -54.5 1.418

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber5_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:41:25 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.5
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2315 km Average loss: 0.196 dB/km Injection level: 12.7 dB
Span loss: 0.828 dB Average splice loss: ---
Span ORL: 27.21 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.781 dB/km A-B average loss: 2.724 dB/km
a 1.9999 12.325 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.478 dB
A 3.9999 11.832 A-B ORL: 48.03 dB Maximum reflectance: -66.8 dB
B 6.0001 6.383
b 8.0001 3.552

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.7 0.000
Section 4.2315 0.828 0.196 0.828
Reflective 2 4.2315 --- -66.8 0.828

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber5_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:41:32 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.5
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2311 km Average loss: 0.339 dB/km Injection level: 14.2 dB
Span loss: 1.436 dB Average splice loss: ---
Span ORL: 27.33 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.594 dB/km A-B average loss: 3.975 dB/km
a 1.9999 13.491 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.042 dB
A 3.9999 12.900 A-B ORL: 45.92 dB Maximum reflectance: -61.3 dB
B 6.0001 4.950
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.4 0.000
Section 4.2311 1.436 0.339 1.436
Reflective 2 4.2311 --- -61.3 1.436

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber6_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:42:13 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.6
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2312 km Average loss: 0.203 dB/km Injection level: 12.6 dB
Span loss: 0.859 dB Average splice loss: ---
Span ORL: 26.91 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.163 dB/km A-B average loss: 3.649 dB/km
a 1.9999 12.353 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.489 dB
A 3.9999 11.730 A-B ORL: 44.11 dB Maximum reflectance: -46.1 dB
B 6.0001 4.432
b 8.0001 4.780

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.4 0.000
Section 4.2312 0.859 0.203 0.859
Reflective 2 4.2312 --- -46.1 0.859

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber6_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:42:21 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.6
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2311 km Average loss: 0.337 dB/km Injection level: 14.1 dB
Span loss: 1.424 dB Average splice loss: ---
Span ORL: 26.97 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.479 dB/km A-B average loss: 6.259 dB/km
a 1.9999 13.385 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.605 dB
A 3.9999 12.521 A-B ORL: 37.68 dB Maximum reflectance: -38.7 dB
B 6.0001 0.000
b 8.0001 6.775

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.4 0.000
Section 4.2311 1.424 0.337 1.424
Reflective 2 4.2311 --- -38.7 1.424

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber7_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:43:55 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.7
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2293 km Average loss: 0.197 dB/km Injection level: 12.3 dB
Span loss: 0.834 dB Average splice loss: ---
Span ORL: 26.51 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.204 dB/km A-B average loss: 3.854 dB/km
a 1.9999 11.960 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.657 dB
A 3.9999 11.584 A-B ORL: 46.76 dB Maximum reflectance: -51.6 dB
B 6.0001 3.875
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -31.0 0.000
Section 4.2293 0.834 0.197 0.834
Reflective 2 4.2293 --- -51.5 0.834

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber7_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:44:02 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.7
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2291 km Average loss: 0.340 dB/km Injection level: 13.8 dB
Span loss: 1.439 dB Average splice loss: ---
Span ORL: 26.75 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.502 dB/km A-B average loss: 3.368 dB/km
a 1.9999 13.127 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.043 dB
A 3.9999 12.367 A-B ORL: 45.04 dB Maximum reflectance: -53.1 dB
B 6.0001 5.630
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2291 1.439 0.340 1.439
Reflective 2 4.2291 --- -53.1 1.439

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber8_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:44:28 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.8
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2302 km Average loss: 0.196 dB/km Injection level: 12.7 dB
Span loss: 0.829 dB Average splice loss: ---
Span ORL: 27.13 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.957 dB/km A-B average loss: 5.930 dB/km
a 1.9999 12.276 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.808 dB
A 3.9999 11.861 A-B ORL: 47.62 dB Maximum reflectance: -56.2 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.6 0.000
Section 4.2302 0.829 0.196 0.829
Reflective 2 4.2302 --- -56.2 0.829

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber8_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:44:36 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.8
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2301 km Average loss: 0.337 dB/km Injection level: 14.2 dB
Span loss: 1.424 dB Average splice loss: ---
Span ORL: 27.36 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.535 dB/km A-B average loss: 6.439 dB/km
a 1.9999 13.540 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.336 dB
A 3.9999 12.880 A-B ORL: 43.47 dB Maximum reflectance: -46.9 dB
B 6.0001 0.000
b 8.0001 4.312

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2301 1.424 0.337 1.424
Reflective 2 4.2301 --- -46.8 1.424

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber9_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:45:44 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.9
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2296 km Average loss: 0.203 dB/km Injection level: 12.2 dB
Span loss: 0.858 dB Average splice loss: ---
Span ORL: 26.23 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.961 dB/km A-B average loss: 5.708 dB/km
a 1.9999 11.622 A-B LSA loss: 1.000 dB 4-point Event Loss: 8.826 dB
A 3.9999 11.418 A-B ORL: 48.28 dB Maximum reflectance: -61.6 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -31.0 0.000
Section 4.2296 0.858 0.203 0.858
Reflective 2 4.2296 --- -61.7 0.858

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber9_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:45:52 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.9
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2298 km Average loss: 0.341 dB/km Injection level: 13.6 dB
Span loss: 1.444 dB Average splice loss: ---
Span ORL: 26.42 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.935 dB/km A-B average loss: 6.195 dB/km
a 1.9999 13.020 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.680 dB
A 3.9999 12.392 A-B ORL: 46.11 dB Maximum reflectance: -64.2 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2298 1.444 0.341 1.444
Reflective 2 4.2298 --- -64.3 1.444

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber10_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:47:53 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.10
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2312 km Average loss: 0.204 dB/km Injection level: 12.5 dB
Span loss: 0.862 dB Average splice loss: ---
Span ORL: 26.94 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.963 dB/km A-B average loss: 5.885 dB/km
a 1.9999 12.112 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.529 dB
A 3.9999 11.772 A-B ORL: 48.20 dB Maximum reflectance: -62.0 dB
B 6.0001 0.000
b 8.0001 4.258

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.4 0.000
Section 4.2312 0.862 0.204 0.862
Reflective 2 4.2312 --- -62.0 0.862

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber10_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:48:01 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.10
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2311 km Average loss: 0.341 dB/km Injection level: 14.1 dB
Span loss: 1.444 dB Average splice loss: ---
Span ORL: 27.14 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.202 dB/km A-B average loss: 6.403 dB/km
a 1.9999 13.396 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.891 dB
A 3.9999 12.809 A-B ORL: 45.54 dB Maximum reflectance: -53.8 dB
B 6.0001 0.000
b 8.0001 7.713

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2311 1.444 0.341 1.444
Reflective 2 4.2311 --- -53.8 1.444

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber11_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:48:34 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.11
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2305 km Average loss: 0.202 dB/km Injection level: 12.6 dB
Span loss: 0.853 dB Average splice loss: ---
Span ORL: 26.99 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.973 dB/km A-B average loss: 3.543 dB/km
a 1.9999 12.159 A-B LSA loss: 1.000 dB 4-point Event Loss: 8.893 dB
A 3.9999 11.657 A-B ORL: 45.76 dB Maximum reflectance: -49.7 dB
B 6.0001 4.571
b 8.0001 6.242

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.4 0.000
Section 4.2305 0.853 0.202 0.853
Reflective 2 4.2305 --- -49.7 0.853

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber11_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:48:41 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.11
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2304 km Average loss: 0.339 dB/km Injection level: 14.1 dB
Span loss: 1.433 dB Average splice loss: ---
Span ORL: 27.03 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.321 dB/km A-B average loss: 3.725 dB/km
a 1.9999 13.425 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.875 dB
A 3.9999 12.659 A-B ORL: 39.46 dB Maximum reflectance: -40.4 dB
B 6.0001 5.208
b 8.0001 4.899

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2304 1.433 0.339 1.433
Reflective 2 4.2304 --- -40.4 1.433

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber12_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:49:18 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.12
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2302 km Average loss: 0.188 dB/km Injection level: 12.6 dB
Span loss: 0.797 dB Average splice loss: ---
Span ORL: 27.05 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.073 dB/km A-B average loss: 5.915 dB/km
a 1.9999 12.199 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.424 dB
A 3.9999 11.831 A-B ORL: 47.92 dB Maximum reflectance: -58.4 dB
B 6.0001 0.000
b 8.0001 6.608

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.5 0.000
Section 4.2302 0.797 0.188 0.797
Reflective 2 4.2302 --- -58.5 0.797

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber12_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:49:26 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.12
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2301 km Average loss: 0.332 dB/km Injection level: 14.1 dB
Span loss: 1.403 dB Average splice loss: ---
Span ORL: 27.21 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.347 dB/km A-B average loss: 6.356 dB/km
a 1.9999 13.474 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.171 dB
A 3.9999 12.714 A-B ORL: 45.64 dB Maximum reflectance: -59.4 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2301 1.403 0.332 1.403
Reflective 2 4.2301 --- -59.4 1.403

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber13_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:51:53 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.13
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2369 km Average loss: 0.191 dB/km Injection level: 12.6 dB
Span loss: 0.809 dB Average splice loss: ---
Span ORL: 26.98 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.171 dB/km A-B average loss: 3.059 dB/km
a 1.9999 12.072 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.319 dB
A 3.9999 11.719 A-B ORL: 46.90 dB Maximum reflectance: -53.3 dB
B 6.0001 5.600
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.4 0.000
Section 4.2369 0.809 0.191 0.809
Reflective 2 4.2369 --- -53.3 0.809

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber13_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:52:01 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.13
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2368 km Average loss: 0.335 dB/km Injection level: 14.1 dB
Span loss: 1.419 dB Average splice loss: ---
Span ORL: 27.22 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.371 dB/km A-B average loss: 6.443 dB/km
a 1.9999 13.403 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.391 dB
A 3.9999 12.887 A-B ORL: 45.63 dB Maximum reflectance: -55.1 dB
B 6.0001 0.000
b 8.0001 4.538

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2368 1.419 0.335 1.419
Reflective 2 4.2368 --- -55.1 1.419

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber14_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:53:06 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.14
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2363 km Average loss: 0.196 dB/km Injection level: 12.6 dB
Span loss: 0.830 dB Average splice loss: ---
Span ORL: 26.96 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.121 dB/km A-B average loss: 5.899 dB/km
a 1.9999 12.264 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.573 dB
A 3.9999 11.799 A-B ORL: 47.46 dB Maximum reflectance: -54.9 dB
B 6.0001 0.000
b 8.0001 3.995

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.4 0.000
Section 4.2363 0.830 0.196 0.830
Reflective 2 4.2363 --- -54.9 0.830

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber14_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:53:13 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.14
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2362 km Average loss: 0.333 dB/km Injection level: 14.1 dB
Span loss: 1.409 dB Average splice loss: ---
Span ORL: 27.16 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.586 dB/km A-B average loss: 6.332 dB/km
a 1.9999 13.503 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.270 dB
A 3.9999 12.666 A-B ORL: 45.34 dB Maximum reflectance: -56.4 dB
B 6.0001 0.000
b 8.0001 5.593

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2362 1.409 0.333 1.409
Reflective 2 4.2362 --- -56.4 1.409

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber15_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:54:05 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.15
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2363 km Average loss: 0.192 dB/km Injection level: 12.5 dB
Span loss: 0.812 dB Average splice loss: ---
Span ORL: 26.79 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.959 dB/km A-B average loss: 5.849 dB/km
a 1.9999 12.227 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.628 dB
A 3.9999 11.700 A-B ORL: 43.86 dB Maximum reflectance: -45.8 dB
B 6.0001 0.000
b 8.0001 5.893

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.3 0.000
Section 4.2363 0.812 0.192 0.812
Reflective 2 4.2363 --- -45.8 0.812

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber15_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:54:13 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.15
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2362 km Average loss: 0.331 dB/km Injection level: 14.0 dB
Span loss: 1.403 dB Average splice loss: ---
Span ORL: 26.90 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.639 dB/km A-B average loss: 6.402 dB/km
a 1.9999 13.262 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.111 dB
A 3.9999 12.807 A-B ORL: 38.06 dB Maximum reflectance: -38.3 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2362 1.403 0.331 1.403
Reflective 2 4.2362 --- -38.3 1.403

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber16_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:54:53 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.16
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2366 km Average loss: 0.200 dB/km Injection level: 12.5 dB
Span loss: 0.849 dB Average splice loss: ---
Span ORL: 26.81 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.048 dB/km A-B average loss: 5.914 dB/km
a 1.9999 12.085 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.157 dB
A 3.9999 11.829 A-B ORL: 47.09 dB Maximum reflectance: -52.4 dB
B 6.0001 0.000
b 8.0001 4.986

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.2 0.000
Section 4.2366 0.849 0.200 0.849
Reflective 2 4.2366 --- -52.4 0.849

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber16_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:55:01 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.16
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2365 km Average loss: 0.333 dB/km Injection level: 14.0 dB
Span loss: 1.411 dB Average splice loss: ---
Span ORL: 27.03 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.302 dB/km A-B average loss: 3.663 dB/km
a 1.9999 13.235 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.859 dB
A 3.9999 12.617 A-B ORL: 44.48 dB Maximum reflectance: -50.3 dB
B 6.0001 5.290
b 8.0001 2.904

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2365 1.411 0.333 1.411
Reflective 2 4.2365 --- -50.3 1.411

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber17_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:56:13 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.17
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2360 km Average loss: 0.198 dB/km Injection level: 12.5 dB
Span loss: 0.838 dB Average splice loss: ---
Span ORL: 26.90 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.936 dB/km A-B average loss: 5.817 dB/km
a 1.9999 12.142 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.564 dB
A 3.9999 11.636 A-B ORL: 46.88 dB Maximum reflectance: -53.3 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.3 0.000
Section 4.2360 0.838 0.198 0.838
Reflective 2 4.2360 --- -53.3 0.838

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber17_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:56:21 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.17
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2362 km Average loss: 0.334 dB/km Injection level: 14.1 dB
Span loss: 1.415 dB Average splice loss: ---
Span ORL: 27.14 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.504 dB/km A-B average loss: 4.365 dB/km
a 1.9999 13.450 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.908 dB
A 3.9999 12.730 A-B ORL: 45.04 dB Maximum reflectance: -52.3 dB
B 6.0001 3.999
b 8.0001 4.379

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2362 1.415 0.334 1.415
Reflective 2 4.2362 --- -52.3 1.415

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber18_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:57:15 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.18
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2363 km Average loss: 0.199 dB/km Injection level: 12.4 dB
Span loss: 0.843 dB Average splice loss: ---
Span ORL: 26.69 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.068 dB/km A-B average loss: 5.858 dB/km
a 1.9999 11.979 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.272 dB
A 3.9999 11.717 A-B ORL: 47.33 dB Maximum reflectance: -53.5 dB
B 6.0001 0.000
b 8.0001 6.329

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.1 0.000
Section 4.2363 0.843 0.199 0.843
Reflective 2 4.2363 --- -53.5 0.843

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber18_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:57:23 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.18
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2362 km Average loss: 0.333 dB/km Injection level: 13.9 dB
Span loss: 1.410 dB Average splice loss: ---
Span ORL: 26.87 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.471 dB/km A-B average loss: 4.006 dB/km
a 1.9999 13.199 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.943 dB
A 3.9999 12.481 A-B ORL: 45.06 dB Maximum reflectance: -53.7 dB
B 6.0001 4.468
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2362 1.410 0.333 1.410
Reflective 2 4.2362 --- -53.7 1.410

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber19_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:59:32 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.19
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2344 km Average loss: 0.198 dB/km Injection level: 12.5 dB
Span loss: 0.839 dB Average splice loss: ---
Span ORL: 26.87 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.107 dB/km A-B average loss: 3.965 dB/km
a 1.9999 12.185 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.289 dB
A 3.9999 11.586 A-B ORL: 45.02 dB Maximum reflectance: -48.3 dB
B 6.0001 3.654
b 8.0001 4.346

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.3 0.000
Section 4.2344 0.839 0.198 0.839
Reflective 2 4.2344 --- -48.2 0.839

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber19_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 2:59:40 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.19
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2346 km Average loss: 0.332 dB/km Injection level: 14.0 dB
Span loss: 1.406 dB Average splice loss: ---
Span ORL: 27.07 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.446 dB/km A-B average loss: 3.705 dB/km
a 1.9999 13.392 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.857 dB
A 3.9999 12.686 A-B ORL: 43.71 dB Maximum reflectance: -47.5 dB
B 6.0001 5.275
b 8.0001 6.742

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2346 1.406 0.332 1.406
Reflective 2 4.2346 --- -47.5 1.406

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber20_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:00:26 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.20
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2344 km Average loss: 0.196 dB/km Injection level: 12.6 dB
Span loss: 0.830 dB Average splice loss: ---
Span ORL: 27.00 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.219 dB/km A-B average loss: 5.806 dB/km
a 1.9999 12.233 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.189 dB
A 3.9999 11.614 A-B ORL: 45.38 dB Maximum reflectance: -49.2 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.5 0.000
Section 4.2344 0.830 0.196 0.830
Reflective 2 4.2344 --- -49.2 0.830

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber20_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:00:33 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.20
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2342 km Average loss: 0.331 dB/km Injection level: 14.1 dB
Span loss: 1.402 dB Average splice loss: ---
Span ORL: 27.11 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.283 dB/km A-B average loss: 6.412 dB/km
a 1.9999 13.387 A-B LSA loss: 1.400 dB 4-point Event Loss: 9.990 dB
A 3.9999 12.825 A-B ORL: 38.67 dB Maximum reflectance: -39.2 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2342 1.402 0.331 1.402
Reflective 2 4.2342 --- -39.2 1.402

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber21_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:01:21 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.21
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2353 km Average loss: 0.194 dB/km Injection level: 12.5 dB
Span loss: 0.822 dB Average splice loss: ---
Span ORL: 26.85 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 2.893 dB/km A-B average loss: 5.888 dB/km
a 1.9999 12.188 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.611 dB
A 3.9999 11.778 A-B ORL: 48.23 dB Maximum reflectance: -63.2 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.3 0.000
Section 4.2353 0.822 0.194 0.822
Reflective 2 4.2353 --- -63.3 0.822

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber21_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:01:29 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.21
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2355 km Average loss: 0.328 dB/km Injection level: 14.0 dB
Span loss: 1.387 dB Average splice loss: ---
Span ORL: 27.10 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.488 dB/km A-B average loss: 4.974 dB/km
a 1.9999 13.310 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.295 dB
A 3.9999 12.738 A-B ORL: 45.84 dB Maximum reflectance: -64.3 dB
B 6.0001 2.789
b 8.0001 0.646

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2355 1.387 0.328 1.387
Reflective 2 4.2355 --- -64.4 1.387

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber22_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:02:37 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.22
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2353 km Average loss: 0.194 dB/km Injection level: 12.4 dB
Span loss: 0.821 dB Average splice loss: ---
Span ORL: 26.76 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.261 dB/km A-B average loss: 5.852 dB/km
a 1.9999 12.066 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.744 dB
A 3.9999 11.705 A-B ORL: 47.69 dB Maximum reflectance: -56.5 dB
B 6.0001 0.000
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.2 0.000
Section 4.2353 0.821 0.194 0.821
Reflective 2 4.2353 --- -56.6 0.821

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber22_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:02:44 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.22
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2352 km Average loss: 0.337 dB/km Injection level: 14.0 dB
Span loss: 1.429 dB Average splice loss: ---
Span ORL: 27.04 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.264 dB/km A-B average loss: 3.498 dB/km
a 1.9999 13.293 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.093 dB
A 3.9999 12.643 A-B ORL: 45.43 dB Maximum reflectance: -55.5 dB
B 6.0001 5.646
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2352 1.429 0.337 1.429
Reflective 2 4.2352 --- -55.5 1.429

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber23_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:04:41 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.23
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2356 km Average loss: 0.194 dB/km Injection level: 12.5 dB
Span loss: 0.820 dB Average splice loss: ---
Span ORL: 26.89 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.176 dB/km A-B average loss: 2.828 dB/km
a 1.9999 12.218 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.374 dB
A 3.9999 11.798 A-B ORL: 48.06 dB Maximum reflectance: -60.2 dB
B 6.0001 6.142
b 8.0001 5.523

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.3 0.000
Section 4.2356 0.820 0.194 0.820
Reflective 2 4.2356 --- -60.2 0.820

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber23_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:04:49 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.23
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2355 km Average loss: 0.328 dB/km Injection level: 14.0 dB
Span loss: 1.390 dB Average splice loss: ---
Span ORL: 27.09 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.386 dB/km A-B average loss: 5.447 dB/km
a 1.9999 13.391 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.279 dB
A 3.9999 12.607 A-B ORL: 45.49 dB Maximum reflectance: -59.6 dB
B 6.0001 1.712
b 8.0001 1.665

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2355 1.390 0.328 1.390
Reflective 2 4.2355 --- -59.6 1.390

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4


OTDR Report (1550 nm (9 µm))
General Information
Filename: opgw .03 fiber24_1550.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:08:20 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.24
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2356 km Average loss: 0.198 dB/km Injection level: 12.5 dB
Span loss: 0.840 dB Average splice loss: ---
Span ORL: 26.72 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.270 dB/km A-B average loss: 2.640 dB/km
a 1.9999 12.093 A-B LSA loss: 1.000 dB 4-point Event Loss: 9.562 dB
A 3.9999 11.675 A-B ORL: 40.95 dB Maximum reflectance: -41.7 dB
B 6.0001 6.395
b 8.0001 0.000

Signature: Date: 12/18/2019 Page 1 of 4


OTDR Report (1550 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -27.2 0.000
Section 4.2356 0.840 0.198 0.840
Reflective 2 4.2356 --- -41.7 0.840

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1550 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1550 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.468325 1310 nm - 1550 nm 0.500
Backscatter (dB) -81.87
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 2 of 4


OTDR Report (1310 nm (9 µm))
General Information
Filename: opgw .03 fiber24_1310.sor
Test date: 12/18/2019 Customer: POWER GRID
Test time: 3:08:28 PM Company: KEC
Cable ID: BHA-BIK-03 Fiber ID: OPGW-3.24
Job ID:
Comments:

Locations
Location A Location B
Location 28A/0 765KV DC LINE PKG-II
Operator
Model MAX-710B-M1-EA
Serial number 957422
Calibration date 14/10/2019 (UTC)

Results
Span length: 4.2358 km Average loss: 0.336 dB/km Injection level: 14.0 dB
Span loss: 1.422 dB Average splice loss: ---
Span ORL: 27.10 dB Maximum splice loss: ---

Graph

Markers
Marker Position (km) Value (dB) A-B LSA attenuation: 3.695 dB/km A-B average loss: 4.536 dB/km
a 1.9999 13.399 A-B LSA loss: 1.400 dB 4-point Event Loss: 10.289 dB
A 3.9999 12.604 A-B ORL: 41.11 dB Maximum reflectance: -43.0 dB
B 6.0001 3.530
b 8.0001 4.658

Signature: Date: 12/18/2019 Page 3 of 4


OTDR Report (1310 nm (9 µm))
Event Table
Type No. Pos./Length Loss Reflectance Attenuation Cumulative
(km) (dB) (dB) (dB/km) (dB)
First Connector 1 0.0000 --- -32.5 0.000
Section 4.2358 1.422 0.336 1.422
Reflective 2 4.2358 --- -43.0 1.422

Macrobend
No macrobend detected.

Pass/Fail Thresholds
1310 nm (9 µm)
Splice loss (dB) 0.300
Connector loss (dB) 0.750
Reflectance (dB) -40.0
Fiber section attenuation (dB/km) 0.400
Span loss (dB) 20.000
Span length (km) 0.0000
Span ORL (dB) 15.00

Test Parameters
A→B
Wavelength (nm) 1310 nm (9 µm)
Range (km) 10.0000
Pulse (ns) 10
Duration (s) 5

Test Settings
A→B Macrobend Wavelengths Macrobend Delta Loss (dB)
IOR 1.467700 1310 nm - 1550 nm 0.500
Backscatter (dB) -79.45
Helix factor (%) 0.00
Splice loss detection threshold (dB) 0.020
Reflectance detection threshold (dB) -72.0
End-of-fiber detection threshold (dB) 5.000

Signature: Date: 12/18/2019 Page 4 of 4