Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Louver Products

Severe Duty, Stationary, Operable

January
1 2014
Page Header
Louver Selection Guide

Louvers Airflow Aesthetics AMCA Certifications


Free Area Free Area Blade Wind-
Depth Blade Water Air
Type Model 48 x 48 in. 48 x 48 in. Angles Driven Sound
(in.) Alignment Penetration Performance
(sq. ft.) (%) (degrees) Rain
EDD-401 8.22 51 4 H 37/45 3 3
EDD-601 8.21 54 6 H 37/45 3 3
EHM-601 7.91 49 6 H 37/45 3 3
Drainable ESD-202 6.01 38 2 H 37/45 3 3
Blade ESD-403 8.00 50 4 H 37/45 3 3
ESD-435 8.98 56 4 H 37.5 3 3
ESD-603 8.36 52 6 H 37/45 3 3
ESD-635 9.41 59 6 H 37.5 3 3
EDJ-202 6.01 38 2 H 45 3 3
EDJ-401 8.32 52 4 H 37/45 3 3
EDJ-430 8.35 45 4 H 30 3 3
EDJ-601 8.69 54 6 H 37/45 3 3
Drainable EDK-402 8.49 53 4 H 37/45 3 3
Head EDK-430 8.80 55 4 H 30 3 3
EDK-602 8.35 52 6 H 37/45 3 3
ESID-430
7.66 48 4 H 30
DISCHARGE
ESID-430 INTAKE 10.88 68 4 H 30
ESJ-202 6.01 38 2 H 45 3 3
ESJ-401 8.44 53 4 H 37/45 3 3
Non-
ESJ-602 8.73 55 6 H 37/45 3 3
Drainable
ESK-402 8.45 53 4 H 37/45 3 3
ESK-602 8.46 56 6 H 37/45 3 3
ESJ-401RM 8.58 54 4 H 37/45 3 3
Recessed ESJ-602RM 8.38 52 6 H 37/45 3 3
Mullion ESK-402RM 8.42 53 4 H 37/45 3 3
ESK-602RM 8.13 51 6 H 37/45 3 3
EAD-401 6.54 41 4 H 45 3 3
EAD-601 7.34 46 6 H 45 3 3
EAD-635 8.73 55 6 H 35 3 3
EADC-401 5.84 37 4 H 45
Adjustable EADC-601 6.44 40 6 H 45
Blade EAH-401 6.48 41 4 H 45 3 3
EAH-690
6.32 40 6 H 45 3
(45º BLADE)
EAH-690
10.87 70 6 H 90 3
(90º BLADE)
EAC-401 6.34 40 4 H 45 3 3
EAC-601 7.41 46 6 H 45 3 3
EACA-601 7.68 48 6 H 45 3 3
EACC-401 5.59 35 4 H 45
EACC-601 6.20 39 6 H 45
Combination EACN-601 7.18 45 6 H 45 3 3
Louver/
Damper ECD-401 7.60 46 4 H 37/45 3 3
ECD-601 7.32 48 6 H 37/45 3 3
GCE-202 4.96 31 2 H 45
GCE-402 6.36 40 4 H 45
GCI-202 5.26 33 2 H 45
GCI-402 6.39 40 4 H 45

2
Page Header
Louver Selection Guide

Louvers Airflow Aesthetics AMCA Certifications


Free Area Free Area Blade Wind-
Depth Blade Water Air
Type Model 48 x 48 in. 48 x 48 in. Angles Driven Sound
(in.) Alignment Penetration Performance
(sq. ft.) (%) (degrees) Rain
SED-202 3.42 21 2 H NA 3 3
SED-401 5.16 32 4 H NA 3 3
SED-501 9.11 57 5 H NA 3 3
SEH-202 3.73 23 2 H NA 3 3
Sightproof SEH-401 5.16 32 4 H NA 3 3
SES-202 3.75 24 2 H NA 3 3
SES-401 5.33 33 4 H NA 3 3
SEV-401 5.33 33 4 V NA
SEV-501 9.11 57 5 V NA
EHH-201 6.20 39 2 H NA 3 3 3
EHH-401 6.72 42 4 H NA 3 3 3
EHH-501 6.80 43 5 H NA 3 3 3
EHH-601 7.58 47 6 H NA 3 3 3
Wind-Driven
EHH-701 6.99 43 7 H NA 3 3 3
Rain
EVH-201 5.71 36 2 V NA 3 3 3
EVH-401 6.38 40 4 V NA 3 3 3
EVH-602 5.88 39 6 V NA 3 3 3
EVH-801 5.05 32 8 V NA 3 3 3
AFJ-601X 4.89 31 6 H 45 3 3 3
Florida EHH-501X 6.80 43 5 H NA 3 3 3
Product ESD-435X 8.98 56 4 H 37.5 3 3
Approved ESD-635X 9.41 59 6 H 37.5 3 3
EVH-602X 5.88 37 6 V NA 3 3 3
EACA-601D 7.21 45 6 H 45 3 3
EHH-601D* 7.58 47 6 H NA 3 3 3
Miami-Dade ESD-635D* 9.41 59 6 H 37/45 3 3
Qualified ESS-502D 8.19 51 5 H NA 3 3
EVH-602D* 5.88 37 6 V NA 3 3 3
EVH-660D 7.29 45 6 V NA 3 3 3
ESF-145 6.08 38 1.5 H 45
ESJ-150 7.29 46 1.5 H 30.5
ESU-130 10.95 68 1.5 H 30
Thinline
ESU-130S 10.95 68 1.375 H 30
ESU-150 7.40 46 1.5 H 52
ESU-150S 7.70 48 1.375 H 52
AFA-801 5.21 33 8 H 45 3 3 3
AFJ-120 3.67 23 12 H 45 3 3 3
Acoustical AFJ-601 4.89 31 6 H 45 3 3 3
AFJ-801 4.28 27 8 H 45 3 3 3
AFS-120 4.27 27 12 H 45 3 3 3
FAD-402 5.98 38 4 H 45 3 3
FAD-602 7.11 45 6 H 45 3 3
FAD-635 8.77 55 6 H 35 3 3
FAJ-402 5.93 37 4 H 45 3 3
Fabricated FAJ-602 6.23 39 6 H 45 3 3
FDS-402 7.03 44 4 H 45 3 3
FDS-602 8.15 51 6 H 45 3 3
FSJ-402 7.55 47 4 H 45 3 3
FSJ-602 7.57 47 6 H 45 3 3
*Optional factory installed VCD-40 control damper **Optional factory installed HCD-240 heavy duty damper

3
Page Header
Drainable Blade
• Drainable blades offer excellent resistance to water penetration.
• Drain gutters located on every blade to capture water.
• Integral downspouts located within the jambs to channel water downward to sloped sill for drainage away from
the louver.
• EDD Series incorporates dual drainable blades for additional water capture.
• EHM Series incorporates recessed mullion design for continuous blade appearance for multiwidth sections.
• Models ESD-435 and ESD-635 lend 56% and 59% free area respectfully.

Drainable Head Flat Head


Drainable Head

Dual Drainable Blades Dual Drainable Blades

Recessed Mullion

Flat Sill
Sloped Sill
Sill Pan
EDD-401
EHM-601

Drainable Drainable Drainable


Head Head Head

Drainable Drainable
Blades Drainable
Blades
Blades

Sloped Sloped Sloped


Sill Sill Sill
ESD-403
ESD
ES 403 ESD-435 ESD-635

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
EDD-401 4 DD 0.081 0.081 8.22 51 992 0.143 8154 8312
EDD-601 6 DD 0.081 0.081 8.21 52 1107 0.204 9088 8399
EHM-601 6 DD 0.081 0.081 7.91 49 1065 0.166 8424 6577
ESD-202 2 D 0.063 0.063 6.01 38 1058 0.141 6359 5963
ESD-403 4 D 0.081 0.081 8.00 50 1007 0.176 8056 8188
ESD-435 4 D 0.081 0.081 8.98 56 1151 0.213 10336 9285
ESD-603 6 D 0.081 0.081 8.36 52 1027 0.178 8586 8359
ESD-635 6 D 0.081 0.081 9.41 59 1077 0.173 10135 9956
* Test size: 48 x 48 in. unit @ 15 min. duration D = Drainable DD = Dual Drainable

4
Page Header
Drainable Head
• Drainable head member improves ability to prevent water penetration due to an additional drain gutter, designed
to capture water.
• Models EDJ-430 and EDK-430 have optional 30 degree blades designed to maximize free area.
• Model ESID-430 is an air intake/discharge louver, which helps prevent the short cycling of air.

Drainable Head Drainable Head

J Blades J Blades

Sloped Sill Sloped Sill

EDJ-430
EDJ-401

Drainable Head Drainable Head

Exhaust Blades

K Blades
Separator Plate

Intake Blades

Sloped Sill Sloped Sill

ESID-430 EDK-402

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
EDJ-202 2 J 0.063 0.063 6.01 38 869 0.105 5223 5947
EDJ-401 4 J 0.081 0.081 8.32 52 963 0.151 8012 8325
EDJ-430 4 J 0.081 0.081 8.35 45 941 0.105 7857 7849
EDJ-601 6 J 0.081 0.081 8.69 54 998 0.166 8673 8563
EDK-402 4 K 0.081 0.081 8.49 53 934 0.145 7930 8219
EDK-430 4 K 0.081 0.081 8.80 55 1002 0.142 8818 9309
EDK-602 6 K 0.081 0.081 8.35 52 1097 0.198 9160 8426
ESID-430
4 K 0.081 0.081 7.66 48 - 0.062 4979 -
(Intake)
ESID-430
4 DC 0.081 0.081 10.88 68 - - - 13056
(Discharge)
* Test size: 48 x 48 in. unit @ 15 min. duration J = J Style K = K Style DC = Discharge

5
Adjustable
Non-Drainable
• Traditional stationary J or K blade styles.
• K blade has as additional offset or “rain hook” for extra protection against water penetration.
• Design incorporates hidden mullions for continuous blade appearance when multiwidth sections are needed.

Non-Drainable Head Non-Drainable Head

J Blades K Blades

Sloped Sill Sloped Sill

ESJ-401 ESK-402

Greenheck Offers Non-Drainable Blade Options

J Blade K Blade

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
ESJ-202 2 J 0.063 0.063 6.01 38 668 0.062 4015 5853
ESJ-401 4 J 0.081 0.081 8.44 53 691 0.085 5832 7962
ESJ-602 6 J 0.081 0.081 8.73 55 739 0.088 6452 8401
ESK-402 4 K 0.081 0.081 8.45 53 689 0.075 5822 8216
ESK-602 6 K 0.081 0.081 8.46 56 772 0.097 6531 8322
* Test size: 48 x 48 in. unit @ 15 min. duration J = J Style K = K Style

6
Recessed
Combination
Mullion
• Recessed mullion designs offer better blade alignment for a true continuous blade appearance.
• Provides more structural integrity between multiwide sections.
• Easier installation with minimal field adjustments.
• Models are easier to seal in the field and thermal expansion is accounted for within the design.

Non-Drainable Head Non-Drainable Head

J Blades K Blades

Recessed Mullion Recessed Mullion

Sloped Sill Sloped Sill

ESJ-401RM ESK-402RM

Greenheck Offers Multiple Mullion Options

Typical Visible Mullion Typical Recessed Mullion Typical Hidden Mullion


for Drainable Blade for RM Series and EHM for Non-Drainable
multiwidth sections (p. 4) multiwidth sections (p. 4) multiwidth sections (p. 6)

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
ESJ-401RM 4 J 0.081 0.081 8.58 54 658 0.074 5646 8350
ESJ-602RM 6 J 0.081 0.081 8.38 52 785 0.102 6578 8267
ESK-402RM 4 K 0.081 0.081 8.42 53 677 0.071 5700 8409
ESK-602RM 4 K 0.081 0.081 8.13 51 800 0.099 6504 8206
* Test size: 48 x 48 in. unit @ 15 min. duration J = J Style K = K Style

7
Adjustable Blades
• Design incorporates operable blades that can be opened or closed to protect air intake and exhaust openings in
exterior building walls.
• Louver blades are center pivoted and can be operated manually or by electric or pneumatic actuators.
• EAD and EAH Series offer concealed blade linkage.
• EADC Series offer both concealed blade linkage and a concealed electric actuator.
• Model EAH-690 provides 70% free area when blades are in full 90 degree open position.

Drainable Drainable Drainable


Head Head Head
Drainable
Drainable 35˚ Drainable
Adjustable
Adjustable Adjustable
Blades
Blades Blades
Concealed
Concealed Blade
Concealed
Blade Linkage
Blade
Linkage Linkage Concealed
Actuator
Location
Flat Sill Flat Sill Flat Sill

EAD-401 EAD-635 EADC-401

Drainable Head Drainable Head

Adjustable Blades
Adjustable Blades

Concealed
Blade Linkage
Concealed
Blade Linkage

Flat Sill Flat Sill

EAH-401 EAH-690

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
EAD-401 4 DA 0.081 0.125 6.54 41 920 0.179 6017 7074
EAD-601 6 DA 0.081 0.125 7.34 46 1007 0.140 7391 7962
EAD-635 6 DA 0.081 0.125 8.73 55 1107 0.150 9664
EADC-401 4 DA 0.081 0.125 5.84 37 920 0.179 5373 6314
EADC-601 6 DA 0.081 0.125 6.44 40 1007 0.140 6485 6986
EAH-401 4 J 0.081 0.125 6.48 41 1023 0.128 6629 5397
EAH-690
6 J 0.081 0.125 6.32 40 1069 0.165 6756 5056
(45º Blade)
EAH-690
6 J 0.081 0.125 10.87 70 - - - 10055
(90º Blade)
* Test size: 48 x 48 in. unit @ 15 min. duration J = J Blade DA = Drainable Adjustable

8
Acoustical
Combination Louver/Damper
• Maintains a stationary appearance when adjustable blades are closed.
Drainable Head
• ECD Series offer exposed on-blade linkage.
• EAC Series and Model EACN-601 offer concealed linkage and center Center Pivot
pivot operable blades. Adjustable Blade

• Model EACA-601 incorporates airfoil blades. Concealed Blade


• EACC Series offer both concealed blade linkage and concealed Linkage
Drainable
electric actuator. Stationary Blades
• GCE and GCI Series require an exhaust or intake fan for proper
operation.
Flat Sill
EAC-401

Drainable Head
Drainable Head Drainable Head
Center Pivot
Center Pivot Adjustable Blade
Adjustable
Center Pivot Airfoil Blade
Adjustable Blade Concealed Blade
Concealed Blade Linkage
Stationary Blades
Linkage
Drainable
Drainable
Stationary Blades
Concealed Blade Stationary Blades
Linkage
Flat Sill
Sloped Sill
Concealed
Flat Sill Actuator Location

EACN-601 EACA-601 EACC-401

Drainable Head
Drainable Head Drainable Head
Exposed
On-Blade Linkage
Adjustable Intake Adjustable Exhaust
Gravity Blades Gravity Blades

Stationary Blades Stationary Blades

Sloped Sill Sloped Sill


Flat Sill
ECD-401 GCI-402 GCE-402

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
EAC-401 4 DA 0.081 0.125 6.34 40 1192 0.170 7557 6062
EAC-601 6 DA 0.081 0.125 7.41 46 1020 0.130 7558 7146
EACA-601 6 DAF 0.081 0.125 7.68 48 1221 0.170 9377 9586
EACC-401 4 DA 0.081 0.125 5.59 35 1192 0.170 6663 5341
EACC-601 6 DA 0.081 0.125 6.20 39 1020 0.130 6324 5977
EACN-601 6 J 0.081 0.125 7.18 45 1193 0.201 8566 7593
ECD-401 4 DA 0.081 0.081 7.60 46 1018 0.176 7737 7769
ECD-601 6 DA 0.081 0.081 7.32 48 1035 0.150 7866 7700
GCE-202 2 JG 0.063 0.063 4.96 31 - - - -
GCE-402 4 JG 0.081 0.081 6.36 40 - - - -
GCI-202 2 JG 0.063 0.063 5.26 33 - - - -
GCI-402 4 JG 0.081 0.081 6.39 40 - - - -
* Test size: 48 x 48 in. unit @ 15 min. duration DA = Drainable Adjustable DAF = Drainable Airfoil JG = J Blade Gravity J = J Blade

9
Page Header
Sightproof
• Louvers are designed to prevent visual see-through, can be applied as air intake or discharge louvers, or can be
applied as louvered equipment screens.
• SES Series most economical of all sightproof models.
• SEH Series incorporates a drainable head member for increased protection against water penetration.
• SED Series offer both a drainable head member and drainable blades for maximum protection against water
penetration.
• Model SED-501 offers 57% free area.
• SEV Series offer a vertical sightproof blade design.

Drainable Drainable
Sightproof Head Sightproof Head

Drainable Drainable
Sightproof Blades Sightproof Blades

Flat Sill Flat Sill


SED-401 SED-501

Flat Head
Sightproof Head Drainable
Sightproof Head

Sightproof Blades Vertical Blades


Sightproof Blades

Flat Sill Flat Sill Flat Sill


SES-401 SEV-401 SEH-401

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
SED-202 2 CD 0.063 0.063 3.42 21 903 0.243 3088 2168
SED-401 4 CD 0.081 0.081 5.16 32 747 0.280 3855 2589
SED-501 5 CD 0.081 0.081 9.11 57 1134 0.448 10331 7364
SEH-202 2 C 0.063 0.063 3.73 23 600 0.137 2238 2140
SEH-401 4 C 0.081 0.081 5.16 32 765 0.276 3947 2664
SES-202 2 C 0.063 0.063 3.75 24 516 0.105 1935 2118
SES-401 4 C 0.081 0.081 5.33 33 718 0.224 3827 2695
SEV-401 4 V 0.081 0.081 5.33 33 - - - -
SEV-501 5 V 0.081 0.081 9.11 57 - - - -
* Test size: 48 x 48 in. unit @ 15 min. duration C = Chevron CD = Chevron Drainable V = Vertical

10
Page HeaderRain
Wind-Driven
• The most effective line of products for minimizing water penetration through openings that are sensitive to rain
penetration.
• All models incorporate a drainable head member and either vertical (EVH Series) or horizontal (EHH Series) rain-
resistant blades to provide maximum resistance to wind-driven rain, as tested by the stringent AMCA 500L test
procedure.

Drainable Head
Drainable Head

Vertical Rain-
Horizontal Rain- Resistant Blades
Resistant Blades

**Formed Aluminum Sill Pan **Formed Aluminum Sill Pan


EHH-401
EHH
EHH 401 EVH
EVH-401
H 401
1

**
Shipped loose formed aluminum sill pan required for models EHH-201, EHH-401, EHH-501, EHH-601, EVH-201, EVH-401.

Wind Velocity - 29 mph Wind Velocity - 50 mph


Wind-Driven Rain Test Results Rainfall - 3 in./hr.³ Rainfall - 8 in./hr.³

Free Area Core Area Water Water Water Water


Airflow
Velocity Velocity Penetration Penetration Penetration Penetration
(cfm)
(fpm) (fpm)1 Effectiveness Classification Effectiveness Classification
1372 298 127 99.6% A - -
EHH-201
0 0 0 - - 99.1% A
9306 1807 864 99.9% A - -
EHH-401
4142 804 400 - - 99.0% A
8353 1564 776 99.1% A - -
EHH-501
7353 1377 683 - - 99.2% A
7276 1257 676 99.8% A - -
EHH-601 Wind-Driven Rain
8211 1418 763 - - 99.2% A
8430 1522 783 100% A - - Penetration Classes
EHH-701
7222 1304 671 - - 99.5% A Class Effectiveness
9301 2178 864 99.8% A - -
EVH-201 A 1 to 0.99
9278 2173 862 - - 99.6% A
7248 1604 673 100% A - - B 0.989 to 0.95
EVH-401
6135 1357 570 - - 99.7% B C 0.949 to 0.80
10564 2224 981 99.9% A - -
EVH-602 D Below 0.8
10427 2195 968 - - 100% A
8337 1654 774 99.0% A - -
EVH-801
9299 1845 864 - - 99.2% A
1
Core area is the open area of the louver face (face area less louver frames). Core area velocity is the airflow velocity through the core
area of the louver.

Beginning Pressure Drop


Blade Frame Max. Intake Exhaust Volume
Blade Free Area Free Area Point of Water at Max. Intake
Model Depth Thickness Thickness Volume Flow Flow Rate @ 0.15
Style (sq. ft.) (%) Penetration Velocity
(in.) (in.) Rate (cfm) in. wg (cfm)
(ft./min.) (in. wg)
EHH-201 2 RR 0.063 0.063 6.20 39 914 0.198 5667 5487
EHH-401 4 RR 0.081 0.081 6.72 42 1250 0.295 8400 5782
EHH-501 5 RR 0.081 0.081 6.80 43 1210 0.224 8500 5998
EHH-601 6 RR 0.081 0.081 7.58 47 1250 0.323 9475 6091
EHH-701 7 RR 0.081 0.081 6.99 43 1250 0.423 8962 4522
EVH-201 2 RR 0.063 0.063 5.71 36 1250 0.368 7138 5185
EVH-401 4 RR 0.081 0.081 6.38 40 1250 0.369 7975 5897
EVH-602 6 RR 0.081 0.081 5.88 39 1250 0.161 7350 8146
EVH-801 8 RR 0.081 0.081 5.05 32 1250 0.100 6313 8627
* Test size: 48 x 48 in. unit @ 15 min. duration RR = Rain-Resistant

11
Page Header
Florida Product Approved
• All mechanically fastened Florida Product Approved models comply with TAS-202 and Uniform Static Pressure
Test (ASTM E330).
• Models also comply with TAS-201 Large Missile Impact Test (ASTM E1996) and TAS-203 Cyclic Wind Pressure
Load Test with optional welded construction.
• Approved for use in Florida’s High-Velocity Hurricane Zone if Miami-Dade Notice of Acceptance is not required.

Drainable Head Drainable Head

Drainable Blades
Drainable Blades

Sloped Sill
Sloped Sill

ESD-435X ESD-635X
Florida Product Approved No.: Florida Product Approved No.:
FL6876.3 FL6876.4
Drainable Head

Rain-Resistant Blades

+
Formed aluminum sill pan

EHH-501X
Florida Product Approved No.:
Drainable Head
FL6876.2
Formed
Acoustical Head

Formed Acoustical J Blades


Vertical Rain with Fiberglass Insulation
Resistant Blades Perforated Aluminum
Insulation Screen

Formed
Acoustical Sill
Formed Sill Pan

Flat Sill
EVH-602X AFJ-601X
Florida Product Approved No.: Florida Product Approved No.:
FL7494.1 FL6876.1
+
Shipped loose formed aluminum sill pan required for model EHH-501X.
Beginning Pressure Drop Exhaust
Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
AFJ-601X 6 J 0.080 0.080 4.89 31 799 0.065 3907 6015
EHH-501X 5 RR 0.081 0.081 6.80 43 1250 0.224 8500 5998
ESD-435X 4 D 0.081 0.081 8.98 56 1151 0.213 10336 9281
ESD-635X 6 D 0.081 0.081 9.41 59 1077 0.173 10135 9932
EVH-602X 6 RR 0.081 0.081 5.88 37 1250 0.174 7350 7873
* Test size: 48 x 48 in. unit @ 15 min. duration RR = Rain-Resistant J = J Style D = Drainable

12
Page Header
Florida Product Approved

Miami-Dade Florida Minimum Opening Maximum Section Maximum Opening


Model Name AMCA AMCA
County, FL Product Protocols
Max. Wind-load Certifications Listed Dimensions – inches (mm)
NOA No. Approved No.

Miami-Dade County Qualified Louvers and Penthouses


144 W x 144 H,
ESS-502D AMCA 540 09-0519.14 8Wx7H Limited to 72 ft 2
Unlimited W x 144 H
FL12941.1
110 PSF Enhanced Level E EXP. 8/5/14 (203 W x 178 H) (3658 W x 3658 H, (Unlimited W x 3658 H)
2
Limited to 6.7m )

ESD-635D* Water, Air 12 W x 12 H 72.563 W x 144.813 H Unlimited W x 144.813 H


AMCA 540 FL10088.3
150 PSF (305 x 305) (1843 W x 3678 H) (Unlimited W x 3678 H)
Basic Level D, TAS 201,
AMCA 540 12-0830.07 TAS 202,
Enhanced Level E EXP. 12/6/17 TAS 203
ESD-635D/VCD-40 (with 0.125 blade/
12 W x 15.25 H 36.563 W x 144.813 H Unlimited W x 144.813 H
frame) FL10088.4
150 PSF (305 W x 387 H) (928 W x 3678 H) (Unlimited W x 3678 H)

EHH-601D* AMCA 540 12 W x 7 H 72.563 W x 144.813 H Unlimited W x 144.813 H


FL10088.1
150 PSF Enhanced Level E (305 W x 178 H) (1843 W x 3678 H) (Unlimited W x 3678 H)
12-0830.08
EXP. 11/1/17 TAS 201,
EHH-601D/VCD-40 TAS 202, 12 W x 13.25 H 36.563 W x 144.813 H Unlimited W x 144.813 H
FL10088.2
150 PSF TAS 203, (305 W x 337 H) (928 W x 3678 H) (Unlimited W x 3678 H)
TAS 100A

Water, Air and TAS 201,


EVH-602D
Wind Driven FL8042.1 TAS 202,
150 PSF
Rain TAS 203
AMCA 550,
11-1103.01 12 W x 16 H 48.25 W x 96.25 H Unlimited W x 96.25 H
AMCA 540
EXP. 12/7/16 (305 W x 406 H) (1226 W x 2445 H) (Unlimited W x 2445 H)
Enhanced Level E
EVH-602D/VCD-40
FL8042.2
150 PSF
TAS 201,
TAS 202,
TAS 203,
TAS 100A
EVH-660D 12-0418.06 FL8042, 6 W x 12 H 48 W x 144 H Unlimited W x 144 H
150 PSF EXP. 10/4/17 16086.1 (153 W x 305 H) (1219 W x 3658 H) (Unlimited W x 3658 H)

Minimum Maximum Maximum


EHH-601PD 13-0510.06 Throat W x L x Max. H Throat W x L x Max. H Throat W x L x Max. H
FL11350.1
115 PSF EXP. 6/19/18 12 x 12 x 12 84 x 108 x 84 84 x 108 x 84
TAS 201, (305 x 305 x 305) (2134 x 2743 x 2134) (2134 x 2743 x 2134)
Not Not
TAS 202,
Applicable Applicable
TAS 203 Minimum Maximum Maximum
ESD-635PD 13-0510.05 Throat W x L x Max. H Throat W x L x Max. H Throat W x L x Max. H
FL11350.2
115 PSF EXP. 6/19/18 12 x 12 x 12 84 x 108 x 84 84 x 108 x 84
(305 x 305 x 305) (2134 x 2743 x 2134) (2134 x 2743 x 2134)

Florida Product Approved Louvers


AFJ-601X Water, Air and AMCA 540 FL6876.1, 12 W x 15 H 60 W x 96 H Unlimited W x 96 H
Max. 200 PSF^ Sound Enhanced Level E 15718.1 (305 W x 381 H) (1524 W x 2438 H) (Unlimited W x 2438 H)

ESD-435X* AMCA 540 FL6876.3, 12 W x 9 H


Max. 200 PSF^ Basic Level D 15718.3 (305 W x 229 H)
Standard:
Water, Air AMCA 540 TAS 202
120 W x 144 H Unlimited W x 144 H
Basic Level D,
ESD-635X* FL6876.4, 12 W x 12 H Limited to 70 ft 2
or 120 W x Unlimited H
AMCA 540 Not
Max. 200 PSF^ Enhanced Level E 15718.4 (305 W x 305 H)
Applicable Welded: (3048 W x 3658 H (Unlimited W x 3658 H
(with 0.125 blade/
frame) TAS 201, Limited to 6.5m ) 2
or 3048 W x Unlimited H)
TAS 202,
TAS 203
EHH-501X* AMCA 540 FL6876.2, 12 W x 7 H
Max. 200 PSF^ Enhanced Level E 15718.2 (305 W x 178 H)
Water, Air and
Wind Driven
Rain AMCA 550,
EVH-602X FL7494.1, 12 W x 16 H 60 W x 96 H Unlimited W x 96 H
AMCA 540
Max. 200 PSF^ 15719.1 (305 W x 406 H) (1524 W x 2438 H) (Unlimited W x 2438 H)
Enhanced Level E

FEMA 361 Tornado Grille


57 ft 2
Unlimited W x Unlimited H
FSG-801 Not Applicable 12 W x 12 H
ICC 500 (configuration (Limited to 1 section
Max. 248 PSF (UL Listed) (305 W x 305 H)
dependent) W or H)

*Also available in architectural shapes. ^Size/section dependent.

13
Page HeaderQualified
Miami-Dade
• Use within Florida’s High-Velocity Hurricane Zone when a Miami-Dade Notice of Acceptance is required.
• All models comply with Miami-Dade structural test protocols TAS-201, Large Missile Impact Test (ASTM E1996);
TAS-202, Uniform Static Pressure Test (ASTM E330) and TAS-203, Cyclic Wind Pressure Test.
• Models ESD-603D with HCD-240, EHH-601D with VCD-40 and EVH-602D with VCD-40 also comply with
Miami-Dade’s test protocol TAS 100A, Wind-Driven Rain Resistance Test.

Drainable Head
Drainable Head
Retaining Angle
Retaining Angle

Horizontal Rain-Resistant Blades


Horizontal Rain-Resistant Blades
Factory Installed
Control Damper

Manual Quadrant Actuator


(Electric also available)

Flat Sill Flat Sill


TAS 100A
EHH-601D EHH-601D with VCD-40
Florida Product Approved No.: FL10088.1 Florida Product Approved No.: FL10088.2
NOA NO.: 08-0229.06 NOA NO.: 07-0925.02

Drainable Head Drainable Head


Retaining Angle
Retaining Angle

Factory Installed
Control Damper
Drainable Blades

Drainable Blades

Manual Quadrant
Actuator (Electric also
Sloped Sill available)
Sloped Sill

ESD-635D
ESD-635D with VCD-40
Florida Product Approved No.: FL10088.3
Florida Product Approved No.: FL10088.4
NOA NO.: 07-1015.06
NOA NO.: 07-1015.06

Anchor Plates (typical at head and sill)


Drainable Head
Drainable Head

Vertical Rain-Resistant
Sightproof Blades
Blades

Flat Sill Sloped Sill

ESS-502D
EVH-602D
Florida Product Approved No.: FL12941.1
Florida Product Approved No.: FL8042.1
NOA NO.: 09-0519.15
NOA NO.: 06-0711.1

14
Page HeaderQualified
Miami-Dade

Anchor Plates (typical at head and sill)


Drainable Head
Factory Installed
Control Damper
Vertical Rain-Resistant
Blades
Vertical Rain-Resistant Blades
Manual Quadrant
Actuator

Exterior Sill Baffle

TAS 100A Sloped Sill Flat Sill


TAS 100A
EVH-602D with VCD-40 EVH-660D
Florida Product Approved No.: FL10088.4 Florida Product Approved No.: FL
NOA NO.: 07-1015.06 NOA NO.:

Drainable Head

Center Pivot Adjustable


Airfoil Blade

Concealed Linkage

Drainable Stationary Blade

Sloped Sill

EACA-601D
Florida Product Approved No.: PENDING
NOA NO.: PENDING

Hinged Hood(s) Member Hinged Hood(s) Member

Drainable Horizontal Rain-


Blades Resistant Blades

Optional factory provided roof curb available. Optional factory provided roof curb available.
ESD-635PD EHH-601PD
Florida Product Approved No.: FL11350.2 Florida Product Approved No.: FL11350.1
NOA NO.: 08-0505.05 NOA NO.: 08-0505.06

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
EACA-601D 6 DAF 0.081 0.125 7.68 48 1221 0.170 9377 9586
EHH-601D 6 RR 0.081 0.081 7.58 47 1250 0.323 9475 5794
ESD-635D 6 D 0.081 0.125 9.41 59 1077 0.173 10135 9932
ESS-502D 5 C 0.081 0.081 8.19 51 1036 0.218 8485 6286
EVH-602D 6 RR 0.081 0.081 5.88 37 1250 0.174 7350 7873
EVH-602D/
6 RR 0.081 0.081 5.88 37 1250 0.174 7350 7873
VCD-40
EVH-660D 6 RR 0.063 0.095 7.29 45 1250 0.285 9113 7160
* Test size: 48 x 48 in. unit @ 15 min. duration RR = Rain-Resistant C = Chevron D = Drainable DAF = Drainable Airfoil
15
Thinline
• Narrow profile products designed for interior and exterior applications.
• Framed units ideal for installation in curtain wall, window wall systems, and door applications.
• Models ESU-130S and ESU-150S are frameless and offer a total product depth of only 1.375 inches.
• Models ESU-130 and ESU-150 offer high free area and are low airflow resistance.

Support Strut Frame

Blades
Blades

ESU-130S ESF-145

Frame
Frame

Blades
Blades

ESU-150
ESJ-150

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
ESF-145 1.5 TL 0.063 0.063 6.08 38 - 0.055 3040 4925
ESJ-150 1.5 J 0.063 0.063 7.29 46 - 0.038 3645 7144
ESU-130 1.5 TL 0.063 0.063 10.9 69 - 0.055 5475 14235
ESU-130S 1.375 TL 0.063 0.063 11.41 71 - 0.030 5705 14833
ESU-150 1.5 TL 0.063 0.063 7.4 46 - 0.035 3700 9990
ESU-150S 1.375 TL 0.063 0.063 7.7 48 - 0.035 3850 10395
* Test size: 48 x 48 in. unit @ 15 min. duration TL = Thinline J = J Style

16
Acoustical
• Acoustically insulated blades provide sound absorption from escaping noise.
• Available in formed aluminum or steel material.
• AFJ Series is the most economical of all acoustical models.
• Model AFA-801 offers the highest free area, has the lowest airflow resistance, and is designed with acoustical
blades.
• Model AFS-120 offers the best sound absorption performance and incorporates sightproof blades.

Formed Head

Formed Acoustical Airfoil Blades


with Fiberglass Insulation

Formed
Perforated Aluminum Acoustical Head
Insulation Screen
Formed Acoustical Sightproof Blades
with Fiberglass Insulation
Formed Sill
Perforated Aluminum
AFA-801 Insulation Screen

Formed
Acoustical Sill

AFS-120

Formed
Acoustical Head

Formed Acoustical J Blades


Free Field Selected 1/3 Octave Bands Center
with Fiberglass Insulation
Noise Frequency Hz
Perforated Aluminum Reduction
Insulation Screen 125 250 500 1000 2000 4000 STC
in Decibels
AFA-801 10 8 10 14 20 15 8
Formed
Acoustical Sill
AFJ-601 10 10 12 16 23 18 10

AFJ-801 11 11 13 19 28 20 12
AFJ-801 AFJ-120 13 12 17 25 36 25 16

AFS-120 11 11 16 25 36 31 16

Sound Transmission Class (STC)


The Sound Transmission Class (STC) is a rating of the
effectiveness of an assembly in isolating or reducing airborne
sound transmission. STC is a single number that summarizes
airborne sound transmission loss data. Assemblies with higher
STC ratings are more efficient at reducing sound transmission.
STC is determined in accordance with ASTM E413-04.

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(in.) (in.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
AFA-801 8 AF 0.080 0.080 5.21 33 879 0.050 4580 7508
AFJ-120 12 J 0.080 0.080 3.67 23 961 0.093 3527 4543
AFJ-601 6 J 0.080 0.080 4.89 31 799 0.065 3907 6015
AFJ-801 8 J 0.080 0.080 4.28 27 887 0.079 3796 5192
AFS-120 12 C 0.080 0.080 4.27 27 830 0.118 3544 3839
* Test size: 48 x 48 in. unit @ 15 min. duration AF = Airfoil C = Chevron J = J Style SP = Sightproof

17
Fabricated
• Fabricated from galvanized steel and are low cost compared to extruded aluminum models.
• All fabricated models are available in stainless steel material.
• FSJ and FDS Series have stationary blades only.
• FAD and FAJ Series are adjustable blade models.

Formed Head Member


Formed Head Member Formed
Formed Stationary Blades
Stationary Blades

Formed Adjustable
Formed Adjustable J Blades
Drainable Blades

Formed Flat Sill Formed Flat Sill


FAD-402 FAJ-402

Formed Head Member Formed Head Member

Formed Drainable Formed Stationary


Stationary Blades J Blades

Formed Flat Sill Formed Flat Sill

FDS-402 FSJ-402

Beginning Pressure Drop Exhaust


Blade Frame Max. Intake
Blade Free Area Free Area Point of Water at Max. Intake Volume Flow
Model Depth Thickness Thickness Volume Flow
Style (sq. ft.) (%) Penetration Velocity Rate @ 0.15
(Ga.) (Ga.) Rate (cfm)
(ft./min.) (in. wg) in. wg (cfm)
FAD-402 4 DA 16 16 5.98 38 1086 0.130 6494 7478
FAD-602 6 DA 16 16 7.11 45 980 0.129 6968 7768
FAD-635 6 DA 16 16 8.77 55 959 0.099 8410 11093
FAJ-402 4 A 16 16 5.93 37 691 0.062 4096 6278
FAJ-602 6 J 16 16 6.23 39 717 0.064 4467 6551
FDS-402 4 D 20 16 7.03 44 1056 0.161 8788 8444
FDS-602 6 D 20 16 8.15 51 948 0.137 7726 8661
FSJ-402 4 J 20 16 7.55 47 839 0.110 6335 6894
FSJ-602 6 J 20 16 7.57 47 896 0.125 6783 7398
* Test size: 48 x 48 in. unit @ 15 min. duration J = J Style D = Drainable A = Adjustable

18
Special Application

FEMA 361 Griille


FEMA 361 grilles are used to protect air intake or exhaust openings from
flying debris, caused by tornadoes spawned by hurricanes or severe
thunderstorms, and must be applied over any wall penetration on a FEMA
361 storm shelter. Model FSG-801 is a FEMA 361 compliant, UL Classified
(R29119) grille, and fabricated of 0.25 inch thick hot-rolled steel materials.
Model FSG-801 withstands the ICC 500 2 x 4 impact standard adopted by
FEMA 361 and withstands wind-loads up to 248 PSF.

Model FSG-801 may be installed in a cantilever or recessed/flush mount


configuration. Mounted flanges may be located on the sides, top, and
bottom. Nearly any Greenheck louver may be factory installed within the
optional deep sleeve when using the flush/recessed mounting configuration,
including many of our Miami-Dade Qualified and all of Florida Product FSG-801
Appr
Ap p ov
o ed lou
ouveerss.

Sand
d Louver
Greenheck’s sand louver is designed to protect air intake and exhaust openings
in building exterior walls from wind-driven sand. Design incorporates vertical
sightproof blades to separate sand from the airstream, which is then channeled
out at the sloped sill.

Model FSL-401 was tested per ASHRAE Standard Method 52.1-1992


(previously ASHRAE standard 52-76), an independent third-party test lab using
crushed quartz of (150-300 μm) dust medium. Standard construction material is
galvanized steel and optional formed aluminum is available. Frame depth: 4 in.

FSL-401

Penthouses & Equipment Screens


Model PEV-400 is a gravity ventilator comprised of three sides of standard stationary non-drainable louver model
ESJ-401, along with one side of 0.125-in. thick plate glass that can be broken with the pressure of a fire hose.
A fire smoke damper is located in the throat of the curb and wired into the fire control panel. The unit is shop-
assembled and shipped complete.
Greenheck penthouse models WIH and WRH offer clean horizontal lines, mitered corners, all aluminum
construction, removable hoods, and weather-resistant blades. Custom louvered penthouses are also available to
meet your specifications. For more information contact your local rep or visit greenheck.com
For screen applications, model EES-401 is an inverted horizontal equipment screen offering extruded aluminum
“J
J” styl
y e blades. As alwayys,, custom config
gurations are available.

PEV-400 WIH/WRH EES-401

19
Accessories and Options
We have a full line of accessories, so whether your project necessitates security bars or filter
racks, we have what you need. An extensive line of standard finishes, including Kynar® paint,
baked enamel paint, industrial coatings or anodize finishes are also available. In addition to our
complete line of standard colors, our custom color matching capabilities are endless. These
accessories and options allow Greenheck to complete your project just as you envision it.
Glazing
Adapters
Flanged Frame
Bird Screen or
Insect Screen
Filters &
Structural Filter Racks
Reinforcing

Sill Anchor Blank Off


Extensions Clips Panels
Security
Bars

Greenheck Fan Corporation Greenheck Fan Corporation certifies that Greenheck Fan Corporation Greenheck Fan
certifies that Models EVH- Models ESD-635D, 603D; ESS-502D; certifies that Models EAH- Corporation certifies
201, 401, 602, 801; EHH- ESD-435X, 635X; ESJ-202, 401, 602; 690 with blade angle at 90º that Models AFJ-120,
201, 401, 501, 601, 701; ESK-402, 602; ESJ-401RM, 602RM; and FSL-401 are licensed 601, 801; AFA-801;
EVH-602D; EHH-601D; EHH- ESK-402RM, 602RM; EDJ-202, 401, to bear the AMCA Seal. The AFS-120; and AFJ-
501X; and EVH-602X are 601, 430; EDK-402, 430, 602; ESD- ratings shown are based 601X are licensed to
licensed to bear the AMCA 202, 403, 435, 603, 635; EDD-401, on tests and procedures bear the AMCA Seal.
Seal. The ratings shown are 601; EHM-601; SES-202, 401; SEH- performed in accordance The ratings shown are
based on tests and proce- 202, 401; SED-202, 401, 501; ECD- with AMCA Publication 511 based on tests and
dures performed in accordance with AMCA Publication 401, 601; EAC-401, 601; EACA-601; EACN-601; EAD-401, and comply with the requirements of the AMCA procedures performed in accordance with
511 and comply with the requirements of the AMCA 601; EAH-401; FSJ-402, 602; FDS-402, 602; FAJ-402, 602; Certified Ratings Program. The AMCA Certified AMCA Publication 511 and comply with the
Certified Ratings Program. The AMCA Certified Ratings and FAD-402, 602, 635 are licensed to bear the AMCA Seal. Ratings Seal applies to air performance. requirements of the AMCA Certified Ratings
Seal applies to water penetration, air performance and The ratings shown are based on tests and procedures per- Program. The AMCA Certified Ratings Seal
wind-driven rain. formed in accordance with AMCA Publication 511 and comply applies to water penetration, air performance
with the requirements of the AMCA Certified Ratings Program. and sound ratings.
The AMCA Certified Ratings Seal applies to water penetration
and air performance.

The Greenheck Fan Corporation certifies that Louver Type ESD-435X, ESD-635X,
ESD-635D, AFJ-601X, EHH-501X, EVH-602X, ESS-502D, EHH-601D, EVH-602D and
EVH-660D shown herein are approved to bear the AMCA Listing Label. The ratings
shown are based on tests and procedures performed in accordance with AMCA
Publications and comply with the requirements of the AMCA Listing Label Program

Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties. Prepared to Support
Green Building Efforts

00.LVR.1000 R4 1-2014 IP
P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com Copyright © 2014 Greenheck Fan Corporation

You might also like