1.25m. 0 0.5 1.25 2.

5 5

SCALE 1:50 METERS

Revision Date Issued For: Approved

Future Consult
Consulting Engineers

Tel.: ( +202 ) 333 650 13 - Fax: ( +202 ) 333 720 16


67 ELMadina ELMonawara St., Jeddah St., ELMohandiseen
Info@futureconsult-eg.com

A1 1 : 50

3 / 2022 2120

Drawing No Revision

SN-04.01 00
North
key plan: North

W E W E

S S

ZONE-3

1.88
M 4/Z3
S SMOKE DETECTOR

H HEAT DETECTOR
FACP

3.75
ZONE-1

4.13
1.17
2/Z1 MULTI-SENSOR
1/Z1
M M HEAT & SMOKE DETECTOR

1.27
2/Z2
1/Z2 FIRE ALARM BELL
FROM FACP IN JB M
2.34

ADMIN. BUILDING 2.00


M 3/Z3 HORN WITH STROP LIGHT

ZONE-2
2.00
3/Z1 M FACP FIRE ALARM CONTROL PANEL (CONVENTIAL)

FIRE ALARM BREAK GLASS

4.06
(MANUAL STATION)
(2X1.5)mm² COPPER CONDUCTOR
FIRE RETARDANT CABLE
ADMIN. BUILDING PLAN GUARD BUILDING PLAN 105°C AS PER BS STANDARD
ZONE-1 ZONE-2
JB JUNCTION BOX

M 2/Z3 THE END LINE RESISTANCE

1/Z3

JB

FROM FACP IN
ADMIN.BUILDING

PUMPS BUILDING PLAN


1/Z5
ZONE-3
ZONE-4 FROM FACP IN
FROM FACP IN 1/Z4 JB
2.00

ADMIN.BUILDING
JB ADMIN.BUILDING

2/Z4 M M H S

H H
2.00

2/Z5 3/Z5

3/Z4 M

3.00
3.00 M H S
:
2.19 4.37
ZONE-5

STORE BUILDING PLAN GENERATOR BUILDING PLAN M H S


ZONE-4 ZONE-5

M H S

:
ZONE-6 M H S

2/Z6 3/Z6 6/Z6

M M M
M H S
:
1/Z6 4/Z6 5/Z6

JB

FROM FACP IN : :
ADMIN.BUILDING
: :
TRANSFROMER BUILDING PLAN
ZONE-6
Drawing No Revision

22-P05-QEN-FA-01-PS02
North
key plan: North

W E W E

S S

FROM FACP IN 1/Z3 ZONE-3

2.00
JB
ADMIN.BUILDING

FACP
ZONE-1

2.49
1.17
1/Z1
2/Z1 2/Z3 M
M 3.00 5.00 3.00

1.27
M M

2.00
2/Z2
1/Z2
FROM FACP IN JB M 5/Z4 6/Z4

2.34
ADMIN. BUILDING 2.00 SMOKE DETECTOR
3/Z3 M
2.00
3/Z1 M ZONE-2
3.00

H HEAT DETECTOR

5.35
MULTI-SENSOR
M HEAT & SMOKE DETECTOR

ADMIN. BUILDING PLAN GUARD BUILDING PLAN STORE BUILDING PLAN FIRE ALARM BELL
ZONE-1 ZONE-2 ZONE-3

HORN WITH STROP LIGHT


M 4/Z4 7/Z4 M
FACP FIRE ALARM CONTROL PANEL (CONVENTIAL)

2.50 5.25 2.50 FIRE ALARM BREAK GLASS


(MANUAL STATION)

5.31
FROM FACP IN 1/Z5
JB
ADMIN.BUILDING (2X1.5)mm² COPPER CONDUCTOR
FIRE RETARDANT CABLE
105°C AS PER BS STANDARD

JB JUNCTION BOX

H H THE END LINE RESISTANCE


2/Z5 3/Z5
M 3/Z4 8/Z4 M

3.50

5.35
GENERATOR BUILDING PLAN
ZONE-5
M 2/Z4 9/Z4 M

1/Z4

JB
2.50 5.00 5.00 3.50

FROM FACP IN
2.00
2.04

ADMIN.BUILDING
14/Z6

M M M M
13/Z6 12/Z6 11/Z6
PUMPS BUILDING PLAN
ZONE-4

:
4.00

10/Z6
1.95

M H S
1.90

15/Z6
M M M M
16/Z6 17/Z6 18/Z6
2.00

M H S

:
3.52 2.70 3.55
1.90

1.90

1.90

M H S

M M M
3/Z6 6/Z6 9/Z6

M H S :
4.12

4.12

4.12

M H S
M M 5/Z6 M 8/Z6
2/Z6

1/Z6 4/Z6 7/Z6 :


M H S
JB

FROM FACP IN
ADMIN.BUILDING
: :

TRANSFROMER BUILDING PLAN


: :
ZONE-6

Drawing No Revision

22-P05-QEN-FA-01-PS01
N

W E

SENSOR

SENSOR

SECTION (B-B) SECTION (C-C)

SENSOR

1:20
A1

04 / 2024 2101
SECTION (A-A) Drawing No Revision

ME-01.02 00
3 PRECAST SLABS DETAILS
STR 05 SCALE
1:25

7 OPINING DETAILS
STR 05 SCALE
N.T.S

2 SECTION (A-A) REINFORCEMENT


SCALE
1 SECTION (A-A) CONCRETE DIM STR 05 1:25
STR 05 SCALE
1:25

Revision Date Issued For: Approved

Future Consult
Consulting Engineers

Tel.: ( +202 ) 333 650 13 - Fax: ( +202 ) 333 720 16


67 ELMadina ELMonawara St., Jeddah St., ELMohandiseen
Info@futureconsult-eg.com

5 HORIZONTAL SECTION (B-B) REINFORCEMENT


STR 05 SCALE
1:25

4 HORIZONTAL SECTION (B-B) CONCRETE DIM 6 ROOF PLAN AT CONCRETE DIM & REINFORCEMENT
SCALE STR 05 SCALE
STR 05 1:25 1:25
A1 1:25

12 / 2022 2101

Drawing No Revision

STR01.02 00