Steam Boiler

Column no 1

BO-B2-01-01-02
Unit No
EC 1

Domestic Hot Water, Clean


System Served
Steam and Heating System

Floor Basement 2

Room Boilers Room-EC


Natural Gas Burner/
Specification Type
Light Fuel burner
Steam Heating Capacity (kW)/Hp 5000 HP

Steam Flow Rate (kg/hr) 7500

Steam Pressure (bars) 10

Entering Fuel Water Temperature (deg C) 80

Fuel Burned Natural Gas /Light Oil E2

Quantity 2

Phase 3

Power (Hp) 30

Ampere 38.2

Protection Type MCCB 80/100

Remarks Boiler with feed pumps


Clean Steam Generator
Column no 1

CSG-J-B01
Unit No
EC 1

Medical Equipment and


System Served
Humidification System

Floor Ground floor

Room Boilers Room

Horizontal Clean Steam


Specification Type
Generator

Plant Primary Steam Pressure (bar) 10

Output Clean Steam Pressure (bar) 5

Feed Water Temperature (deg C) 90

Clean Steam Flow rate (kg/hr) 1500

Quantity 2

Remarks Clean Steam Generator


Calorifiers
Column # 1

HWC-EC-01
Unit Identification
B2 1

System Served Hospital Domestic Hot Water

Floor Energy Centre

Room Boiler Room

Specification Type Vertical Packaged Steam Fired Water Calorifier

Storage Capacity (litres) 9000 each

Steam heating Capacity (kW) 1100 each

Entering Temperature ( ͦC) 5

Leaving Temperature ( ͦC) 60

Quantity 3

Remarks -

Steam Side Pressure 4.5 bar

Steam Flow 5480 kg/hr

Water Flow 220 gpm, 14 l/s Hot Water Demand


ΔT
c
q
@4.5 bar
q
###

###
###
###
S & T Heat Exchanger
Column No 1

Unit No. HX-ST-EC-01

Building Hospital

location Ground Floor

Type Shell and Tube

Flow Rate (kg/hr) 4307


Industrial Steam

Entering Temperature (deg C) 151


Data

Leaving Temperature (deg C) -

Pressure (bar) 4.5

Flow Rate (L/S) 50.00


Heating Water

Entering Temperature (deg C) 48


Data

Leaving Temperature (deg C) 60

Pressure (bar) 5

Quantity 1

Remarks -
STEAM NETWORK ACCESSORIES:

Entering Entering
Pipe Size
No. Description Pressure Temperature
mm
(Bar) (°C)

1 PRV Station 200 10 181

2 PRV Station 200 10 181

3 Steam Traps 200 10 181

4 Steam Traps 200 4.5 155

5 Steam Traps 150 2.5 139

6 Steam Traps (Calorifier Connections) 100 4.5 155

7 Steam Traps (Shell & Tube HX) 150 4.5 155

8 Steam Traps 100 2.5 139

9 Drip Legs to be considered tentaive

Note:

Shop Drawings will be provided later, at present need estimated quotes.


Leaving Entering
Pipe Size
Pressure Temperature Qty.
mm
(Bar) (°C)

4.5 144 200 1

2.5 - 150 1

- - 1

- - 1

- - 1

- - 3

- - 1

- - 5